2016 Fire Code Flammable and Combustible Liquids PRESENTED BY Reinhard Hanselka, PhD, PE , CRB Presentation images provided by International Code Council (ICC)
Jan 28, 2016
2016 Fire CodeFlammable and Combustible
Liquids
PRESENTED BY
Reinhard Hanselka,
PhD, PE , CRB
Presentation images provided by
International Code Council (ICC)
Description
� This course provides a basic understanding of the flammable and combustible liquid storage, use, dispensing, handling and mixing requirements in IFC Chapter 57 and NFPA 30, Flammable and Combustible Liquids Code.
• General fire code requirements for hazardous materials and specialized requirements for Laboratories, Bio-Pharm, vehicle fuel-dispensing activities (IFC Chapter 23), dry cleaning (IFC Chapter 12) and other specialized uses of flammable and combustible liquids are not covered in detail due to the time limitations of a single-day course.
Course Outline
�Definitions and classification of flammable & combustible liquids
�Above-ground vessel storage
�Underground tank storage
�Containers and portable tank storage
Course Outline (cont.)
�Use, dispensing, mixing and handling
�Biotech and Laboratory use
�Special processes involving flammable & combustible liquids
�Special requirements• Spill control and secondary containment• Classified electrical locations• Ventilation
Improper Ventilation
Flammable and Combustible Liquids
How do you keep
this…from becoming this ?
� Flammable and
combustible liquids
are those liquids
that are capable of
supporting
combustion
� Flammable &
combustible liquids
may be easily
ignitable and have
high heat release
rates.
� Liquids can present
two- or three-
dimension fires (pool
or dripping/running
spill) that spread
rapidly
� If vapor is suspended
in air in a confined
space, a deflagration
can occur.
� Vapor can migrate
to ignition sources
remote from a
spill.
� A Real Problem
with HPLC’s
Focus on Flammable & Combustible Liquids
Classification of Flammable & Combustible
Liquids
�The CFC classifies liquids that burn as either FLAMMABLE or COMBUSTIBLE .
�To classify a flammable liquid, theflash point and boiling point must be determined.• Flash points and boiling points are determined by
experimentation.
�Combustible liquids are also classified by flash point tests but do not require determination of the material’s boiling point.
Understanding the Flash Point System
� Section 5702.1 defines FLASH
POINT as: “The minimum
temperature in degrees
Fahrenheit at which a liquid
will give off sufficient vapors
to form an ignitable mixture
with air near the surface or in
the container, but will not
sustain combustion. The flash
point of a liquid shall be
determined by appropriate test
procedure and apparatus as
specified in ASTM D 56, ASTM
D 93 or ASTM D 3278.”
Understanding the Flash Point System
�Section 5702.1
defines FIRE POINT
as: “The lowest
temperature at
which a liquid will
ignite and achieve
sustained burning
when exposed to a
test flame in
accordance with
ASTM D 92.”
Understanding the Flash Point System
� All of the adopted flash point tests are closed cup tests.
• More conservative
• More reproducible
� Flash point testing is a LIMITED method for determining the ignitability of a particular liquid.
• Serves better as a basis of comparing liquids than as an absolute measure of fire risk
� The CFC defines:
• Liquids with a flash point less than 100°F as FLAMMABLE
• Liquids with a flash point at or above 100°F as COMBUSTIBLE
• This differs from DOT
DOT Classification of Liquids
� Flammable Liquid
• Generally applies to liquids with a flash point less than 140°F
• There are MANY exceptions
• In some cases, a liquid with a flash point exceeding 100°F may be reclassified as a combustible liquid
� Combustible Liquid
• Generally applies to liquids with a flash point 140°F to 200°F
• Liquids with flash points exceeding 200°F are not considered combustible under DOT regulations
FLAMMABLE
3
DOT Classification of Liquids
� Be careful that differences
between the IFC, CMC and
DOT classification systems
don’t lead to
miscommunication between
an owner (who often deals
with transportation
regulations) and a fire
inspector (who primarily deals
in fire codes) when speaking
about “flammable liquids.”
FLAMMABLE
3
Max. Qty.
Per
Control
Area
= 30 Gallons FLOORMax. Qty.
Per Floor
Qty. with
4 Lab
Suites
Per Floor
10 3 50% 50% 50% 50% 60
9 6 50% 50% 50% 50% 60
8 6 50% 50% 50% 50% 60
7 6 50% 50% 50% 50% 60
6 15 75% 75% 75% 75% 90
5 15 75% 75% 75% 75% 90
4 15 75% 75% 75% 75% 90
3 60 100% 100% 100% 100% 120
2 75% 75% 135 100% 100% 100% 100% 120
1 100% 100% 100% 100% 240 100% 100% 100% 100% 120
30Basement
Level - 175% 75% 135 100% 100% 100% 100% 120
Basement
Level - 260 75% 75% 75% 75% 90
120 UFC TOTAL 696 1080
30
IFC 2006
30
30
12.50%
12.50%
12.50%
12.50%
5% 5%
12.50% 12.50%
5% 5%
5% 5%
L-Occupancy
= 30 Gallons= 60 Gallons
50% 50%
50% 50%
75%
75%
5%
TOTALS
4TH FLOOR
LIMITS
FL-1B Use Open
CLASSIFICATION OF FLAMMABLE AND COMBUSTIBLE LIQUIDS
CLASSIFICATION1 FLASH POINT (ºF) VAPOR PRESSURE
(PSI ABSOLUTE)
BOILING POINT
(ºF)
Class IA Less than 73 Less than or equal to 40 Less than 100
Class IB Less than 73 Less than or equal to 40 Greater than or
equal to 100
Class IC
Greater than 73 and
less than or equal to
100
Less than or equal to 40 N/A
Class II Greater than 100 and
less than 140 N/A N/A
Class IIIA Greater than or equal to
140 and less than 200 N/A N/A
Class IIIB Greater than or equal to
200 N/A N/A
N/A = Not applicable to classification.
1 When heated, sprayed or mixed, Class II or III liquids can assume the characteristics of lower
flash point liquids. Under such conditions the appropriate provisions of Chapter 34 for the actual
flash point shall apply.
When flammable or combustible liquids present multiple hazards, all hazards must be addressed.
Ignition and Burning Comparison of
Two Class I Liquid “Types”
� Heptane is a “typical” flammable
liquid.
� Styrene resin is viscous and has a
low vapor pressure, both important
considerations in evaluating true
fire risk.
� Flash point doesn’t necessarily
indicate how easily a liquid ignites
and burns. It is simply a relative
measure of ignitibility of vapors in a
test environment
Styrene Resin
Heptane
Navigating the IFC
� The CFC is organized into 7 “parts.”
� Unlike some legacy codes, the parts
are
• Not formally identified;
• Not separated by breaks in chapter
numbering.
� The CFC has 47 chapters and 10
appendices.
Chapter 57
Flammable and Combustible Liquids
� Chapter 57 is largely derived from the legacy 1997
Uniform Fire Code, but it gives more deference to
NFPA 30, Flammable and Combustible Liquids Code.
� Most IFC regulations are similar to provisions in
NFPA 30, but there are some differences.
