Fire Damper
FD25FIRE DAMPER
All possible combinations of width and height are available. Standard dimensions are avaliable with increments of 50mm.
Min. dimensions B(W) x H [mm]
Max. dimensions B(W) x H[mm]
200x200 800x600
350
2
3
4
5
B
250
3030
30
120
30
H
6
1
• Fire resistance according to EN 1366-2, classified according to EN 13501-3, Declaration of performance given according to Anex III of Regulation No 305/2011
• Rigid wall: EI 90 (ve, i↔o)S• Flexible wall: EI 90 (ve, i↔o)S• Ceiling / floor: EI 120 (ho, i↔o)S
• Used for the isolation of duct penetrations between fire com-partments.
• Fire dampers consist of housing, fire-resistant damper blade and release mechanism.
• Casing made of galvanised sheet steel, damper blade made of special insulating material, damper blade shaft and push rod made of stainless steel, plastic plain bearings made of brass, seals made of polyurethane and elastomer.
FIRE DAMPER FD25
FIRE PROTECTION
DAMPER MODELS
FD25-M rectangular fire damper with electric actuator.
• thermoelectric activation (72°C) with electric actuator and re-turn spring
• integrated end switches • fully automatic operation• networking capability (MP-BUS, LonWorks, AS-i BUS)
Options: M230 – electric actuator AC 230V M24 – electric actuator AC/DC 24V
DIMENSIONS
fire damper housingdamper bladeelectric actuator: Belimo BLFthermo-electric tripping device (72°C)smoke sealintumescent strip
123456
Design changes reserved01
FIRE DAMPERS - FD25
s>80
Fire damper FD25 is suitable for installation in all types of rigid, flexible walls and ceilings. Installation should be performed according to the installation instructions provided by the manufacturer.
Installation steps:
1. Wall opening H(B)+160mm 2. Damper fixing (damper blade should be in a closed position during installation!) 3. Fill the gap between damper and wall with mortar
INSTALLATION IN RIGID WALL
standard gypsum plaster
During installation use wooden struts toprevent deformation of casing, caused by drying gypsium plaster.
z
137 Opening in the wall: (B+160) x (H+160)
Masterboard thickness 20mm
200
After installation check for damper blade mobility, preform an opening and closing test.
FIRE DAMPERS - FD25
02Design changes reserved
INSTALLATION IN FLEXIBLE WALL
INSTALLATION IN CEILING
120
z>125
200
s≥80
standard gypsum plaster
gypsum plasterboards (thickness 12,5mm)
mineral wool (density 50kg/m3)
CW metal profile
screw for gypsum plasterboard
Opening in the wall: (B+160) x (H+160)
Masterboard thickness 20mm
137
After installation check for damperblade mobility, perform an opening andclosing test.
s>80
021521>z
200
Opening in the wall: (B+160) x (H+160)
Masterboard thickness20mm
standard gypsum plaster
731
After installation check for damperblade mobility, preform an opening andclosing test.
Design changes reserved03
FIRE DAMPERS - FD25
SELECTION DIAGRAM
The values of total pressure loss for other sizes are obtained in a manner that read value from the graph is multiplied with the correc-tion value from the table. Value of sound power are obtained in a manner that read value is added the correction value from the table.
