Fans in Fire SafetyPressurisation and Ventilation Equipment

Page 2: fire safety

2

Contents

Introduction

Applications

Smoke Control by Pressurisation

H.T. Series Smoke Venting

Control Equipment

Dimensions & Weights

3

4

5-7

8-17

18-19

20-24

Page:

Page 3: fire safety

3

Fläkt Woods Limtied (FW) are the acknowledged leaders in the specialised world of airmovement technology.

Over 100 years experience in designing and manufacturing air movement equipment has kept FWin the forefront of innovation, enabling the company to maintain their leadership in a sophisticatedand competitive market.

This long experience and expertise forms the basis for the range of fans and roof extract unitsdesigned specifically for the control and ventilaiton of fire smoke.

Fläkt Woods Limited are a company committed to Quality Assurance.

Registration to BS EN ISO 9001.94 means that FW design is quality assured as well as themanufacture. The commitment to quality doesn't stop with the hardware. The performance datacomes from standard tests carried out in FW's own laboratory which is BSI and AMCA approved.Woods fans can be bought with the confidence that they will achieve the published performance dataand match the assured quality essential in FIRE SAFETY SYSTEMS.

Two main areas of fire safety are detailed within this publication.

Smoke Control by PRESSURISATIONSmoke Control by VENTILATION

Further detailed information on Fan selections and specification can be obtained from Publication JM/SS or by contacting a Fläkt Woods Sales Centre.

Introduction

Page 4: fire safety

4

VENTILATION is used mainly in buildings with large open areas - Shopping Malls, SportsCentres, Car Parks, Department Stores etc.Smoke Ventilation systems are designed to:-

ApplicationsThere are basically two methods of Fire Smoke Control which utilise fans and fan equipment - PRESSURISATIONand VENTILATION.In any building fire smoke can be the major killer, and hence reliable smoke control systems can act both to save livesand assist fire fighting. Woods Fire Safety Fans are designed and tested for use in smoke control systems.

Smoke Control by PRESSURISATION

Stairwell Lobby Offices

Inlet

Duty/standbyfan unitsPressure

relief cowl

Pressurisation

Woods offer fans from their JM Aerofoil/Varofoil ranges for use on pressurisation supply systems, andtheir H.T. Series Bifurcated for Exhaust Systems, supported by Woods Technical Paper ref WTP41 - FansIn Fire Safety- Smoke Control By Pressurisation.

PRESSURISATION is often the preferred method ofsmoke control in buildings where the staircases, liftlobbies and corridors form part of the escape routes.i.e. high rise buildings with multiple occupants, Ho-tels, Offices and Residential Flats.Smoke Control using pressure differential is basedon two simple principles:-

Airflow can control smoke movement if the average VELOCITY is of sufficient magnitude

A PRESSURE differential across a barrier can act to control smoke movement.

These two principles form the basis for the designof pressurisation systems to control smoke move-ment, the details of which are outlined in the FireSafety in Buildings- Codes of Practice - BS5588 Parts 4 and 5.

Stairwell Pressurisation System Schematic

Fresh air flow

Floor

Ceiling

Smoke Control by VENTILATION

Ventilation

Smoke Ventilation fans are required to exhaust the hot fire smoke away from the building for givenperiods of time. Woods H.T. and JM H.T. Series smoke venting fans and roof extract units achievethis using simple designs and well proven components.

The application of the H.T. fan ranges are supported by two Woods Fans In Fire Safety technicalpapers ref WTP20 - Fans For Fire Smoke Venting and WTP 39 Regulations, Codes of Practice,System Reliability.

All H.T. Series fans and roof extract units are suitable for continuous operation at temperatures up to 50°Cmaximum and can therefore be used to provide the normal ventilation requirements of the building.

Keep the hot smoke above the escapingocccupant. Assist the fire brigade in fighting fire.Minimise damage to buildings and contents.Clear the residue smoke after fire has been extinguished.

Page 5: fire safety

5

Exhaust Fans - H.T. SeriesMost Woods H.T. Series Bifurcated fans areindependently tested and certified by T.U. -Munich to handle 600°C for 90 minutes - categoryG of BS7346 Part 2. This rating is above thatrecommended by most codes of practice.For additional information please refer to sectionon smoke venting equipment in this publication.

Pressure Relief CowlsWoods Pressure Relief Cowls provide aconvenient unobtrusive method of bleeding theexcess air from the staircase, necessary tomaintain 50 Pa with all doors closed. Based onthe Woods Colchester Range of roof extractunits, they are roof top mounted and generallyout of sight.

AncillariesGuards Bellmouth InletsMounting feet Vibration IsolatorsMatching flanges Pressure relief dampers/Flexible connectors CowlsAir operated dampers

Supply Fans - JM Aerofoils

Woods new JM Aerofoil fans meet all the re-quirements of Pressurisation Supply fans iden-tified in WTP41.

JM Aerofoils develop up to 15% more pressurethan more traditional aerofoil sections providingimproved stability and steeper performancecurves.(see opposite).

Blade pitch angles of JM Aerofoil fans can be sim-ply adjusted on site, allowing the air duty to bematched to site conditions (within motor limita-tions).

JM Aerofoils are lightweight. Their impellersare electronically balanced allowing their instal-lation into most structures.

This catalogue details only a small selectionfrom the JM Aerofoil range chosen to meetmost Pressurisation Supply fan duties. For fullproduct specification and performance see pub-lications C22a and C23a.

Supply Fans - Varofoil

Woods Varofoil - Variable Pitch in Motion fans areavailable to provide the supply air for a pressuri-sation system. The performance of the fan canbe automatically adjusted to match the require-ments of the system thereby reducing the size ofpressure relief dampers.Publication VF2010 details full information onWoods Varofoil range.

