KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com klimaoprema HR-10430 Samobor, Croatia, Gradna 78A. FD25 FIRE DAMPER
32

FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web:

Oct 06, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com

klimaopremaHR-10430 Samobor,

Croatia, Gradna 78A.

Fire Damper

FD25FIRE DAMPER

Page 2: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

All possible combinations of width and height are available. Standard dimensions are avaliable with increments of 50mm.

Min. dimensions B(W) x H [mm]

Max. dimensions B(W) x H[mm]

200x200 800x600

350

2

3

4

5

B

250

3030

30

120

30

H

6

1

• Fire resistance according to EN 1366-2, classified according to EN 13501-3, Declaration of performance given according to Anex III of Regulation No 305/2011

• Rigid wall: EI 90 (ve, i↔o)S• Flexible wall: EI 90 (ve, i↔o)S• Ceiling / floor: EI 120 (ho, i↔o)S

• Used for the isolation of duct penetrations between fire com-partments.

• Fire dampers consist of housing, fire-resistant damper blade and release mechanism.

• Casing made of galvanised sheet steel, damper blade made of special insulating material, damper blade shaft and push rod made of stainless steel, plastic plain bearings made of brass, seals made of polyurethane and elastomer.

FIRE DAMPER FD25

FIRE PROTECTION

DAMPER MODELS

FD25-M rectangular fire damper with electric actuator.

• thermoelectric activation (72°C) with electric actuator and re-turn spring

• integrated end switches • fully automatic operation• networking capability (MP-BUS, LonWorks, AS-i BUS)

Options: M230 – electric actuator AC 230V M24 – electric actuator AC/DC 24V

DIMENSIONS

fire damper housingdamper bladeelectric actuator: Belimo BLFthermo-electric tripping device (72°C)smoke sealintumescent strip

123456

Design changes reserved01

FIRE DAMPERS - FD25

Page 3: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

s>80

Fire damper FD25 is suitable for installation in all types of rigid, flexible walls and ceilings. Installation should be performed according to the installation instructions provided by the manufacturer.

Installation steps:

1. Wall opening H(B)+160mm 2. Damper fixing (damper blade should be in a closed position during installation!) 3. Fill the gap between damper and wall with mortar

INSTALLATION IN RIGID WALL

standard gypsum plaster

During installation use wooden struts toprevent deformation of casing, caused by drying gypsium plaster.

z

137 Opening in the wall: (B+160) x (H+160)

Masterboard thickness 20mm

200

After installation check for damper blade mobility, preform an opening and closing test.

FIRE DAMPERS - FD25

02Design changes reserved

Page 4: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

INSTALLATION IN FLEXIBLE WALL

INSTALLATION IN CEILING

120

z>125

200

s≥80

standard gypsum plaster

gypsum plasterboards (thickness 12,5mm)

mineral wool (density 50kg/m3)

CW metal profile

screw for gypsum plasterboard

Opening in the wall: (B+160) x (H+160)

Masterboard thickness 20mm

137

After installation check for damperblade mobility, perform an opening andclosing test.

s>80

021521>z

200

Opening in the wall: (B+160) x (H+160)

Masterboard thickness20mm

standard gypsum plaster

731

After installation check for damperblade mobility, preform an opening andclosing test.

Design changes reserved03

FIRE DAMPERS - FD25

Page 5: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

SELECTION DIAGRAM

The values of total pressure loss for other sizes are obtained in a manner that read value from the graph is multiplied with the correc-tion value from the table. Value of sound power are obtained in a manner that read value is added the correction value from the table.

B [mm] 200 250 300 350 400 450 500 550 600 650 700 750 800

∆pt x 1,22 1,14 1,07 1,0 0,94 0,88 0,83 0,77 0,73 0,68 0,64 0,6 0,58

Lwa+ -1 -1 0 0 0 0 0 0 0 0 1 1 2

ORDERING KEY

Symbol: v ∆pt LWA

- air velocity in the duct [m/s]- total pressure loss [Pa]- sound power level [dB(A)]

Total pressure loss and sound power level for B=400:

FD25 400x300 M230 S G1- - --

Damper typeDamper dimensions B(W) x H [mm]