B [mm] 200 250 300 350 400 450 500 550 600 650 700 750 800
∆pt x 1,22 1,14 1,07 1,0 0,94 0,88 0,83 0,77 0,73 0,68 0,64 0,6 0,58
Lwa+ -1 -1 0 0 0 0 0 0 0 0 1 1 2
ORDERING KEY
Symbol: v ∆pt LWA
- air velocity in the duct [m/s]- total pressure loss [Pa]- sound power level [dB(A)]
Total pressure loss and sound power level for B=400:
FD25 400x300 M230 S G1- - --
Damper typeDamper dimensions B(W) x H [mm]
Mechanism type:R - manual mechanismE230 - solenoid actuator AC230VE24 - solenoid actuator AC 24VM230 - electric actuator AC230VM24 - electric actuator AC/DC 24VOptions:s - electric limit switches (indicating damper “OPEN” and “CLOSED”)z - electric limit switch (indicating damper “CLOSED”)o - electric limit switch (indicating damper “OPEN”)Grille:G1 - grid on one sideG2 - grid on both sides
FIRE DAMPERS - FD25
04Design changes reserved
BELIMOBLF230
OPERATING INSTRUCTIONS
Damper is delivered in closed position. When electric actuator is connected to the power supply damper will open. When the damperreaches the end position (damper open), in which is it blocked, the electromotor will stop. Closing fire damper takes place automati-cally when a power failure occurs. Thermal tripping device that comes with fire damper causes power circuit break at a temperatureof 72 °C (inside or outside duct). If checking is needed for proper fuctioning of fire damper, pushing the switch on the thermal trippingdevice will close damper. When switch on tripping device is released, the damper will open.
Manual opening
Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric acuator(clockwise). Damper can be locked in the desired position by fast turning back handle a quarter of a turn (counterclockwise).To unlock the electromotor, turn handle clockwise for a quarter of a turn. If the handle is released, damper will be closed by returnspring. When damper is opened manually, electric actuator will not move the damper into closed position after power failure (ther-moelectric fuse).
switch for checking forproper fuctioning
handle for manual opening
Open position Closed position
Design changes reserved05
FIRE DAMPERS - FD25
Belimo BLF24-T i BF24-T supply viasafety isolation transformer
1 negative (direct-current) or neutral (alternating current)2 positive (direct-current) or faze (alternating current)
S1 common micro switch closed damper
S2 normally closed micro switch closed damperS3 normally open micro switch closed damperS4 common micro switch open damperS5 normally closed micro switch open damperS6 normally open micro switch open damper
Tf1 temperature sensor on the outer side of the duct (ambienttemperature) max. 72°C
Tf2 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C
Tf3 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C
S1 S2 S3 S4 S5 S6
<5° <80°
21
– +
T ~
BAE72B-STf1 Tf2 Tf3 LED
Type of Belimo actuator BLF24-T BLF230-T
Nominal voltage /power consumption
voltage AC/DC 24V, 50/60Hz AC 230V, 50/60Hz
opening 5 W 8 W
holding 2,5 W 3 Wfor wire sizing 7 VA 12,5 VA
End switch1 mA...3 A (0,5 A), DC
5 V...AC 250V1 mA...3 A (0.5 A), DC 5 V...AC 250 V
Running timemotor 40...75 s 40...75 sspring-return ~20 s ~20 s
Ambient temperature range max. 50°C
ELECTRICAL CARACTERISTICS AND WIRING SCHEME OF ELECTRICAL ACTUATOR BELIMO
FIRE DAMPERS - FD25
06Design changes reserved
CONTACT US
KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com
klimaopremaHR-10430 Samobor,
Croatia, Gradna 78A.
KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com
klimaopremaHR-10430 Samobor,
Croatia, Gradna 78A.
Fire Damper
FIRE DAMPERFDC25
Design changes reserved01
FIRE DAMPER - FDC25
• Fire resistance according to EN 1366-2, classified according to EN 13501-3, Declaration of performance given according to Anex III of Regulation No 305/2011
• Rigid wall: EI 90 (ve, i↔o)S • Flexible wall: EI 90 (ve, i↔o)S • Ceiling / floor: EI 120 (ho, i↔o)S
• Used for the isolation of duct penetrations between fire com-partments.
• Fire dampers consist of housing, fire-resistant damper blade-and release mechanism.
• Casing made of galvanised sheet steel, damper blade made of special insulating material, damper blade shaft and push rod-made of stainless steel, plastic plain bearings made of brass, seals made of polyurethane and elastomer.
PROFIRE DAMPER FDC25
FIRE PROTECTION
DAMPER MODELS
FDC25-M cylindrical fire damper with electric actuator.