Supply Fans - standby

Fans can be mounted in either Series orParallel to provide 100% standby. Please consultWoods technical staff for advice on selection.

p sF

- FAN

STA

TIC

PRES

SURE

Pa

200

2

500

100

300

400

4 6 8 10 12 14qv VOLUME FLOW m3/s

016

80JM/25 - 1420 rev/min

30J - 1440 rev/min

Pressurisation Equipment

Page 6: fire safety

6

JM Aerofoils - Supply Air Fans

NotesFans detailed above are a small selection from the JM Aerofoil range, chosen to cover most Pressurisation System duties. They are not the only fans availableand alternatives may better suit the requirements of a particular system, see publication C22a, C23a or C1a.100 % standby can be provided by mounting JM Aerofoils in either series or parallel. Please Consult Woods technical staff for advise on fan selection.

40JM2840 rev/min

56JM

- 14

20 re

v/min

50JM2910 rev/min

63JM

- 14

20 re

v/min

71JM

- 14

20 re

v/min

80JM

- 14

40 re

v/min

90JM

- 14

50 re

v/min

100J

M -

1450

rev/m

in48

J - 14

80 re

v/min

2000

1000800

600

400

200

10080

60

40

20

Tota

l Pre

ssur

e Pa

.2 .4 .6 .8 1 2 4 6 8 10 20 40

Volume Flow Rate m3/s

m3/sec @ Pa 380-420 V / 50 Hz / 3φ

Code Speed

rev/min

dB(A)

@ 3m

Pitch Angle (°)min/max

0 50 100 200 300 400 500 MotorMotorRating

(kW)

Full LoadCurrent

(at 400 V)(A)

StartingCurrent

(at 400 V)(A)

40JM/16/2/5... 2840 8°32°

0.952.5

0.92.4

0.82.25

0.72.1

0.51.85

-1.6

BT9CT9

0.581.70

1.43.5

6.020.0

50JM/20/2/6... 2910 8°24°

2.04.2

1.94.1

1.84.0

1.63.8

1.53.6

1.43.4

CT9F2225

1.703.80

3.57.1

20.044.0

56JM/20/4/6... 1420 8°38°

1.44.0

1.33.2

0.73.0

BT9CT9

0.31.4

0.93.5

4.614.0

63JM/20/4/6... 1420 8°36°

1.85.6

1.65.3

1.34.6

CT5F2225

0.582.7

1.75.8

6.531.0

71JM/20/4/6... 1420 8°36°

2.88.4

2.68.0

2.27.3

1.66.3

CT9F2249

1.44.4

3.59.3

14.052.0

80JM/25/4/6... 1440 8°36°

4.010.8

3.810.5

3.09.6

2.08.0

F2245D132/18

2.16.3

4.712.8

30.065.0

90JM/25/4/6... 1450 8°32°

5.914.6

5.614.1

4.713.2

3.812.0

2.510.5

F2245D132/24

2.19.0

4.718.0

30.0100.0

1.02.6

2.14.3

1.54.2

2.06.0

3.18.8

4.211.2

6.215.2

6767

7773

6164

6769

6969

7275

7579

100JM/25/4/6... 1450 8°32°

7.021.0

8.020.0

7.018.5

6.017.5

4.515.5

3.513.5

F2249D160/26

4.417.0

9.333.0

52.0185.0

9.022.0

7883

48J 1480 8°31°

16.641.2

16.341.0

15.940.1

15.139.6

14.738.5

14.037.4

D160/LBKD200/57

25.065.0

44.0120.0

330.0790.0

17.041.6

8494

Performance Data

Page 7: fire safety

7

Bifurcated Fans - HT600/1.5B - Exhaust System Fans

Bifurcated fans must be sited away from the fire zone to ensure a supply of ambient air to motor compartment (50°C Max)

24JF - 1440 rev/min30JF - 1450 rev/min

19JF - 2900 rev/min

24KF - 2900 rev/min

19JF - 1440 rev/min

1500

1000800

600

400

200

1008060

40

20

10.5 .8 1 21.5 3 4 5 6 8 10 15

Fan

Total

Pre

ssur

e (Pa

)

Volume Flow (m3/s)

m3/sec @ Pa 380-420 V / 50 Hz / 3φ

Code Speed

rev/min

dB(A)

@ 3m

Pitch Angle (°)

min/max

0 50 100 200 300 400 500 600 MotorMotorRating

(kW)

Full LoadCurrent

(at 400 V)(A)

StartingCurrent

(at 400 V)(A)

19 JF 14408°28°

0.851.95

0.721.80

F2245CF2245C

1.01.0

2.42.4

14.014.0

19 JF 29008°28°

1.94.3

1.804.2

1.753.95

1.603.75

1.453.60

1.33.4

1.03.2

F2225CF2229C

2.55.5

5.611.1

38.090.0

24 JF 14008°28°

1.64.0

1.43.8

0.93.3

F2245CF2245C

1.02.2

2.45.0

14.030.0

24 KF 29508°28°

3.457.15

3.47.1

3.37.0

3.26.9

3.16.7

3.156.5

3.06.4

D132SCD160LC

5.518.5

10.934.8

65.0245.0

30 JF 14508°20°

2.56.4

2.36.1

1.85.7

1.15.0

F2245CF2249C

1.83.8

4.17.7

24.045.0

1.02.15

2.04.4

1.74.3

3.57.2

2.76.6

5862

7579

6569

8387

7375

Performance Data

Page 8: fire safety

8

Woods of Colchester Limited,have made Aerofoil fans suit-able for continuous operationin high temperature air streamsfor over 25 years. These fansare currently fitted into DryingMachines, and Smoke Ventingsystems, all over the world.

This long experience forms thebasis for the new range of H.T.SERIES fans and roof extractunits designed specifically forFire Smoke Ventilation.

Woods manufactures fan mo-tors, and is therefore able tolook critically at the require-ments of motor insulation, bear-

ings and lubricants which arevital elements in achieving hightemperature performance. Ex-tensive stress tests on fanimpellers for operation at hightemperatures has enabledWoods to make the best use ofexisting designs and materials.

A full high temperature test pro-gramme has been successfullycompleted. Some of these testswere carried out at independ-ent laboratories.

These tests, combined withWoods’ renowned high stand-ard of engineering and qualityassurance, serve to support

the H.T. Series specification.

Extensive market research hasresulted in the H.T. Series be-ing offered in six temperature/time categories. This addedflexibility enables a fan, or roofextract unit, to be selected tomatch the requirements of thesystem, ensuring the most costeffective installation.

