STRUCTURAL SURVEY OF THE SCHOOLS AFFECTED BY TSUNAMI AND EARTHQUAKE IN ACEH PROVINCE AND NIAS INDONESIA - FINAL REPORT - March 2005 February 2006
49

Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Mar 13, 2019

Download

Documents

vothu
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

STRUCTURAL SURVEY OF THE SCHOOLS

AFFECTED BY TSUNAMI AND EARTHQUAKE IN ACEH PROVINCE

AND NIAS INDONESIA

- FINAL REPORT -

March 2005 – February 2006

Page 2: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 2 Lamia Maglic UNOPS Construction Engineer

TABLE OF CONTENT:

Page 1. INTRODUCTION……………………………………………………….……. 3 2. OBJECTIVES AND EXPECTED OUTPUTS OF SCHOOLS

SURVEY……………………………………………………………….…….. 3 2.1. METHODOLOGY OF WORKS………………………………..…….. 3

3. ACHIEVED OUTPUTS OF SCHOOLS SURVEY………………….…......... 4 4. OBSERVATIONS ON TECHNICAL ISSUES………………………….….... 5 4.1. EXISTING SCHOOLS (STANDARDS APPLIED)………………….... 5 4.2. STRUCTURAL TYPES OF THE BUILDINGS………………........….. 6 4.3. STRUCTURAL DAMAGES ON SCHOOL BUILDINGS……………. 7 4.4. COMMON STRUCTURAL DEFICIENCIES CONTRIBUTING MOST DAMAGES..…………………..……….….. 9 4.4.1. REINFORCEMENT RELATED DEFICIENCIES……………………. 9 4.4.2. CONCRETE RELATED DEFICIENCIES…………………..………… 10 4.4.3. WOODEN STRUCTURES DEFICIENCIES………………………….. 10 4.4.4. STRUCTURAL DETAILING DEFICIENCIES……………………..… 11 4.5. RECOMMENDATIONS FOR RETROFITTING……………………… 12 4.5.1. REPAIR OF CRACKS…………………………………………………. 12 4.5.2. FIXING THE CROSS WALLS TO LONG WALLS……………….….. 12 4.5.3. REBUILDING OF DAMAGED PART OF THE WALL……………… 13 4.5.4. REPAIR OF DAMAGED RING BEAMS JUNCTIONS…………….… 13 4.5.5. REPAIR OF DAMAGED CONCRETE COLUMNS……………......… 13 4.5.6. REPAIR OF DAMAGED WOODEN SEGMENTS..…………………. 14

4.6. RECOMMENDATIONS FOR CONSTRUCTION OF NEW SCHOOLS………………………………………………...…. 15 4.6.1. NEW CONSTRUCTION STANDARDS…………………………….... 15 4.6.2. PRACTICAL IMPROVEMENT OF STRUCTURAL SEGMENTS..… 16 4.6.3. RECOMMENDATIONS FOR PRE-CONSTRUCTION PHASE.…..… 17 4.6.4. RECOMMENDATIONS FOR CONSTRUCTION PHASE.………..… 17 4.6.4.1. SUPERVISION OF WORKS………………………………………... 17 4.6.4.2. MATERIALS AND WORKMASHIP……………………………….. 17 4.6.4.3. CERTIFICATION AND TESTING OF MATERIALS……………… 18 5. CONCLUSION…………………………………………………………...….. 19 5.1. LESSONS FROM RECENT DESTRUCTION……………………….. 19 6. ANNEXES…………………………………………………………………… 20

ANNEX 1: BUILDING STANDARDS FOR SEISMIC ZONES 4,5,6…...... 21 ANNEX 2: PHOTOS OF TYPICAL DAMAGES ON SCHOOLS……...…. 25 ANNEX 3: PHOTOS OF TYPICAL DEFICIENCIES ON SCHOOLS…..... 31 ANNEX 4: LIST OF SURVEYED SCHOOLS BY DISTRICTS………....... 34

Page 3: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 3 Lamia Maglic UNOPS Construction Engineer

1. INTRODUCTION Earthquake and Tsunami that hit Aceh province in December 26th 2004 but also earthquake that hit Nias in March 28th 2005, caused unprecedented devastation of housing, social and communal infrastructure and huge human casualties. Hundreds of schools throughout Aceh Province and Nias were damaged or destroyed. Ministry of National Education (MoNE, figures from June 2005) estimates that 2.269 schools out of total 5.565 in Aceh Province were damaged. 309 SDN and MIN primary schools suffered light damages, further 494 were heavyly damaged, 235 were totally destroyed. In Nias heavy damages were reported on 413 SDN and MIN schools. The learning capacities were severely reduced, remaining learning facilities endangered. Together with material damages, there were huge casualties both among students and teachers. In new situation, approximately 177.000 students needed learning facilities. About 400.000 persons had to move to other locations as Internally Displaced Persons. In order to continue lectures, in many remaining schools classes were regrouped, more classes attended lessons in one class room etc. In order to plan and coordinate necessary actions towards ensuring safety for students in remaining schools, there was urgent need to survey all schools and provide figures about real state of facilities in new situation. Remaining schools had to be surveyed in order to identify potentially unsafe ones and determine those to be rehabilitated or reconstructed in order to enable continuation of education process. All figures necessary to plan further actions on provision of safe school spaces had to be compiled in short time. In co-ordination with Department of Education, short after disaster, UNICEF started the structural survey of the schools in Aceh Province through cooperation with UNOPS, whose team of structural engineers commenced survey in late March 2005. 2. OBJECTIVES AND EXPECTED OUTPUTS OF SCHOOLS SURVEY 2.1. METHODOLOGY OF WORK

• Field visit of schools • Visual observation with recording of photos • Detection of damages • Analysis of cause of damages • Assessment of safety condition in every class room and other school rooms • Warning of schools authorities on site in case of unsafe rooms • Recommending of necessary actions: rehabilitation/reconstruction • Reporting to UNICEF/UNOPS on survey findings: unsafe rooms and recommended

activities Many schools had already been surveyed by DoE, NGOs or other state institutions teams, however compiled reports about structural conditions and level of damage on these schools were confusing and not reliable and had to be checked again. Targeted category of schools to be surveyed were all SDN and MIN schools in use. Priority was to identify unsafe schools or rooms within the schools and to issue warning through UNICEF to school authorities and Department of Education. In case of condemning the schools, after approval by DoE,

Page 4: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 4 Lamia Maglic UNOPS Construction Engineer

students would be evacuated from unsafe school and the temporary schools (in the beginning tents, later prefabricated buildings) would be erected to enable continuation of lectures out of unsafe buildings until new permanent school is completed. Since the most affected areas by Tsunami and earthquakes were Banda Aceh, Aceh Barat, Aceh Besar, Aceh Jaya, Nagan Raja, Pidie and Nias, survey of the schools was focused on these districts. Together with structural survey of the schools aiming to identify unsafe learning spaces and those for rehabilitation or new construction, the intention was also to provide accurate findings about construction failures contributing severe damages. These findings would enable to determine corrective measures in rehabilitation and reconstruction of damaged schools also learn about failures in previous construction practices allowing destruction of the schools and which improvements are needed for construction of new ones. Beside schools damaged by Tsunami, also those deep inland, damaged by earthquake were to be surveyed. 3. ACHIEVED OUTPUTS OF SCHOOLS SURVEY From March 2005 till February 2006, UNOPS Structural Engineers surveyed 428 schools. The structural survey of the schools was performed in districts Banda Aceh, Aceh Barat, Aceh Besar, Aceh Jaya, Nagan Raja, Pidie, Nias and Nias Selatan.These districts were the most affected and survey of the schools was focused on them. Together with SDN and MIN that were targeted category, 51 SMAN, SMPS and SMPN schools were surveyed. Out of 428 surveyed schools, 212 schools were found to need rehabilitation, 154 to need reconstruction, 56 to need both rehabilitation and reconstruction (schools with more buildings of different level of damages), only 6 schools needed no activity. These figures are presented in following table: District Banda

Aceh Aceh Besar

Aceh Barat

Aceh Jaya

Nagan Raya

Nias and Nias Selatan

Pidie

Surveyed schools

107 136 53 21 22 80 9

Rehabilitation 69 90 22 6 12 9 4 Reconstruction 31 29 24 12 5 51 2 Rehabilitation/ Reconstruction

7 11 7 3 5 20 3

No activity 0 6 0 0 0 0 0 Together with determining of activities that need to be undertaken, the safety conditions were inspected on each school. The schools were declared as UNSAFE, PARTS UNSAFE, GOOD, * GOOD, PARTS DESTROYED, DESTROYED, depending on scale and type of destruction and estimate that some class rooms or entire school can collapse. Out of total of 428 surveyed schools, 25 were declared as UNSAFE, meaning that classes were still ongoing in entirely unsafe buildings (close to collapse) in the time of structural survey. In such cases

Page 5: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 5 Lamia Maglic UNOPS Construction Engineer

the school authorities were warned immediately on site, Department of Education through UNICEF. This and other safety categories are presented in “Lists of surveyed schools by Districts”, given in ANNEX 4 of this report. Exact lists of the schools to be surveyed were composed in co-operation between UNICEF and Government (Department of Education and BRR). The survey performed was of “quick assessment” type, meaning visual inspection of the schools, with identification and defining the level of damage on site. Following intention to improve the general condition of schools where needed, besides structural safety of them, also other non-structural items (conditions of toilets, sanitation and water supply, capacities of teachers accommodation-houses in remote schools, roofs, eaves and ceilings conditions etc.) were inspected and findings included in reports. For each surveyed school, the numbers of photos were taken for reports and files. The findings of all 428 surveyed schools were presented in 24 reports, submitted to UNICEF. The list of surveyed schools with findings and recommendations is given in Annex to this report. ANNEX 1 to this report is matrix with new construction standards, ANNEX 2 is photo presentation of most common structural damages on schools, ANNEX 3 is photo presentation of most common deficiencies in construction, which contributed most damages. Summary of structural survey is presented as ANNEX 4 “Surveyed schools by districts”. . 4. OBSERVATIONS ON TECHNICAL ISSUES 4.1. EXISTING SCHOOLS (STANDARDS APPLIED) In 1997 Department of Public Works issued a decree No 295/KPTS/CK/1997 about "Technical Guidelines for the Construction of Government Buildings". This guidelines considered buildings even up to 2 floors as simple, non engineered buildings. The most of schools buildings are up to that height and therefore belong to that category. The designs of school buildings, technical specifications and the administration procedures were described in those Guidelines. Typical model of schools buildings for elementary schools is ground floor building, masonry bearing wall, construction with RC columns, RC ring beam, timber roof trusses, and galvanized tin sheet roofing. The typical materials used in the model were:

• K-175 reinforced concrete for columns and beams, • 1:6 mortar mix (the typical strengths of masonry: compressive stress 21kg/cm2, shear

stress 3.9 kg/cm2, bending tensile stress 2.5 kg/cm2) for brick masonry walls, • U-24 reinforcing steel (fy =2400 kg/cm2), • wooden roof truss (2nd class, allowable stresses of wood:

compressive stress // grain = 81 kg/cm2, bending tensile stress = 91.8 kg/cm2) • roof cover is light galvanized steel roof sheets.

Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal and vertical seismic coefficients based on seismic zones, importance of buildings, height of building and soil stiffness. These regulations did not apply for simple buildings with a maximum height of 5 m above the foundation. Most of the school buildings were in that category and remained non-engineered for earthquake resistance.

Page 6: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 6 Lamia Maglic UNOPS Construction Engineer

4.2. STRUCTURAL TYPES OF THE BUILDINGS There are following structural types of the buildings:

• Ground floor wall bearing buildings with RC columns intermediate and in walls crossings and within the wall thickness (size 10 x 10cm), clay bricks wall between, with RC ring beam (size 10 x 15cm) at roof level over all external and partition walls, on which the roof trusses are fixed. The walls are usually constructed of burnt clay bricks in cement plaster, with a total thickness of 12 cm with plaster. This is the most common structural type of the schools.

• The buildings with timber columns in wall thickness (size 10 x 10cm), compacted

concrete or clay bricks masonry 80cm-180cm high between columns, wooden ring beam on which the roof trusses are fixed. At this type of structure, masonry has bracing function for wooden columns. The walls are usually constructed of burnt clay bricks, in some areas of compacted concrete, with a total thickness of 12 cm with plaster. This is very common structural type in Aceh Barat, Nagan Raya, Aceh Jaya and Nias.