• thermoelectric activation (72°C) with electric actuator and return spring
• integrated end switches• fully automatic operation• networking capability (MP-BUS, LonWorks, AS-i BUS)
Options: M230 – electric actuator AC 230V M24 – electric actuator AC/DC 24V
Standard diameters
Øn[mm] 100 125 160 200 250 300 315
fire damper housingdamper bladedamper blade rotation axiselectric actuator: Belimo BLFthermo-electric tripping device (72°C)smoke sealintumescent strip
1234567
425
Ø n-2
35(Dn=315)
1
4
3
270
Øn+100
2
5
6
7
40
DIMENSIONS
FIRE DAMPER - FDC25
02Design changes reserved
Fire damper FDC25 is suitable for installation in all types of rigid, flexible walls, ceilings. Installation should be performed accordingto the installation instructions provided by the manufacturer.
Installation steps:
1. Wall opening Øn+160mm 2. Damper fixing (damper blade should be in a closed position during installation!) 3. Fill the gap between damper and wall with mortar
INSTALLATION IN RIGID WALL
During installation use wooden struts toprefent deformation of casing becauseof mortar drying.
230z>100
s>80
standard concrete mortar
Wall opening: Øn+160 mm
Check the mobility of damper blade, test opening and closing of fire damper
Design changes reserved03
FIRE DAMPER - FDC25
INSTALLATION IN FLEXIBLE WALL
gypsum plaster
gypsum plasterboards (thickness 12,5mm)
mineral wool (density 50kg/m3)
CW metal profile
screw for gypsum plasterboardlength >60 mm
s≥80
Z
120
Masterboard thickness 20mm
Wall opening: Øn+160 mm
Check the mobility of damper blade, test opening and closing of fire damper
230
z>125s>80
INSTALLATION IN CEILING
Ceiling/floor opening: Øn + 160
gypsum plaster
Check the mobility of damper blade, test opening and closing of fire damper
FIRE DAMPER - FDC25
04Design changes reserved
SELECTION DIAGRAM
ORDERING KEY
Symbol: v ∆pt LWA
- air velocity in the duct [m/s]- total pressure drop [Pa]- sound power level [dB(A)]
FDC25 Ø 250 M230 S G1- - --
Damper type
Damper diameter Øn [mm]
Mechanism type:R - manual mechanismE230 - solenoid actuator AC230VE24 - solenoid actuator AC 24VM230 - electrical actuator AC230VM24 - electrical actuator AC/DC 24V
Options:s - electric limit switches (indicating damper “OPEN” and “CLOSED”)z - electric limit switch (indicating damper “CLOSED”)o - electric limit switch (indicating damper “OPEN”)
Grille (option):G1 - grid on one sideG2 - grid on both sides
Design changes reserved05
FIRE DAMPER - FDC25
BELIMOBLF230
OPERATING INSTRUCTIONS
Damper is delivered in closed position. When electric actuator is connected to the power supply damper will open. When the damperreaches the end position (damper open), in which is it blocked, the electromotor will stop. Closing fire damper takes place automati-cally when a power failure occurs. Thermal tripping device that comes with fire damper causes power circuit break at a temperatureof 72 °C (inside or outside duct). If checking is needed for proper fuctioning of fire damper, pushing the switch on the thermal trippingdevice will close damper. When switch on tripping device is released, the damper will open.
Manual opening
Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric acuator(clockwise). Damper can be locked in the desired position by fast turning back handle a quarter of a turn (counterclockwise).To unlock the electromotor, turn handle clockwise for a quarter of a turn. If the handle is released, damper will be closed by returnspring. When damper is opened manually, electric actuator will not move the damper into closed position after power failure (ther-moelectric fuse).