The equipment detailed in thispublication is not the full rangeof items available. If the re-quirement is not included pleaseenquire to head office.

ROOF EXTRACTUNITS AVAILABLE

DVA & UDA

DVA & UDA

DVA & UDA

DVA & UDA

UDA

UDA

FAN TYPESAVAILABLE

AEROFOILBIFURCATED

VAROFOIL

AEROFOILBIFURCATED

VAROFOIL

AEROFOILBIFURCATED

VAROFOIL(†)

AEROFOILBIFURCATED

AEROFOILBIFURCATED

BIFURCATED

CATEGORYCODE *

H.T.150/2

H.T.200/2

H.T.300/0.5

H.T.300/1

H.T.400/2A

H.T.600/1.5B

CATEGORY

(†) Varofoil Fan - For Temperatures Above 250°C Please Enquire.* Add suffix "B" when Bifurcated fan is specified, eg. H.T.400/2B

TEMPERATURE(°C)

150

200

250

300

300

400

600

TIME(Hours)

2.0

2.0

2.0

0.5

1.0

2.0

1.5

Smoke Venting Equipment

Page 9: fire safety

9

Quality is assured at Woods. The H.T.SERIES is no e xception, thecompliance of Woods to BSEN ISO 9001.94 the inter nationalstandard f or Quality Assur anceconfirms this.

H.T. Series fans and roof extract unitshave successfully completed anextensive prog ramme of hightemperature tests in accordance withBS7346: Part 2: 1990, from 200 °C to600°C f or per iods v arying from 30minutes to two hours.

Some of these tests ha ve beenwitnessed by independent author itiessuch as the Loss Pre vention Council(F.I.R.T.O.) in the U.K., or under takenin independent labor atories atC.T.I.C.M. in F rance and TechnischeUniversität (T.Ü.) in Germany.

The H.T . Ser ies is cer tified andapproved for use in fire smoke ventingsystems.

Performance Testing

Page 10: fire safety

10

Aerofoil impeller, die cast inaluminium alloy. Componentsare X-ray inspected to ensurecompliance with standards.Categories H.T.400/2A:H.T.400/2B use either an alu-minium impeller or a speciallydesigned impeller fabricated insteel to provide stability at thehigher temperatures. TheH.T.600/1.5 uses the steelimpeller exclusively.Both impellers have a range ofblade angles and impeller so-lidity (number of blades) for flex-ibility of air duty. Impeller bladeangles are set and fixed atworks.

MotorsWoods H.T. Series fans utilisea totally enclosed squirrel cagemotor. The motor carcase isconstructed of either aluminiumalloy or cast iron dependent onthe temperature of operation.

The grades of motor insulationhave been selected to meet thespecific requirements of eachH.T. Category, as the essentialproperty of withstanding ther-mal shock is not common to allhigh temperature materials. Attemperatures above 400°C, bi-furcated fans with motor out ofthe air stream are the only reli-able solution.

Motor tests indicate than whennew, all motors used on WoodsH.T. Series fans have a safetymargin of an average of twicethe expected survival times, thisbeing based on Woods exten-sive test experience gainedduring the development of theirrange of specifications.

LubricationWoods H.T. Series fan motorbearings must be lubricated

Aerofoil FansFull technical data of the highlyefficient Woods Aerofoil Fanrange can be found in publica-tion C22a and C1a.

Aerofoil fan motors are rated tohandle the peak powers of thefans at both ambient and hightemperature. Aerofoil fanshave a safe non-overloadingcharacteristic. Two speedmotors available - please en-quire.

CasingsThe cylindrical casing, housingthe fan, is made of steel, hotdipped galvanised after manu-facture. It is flanged at each end.

S-Type - The casing surroundsthe impeller only and supportsthe motor mounting. The elec-trical terminal box is mountedon the motor. Suitable for tem-peratures up to 300°C.

L-Type - The casing completelysurrounds both the impeller andmotor. The terminal box ismounted on the casing and pre-wired at works.

Bifurcated - Simpler than theusual or split case fan, theWoods Bifurcated Aerofoil issimilar to a normal axial flow fan,but the motor is isolated from themain air stream in a tunnelwhich extends to one side of thefan casing. The motor is cooledby a cooling fan mounted on thetail end of the motor. An unob-structed supply of air at ambi-ent temperature of max 50 °Cmust be available to cool themotor, through the tunnel.

ImpellersFan categories H.T.150/2:H.T.300/0.5 and H.T.300/1mostly use the classic Woods

strictly in accordance with theinstructions on the motor name-plate.

The motor bearings andgreases used in the H.T. Serieshave been selected to providelong life at normal ambient tem-perature and still survive theemergency condition during thislife-time.

The special greases requiredfor fan motors operating above300°C are unsuitable for con-ventional relubricating methods- extended lubricators, greaseguns etc. Here the motor willneed to be dismantled andregreased at specified intervals.This does not apply to Bifur-cated Fans where the motor isseparated from the hot gases.

Electrical SuppliesH.T. Series fans are availablefor connections to 380 - 420 V/ 50 Hz / 3φ electrical supplies.For other voltages and frequen-cies - please enquire.

Bifurcated Aerofoil Fan

L-Type Aerofoil Fan

Specifications - Fans

Page 11: fire safety

11

FansThe DVA range is powered by theWoods Aerofoil fan described onpage 10. On an open inlet, abellmouth must be used to obtainthe specified performance. Twospeed motors are available -please enquire.

The UDA Unit• 9 Unit Sizes 300 mm to

2000 mm.• Volume Flow up to 45 m3/s.

• Air Pressure up to 1000 Paavailable

Unit ConstructionThe unit base is constructed fromsheet steel, hot dipped galvanisedafter manufacture. The windshieldand air operated shutters, designedto prevent the ingress of rain orsnow, are manufactured fromaluminium.

FansThe UDA range is powered by theWoods Aerofoil fan described onpage 10. On an open inlet, abellmouth must be used to obtainthe specified performance. Twospeed motors are available -please enquire.

