Fans in Fire Safety Pressurisation and Ventilation Equipment
Oct 31, 2014
Fans in Fire SafetyPressurisation and Ventilation Equipment
2
Contents
Introduction
Applications
Smoke Control by Pressurisation
H.T. Series Smoke Venting
Control Equipment
Dimensions & Weights
3
4
5-7
8-17
18-19
20-24
Page:
3
Fläkt Woods Limtied (FW) are the acknowledged leaders in the specialised world of airmovement technology.
Over 100 years experience in designing and manufacturing air movement equipment has kept FWin the forefront of innovation, enabling the company to maintain their leadership in a sophisticatedand competitive market.
This long experience and expertise forms the basis for the range of fans and roof extract unitsdesigned specifically for the control and ventilaiton of fire smoke.
Fläkt Woods Limited are a company committed to Quality Assurance.
Registration to BS EN ISO 9001.94 means that FW design is quality assured as well as themanufacture. The commitment to quality doesn't stop with the hardware. The performance datacomes from standard tests carried out in FW's own laboratory which is BSI and AMCA approved.Woods fans can be bought with the confidence that they will achieve the published performance dataand match the assured quality essential in FIRE SAFETY SYSTEMS.
Two main areas of fire safety are detailed within this publication.
Smoke Control by PRESSURISATIONSmoke Control by VENTILATION
Further detailed information on Fan selections and specification can be obtained from Publication JM/SS or by contacting a Fläkt Woods Sales Centre.
Introduction
4
VENTILATION is used mainly in buildings with large open areas - Shopping Malls, SportsCentres, Car Parks, Department Stores etc.Smoke Ventilation systems are designed to:-
ApplicationsThere are basically two methods of Fire Smoke Control which utilise fans and fan equipment - PRESSURISATIONand VENTILATION.In any building fire smoke can be the major killer, and hence reliable smoke control systems can act both to save livesand assist fire fighting. Woods Fire Safety Fans are designed and tested for use in smoke control systems.
Smoke Control by PRESSURISATION
Stairwell Lobby Offices
Inlet
Duty/standbyfan unitsPressure
relief cowl
Pressurisation
Woods offer fans from their JM Aerofoil/Varofoil ranges for use on pressurisation supply systems, andtheir H.T. Series Bifurcated for Exhaust Systems, supported by Woods Technical Paper ref WTP41 - FansIn Fire Safety- Smoke Control By Pressurisation.
PRESSURISATION is often the preferred method ofsmoke control in buildings where the staircases, liftlobbies and corridors form part of the escape routes.i.e. high rise buildings with multiple occupants, Ho-tels, Offices and Residential Flats.Smoke Control using pressure differential is basedon two simple principles:-
Airflow can control smoke movement if the average VELOCITY is of sufficient magnitude
A PRESSURE differential across a barrier can act to control smoke movement.
These two principles form the basis for the designof pressurisation systems to control smoke move-ment, the details of which are outlined in the FireSafety in Buildings- Codes of Practice - BS5588 Parts 4 and 5.
Stairwell Pressurisation System Schematic
Fresh air flow
Floor
Ceiling
Smoke Control by VENTILATION
Ventilation
Smoke Ventilation fans are required to exhaust the hot fire smoke away from the building for givenperiods of time. Woods H.T. and JM H.T. Series smoke venting fans and roof extract units achievethis using simple designs and well proven components.
The application of the H.T. fan ranges are supported by two Woods Fans In Fire Safety technicalpapers ref WTP20 - Fans For Fire Smoke Venting and WTP 39 Regulations, Codes of Practice,System Reliability.
All H.T. Series fans and roof extract units are suitable for continuous operation at temperatures up to 50°Cmaximum and can therefore be used to provide the normal ventilation requirements of the building.
Keep the hot smoke above the escapingocccupant. Assist the fire brigade in fighting fire.Minimise damage to buildings and contents.Clear the residue smoke after fire has been extinguished.
5
Exhaust Fans - H.T. SeriesMost Woods H.T. Series Bifurcated fans areindependently tested and certified by T.U. -Munich to handle 600°C for 90 minutes - categoryG of BS7346 Part 2. This rating is above thatrecommended by most codes of practice.For additional information please refer to sectionon smoke venting equipment in this publication.
Pressure Relief CowlsWoods Pressure Relief Cowls provide aconvenient unobtrusive method of bleeding theexcess air from the staircase, necessary tomaintain 50 Pa with all doors closed. Based onthe Woods Colchester Range of roof extractunits, they are roof top mounted and generallyout of sight.
AncillariesGuards Bellmouth InletsMounting feet Vibration IsolatorsMatching flanges Pressure relief dampers/Flexible connectors CowlsAir operated dampers
Supply Fans - JM Aerofoils
Woods new JM Aerofoil fans meet all the re-quirements of Pressurisation Supply fans iden-tified in WTP41.
JM Aerofoils develop up to 15% more pressurethan more traditional aerofoil sections providingimproved stability and steeper performancecurves.(see opposite).
Blade pitch angles of JM Aerofoil fans can be sim-ply adjusted on site, allowing the air duty to bematched to site conditions (within motor limita-tions).
JM Aerofoils are lightweight. Their impellersare electronically balanced allowing their instal-lation into most structures.
This catalogue details only a small selectionfrom the JM Aerofoil range chosen to meetmost Pressurisation Supply fan duties. For fullproduct specification and performance see pub-lications C22a and C23a.
Supply Fans - Varofoil
Woods Varofoil - Variable Pitch in Motion fans areavailable to provide the supply air for a pressuri-sation system. The performance of the fan canbe automatically adjusted to match the require-ments of the system thereby reducing the size ofpressure relief dampers.Publication VF2010 details full information onWoods Varofoil range.