switch for checking forproper fuctioning
handle for manual opening
Open position Closed position
FIRE DAMPER - FDC25
06Design changes reserved
Belimo BLF24-T i BF24-T supply viasafety isolation transformer
1 negative (direct-current) or neutral (alternating current)2 positive (direct-current) or faze (alternating current)
S1 common micro switch closed damper
S2 normally closed micro switch closed damperS3 normally open micro switch closed damperS4 common micro switch open damperS5 normally closed micro switch open damperS6 normally open micro switch open damper
Tf1 temperature sensor on the outer side of the duct (ambienttemperature) max. 72°C
Tf2 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C
Tf3 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C
S1 S2 S3 S4 S5 S6
<5° <80°
21
– +
T ~
BAE72B-STf1 Tf2 Tf3 LED
Type of Belimo actuator BLF24-T BLF230-T
Nominal voltage /power consumption
voltage AC/DC 24V, 50/60Hz AC 230V, 50/60Hz
opening 5 W 8 W
holding 2,5 W 3 Wfor wire sizing 7 VA 12,5 VA
End switch1 mA...3 A (0,5 A), DC
5 V...AC 250V1 mA...3 A (0.5 A), DC 5 V...AC 250 V
Running timemotor 40...75 s 40...75 sspring-return ~20 s ~20 s
Ambient temperature range max. 50°C
ELECTRICAL CARACTERISTICS AND WIRING SCHEME OF ELECTRICAL ACTUATOR BELIMO
CONTACT US
KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com
klimaopremaHR-10430 Samobor,
Croatia, Gradna 78A.
KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com
klimaopremaHR-10430 Samobor,
Croatia, Gradna 78A.
Fire Damper
FIRE DAMPERFD40
Design changes reserved01
FIRE DAMPER - FD40
• Fire resistance according to EN 1366-2, classified according to EN 13501-3, Declaration of performance given according to Anex III of Regulation No 305/2011
• Rigid wall: EI 120 (ve, i↔o)S• Flexible wall: EI 120 (ve, i↔o)S• Ceiling / floor: EI 120 (ho, i↔o)S
All possible combinations of width and height are available.Standard dimensions are avaliable with increments of 50mm.
Min. dimensions B(W) x H [mm]
Max. dimensions B(W) x H[mm]
200x200 1500x800
• Used for the isolation of duct penetrations between fire com-partments.
• Fire dampers consist of housing, fire-resistant damper blade and release mechanism.
• Casing made of galvanised sheet steel, damper blade made of special insulating material, damper blade shaft and push rod made of stainless steel, plastic plain bearings made of brass, seals made of polyurethane and elastomer.
FIRE DAMPER FD40
FIRE PROTECTION
DAMPER MODELS
FD40-M rectangular fire damper with electric actuator.
• thermoelectric activation (72°C) with electric actuator and return spring
• integrated end switches• fully automatic operation• networking capability (MP-BUS, LonWorks, AS-i BUS)
Options: M230 – electric actuator AC 230V M24 – electric actuator AC/DC 24V
DIMENSIONS
fire damper housingdamper bladeelectric actuator: Belimo B(L)Fthermo-electric tripping device (72°C)smoke sealintumescent strip
123456
350
2
3
4
5
B
250
3030
30
120
30
H
6
FIRE DAMPER - FD40
02Design changes reserved
s>80
Fire damper FD40 is suitable for installation in all types of rigid, flexible walls and ceilings. Installation should be performed accordingto the installation instructions provided by the manufacturer.
Installation steps:
1. Wall opening H(B)+160mm 2. Damper fixing (damper blade should be in a closed position during installation!) 3. Fill the gap between damper and wall with mortar
INSTALLATION IN RIGID WALL
standard gypsum plaster
During installation use wooden struts toprevent deformation of casing, causedby drying gypsium plaster or mortar.
z > 100
137 Opening in the wall: (B+160) x (H+160)
Masterboard thickness 20mm
200
After installation check for damperblade mobility, preform an opening andclosing test.
Design changes reserved03
FIRE DAMPER - FD40
s>80
021521>z
200
120
z>125
200
s≥80
standard concrete mortar
gypsum plasterboards (thickness 12,5mm)
mineral wool (density 50kg/m3)
CW metal profile
screw for gypsum plasterboard
Opening in the wall: (B+160) x (H+160)
Masterboard thickness20mm
INSTALLATION IN FLEXIBLE WALL
INSTALLATION IN CEILING
Opening in the wall: (B+160) x (H+160)
Masterboard thickness 20mm
gypsum plaster or mortar
137
731After installation check for damperblade mobility, preform an opening andclosing test.