Chapter 57 Major Subsections
� 5701 General
� 5702 Definitions
� 5703 General requirements
� 5704 Storage• 5704.2 Above-ground and
underground tank storage
• 5704.3 Indoor portable tank and container storage
• 5704.4 Outdoor portable tank and container storage
� 5705 Dispensing, use, mixing and handling
� 5706 Special operations
Chapter 57 Flammable and
Combustible Liquids
It should be noted that
Chapter 57 differs from
the other hazardous
material chapters in
that many of the
requirements in
Sections 5704 and 5705
apply regardless of the
indoor or outdoor
Maximum Allowable
Quantities (MAQs).
Section 5701 General
Provisions in this section apply to all
storage, use and handling of
flammable and combustible liquids,
exceptF
Section 5701.2 Non-applicability
Chapter 57 requirements do not apply to the following:
� Specific provisions for liquids in vehicle fueling stations, repair garages, airports and marinas (Chapter 22).
� Medicine; foodstuffs; cosmetics; commercial, institutional and industrial products in similar packaging to the items listed here that are maximum 50 percent by volume water-miscible flammable or combustible liquid with the remainder being nonflammable in retail or wholesale storage uses.
� Alcoholic beverages not exceeding 1.3 gallon containers in retail or wholesale sales or storage uses; distilled spirits and wines in wooden barrels and casks.
Section 5701.2 Non-applicability (cont.)
Chapter 57 requirements do not apply to the following:
� Storage and use of fuel oil tanks and containers connected to oil-burning equipment.
� Refrigerant liquids and oils in refrigeration systems.
� Storage and display of aerosols.
� Liquids without fire points.
Section 5701 Material Classification
�Section 5701.1 – Flammable and combustible liquids with multiple hazards must also comply with Chapter 50.• Example: Acetic acid is a Class II combustible liquid
that is also corrosive.
• Example: Methyl Ethyl Ketone Peroxide which is a Class II or IIIA combustible liquid and a Class II or III organic peroxide
�Section 5701.5 – When combustible liquids are heated above their flash points, they are regulated as flammable liquid.
Section 5703 General Requirements
� 5703.1 Electrical
� 5703.2 Fire Protection
� 5703.4 Spill Control
and Secondary
Containment
� 5703.5 Labels and
Signs
� 5703.6 Piping, Valves
and Fittings
Section 5703.6.2 Piping Systems
� Piping systems must be designed in accordance with NFPA
30 and ASME B31.3, Process Piping.
� Piping systems may be either metallic or nonmetallic.
� Low melt point materials
� At a minimum, the system design should indicate the:
• Design temperature and ressure
• Pipe and fitting specifications
• Method of pipe assembly
• Method of pipe erection and support
• Method of testing and test medium
A Properly Designed and Installed
Piping System
And then there is thisF
Section 5704 Storage
Section 5704.2 Tank Storage
� Section 5704.2 addresses tanks over 660 gallons:
• Construction
• Installation
• Venting
– Normal vents
– Emergency vents
• Separation requirements
• Secondary containment
• Protection from corrosion
Section 5704.2 Tank Storage
� 5704.2.2 Use of
tank vehicles and
cars for storage
� 5704.2.3 Labeling
and signs
� 5704.2.4 Sources of
ignition
� 5704.2.5 Explosion
control
Section 5704.2 Tank Storage (cont.)
� 5704.2.6 Separation
from incompatible
materials
� 5704.2.7 Design
and construction• 3404.2.7.3 Normal venting –
60 gallons!!!
• 3404.2.7.4 Emergency venting
• 3404.2.7.5 Tank openings
other than vents
� 5704.2.8 Vaults
Section 5704.2 Tank Storage
� 5704.2.9 Above-
ground tanks• 5704.2.9.1 Existing
noncompliant installations
• 5704.2.9.2 Fire protection
• 5704.2.9.3 Supports
• 5704.2.9.5 Above-ground
storage tanks in buildings
• 5704.2.9.6 Location of
tanks outdoors
• 5704.2.9.7 Protected tanks
Section 5704.2 Tank Storage (cont.)
� 5704.2.10 Drainage and
diking
� 5704.2.11 Underground
tanks
� 5704.2.12 Testing
� 5704.2.13
Abandonment of tanks
Section 5704.2.7
Design and Construction of Tanks
�The IFC permits the use of the following types of storage tanks:• Shop-fabricated tanks which can
be listed for underground orabove-ground installation
• Field erected above-ground tanks
• Protected above-ground tanks
• Vaulted tanks
• Special enclosures( See Chapter 22—motor fueling)
Section 5704.2.7
Design and Construction of Tanks
� Design, fabrication and construction must be in
accordance with NFPA 30’s recognized standards.– UL 58 – Steel Underground Tanks for Flammable & Combustible Liquids– UL 142 – Steel Aboveground Tanks for Flammable & Combustible Liquids
– API 620 – Welded, Low-pressure Storage Tanks
– API 650 – Welded Steel Tanks for Oil Storage
– API 2000 – Venting Atmospheric & Low-pressure Storage Tanks
– ASME Boiler and Pressure Vessel Code – Section VIII - Pressure Vessels
– UL 2085 – Protected Aboveground Tanks for Flammable & Combustible Liquids
– UL 2245 – Below-Grade Vaults for Flammable Liquid Storage
� IFC Section 5704.2.7 requires a permanent marking
or nameplate on ASTs indicating the standard used
as the basis of design, fabrication and construction
(origin 1997 UFC).
Field-Erected versus Shop-Fabricated
Above-ground Storage Tanks
Field-Erected ASTs
� Volume and the diameter are unlimited.
� The tank bottom is the thickest part of the tank.
� Generally constructed inside of a containment dike.
� Are subject to a periodic internal and external corrosion examination.
� Are approved.
Shop-Fabricated ASTs
� Volume is limited to ≈ 50,000 gallons.
� The tank wall is thinner than the tank heads.
� Can be constructed with integral secondary containment.
� Are not subject to a periodic internal corrosion examination.
� Are listed.
API 650 Field-Erected AST
UL 2245 Vaulted Below-grade AST
2,000 Gallon w.c. ASME Pressure Vessel
Section 5704.2.2 Use of Tank Vehicles
and Tank Cars for Storage
�Tank vehicles and tank cars are not permitted to be used as storage tanks.
�However, Section 5706.5 permits their use for bulk transfer and process transfer operations.
Use of a DOT Tanker as an Above-
ground Storage Tank
Section 5704.2.9.1
Existing Noncompliant Installations
� Section 5704.2.9.1 ensures that any existing above-ground storage tank (AST) is properly installed and maintained.
� An existing AST found to be in violation of the IFC or the NFPA standards adopted by reference that were in effect at the time of construction must be brought into compliance or removed from service.
Section 5704.2.9.2 Fire Protection
� The requirements for fire protection systems on field-erected storage tanks are found in Section 5704.2.9.2.1 and apply to:• Tanks operating at
atmospheric pressure.
• Contents that are Class I or II liquids or crude oil.
• All tanks within a group having a surface area > 1,500 ft².
• Tanks located in relation to fired fuel sources.
• Situations when required by the fire code official.
Section 5704.2.9.2.2
Foam Fire Protection Systems
� Section 5704.2.9.2.2 requires foam fire protection systems to be in accordance with NFPA 11, Low-, Medium- and High-Expansion Foam Systems.