DVA Roof Unit

UDA Roof Unit

Ancillaries - Fans and Roof Extract Units

All standard steel ancillaries e.g.Mounting Feet, Bellmouth Inlets,Matching Flanges, Wire Guardsetc., are suitable for 600°C,

Aerofoil dampers are limited to400°C.

Upstream Guidevane Units ie GJtype fans with aluminium impellers

- Suitable for operation up to 400°C (See page 8 for time categories)

can be used up to 300°C, providingthe impeller is suitable for thistemperature.

Flexible Connector - Silicon coatedglass fibre fabric.

Vibration Isolators - Spring typeare available for all fans.

The DVA Unit - Suitable for operation up to 300°C (See page 8 for time categories)

• 5 Unit Sizes 400 mm to1000 mm.

• Volume Flow up to 10 m3/s.

• Air Pressure up to 500 Paavailable

Unit ConstructionWeathershield and base in stronglightweight glass re-inforcedpolyester resin rendered fireretardent to BS476: Part 7 Class 2.

Standard colour is to BS4800:08B/21.

The cowl is secured to the mountingbrackets by stainless steel screws.Air operated, anti-backdraughtshutters are fitted as standard.

Specifications - Roof Extract Units

Page 12: fire safety

12

Category - HT150/2; HT200/2; HT300/0.5; HT300/1

Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection ofpopular fans are detailed in thispublication. Please enquire foralternative pitch angles andspeeds.

2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.

45JM2910 rev/min

31JM2840 rev/min

50JM - 2910 rev/min56JM - 2910 rev/min

63JM - 2910 rev/min

56JM

- 14

20 re

v/min

63JM

- 14

40 re

v/min

71JM

- 14

40 re

v/min

80JM

- 14

40 re

v/min

90JM

- 14

40 re

v/min

100J

M -

1470

rev/m

in

48J - 1480 rev/min

60J -

975

rev/m

in

75J1/2975 rev/min

2000

1000800600

400

200

10080

60

40

20

10

Tota

l Pre

ssur

e Pa

.1 .2 .4 .6 .8 1 2 4 6 8 10 20 40

Volume Flow Rate m3/s

80

Code MotorMotor Rating

(kW)Speedrev/min

Pitch angle(max.)

31JM/16/2/5... 10.9

28402840

40°40°

5.74.6

29102910

40°40°

5.74.6

29102910

32°28°

22°18°

2.51.75

14201420

40°40°

22 2910 36°

63JM/25/4/9... 4.24.6

14401440

40°40°

71JM/25/4/9... 6.3 1440 36°

75J1/2 37 725 26°

45JM/20/2/6...

50JM/20/2/6...

56JM/20/2/6... 5.74.6

29102910

56JM/20/4/6...

63JM/25/2/6...

80JM/25/4/9... 10 1440 36°90JM/25/4/9... 17.3 1440 36°

100JM/25/4/9... 25 1470 36°48J 54 1480 26°

60J 45 975 24°

CT5 (†)D80/A

F2229B (†)D112/M

F2245B (†)D90/LN

DF160/L

F2249B (†)D112/M

DF132/MS

DF250/MG

F2229B (†)D112/M

F2229B (†)D112/M

DF132/M

DF160/L

DF160/LBKDF225/M

DF250/MG

(†) - Not suitable for category HT300/1

Aerofoil Fans

Page 13: fire safety

13

Category - HT150/2; HT200/2; HT300/0.5; HT300/1

Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection ofpopular fans are detailed in thispublication. Please enquire foralternative blade pitch angles andspeeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.3. When selecting aerofoilfans for use in Roof Extract Unitsallow for the following overallstatic pressure losses through theunit:-

Type UDA - 1.0 x fan velocitypressure. (Plus any inlet ductsystem resistance).

TYPE UDA

.1 .2 .4 .6 .8 1 2 4 6 8 10

40

60

80100

Stat

ic P

ress

ure

Pa

Volume Flow Rate m3/s

200

400

600

800

20

1020 40

UDA 7601440 rev/min

UDA 3002840 rev.min

UDA 3802840 rev/min

UDA 4802910 rev/min

UDA 9601470 rev/min

UDA 6001440 rev/minUDA 480

1420 rev/min

60

UDA 1220 - 1480 rev/min

UDA 1600 - 975 rev/min UDA 2000 - 725 rev/m

in

1500

1000

Code Fan RefMotor Rating

(kW)Speed

rev/minPitch angle

(max.)

UDA 300 31JM31JM

1.00.9

28402840

40°40°

UDA 38040JM40JM

UDA 480

50JM50JM

5.74.6

29102910

32°28°

50JM50JM

1.30.9

14201420

40°40°

UDA 60063JM 22.0 2950 36°63JM63JM

4.24.6

14401440

36°36°

UDA 760 80JM 10.0 1440 36°

UDA 960 100JM 25.0 1470 36°

UDA 1220 48J 52.0 1480 26°

UDA 1600 60J 55.0 975 29°

UDA 2000 75J1/2 37.0 725 26°

CT5 (†)D80/A

F2229B (†)D112/M

CT9 (†)D80/B

DF160/L

F2249B (†)D112/M

DF132/M

DF160/LBK

DF225/M

DF250/M

DF250/MG

1.70.9

28402840

32°18°

CT9 (†)D80/A

(†) - Not suitable for category HT300/1

Roof Extract Units

Page 14: fire safety

14

Category - HT150/2; HT200/2; HT300/0.5; HT300/1

Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection ofpopular fans are detailed in thispublication. Please enquire foralternative blade pitch angles andspeeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.3. When selecting aerofoilfans for use in Roof Extract Unitsallow for the following overallstatic pressure losses through theunit:-

Type DVA - 0.2 x fan velocitypressure. (Plus any inlet ductsystem resistance).