• Ground floor non-bearing walls type of the structure, with larger RC columns in walls crossings and intermediate (size 20 x 20cm, out of wall thickness), non-bearing, infill brick walls between, RC ring beam at roof level over external and partition walls on which the roof trusses are fixed. This structural type is newer, structurally improved, it is common especially in urban areas. It is found as better version than older wall bearing structure.

• Ground floor with one or more floors buildings, non-bearing walls type, structure

built of RC columns, RC beams supporting RC slabs, RC ring beams over all external and partition walls, carrying roof trusses. The infill walls are constructed of clay bricks in cement plaster, total thickness 12cm with plaster. This structural type is minority, found mostly in urban areas.

• Ground floor non-bearing walls type of the structure, with timber columns as bearing

structure and infill of timber planks, as wall paneling, wooden ring beam over columns tops on which the roof trusses are fixed. This type is found mostly in remote rural areas in Aceh Barat, Nagan Raya and Nias.

The common building materials used for school buildings in Aceh Province and Nias are reinforced concrete, clay bricks, wood and cement mortar. Wood is very frequently used for structural parts such as columns, beams, roof trusses, as well as non structural purposes, as partition and external walls panels, ceiling panels, eaves, etc. School buildings have sloping roofs, structure mostly made of timber roof trusses, rafters and purlins, covered by roof galvanized steel sheets or cement asbestos sheets.

Page 7: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 7 Lamia Maglic UNOPS Construction Engineer

4.3. STRUCTURAL DAMAGES ON SCHOOL BUILDINGS Common specific damages were found on the buildings during structural survey of the schools. Many of damages were visible on standing school buildings, the most of them still in use. The destroyed schools could also be inspected and primary damages leading to collapse of entire buildings could be identified. The cause of damage or collapse of the segments was identified by observing remaining structural segment in location of damage, where reinforcement is visible and diameter and positioning of bars, overlapping in extensions, clearance between stirrups can be determined. Also concrete could be checked, composition of gravel applied in concrete, presence of voids and honey combs, presence of other particles but aggregate, dirt, etc. However, all damages visible on standing or destroyed buildings were caused by the same common deficiencies in construction. Foundations - Break or collapse of foundation beams The foundation beams (connecting foundations footings of columns and supporting walls above) are especially weak segments due to insufficient reinforcement built-in, sometimes not reinforced at all. Laying on “stone-in-cement” sub construction (which is not reinforced as well), often collapse, break and cause breaking of the masonry above. Common for many schools is occurrence of separation of the walls from columns above broken foundation beam in junction with column footing. Columns - Break or collapse of columns Columns (reinforced columns) are affected by applying insufficient reinforcement (both main bars and stirrups) in terms of insufficient anchoring between footing and column and also column with ring beam above, too small diameter or too big clearance for stirrups, even grouping of main reinforcement bars in one corner of the column was frequently found. Many times reinforcement is visible on surface of column, not under protective coat of concrete. Break of column causes separation of the wall from the column, breaking or collapse of entire wall. Beams (lintels and ring beams) - Break or collapse of beams Ring beams have function of “horizontal belt “, framing structure against horizontal forces during earthquake and ensuring connection of structural segments. They are affected especially in junctions of segments (column with ring beam, junctions above partition and external walls). The most common cause of break of ring beam is extending by overlapping of all bars in one location with too short overlapping. Common deficiencies found were insufficient reinforcement applied (both main bars and stirrups), insufficient anchoring in junction to other structural segments, wrong positioning by grouping of bars in one corner of beam. Break or collapse of ring beam causes break of wall below, if in junction then separation of the walls occurs. Lintels mostly do not exist as reinforced beam over door and window openings. Istead of lintels, there are masonry constructed over door or window frames. Such segments are weak against horizontal forces during earthquakes, easily break and collapse. If reinforced lintel is constructed, it still does not extend to columns on both sides of openings, but only above the openings.

Page 8: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 8 Lamia Maglic UNOPS Construction Engineer

Walls (brick masonry or cast concrete) – Cracks, gaps and collapse of walls Many walls were found with minor or major cracks, in parapet walls or above doors and windows openings (mostly where the reinforced concrete lintel is not constructed). This is caused either by collapse of foundation beam below wall, or collapse of ring beam above wall. Even in case that foundation and ring beams are not damaged, wall itself can be too long and too high comparing to small width of 12cm only, to withstand out-of-plane moving effects (best visible where diagonal cracks in the walls and from windows openings). This occurs especially when the columns are too distant and there is no beam in the walls except ring beam on the top of walls. Common damage is separation of walls in corners (actually separation of masonry from concrete column). The cause of this is weak junction of masonry to columns, the walls are too high and too long, the damages occur along perimeter of the wall. The gable walls are frequently affected, there are minor or major cracks in masonry or collapse of parts or entire walls. These walls can be too long and too high comparing to small width of 12cm only. Common deficiencies in gable walls constructed by brick masonry are missing concrete column or weak ones in a middle of wall (extended from foundation) and top beams over the wall. In the wooden structure type of buildings (wooden columns with masonry), the masonry of walls separates from columns, gaps occur in junctions. Worse case is collapse of masonry between columns in parts or entirely. In these buildings the walls have role to brace columns, but when the walls collapse, all structure could collapse as well. The gaps also occure between wooden column and masonry due to deterioration of wooden parts caused by moisture. Wooden structure buildings with planks - Sloped walls, decomposition of junctions, collapse of buildings, exhausted buildings. The walls of many wooden buildings are sloped, in worst cases collapsed. This occurred by moving of columns out of supports bringing the walls in slope and finaly collapse of building. The cause for this is lack of timber bracing members between columns and top beams for all cross and external walls, the structure is not rigid enough against seismic horizontal forces. The junctions are made simply by nails for all coupled structural members. Second common cause is lack of maintenance (mostly no maintenance at all), the wooden structure members during construction were not protected against moisture nor insects, soon condition deteriorates and they become rotten, junctions decompose and finally building collapse. These damages are found on many school buildings in Aceh Barat, Nagan Raya and Nias. School destroyed or damaged by Tsunami located close to ocean: The most of schools located close to ocean are destroyed entirely or in part. In some cases the parts of the schools are still standing but locations are flooded. Such schools need to be relocated. Burnt schools: Some schools are located in former GAM area that after August 2005 Agreement between Government and GAM became accessable. The numbers of these schools were burnt between 2000 and 2002. Inhabitans of villages moved to other locations, with temporary schools solution for ID (internally displaced) students. The original locations of former schools are usually overgrown with heigh grass, bushes or plants. The villages are abandoned, residents moved, such schools need relocation.

Page 9: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 9 Lamia Maglic UNOPS Construction Engineer

4.4. COMMON STRUCTURAL DEFICIENCIES CONTRIBUTING MOST

DAMAGES The most damages and collapses of the schools buildings during earthquakes occurred as the result of improper construction methods, poor workmanship and application of bad materials. Thousands of elementary school buildings were constructed all over the country as the Presidential instruction was given twenty years ago to reduce the lack of elementary schools in Indonesia. The building standards were issued by government through Ministry of Public Works. The typical model for school buildings (ground floor building, masonry bearing wall, construction with RC columns, RC ring beam, timber roof trusses, and galvanized tin sheet roofing , see 4.1.) was accepted and widely constructed throughout Indonesia (thus in Aceh and Nias). Calculations and computer simulations proved that if constructed properly, with good materials, good workmanship and appropriate structural detailing in accordance with the design, that this model of building can withstand a earthquake of PGA of 0.22 g. However, failures and damages occurred frequently during construction before building was completed, most of schools were not constructed properly. Although the construction supervisors on behalf of Government should have been appointed during construction phase to ensure compliance with design and technical specification, they were frequently not engaged or they mostly failed in monitoring of construction phase. The construction did not comply with design and technical specifications. Even wrong construction methods were frequently applied as traditional ones, leaving everything to the contractor to complete the building. The quality of new schools was often poor. This affected the resistance of the buildings to seismic forces and made them more sensitive and weak to withstand earthquakes. During structural survey, the damages were visually observed, analyzed and defined as the part of the “quick survey or rapid assessment” of the schools. 4.4.1. Reinforcement related deficiencies:

• Too small diameter used in concrete columns, lintels and beams, both for main longitudinal reinforcement (even Q 6mm instead of 10 mm for beams and 12mm minimum for columns) and stirrups (even 3mm instead of 8mm minimum).

• The overlapping of bars of main longitudinal reinforcement for extensions is often in the middle of the span of the beam (where the tension is strongest).

• Entire longitudinal reinforcement of beams or lintels is extended and overlapped in the same location, allowing breaking of segment. In other cases the overlapping is too short (few cm only instead of 40dia of bars) or even does not exist, the hooks of the bars simply extend to each other.

• The stirrups clearance in the middle of segment or in the area of overlapping is too big (30 cm and more, clearance between should be half of clearance in normal segment, but not more than 15cm). It was often found that stirrups are not installed into junctions of segments (column with beam etc).

• RC columns acting as vertical bracing and RC ring beam acting as horizontal belt (connecting long façade walls and cross walls), frequently have insufficient ties (reinforcement anchoring), allowing collapse of ties and moving of such walls

Page 10: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 10 Lamia Maglic UNOPS Construction Engineer

independently in case of earthquake. The result of this is separation of walls in the corners and junctions, often collapse of walls.

• Bars of different diameter are sometimes found built-in into the structure segment, some smooth bars without hooks on ends.

• Over the beams of ground floor ceiling (acting as upper floor slab supports), the longitudinal reinforcement of the slab has no upper component to prevent occurring of cracks due to tension in that area (negative bending moment) over supports-beams.

• The reinforcement was often found visible, on surface of segment, rusty as result of bad installation with no spacers in formwork (no protective coat of concrete around). Such reinforcement is exposed to corrosion, decrease of diameter, deteriorates structural stability.

• Grouping of all main reinforcement bars in one corner or in the middle of columns or beams cross section is found on few schools. The participating reinforcement is moved from tense area of cross section, cracks or collapse of segment occurs.

4.4.2. Concrete related deficiencies:

• Concrete used is of non-controlled quality, simple river gravel with non-adequate sand-gravel particles division for proper mixing rates. The concrete inside damaged segment varies in quality, can be scratched even by finger (too little cement, sand but no gravel particles inside, insufficient mixing, etc).

• During the works ongoing on the schools under rehabilitation, it was seen that the concrete was mixed manually (by shovel, not in machine mixer), the concrete quality even required properly by design can not achieve needed level.

• The pouring of concrete into formwork is mostly performed by shovel, no vibrators to allow compaction in the formwork. Honey combs and voids in concrete are common for most structures, create weak locations in structure by reducing compressive strength, disable common acting of concrete and reinforcement steel and allow corrosion. In junctions of segments and overlapping of reinforcement, disable compression share and cause crush of concrete and collapse of junction.

• On some schools concrete is “white” in some segments, can be easily scratched into dust. After pouring of the concrete in strong sun, it was not covered nor cured by wetting next days.

4.4.3. Wooden structure deficiencies:

• There is no bracing between wooden structural members (column with beam) to ensure horizontal rigidity of building. Masonry is used as bracing for columns, frequently crackes or collapses, columns move from original supports, walls come into slope.

• There is no proper connection between wooden columns and masonry. It is usually done by nails (as anchoring for plaster for masonry). This is location where gaps between masonry and columns occur.

• The top beam over the walls is too weak to “frame” the structure, walls and columns become movable, cracks and gaps occur in masonry.

Page 11: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 11 Lamia Maglic UNOPS Construction Engineer

• Plaster was applied over wooden columns without wire mesh, it collapses in transition between different materials (wood-masonry) and insufficient adhearence

over wood. Plaster cracks, collapses and wooden column becomes unprotected against moisture.

• Roof wooden structure of the schools in general is often rotten in part, damaged by roof tin cover leakage, but also damaged by termites. In number of cases wooden roof members are insufficient in dimension or missing some bracing parts.

• There is no maintenance of wooden segments. During construction of wooden structure, the protection against moisture and insects was not applied. Wooden segments are damaged, rotten. The damaged parts are rarely repaired or replaced, become weak, exhausted and collapse. The most of these schools were built 5-20 years ago. Some of these schools are in very bad condition, exhausted and it is not effective to rehabilitate them, only reconstruction of such schools is recommended to improve bad general condition.