Mechanism type:R - manual mechanismE230 - solenoid actuator AC230VE24 - solenoid actuator AC 24VM230 - electric actuator AC230VM24 - electric actuator AC/DC 24VOptions:s - electric limit switches (indicating damper “OPEN” and “CLOSED”)z - electric limit switch (indicating damper “CLOSED”)o - electric limit switch (indicating damper “OPEN”)Grille:G1 - grid on one sideG2 - grid on both sides

FIRE DAMPERS - FD25

04Design changes reserved

Page 6: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

BELIMOBLF230

OPERATING INSTRUCTIONS

Damper is delivered in closed position. When electric actuator is connected to the power supply damper will open. When the damperreaches the end position (damper open), in which is it blocked, the electromotor will stop. Closing fire damper takes place automati-cally when a power failure occurs. Thermal tripping device that comes with fire damper causes power circuit break at a temperatureof 72 °C (inside or outside duct). If checking is needed for proper fuctioning of fire damper, pushing the switch on the thermal trippingdevice will close damper. When switch on tripping device is released, the damper will open.

Manual opening

Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric acuator(clockwise). Damper can be locked in the desired position by fast turning back handle a quarter of a turn (counterclockwise).To unlock the electromotor, turn handle clockwise for a quarter of a turn. If the handle is released, damper will be closed by returnspring. When damper is opened manually, electric actuator will not move the damper into closed position after power failure (ther-moelectric fuse).

switch for checking forproper fuctioning

handle for manual opening

Open position Closed position

Design changes reserved05

FIRE DAMPERS - FD25

Page 7: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

Belimo BLF24-T i BF24-T supply viasafety isolation transformer

1 negative (direct-current) or neutral (alternating current)2 positive (direct-current) or faze (alternating current)

S1 common micro switch closed damper

S2 normally closed micro switch closed damperS3 normally open micro switch closed damperS4 common micro switch open damperS5 normally closed micro switch open damperS6 normally open micro switch open damper

Tf1 temperature sensor on the outer side of the duct (ambienttemperature) max. 72°C

Tf2 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C

Tf3 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C

S1 S2 S3 S4 S5 S6

<5° <80°

21

– +

T ~

BAE72B-STf1 Tf2 Tf3 LED

Type of Belimo actuator BLF24-T BLF230-T

Nominal voltage /power consumption

voltage AC/DC 24V, 50/60Hz AC 230V, 50/60Hz

opening 5 W 8 W

holding 2,5 W 3 Wfor wire sizing 7 VA 12,5 VA

End switch1 mA...3 A (0,5 A), DC

5 V...AC 250V1 mA...3 A (0.5 A), DC 5 V...AC 250 V

Running timemotor 40...75 s 40...75 sspring-return ~20 s ~20 s

Ambient temperature range max. 50°C

ELECTRICAL CARACTERISTICS AND WIRING SCHEME OF ELECTRICAL ACTUATOR BELIMO

FIRE DAMPERS - FD25

06Design changes reserved

Page 8: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

CONTACT US

KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com

klimaopremaHR-10430 Samobor,

Croatia, Gradna 78A.

Page 9: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com

klimaopremaHR-10430 Samobor,

Croatia, Gradna 78A.

Fire Damper

FIRE DAMPERFDC25

Page 10: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

Design changes reserved01

FIRE DAMPER - FDC25

• Fire resistance according to EN 1366-2, classified according to EN 13501-3, Declaration of performance given according to Anex III of Regulation No 305/2011

• Rigid wall: EI 90 (ve, i↔o)S • Flexible wall: EI 90 (ve, i↔o)S • Ceiling / floor: EI 120 (ho, i↔o)S

• Used for the isolation of duct penetrations between fire com-partments.

• Fire dampers consist of housing, fire-resistant damper blade-and release mechanism.

• Casing made of galvanised sheet steel, damper blade made of special insulating material, damper blade shaft and push rod-made of stainless steel, plastic plain bearings made of brass, seals made of polyurethane and elastomer.

PROFIRE DAMPER FDC25

FIRE PROTECTION

DAMPER MODELS

FDC25-M cylindrical fire damper with electric actuator.