(†) - Not suitable for category HT300/1

TYPE DVA

1000

.1 .2 .4 .6 .8 1 2 4 6 10

40

60

80

100

Stat

ic P

ress

ure

Pa

Volume Flow Rate m3/s

200

400

600

800

20

1020

DVA 4002840 rev/min

DVA 5002840 rev/min

DVA 6302910 rev/min

DVA 6301420 rev/min

DVA 8001440 rev/min

DVA 10001440 rev/min

Code Fan Ref. Motor Rating(kW)

Speedrev/min

Pitch angle (max)

DVA 400 31JM CT5 (†) 1.0 2840 40° 31JM D80/A 0.9

DVA 500

DVA 630

50JM F2229/B(†) 5.72910

32° 50JM D112/M 4.6 28° 50JM CT9 (†) 1.3

1420 40° 50JM D80/B 0.9

DVA 800 63JM F2249/B(†) 4.2

1440 40° 63JM D112/M 4.6

DVA 1000

2840

2910

1420

1440

40°

40°

40°

1440 80JM DF132/M 10.0 36°

40JM CT9 (†) 1.7 2840 32° 40JM D80/A 0.9 2840 18°

Roof Extract Units

Page 15: fire safety

15

Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection of popularfans are detailed in this publication.Please enquire for alternative bladepitch angles and speeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.

Category - HT400/2

Code Motor Motor Rating(kW)

Speedrev/min

Pitch angle (°)(max.)

50JM/20/4/6... D80/B 0.75 1420 36°56JM/20/4/6... D90/LN 1.5 1420 40°63JM/25/4/9... DF112/M 4 1440 40°71JM/25/4/9... DF132/MS 5.5 1440 36°80JM/25/4/9... DF160/LM 11 1440 36°90JM/25/4/9... DF160/LAK 18.5 1440 36°

100JM/25/4/9... DF160/LBK 21 1470 32°48JF60JF

D225/MD250/M

40.540.5

1470975

20°20°

56JM

- 14

20 re

v/min

63JM

- 14

40 re

v/min

71JM

- 14

40 re

v/min

80JM

- 14

40 re

v/min

90JM

- 14

40 re

v/min

100J

M -

1470

rev/m

in

48JF1470 rev/min

60JF

- 97

5 re

v/min

50JM

- 14

20 re

v/min

2000

1000800

600

400

200

10080

60

40

20

10

Tota

l Pre

ssur

e Pa

.1 .2 .4 .6 .8 1 2 4 6 8 10 20 40

Volume Flow Rate m3/s

80

Aerofoil Fans

Page 16: fire safety

16

Category - HT400/2A

Notes:-1. Most Woods Aerofoil Fanscan be built to the H.T. Seriesspecification. A selection of popularfans are detailed in this publication.Please enquire for alternativeblade pitch angles and speeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.3. When selecting aerofoilfans for use in Roof Extract Unitsallow for the following overallstatic pressure losses through theunit:-

Type UDA - 1.0 x fan velocitypressure. (Plus any inlet ductsystem resistance).

4. For this category L-typeAerofoil fans only are available.

TYPE UDA

Code Fan Ref. Motor Rating(kW)

Speedrev/min

Pitch angle (max.)

UDA 380 15J D90/LN 2.2 2850 36°

UDA 480 19JF D112/M 4.0 2900 24° 50JM D80/B 0.75 1420 36°

UDA 600 24KF D160/LMB 15.0 2900 28° 63JM DF112/M 4.0 1440 40°

UDA 760 80JM DF160/LM 11.0 1440 36°UDA 960 100JM DF160/LBK 21.0 1470 32°UDA 1220 48JF D225/M 40.5 1470 20°UDA 1600 60JF D250/M 40.5 975 20°

UDA 3802850 rev/min

.2 .4 .6 .8 1 2 4 6 8 10

40

60

80100

Stat

ic P

ress

ure

Pa

Volume Flow Rate m3/s

200

400

600

800

20

1020 40

UDA 7601440 rev/min

UDA 9601470 rev/min

UDA 6001440 rev/minUDA 480

1420 rev/min

60

1500

1000

UDA 4802900 rev/min UDA 600

2900 rev/min

UDA 1220 - 1440 rev/min

UDA 1600 - 975 rev/min

Roof Extract Units

Page 17: fire safety

17

Category - HT400/2B; HT600/1.5B

Notes:-1. Most Woods Bifurcated Fanscan be built to the H.T. Seriesspecification. A selection of popularfans are detailed in this publication.Please enquire for alternative bladepitch angles and speeds.2. The performance curvesshown are examples of the rangeof fans available. Fully specifiedquotations for single or two speedfans will be supplied upon request.3. Bifurcated fans must be sitedaway from the fire zone to ensure asupply of ambient air to motorcompartment (50°C Max).

24JF - 1440 rev/min30JF - 1450 rev/min

19JF - 2900 rev/min

24KF - 2900 rev/min

38JF - 1450 rev/min

44JF

- 146

0 rev

/min

48JF - 1460 rev/min

19JF - 1440 rev/min

1500

1000800

600

400

200

1008060

40

20

10.5 .8 1 21.5 3 4 5 6 8 10 15 20 30

Fan

Tota

l Pr

essu

re (P

a)

Volume Flow (m3/s)

F2229C F2245C

F2245C F2249C D180LD

D160LC

Code Motor Speedrev/min

Pitch angle(max.)

19JF 2900 28°1440 28°

24JF 1440 28°30JF 1450 20°38JF 1450 28°44JF D200LD 1460 20°48JF D225MD 1460 20°

Motor Rating(kW)

5.51.0

2.23.8

22.030.045.0

24KF 2900 28°18.519JF

Bifurcated Fans

Page 18: fire safety

18

An essential part of any SmokeVenting system is its control gear.Woods offer the following controlsystem variations with the H.T.Series Fans and Roof ExtractUnits on Fire Safety Systems.

1 Emergency Extract Only: Type ESS. Type ESS/SD Star Delta

2 Normal Ventilation/ Emergency Extract Starter: (Single Speed Units) Type EDSS/D.O.L. Type EDSS/SD Star Delta.

3 Two Speed Starter/High Speed Emergency Extract: (Two Speed Units) Type EDSS/DW Dual Wound. Type EDSS/PC Pole Change.

the control circuits.

If control circuit supply fails or isdisconnected by sensors, panelwill switch to emergency extract.