� The requirements in NFPA 11 are dependent on several variables including:
• Tank diameter and height,
• The classification of the stored liquid,
• If ATC type foam is required,
• When fixed foam chambers are used, if the roof is either fixed or floating, and
• If the roof is floating, the design of the foam dam.
Photograph courtesy of
Tyco/Ansul Products,
Marinette WI
Section 5704.2.9.2.2.1 Foam Storage
� The IFC permits the storage
of AFFF on site or off site. If
off-site storage is the
selected method, it must
comply with the following:
• The foam is compatible with the
hazards being protected.
• Adequate material handling and
logistical resources are available.
• A sufficient volume of AFFF is
accumulated before commencing the
fire attack.Photograph courtesy of Tyco/Ansul
Products, Marinette WI
Section 5704.2.9.2.3
Fire Protection of Tank Supports
� Tanks storing Class I, II or IIIA liquids elevated more than 12 inches above grade require that columns or supports have a minimum 2-hour fire-resistance rating based on the fire exposure criteria in ASTM E 1529.
� Protected ASTs, tanks protected by a water spray system or tanks inside of buildings protected by an approved automatic sprinkler system are exempt from the requirement.
Section 5704.2.9.6
Above-ground Tank Location
� Section 5703.2.9.6.1 allows
the jurisdiction to establish
locations where above-
ground storage of Class I
and II liquids is prohibited.
� The NFPA 30 tank siting
requirements depend on the
type of tank, and the
classification and stability of
the liquid stored.
Table 22.4.1.1(a) Location of Aboveground Storage Tanks Storing Stable Liquids — Internal Pressure Not to Exceed a Gauge Pressure of 2.5 PSI (17 kPa)
Minimum Distance (ft)
Type of Tank Protection
From Property Line That Is or Can Be Built Upon, Including the Opposite Side of A Public Waya
From Nearest Side of Any Public Way or from Nearest Important Building on the Same Propertya
Protection from exposuresb
½ x diameter of tank 1/6 x diameter of tank Floating roof
None Diameter of tank but need not exceed 175 ft
1/6 x diameter of tank
Approved foam or inerting system on tanks not exceeding 150 ft. in diameterd
½ x diameter of tank 1/6 x diameter of tank
Protection from exposuresb
Diameter of tank 1/3 x diameter of tank
Vertical with weak roof-to-shell seam
None 2 x diameter of tank but need not exceed 350 feet
1/3 x diameter of tank
Approved foam or inerting systemb on the tank or approved foam system on vertical tanks
½ x Table 22.4.1.1(b) ½ x Table 22.4.1.1(b)
Protection of exposuresb
Table 22.4.1.1 (b) Table 22.4.1.1 (b)
Horizontal and vertical tanks with emergency relief venting to limit pressures to 2.5 PSIG (17.2 kPa gauge)
None 2 x Table 22.4.1.1 (b) Table 22.4.1.1 (b)
Protected aboveground tank
None ½ x Table 22.4.1.1(b) ½ x Table 22.4.1.1(b)
a. The minimum distance cannot be less than 5 feet (1.5 m) b. See 3.3.42, Protection for Exposures c. See NFPA 69, Standard on Explosion Protection Systems d. For tanks over 150 ft (45 m) in diameter, use “Protection for exposures” or “none” as applicable
Table 22.4.1.1 (b) Reference Table for Use in Tables 22.4.1.1(a), 22.4.1.3, and 22.4.1.5
Tank Capacity (gal) Minimum Distance From Property Line That Is or Can Be
Built Upon, Including the Opposite Side of A Public Way
(ft)
Minimum Distance From Nearest Side of Any Public
Way or from Nearest Important Building on the
Same Property (ft) 275 or less 5 5 276 to 750 10 5
751 to 12,000 15 5 12,001 to 30,000 20 5 30,001 to 50,000 30 15
50,001 to 100,000 50 25 100,001 to 500,000 80 25
500,001 to 1,000,000 100 35 1,000,001 to 2,000,000 135 45 2,000,001 to 3,000,000 165 55
3,000,001 or more 175 60
Table 22.4.2.1 Minimum Shell-to-Shell Spacing of Aboveground Storage Tanks
Fixed or Horizontal Tanks Tank Diameter Floating Roof Tanks
Class I or II Liquids Class IIIA Liquids
All tanks not over 150 ft (45 m) in diameter
1/6 x ∑ of adjacent tank diameters but not less than 3 ft (0.9 m)
1/6 x ∑ of adjacent tank diameters but not less than 3 ft (0.9 m)
1/6 x ∑ of adjacent tank diameters but not less than 3 ft (0.9 m)
Tanks larger than 150 ft (45 m) in diameter:
If remote impounding is provided in accordance with 22.11.1
1/6 x ∑ of adjacent tank diameters
¼ x ∑ of adjacent tank diameters
¼ x ∑ of adjacent tank diameters
If open diking is provided is provided in accordance with 22.11.2
¼ x ∑ of adjacent tank diameters
1/3 x ∑ of adjacent tank diameters
1/3 x ∑ of adjacent tank diameters
Location of ASTs
� Four 65,000-gallon
(nominal) vertical API 12F
ASTs are being installed at
a terminal.
� Each tank will store Class
IC stable flammable liquids.
� Each tank has an
emergency vent with an
opening pressure of 1 psig.
� All four tanks are within a
single containment dike.
� Protection of exposures will
be provided by a public fire
department.
AST Site Plan
N
Control Building
Property Line
SS
IB
PL
PL
� NFPA 30 • The distance to the
South and West terminal Property Line (PL)
• The distance to the Control Building, which is an Important Building (IB)
• The Shell to Shell (SS) tank separation distance
Solution: Location of ASTs
� Separation Distance to Property Lines (PL)
• Apply Table 22.4.1.1 (a). Minimum PL distance is based on Table
22.4.1.1 (b). For a nominal 65,000- gallon AST, the minimum PL
separation distance is 50 feet.
� Separation Distance to Important Building (IB)
• The control building is on the same property as the ASTs.
• Table 22.4.1.1 (a) states the separation distance is based on Table
22.4.1.1 (b). For a nominal 65,000-gallon AST the minimum IB
separation distance is 15 feet.
� Tank Shell to Shell (SS) Separation Distance
• Apply Table 22.4.2.1. The each tank’s diameter < 150 feet. Shop
drawings indicate each tank has a nominal 14 foot diameter. The
sum diameter of the three adjacent tanks is 42 feet. (42 feet x
0.167 = Minimum 7 foot SS distance).
Section 5704.2.7
Above-ground Tank Openings
� Atmospheric ASTs are constructed with openings to accommodate:
• Normal vent
• Emergency vent
• Other tank openings
� Other tank openings may be located above or below the liquid level of the tank, except if it is a protected AST or is used for motor vehicle fuel dispensing.
Section 5704.2.7.3.3
Normal Tank Vents
� Atmospheric storage tanks require a method of relieving the internal pressure caused by the introduction or withdrawal of product.
� Section 5704.2.7.3.3 requires the normal vents for tanks that contain Class I, II or IIIA liquids be terminated:• At a safe point outside of buildings
• Not less than 12 feet above the adjacent ground level
• Not less than 5 feet from property lines and building openings
2009 IF
C F
lam
mable
and
Com
bustible
Liq
uid
s
57
Normal vent
pressure – vacuum type
This SUCKED…literally
Make sure that it is the
IMPORTANCE OF EMERGENCY VENTS!