Supply Fans - standby
Fans can be mounted in either Series orParallel to provide 100% standby. Please consultWoods technical staff for advice on selection.
p sF
- FAN
STA
TIC
PRES
SURE
Pa
200
2
500
100
300
400
4 6 8 10 12 14qv VOLUME FLOW m3/s
016
80JM/25 - 1420 rev/min
30J - 1440 rev/min
Pressurisation Equipment
6
JM Aerofoils - Supply Air Fans
NotesFans detailed above are a small selection from the JM Aerofoil range, chosen to cover most Pressurisation System duties. They are not the only fans availableand alternatives may better suit the requirements of a particular system, see publication C22a, C23a or C1a.100 % standby can be provided by mounting JM Aerofoils in either series or parallel. Please Consult Woods technical staff for advise on fan selection.
40JM2840 rev/min
56JM
- 14
20 re
v/min
50JM2910 rev/min
63JM
- 14
20 re
v/min
71JM
- 14
20 re
v/min
80JM
- 14
40 re
v/min
90JM
- 14
50 re
v/min
100J
M -
1450
rev/m
in48
J - 14
80 re
v/min
2000
1000800
600
400
200
10080
60
40
20
Tota
l Pre
ssur
e Pa
.2 .4 .6 .8 1 2 4 6 8 10 20 40
Volume Flow Rate m3/s
m3/sec @ Pa 380-420 V / 50 Hz / 3φ
Code Speed
rev/min
dB(A)
@ 3m
Pitch Angle (°)min/max
0 50 100 200 300 400 500 MotorMotorRating
(kW)
Full LoadCurrent
(at 400 V)(A)
StartingCurrent
(at 400 V)(A)
40JM/16/2/5... 2840 8°32°
0.952.5
0.92.4
0.82.25
0.72.1
0.51.85
-1.6
BT9CT9
0.581.70
1.43.5
6.020.0
50JM/20/2/6... 2910 8°24°
2.04.2
1.94.1
1.84.0
1.63.8
1.53.6
1.43.4
CT9F2225
1.703.80
3.57.1
20.044.0
56JM/20/4/6... 1420 8°38°
1.44.0
1.33.2
0.73.0
BT9CT9
0.31.4
0.93.5
4.614.0
63JM/20/4/6... 1420 8°36°
1.85.6
1.65.3
1.34.6
CT5F2225
0.582.7
1.75.8
6.531.0
71JM/20/4/6... 1420 8°36°
2.88.4
2.68.0
2.27.3
1.66.3
CT9F2249
1.44.4
3.59.3
14.052.0
80JM/25/4/6... 1440 8°36°
4.010.8
3.810.5
3.09.6
2.08.0
F2245D132/18
2.16.3
4.712.8
30.065.0
90JM/25/4/6... 1450 8°32°
5.914.6
5.614.1
4.713.2
3.812.0
2.510.5
F2245D132/24
2.19.0
4.718.0
30.0100.0
1.02.6
2.14.3
1.54.2
2.06.0
3.18.8
4.211.2
6.215.2
6767
7773
6164
6769
6969
7275
7579
100JM/25/4/6... 1450 8°32°
7.021.0
8.020.0
7.018.5
6.017.5
4.515.5
3.513.5
F2249D160/26
4.417.0
9.333.0
52.0185.0
9.022.0
7883
48J 1480 8°31°
16.641.2
16.341.0
15.940.1
15.139.6
14.738.5
14.037.4
D160/LBKD200/57
25.065.0
44.0120.0
330.0790.0
17.041.6
8494
Performance Data
7
Bifurcated Fans - HT600/1.5B - Exhaust System Fans
Bifurcated fans must be sited away from the fire zone to ensure a supply of ambient air to motor compartment (50°C Max)
24JF - 1440 rev/min30JF - 1450 rev/min
19JF - 2900 rev/min
24KF - 2900 rev/min
19JF - 1440 rev/min
1500
1000800
600
400
200
1008060
40
20
10.5 .8 1 21.5 3 4 5 6 8 10 15
Fan
Total
Pre
ssur
e (Pa
)
Volume Flow (m3/s)
m3/sec @ Pa 380-420 V / 50 Hz / 3φ
Code Speed
rev/min
dB(A)
@ 3m
Pitch Angle (°)
min/max
0 50 100 200 300 400 500 600 MotorMotorRating
(kW)
Full LoadCurrent
(at 400 V)(A)
StartingCurrent
(at 400 V)(A)
19 JF 14408°28°
0.851.95
0.721.80
F2245CF2245C
1.01.0
2.42.4
14.014.0
19 JF 29008°28°
1.94.3
1.804.2
1.753.95
1.603.75
1.453.60
1.33.4
1.03.2
F2225CF2229C
2.55.5
5.611.1
38.090.0
24 JF 14008°28°
1.64.0
1.43.8
0.93.3
F2245CF2245C
1.02.2
2.45.0
14.030.0
24 KF 29508°28°
3.457.15
3.47.1
3.37.0
3.26.9
3.16.7
3.156.5
3.06.4
D132SCD160LC
5.518.5
10.934.8
65.0245.0
30 JF 14508°20°
2.56.4
2.36.1
1.85.7
1.15.0
F2245CF2249C
1.83.8
4.17.7
24.045.0
1.02.15
2.04.4
1.74.3
3.57.2
2.76.6
5862
7579
6569
8387
7375
Performance Data
8
Woods of Colchester Limited,have made Aerofoil fans suit-able for continuous operationin high temperature air streamsfor over 25 years. These fansare currently fitted into DryingMachines, and Smoke Ventingsystems, all over the world.
This long experience forms thebasis for the new range of H.T.SERIES fans and roof extractunits designed specifically forFire Smoke Ventilation.
Woods manufactures fan mo-tors, and is therefore able tolook critically at the require-ments of motor insulation, bear-
ings and lubricants which arevital elements in achieving hightemperature performance. Ex-tensive stress tests on fanimpellers for operation at hightemperatures has enabledWoods to make the best use ofexisting designs and materials.
A full high temperature test pro-gramme has been successfullycompleted. Some of these testswere carried out at independ-ent laboratories.