After installation check for damperblade mobility, preform an opening andclosing test.
FIRE DAMPER - FD40
04Design changes reserved
H=700
H=800
Grille:G1 - grid on one sideG2 - grid on both sides
SELECTION DIAGRAM
The values of total pressure loss for other sizes are obtained in a manner that read value from the graph is multiplied with the correc-tion value from the table. Value of sound power are obtained in a manner that read value is added the correction value from the table.
FD40 400x300 M230 S G1- - --
Damper typeDamper dimensions B(W) x H [mm]
Options:s - electric limit switches (indicating damper “OPEN” and “CLOSED”)z - electric limit switch (indicating damper “CLOSED”)o - electric limit switch (indicating damper “OPEN”)
ORDERING KEY
Symbol: v ∆pt LWA
- air velocity in the duct [m/s]- total pressure loss [Pa]- sound power level [dB(A)]
Total pressure loss and sound power level for B=400:
B [mm] 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000-1200
1200-1500
∆pt x 1,22 1,14 1,07 1,0 0,94 0,88 0,83 0,77 0,73 0,68 0,64 0,6 0,58 0,56 0,55 0,54 0,5 0,4
Lwa+ -1 -1 0 0 0 0 0 0 0 0 1 1 2 2 2 3 3 4
Mechanism type:R - manual mechanismE230 - solenoid actuator AC230VE24 - solenoid actuator AC 24VM230 - electric actuator AC230VM24 - electric actuator AC/DC 24V
Design changes reserved05
FIRE DAMPER - FD40
BELIMOBLF230
OPERATING INSTRUCTIONS
Damper is delivered in closed position. When electric actuator is connected to the power supply damper will open. When the damperreaches the end position (damper open), in which is it blocked, the electromotor will stop. Closing fire damper takes place automati-cally when a power failure occurs. Thermal tripping device that comes with fire damper causes power circuit break at a temperatureof 72 °C (inside or outside duct). If checking is needed for proper fuctioning of fire damper, pushing the switch on the thermal trippingdevice will close damper. When switch on tripping device is released, the damper will open.
Manual opening
Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric acuator(clockwise). Damper can be locked in the desired position by fast turning back handle a quarter of a turn (counterclockwise).To unlock the electromotor, turn handle clockwise for a quarter of a turn. If the handle is released, damper will be closed by returnspring. When damper is opened manually, electric actuator will not move the damper into closed position after power failure (ther-moelectric fuse).
switch for checking forproper fuctioning
handle for manual opening
CLOSED OPEN
DAMPER OPENDAMPER CLOSED
CLOSED OPEN
FD40-R
FIRE DAMPER - FD40
06Design changes reserved
Belimo BLF24-T i BF24-T supply viasafety isolation transformer
1 negative (direct-current) or neutral (alternating current)2 positive (direct-current) or faze (alternating current)
S1 common micro switch closed damper
S2 normally closed micro switch closed damperS3 normally open micro switch closed damperS4 common micro switch open damperS5 normally closed micro switch open damperS6 normally open micro switch open damper
Tf1 temperature sensor on the outer side of the duct (ambienttemperature) max. 72°C
Tf2 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C
Tf3 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C
S1 S2 S3 S4 S5 S6
<5° <80°
21
– +
T ~
BAE72B-STf1 Tf2 Tf3 LED
Type of Belimo actuator BLF24-T BF24-T BLF230-T BF230-T
Nominal voltage /power consumption
voltage AC/DC 24V, 50/60Hz AC/DC 24V, 50/60Hz AC 230V, 50/60Hz AC 230V, 50/60Hz
opening 5 W 7 W 6 W 8 W
holding 2,5 W 2 W 3 W 3 W
for wire sizing 7 VA 10 VA 7 VA 12,5 VA
End switch 1 mA...3 A (0,5 A), DC 5 V...AC 250V
1mA...6A (3A), DC 5V...AC 250V
1 mA...3 A (0.5 A), DC 5 V...AC 250 V
1 mA...6 A (3 A), DC 5 V...AC 250 V
Running timemotor 40...75 s <120 s 40...75 s <140 s
spring-return ~20 s ~16 s ~20 s ~16 s
Ambient temperature range max. 50°C
ELECTRICAL CARACTERISTICS AND WIRING SCHEME OF ELECTRICAL ACTUATOR BELIMO
CLOSED OPEN CLOSED OPEN
Fire damper is delivered in closed position. To open the damper, handle should be turned in counter-clockwise direction to “OPEN”position. It is possible to close damper with solenoid. The damper is opened manually. Manual damper activation is intended forperiodic maintenance.