Control circuits are shown suitablefor connection to 220-240 voltsingle phase supply. Other controlcircuit voltages are available. Toensure that control panels interfacecorrectly with smoke detectors,please advise details of smokedetectors to be used. Note: Smokedetectors and remote emergencybuttons are not supplied with thecontrol panel. If fitted, overheatprotectors in motor windings andany other motor protection device,must be by-passed in emergency.

In emergency conditions fans canbe started in one of three ways:

a) Using emergency button mounted on control panels.b) By automatic smoke detectors.c) By using manual remote emergency buttons.

Electrical SupplyThree Phase Panels require asustained three phase supply plusneutral, wired with fire resistantcable and a separate single phasesupply for the control circuits.

Single Phase Panels requiresustained single phase supplywired with fire resistant cable anda separate single phase supply for

EmergencyExtract Only(Single Speed)Fans/control operated inemergency conditions only.

Panel Ref:ESS D.O.L StartingESS/SD Star/Delta Starting

(Automatic)

Starter/EmergencyExtract(Single Speed)For normal ventilation panelfunctions as a standard manualstarter switching to permanentoperation in emergency.

Panel Ref:EDSS D.O.L StartingEDSS/SD Star/Delta Starting

(Automatic)

N L1 L2 L3L N

L N

U V W

C1 EmergencyOn

RLA1(a)

To fan motor(fire resistant cable)

DoorLockIsolator

Sustained supply(fire resistant cable)

Separate single phase supply

(control circuit)

Smoke Detector(s)(normally closed contact)

Remote EmergencyPush Switch (if fitted)

EmergencyStart

Fuse

DL

C1

THREE PHASE ESS PANEL

RLA1

N L1 L2 L3L N

N

C1 EmergencyOn

RLA1(a) RLA1

To fan motor(fire resistant cable)

DoorLock

Isolator

Sustained supply(fire resistant cable)

THREE PHASE EDSS PANEL

Separate single phase supply

(control circuit)

Smoke Detector(s)(normally closedcontact)

Remote EmergencyPush Switch (if fitted)

EmergencyStart

Fuse

DL

C1C2

C2

Start

Stop

Reset

Fan Run

U V W

L

OverloadRelay

Control Equipment

Page 19: fire safety

19

Power switching circuit forEDSS/PC control panel (direct online starting).

Using two speed motors fornormal ventilation using eitherspeed, panel functions as a D.O.L.starter, switching to high speed inemergency conditions.

Panels can be supplied for usewith two speed dual wound or polechange motors.

Panel Ref:EDSS/DW Two speed dual

wound motorsEDSS/PC Two speed pole

change motors

D.O.L. starting both speeds isstandard.

Automatic Star/Delta starting canbe supplied with EDSS/DW panels,please enquire.

Power switching circuit forEDSS/DW control panel (direct online starting).

Control circuit for EDSS/PC andEDSS/DW control panels (directon line starting).

All Woods smoke venting controlgear is housed in sheet steelenclosures to IP44 and have thefollowing standard features:

• Door Lock Isolator• Indicator Lights• Panels supplied with

removable gland plates

Panel construction & dimensions

C1

CBA

C2

Start

ResetHGF

D

Run

O/L Aux O/L Aux

Off

LowSpeed

High Speed

C1 C2

High Speed Low SpeedJ

C1

C2

Run

1W1V1U2W2V2U

Reset

N L1 L2 L3

L N

L N

F G H

Emergency'on' Light

RLA1(A)

DoorLockIsolator

Sustained Supply(Fire Resistant Cable)

Separate single phase supply(control circuit)

Smoke Detector(s)(normally closedcontact)

Remote EmergencyPush Switch (if fitted)

EmergencyStart

Fuse

C4

C4

C B A

J

RLA1(A)

C4 AUX NCRLA1

DEDL

Control Panel Dimensions

C1

CBA

C2

StartResetHGF

D

Reset

Run

O/L Aux

O/L Aux

Off

LowSpeed

High Speed

C2

JC1

C2

Run

E

C4 Aux. No.

C3

C3

C3Aux.

High Speed Low Speed

1W1V1U2W2V2U

C3Aux.

C1

All dimensions in millimetres

Model Rating (kW) A B C

ESS 4,5.5,9,11 215 215 150ESS 22 & 37 240 420 240EDSS 4 & 5.5 215 215 150

EDSS 9 & 11 240 300 150EDSS 22 & 27 240 420 240

A C

B

Control Equipment (continued)

Page 20: fire safety

20

Aerofoils (L Type)

Note : For vertical mounting details of 48J and 60J - please enquire

CodeMotorFrame

DIMENSION REFERENCE (mm) Weight(kg)A B C D E G H K L M N P S T

31JM8

40JMBT9CT5

400400

480480

375375

279279

2.52.5

225225

450450

289289

350350

400400

1010

250250

88

1212

45JM F2229 450 530 520 306 3 255 500 434 400 450 10 280 8 12

71JM

263055

303030

V

80JM

90JM

100JM

CT5 315 395 375 235 2.5 175 355 289 265 315 10 200 108 2730

50JM

CT9F2225F2229

500500500

594594594

375520520

338338338

2.533

290290290

560560560

289434434

450450450

500500500

101010

315315315

121212

121212

345465

303030

56JM

BT9CT9F2245F2229

560560560560

654654654654

375375520520

368368368368

2.52.533

330330330330

620620620620

289289434434

510510510510

560560560560

10101010

355355355355

12121212

12121212

34385667

50505050

63JM

CT5F2225F2249

630630630

724724724

375520520

403403403

333

375375375

690690690

289434434

580580580

630630630

101010

400400400

121212

121212

527081

505050

CT9 710 804 375 443 3 415 770 259 660 710 10 440 16 12 5450F2249 710 804 520 443 3 415 770 404 660 710 10 440 16 12 8550

710 804 415 770 660 710 10 440 16 12 50404480 147DF132 520 4

F2249D132

800800

894894

520520

488525

35

485485

860860

404404

750750

800800

1010

510510

1616

1212

94163

5050

800 894 485 860 750 800 10 510 16 12 50404525 194DF132 520 5F2245 900 1006 520 538 3 491 970 444 850 900 10 518 16 15 8850D132 900 1006 520 575 5 491 970 444 850 900 12 518 16 15 18350