These tests, combined withWoods’ renowned high stand-ard of engineering and qualityassurance, serve to support
the H.T. Series specification.
Extensive market research hasresulted in the H.T. Series be-ing offered in six temperature/time categories. This addedflexibility enables a fan, or roofextract unit, to be selected tomatch the requirements of thesystem, ensuring the most costeffective installation.
The equipment detailed in thispublication is not the full rangeof items available. If the re-quirement is not included pleaseenquire to head office.
ROOF EXTRACTUNITS AVAILABLE
DVA & UDA
DVA & UDA
DVA & UDA
DVA & UDA
UDA
UDA
FAN TYPESAVAILABLE
AEROFOILBIFURCATED
VAROFOIL
AEROFOILBIFURCATED
VAROFOIL
AEROFOILBIFURCATED
VAROFOIL(†)
AEROFOILBIFURCATED
AEROFOILBIFURCATED
BIFURCATED
CATEGORYCODE *
H.T.150/2
H.T.200/2
H.T.300/0.5
H.T.300/1
H.T.400/2A
H.T.600/1.5B
CATEGORY
(†) Varofoil Fan - For Temperatures Above 250°C Please Enquire.* Add suffix "B" when Bifurcated fan is specified, eg. H.T.400/2B
TEMPERATURE(°C)
150
200
250
300
300
400
600
TIME(Hours)
2.0
2.0
2.0
0.5
1.0
2.0
1.5
Smoke Venting Equipment
9
Quality is assured at Woods. The H.T.SERIES is no e xception, thecompliance of Woods to BSEN ISO 9001.94 the inter nationalstandard f or Quality Assur anceconfirms this.
H.T. Series fans and roof extract unitshave successfully completed anextensive prog ramme of hightemperature tests in accordance withBS7346: Part 2: 1990, from 200 °C to600°C f or per iods v arying from 30minutes to two hours.
Some of these tests ha ve beenwitnessed by independent author itiessuch as the Loss Pre vention Council(F.I.R.T.O.) in the U.K., or under takenin independent labor atories atC.T.I.C.M. in F rance and TechnischeUniversität (T.Ü.) in Germany.
The H.T . Ser ies is cer tified andapproved for use in fire smoke ventingsystems.
Performance Testing
10
Aerofoil impeller, die cast inaluminium alloy. Componentsare X-ray inspected to ensurecompliance with standards.Categories H.T.400/2A:H.T.400/2B use either an alu-minium impeller or a speciallydesigned impeller fabricated insteel to provide stability at thehigher temperatures. TheH.T.600/1.5 uses the steelimpeller exclusively.Both impellers have a range ofblade angles and impeller so-lidity (number of blades) for flex-ibility of air duty. Impeller bladeangles are set and fixed atworks.
MotorsWoods H.T. Series fans utilisea totally enclosed squirrel cagemotor. The motor carcase isconstructed of either aluminiumalloy or cast iron dependent onthe temperature of operation.
The grades of motor insulationhave been selected to meet thespecific requirements of eachH.T. Category, as the essentialproperty of withstanding ther-mal shock is not common to allhigh temperature materials. Attemperatures above 400°C, bi-furcated fans with motor out ofthe air stream are the only reli-able solution.
Motor tests indicate than whennew, all motors used on WoodsH.T. Series fans have a safetymargin of an average of twicethe expected survival times, thisbeing based on Woods exten-sive test experience gainedduring the development of theirrange of specifications.
LubricationWoods H.T. Series fan motorbearings must be lubricated
Aerofoil FansFull technical data of the highlyefficient Woods Aerofoil Fanrange can be found in publica-tion C22a and C1a.
Aerofoil fan motors are rated tohandle the peak powers of thefans at both ambient and hightemperature. Aerofoil fanshave a safe non-overloadingcharacteristic. Two speedmotors available - please en-quire.
CasingsThe cylindrical casing, housingthe fan, is made of steel, hotdipped galvanised after manu-facture. It is flanged at each end.
S-Type - The casing surroundsthe impeller only and supportsthe motor mounting. The elec-trical terminal box is mountedon the motor. Suitable for tem-peratures up to 300°C.
L-Type - The casing completelysurrounds both the impeller andmotor. The terminal box ismounted on the casing and pre-wired at works.
Bifurcated - Simpler than theusual or split case fan, theWoods Bifurcated Aerofoil issimilar to a normal axial flow fan,but the motor is isolated from themain air stream in a tunnelwhich extends to one side of thefan casing. The motor is cooledby a cooling fan mounted on thetail end of the motor. An unob-structed supply of air at ambi-ent temperature of max 50 °Cmust be available to cool themotor, through the tunnel.
ImpellersFan categories H.T.150/2:H.T.300/0.5 and H.T.300/1mostly use the classic Woods
strictly in accordance with theinstructions on the motor name-plate.
The motor bearings andgreases used in the H.T. Serieshave been selected to providelong life at normal ambient tem-perature and still survive theemergency condition during thislife-time.
The special greases requiredfor fan motors operating above300°C are unsuitable for con-ventional relubricating methods- extended lubricators, greaseguns etc. Here the motor willneed to be dismantled andregreased at specified intervals.This does not apply to Bifur-cated Fans where the motor isseparated from the hot gases.
Electrical SuppliesH.T. Series fans are availablefor connections to 380 - 420 V/ 50 Hz / 3φ electrical supplies.For other voltages and frequen-cies - please enquire.
Bifurcated Aerofoil Fan
L-Type Aerofoil Fan
Specifications - Fans
11
FansThe DVA range is powered by theWoods Aerofoil fan described onpage 10. On an open inlet, abellmouth must be used to obtainthe specified performance. Twospeed motors are available -please enquire.
The UDA Unit• 9 Unit Sizes 300 mm to
2000 mm.• Volume Flow up to 45 m3/s.
• Air Pressure up to 1000 Paavailable
Unit ConstructionThe unit base is constructed fromsheet steel, hot dipped galvanisedafter manufacture. The windshieldand air operated shutters, designedto prevent the ingress of rain orsnow, are manufactured fromaluminium.