4.4.4. Structural detailing deficiencies: The main structural failures contributing damages were:

• The walls are usually too long (7m between columns at cross walls and more) and too high (3,5m to ring beam and more) comparing to wall thickness (12 cm), allowing out-of-plane moving and overturning of walls as a common feature. RC columns in walls crossings and intermediate in wall thickness (at wall bearing type only 10x10cm) have no capacity to ensure resistance to horizontal bending effect during earthquake. The result of this is occurring of many cracks in the walls, often the collapse of walls or entire building.

• Very commonly the reinforced concrete lintel is not made above windows and doors openings, only masonry-bricks directly laid down onto window or door frame. The cracks occur, portions of masonry may collapse.

• The masonry-brick walls, partition and parapet walls, at non-bearing wall building type with increased RC columns are built after concrete columns are built. The anchors on junctions are not used, the cracks in junctions of masonry with RC columns occur because of insufficient ties, the masonry separates from the column or collapse.

• Gable walls are especially weak segments, no top RC beam, only one vertical intermediate RC column in thickness of the wall (10x10cm) extended to the top (small dimension, insufficient reinforcement), often collapse.

Page 12: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 12 Lamia Maglic UNOPS Construction Engineer

4.5. RECOMMENDATIONS FOR RETROFITTING Retrofitting is activity applied on damaged structural parts in order to bring the building into original state. However, the buildings surveyed in this structural survey declared for rehabilitation will be rehabilitated only if proved that remainder of the building complies with latest construction standards. Othewise the building will be reconstructed. 4.5.1 REPAIR OF CRACKS If minor or major cracks occur in plaster and masonry, they should be repaired to obtain original integrity of walls. In case the cracks are wide enough, cement - sand mortar grout of 1:6 ratio (better effect if prefabricated mixture of expanding mortar Sika, ROFIX or similar is used) can be applied :

• Remove the plaster over a width of 20 cm on each side of the crack from both inside and outside surface of the wall, clean the crack area with air pressure.

• Wet the cracks by sprinkling water • Seal the cracks on opposite side, fill the grout into the cracks starting with the lowest

end and moving up the height of the wall. In case grout can not be filled into the cracks, use the following method:

• Remove the plaster over a width of 20 cm on each side of the crack from inside as well as outside the walls, clean the crack with air pressure.

• Use galvanized wire mesh 40 cm wide and nail it to the wall over whole length of the crack about 20 cm for each side.

• Wet the wall by sprinkling water • Sprinkle neat cement slurry on the surface and apply 1:4 cement sand plaster to cover

the total width of 20 cm each side of the crack, flatten whole new surface. Prior to this repair, first check that other structural segments are not broken. Otherwise, firstly structural segments must be repaired. 4.5.2. FIXING THE CROSS WALLS TO LONG WALLS The cross walls are usually built after façade walls, do not have good connection with the facade walls, junctions of masonry are done only by cement plaster, junctions of ring beams are not good enough (insufficient reinforcement or weak concrete). These locations are among first ones where damages occur in form of separation of walls. To repair connection, it is recommended as follows:

• Remove plaster on both sides from corner 50 cm in whole height of wall • Make dia 6mm holes in walls to be connected in every 30cm vertically and

horizontally in the plaster between bricks • Apply reinforcement net (with bars dia 6mm with openings 15cm) over whole height

of the walls (starting from wall foundation beam below and over ring beam above) • Insert dia 6mm connecting pieces into holes in the walls and bend ends to hold net on

both sides of the walls • Fix galvanized wire mesh over net installed

Page 13: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 13 Lamia Maglic UNOPS Construction Engineer

• Apply cement sand-plaster 1:4 ratio in thickness of 25 mm all over the mesh Prior to this repair, first check that other structural segments are not broken. Otherwise, firstly structural segments must be repaired. 4.5.3. REBUILDING OF DAMAGED PART OF THE WALL If part of the wall is badly cracked or collapsed, such part of the wall should be demolished and reconstructed by using clay bricks and 1:6 cement sand mortar. The structure above (if any) should be supported until the wall is complete again.

• All weak and unstable pieces of masonry (damaged plaster, cracked bricks) must be removed

• Clean the contact surfaces by air pressure • Wet the contact surfaces to achieve better adherence of new mortar to old one • Build the missing part of the wall • Apply 1:6 cement-sand plaster coat over both sides of new part of wall, flatten whole

new surface of plaster. Prior to this repair, first check that other structural segments are not broken. Otherwise, firstly structural segments must be repaired. 4.5.4. REPAIR OF DAMAGED RING BEAM JUNCTIONS The common weak locations in structures are ring beams in junctions of internal cross walls with façade walls, due to insufficient reinforcement built in, incorrectly anchored and insufficiently overlapped. This causes separation of walls below. In order to strengthen or repair cracked junction, following method is suggested:

• Demolish concrete in junction from all beams in length of 40cm for each (preserve existing reinforcement).

• Clean area from remaining unstable pieces of concrete, also by air pressure • Insert previously bent and hooked additional reinforcement (4 pcs of main bars dia

12mm starting with cross wall beam) into existing reinforcement of external wall ring beam, ensure overlapping is minimum 40cm for each direction and install stirrups dia 8mm with clearances in overlapping not more than 8cm.

• Assemble and install formwork for concrete pouring (height and width as rest of the beam)

• Pour concrete with proper compaction for entire parts length of new beams • Wet new concrete next 7 days

This method often requires fixing of separated walls described under 4.5.2. 4.5.5. REPAIR OF DAMAGED CONCRETE COLUMNS Applying insufficient reinforcement in RC columns and in junctions of coupled segments (foundation with RC column, RC column with RC ring beam, etc), allows the out-of-plane acting of walls, cracking or collapse in case of earthquake.

Page 14: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 14 Lamia Maglic UNOPS Construction Engineer

In order to repair broken column or strengthen weak one, following is recommended: For lightly damaged columns: This method requires less demolishment of existing structure:

• Remove plaster on both sides from coupled walls (both walls 80 cm from corner) in whole height

• Make holes dia 6mm in walls plaster between bricks in vertical and horizontal distance 30cm in zig-zag line

• Apply reinforcement nets bent over corner (with bars dia 6mm with openings 15cm), on both sides and over whole height of the walls (starting from wall foundation beam below and over ring beam above)

• Insert dia 6mm connecting pieces into holes in the walls and bend ends to hold nets on both sides of the walls

• Apply cement sand-plaster 1:4 ratio in thickness of 25 mm all over the nets (preferably using pressure plastering machine) For heavily damaged columns (rebuilding of new ones): This method requires more demolishment of existing structure:

• Support the structure above column and ring beam to be repaired (roof truss, etc), also stabilize masonry around column to be repaired

• Remove plaster, demolish concrete and all reinforcement from the column • Demolish concrete from ring beam above (40 cm to each side from column top) and

foundation beam below (deep as needed to obtain 40 cm overlapping of new concrete and existing foundation reinforcement), preserve all existing reinforcement of ring beam and foundation

• Clean all contact surfaces to receive new concrete, especially masonry around • Install new column reinforcement in needed height to get into foundation and ring

beam 40cm in each direction ( 4 pcs dia 12mm main bars and stirrups dia 8mm with clearance 15 cm, in overlapping with ring beam and foundation bars to be 10cm)

• Assemble and install formwork for new column (20x20cm) • Mix in mixer and pour concrete fc=20 MPa into formwork all from foundation to ring

beam, compaction by vibrator to prevent voids occurence • Wet new concrete next 7 days

All above repair suggestions are related to simple one storey buildings. The similar methods but with items properties according to calculations can be applied for two storey buildings. 4.5.6. REPAIR OF DAMAGED WOODEN SEGMENTS

• Damaged wooden segments must be replaced in order to bring structure capacity into original state. Other structural segments to be temporarily supported

• Wooden segments damaged by termits or rotten are not of original capacity must be replaced as well

• The endangered junctions must be dismantled and new segments coupled. Prior to installation, they must be protected against moisture and termites.

Page 15: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 15 Lamia Maglic UNOPS Construction Engineer

4.6. RECOMMENDATIONS FOR RECONSTRUCTION OF SCHOOLS 4.6.1. NEW CONSTRUCTION STANDARDS Given by new regulations by Ministry of Public Works issued in late 2005, districts Aceh Besar, Aceh Barat, Aceh Jaya, Nagan Raya, Banda Aceh of Aceh Province now belong to seismic zone 5 and Nias and Nias Selatan to zone 6. Furher improvement comparing to previous standards is seicmic strengthening also of “ground floor” buildings, which was not practice before. The buildings must be designed as “Engineered structures”, meaning taking in account importance and type of building, seismic zone and geological conditions on locality. The zonation is further specified by possible Tsunamy occurrence, as follows: Upon distance from the coastline: 5km<R, 5km<R<20km, R>20km Upon elevation of building: 5m<EL, 5m<EL<15m, EL>15m giving instructions for positioning of the buildings (vertical or optional to shoreline) in “lay out”depending of distance from the shore line and elevation of building. For seismic analisys and calculations, zone 5 has PGA (peak ground acceleration) ≥ 0,25 g, zone 6 has PGA (peak ground acceleration) ≥ 0,30 g. The construction standards for seismic zones 4, 5 and 6 are given as matrix presented in ANNEX 1 of this report. Other seismic zones cover rest of Aceh Province, mostly east areas less affected by earthquakes, far from the ocean and are not considered in this report.

Seismic zone 2 (North-east part of Aceh Province)

Seismic zone 3 (East part of Aceh Province and north coast)

Seismic zone 4 Major part of Aceh Besar and central area of Aceh province)

Seismic zone 5 (Banda Aceh, Aceh Barat, Aceh Jaya, Nagan Raya, coastal part of Aceh Besar)

Seismic zone 6 (Nias and Nias Selatan)

Page 16: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 16 Lamia Maglic UNOPS Construction Engineer

4.6.2. PRACTICAL IMPROVEMENTS OF STRUCTURAL SEGMENTS Following measures to be applied for reconstruction of school buildings:

• Limit the free length of the walls to 3-4m (currently 8m to 10 m), in order to decrease out-of-plane bending effects of horizontal earthquake forces. This can be done by constructing intermediate RC columns of proper dimension (min.30x30cm), with proper reinforcement (min. 4pcs dia 12mm for main bars and min. 8mm for stirrups with maximal clearance 15cm. for ground floor buildings). All RC columns must be fully anchored into RC foundations and RC ring beams by applying appropriate overlapping of reinforcement (40dia of reinforcement bars) to ensure integrity and horizontal bending forces resistance.

• Limit the free height of the walls to 2,5m (currently up to 4 m) by constructing horizontal RC beams in all walls of the rooms at the door and window top level (min. 4pcs of dia 12mm for main bars and min. 8mm for stirrups with maximal clearance 15cm), all to be attached to RC columns by appropriate reinforcement overlapping.

• Gable walls must have central RC column extended from foundations (min. 4pcs of dia 12mm for main bars and min. 8mm for stirrups with maximal clearance 15cm) and sloped top RC beam all over masonry.

• The ring beams on top of the walls need to be properly reinforced (hb≥lb/12, bb≥30cm, min. 4 pcs of dia 12mm for main bars and min.8mm for stirrups with maximal clearance 15cm) and fully attached with the vertical columns, using reinforcement overlapping 40dia in the joints.

• Foundation footing for columns and foundation beams must be properly reinforced and calculated for specific soil conditions on location of school. Single footings must be mutually connected by foundation beams by applying sufficient reinforcement in junctions.

• Walls foundation beams must be reinforced (hb≥lb/16, min. 4pcs of dia 12mm for main bars and min. 8mm for stirrups with maximal clearance 15cm).

• Two storey buildings must have RC slab reinforced both in lower and upper zone in area above slab support (reinforcing welded nets or bars, according to calculation, to receive tension in upper zone due to of negative bending moment in slab over all supports).