If you only remember ONE THING
from this classF
Workbook Page
Practical Application
Chemical LEL UEL Optimal
Acetone 2.5% 15% 5.0%
Acetylene 2.5% 83% 8.0%
Ammonia 15% 28% 17%
Gasoline 1.4% 7.6% 1.6%
Hydrogen 4.0% 75% 8.0%
Methane 5.0% 15% 9.0%
Toluene 1.2% 7.1% 2.5%
Explosive Limits
Section 5704.2.7.4
Emergency Relief Venting for Tanks
� Stationary ASTs require emergency relief vents to
relieve excessive internal pressures resulting from
fire exposure on or near the tank.
� Incidents in Kansas City, KS, Amarillo and
Kennadale, TX and Gadsden, AL, resulted in fire
fighters’ deaths because adequate emergency
venting was not provided or the vents were
disabled.
� Vent designs include long-bolt vents, venting by
construction or the use of direct-action
emergency vents.
62
Emergency Vent Normal Vent
2009 IFC FLammable and Combustible Liquids
63
Emergency vents
An absolute must to prevent explosive
tank ruptures.
Graphite rupture pin on hinged vent
Section 5704.2.7.4
Emergency Relief Venting for Tanks
� Determining the required vent capacity for an atmospheric storage tank is based on the tank’s orientation, its wetted area, and the minimum volume of free air discharged per hour specified in NFPA 30, Section 22.7 and Annex B [2008 ed.].
� Three steps to determine adequacy of emergency vent:
1. Calculating the tank wetted area
2. Determining the required discharge flow rate based on the material stored in the tank
3. Ensuring the emergency vent will relieve enough vapor to achieve the required flow rate
Section 5704.2.7.4
Emergency Relief Venting for Tanks
� Listed shop-fabricated ASTs will often have a nameplate specifying the minimum flow rate required for emergency vent.
� NFPA 30 Section 22.7.3.10 [2008 ed.] requires the vent discharge capacity to be indicated on the emergency vent.
� To determine if the emergency vent is properly sized, compare the nameplate data to the emergency vent flow rate.
� Vent device flows assume a maximum 1-foot pipe extension based on calculations in API 2000, Venting Atmospheric and Low Pressure Storage Tanks: Nonrefrigerated and Refrigerated.
Section 5704.2.7.4
Emergency Relief Venting for Tanks
Emergency Vent Discharge
Rate: 233,000 SCFH
Hopper Model 34
Emergency Vent
198,000 SCFH @ 8 oz.
Methyl Iso Bad Karma
67
What’s Missing?
68
Pitting indicates a reused
underground tank.
Other ConsiderationsF
Pressure Relief for Vessels
Short on space for your tank farm?
� A protected above-ground storage tank is one
method of resolving safety concerns regarding
above-ground tanks for liquid storage
� PASTs must:
• Be listed to UL 2085
(2-hour temp. limited fire test)
• Have impact protection
• Have secondary containment
• Have overfill protection
• Have openings on top only
� NFPA 30A fire-resistant
tanks are not recognized.
Section 5704.2.9.7
Protected Above-ground Tanks
Section 5704.2.9.7
Protected Above-ground Tanks
� Tanks for fuel storage are specifically regulated in
Chapter 22.
� Above-ground tanks for fuel
storage are limited to a volume
of:
• 12,000 gallons per tank
• 48,000 gallons aggregate
� Table 2206.2.3 specifies
tank siting requirements
based on tank volume
and exposures such as
property lines, important
buildings and adjacent tanks.
Section 5704.2.8
Tank Vaults
� Vaults are used for installing ASTs below grade.
• Premanufactured vaults must be listed in accordance with UL 2245.
• Construction must be a minimum of 6-inches of reinforced concrete.
• Vaults containing Class I liquids require mechanical ventilation.
• Overfill protection, leak monitoring and alarm systems are required.
• Vaults require approved automatic or manual means of applying a fire suppression agent.
Section 5704.2.9.5
Stationary Tanks Inside Buildings
� Typically requires a Group H
occupancy in accordance
with the IBC.
� Tanks for Class I, II and IIIA
liquids require a means of
overfill protection to prevent
liquid from spilling into the
building.
� Section 5704.2.7.5.6 requires
connections that are made
and broken, including fill
connections, to be outside.
� An area surrounding
tanks must be provided
with drainage control or
diking to prevent
accidental discharge
from endangering other
tanks, adjoining
property or waterways.
� Depending on the total
volume within the
containment basin,
intermediate diking may
be required by NFPA 30.
Section 5704.2.10
Drainage and Diking for Tanks
Section 5704.2.10
Drainage and Diking for Tanks
� The IFC requires a dike to
contain the volume of the
largest tank in the dike
plus the volume displaced
by other tanks in the same
dike.
� Walls to be earth, steel,
concrete or solid masonry.
� Must have method to
remove excess water.
Section 5704.2.11
Underground Storage Tanks
� Underground Storage Tanks (USTs) are constructed of carbon steel or fiberglass reinforced plastic.
� Tanks must be located:
• Away from loads caused by foundations,
• At least 3 feet from nearest wall of a basement, pit, cellar or property line, and
• At least 1 foot from other tanks.
Photograph courtesy of the Steel Tank Institute,
Lake Zurich IL
Section 5704.2.11
Underground Storage Tanks
� Tanks must be
sufficiently covered with
earth or other coverings
to prevent damage.
� Fill pipes require a spill
container and an overfill
prevention device.
� Spill containers must
have a capacity of at
least 5 gallons and be
equipped with a drain
valve.
Section 5704.2.11.4
Underground Storage Tanks
� An overfill prevention system must:
• Activate an audible and visual alarm when 90% of tank capacity is reached,
• Shut off flow when 95% of tank capacity is reached, or
• Reduce the flow to 15 gpm, the tank will not fill for 30 minutes and none of the fittings is exposed to product.
Section 5704.3
Container and Portable Tank Storage
� 5704.3 addresses portable tanks ≤ 660 gallons and containers ≤ 60 gallons in volume.
� Their design, construction and maximum volume requirements are established in NFPA 30.
Section 5704.3
Container and Portable Tank Storage
�5704.3.1 Design, construction and capacity
�5704.3.2 Liquid storage cabinets
�5704.3.3 Indoor storage
�5704.3.4 Quantity limits for indoor storage
�5704.3.5 Storage in control areas
�5704.3.6 Wholesale and retail sales
�5704.3.7 Liquid storage rooms
�5704.3.8 Liquid storage warehouses
Section 5704.3.1
Containers and Portable Tanks
� Section 5002.1.1 defines a container as a vessel of 60 gallons or less used for transporting or storing flammable or combustible liquids.
� The IFC, by reference to NFPA 30, requires containers storing Class I, II and IIIA liquids to be constructed in accordance with DOT requirements.
� NFPA 30 limits the volume of a container or portable tank based on container construction materials and the class of liquid contained.
� NFPA 30 regulates storage of plastic containers in other than Group M occupancies. Special regulations for storage in plastic containers in Group M occupancies are set forth in the IFC.