FansThe UDA range is powered by theWoods Aerofoil fan described onpage 10. On an open inlet, abellmouth must be used to obtainthe specified performance. Twospeed motors are available -please enquire.
DVA Roof Unit
UDA Roof Unit
Ancillaries - Fans and Roof Extract Units
All standard steel ancillaries e.g.Mounting Feet, Bellmouth Inlets,Matching Flanges, Wire Guardsetc., are suitable for 600°C,
Aerofoil dampers are limited to400°C.
Upstream Guidevane Units ie GJtype fans with aluminium impellers
- Suitable for operation up to 400°C (See page 8 for time categories)
can be used up to 300°C, providingthe impeller is suitable for thistemperature.
Flexible Connector - Silicon coatedglass fibre fabric.
Vibration Isolators - Spring typeare available for all fans.
The DVA Unit - Suitable for operation up to 300°C (See page 8 for time categories)
• 5 Unit Sizes 400 mm to1000 mm.
• Volume Flow up to 10 m3/s.
• Air Pressure up to 500 Paavailable
Unit ConstructionWeathershield and base in stronglightweight glass re-inforcedpolyester resin rendered fireretardent to BS476: Part 7 Class 2.
Standard colour is to BS4800:08B/21.
The cowl is secured to the mountingbrackets by stainless steel screws.Air operated, anti-backdraughtshutters are fitted as standard.
Specifications - Roof Extract Units
12
Category - HT150/2; HT200/2; HT300/0.5; HT300/1
Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection ofpopular fans are detailed in thispublication. Please enquire foralternative pitch angles andspeeds.
2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.
45JM2910 rev/min
31JM2840 rev/min
50JM - 2910 rev/min56JM - 2910 rev/min
63JM - 2910 rev/min
56JM
- 14
20 re
v/min
63JM
- 14
40 re
v/min
71JM
- 14
40 re
v/min
80JM
- 14
40 re
v/min
90JM
- 14
40 re
v/min
100J
M -
1470
rev/m
in
48J - 1480 rev/min
60J -
975
rev/m
in
75J1/2975 rev/min
2000
1000800600
400
200
10080
60
40
20
10
Tota
l Pre
ssur
e Pa
.1 .2 .4 .6 .8 1 2 4 6 8 10 20 40
Volume Flow Rate m3/s
80
Code MotorMotor Rating
(kW)Speedrev/min
Pitch angle(max.)
31JM/16/2/5... 10.9
28402840
40°40°
5.74.6
29102910
40°40°
5.74.6
29102910
32°28°
22°18°
2.51.75
14201420
40°40°
22 2910 36°
63JM/25/4/9... 4.24.6
14401440
40°40°
71JM/25/4/9... 6.3 1440 36°
75J1/2 37 725 26°
45JM/20/2/6...
50JM/20/2/6...
56JM/20/2/6... 5.74.6
29102910
56JM/20/4/6...
63JM/25/2/6...
80JM/25/4/9... 10 1440 36°90JM/25/4/9... 17.3 1440 36°
100JM/25/4/9... 25 1470 36°48J 54 1480 26°
60J 45 975 24°
CT5 (†)D80/A
F2229B (†)D112/M
F2245B (†)D90/LN
DF160/L
F2249B (†)D112/M
DF132/MS
DF250/MG
F2229B (†)D112/M
F2229B (†)D112/M
DF132/M
DF160/L
DF160/LBKDF225/M
DF250/MG
(†) - Not suitable for category HT300/1
Aerofoil Fans
13
Category - HT150/2; HT200/2; HT300/0.5; HT300/1
Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection ofpopular fans are detailed in thispublication. Please enquire foralternative blade pitch angles andspeeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.3. When selecting aerofoilfans for use in Roof Extract Unitsallow for the following overallstatic pressure losses through theunit:-
Type UDA - 1.0 x fan velocitypressure. (Plus any inlet ductsystem resistance).
TYPE UDA
.1 .2 .4 .6 .8 1 2 4 6 8 10
40
60
80100
Stat
ic P
ress
ure
Pa
Volume Flow Rate m3/s
200
400
600
800
20
1020 40
UDA 7601440 rev/min
UDA 3002840 rev.min
UDA 3802840 rev/min
UDA 4802910 rev/min
UDA 9601470 rev/min
UDA 6001440 rev/minUDA 480
1420 rev/min
60
UDA 1220 - 1480 rev/min
UDA 1600 - 975 rev/min UDA 2000 - 725 rev/m
in
1500
1000
Code Fan RefMotor Rating
(kW)Speed
rev/minPitch angle
(max.)
UDA 300 31JM31JM
1.00.9
28402840
40°40°
UDA 38040JM40JM
UDA 480
50JM50JM
5.74.6
29102910
32°28°
50JM50JM
1.30.9
14201420
40°40°
UDA 60063JM 22.0 2950 36°63JM63JM
4.24.6
14401440
36°36°
UDA 760 80JM 10.0 1440 36°
UDA 960 100JM 25.0 1470 36°
UDA 1220 48J 52.0 1480 26°
UDA 1600 60J 55.0 975 29°
UDA 2000 75J1/2 37.0 725 26°
CT5 (†)D80/A
F2229B (†)D112/M
CT9 (†)D80/B
DF160/L
F2249B (†)D112/M
DF132/M
DF160/LBK
DF225/M
DF250/M
DF250/MG
1.70.9
28402840
32°18°
CT9 (†)D80/A
(†) - Not suitable for category HT300/1
Roof Extract Units
14
Category - HT150/2; HT200/2; HT300/0.5; HT300/1
Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection ofpopular fans are detailed in thispublication. Please enquire foralternative blade pitch angles andspeeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.3. When selecting aerofoilfans for use in Roof Extract Unitsallow for the following overallstatic pressure losses through theunit:-
Type DVA - 0.2 x fan velocitypressure. (Plus any inlet ductsystem resistance).