• thermoelectric activation (72°C) with electric actuator and return spring

• integrated end switches• fully automatic operation• networking capability (MP-BUS, LonWorks, AS-i BUS)

Options: M230 – electric actuator AC 230V M24 – electric actuator AC/DC 24V

Standard diameters

Øn[mm] 100 125 160 200 250 300 315

fire damper housingdamper bladedamper blade rotation axiselectric actuator: Belimo BLFthermo-electric tripping device (72°C)smoke sealintumescent strip

1234567

425

Ø n-2

35(Dn=315)

1

4

3

270

Øn+100

2

5

6

7

40

DIMENSIONS

Page 11: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

FIRE DAMPER - FDC25

02Design changes reserved

Fire damper FDC25 is suitable for installation in all types of rigid, flexible walls, ceilings. Installation should be performed accordingto the installation instructions provided by the manufacturer.

Installation steps:

1. Wall opening Øn+160mm 2. Damper fixing (damper blade should be in a closed position during installation!) 3. Fill the gap between damper and wall with mortar

INSTALLATION IN RIGID WALL

During installation use wooden struts toprefent deformation of casing becauseof mortar drying.

230z>100

s>80

standard concrete mortar

Wall opening: Øn+160 mm

Check the mobility of damper blade, test opening and closing of fire damper

Page 12: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

Design changes reserved03

FIRE DAMPER - FDC25

INSTALLATION IN FLEXIBLE WALL

gypsum plaster

gypsum plasterboards (thickness 12,5mm)

mineral wool (density 50kg/m3)

CW metal profile

screw for gypsum plasterboardlength >60 mm

s≥80

Z

120

Masterboard thickness 20mm

Wall opening: Øn+160 mm

Check the mobility of damper blade, test opening and closing of fire damper

230

z>125s>80

INSTALLATION IN CEILING

Ceiling/floor opening: Øn + 160

gypsum plaster

Check the mobility of damper blade, test opening and closing of fire damper

Page 13: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

FIRE DAMPER - FDC25

04Design changes reserved

SELECTION DIAGRAM

ORDERING KEY

Symbol: v ∆pt LWA

- air velocity in the duct [m/s]- total pressure drop [Pa]- sound power level [dB(A)]

FDC25 Ø 250 M230 S G1- - --

Damper type

Damper diameter Øn [mm]

Mechanism type:R - manual mechanismE230 - solenoid actuator AC230VE24 - solenoid actuator AC 24VM230 - electrical actuator AC230VM24 - electrical actuator AC/DC 24V

Options:s - electric limit switches (indicating damper “OPEN” and “CLOSED”)z - electric limit switch (indicating damper “CLOSED”)o - electric limit switch (indicating damper “OPEN”)

Grille (option):G1 - grid on one sideG2 - grid on both sides

Page 14: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

Design changes reserved05

FIRE DAMPER - FDC25

BELIMOBLF230

OPERATING INSTRUCTIONS

Damper is delivered in closed position. When electric actuator is connected to the power supply damper will open. When the damperreaches the end position (damper open), in which is it blocked, the electromotor will stop. Closing fire damper takes place automati-cally when a power failure occurs. Thermal tripping device that comes with fire damper causes power circuit break at a temperatureof 72 °C (inside or outside duct). If checking is needed for proper fuctioning of fire damper, pushing the switch on the thermal trippingdevice will close damper. When switch on tripping device is released, the damper will open.

Manual opening

Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric acuator(clockwise). Damper can be locked in the desired position by fast turning back handle a quarter of a turn (counterclockwise).To unlock the electromotor, turn handle clockwise for a quarter of a turn. If the handle is released, damper will be closed by returnspring. When damper is opened manually, electric actuator will not move the damper into closed position after power failure (ther-moelectric fuse).

switch for checking forproper fuctioning

handle for manual opening

Open position Closed position

Page 15: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

FIRE DAMPER - FDC25

06Design changes reserved

Belimo BLF24-T i BF24-T supply viasafety isolation transformer

1 negative (direct-current) or neutral (alternating current)2 positive (direct-current) or faze (alternating current)

S1 common micro switch closed damper

S2 normally closed micro switch closed damperS3 normally open micro switch closed damperS4 common micro switch open damperS5 normally closed micro switch open damperS6 normally open micro switch open damper