• The roof trusses must be fully anchored into the supporting RC ring beams. • The roof trusses must have horizontal cross bracing at the ceiling level as well as in

the planes of the rafters. Reinforcement to be used should be smooth bars fy=240/360 MPa with hooks on ends or ribbed bars fy=400/500 MPa with no hooks on ends. For multistory buildings reinforcement nets should be applied with fy=500/560 MPa for stairways, galleries and ceiling slabs because of easy and accurate installation. Concrete compressive strength should be fc>20 MPa for columns, stairways, beams, lintels, slabs. Concrete for pavements and floors can be of lower category. Based on schools structural survey findings, it can be concluded that most of damages caused by earthquakes occurred because of failure in applying appropriate building methods. Beside

Page 17: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 17 Lamia Maglic UNOPS Construction Engineer

technical properties for all materials to be used, determined in Technical Specification for each school reconstruction, following items should be especially considered: 4.6.3. RECOMMENDATIONS FOR PRE-CONSTRUCTION PHASE Design must comply with latest construction standards. Especially following items must be clearly determined and designed:

• Geological conditions on location of the school • Seismic and other structural calculations for the school • Reinforcement main bars and stirrups, positioning, diameters and clearances, • Details of reinforcement overlapping in junctions of structural members, • Details of reinforcement anchoring, • Dimensions of structural members (columns, beams, slabs, foundations, etc), • Concrete category for structural segments (compressive strength), • Schedule of works by phases, • Works Method Statement to be included for more complex works operations

4.6.4. RECOMMENDATIONS FOR CONSTRUCTION PHASE: 4.6.4.1. SUPERVISION OF WORKS Supervision of works as crucial activity that ensures compliance with design and required standards must provide following:

• Building diary is requested (daily input of all operations, tests and results, signed by Contractor and Supervisor, weekly by Project Manager).

• All phases of the works to be covered or back filled must be first checked and approved by supervisor in written.

• Check dimensions and levels of excavated foundation pits prior to next operation. • Check that all reinforcement bars or nets applied are as per design in terms of

dimensions, type, etc. prior to concrete pouring. • Check that all reinforcement bars or nets are properly positioned by spacers. (wooden

once not allowed), supervisor needs to approve positioned reinforcement and check stability of formwork before concrete pouring.

• Check vertical and horizontal position of structural elements (formwork) before and after concrete works (using appropriate devices).

• Supervision of all other operations as stated in Technical Specifications. 4.6.4.2. MATERIALS AND WORKMANSHIP Materials and construction practices stated in design must be applied during construction, following measures to be performed:

Page 18: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 18 Lamia Maglic UNOPS Construction Engineer

• All levels of foundations, beams, slabs, vertical and horizontal positions of structural elements and formwork must be obtained as per design.

• Reinforcement in dimensions, quality and quantity as per design, to be properly positioned in formwork. Reinforcement to be clean from dirt, rust and grease.

• Reinforcement overlapping and anchoring in junctions of structural members to be done as per design.

• Formwork must be oiled to prevent adhearance and damages of concrete during dismantling.

• Concrete needs to be properly mixed at least in 50 lit. mixer machine, not manually. • Structural segments to be constructed as one operation if possible. If not, preparation

for continuation of concrete pouring to be done. • Vibrators must be used for compaction of concrete in the formwork after pouring, to

ensure consolidation and prevent voids occurrence. • Wetting of concrete next 7 days after pouring, protect against direct sun. • Gravel from river or sea is not allowed to be mixed into concrete for structural

segments such as beams, columns, lintels, stairways, slabs etc. (can be allowed only for ground floor slab, outdoor pavements, access roads etc.).

• Other items as per Technical Specifications. 4.6.4.3. CERTIFICATION AND TESTING OF MATERIALS In order to ensure that applied materials and construction practices complies with design and required standards, following measures to be performed:

• All materials should be approved before installation (reinforcement steel, stone for concrete, bricks, wooden segments, roof sheeting, etc), need to have manufacturers attest or certificate of technical properties and origin.

• Concrete cubs 20x20x20cm in required number (or other dimensions samples, to be defined in Technical Specification) to be taken on site of making concrete to allow testing of concrete category after 28 days. Slump test of fresh concrete to be performed on site.

• All test results of completed works operations (soil compaction for foundations, depths of excavations, formwork positioning, etc) must be provided and filed.

• Other specific tests can be performed additionally if necessary, after completion of building or parts, assisted by authorized institution (Faculty for Civil Engineering, etc).

• Other items as per Technical Specifications.

Page 19: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 19 Lamia Maglic UNOPS Construction Engineer

5. CONCLUSION 5.1. LESSONS FROM RECENT DESTRUCTION The level of destruction on schools would have been much lower if the construction failures described under 4.3. had not occurred. The damages of school buildings in past Tsunami and earthquakes in Aceh Province and Nias were caused in part by design deficiencies but primarily by poor quality control, resulting in poor workmanship, the use of materials of poor quality, and improper and inadequate detailing. Further major contribution to the damages of buildings is the lack of maintenance, resulting in deterioration and reduced structural resistance. • Quality of workmanship must be improved because even with best materials applied the

construction quality will be poor after improper detailing. Such building will be more affected by earthquake and easily damaged or collapse. Structure must be “framed”, junctions of structural members must be firm, improved structural integrity will ensure better seismic resistance.

• Poor quality control is the result of insufficient awareness of for this crucial activity. This still happens despite experience from past earthquakes, whole construction cycle relies on knowledge of contractor on site. Although design has been improved to compy with latest standards, the wrong construction practices are applied again. This should be improved by proper quality control.

During the inspection of damaged schools, new ones under reconstruction were found with same failures as old ones. These were constructed by funds of NGO or DoE. Obviously, the lessons from recent events have not been entirely learnt.

Page 20: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 20 Lamia Maglic UNOPS Construction Engineer

ANNEXES

Page 21: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 21 Lamia Maglic UNOPS Construction Engineer

ANNEX 1: NEW CONSTRUCTION STANDARDS

Page 22: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 22 Lamia Maglic UNOPS Construction Engineer

Page 23: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 23 Lamia Maglic UNOPS Construction Engineer

Page 24: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 24 Lamia Maglic UNOPS Construction Engineer

Page 25: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 25 Lamia Maglic UNOPS Construction Engineer

ANNEX 2: PHOTOS OF TYPICAL DAMAGES ON SCHOOLS

Page 26: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 26 Lamia Maglic UNOPS Construction Engineer

SD Lhok Simelu Foundation beams junction insufficiently reinforced, junction of beams and masonry above broken.

SDN 070983 Sihareo Foundation beam insufficiently reinforced, beam and masonry above broken.

SDN 071002 Lolowua Foundation beam junction insufficiently reinforced, junction broken, masonry separated from column.

SDN 074050 Sawo Ring beam junction with column insufficiently reinforced, junction broken, masonry separated from column (column broken in lower section).

Page 27: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 27 Lamia Maglic UNOPS Construction Engineer

SDN 83 Banda Aceh Wall collapsed due to weak RC column, main reinforcement dia 6mm only and insufficient stirrups installed.

SDN 070983 Sihareo Collapse of masonry above window, no reinforced concrete lintel was constructed.

MIN UPT II Lamie Partition wall broken, too long and too high (8m/3,5m), there is no RC column in the middle nor RC lintel above opening.

SDN 076720 Maluo Ring beam insufficiently reinforced, broken, masonry broken and separated from column.

Page 28: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 28 Lamia Maglic UNOPS Construction Engineer

SDN 071223 Orahili Gomo Cross wall broken, too long and too high (8m/3,5m), central RC column broken, unable to prevent out-of plane bending effect of wall.

SDN 076070 Tugala Lauru Cross wall collapsed due to out-of plane bending effect, due to collapse of central RC column together with ring beam above.

SDN 078012 Mida Gable wall collapsed, there is no top RC beam over masonry nor RC column in the middle to frame the wall.

SMAN 7 Banda Aceh Gable wall collapsed, there is no top RC beam over masonry nor RC column in the middle to frame the wall. .

Page 29: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 29 Lamia Maglic UNOPS Construction Engineer

SDN 1 Tuwi Kareung Wooden structure with masonry, gaps in junctions with columns, masonry cracked.

SDN 071008 Gada Collapse of masonry, wooden columns moved from supports.

SDN 074056 Dahana Humene Wooden columns on rear facade moved from supports, weak bracing of columns to ring beam, building sloped.

SDN 075022 Mazingo Tabaloho Wooden column moved from support and sloped, masonry collapsed.

Page 30: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 30 Lamia Maglic UNOPS Construction Engineer

SDN 075083 Sihene'asi Wooden columns on front facade moved from supports, few columns broken, building sloped.

SDN 174052 Tulumbaho Wooden column moved from support and sloped, masonry broken.

SDN 071078 Hiliweto Wooden column moved from supports, entire wall sloped.

SDN 077295 Baruzo Bobozioli Wooden columns sloped due to deteriorated condition of wooden segments and junctions (rotten, no maintenance). Weak bracing, building exhausted close to collapse.

Page 31: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 31 Lamia Maglic UNOPS Construction Engineer

ANNEX 3:

PHOTOS OF TYPICAL DEFICIENCIES IN CONSTRUCTION

Page 32: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 32 Lamia Maglic UNOPS Construction Engineer

SDN 075087 Muzoi Too small main reinforcement diameter and too big clearance between stirrups in bottom of column, column collapsed.

SDN 075090 Sirombu Too small main reinforcement diameter and too big clearance between stirrups in bottom of column, column collapsed.

SDN 071061Tetehosi Idanoi Entire main reinforcement of column grouped in one corner (reduced active cross section), column collapsed.

SDN Maluo Incorrect extending of reinforcement of foundation beam (no overlapping but “hook to hook” tie, reinforcement out of concrete).

Page 33: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 33 Lamia Maglic UNOPS Construction Engineer

SDN 074050 Sawo Grouping of entire main reinforcement in the middle of ring beam in overlapping of reinforcement, ring beam broken.

SDN 071002 Lolowua Reinforcement of beam in not anchored into column, broken in junction with column.

.

SDN 071180 Iraono Gaila Collapsed beam with too small main reinforcement (diameter 6mm) and stirrups diameter 3mm only.

SDS Muhammadiyah Column broken in bottom and sloped, weak ring beam with insufficient reinforcement collapsed, resulting collapse of entire wall.

Page 34: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 34 Lamia Maglic UNOPS Construction Engineer

ANNEX 4 SURVEYED SCHOOLS BY DISTRICTS

Page 35: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 35 Lamia Maglic UNOPS Construction Engineer

District BANDA ACEH

No of students

No Name of school Address Sub-district Currently in use

Before Now

Safety condition:

Recommended activity

1 SDN 73 Labui Baiturrahman Yes 70 80 Parts unsafe Rehabilitation 2 SDN 43 Labui Baiturrahman Yes 166 176 Good Rehabilitation 3 SDN 30 Labui Baiturrahman Yes 67 67 Parts unsafe Reconstruction 4 SDN 53 Lueng Bata Lueng Bata Yes 183 242 Parts unsafe Rehabilitation 5 SDN 86 Lueng Bata Lueng Bata Yes 197 202 Parts unsafe Rehabilitation 6 SDN 85 Lueng Bata Lueng Bata Yes 178 220 Parts unsafe Rehabilitation 7 SDLB Banda

Aceh Labui Baiturrahman Yes 94 65 Good Rehabilitation

8 SDN 64 Ateuk Jawo Baiturrahman Yes 90 109 Parts unsafe Rehabilitation 9 SDN 15 Kuta Alam Kuta Alam Yes 240 279 Parts unsafe Rehabilitation 10 SDN 4 Kuta Alam Kuta Alam Yes 242 363 Parts unsafe Rehabilitation 11 SDN 44 Beurawe Kuta Alam Yes 129 128 Parts unsafe Rehabilitation 12 SDN 42 Peuniti Baiturrahman Yes 214 162 Unsafe Reconstruction

13 SDN 3 Peuniti Baiturrahman Yes 236 208 Parts unsafe Rehabilitation 14 SDN 14 Peuniti Baiturrahman Yes 111 92 Parts unsafe Rehabilitation 15 SDN 13 Peuniti Baiturrahman Yes 104 63 Parts unsafe Rehabilitation 16 SDN 33 Peuniti Baiturrahman In part 258 228 Parts unsafe Rehabilitation 17 SDN 41 Peuniti Baiturrahman Yes 132 100 Parts unsafe Rehabilitation 18 SDN 23 Peuniti Baiturrahman Yes 172 125 Parts unsafe Rehabilitation 19 SDN 12 Peuniti Baiturrahman Yes 157 97 Good Rehabilitation 20 SDN 93 Lamtemen

Timur Meuraxa Yes 303 182 Parts unsafe Rehabilitation

21 SDN 97 Lamtemen Timur

Meuraxa No 168 0 Parts unsafe Rehabilitation

22 SDN 29 Blower Baiturrahman In part 300 230 Parts unsafe Rehabilitation 23 SDN 50 Lamlagang Banda Raya In part 423 447 Unsafe Reconstruction