(†) - Not suitable for category HT300/1
TYPE DVA
1000
.1 .2 .4 .6 .8 1 2 4 6 10
40
60
80
100
Stat
ic P
ress
ure
Pa
Volume Flow Rate m3/s
200
400
600
800
20
1020
DVA 4002840 rev/min
DVA 5002840 rev/min
DVA 6302910 rev/min
DVA 6301420 rev/min
DVA 8001440 rev/min
DVA 10001440 rev/min
Code Fan Ref. Motor Rating(kW)
Speedrev/min
Pitch angle (max)
DVA 400 31JM CT5 (†) 1.0 2840 40° 31JM D80/A 0.9
DVA 500
DVA 630
50JM F2229/B(†) 5.72910
32° 50JM D112/M 4.6 28° 50JM CT9 (†) 1.3
1420 40° 50JM D80/B 0.9
DVA 800 63JM F2249/B(†) 4.2
1440 40° 63JM D112/M 4.6
DVA 1000
2840
2910
1420
1440
40°
40°
40°
1440 80JM DF132/M 10.0 36°
40JM CT9 (†) 1.7 2840 32° 40JM D80/A 0.9 2840 18°
Roof Extract Units
15
Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection of popularfans are detailed in this publication.Please enquire for alternative bladepitch angles and speeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.
Category - HT400/2
Code Motor Motor Rating(kW)
Speedrev/min
Pitch angle (°)(max.)
50JM/20/4/6... D80/B 0.75 1420 36°56JM/20/4/6... D90/LN 1.5 1420 40°63JM/25/4/9... DF112/M 4 1440 40°71JM/25/4/9... DF132/MS 5.5 1440 36°80JM/25/4/9... DF160/LM 11 1440 36°90JM/25/4/9... DF160/LAK 18.5 1440 36°
100JM/25/4/9... DF160/LBK 21 1470 32°48JF60JF
D225/MD250/M
40.540.5
1470975
20°20°
56JM
- 14
20 re
v/min
63JM
- 14
40 re
v/min
71JM
- 14
40 re
v/min
80JM
- 14
40 re
v/min
90JM
- 14
40 re
v/min
100J
M -
1470
rev/m
in
48JF1470 rev/min
60JF
- 97
5 re
v/min
50JM
- 14
20 re
v/min
2000
1000800
600
400
200
10080
60
40
20
10
Tota
l Pre
ssur
e Pa
.1 .2 .4 .6 .8 1 2 4 6 8 10 20 40
Volume Flow Rate m3/s
80
Aerofoil Fans
16
Category - HT400/2A
Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection of popularfans are detailed in this publication.Please enquire for alternativeblade pitch angles and speeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.3. When selecting aerofoilfans for use in Roof Extract Unitsallow for the following overallstatic pressure losses through theunit:-
Type UDA - 1.0 x fan velocitypressure. (Plus any inlet ductsystem resistance).
4. For this category L-typeAerofoil fans only are available.
TYPE UDA
Code Fan Ref. Motor Rating(kW)
Speedrev/min
Pitch angle (max.)
UDA 380 15J D90/LN 2.2 2850 36°
UDA 480 19JF D112/M 4.0 2900 24° 50JM D80/B 0.75 1420 36°
UDA 600 24KF D160/LMB 15.0 2900 28° 63JM DF112/M 4.0 1440 40°
UDA 760 80JM DF160/LM 11.0 1440 36°UDA 960 100JM DF160/LBK 21.0 1470 32°UDA 1220 48JF D225/M 40.5 1470 20°UDA 1600 60JF D250/M 40.5 975 20°
UDA 3802850 rev/min
.2 .4 .6 .8 1 2 4 6 8 10
40
60
80100
Stat
ic P
ress
ure
Pa
Volume Flow Rate m3/s
200
400
600
800
20
1020 40
UDA 7601440 rev/min
UDA 9601470 rev/min
UDA 6001440 rev/minUDA 480
1420 rev/min
60
1500
1000
UDA 4802900 rev/min UDA 600
2900 rev/min
UDA 1220 - 1440 rev/min
UDA 1600 - 975 rev/min
Roof Extract Units
17
Category - HT400/2B; HT600/1.5B
Notes:-1. Most Woods Bifurcated Fanscan be built to the H.T. Seriesspecification. A selection of popularfans are detailed in this publication.Please enquire for alternative bladepitch angles and speeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.3. Bifurcated fans must be sitedaway from the fire zone to ensure asupply of ambient air to motorcompartment (50°C Max).
24JF - 1440 rev/min30JF - 1450 rev/min
19JF - 2900 rev/min
24KF - 2900 rev/min
38JF - 1450 rev/min
44JF
- 146
0 rev
/min
48JF - 1460 rev/min
19JF - 1440 rev/min
1500
1000800
600
400
200
1008060
40
20
10.5 .8 1 21.5 3 4 5 6 8 10 15 20 30
Fan
Tota
l Pr
essu
re (P
a)
Volume Flow (m3/s)
F2229C F2245C
F2245C F2249C D180LD
D160LC
Code Motor Speedrev/min
Pitch angle(max.)
19JF 2900 28°1440 28°
24JF 1440 28°30JF 1450 20°38JF 1450 28°44JF D200LD 1460 20°48JF D225MD 1460 20°
Motor Rating(kW)
5.51.0
2.23.8
22.030.045.0
24KF 2900 28°18.519JF
Bifurcated Fans
18
An essential part of any SmokeVenting system is its control gear.Woods offer the following controlsystem variations with the H.T.Series Fans and Roof ExtractUnits on Fire Safety Systems.
1 Emergency Extract Only: Type ESS. Type ESS/SD Star Delta
2 Normal Ventilation/ Emergency Extract Starter: (Single Speed Units) Type EDSS/D.O.L. Type EDSS/SD Star Delta.
3 Two Speed Starter/High Speed Emergency Extract: (Two Speed Units) Type EDSS/DW Dual Wound. Type EDSS/PC Pole Change.
the control circuits.