Tf1 temperature sensor on the outer side of the duct (ambienttemperature) max. 72°C

Tf2 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C

Tf3 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C

S1 S2 S3 S4 S5 S6

<5° <80°

21

– +

T ~

BAE72B-STf1 Tf2 Tf3 LED

Type of Belimo actuator BLF24-T BLF230-T

Nominal voltage /power consumption

voltage AC/DC 24V, 50/60Hz AC 230V, 50/60Hz

opening 5 W 8 W

holding 2,5 W 3 Wfor wire sizing 7 VA 12,5 VA

End switch1 mA...3 A (0,5 A), DC

5 V...AC 250V1 mA...3 A (0.5 A), DC 5 V...AC 250 V

Running timemotor 40...75 s 40...75 sspring-return ~20 s ~20 s

Ambient temperature range max. 50°C

ELECTRICAL CARACTERISTICS AND WIRING SCHEME OF ELECTRICAL ACTUATOR BELIMO

Page 16: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

CONTACT US

KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com

klimaopremaHR-10430 Samobor,

Croatia, Gradna 78A.

Page 17: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com

klimaopremaHR-10430 Samobor,

Croatia, Gradna 78A.

Fire Damper

FIRE DAMPERFD40

Page 18: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

Design changes reserved01

FIRE DAMPER - FD40

• Fire resistance according to EN 1366-2, classified according to EN 13501-3, Declaration of performance given according to Anex III of Regulation No 305/2011

• Rigid wall: EI 120 (ve, i↔o)S• Flexible wall: EI 120 (ve, i↔o)S• Ceiling / floor: EI 120 (ho, i↔o)S

All possible combinations of width and height are available.Standard dimensions are avaliable with increments of 50mm.

Min. dimensions B(W) x H [mm]

Max. dimensions B(W) x H[mm]

200x200 1500x800

• Used for the isolation of duct penetrations between fire com-partments.

• Fire dampers consist of housing, fire-resistant damper blade and release mechanism.

• Casing made of galvanised sheet steel, damper blade made of special insulating material, damper blade shaft and push rod made of stainless steel, plastic plain bearings made of brass, seals made of polyurethane and elastomer.

FIRE DAMPER FD40

FIRE PROTECTION

DAMPER MODELS

FD40-M rectangular fire damper with electric actuator.

• thermoelectric activation (72°C) with electric actuator and return spring

• integrated end switches• fully automatic operation• networking capability (MP-BUS, LonWorks, AS-i BUS)

Options: M230 – electric actuator AC 230V M24 – electric actuator AC/DC 24V

DIMENSIONS

fire damper housingdamper bladeelectric actuator: Belimo B(L)Fthermo-electric tripping device (72°C)smoke sealintumescent strip

123456

350

2

3

4

5

B

250

3030

30

120

30

H

6

Page 19: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

FIRE DAMPER - FD40

02Design changes reserved

s>80

Fire damper FD40 is suitable for installation in all types of rigid, flexible walls and ceilings. Installation should be performed accordingto the installation instructions provided by the manufacturer.

Installation steps:

1. Wall opening H(B)+160mm 2. Damper fixing (damper blade should be in a closed position during installation!) 3. Fill the gap between damper and wall with mortar

INSTALLATION IN RIGID WALL

standard gypsum plaster

During installation use wooden struts toprevent deformation of casing, causedby drying gypsium plaster or mortar.

z > 100

137 Opening in the wall: (B+160) x (H+160)

Masterboard thickness 20mm

200

After installation check for damperblade mobility, preform an opening andclosing test.

Page 20: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

Design changes reserved03

FIRE DAMPER - FD40

s>80

021521>z

200

120

z>125

200

s≥80

standard concrete mortar

gypsum plasterboards (thickness 12,5mm)

mineral wool (density 50kg/m3)

CW metal profile

screw for gypsum plasterboard

Opening in the wall: (B+160) x (H+160)

Masterboard thickness20mm

INSTALLATION IN FLEXIBLE WALL

INSTALLATION IN CEILING

Opening in the wall: (B+160) x (H+160)

Masterboard thickness 20mm

gypsum plaster or mortar

137

731After installation check for damperblade mobility, preform an opening andclosing test.