24 SDN 63 Lamlagang Banda Raya Yes 173 188 Parts unsafe Rehabilitation 25 SD Katolik Karya

Budi Kampung Baru

Baiturrahman In part 209 53 Parts unsafe Rehabilitation

26 SDN 68 Lamgugob Syiah Kuala Yes 75 83 Parts unsafe Rehabilitation 27 SLB Bukesra Doi Ulee Kareng Yes 50 30 Parts unsafe Rehabilitation 28 SDN 76 Doi Ulee Kareng Yes 100 210 Parts unsafe Rehabilitation 29 SMPN 5 Banda

Aceh Cot Lamkewuh

Meuraxa No 0 Not for use Reconstruction

30 SMPN 11 Banda Aceh

Blang Oi Meuraxa No 0 Destroyed Reconstruction

31 SMPN 2 Banda Aceh

Lamprit Kuta Alam In part 1.015 594 Parts unsafe Rehabilitation

32 SMPS Keumala Bhayangkari

Laniteumen Barat

Jaya Baru Yes 108 76 Parts unsafe Rehabilitation

33 SMPN 1 Banda Aceh

Blang Padang

Meuraxa No 0 Not for use Reconstruction

34 SMPN 6 Banda Aceh

Lampineung Kuta Alam In part 900 750 Parts unsafe Reconstruction

35 SMPN 8 Banda Aceh

Darussalam Syiah Kuala Yes 658 622 Good Rehabilitation

Page 36: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 36 Lamia Maglic UNOPS Construction Engineer

36 SMPN 14 Banda Aceh

Alue Naga Syiah Kuala No 0 Destroyed Reconstruction

37 SMPS Islam Jambo Tape Kuta Alam In part 160 120 Good Rehabilitation 38 SMPS Metodist Kampong

Mulia Kuta Alam In part 178 156 Good Rehabilitation

39 SMPN 4 Banda Aceh

Peunayong Kuta Alam No 0 Not for use Reconstruction

40 SMPN 9 Banda Aceh

Peunayong Kuta Alam No 0 Not for use Reconstruction

41 SMPN 16 Banda Aceh

Kampung Mulia

Kuta Alam No 0 Not for use Reconstruction

42 SMPN 12 Banda Aceh

Gampong Jawa

Kuta Raja No 0 Not for use Rehabilitation / Reconstruction

43 SMPS Inshafuddin

Lamprit Kuta Alam In part 300 75 Parts unsafe Rehabilitation

44 SMPN 17 Banda Aceh

Blang Padang

Baiturrahman In part 864 790 Good Rehabilitation

45 SMPS Muhammadiyah

Lampaseh Kuta Raja No 0 Not for use Reconstruction

46 SMPS Iskandar Muda

Lampaseh Kuta Raja No 0 Destroyed Reconstruction

47 SMPN 15 Banda Aceh

Lamjame Jaya Baru No 0 Destroyed Reconstruction

48 SMPLB YPAC Kampung Mulia

Kuta Alam No 0 Not for use Rehabilitation / Reconstruction

49 SDN 31 Banda Aceh

Punge Blang Cot

Meuraxa Yes 87 20 Good Rehabilitation

50 SDN 2 Banda Aceh

Punge Jurong

Meuraxa No 0 Not for use Reconstruction

51 SDN 90 Banda Aceh

Cot Lam Keoh

Meuraxa No 116 0 Destroyed Reconstruction

52 SDN 92 Banda Aceh

Dayah Baro Meuraxa No 125 0 Destroyed Reconstruction

53 SDN 25 Banda Aceh

Lamprit Kuta Alam Yes 200 58 Good Rehabilitation

54 SDN 35 Banda Aceh

Lamprit Kuta Alam Yes 152 50 Parts unsafe Rehabilitation

55 SDN 27 Banda Aceh

Kampung Mulia

Kuta Alam No 0 Destroyed Reconstruction

56 SDN 37 Banda Aceh

Kampung Mulia

Kuta Alam No 0 Destroyed Reconstruction

57 SDN 28 Banda Aceh

Kampung Kramat

Kuta Alam Yes 97 159 Parts unsafe Rehabilitation

58 SDN 36 Banda Aceh

Kampung Laksana

Kuta Alam Yes 216 145 Good Rehabilitation

59 SDN 24 Banda Aceh

Lampineung Kuta Alam Yes 302 296 Parts unsafe Rehabilitation

60 SDN 34 Banda Aceh

Lampineung Kuta Alam Yes 270 305 Good Rehabilitation

61 MIN Rukoh Rukoh Darussalam Yes 355 200 Parts unsafe Rehabilitation 62 SDN 7 Banda

Aceh Blang Padang

Kuta Raja No 0 Destroyed Reconstruction

63 SDN 75 Banda Aceh

Lamteumen Timur

Jaya Baru Yes 225 180 Good Rehabilitation

Page 37: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 37 Lamia Maglic UNOPS Construction Engineer

64 MIN Teladan Banda Aceh

Lamteumen Barat

Jaya Baru In part 1340 813 Parts unsafe Rehabilitation

65 SMAN 7 Banda Aceh

Geucu Inem Banda Jaya In part 1200 800 Parts unsafe Rehabilitation / Reconstruction

66 SMAN 1 Banda Aceh

Punge Jurong

Meuraxa In part 1132 920 Good Rehabilitation

67 SMAN 3 Banda Aceh

Lamprit Kuta Alam In part 1600 1500 Good Rehabilitation

68 SMAN 4 Banda Aceh

Lampineung Kuta Alam In part 1427 1261 Parts unsafe Rehabilitation

69 SMAN 8 Banda Aceh

Lampineung Kuta Alam In part 883 718 Parts unsafe Rehabilitation

70 SMAN 5 Banda Aceh

Darussalam Syiah Kuala In part 1132 970 Parts unsafe Rehabilitation / Reconstruction

71 MIN Banda Aceh Kampung Kramat

Kuta Alam In part 1663 1300 Parts unsafe Rehabilitation

72 MIN Merduati Kampung Kramat

Kuta Alam No 0 Not for use Reconstruction

73 SMAN 9 Banda Aceh

Lhong Raya Banda Raya In part 480 480 Parts unsafe Rehabilitation / Reconstruction

74 SMAN 10 Banda Aceh

Ateuk Jawo Baiturrahman Yes 164 153 Parts unsafe Rehabilitation

75 SMKN 3 Banda Aceh

Lampineung Kuta Alam In part 563 230 Good Rehabilitation

76 SDN 6 Banda Aceh

Keudah Kuta Raja No 0 Destroyed Reconstruction

77 SDN 102 Banda Aceh

Lamdi Kuta Alam No 0 Destroyed Reconstruction

78 SDN 106 Banda Aceh

Lamarh Rukoh

Syiah Kuala No 66 0 Destroyed Reconstruction

79 SDN 83 Banda Aceh

Rukoh Syiah Kuala No 180 0 Not for use Reconstruction

80 SDN 109 Banda Aceh

Cot Lam Keuh

Meuraxa No 0 Destroyed Reconstruction

81 SDN 95 Banda Aceh

Gampong Baro

Meuraxa No 0 Destroyed Reconstruction

82 SDN 59 Banda Aceh

Betai Jaya Baru No 0 Destroyed Reconstruction

83 SMKN 1 Banda Aceh

Lampineung Kuta Alam In part 880 431 Parts unsafe Rehabilitation

84 SMKN 2 Banda Aceh

Lampineung Kuta Alam In part 1400 850 Parts unsafe Rehabilitation / Reconstruction

85 SDN 5 Setui Baiturrahman In part 205 218 Parts unsafe Rehabilitation / Reconstruction

86 SDN 16 Setui Baiturrahman Yes 222 230 Good Rehabilitation 87 SDN 51 Geucu

Meunara Jaya Baru Yes 280 300 Parts unsafe Rehabilitation

88 SDN 22 Neusu Baiturrahman Yes 250 234 Good Rehabilitation 89 SDN 26 Neusu Baiturrahman Yes 224 233 Good Rehabilitation 90 SDN 77 Neusu Baiturrahman Yes 135 170 Parts unsafe Rehabilitation 91 MIN Setui Setui Meuraxa Yes 304 265 Good Rehabilitation 92 SDN 32 Beurawe Kuta Alam Yes 213 248 Good Rehabilitation 93 SDN 56 Lam

Glumpang Ulee Kareng Yes 289 490 Parts unsafe Rehabilitation

94 MIN Lambhuk Lambhuk Lambhuk Yes 490 473 Good Rehabilitation

Page 38: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 38 Lamia Maglic UNOPS Construction Engineer

95 SDN 104 Lamteh Ulee Kareng Yes 200 250 Parts unsafe Rehabilitation 96 SDN 66 Ilie Ulee Kareng Yes 185 132 Good Rehabilitation 97 SDN 110

Percontoh Lamlagang Banda Raya Yes 360 357 Parts unsafe Reconstruction

98 SDN 108 Lhong Cut Banda Raya Yes 184 210 Parts unsafe Rehabilitation 99 SDN 40 Neusu Jaya Baiturrahman Yes 172 191 Good Rehabilitation

100 SDN 96 Neusu Aceh Baiturrahman Yes 114 150 Unsafe Reconstruction 101 SDN 55 Kp. Pineung Syiah Kuala Yes 91 135 Good Rehabilitation 102 SDN 82 Rukoh Syiah Kuala Yes 400 549 Good Rehabilitation 103 SDN 105 Ceurih Ulee Kareng Yes 184 214 Good Rehabilitation 104 MIN Ulee Kareng Iemasen Ulee Kareng Yes 717 780 Parts unsafe Rehabilitation 105 SDN 52 Banda

Aceh Peunyerat Banda Raya In part 60 50 Parts unsafe Rehabilitation

106 SDN Persit 1 Bandar Baru Kuta Alam In part 615 535 Good Rehabilitation 107 SDN 18 Banda

Aceh Punge Blang Cot

Jaya Baru No 200 0 Not for use Reconstruction

District ACEH BESAR

No of students

No Name of school Address Sub-district Currently in use

Before Now

Safety condition:

Recommended activity

1 SDN Lampeneurut

Lampeneurut Darul Imarah In part 440 597 Parts unsafe Reconstruction

2 MIN Jeumpet Jeumpet Darul Imarah Yes 100 120 Parts unsafe Rehabilitation 3 MIN Keutapang II Lambheu Darul Imarah In part 230 250 Parts unsafe Rehabilitation 4 SD Neusok

Teubaluy Neusok Darul Kamal Yes 130 179 Parts unsafe Rehabilitation

5 SD Blang Kiree Blang Kiree Darul Kamal Yes 123 153 Parts unsafe Rehabilitation 6 SDN Ladong Ladong Mesjid Raya In part 200 190 Parts unsafe Rehabilitation 7 SD Perumnas

Neuheun Kompleks Perumnas Neuheun

Mesjid Raya Yes 315 427 Good Rehabilitation

8 SDN Cot Bambu Babah Jurong

Kuta Baro Yes 108 115 Parts unsafe Rehabilitation

9 SD Ateuk Lampoh keude

Kuta Baro Yes 139 161 Good Rehabilitation

10 MIN Bung Cala Lambrobileue Kuta Baro In part 700 757 Parts unsafe Rehabilitation 11 SDN Lambrabo Beurangong Kuta Baro In part 60 110 Parts unsafe Rehabilitation 12 SDN Buengcala Seupeu Kuta Baro Yes 251 113 Parts unsafe Rehabilitation 13 SD Lamtamot Lamtamot Lembah

Seulawah In part 75 83 Parts unsafe Reconstruction

14 MIN Lamteuba Lambada Seulimeum Yes 120 137 Good Rehabilitation 15 SD I Lamteuba Lamteuba

Dro Seulimeum Yes 483 527 Good Rehabilitation

16 SD Meureu Mureu Baro Indrapuri Yes 265 247 Parts unsafe Rehabilitation 17 MIN Meureu Mureu Lam

Glumpang Indrapuri Yes 300 330 Parts unsafe Rehabilitation

Page 39: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 39 Lamia Maglic UNOPS Construction Engineer