900 1006 491 970 549 850 900 12 518 16 15 50575 280DF160 625 5

F2249 1000 1106 520 588 3 547 1070 444 950 1000 10 574 16 15 10750D160 1000 1106 625 625 5 547 1070 539 950 1000 12 574 16 15 26850

1000 1106 547 1070 549 950 1000 12 574 16 15 50625 317DF160 625 5

D160/LBK 1219 1357 711 753 5 - 1289 574 1143 1219 14 737 20 18 28786D200/57 1219 1357 914 753 6 - 1289 777 1143 1219 14 737 20 18 56286

1219 1357 - 1289 674 1143 1219 14 737 20 18 86753 638D225/M 813 648J

D225/M 1524 1694 813 910 6 - 1626 674 1422 1524 14 921 12 18 67687D250/M 1524 1694 914 910 6 - 1626 775 1422 1524 14 921 12 18 90487

D250/M

60J

75J 1/2 please enquire

315 395 175 355 289 265 315 10 200 10 30235 31D80 375 2.5

450 530 255 500 434 400 450 10 280 8 12 30306 72DF112 520 3

500 594 290 560 434 450 500 10 315 12 12 30338 77DF112 520 4

560560

654654

330330

620620

434434

510510

560560

1010

355355

1212

1212

5050

368368

5880

D90DF112

520520

34

630630

724724

375375

690690 529

580580

630630

1010

400400

1212

1212

5050

434403440

96234DF160

DF112 520625

44

C

ØB

O

VE

R F

LA

NG

ES

ØA

IN

SID

E

E

GUARDS OPTIONAL

AIRFLOW

FORM B

AIRFLOW

FORM A

K CRS

DF132,D160,DF132,DF160 FRAMES40 DIA. HOLES FOR CONDUIT.2 EACH SIDE SUITABLE FOR PG29 OR 1.5"BT,CT,F22,D80,D90,DF112 FRAMES23 DIA. HOLES FOR CONDUIT.2 EACH SIDE SUITABLE FOR CM20 OR PG16

S No. OF HOLES T DIA.EQUISPACED ON H PCD.

L CRS

M

SIGHT PORT

DP

BT,CT,F22,D80,D90,DF112 FRAMES1 HOLE 20 DIA. (END OF BOX) TO SUIT CM16 OR PG11 GLAND FOR AUXILIARY CABLES

G

FOOT POSITION FOR VERTICAL MOUNTING

VLENGTH OF GUARD31JM TO 100JM - 137mm48J & 60J - 212mm

IMPERIAL SIZEST/Box D160,D180,D200,D225 FRAMES2-HOLES TAPPED PG29OTHER SIZES AVAILABLE TO ORDER

Dimensions and Weights

Page 21: fire safety

21

Bifurcated Fans

Type I

Type II

ATTACHABLE FEETTHICKNESS Q

235 S No. OF HOLESØT ON H P.C.D.

SLOTS IN FEET ØN

M

L crs.

AIRFLOW

FORM B

C

G

DP

= K crs. =

ØB

ØA

E

F

HOLE ØJ

AIRFLOW

FORM B

DP

E

F HOLE ØJ

ØA

ØB

C

= K crs =

G

S No. OF HOLES ØT ON H P.C.D.

L crs.

MSLOTS INFEET ØN ATTACHABLE FEET

THICKNESS Q

All dimensions in millimetres

Code Motor Type A B C D E F G H K L M N P Q S TWeight

(Kg)

19JFF2225/45F2229

II

483483

592592

787787

408408

66

376431

366366

541541

692692

438438

483483

1111

311311

33

88

1414

100112

24JF F2245 II 610 699 616 427 3 360 385 668 502 559 610 11 381 3 12 14 108

24KFD132D160LC

II

610610

721721

10501050

540578

66

495550

498493

668668

930930

559559

610610

1111

381381

33

1212

1515

210250

30J F2249 II 762 851 660 503 5 460 461 821 542 711 762 11 483 5 12 14 147

30JF F2245 II 762 851 660 503 5 405 461 821 542 711 762 11 483 5 12 14 135

38JF D180LD II 965 1103 1000 689 5 565 604 1035 863 914 965 14 597 6 16 19 400

44JF D200LD II 1120 1258 1100 768 6 604 683 1190 958 1070 1120 14 710 6 20 15 520

48JF D225MD II 1219 1361 1250 827 12 705 736 1289 1099 1143 1219 14 737 6 20 19 750

Dimensions and Weights

Page 22: fire safety

22

DVA400 AND DVA500 - 4 OFF M8 FIXINGS ON CENTRE LINES FOR UNIT SKIRT

DVA630 TO DVA1000 - 8 OFF M8 FIXINGS ON J CENTRES FOR UNIT SKIRT

8 OFF M8 FIXINGS FOR DUCT

MOUNTING PLATE

ROOF CURB (PLAN)

J cr

s.

F s

q.

E s

q.

G c

rs.

H c

rs.

72

C

’S' TYPE FAN ASSEMBLYSHOWN THIS SIDE

A sq.

SPACER DUCT

B sq.

D

'S' TYPE FAN

CUSTOMER'SDUCTING

’L' TYPE FAN ASSEMBLYSHOWN THIS SIDE

'L' TYPE FAN

DVA Roof Units

All dimensions in millimetresAll dimensions and weights shown are for L type fans.

Unit Code Fan Ref A B C D E F G H JMax Weight

Less fan(Kg)

With fan

DVA 40031JM31JM

CT5D80/A

600600

530530

480480

783783

550550

400400

210210

460460

--

1818

4549

DVA 50040JM40JM

700700

630630

530530

650650

500500

260260

560560

--

2424

DVA 630

50JM50JM50JM50JM

CT9D80/BF2229/BD112/M

900900900900

780780780780

630630630630

933107810781078

850850850850

700700700700

360360360360

740740740740

400400400400

47474747

8186

112124

DVA 80063JM63JM

F2249/BD112/M

10501050

950950

750750

11981198

10001000

800800

400400

886886

400400

6565

146161

DVA 1000 80JM DF132/M 1250 1180 880 1328 1200 1000 300 1080 500 96 259

CT9D80/A

833833

5456

Dimensions and Weights

Page 23: fire safety

23

B sq.