If control circuit supply fails or isdisconnected by sensors, panelwill switch to emergency extract.
Control circuits are shown suitablefor connection to 220-240 voltsingle phase supply. Other controlcircuit voltages are available. Toensure that control panels interfacecorrectly with smoke detectors,please advise details of smokedetectors to be used. Note: Smokedetectors and remote emergencybuttons are not supplied with thecontrol panel. If fitted, overheatprotectors in motor windings andany other motor protection device,must be by-passed in emergency.
In emergency conditions fans canbe started in one of three ways:
a) Using emergency button mounted on control panels.b) By automatic smoke detectors.c) By using manual remote emergency buttons.
Electrical SupplyThree Phase Panels require asustained three phase supply plusneutral, wired with fire resistantcable and a separate single phasesupply for the control circuits.
Single Phase Panels requiresustained single phase supplywired with fire resistant cable anda separate single phase supply for
EmergencyExtract Only(Single Speed)Fans/control operated inemergency conditions only.
Panel Ref:ESS D.O.L StartingESS/SD Star/Delta Starting
(Automatic)
Starter/EmergencyExtract(Single Speed)For normal ventilation panelfunctions as a standard manualstarter switching to permanentoperation in emergency.
Panel Ref:EDSS D.O.L StartingEDSS/SD Star/Delta Starting
(Automatic)
N L1 L2 L3L N
L N
U V W
C1 EmergencyOn
RLA1(a)
To fan motor(fire resistant cable)
DoorLockIsolator
Sustained supply(fire resistant cable)
Separate single phase supply
(control circuit)
Smoke Detector(s)(normally closed contact)
Remote EmergencyPush Switch (if fitted)
EmergencyStart
Fuse
DL
C1
THREE PHASE ESS PANEL
RLA1
N L1 L2 L3L N
N
C1 EmergencyOn
RLA1(a) RLA1
To fan motor(fire resistant cable)
DoorLock
Isolator
Sustained supply(fire resistant cable)
THREE PHASE EDSS PANEL
Separate single phase supply
(control circuit)
Smoke Detector(s)(normally closedcontact)
Remote EmergencyPush Switch (if fitted)
EmergencyStart
Fuse
DL
C1C2
C2
Start
Stop
Reset
Fan Run
U V W
L
OverloadRelay
Control Equipment
19
Power switching circuit forEDSS/PC control panel (direct online starting).
Using two speed motors fornormal ventilation using eitherspeed, panel functions as a D.O.L.starter, switching to high speed inemergency conditions.
Panels can be supplied for usewith two speed dual wound or polechange motors.
Panel Ref:EDSS/DW Two speed dual
wound motorsEDSS/PC Two speed pole
change motors
D.O.L. starting both speeds isstandard.
Automatic Star/Delta starting canbe supplied with EDSS/DW panels,please enquire.
Power switching circuit forEDSS/DW control panel (direct online starting).
Control circuit for EDSS/PC andEDSS/DW control panels (directon line starting).
All Woods smoke venting controlgear is housed in sheet steelenclosures to IP44 and have thefollowing standard features:
• Door Lock Isolator• Indicator Lights• Panels supplied with
removable gland plates
Panel construction & dimensions
C1
CBA
C2
Start
ResetHGF
D
Run
O/L Aux O/L Aux
Off
LowSpeed
High Speed
C1 C2
High Speed Low SpeedJ
C1
C2
Run
1W1V1U2W2V2U
Reset
N L1 L2 L3
L N
L N
F G H
Emergency'on' Light
RLA1(A)
DoorLockIsolator
Sustained Supply(Fire Resistant Cable)
Separate single phase supply(control circuit)
Smoke Detector(s)(normally closedcontact)
Remote EmergencyPush Switch (if fitted)
EmergencyStart
Fuse
C4
C4
C B A
J
RLA1(A)
C4 AUX NCRLA1
DEDL
Control Panel Dimensions
C1
CBA
C2
StartResetHGF
D
Reset
Run
O/L Aux
O/L Aux
Off
LowSpeed
High Speed
C2
JC1
C2
Run
E
C4 Aux. No.
C3
C3
C3Aux.
High Speed Low Speed
1W1V1U2W2V2U
C3Aux.