18 SD Lam Birah Lam Birah Suka Makmur

Yes 77 85 Unsafe Reconstruction

19 SD Bira Cot Bira Cot Montasik Yes 117 127 Parts unsafe Rehabilitation 20 SD Lhok Simelu Kayee

Kunyet Montasik Yes 281 331 Parts unsafe Rehabilitation

21 SD Rumpet Rumpet Krueng Barona Jaya

Yes 60 76 Parts unsafe Rehabilitation

22 MIN Miruek Miruek Taman

Darussalam Yes 300 320 Good Rehabilitation

23 SD Kulam Data Lam Ateuk Lhok Nga Yes 70 90 Good Rehabilitation 24 MIS Al-Istiqamah Kueh Lhok Nga Yes 90 167 Good Rehabilitation 25 SMP 2 Lhoong Tanah Ano Lhoong No 0 Destroyed Reconstruction 26 SMP 1 Lhoong Blang Me Lhoong No 0 Destroyed Reconstruction 27 SMP 3 Lhoong Gleu Bruk Lhoong No 0 Destroyed Reconstruction 28 SMP 1 Lhoknga Pasar

Lhoknga Lhoknga No 0 Destroyed Reconstruction

29 SMP 2 Lhoknga Lampuuk Lhoknga No 0 Destroyed Reconstruction 30 SMP 1 Peukan

Bada Peukan Bada Peukan Bada No 0 Destroyed Reconstruction

31 SMP 2 Peukan Bada

Peukan Bada Peukan Bada No 0 Destroyed Reconstruction

32 SMP 3 Lhoknga Keude Bieng Lhoknga Yes 49 78 Good No activity 33 SMP 3 Ingin Jaya Siron Ingin Jaya In part 580 685 Parts unsafe Rehabilitation /

Reconstruction 34 SMP 1

Baitussalam Kajhu Baitussalam No 0 Destroyed Reconstruction

35 SMP 2 Seulimeum

Desa Ateuk Lamteuba

Seulimeum In part 235 240 Parts unsafe Rehabilitation

36 SD Pertiwi Lamgarot

Siron Ingin Jaya Yes 164 322 Parts unsafe Rehabilitation

37 SD Meunasah Tutong

Meunasah Tutong

Ingin Jaya Yes 135 208 Unsafe Reconstruction

38 SD Kayee Leeu Kayee Leeu Ingin Jaya Yes 78 145 Parts unsafe Rehabilitation 39 SD Jeumpet Jeumpet Darul Imarah Yes 175 265 Good No activity 40 SD Capeung Capeung Seulimeum In part 155 161 Unsafe Rehabilitation /

Reconstruction 41 SD Sibreh Sibreh

Keumudee Suka Makmur

Yes 320 405 Parts unsafe Rehabilitation

42 SDN Krueng Raba

Krueng Raba Lhoknga No 0 Destroyed Reconstruction

43 SD Dham Cukok Dham Cukok Ingin Jaya Yes 142 150 Parts unsafe Rehabilitation 44 SD Dham Lubok Lubok Ingin Jaya Yes 164 208 Good Rehabilitation 45 MIN Lamjampok Lamjampok Ingin Jaya Yes 126 250 Good Rehabilitation 46 SDN 1 Pagar Air Pagar Air Ingin Jaya Yes 140 203 Good Rehabilitation 47 SD 1 Lamcot Lamcot Darul Imarah In part 150 157 Parts unsafe Rehabilitation 48 SDN 2 Lamcot Lamreung Darul Imarah Yes 110 116 Parts unsafe Rehabilitation 49 SD Lam Sayeung Lam

Sayeung Ingin Jaya Yes 153 208 Good No activity

50 SD Mesjid Leu Desa Lagang Darul Imarah Yes 150 175 Good Rehabilitation 51 MIN Cot Gue Lam Kawe Darul Imarah In part 360 385 Good Rehabilitation 52 SDN Kandang

Cut Desa Kandang

Darul Imarah Yes 103 157 Parts unsafe Rehabilitation / Reconstruction

53 SD Lamthen Deunong Darul Imarah Yes 115 145 Parts unsafe Rehabilitation

Page 40: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 40 Lamia Maglic UNOPS Construction Engineer

54 SDN Lam Kunyet Lam Kunyet Darul Imarah Yes 270 302 Parts unsafe Rehabilitation / Reconstruction

55 MIN Biluy Desa Biluy Darul Imarah In part 230 255 Parts unsafe Rehabilitation 56 SD Lamteungoh Lamteungoh Ingin Jaya Yes 214 220 Parts unsafe Rehabilitation 57 SD Gani Bueng

Ceukok Ingin Jaya Yes 247 267 Parts unsafe Rehabilitation

1-Cot Meuraja

78 1-Good Rehabilitation 58 SD Cot Meuraja

2- Cot Karing

Ingin Jaya Yes 308

320 2-Unsafe Reconstruction 59 SD Ajee Rayek Ajee Rayek Ingin Jaya Yes 75 83 Good Rehabilitation 60 MIN Bukloh Bukloh Suka

Makmur Yes 223 238 Parts unsafe

Rehabilitation 61 SDN Blang

Bintang Cot Mon Raya

Kuta Baro Yes 128 139 Good Rehabilitation

62 SD Iam Jampok Lambada Ingin Jaya Yes 96 107 Good Rehabilitation 63 SD Seumet Seumet Montasik In part 112 120 Unsafe Reconstruction 64 MIN Jeurela I Lambaro

Sibreh Suka Makmur

Yes 290 338 Parts unsafe Rehabilitation

Seumer Eung Yes 215 Parts unsafe Rehabilitation

65 MIN Jeurela II

Tampok Blang

Suka Makmur In part 266 60 Parts unsafe Rehabilitation

66 SDN 1 Seulimum Pasar Seulimum

Seulimeum Yes 330 365 Good Rehabilitation

67 SD Seunebok Seunebok Seulimeum Yes 137 240 Good Rehabilitation 68 SD 1 Tanoh

Abee Lampisang Seulimeum Yes 217 221 Parts unsafe Rehabilitation

69 SD Banda Safa Banda Safa Kota Cot Glie Yes 166 172 Good Rehabilitation 70 MIN Tungkop Tungkop Darussalam Yes 866 905 school under

construction No activity

71 SDN Lamklat Lieue Darussalam Yes 170 220 Good Rehabilitation 72 SDN Siem Lambiheue

Siem Darussalam Yes 215 265 Good Rehabilitation

73 SDN Lambaro Angan

Lambada Peukan

Darussalam Yes 100 120 Good Rehabilitation

74 SD Data Gaseu Data Gaseu Seulimeum In part 138 138 Parts unsafe Rehabilitation 75 SD 7 Jantho Bukit Mewara Kota Jantho Yes 110 220 Good Rehabilitation 76 SD 6 Kota Jantho Jantho Baru Kota Jantho In part 105 165 Good Rehabilitation 77 MIN Kota Jantho Jantho

Makmur Kota Jantho Yes 203 255 Good Rehabilitation

78 SD 3 Kota Jantho Teurebah Kota Jantho Yes 68 120 Good Rehabilitation 79 SDN Tanjong

Selamat Tanjong Selamat

Darussalam Yes 77 100 Good Rehabilitation

80 SDN Kuta Bakmee

Tanjong Deah

Darussalam Yes 83 87 Good Rehabilitation

81 SD Cot Angan Cot Angan Darussalam Yes 85 124 Good Rehabilitation 82 SDN Garot

Geuceu Garot Darul Imarah Yes 104 132 Parts unsafe Rehabilitation

83 SD 2 Jeumpet Lampasi Engking

Darul Imarah Yes 76 120 Good Rehabilitation

84 SDN 1 Lambheu Lambheu Darul Imarah Yes 263 350 Parts unsafe Reconstruction 85 SDN 2 Lambheu Lambheu Darul Imarah Yes 186 223 Good Rehabilitation

Page 41: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 41 Lamia Maglic UNOPS Construction Engineer

86 SD Simpang Kramat

Cot Rumpun Montasik Yes 78 78 Parts unsafe Reconstruction

87 MIN Montasik Lampaseh Lhok

Montasik Yes 340 355 Good Rehabilitation

88 SD Montasik Lamnga Montasik Yes 113 169 Good Rehabilitation 89 SD Cot

Meuntiwan Cot Meuntiwan

Ingin Jaya Yes 80 85 Parts unsafe Rehabilitation

90 SDN Meulayo Cot Puklat Kuta Baro In part 94 140 Parts unsafe Rehabilitation / Reconstruction

91 SD 2 Mata Ie Mata Ie Darul Kamal Yes 160 220 Good Rehabilitation 92 MIN Punie Punie Darul Imarah Yes 150 162 Parts unsafe Rehabilitation 93 SD 1 Mata Ie Ulee Tuy Darul Imarah Yes 122 146 Parts unsafe Rehabilitation 94 SDN Gue Gajah Gue Gajah Darul Imarah Yes 120 330 Good Rehabilitation 95 SD Pulot Leupung Leupung No 0 Destroyed Reconstruction 96 SDN Layeun Layeun Leupung No 0 Destroyed Reconstruction 97 SD Keude Bing Lam Gaboh Lhok Nga Yes 160 273 Good Rehabilitation 98 MIN Lhoknga Lamkruet Lhoknga temp.school 369 137 Destroyed Reconstruction 99 SDN 2 Tanjong Nusa Lhok Nga Yes 106 140 Good Rehabilitation

100 SDLB Neg Kota Jantho

Jantho Makmur

Kota Jantho Yes 46 46 Unsafe Reconstruction

101 SD 4 Kota Jantho Blang Awek Kota Jantho In part 89 89 Parts unsafe Rehabilitation 102 SD 1 Kota Jantho Jantho Kota Jantho In part 95 95 Parts

destroyed Rehabilitation / Reconstruction

103 SD 2 Kota Jantho Jantho Makmur

Kota Jantho Yes 229 281 Good Rehabilitation

104 SD 5 Kota Jantho Baroh Kota Jantho Yes 56 56 Good Rehabilitation 105 SD Ulee Kareeng Gue Gajah Kuta Baro Yes 72 87 Good No activity 106 SD Ateuk Anggok Ateuk

Anggok Kuta Baro Yes 116 137 Good Rehabilitation

107 SD Gla Meunasah Baro

Lampermai Krueng Barona Jaya

Yes 94 109 Good Rehabilitation

108 SD Lamreung Ateuk Anggok

Krueng Barona Jaya

Yes 356 420 Parts unsafe Rehabilitation / Reconstruction

109 SD Lamnga Lamnga Mesjid Raya No 230 0 Destroyed Reconstruction 110 SD 1 Glee Bruek Glee Bruek Lhong No 0 Destroyed Reconstruction 111 MIN Lhong Keutapang Lhong Yes 220 208 Good Rehabilitation 112 SD Lamsujen Lamsujen Lhong Yes 65 55 Good No activity 113 SD Monmata Lamjuhang Lhong Yes 110 113 Parts unsafe Rehabilitation 114 SD Cundien Lamsujen Lhong No 0 Destroyed Reconstruction 115 SDN Krueng Kala Tunong-

Krueng Kala Lhong No 0 Destroyed Reconstruction

116 SD Abulyatama Lampoh Keude

Lampoh Keude

Yes 111 152 Unsafe Reconstruction

117 SDN Cot Preh Cot Preh Kuta Baro Yes 126 200 Good Rehabilitation 118 MIN Lamrabo Beurangong Kuta Baro Yes 248 262 Good Rehabilitation 119 MIN Indrapuri Pasar Lama

Indrapuri Indrapuri Yes 250 261 Good Rehabilitation

120 SDN 1 Indrapuri Pasar Indrapuri

Indrapuri In part 156 156 Good Rehabilitation

121 SDN 2 Indrapuri Lheue Indrapuri Yes 53 53 Parts unsafe Rehabilitation 122 SDN Sukadamai Sukadamai Lembah

Seulawah In part 125 129 Good Rehabilitation

Page 42: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 42 Lamia Maglic UNOPS Construction Engineer

123 SDN Desa Teuladan

Desa Teuladan

Lembah Seulawah

In part 250 257 Good Rehabilitation

124 SDN Bak Sukon Lam Leot Cuta Cot Glie Yes 135 135 Parts unsafe Reconstruction 125 SDN Ie Suuem Ie Suuem Mesjid Raya Yes 94 94 * Good Reconstruction 126 SDN Leupueng

26 Cot Raya Kuta Baro Yes 320 360 Good Rehabilitation

127 SDN Lam Ujong Meunasah Baet

Krueng Barona Jaya

Yes 108 108 Parts unsafe Reconstruction

128 SDN Leungah Desa Leungah

Seulimeum Yes 150 150 * Good Rehabilitation / Reconstruction

129 SDN Blang Lambaro

Blang Lambaro

Seulimeum In part 40 40 Good Rehabilitation

130 SDN 2 Lampaseh Alue Montasik Yes 109 102 Good Rehabilitation 131 SDN 1 Lampaseh Bampong

Baro Montasik Yes 120 105 Parts unsafe Rehabilitation /

Reconstruction 132 SDN Bung Simek Bung Simek Kuta Cot Glie Yes 112 123 Good Rehabilitation 133 SDN Siron Siron Kuta Cot Glie Yes 70 70 * Good Reconstruction 134 SDN 8 Jantho Suka Tani Kuta Jantho Yes 40 37 Good Rehabilitation 135 SDN Suhom Tunong-