NFPA 30 – Table 9.4.3
Table 9.4.3 Maximum Allowable Size ─ Containers, Intermediate Bulk Containers (IBCs) and Portable Tanks
Flammable Liquids Combustible Liquids
Container Type Class IA Class IB Class IC Class II Class IIIA
Glass 1 pint (0.5 L) 1 quart (1 L) 1.3 gal (5 L) 1.3 gal (5 L) 5.3 gal (20 L)
Metal (other than drums) or approved plastic
1.3 gal (5 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L)
Safety cans 2.6 gal (10 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L)
Metal drum (e.g., UN 1A1/1A2)
119 gal (450 L) 119 gal (450 L) 119 gal (450 L) 119 gal (450 L) 119 gal (450 L)
Approved metal portable tanks and IBCa
793 gal (3000 L) 793 gal (3000 L) 793 gal (3000 L) 793 gal (3000 L) 793 gal (3000 L)
Rigid plastic IBCs (UN 31H1 or 31H2) and composite IBCs with rigid inner receptacle (UN 31HZ1)
NP NP NP 793 gal (3000 L) 793 gal (3000 L)
Composite IBCs with flexible inner receptacle (UN 31HZ2) and DOT/UN approved flexible IBCs
NP NP NP NP NP
Non-bulk Bag-In-Box NP NP NP NP NP
Polyethylene UN 1H1 and UN 1H2, or as authorized by DOT exemption
1.3 gal (5 L) 5.3 gal (20 L) 5.3 gal (20 L) 119 gal (450 L) 119 gal (450 L)
Fiber drum
NMFC or UFC Type 2A; Type 2a, 3B-H, or 3B-L; or Type 4A
NP NP NP 119 gal (450 L) 119 gal (450 L)
NP: Not permitted for the container categories so classified unless a fire protection system is provided that is Developed in accordance with 16.3.6 and is approved for specific container and protection against static electricity is provided.
Fire Protection Issues for Containers
and Intermediate Bulk Containers
� Two issues that
require special
consideration with
respect to fire
protection are:• Storage of plastic
containers of Class I and II
liquids in Group S-1
occupancies
• Use of relieving-style
containers for storage
Plastic Containers
� For a fire code official to “approve” a
container, it must comply with NFPA 30,
Table 9.4.3 and Chapter 12.
�Section 12.8.4, Liquids in Plastic
Containers states:
Class I and II liquids in plastic containers shall not
be stored in general-purpose warehouses but shall
be stored in inside liquid storage areas that meet the
requirements of this chapter.
�This section has two exceptions.
Plastic Containers
� Exception No. 1: The following liquids, packaged
in plastic containers, are permitted to be stored in
general-purpose warehouses in accordance with
the protection and storage limitations specified in
Section 12.8 as follows:
(1) Products containing not more than 50 percent by
volume of water- miscible liquids, with the remainder
of the product consisting of components that do not
burn and where packaged in individual containers
(2) Products containing more than 50-percent water-
miscible liquids in individual containers not
exceeding 16 oz (0.5 L) capacity in cartons
Plastic Containers
� Exception No. 2: Class I
and II liquids in plastic
containers are
permitted to be stored
in a general-purpose
warehouse if the
packaging systems are
listed and labeled for
use with these
commodities. All other
provisions of Section
12.8 also apply.
Fire Protection of Plastic Containers
� In the case of liquid storage rooms and liquid storage warehouses, fire protection of plastic containers containing Class I and II liquids will generally need to be designed as an Alternative Means and Method to Note “b” in Table 5704.3.6.3(3):
In buildings protected by an automatic sprinkler system, the storage height for containers and portable tanks shall not exceed the maximum storage height permitted for the fire protection scheme set forth in NFPA 30 or the maximum storage height demonstrated in a full-scale fire test, whichever is greater. NFPA 30 criteria and fire test results for metallic containers and portable tanks shall not be applied to nonmetallic containers and portable tanks.
Relieving Style Containers
Have a liquid storage room?
Plastic caps (bungs) can
reduce the risk of rupturing a
drum in a fire event.
Relieving Style Containers
� Protection schemes in NFPA 30 for liquid storage call for “relieving style” containers.
� The listed plastic bungs are designed to melt during a fire and prevent explosive rupture of the vessel.
� Covering plastic bungs with a foil seal may prevent proper operation and is not permitted.
Pressure Relief for Vessels
There’s more to sprinkler
design than just hanging
sprinklers from a pipe
This was styrene
monomer…heptane would
have leveled the building!
Even plastic bungs cannot
entirely ensure that rupture
will not occur.
Pressure Relief for Vessels
Even plastic bungs cannot
entirely ensure that rupture
will not occur.
This was styrene
monomer…heptane would
have leveled the building!
Venting is the desired result
Section 5704.3.1 Portable Tanks
� The IFC does not define
PORTABLE TANK; however, it
is any packaging over 60
gallons that is designed to be
loaded into, onto or
temporarily attached to a
transport vehicle.
� NFPA 30 requires portable
tanks to be equipped with an
emergency vent.
� Portable tanks and
intermediate bulk containers
must also meet the
requirements in NFPA 30
Table 9.4.3.
Section 5704.3.1
Intermediate Bulk Containers
� Intermediate Bulk Containers,
often called “totes”, are portable
tanks with a volume up to 793
gallons (3000 L).
• They can be designed for a one-time
use or continuous duty
• Normally designed for gravity
dispensing
� A significant fire protection
concern is the use of plastic IBCs
for the storage liquids.
Section 5704.3.1
Intermediate Bulk Containers
� The National Fire Protection
Research Foundation fire
testing of Intermediate Bulk
Containers found:
• Sprinkler protection using only water
can protect plastic IBCs storing
Class II and IIIA water-miscible
liquids.
� NFPA 30 does not permit
storage of Class I liquids in
nonmetallic IBCs, due to
concerns about static causing
ignition during filling.
Section 5704.3.3 Container & Portable
Tank Storage Inside of Buildings
� Section 5704.3.3 applies to
containers with capacities less
than 60 gallons and portable
tanks less than 660 gallons.
• Storage of liquid in vehicle fuel
tanks and liquor in wooden barrels
or casks is exempt from these
provisions.
Section 5704.3.4 Maximum Allowable
Quantity & Control Areas
� A control area is an area in a building where limited quantities of flammable or combustible liquids are allowed to be stored or used without requiring reclassification to more hazardous occupancy.
� IBC Section 414.2 requires two or more control areas be separated from each other by 1-hour or greater fire barriers, with floor construction and members supporting the floor rated for 2 hours.
� The concept of the control area is to limit the Maximum Allowable Quantity (MAQ) of hazardous materials per control area rather than per building, and then limit the number of control areas within each building.
� Any combination of hazardous materials up to the MAQ is allowed in a control area.