C1
All dimensions in millimetres
Model Rating (kW) A B C
ESS 4,5.5,9,11 215 215 150ESS 22 & 37 240 420 240EDSS 4 & 5.5 215 215 150
EDSS 9 & 11 240 300 150EDSS 22 & 27 240 420 240
A C
B
Control Equipment (continued)
20
Aerofoils (L Type)
Note : For vertical mounting details of 48J and 60J - please enquire
CodeMotorFrame
DIMENSION REFERENCE (mm) Weight(kg)A B C D E G H K L M N P S T
31JM8
40JMBT9CT5
400400
480480
375375
279279
2.52.5
225225
450450
289289
350350
400400
1010
250250
88
1212
45JM F2229 450 530 520 306 3 255 500 434 400 450 10 280 8 12
71JM
263055
303030
V
80JM
90JM
100JM
CT5 315 395 375 235 2.5 175 355 289 265 315 10 200 108 2730
50JM
CT9F2225F2229
500500500
594594594
375520520
338338338
2.533
290290290
560560560
289434434
450450450
500500500
101010
315315315
121212
121212
345465
303030
56JM
BT9CT9F2245F2229
560560560560
654654654654
375375520520
368368368368
2.52.533
330330330330
620620620620
289289434434
510510510510
560560560560
10101010
355355355355
12121212
12121212
34385667
50505050
63JM
CT5F2225F2249
630630630
724724724
375520520
403403403
333
375375375
690690690
289434434
580580580
630630630
101010
400400400
121212
121212
527081
505050
CT9 710 804 375 443 3 415 770 259 660 710 10 440 16 12 5450F2249 710 804 520 443 3 415 770 404 660 710 10 440 16 12 8550
710 804 415 770 660 710 10 440 16 12 50404480 147DF132 520 4
F2249D132
800800
894894
520520
488525
35
485485
860860
404404
750750
800800
1010
510510
1616
1212
94163
5050
800 894 485 860 750 800 10 510 16 12 50404525 194DF132 520 5F2245 900 1006 520 538 3 491 970 444 850 900 10 518 16 15 8850D132 900 1006 520 575 5 491 970 444 850 900 12 518 16 15 18350
900 1006 491 970 549 850 900 12 518 16 15 50575 280DF160 625 5
F2249 1000 1106 520 588 3 547 1070 444 950 1000 10 574 16 15 10750D160 1000 1106 625 625 5 547 1070 539 950 1000 12 574 16 15 26850
1000 1106 547 1070 549 950 1000 12 574 16 15 50625 317DF160 625 5
D160/LBK 1219 1357 711 753 5 - 1289 574 1143 1219 14 737 20 18 28786D200/57 1219 1357 914 753 6 - 1289 777 1143 1219 14 737 20 18 56286
1219 1357 - 1289 674 1143 1219 14 737 20 18 86753 638D225/M 813 648J
D225/M 1524 1694 813 910 6 - 1626 674 1422 1524 14 921 12 18 67687D250/M 1524 1694 914 910 6 - 1626 775 1422 1524 14 921 12 18 90487
D250/M
60J
75J 1/2 please enquire
315 395 175 355 289 265 315 10 200 10 30235 31D80 375 2.5
450 530 255 500 434 400 450 10 280 8 12 30306 72DF112 520 3
500 594 290 560 434 450 500 10 315 12 12 30338 77DF112 520 4
560560
654654
330330
620620
434434
510510
560560
1010
355355
1212
1212
5050
368368
5880
D90DF112
520520
34
630630
724724
375375
690690 529
580580
630630
1010
400400
1212
1212
5050
434403440
96234DF160
DF112 520625
44
C
ØB
O
VE
R F
LA
NG
ES
ØA
IN
SID
E
E
GUARDS OPTIONAL
AIRFLOW
FORM B
AIRFLOW
FORM A
K CRS
DF132,D160,DF132,DF160 FRAMES40 DIA. HOLES FOR CONDUIT.2 EACH SIDE SUITABLE FOR PG29 OR 1.5"BT,CT,F22,D80,D90,DF112 FRAMES23 DIA. HOLES FOR CONDUIT.2 EACH SIDE SUITABLE FOR CM20 OR PG16
S No. OF HOLES T DIA.EQUISPACED ON H PCD.
L CRS
M
SIGHT PORT
DP
BT,CT,F22,D80,D90,DF112 FRAMES1 HOLE 20 DIA. (END OF BOX) TO SUIT CM16 OR PG11 GLAND FOR AUXILIARY CABLES
G
FOOT POSITION FOR VERTICAL MOUNTING
VLENGTH OF GUARD31JM TO 100JM - 137mm48J & 60J - 212mm
IMPERIAL SIZEST/Box D160,D180,D200,D225 FRAMES2-HOLES TAPPED PG29OTHER SIZES AVAILABLE TO ORDER
Dimensions and Weights
21
Bifurcated Fans
Type I
Type II
ATTACHABLE FEETTHICKNESS Q
235 S No. OF HOLESØT ON H P.C.D.
SLOTS IN FEET ØN
M
L crs.
AIRFLOW
FORM B
C
G
DP
= K crs. =
ØB
ØA
E
F
HOLE ØJ
AIRFLOW
FORM B
DP
E
F HOLE ØJ
ØA
ØB
C
= K crs =
G
S No. OF HOLES ØT ON H P.C.D.
L crs.
MSLOTS INFEET ØN ATTACHABLE FEET
THICKNESS Q
All dimensions in millimetres
Code Motor Type A B C D E F G H K L M N P Q S TWeight
(Kg)
19JFF2225/45F2229
II
483483
592592
787787
408408
66
376431
366366
541541
692692
438438
483483
1111
311311
33
88
1414
100112
24JF F2245 II 610 699 616 427 3 360 385 668 502 559 610 11 381 3 12 14 108
24KFD132D160LC
II
610610
721721
10501050
540578
66
495550
498493
668668
930930
559559
610610
1111
381381
33
1212
1515
210250
30J F2249 II 762 851 660 503 5 460 461 821 542 711 762 11 483 5 12 14 147
30JF F2245 II 762 851 660 503 5 405 461 821 542 711 762 11 483 5 12 14 135
38JF D180LD II 965 1103 1000 689 5 565 604 1035 863 914 965 14 597 6 16 19 400
44JF D200LD II 1120 1258 1100 768 6 604 683 1190 958 1070 1120 14 710 6 20 15 520
48JF D225MD II 1219 1361 1250 827 12 705 736 1289 1099 1143 1219 14 737 6 20 19 750
Dimensions and Weights
22
DVA400 AND DVA500 - 4 OFF M8 FIXINGS ON CENTRE LINES FOR UNIT SKIRT
DVA630 TO DVA1000 - 8 OFF M8 FIXINGS ON J CENTRES FOR UNIT SKIRT
8 OFF M8 FIXINGS FOR DUCT
MOUNTING PLATE
ROOF CURB (PLAN)
J cr
s.
F s
q.
E s
q.
G c
rs.
H c
rs.
72
C
’S' TYPE FAN ASSEMBLYSHOWN THIS SIDE
A sq.
SPACER DUCT
B sq.
D
'S' TYPE FAN
CUSTOMER'SDUCTING
’L' TYPE FAN ASSEMBLYSHOWN THIS SIDE
'L' TYPE FAN
DVA Roof Units
All dimensions in millimetresAll dimensions and weights shown are for L type fans.