Krueng Kala Lhoong Yes 86 103 Good Rehabilitation

136 SDN Cot Jeumpa Cot Jeumpa Lhoong Yes 155 60 Parts unsafe Rehabilitation / Reconstruction

District ACEH BARAT

No of students

No Name of school Address Sub-district Currently in use

Before Now

Safety condition:

Recommended activity

1 MIN Putim Putim Kaway XVI Yes 97 107 Good Rehabilitation 2 SDN Cot Trueng Meunasah

Rambut Kaway XVI Yes 106 120 Good Rehabilitation

3 SDN Pungkie Pungkie Kaway XVI In part 149 159 Good Rehabilitation 4 SDN Alue Peudeung Alue

Peudeung Kaway XVI Yes 120 123 * Good Reconstruction

5 SDN Pasi Teungoh Pasi Teungoh

Kaway XVI Yes 118 132 Good Rehabilitation

6 SDN Kuala Bubon Kuala Bubon Samatiga No 0 Destroyed Reconstruction 7 SDN Layung

Beurawang Beurawang Bubon Yes 135 142 * Good Reconstruction

8 SDN Seumeuleng Kuala Pling Bubon In part 130 140 * Good Reconstruction 9 SDN Peulantee Peulantee Bubon In part 150 160 Good Rehabilitation

10 MIN Suak Siron Suak Siron Samatiga No 0 Destroyed Reconstruction 11 MIS Suak Trieng Suak Trieng Woyla Induk Yes 57 53 Good Rehabilitation 12 SDN Kuala Bhee Kuala Bhee Woyla Induk Yes 137 157 * Good Reconstruction 13 MIN Kuala Bhee Kuala Bhee Woyla Induk Yes 112 137 Good Rehabilitation 14 MIS Peulanteu

Lambalek Ujong Simpang

Arongan Lambalek

In part 74 72 Part collapsed

Reconstruction

15 SDN Drien Rampak Drien Rampak

Arongan Lambalek

In part 100 120 Good Rehabilitation

Page 43: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 43 Lamia Maglic UNOPS Construction Engineer

16 SDN Luengtanoh Tho Luengtanoh Tho

Woyla Induk Yes 260 285 * Good Reconstruction

17 SDN Pasi Mali Pasi Mali Woyla Barat In part 200 170 Parts unsafe Reconstruction 18 SDN Keuleumbah Keuleumbah Woyla

Tengah In part 150 160 Parts unsafe Reconstruction

19 SDN 1 Bubon Cot Seumeureng

Samatiga Yes 90 200 Good Rehabilitation

20 SDN 18 Meulaboh Jl. Nasional Meulaboh

Johan Pahlawan

Yes 298 242 Good Rehabilitation

21 SDN 9 Meulaboh Jl. Nasional Meulaboh

Johan Pahlawan

Yes 255 170 Good Rehabilitation

22 SDN 15 Meulaboh Jl. Nasional Meulaboh

Johan Pahlawan

Yes 292 266 Part collapsed

Reconstruction

23 SDN 13 Meulaboh Bakti Pemuda

Johan Pahlawan

Yes 250 40 Good Rehabilitation

24 SDN Alue Kuyun Alue Kuyun Woyla Timur

In part 129 110 Parts unsafe Reconstruction

25 SDN Lancong Sarah Perlak Sungai Mas In part 139 156 * Good Reconstruction

26 SDN Tuwi Saya Geudong Sungai Mas Yes 34 60 Good Rehabilitation

27 SDN Paya II Paya Dua Woyla Induk In part 108 124 * Good Reconstruction

28 SDN Meunuwang Kinco

Meunuwang Kinco

Pante Cermin

In part 156 130 * Good Reconstruction

29 SDN Alue Keumang Alue Keumang

Pante Cermin

In part 58 70 * Good Reconstruction

30 SDN LB Drien Rampak

Johan Pahlawan

In part 25 24 Good Rehabilitation

31 SDN Gampong Mesjid

Gampong Mesjid

Kaway XVI Yes 26 28 * Good Reconstruction

32 MIN Paya Lumpat Paya Lumpat Samatiga Yes 87 115 * Good Rehabilitation / Reconstruction

33 MIS Pribu Pribu Arongan Lam Balek

In part 225 123 Unsafe Reconstruction

34 SDN Cot Buloh Cot Buloh Arongan Lam Balek

Yes 124 167 Good Rehabilitation

35 SDN UPT II Cot Lagan

Cot Lagan Woyla Barat In part 77 72 * Good Rehabilitation / Reconstruction

36 SDN UPT III Batee Puteh

Alue Perman Woyla Barat Yes 65 92 Good Rehabilitation

37 SDN UPT I Krueng Hampa

Krueng Hampa

Woyla Barat No 120 0 Destroyed Reconstruction

38 SDN UPT IV Alue Keumang

Alue Keumang

Woyla Barat No 114 0 Good Rehabilitation

39 SDN Kajeung Kajeung Sungai Mas In part 160 151 Parts destroyed

Rehabilitation / Reconstruction

40 SDN Tanoh Mirah Tanoh Mirah Sungai Mas In part 98 108 Parts destroyed

Rehabilitation / Reconstruction

41 SDN Tungkop Tungkop Sungai Mas Yes 78 70 Good Rehabilitation 42 SDN Alue Lhee Alue Lhee Kaway XVI Yes 76 20 * Good Rehabilitation /

Reconstruction 43 SDN UPT I Kutatuha Bukit Jaya Meurobo Yes 120 167 Good Rehabilitation

Page 44: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 44 Lamia Maglic UNOPS Construction Engineer

44 SDN UPT I Alue Peunyareng

Bukit Jaya Meurobo No 92 0 Destroyed Reconstruction

45 SDN UPT II Sumber Batu

Sumber Batu Meurobo In part 103 60 * Good Rehabilitation / Reconstruction

46 SDN UPT III Anoe Puteh

Blang Genang

Meurobo Yes 117 42 * Good Reconstruction

47 SDN Pasi Aceh Pasi Aceh Woyla Induk Yes 150 157 Good Rehabilitation 48 SDN Cot Punti Pasi Janeng Woyla

Timur Yes 135 125 Good Rehabilitation

49 SDN Kampong Baro Manggi

Gunong Mata Ie

Kaway XVI Yes 97 106 * Good Reconstruction

50 SDN Blang Teungoh Blang Teungoh

Kaway XVI No 85 0 Destroyed Reconstruction

51 SDN Gleng Gleng Sungai Mas Yes 99 110 Good Rehabilitation 52 SD Alue Peuniareng II

(SDN Transloak SP6) Sumber Batu Meurobo No 118 0 Destroyed Reconstruction

53 SDN Reudeup Reudeup Meurobo Yes 100 150 Parts unsafe Reconstruction District NAGAN RAYA

No of students

No Name of school Address Sub-district Currently in use

Before Now

Safety condition:

Recommended activity

1 SDN Sikabu Sikabu Seunagan Yes 128 116 Good Rehabilitation 2 MIN Blang

Teungoh Blang Teungoh

Seunagan Yes 130 180 * Good Reconstruction

3 MIN Parom Parom Seunagan In part 150 130 Good Rehabilitation 4 SDN Keude

Neulop Keude Neulop

Seunagan Yes 69 62 * Good Reconstruction

5 MIN Suka Raja Suka Raja Darul Makmur Yes 173 250 Unsafe Reconstruction 6 SDN Krueng

Seumayam Krueng Seumayam

Darul Makmur In part 190 197 Good Rehabilitation

7 MIN UPT II Lamie Rantao Selamat

Kuala In part 130 103 Parts unsafe Reconstruction

8 SD Dayah Dayah Beutong Yes 146 162 * Good Reconstruction 9 SD 2 Nigan Nigan Seunagan Yes 245 245 Good Rehabilitation 10 SDN Krueng

Buloh 1 Baturaja Kuala No 220 0 Good Rehabilitation

11 SDN Krueng Buloh 2

Baturaja Kuala No 253 0 Good Rehabilitation / Reconstruction

12 SDN Gunong Geulugu

Gunong Geulugu

Kuala In part 63 79 Parts unsafe Reconstruction

13 SDN Tadu Ateuh Gunong Sapek

Kuala Yes 60 50 * Good Reconstruction

14 SDN Karang Anyar

Karang Anyar

Darul Makmur Yes 302 327 Good Rehabilitation

15 SDN UPT IV Seuneuam

Sumber Bakti

Darul Makmur In part 308 308 Good Rehabilitation

16 SDN Panton Bayu Panton Bayu

Darul Makmur Yes 150 177 Good Rehabilitation / Reconstruction

Page 45: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 45 Lamia Maglic UNOPS Construction Engineer

17 SDN Kuala Seymayam

Kuala Seymayam

Darul Makmur No 63 0 Reconstruction ongoing 1GF

Rehabilitation

18 SDN Pulo Teungoh 1

Pulo Teungoh

Darul Makmur Yes 191 200 Good Rehabilitation

19 SDN Gunong Kong

Alue Waki Darul Makmur Yes 177 172 Good Rehabilitation

20 SDN Pulo Raga Pulo Raga Beutong Yes 96 106 Good Rehabilitation 21 SDN Blang Dalam Blang

Dalam Beutong Yes 119 126 Good Rehabilitation

22 MIN Gunong Reubo

Gunong Reubo

Kuala Yes 125 95 * Good Reconstruction

District ACEH JAYA

No of students No Name of school Address Sub-district Currently in use Before Now

Safety condition:

Recommended activity

1 SDN Pasie Timon

Pasie Timon

Teunom Yes 79 85 Good Rehabilitation

2 SDN Pulo Tinggi Pulo Tinggi Teunom Yes 150 176 Good Rehabilitation 3 SDN Pasie

Teubee Pasie Teubee

Teunom In part 245 337 Parts unsafe Reconstruction

4 SDN Padang Kleng

Padang Kleng

Teunom In part 270 290 Parts unsafe Reconstruction

5 SDN Lhok Bot Lhok Bot Setia Bakti Yes 40 50 Parts unsafe Reconstruction 6 SDN Tuwi

Kareung 1 Lhok Guli Teunom No 210 196 Parts unsafe Reconstruction

7 SDN Bunta Bunta Krueng Sabee

Yes 150 100 * Good Reconstruction

8 SDN Panggong Panggong Krueng Sabee

No 80 0 Good Rehabilitation

9 SDN Rantau Panjang

Rantau Panjang

Krueng Sabee

Yes 90 93 * Good Reconstruction

10 SDN Paya Seumantok

Paya Seumantok

Krueng Sabee

No 206 182 * Good Reconstruction

11 MIS Tuwi Kareung

Tuwi Kareung

Teunom Yes 117 91 Parts destroyed

Reconstruction

12 MIN Alue Jang Ceuracee Teunom Yes 125 90 * Good Reconstruction 13 MIN Panga

Pucok Twi Kayee Panga Yes 200 180 Good Rehabilitation

14 MIN Tuwi Eumpeuk

Tuwi Eumpeuk

Panga Yes 150 160 Parts unsafe Rehabilitation / Reconstruction

15 SDS Panton Krueng

Panton Krueng

Panga In part 57 65 Parts not for use

Rehabilitation / Reconstruction

16 SDN Gunong Meunasah

Gunong Meunasah

Setia Bakti Yes 100 50 Good Rehabilitation

17 SDN Padang Padang Layeun

Setia Bakti In part 120 56 Parts not for use

Reconstruction

18 SDN Sapek Sapek Setia Bakti In part 102 88 * Good Reconstruction 19 MIN Pante

Kuyun Pante Kuyun

Setia Bakti Yes 120 150 * Good Reconstruction

20 MIS Lam Teungoh

Lam Teungoh

Sampoiniet No 0 Parts unsafe Reconstruction

21 SDN UPT IV Patek

Krueng Ayun

Sampoiniet In part 198 78 Good Rehabilitation

Page 46: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 46 Lamia Maglic UNOPS Construction Engineer