FD40-E
DAMPER OPENDAMPER CLOSED
CONTACT US
KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com
klimaopremaHR-10430 Samobor,
Croatia, Gradna 78A.
KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com
klimaopremaHR-10430 Samobor,
Croatia, Gradna 78A.
Fire Damper
FIRE DAMPERFDC40
425
Øn-2
(Øn-20)/2-155
1
4 3
270 40
• Fire resistance according to EN 1366-2, classified according to EN 13501-3, Declaration of performance given according to Anex III of Regulation No 305/2011
• Rigid wall: EI 120 (ve, i↔o)S • Flexible wall: EI 120 (ve, i↔o)S • Ceiling / floor: EI 120 (ho, i↔o)S
• Used for the isolation of duct penetrations between fire com-partments.
• Fire dampers consist of housing, fire-resistant damper blade-and release mechanism.
• Casing made of galvanised sheet steel, damper blade made of special insulating material, damper blade shaft and push rod made of stainless steel, plastic plain bearings made of brass, seals made of polyurethane and elastomer.
FIRE DAMPER FDC40
FIRE PROTECTION
DAMPER MODELS
FDC40-M cylindrical fire damper with electric actuator.
• thermoelectric activation (72°C) with electric actuator and re-turn spring
• integrated end switches• fully automatic operation• networking capability (MP-BUS, LonWorks, AS-i BUS)
Options: M230 – electric actuator AC 230V M24 – electric actuator AC/DC 24V
fire damper housingdamper bladedamper blade rotation axiselectric actuator: Belimo B(L)Fthermo-electric tripping device (72°C)smoke sealintumescent strip
1234567
DIMENSIONS
Standard diameters
Øn[mm] 100 125 160 200 250 300 315 355 400 500 630
Øn+100
2
5
6
7
Design changes reserved01
FIRE DAMPER - FDC40
FIRE DAMPER - FDC40
02Design changes reserved
230 z
s>80
Fire damper FDC40 is suitable for installation in all types of rigid, flexible walls, ceilings. Installation should be performed accordingto the installation instructions provided by the manufacturer.
Installation steps:
1. Wall opening Øn+160mm 2. Damper fixing (damper blade should be in a closed position during installation!) 3. Fill the gap between damper and wall with mortar
INSTALLATION IN RIGID WALL
During installation use wooden struts toprefent deformation of casing becauseof mortar drying.