After installation check for damperblade mobility, preform an opening andclosing test.

Page 21: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

FIRE DAMPER - FD40

04Design changes reserved

H=700

H=800

Grille:G1 - grid on one sideG2 - grid on both sides

SELECTION DIAGRAM

The values of total pressure loss for other sizes are obtained in a manner that read value from the graph is multiplied with the correc-tion value from the table. Value of sound power are obtained in a manner that read value is added the correction value from the table.

FD40 400x300 M230 S G1- - --

Damper typeDamper dimensions B(W) x H [mm]

Options:s - electric limit switches (indicating damper “OPEN” and “CLOSED”)z - electric limit switch (indicating damper “CLOSED”)o - electric limit switch (indicating damper “OPEN”)

ORDERING KEY

Symbol: v ∆pt LWA

- air velocity in the duct [m/s]- total pressure loss [Pa]- sound power level [dB(A)]

Total pressure loss and sound power level for B=400:

B [mm] 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000-1200

1200-1500

∆pt x 1,22 1,14 1,07 1,0 0,94 0,88 0,83 0,77 0,73 0,68 0,64 0,6 0,58 0,56 0,55 0,54 0,5 0,4

Lwa+ -1 -1 0 0 0 0 0 0 0 0 1 1 2 2 2 3 3 4

Mechanism type:R - manual mechanismE230 - solenoid actuator AC230VE24 - solenoid actuator AC 24VM230 - electric actuator AC230VM24 - electric actuator AC/DC 24V

Page 22: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

Design changes reserved05

FIRE DAMPER - FD40

BELIMOBLF230

OPERATING INSTRUCTIONS

Damper is delivered in closed position. When electric actuator is connected to the power supply damper will open. When the damperreaches the end position (damper open), in which is it blocked, the electromotor will stop. Closing fire damper takes place automati-cally when a power failure occurs. Thermal tripping device that comes with fire damper causes power circuit break at a temperatureof 72 °C (inside or outside duct). If checking is needed for proper fuctioning of fire damper, pushing the switch on the thermal trippingdevice will close damper. When switch on tripping device is released, the damper will open.

Manual opening

Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric acuator(clockwise). Damper can be locked in the desired position by fast turning back handle a quarter of a turn (counterclockwise).To unlock the electromotor, turn handle clockwise for a quarter of a turn. If the handle is released, damper will be closed by returnspring. When damper is opened manually, electric actuator will not move the damper into closed position after power failure (ther-moelectric fuse).

switch for checking forproper fuctioning

handle for manual opening

CLOSED OPEN

DAMPER OPENDAMPER CLOSED

CLOSED OPEN

FD40-R

Page 23: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

FIRE DAMPER - FD40

06Design changes reserved

Belimo BLF24-T i BF24-T supply viasafety isolation transformer

1 negative (direct-current) or neutral (alternating current)2 positive (direct-current) or faze (alternating current)

S1 common micro switch closed damper

S2 normally closed micro switch closed damperS3 normally open micro switch closed damperS4 common micro switch open damperS5 normally closed micro switch open damperS6 normally open micro switch open damper

Tf1 temperature sensor on the outer side of the duct (ambienttemperature) max. 72°C

Tf2 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C

Tf3 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C

S1 S2 S3 S4 S5 S6

<5° <80°

21

– +

T ~

BAE72B-STf1 Tf2 Tf3 LED

Type of Belimo actuator BLF24-T BF24-T BLF230-T BF230-T

Nominal voltage /power consumption

voltage AC/DC 24V, 50/60Hz AC/DC 24V, 50/60Hz AC 230V, 50/60Hz AC 230V, 50/60Hz

opening 5 W 7 W 6 W 8 W

holding 2,5 W 2 W 3 W 3 W

for wire sizing 7 VA 10 VA 7 VA 12,5 VA

End switch 1 mA...3 A (0,5 A), DC 5 V...AC 250V

1mA...6A (3A), DC 5V...AC 250V

1 mA...3 A (0.5 A), DC 5 V...AC 250 V

1 mA...6 A (3 A), DC 5 V...AC 250 V

Running timemotor 40...75 s <120 s 40...75 s <140 s

spring-return ~20 s ~16 s ~20 s ~16 s

Ambient temperature range max. 50°C

ELECTRICAL CARACTERISTICS AND WIRING SCHEME OF ELECTRICAL ACTUATOR BELIMO

CLOSED OPEN CLOSED OPEN

Fire damper is delivered in closed position. To open the damper, handle should be turned in counter-clockwise direction to “OPEN”position. It is possible to close damper with solenoid. The damper is opened manually. Manual damper activation is intended forperiodic maintenance.