Unit Code Fan Ref A B C D E F G H JMax Weight
Less fan(Kg)
With fan
DVA 40031JM31JM
CT5D80/A
600600
530530
480480
783783
550550
400400
210210
460460
--
1818
4549
DVA 50040JM40JM
700700
630630
530530
650650
500500
260260
560560
--
2424
DVA 630
50JM50JM50JM50JM
CT9D80/BF2229/BD112/M
900900900900
780780780780
630630630630
933107810781078
850850850850
700700700700
360360360360
740740740740
400400400400
47474747
8186
112124
DVA 80063JM63JM
F2249/BD112/M
10501050
950950
750750
11981198
10001000
800800
400400
886886
400400
6565
146161
DVA 1000 80JM DF132/M 1250 1180 880 1328 1200 1000 300 1080 500 96 259
CT9D80/A
833833
5456
Dimensions and Weights
23
B sq.
'L' TYPE FAN
'S' TYPE FAN
BIRD GUARD(OPTIONAL)
D
CE
A sq.
K
H c
rs.
J cr
s.
G s
q.
ROOF CURB (PLAN)
L No. OF HOLES Ø12
K
J cr
s.
’L' TYPE FAN ASSEMBLYSHOWN THIS SIDE
CUSTOMER'S DUCTING
’S' TYPE FAN ASSEMBLYSHOWN THIS SIDE
UDA Roof Units
All dimensions in millimetres
Unit Code Fan Ref A B C D G H J K L Max WeightLess fan
(Kg)With fan
UDA 30031JM31JM
CT5D80/A
600600
530530
302302
627627
400400
--
245245
7575
44
10.910.9
37.941.9
UDA 38040JM40JM15J D90/L
700700700
628628628
344344344 700
500500500
340340340
288288288
757575
888
14.214.214.2 58.2
UDA 480
50JM50JM50JM50JM50JM19JF
F2229BD112/MCT9D90D80/BD112/M
850850850850850850
743743743743743743
398398398398398398
868868723868723856
600600600600600600
400400400400400400
350350350350350350
757575757575
888888
18.418.418.418.418.418.4
83.493.452.477.457.485.4
UDA 600
63JM63JM63JM63JM24KF
DF160/LF2249BD112/MDF112/MD160/LMB
10501050105010501050
879879879879879
398398398398398
973868868868
1059
800800800800800
490490490490490
450450450450450
100100100100100
88888
28.828.828.828.828.8
243.8109.8117.8117.8223.8
UDA 76080JM80JM
DF132/MDF160/LM
12501250
10481048
434434
9041009
10001000
680680
550550
100100
1212
5050
244279
UDA 960 100JM DF160/LBK 1450 1276 534 1109 1200 880 650 100 12 122 760
UDA 1220 48J D225/M 1750 1585 665 1529 1500 1120 800 100 12 122 760
UDA 1600 60J D250/M 2272 2026 706 1585 2000 1440 1050 100 12 409 1321
UDA 2000 75J 1/2 D250/M 2672 2438 749 1628 2400 1800 1250 100 12 545 Enq
CT9D80/A
669669
44.246.2
Dimensions and Weights
24
Pressure Relief Cowls
CowlRef
PRC 500
PRC 800
PRC 1000
820
1300
1700
700
1050
1250
400
550
710
500
800
1000
1.2
3.0
5.0
A B C DOutlet volume (max)
@ 50 Pa(m3/s)
Weight(Kg)
24
40
68
C
A Square
D Square
B Square
Shutter Open
Shutter Closed
Balance Weight(adjustable)
All dimensions in millimetres
Dimensions and Weights
25
• Fast positive smoke extraction and pressurisation.
• Woods high efficiency, high temperature smoke venting
equipment using proven components.
• Extensively tested at high temperatures.
• Six temperature/time categories from 150°C to 600°C.
• Performance tested to BS848 (Part 1).
• Company quality registered to BS EN ISO 9001:94
• Products certified and witness tested by LPC (F.I.R.T.O) U.K.,
TÜ, (Germany) and CTICM (France).
• Pressure development to allow connection to ducted systems.
• Roof mounted units have fibreglass or aluminium cowls with
a pleasing appearance and giving excellent resistance to
atmospheric corrosion.
• High velocity discharge and dispersal.
• Optional spring loaded fusible link set to open roof unit shutters
at 72°C.
• Control panels available.
• Full range of ancillaries available.
Conculsion and Benefits
Fläkt Woods LimitedAxial Way, Colchester, Essex C04 5ZDTel 01206 222 555 Fax 01206 222 777email [email protected] www.flaktwoods.co.uk
See global website for international sales offices www.flaktwoods.com
Precise Air Management
Fläkt Woods is a globalleader in air management.We specialise in the designand manufacture of a widerange of air climate and airmovement solutions. Andour collective experience is unrivalled.
Our constant aim is to provide systems that precisely deliver requiredfunction and performance,as well as maximise energy efficiency.
Fans
Advanced axial, centrifugal andboxed fans for general and specialistapplications. Comprehensive rangeincluding high temperature andATEX compliant options. Engineeredfor energy efficiency and minimisedlife cycle cost.
Air Handling Units (AHUs)
Modular, compact and small AHU units. Designed to ensureoptimisation of indoor air quality,operational performance and service life.
Chillers
Air-cooled and water-cooled chillerswith cooling capacity up to 1800kW.Designed to minimise annual energy consumption in all types of build-ings.
Chilled beams
Active induction beams for ventilation, cooling and heating, and passive convection beams for cooling. For suspended or flush-mounted ceiling installation –and multi-service configuration.With unique Comfort Control andFlow Pattern Control features.
Solutions for all your air climate and air movement needs
Fläkt Woods is the only company in the UK capable of providing total system solutions from the following portfolio:
Smoke control and car parkventilation systems
Unique approach to car park ventilation, aided and optimised by Computational Fluid Dynamics(CFD) software. Complete turnkeysolutions for designing, installingand commissioning mechanical and natural smoke ventilation.
Controls and drives
Variable speed drives and controlsystems, all tested to ensure totalcompatibility with our products. Specialist team can advise on ener-gy saving and overall system integra-tion.
Technical Site Services