TABLE 2703.1.1(1)
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDa,j,m,n,p
MATERIAL CLASS
GROUP WHEN
MAXIMUM ALLOWABLE QUANITY IS EXCEEDED
STORAGEb USE-CLOSED SYSTEM
b USE-OPEN SYSTEM
b
Solid pounds
(cubic feet)
Liquid gallons
(pounds)
Gas cubic feet at NTP
Solid pounds
(cubic feet)
Liquid gallons
(pounds)
Gas cubic feet
at NTP
Solid pounds (cubic feet)
Liquid gallons
(pounds)
Combustible
liquidsc, i
II
IIIA
IIIB
H-2 or H-3
H-2 or H-3
Not Applicable
Not
Applicable
120d,e
330d,e
13,200e,f
Not
Applicable
Not
Applicable
120d
330d
13,200f
Not
Applicable
Not
Applicable
30d
80d
3,300d
Flammable liquidsc IA
IB and IC
H-2
or
H-3
Not
Applicable
30d,e
120d,e
Not
Applicable
Not
Applicable
30d
120d
Not
Applicable
Not
Applicable
10d
30d
Organic peroxide UD
I
II
III
IV
V
H-1
H-2
H-3
H-3
Not Applicable
Not Applicable
1e,g
5d,e
50d,e
125d,e
Not Limited
Not Limited
(1)e,g
(5)d,e
(50)d,e
(125)d,e
No Limit
No Limit
Not
Applicable
0.25e,g
1d,e
50d,e
125d,e
Not Limited
Not Limited
(0.25)e,g
(1)d,e
(50)d,e
(125)d,e
No Limit
No Limit
Not
Applicable
0.25g
1e
50e
125e
Not Limited
Not Limited
(0.25)g
(1)e
(50)e
(125)e
No Limit
No Limit
a. For use of control areas, see Section 2703.8.3.
b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers not
exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not
more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable shall not be limited, provided that such materials
are packaged in individual containers not exceeding 1.3 gallons.
d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with
Section 903.3.1.1.Where Note e also applies, the increase for both notes shall be applied accumulatively.
e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day boxes, gas cabinets, exhausted enclosures or listed
safety cans. Where Note d also applies, the increase for both notes shall be applied accumulatively.
g. Allowed only in buildings equipped throughout with an approved automatic sprinkler system.
i. The maximum allowable quantity shall not apply to fuel storage complying with Section 603.3.2.
j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column.
Section 5704.3.4 Maximum Allowable
Quantity
• The number of control areas in a building
is limited by IBC Table 414.2.2 and IFC
Table 5003.8.3.2.
99
Table 5003.1.1(1) – Fuel Oil Systems
� IFC Table 5003.1.1(1), Note “i” allows up to 3,000 gallons of fuel oil when the installation complies with Section 603.3.2.
� IMC Section 202 defines a fuel oil as a liquid with a flash point temperature > 100°F.
� Tanks inside buildings must meet IFC Section 5704.2.9.4. Piping must meet ASME B31.9, Building Services Piping, in accordance with Section 5703.6.2 and IMC Chapter 13, Fuel Oil Systems.
Table 5003.1.1(1) – Safety Cans
� Note “e” and Section 5003.9.10
require the use of listed safety cans
to increase the MAQ of Class I, II and
IIIA liquids.
� Safety cans must be listed as
meeting UL 30 or Factory Mutual
Global standards.
• UL listings are limited to metallic cans.
• FM listings cover nonmetallic and metallic
cans.
Photograph courtesy of
Justrite Manufacturing Inc.,
LLC, Des Plaines IL
Section 5704.3.2.1
Liquid Storage Cabinets
� Cabinets are required to be listed as meeting UL 1275 or can be constructed of metal or wood based on the prescriptive requirements in Section 5704.3.2.1.1.
� The IFC permits up to 120 gallons of liquid inside of each cabinet.
� Doors shall be self-closing and equipped with a 3-point latch.
� The bottom 2 inches of the cabinet shall be liquid tight.
Photograph courtesy of
Justrite Manufacturing Inc.,
LLC, Des Plaines IL
Flammable Liquid Cabinet After Fire
Section 5704.3.3.9
Idle Combustible Pallets
� Because of their heat release and burning rates, Section 5704.3.3.9 requires a minimum 8-foot separation between idle combustible pallets and liquid storage.
� In a sprinklered building, the height of storage is limited by the requirements in Section 12.1 of NFPA 13.
� In an unsprinklered building, pallets are limited to a maximum storage height of 6 feet and a maximum pile area of 2,500 ft.²
Section 5704.3.5.1
Storage in Basements
� Section 5704.3.5.1 permits
basement storage of Class I
liquids.
� The quantity limit is based on
the use-open system MAQ and
that the basement is protected
by a fire protection system in
accordance with IFC Chapter 9.
� For Class I liquids in each of 3
control areas in a basement
located one level below the
grade plane:
• Class IA MAQ: 15 gallons/CA
• Class IB & IC MAQ: 45 gallons/CA
Section 5704.3.6
Group M Occupancies
� Group M provisions were developed recognizing demonstrated fire protection designs and understanding that the density method of regulating liquid storage and display in retail occupancies was difficult to enforce.
� Table 5704.3.4.1 allows 7,500 gallons of Class IB, IC, II and IIIA liquids in one control area of Group M occupancies when the automatic sprinkler design is in accordance with Note b.
� Up to 15,000 gallons can be stored when the automatic sprinkler protection meets the criteria in Tables 5704.3.6.3(4) through (8).
Section 5704.3.6
Group M Occupancies
� To obtain the 7,500 gallon quantity limit:• Shelf storage is limited to 6 feet and cartoned, palletized,
or racked storage is limited to 4 feet, 6 inches, the height of a typical pallet load.
• The height of liquid storage is limited by Table 3404.3.6.3(1).
� To assist in the enforcement of these requirements, the code official may require a storage plan to be developed.
� Class I liquid containers in Group M occupancies must be constructed of metal• Except for not more than 120 gallons of nonmetallic
containers not exceeding 16 ounces capacity.
� Maximum container size is 5 gallons.
Section 5704.3.6
Group M Occupancies
Section 5704.3.6 Because Plastic
Containers Are Limited
� Some retailers have switched to steel
packaging to make use of the increased
MAQ amounts allowed in Group M
occupancies, due to the required use of steel
containers.
Sections 5704.3.7 and 5704.3.8
Liquid Storage Rooms & Warehouses
� When the MAQ is exceeded in
a control area, three options
are available: 1) reduce the
quantity below the MAQ
amount; 2) move the storage
outdoors; or 3) construct a
liquid storage room or
warehouse.
� To determine if an occupancy
is a LIQUID STORAGE ROOM
or LIQUID STORAGE
WAREHOUSE, the quantity is
compared to the values in
Table 5704.3.6.3(2) for solid-
pile and palletized storage or
Table5704.3.6.3(3) for rack
storage.
Section 5704.3.7 Liquid Storage Rooms
� A Group H-2 or H-3 occupancy is assigned when the amount of Class I, II or IIIA liquids exceeds the MAQ.
� Quantity limits are based on the amount stored in containers or portable tanks and the method of storage.
� For solid pile & palletized storage, see the “Maximum Quantity Per Room” column in Table 5704.3.6.3 (2).
� For rack storage see the “Maximum Quantity Per Room” column in Table 5704.3.6.3(3).
Section 5704.3.8
Liquid Storage Warehouse
� Required when quantities exceed those for liquid storage rooms.
� Liquid storage warehouses are classified as Group H-2 or H-3 occupancies, and must meet the same requirements of the IBC and IFC for liquid storage rooms.