FD40-E

DAMPER OPENDAMPER CLOSED

Page 24: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

CONTACT US

KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com

klimaopremaHR-10430 Samobor,

Croatia, Gradna 78A.

Page 25: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com

klimaopremaHR-10430 Samobor,

Croatia, Gradna 78A.

Fire Damper

FIRE DAMPERFDC40

Page 26: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

425

Øn-2

(Øn-20)/2-155

1

4 3

270 40

• Fire resistance according to EN 1366-2, classified according to EN 13501-3, Declaration of performance given according to Anex III of Regulation No 305/2011

• Rigid wall: EI 120 (ve, i↔o)S • Flexible wall: EI 120 (ve, i↔o)S • Ceiling / floor: EI 120 (ho, i↔o)S

• Used for the isolation of duct penetrations between fire com-partments.

• Fire dampers consist of housing, fire-resistant damper blade-and release mechanism.

• Casing made of galvanised sheet steel, damper blade made of special insulating material, damper blade shaft and push rod made of stainless steel, plastic plain bearings made of brass, seals made of polyurethane and elastomer.

FIRE DAMPER FDC40

FIRE PROTECTION

DAMPER MODELS

FDC40-M cylindrical fire damper with electric actuator.

• thermoelectric activation (72°C) with electric actuator and re-turn spring

• integrated end switches• fully automatic operation• networking capability (MP-BUS, LonWorks, AS-i BUS)

Options: M230 – electric actuator AC 230V M24 – electric actuator AC/DC 24V

fire damper housingdamper bladedamper blade rotation axiselectric actuator: Belimo B(L)Fthermo-electric tripping device (72°C)smoke sealintumescent strip

1234567

DIMENSIONS

Standard diameters

Øn[mm] 100 125 160 200 250 300 315 355 400 500 630

Øn+100

2

5

6

7

Design changes reserved01

FIRE DAMPER - FDC40

Page 27: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

FIRE DAMPER - FDC40

02Design changes reserved

230 z

s>80

Fire damper FDC40 is suitable for installation in all types of rigid, flexible walls, ceilings. Installation should be performed accordingto the installation instructions provided by the manufacturer.

Installation steps:

1. Wall opening Øn+160mm 2. Damper fixing (damper blade should be in a closed position during installation!) 3. Fill the gap between damper and wall with mortar

INSTALLATION IN RIGID WALL

During installation use wooden struts toprefent deformation of casing becauseof mortar drying.

standard concrete mortar

Wall opening: Øn+160 mm

Check the mobility of damper blade, test opening and closing of fire damper

Masterboard thickness 20mm

Page 28: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

Design changes reserved03

FIRE DAMPER - FDC40

INSTALLATION IN FLEXIBLE WALL

gypsum plaster

gypsum plasterboards (thickness 12,5mm)

mineral wool (density 50kg/m3)

CW metal profile

screw for gypsum plasterboardlength >60 mm

s≥80

Z

120

Masterboard thickness 20mm

Wall opening: Øn+160 mm

Check the mobility of damper blade, test opening and closing of fire damper

230

z>125s>80

INSTALLATION IN CEILING

Ceiling/floor opening: Øn + 160

gypsum plaster

Check the mobility of damper blade, test opening and closing of fire damper

Page 29: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

FIRE DAMPER - FDC40

04Design changes reserved

SELECTION GRAPH

Symbol: v ∆pt LWA

- air velocity in the duct [m/s]- total pressure drop [Pa]- sound power level [dB(A)]

ORDERING KEY

FDC40 Ø 250 M230 S G1- - --

Damper type

Damper diameter Øn [mm]