'L' TYPE FAN

'S' TYPE FAN

BIRD GUARD(OPTIONAL)

D

CE

A sq.

K

H c

rs.

J cr

s.

G s

q.

ROOF CURB (PLAN)

L No. OF HOLES Ø12

K

J cr

s.

’L' TYPE FAN ASSEMBLYSHOWN THIS SIDE

CUSTOMER'S DUCTING

’S' TYPE FAN ASSEMBLYSHOWN THIS SIDE

UDA Roof Units

All dimensions in millimetres

Unit Code Fan Ref A B C D G H J K L Max WeightLess fan

(Kg)With fan

UDA 30031JM31JM

CT5D80/A

600600

530530

302302

627627

400400

--

245245

7575

44

10.910.9

37.941.9

UDA 38040JM40JM15J D90/L

700700700

628628628

344344344 700

500500500

340340340

288288288

757575

888

14.214.214.2 58.2

UDA 480

50JM50JM50JM50JM50JM19JF

F2229BD112/MCT9D90D80/BD112/M

850850850850850850

743743743743743743

398398398398398398

868868723868723856

600600600600600600

400400400400400400

350350350350350350

757575757575

888888

18.418.418.418.418.418.4

83.493.452.477.457.485.4

UDA 600

63JM63JM63JM63JM24KF

DF160/LF2249BD112/MDF112/MD160/LMB

10501050105010501050

879879879879879

398398398398398

973868868868

1059

800800800800800

490490490490490

450450450450450

100100100100100

88888

28.828.828.828.828.8

243.8109.8117.8117.8223.8

UDA 76080JM80JM

DF132/MDF160/LM

12501250

10481048

434434

9041009

10001000

680680

550550

100100

1212

5050

244279

UDA 960 100JM DF160/LBK 1450 1276 534 1109 1200 880 650 100 12 122 760

UDA 1220 48J D225/M 1750 1585 665 1529 1500 1120 800 100 12 122 760

UDA 1600 60J D250/M 2272 2026 706 1585 2000 1440 1050 100 12 409 1321

UDA 2000 75J 1/2 D250/M 2672 2438 749 1628 2400 1800 1250 100 12 545 Enq

CT9D80/A

669669

44.246.2

Dimensions and Weights

Page 24: fire safety

24

Pressure Relief Cowls

CowlRef

PRC 500

PRC 800

PRC 1000

820

1300

1700

700

1050

1250

400

550

710

500

800

1000

1.2

3.0

5.0

A B C DOutlet volume (max)

@ 50 Pa(m3/s)

Weight(Kg)

24

40

68

C

A Square

D Square

B Square

Shutter Open

Shutter Closed

Balance Weight(adjustable)

All dimensions in millimetres

Dimensions and Weights

Page 25: fire safety

25

• Fast positive smoke extraction and pressurisation.

• Woods high efficiency, high temperature smoke venting

equipment using proven components.

• Extensively tested at high temperatures.

• Six temperature/time categories from 150°C to 600°C.

• Performance tested to BS848 (Part 1).

• Company quality registered to BS EN ISO 9001:94

• Products certified and witness tested by LPC (F.I.R.T.O) U.K.,

TÜ, (Germany) and CTICM (France).

• Pressure development to allow connection to ducted systems.

• Roof mounted units have fibreglass or aluminium cowls with

a pleasing appearance and giving excellent resistance to

atmospheric corrosion.

• High velocity discharge and dispersal.

• Optional spring loaded fusible link set to open roof unit shutters

at 72°C.

• Control panels available.

• Full range of ancillaries available.

Conculsion and Benefits

Page 26: fire safety

Fläkt Woods LimitedAxial Way, Colchester, Essex C04 5ZDTel 01206 222 555 Fax 01206 222 777email [email protected] www.flaktwoods.co.uk

See global website for international sales offices www.flaktwoods.com

Precise Air Management

Fläkt Woods is a globalleader in air management.We specialise in the designand manufacture of a widerange of air climate and airmovement solutions. Andour collective experience is unrivalled.

Our constant aim is to provide systems that precisely deliver requiredfunction and performance,as well as maximise energy efficiency.

Fans

Advanced axial, centrifugal andboxed fans for general and specialistapplications. Comprehensive rangeincluding high temperature andATEX compliant options. Engineeredfor energy efficiency and minimisedlife cycle cost.

Air Handling Units (AHUs)

Modular, compact and small AHU units. Designed to ensureoptimisation of indoor air quality,operational performance and service life.

Chillers

Air-cooled and water-cooled chillerswith cooling capacity up to 1800kW.Designed to minimise annual energy consumption in all types of build-ings.

Chilled beams

Active induction beams for ventilation, cooling and heating, and passive convection beams for cooling. For suspended or flush-mounted ceiling installation –and multi-service configuration.With unique Comfort Control andFlow Pattern Control features.

Solutions for all your air climate and air movement needs

Fläkt Woods is the only company in the UK capable of providing total system solutions from the following portfolio:

Smoke control and car parkventilation systems

Unique approach to car park ventilation, aided and optimised by Computational Fluid Dynamics(CFD) software. Complete turnkeysolutions for designing, installingand commissioning mechanical and natural smoke ventilation.

Controls and drives

Variable speed drives and controlsystems, all tested to ensure totalcompatibility with our products. Specialist team can advise on ener-gy saving and overall system integra-tion.

Technical Site Services

Our dedicated team providing comprehensive post-installationservices. Including condition-based contract monitoring, preventative androutine maintenance, refurbishmentand system upgrades.

Fläkt Woods operates a policy of continuous development and improvement. Accordingly, the Company reserves the right to supply products thatmay differ from those illustrated and described in thispublication. Certified dimensions will be supplied onrequest on receipt of order. FW