• Warehouses must also have occupant-use hose lines to reach all portions of the storage areas.
� Pile arrangements and aisle spacing are limited, but quantities are not.
Sections 5704.3.7 and 5704.3.8
Liquid Storage Rooms
� Liquid storage rooms and warehouses are classified as Group H-3 or H-2 occupancies.
� Rooms or warehouses must meet the requirements of IBC Sections 307, 414 and 415.
� Automatic sprinkler protection must comply with IFC Chapter 57 and NFPA 30.
� Rooms require spill control, secondary containment and mechanical ventilation in accordance with CMC Section 505.
1/11/02 – University of California at Santa Cruz
A three-alarm fire Friday on the fourth floor of Sinsheimer
Laboratories injured no one but gutted two large research
labs, damaged other areas of the building, and closed
several other buildings in the Science Hill area of campusF
Laboratory Fires
Fire Protection of Flammable &
Combustible Liquids
� In comparison to other
stored commodities and
goods, designing
automatic sprinkler
systems for the protection
of flammable and
combustible liquids
represents a challenge.
� Fire protection for these
hazardous materials is an
“either/or” proposition.
Fire Protection of Flammable &
Combustible Liquids
20 40 60 80 100
100
80
60
40
20
10
30
50
70
90
Viscosity at room temperature [in thousands of centipoise (cp)]
Weig
ht
(perc
ent flam
mable
or
com
bustible
liq
uid
com
ponent)
� Automatic sprinkler systems for liquid storage rooms and warehouses must also comply with NFPA 30 (see Sections 5704.3.7.5 and 5704.3.8.4).
� The following variables must be evaluated:
• Container, portable tank or IBC?
• Container material of construction
• Miscibility of the stored liquid
• Viscosity of the stored liquid
• Pressure-relieving construction
• Solid-pile, palletized or rack storage?
• Classification and chemical stability of the stored liquid
Fire Protection of Flammable &
Combustible Liquids
� In many cases the only viable protection option is the use of rack storage.
� When rack storage is selected NFPA 30, Chapter 16 commonly specifies fire protection based on four various design schemes.
� Schemes “A” through “D” all require the construction of horizontal barriers and the installation of in-rack or in-rack and face sprinklers.
Containers and Portable Tanks Inside
of Buildings
1. A sprinklered Group F occupancy contains 90 gallons of Class IB liquids stored in two approved liquid cabinets (split 45 gallons in each cabinet). The 9,000-square-foot building is considered as one control area. What is the MAQ for this control area?
2. What is minimum air exchange rate required for a ventilation system in a Group H, Division 3, liquid storage room?
Containers and Portable Tanks Inside
of Buildings
3. What is the maximum amount of liquid permitted in a single control area of Group M occupancy which contains rack storage of Class IB, IC, II and IIIA liquids protected in accordance with Table 5704.3.6.3(4)?
4. How many gallons of Class IC flammable liquids can be stored in an unsprinkleredbasement located one level below the grade plane?
Section 5704.4 Outdoor Storage of
Containers and Portable Tanks
� 5704.4.1 Plans
� 5704.4.2 Location on
property
� 5704.4.3 Spill control and
containment
� 5704.4.4 Security
� 5704.4.5 Protection from
vehicles
� 5704.4.6 Clearance from
combustibles
� 5704.4.7 Weather protection
� 5704.4.8 Empty container
and tank storage
Section 5704.4
Outdoor Container & Portable Tank Storage
� Storage requirements and pile volume limits in Table 5704.4.2 are based on the classification of the liquid and if it is stored in containers or portable tanks.
� Quantity/pile limits are based on the most hazardous class of liquid present.
� Limited quantities are permitted adjacent to buildings.
Section 5705
Dispensing, Use, Mixing and Handling
Section 5705
Dispensing, Use, Mixing and Handling
� When flammable and combustible liquids are taken out of storage and put into use, the fire risk increases.
� Because product transfer, dispensing, mixing, blending and a variety of other processes may liberate flammable vapors into the atmosphere, where they can be ignited, additional safeguards and protection methods are often required.
Section 5705
Dispensing, Use, Mixing and Handling
� Section 5705 sets forth
minimum safety
requirements to prevent
or control fires and
explosions associated
with the use of
flammable and
combustible liquids.
Section 5705
Dispensing, Use, Mixing and Handling
• Permitted liquid transfer
methods
• Cleaning with flammable and
combustible liquids
• Solvent distillation units
• Use, dispensing, mixing rooms
• Explosion control
• Special ventilation for open
systems
Section 5705.2.4
Liquid Transfer
� Class I liquids and Class II and IIIA liquids heated above their flash point in containers exceeding 5.3 gallons must be transferred:
• From UL 30 listed safety cans,
• Through approved closed piping system,
• From containers or tanks by a pump taking suction from the top,
• By gravity through an approved self-or automatic closing valve when spill control and secondary containment are provided and only Class IB, IC, II or III liquids are used, or
• Using approved engineered systems. 127
Section 5705.3.5.2
Maximum Allowable Quantities
� Quantities per control area are limited to those in Table 5003.1.1(1) and occupancy limits of Section 5705.3.5.2.
� Quantities are limited in open or closed systems.
� The MAQ may be increased 100% in sprinklered buildings.
� When the MAQ is exceeded the use must occur in a Group H, Division 2 or 3, liquid use, dispensing and (UDM) mixing room. (See IBC Section 414.5 and IFC Section 5705.3.5.3.)
Section 5705.3.6 Cleaning Operations
� Cleaning with flammable and
combustible liquids is only
permitted in a:
• Code-compliant Group H-2 or H-3
UDM room, or
• Listed parts cleaning machine.
� Listed machines must use a solvent
that is approved for use in the
cleaning machine and not exceed
the quantity limits in Section
5705.3.6.2.1.
� Multiple machines require
separation in accordance with
Section 5705.3.6.2.5.
Photograph courtesy of Safety
Kleen Corporation, Plano TX
Section 5705.3.7
Closed System UDM Rooms
� Mechanical ventilation designed to exhaust not less than 1 cfm per square foot.Explosion control in accordance with the IBC is required for:
• Class IA liquids, and
• Otherwise where an explosive environment can occur as a result of the process.
� Spill control and secondary containment are required when:
• Individual container volume exceeds 55 gallons, or
• The aggregate capacity of containers is greater than 1,000 gallons.
Section 5705.3.7
Open System UDM Rooms
� Requirements for use-open systems are more restrictive because of the ease that vapor can be ignited:• Explosion control is required for
Class IA and IB liquids.
• Spill control is required when liquids are dispensed into containers greater than 1.1 gallon capacity, or liquids are used and mixed in open containers greater than 5.3 gallon capacity.
Section 5705.3.8 Dispensing, Use,
Mixing & Handling Outside Buildings
� Refer to Chapter 23 for motor-vehicle fuel dispensing.
� Spill control and drainage control are required.
� Location on property must satisfy the distances in Section 5705.3.8.2.
� Table 5705.3.8.2 specifies dispensing MAQ for outdoor areas. These MAQs are much lower than those in Chapter 50.
Section 5705.4
Solvent Distillation Units
� SDUs are an appliance that receives contaminated flammable or combustible liquids and distills the contents to remove contaminants and recover the solvents.