Mechanism type:R - manual mechanismE230 - solenoid actuator AC230VE24 - solenoid actuator AC 24VM230 - electrical actuator AC230VM24 - electrical actuator AC/DC 24V

Options:s - electric limit switches (indicating damper “OPEN” and “CLOSED”)z - electric limit switch (indicating damper “CLOSED”)o - electric limit switch (indicating damper “OPEN”)

Grille (option):G1 - grid on one sideG2 - grid on both sides

Page 30: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

Design changes reserved05

FIRE DAMPER - FDC40

BELIMOBLF230

OPERATING INSTRUCTIONS

Damper is delivered in closed position. When electric actuator is connected to the power supply damper will open. When the damperreaches the end position (damper open), in which is it blocked, the electromotor will stop. Closing fire damper takes place automati-cally when a power failure occurs. Thermal tripping device that comes with fire damper causes power circuit break at a temperatureof 72 °C (inside or outside duct). If checking is needed for proper fuctioning of fire damper, pushing the switch on the thermal trippingdevice will close damper. When switch on tripping device is released, the damper will open.

Manual opening

Damper can be opened without connecting to a voltage with enclosed handle turning in the direction of the arrow on electric acuator(clockwise). Damper can be locked in the desired position by fast turning back handle a quarter of a turn (counterclockwise).To unlock the electromotor, turn handle clockwise for a quarter of a turn. If the handle is released, damper will be closed by returnspring. When damper is opened manually, electric actuator will not move the damper into closed position after power failure (ther-moelectric fuse).

switch for checking forproper fuctioning

handle for manual opening

CLOSED OPEN

DAMPER OPENDAMPER CLOSED

CLOSED OPEN

FDC40-R

Page 31: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

FIRE DAMPER - FDC40

06Design changes reserved

Belimo BLF24-T i BF24-T supply viasafety isolation transformer

1 negative (direct-current) or neutral (alternating current)2 positive (direct-current) or faze (alternating current)

S1 common micro switch closed damper

S2 normally closed micro switch closed damperS3 normally open micro switch closed damperS4 common micro switch open damperS5 normally closed micro switch open damperS6 normally open micro switch open damper

Tf1 temperature sensor on the outer side of the duct (ambienttemperature) max. 72°C

Tf2 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C

Tf3 temperature sensor on the inner side of the duct (temperaturein the duct) max. 72°C

S1 S2 S3 S4 S5 S6

<5° <80°

21

– +

T ~

BAE72B-STf1 Tf2 Tf3 LED

Type of Belimo actuator BLF24-T BF24-T BLF230-T BF230-T

Nominal voltage /power consumption

voltage AC/DC 24V, 50/60Hz AC/DC 24V, 50/60Hz AC 230V, 50/60Hz AC 230V, 50/60Hz

opening 5 W 7 W 6 W 8 W

holding 2,5 W 2 W 3 W 3 W

for wire sizing 7 VA 10 VA 7 VA 12,5 VA

End switch 1 mA...3 A (0,5 A), DC 5 V...AC 250V

1mA...6A (3A), DC 5V...AC 250V

1 mA...3 A (0.5 A), DC 5 V...AC 250 V

1 mA...6 A (3 A), DC 5 V...AC 250 V

Running timemotor 40...75 s <120 s 40...75 s <140 s

spring-return ~20 s ~16 s ~20 s ~16 s

Ambient temperature range max. 50°C

ELECTRICAL CARACTERISTICS AND WIRING SCHEME OF ELECTRICAL ACTUATOR BELIMO

CLOSED OPEN CLOSED OPEN

Fire damper is delivered in closed position. To open the damper, handle should be turned in counter-clockwise direction to “OPEN”position. It is possible to close damper with solenoid. The damper is opened manually. Manual damper activation is intended forperiodic maintenance.

FDC40-E

DAMPER OPENDAMPER CLOSED

Page 32: FIRE DAMPER - Dasmal Trading LLCKAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: airconditioning@bindasmal.com Web:

CONTACT US

KAD Air Conditioning Est. P.O. Box 5389, Dubai, UAE. Tel: +971 4 806 7676 Fax: +971 4 806 7688 Email: [email protected] Web: www.kadairconditioning.com

klimaopremaHR-10430 Samobor,

Croatia, Gradna 78A.