standard concrete mortar
Wall opening: Øn+160 mm
Check the mobility of damper blade, test opening and closing of fire damper
Masterboard thickness 20mm
Design changes reserved03
FIRE DAMPER - FDC40
INSTALLATION IN FLEXIBLE WALL
gypsum plaster
gypsum plasterboards (thickness 12,5mm)
mineral wool (density 50kg/m3)
CW metal profile
screw for gypsum plasterboardlength >60 mm
s≥80
Z
120
Masterboard thickness 20mm
Wall opening: Øn+160 mm
Check the mobility of damper blade, test opening and closing of fire damper
230
z>125s>80
INSTALLATION IN CEILING
Ceiling/floor opening: Øn + 160
gypsum plaster
Check the mobility of damper blade, test opening and closing of fire damper
FIRE DAMPER - FDC40
04Design changes reserved
SELECTION GRAPH
Symbol: v ∆pt LWA
- air velocity in the duct [m/s]- total pressure drop [Pa]- sound power level [dB(A)]
ORDERING KEY
FDC40 Ø 250 M230 S G1- - --
Damper type
Damper diameter Øn [mm]
Mechanism type:R - manual mechanismE230 - solenoid actuator AC230VE24 - solenoid actuator AC 24VM230 - electrical actuator AC230VM24 - electrical actuator AC/DC 24V
Options:s - electric limit switches (indicating damper “OPEN” and “CLOSED”)z - electric limit switch (indicating damper “CLOSED”)o - electric limit switch (indicating damper “OPEN”)
Grille (option):G1 - grid on one sideG2 - grid on both sides
Design changes reserved05
FIRE DAMPER - FDC40
BELIMOBLF230
OPERATING INSTRUCTIONS
Damper is delivered in closed position. When electric actuator is connected to the power supply damper will open. When the damperreaches the end position (damper open), in which is it blocked, the electromotor will stop. Closing fire damper takes place automati-cally when a power failure occurs. Thermal tripping device that comes with fire damper causes power circuit break at a temperatureof 72 °C (inside or outside duct). If checking is needed for proper fuctioning of fire damper, pushing the switch on the thermal trippingdevice will close damper. When switch on tripping device is released, the damper will open.
Manual opening
Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric acuator(clockwise). Damper can be locked in the desired position by fast turning back handle a quarter of a turn (counterclockwise).To unlock the electromotor, turn handle clockwise for a quarter of a turn. If the handle is released, damper will be closed by returnspring. When damper is opened manually, electric actuator will not move the damper into closed position after power failure (ther-moelectric fuse).
switch for checking forproper fuctioning
handle for manual opening
CLOSED OPEN
DAMPER OPENDAMPER CLOSED
CLOSED OPEN
FDC40-R
FIRE DAMPER - FDC40
06Design changes reserved
Belimo BLF24-T i BF24-T supply viasafety isolation transformer
1 negative (direct-current) or neutral (alternating current)2 positive (direct-current) or faze (alternating current)
S1 common micro switch closed damper
S2 normally closed micro switch closed damperS3 normally open micro switch closed damperS4 common micro switch open damperS5 normally closed micro switch open damperS6 normally open micro switch open damper
Tf1 temperature sensor on the outer side of the duct (ambienttemperature) max. 72°C
Tf2 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C
Tf3 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C
S1 S2 S3 S4 S5 S6
<5° <80°
21
– +
T ~
BAE72B-STf1 Tf2 Tf3 LED
Type of Belimo actuator BLF24-T BF24-T BLF230-T BF230-T
Nominal voltage /power consumption
voltage AC/DC 24V, 50/60Hz AC/DC 24V, 50/60Hz AC 230V, 50/60Hz AC 230V, 50/60Hz
opening 5 W 7 W 6 W 8 W
holding 2,5 W 2 W 3 W 3 W
for wire sizing 7 VA 10 VA 7 VA 12,5 VA
End switch 1 mA...3 A (0,5 A), DC 5 V...AC 250V
1mA...6A (3A), DC 5V...AC 250V
1 mA...3 A (0.5 A), DC 5 V...AC 250 V
1 mA...6 A (3 A), DC 5 V...AC 250 V
Running timemotor 40...75 s <120 s 40...75 s <140 s
spring-return ~20 s ~16 s ~20 s ~16 s
Ambient temperature range max. 50°C
ELECTRICAL CARACTERISTICS AND WIRING SCHEME OF ELECTRICAL ACTUATOR BELIMO
CLOSED OPEN CLOSED OPEN
Fire damper is delivered in closed position. To open the damper, handle should be turned in counter-clockwise direction to “OPEN”position. It is possible to close damper with solenoid. The damper is opened manually. Manual damper activation is intended forperiodic maintenance.
FDC40-E
DAMPER OPENDAMPER CLOSED