� Section 5705.4.1 limits SDUs to a maximum capacity of 60 gallons and requires they be listed in accordance with UL 2208.
Closed Cup Flash Point and Boiling
Point Temperatures for 4 Solvents
Ace
ton
e
He
xa
ne
Me
thyl E
thyl
Ke
ton
e
To
lue
ne
Tfp (°F)Tbp (°F)-50
0
50
100
150
200
250
Section 5705.4
Solvent Distillation Units
� SDUs that exceed 60 gallons
are treated by Section
5705.4.2 as process vessels.
� SDUs are prohibited in
basements and must be listed
for processing any liquids that
are also classified as unstable
(reactive), including
nitrocellulose.
� These appliances require
labeling and a manufacturer’s
instruction manual.
135
Section 5706 Special Operations
Section 5706 Special Operations
� 5706.2 Farms and construction sites
� 5706.3 Well drilling and operations
� 5706.4 Bulk plants or terminals
� 5706.5 Bulk transfer and process transfer operations
� 5706.6 Tank vehicles and vehicle operation
� 5706.7 Refineries
� 5706.8 Vapor recovery and vapor-processing systems
Special Controls for
Flammable and Combustible Liquids
Spill Control and Secondary
Containment
� From Chapter 50
• Spill control– Largest single container
• Secondary containment– Largest container + 20 minutes of sprinkler water discharge
(indoor)
– Unlike other hazardous materials, additional free board for rainwater accumulation is not required for outdoor tank dikes or outdoor tank car and tank vehicle loading and unloading areas
• For storage and closed use, thresholds are 55-gallon individual container and 1,000-gallon aggregate (aggregate for secondary containment only)
• For open use, thresholds are 1.3-gallon individual container and 5.3-gallon aggregate
Section 5004.2 Spill Control and
Secondary Containment
Secondary Containment
A 600-gallon tank of a flammable liquid is stored in a room
classified as a Group H, Division 3-Occupancy. The 1,000-square-foot room is protected by the building sprinkler system which has been hydraulically calculated to provide 0.45 gallon per minute over the most remote 4,000 square feet.
Using the IFC answer the following questions:
Hazardous (Classified) Locations
Hazardous (Classified) Locations
� Hazardous locations are those locations, areas or spaces where fire or explosion hazards may exist due to the presence of flammable gases or vapors, flammable liquids, combustible dusts or ignitable fibers or flyings.
� An area is classified as a hazardous location when a flammable gas or vapor may be present in explosive or ignitable quantities under normal or abnormal conditions.
� The presence or likelihood of flammable gases, liquids or vapors in process vessels or piping does not imply that classification outside of the vessel or piping is required.
� For classification to occur, there must be a means for leakage or release outside of the system.
Classified Electrical Locations
� The IFC’s classified electrical location requirements are set forth in Section 5703.1.
� Section 5703.1.1 requires classified electrical equipment in locations using or handling Class I liquids when specified in Table 5703.1.1.
� The fire code official can eliminate classified location electrical equipment when it is demonstrated that the atmosphere can be maintained at less than 25% LFL.
Classified Electrical Locations
� For specific applications, the NEC references NFPA 497, Recommended Practice for the Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas, and NFPA 496, Standard for Purged and Pressurized Enclosures for Electrical Equipment
Electrical Equipment in Hazardous
(Classified) Locations
� The conventional method of classification is
contained in NEC Section 500-2. The requirements
for classifying electrical equipment are based on
the ignitability of a material and whether a
flammable atmosphere is or can be present.
� The three elements of the system are
• The class of material
• The group of material
• The likelihood of a flammable concentration being present
(Division)
Hazardous (Classified) Locations
� The class designation is assigned based on the type of material. Class I materials are flammable liquids, gases or vapors.
� For a hazardous (classified) location to be properly identified, the material group must be assigned.
� Flammable liquids applied as flammable finishes are classified as Group D materials.
Division 1 Locations
�Open process equipment and inadequate
ventilation are conditions that will require a
Division 1 area classification.• Locations where flammable liquids or liquefied gases are
transferred from one container to another
• Open vats or tanks
• Inadequately ventilated pump rooms
• Interior of a spray booth or spraying room
Class I, Division 1, Location Example
Class I, Group D,
Division 1Liquid Limit
Switch
1-Pentanol
Division 2 Locations
� Locations where flammables are contained in
closed piping systems for which leaks or releases
can occur only due to accidental breakdown,
rupture or abnormal operation of equipment.
� Locations adjacent to Division 1 locations where
transmission of gases or vapors can occur but is
prevented by positive pressure ventilation.
� Adequately ventilated areas where flammable
liquids are handled but the potential for leakage
exists.
Class I, Division 2, Location Example
The pump room is most
likely a Class I, Group
D, Division 2 location.
Flammable
Liquid Pump
Adequate Mechanical Ventilation
Hazardous (Classified) Locations
� The NEC® requires all listed equipment to contain markings indicating that it can be installed in a given hazardous (classified) location based on its:
• Class
• Division
• Group
• Equipment Temperature
• Ambient Temperature Range
Photo courtesy of Cooper Industries, Crouse
Hinds Electrical Division
Changing Classified Locations
� Reduce or eliminate leak sources and open process equipment.
� Change facility from indoors to outdoors.
� Do not erect small buildings around compressors or other equipment that process flammables.
� Reduce process temperatures to below the flash points for the liquids.
� Inside of a building, provide adequate mechanical ventilation with safeguards to ensure operation.
� Construct vapor barriers or unpierced walls to limit the area of classified locations for vapors and gases.
� Change to a pneumatic or hydraulic source of power.
Section 5003.7.3
Powered Industrial Trucks
�Electrical classification also impacts
requirements for powered industrial
trucks.
Section 5003.7.3
Powered Industrial Trucks
�Powered industrial trucks shall be listed
and labeled for their environment.
LPS
Section 5003.7.3
Powered Industrial Trucks
� Powered industrial trucks are regulated by
NFPA 505.
� Types that may be approved for classified
locations are:
• -X
• -Y
• -E
• -S
� For example:
• LPS
• ES
• EX
LPS
157
Section 5004.3 Exhaust Ventilation
� For liquid storage rooms, liquid storage warehouses, use dispensing and mixing rooms and other hazardous uses, special ventilation is required that:• Exhausts 1 cfm per square foot of floor space
• Operates continuously, except for emergency shutoff, unless otherwise approved
• Has makeup air provided
• Has intakes not more than 12 inches above the floor for heavier-than-air vapors
• Provides for air movement across the entire floor
• Is provided with “legally required standby power” (Section 5004.7)
2009 IF
C F
lam
mable
and
Com
bustible
Liq
uid
s
159
Special
exhaust
ventilation
160
A little planning can
help prevent running
air around in a circleF
Yes, that’s a tank
car outside !!!
161
Makeup air for exhaust ventilationis essential for proper operation.
Summary
� This provides a basic familiarity with the requirements for flammable and combustible liquids in the CFC, including:
• Hazards and classification of flammable and combustible liquids
• Above-ground stationary tanks
• Underground tanks
• Containers and portable tanks
• Use, dispensing, mixing and handling
• Special requirements– Spill control and secondary containment
– Classified electrical locations
– Ventilation and Mitigation