District NIAS AND NIAS SELATAN

No of students

No Name of school Address Sub-district Currently in use

Before Now

Safety condition:

Recommended activity

1 SDN 074048 Luaha Bouso

Gawu-Gawu Bouso

Tuhemberua Yes 227 216 * Good Reconstruction

2 SDN 078435 Tetehosi Afia

Tetehosi Afia Tuhemberua In part 118 107 * Good Rehabilitation / Reconstruction

3 SDN 071020 Awaai Hilimbosi Tuhemberua In part 198 177 Parts unsafe Reconstruction 4 SDN 074050 Sawo Sawo Tuhemberua In part 310 283 Unsafe Reconstruction 5 SDN 075030

Ambukha Lasarasohu Tuhemberua Yes 111 111 * Good Reconstruction

6 SDN 070999 Tarakhaini

Tarakhaini Hiliduho In part 110 97 Unsafe Reconstruction

7 SDN 076674 Orahili Tanoseo

Orahili Tanoseo

Hiliduho Yes 156 133 * Good Reconstruction

8 SDN 074043 Lolowua

Botombano Hiliduho No 120 136 Destroyed Reconstruction

9 SDN 075022 Mazingo Tabaloho

Mazingo Tabaloho

Gunungsitoli In part 105 82 Unsafe Reconstruction

10 SDN 075053 Fadoro Idanoi

Desa Fadoro Gido Yes 190 185 * Good Reconstruction

11 SDN 074056 Dahana Humene

Desa Dahana Gido In part 138 140 Parts unsafe Rehabilitation / Reconstruction

12 SDN 074055 Humene Satua

Desa Humene Gido Yes 183 190 * Good Reconstruction

13 SDN 071078 Hiliweto

Desa Hiliweto Gido

Gido In part 242 272 Parts unsafe Rehabilitation / Reconstruction

14 SDN 071058 Sogaeadu

Desa Sogaeadu

Gido In part 230 232 Parts unsafe Rehabilitation / Reconstruction

15 SDN 071061 Tetehosi Idanoi

Desa Tetehosi Gido In part 279 303 Unsafe Reconstruction

16 SDN 074053 Duria Hilisebua

Desa Hilisebua Gido In part 300 285 Parts destroyed

Reconstruction

17 SDN 075045 Somi Desa Somi Gido Yes 310 305 Good Rehabilitation 18 SDN 174052

Tulumbaho Desa Tulumbaho

Gido No 306 305 Not for use Reconstruction

19 SDN 074038 Tohia Ilir Gunungsitoli No 535 512 Not for use Reconstruction 20 SDN 070975

Gunungsitoli Ilir Gunungsitoli In part 500 460 Parts unsafe Rehabilitation /

Reconstruction 21 SDS

Muhammadiyah Kel. Ilir Gunungsitoli In part 330 284 Parts

destroyed Reconstruction

22 SDN 077779 Sisobahili

Sisobahili Tabaloho Dahana

Gunungsitoli Yes 119 119 * Good Reconstruction

23 MIN Gunungsitoli Kel. Pasar Gunungsitoli

Gunungsitoli No 125 145 Destroyed Reconstruction

24 SDN 070976 Gunungsitoli

Kel. Pasar Gunungsitoli

Gunungsitoli Yes 239 259 Parts unsafe Reconstruction

25 SDN 07778 Hiligodu Ulu

Hiligodu Ulu Gunungsitoli Yes 100 80 Parts unsafe Reconstruction

26 SDN 070983 Sihareo

Sihareo Siwahili

Gunungsitoli In part 246 255 Parts unsafe Reconstruction

Page 47: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 47 Lamia Maglic UNOPS Construction Engineer

27 SDN 071008 Gada Gada Gunungsitoli In part 99 95 Unsafe Reconstruction 28 SDN 078137

Hiligogowaya Maliwa'a Idano Gawo Yes 205 222 * Good Rehabilitation /

Reconstruction 29 SDN 077295 Baruzo

Bobozioli Bobozioli Loloana'a

Idano Gawo Yes 200 197 Unsafe Reconstruction

30 SDN 071051 Bawanaoha

Bawanaoha Bawolato In part 198 208 Parts destroyed

Rehabilitation / Reconstruction

31 SDN 076700 Hiliganoita

Hiliganoita Bawolato No 305 305 Parts destroyed

Reconstruction

32 SDN 071053 Bawalia

Siefa Ewali Bawolato No 315 367 Not for use Reconstruction

33 SDN 075054 Huno Lahemo Gido In part 181 170 Remainder Unsafe

Reconstruction

34 SDN 075036 Tuhewaebu

Hililawae Idano Gawo In part 96 96 Unsafe Reconstruction

35 SDN 075050 Hiliuso Moi

Hiliuso Moi Lolofitumoi In part 172 300 Unsafe Reconstruction

36 SDN 071063 Soromaasi

Soromaasi Lolofitumoi In part 300 320 Unsafe Reconstruction

37 SDN 078436 Duria Duria Lolofitumoi In part 369 407 Parts unsafe Reconstruction 38 SDN 071151 Kare

Alasa Hilimbowo Kare

Alasa Yes 102 132 Parts unsafe Rehabilitation / Reconstruction

39 SDN 076688 Hiligawoni

Hiligawoni Alasa No 140 155 Destroyed Reconstruction

40 SDN 078012 Mida Laehuwa Alasa Yes 63 63 Parts unsafe Rehabilitation 41 SDN 077305

Tuwuna Desa Tuwuna Mandrehe Yes 129 134 * Good Reconstruction

42 SDN 076715 Sianaa Desa Sianaa Mandrehe In part 241 266 Parts destroyed

Reconstruction

43 SDN 076716 Lolohia

Desa Lolohia Mandrehe In part 281 281 Parts unsafe Reconstruction

44 SDN 075062 Doli-doli

Desa Doli-doli Mandrehe In part 372 301 Parts destroyed

Rehabilitation / Reconstruction

45 SDN 075021 Ombolato Salo'o

Ombolato Salo'o

Hiliduho Yes 74 86 * Good Reconstruction

46 SDN 071021 Hilindruria

Desa Maziaya Lotu Yes 271 271 Good Rehabilitation

47 SDN 078434 Sisobaoho

Desa Sisobaoho

Sirombu Yes 80 119 Parts unsafe Rehabilitation

48 SDN 071180 Iraono Gaila

Desa Iraono Gaila

Sirombu No 209 221 Destroyed Reconstruction

49 SDN 071183 Faondrato

Desa Gunung Cahaya

Sirombu In part 167 185 Parts destroyed

Rehabilitation / Reconstruction

50 SDN 075090 Sirombu

Desa Sirombu Sirombu In part 131 90 Parts unsafe Rehabilitation / Reconstruction

51 SDN 071196 Soledua

Desa Sisarahili Oyo

Lolowau Yes 500 550 * Good Rehabilitation / Reconstruction

52 SDN 071191 Hiliadulo

Desa Hiliadulo Lolowau No 187 197 Destroyed Reconstruction

53 SDN 076720 Maluo Desa Maluo Lolowau In part 200 200 Parts unsafe Reconstruction 54 SDN 071187 Amuri Desa Sisarahili

Ekholo Lolowau In part 252 270 Parts unsafe Rehabilitation

55 SDN 071186 Lolomaya

Desa Simandralo

Lolowau In part 302 302 * Good Rehabilitation / Reconstruction

56 SDN 075099 Bawohilinamizohono

Desa Hilinamizohono

Lolowau In part 259 270 Parts unsafe Rehabilitation

Page 48: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 48 Lamia Maglic UNOPS Construction Engineer

57 SDN 076678 Fadoro Fululo

Desa Fadoro Fululo

Lotu Yes 154 139 Good Rehabilitation

58 SDN 075087 Muzoi Desa Muzoi Lahewa In part 105 118 Parts unsafe Reconstruction 59 SDN 076070 Tugala

Lauru Tugala Lauru Lahewa In part 205 155 Remainder

unsafe Reconstruction

60 SDN 071141 Tefao Desa Tefao Lahewa Yes 265 302 Unsafe Reconstruction 61 SDN 075083

Siheneasi Desa Siheneasi

Lahewa In part 152 133 Parts unsafe Rehabilitation / Reconstruction

62 SDN 076681 Bahosea

Desa Hiligeo Afia

Lotu In part 250 208 Parts unsafe Rehabilitation / Reconstruction

63 SDN 071145 Sohahau Lafau

Desa Siheneasi

Lahewa In part 73 73 Parts unsafe Reconstruction

64 SDS BNKP Lahewa Kelurahan Lahewa

Lahewa Yes 204 209 Parts unsafe Rehabilitation / Reconstruction

65 SDN 071138 Lahewa

Kelurahan Pasar Lahewa

Lahewa No 226 224 Destroyed Reconstruction

66 SDN 071146 Iraono Lase

Desa Iraono Lase

Lahewa In part 140 140 Parts destroyed

Reconstruction

67 SDN 071118 Sifaoroasi

Desa Sifaoroasi

Amandraya In part 340 290 Parts destroyed

Reconstruction

68 SDN 075066 Hilisimaetano

Desa Hilisimaetano

Teluk Dalam In part 117 140 Parts destroyed

Reconstruction

69 SDN 071102 Bawomataluo

Desa Bawomataluo

Teluk Dalam Yes 185 178 Parts unsafe Reconstruction

70 SDN 071122 Pasar Teluk Dalam

Kelurahan Pasar Teluk Dalam

Teluk Dalam In part 295 324 Parts destroyed

Rehabilitation / Reconstruction

71 SDN 076103 Bawoza'ua

Desa Bawoza'ua

Teluk Dalam Yes 250 250 Good Rehabilitation

72 SDN 071108 Hilisataro

Desa Hilisataro Teluk Dalam In part 479 479 Parts destroyed

Rehabilitation / Reconstruction

73 SDN 076102 Soto'o Hilialawa

Desa Soto'o Hilialawa

Teluk Dalam In part 205 202 Parts destroyed

Reconstruction

74 SDN 078143 Hilimagari

Desa Bawo Ganowo

Teluk Dalam Yes 60 45 Good Rehabilitation

75 SDN 071213 Hiliana'a Gomo

Desa Hiliana'a Gomo

Gomo No 200 192 Destroyed Reconstruction

76 SDN 071223 Orahili Gomo

Desa Orahili Gomo

Gomo Yes 200 200 Parts unsafe Rehabilitation / Reconstruction

77 SDN 071204 Lahusa

Desa Lahusa Lahusa In part 525 331 Unsafe Reconstruction

78 SDN 071211 Helezalulu

Desa Bawo'otalua

Lahusa Yes 312 340 Parts unsafe Rehabilitation / Reconstruction

79 SDN 071202 Helezalulu

Desa Bawo'otalua

Lahusa Yes 316 330 Parts unsafe Reconstruction

80 SDN 071111 Hilizalo'otano

Desa Hilizalo'otano

Teluk Dalam In part 313 312 Parts destroyed

Reconstruction

Page 49: Final Report-Structural Survey of Schools · Indonesian Loading code SNI-03-1727-1989 determined specification for earthquake loads. The earthquake is presented in the form of horizontal

Final Report on Structural Survey of Schools: March 2005 - February 2006

Bojan Stajic UNOPS Construction Engineer Page: 49 Lamia Maglic UNOPS Construction Engineer

District PIDIE

No of

students No Name of school Address Sub-district Currently

in use Before Now

Safety condition:

Recommended activity

1 SMPN 2 Trienggadeng

Matang Trienggadeng In part 240 240 Parts unsafe Reconstruction

2 SMPN 4 Sigli 1-Tijue 2-Blok Bengel

1-Sigli 2-Kota Sigli

In part 300 275 Parts unsafe Reconstruction

3 SMPN 1 Sigli (Kota Sigli)

Sigli Sigli In part 857 827 Parts unsafe Rehabilitation

4 SMPN 1 Sigli (Blang Paseh)

Blang Paseh

Sigli No 0 Not for use Reconstruction

5 SMPN 3 Sigli Pasi Rawa Kota Sigli In part Parts unsafe Reconstruction

6 SDN 2 Kale Kale Muara Tiga Yes 283 288 Parts unsafe Rehabilitation 7 SDN Blang

Raya Blang Raya

Muara Tiga In part 307 120 Parts unsafe Rehabilitation

8 SMPN 2 Muara Tiga

Ujong Pik Muara Tiga Yes 320 335 Good Rehabilitation

9 SDN Suka Jaya Suka Jaya Muara Tiga In part 170 190 Unsafe Reconstruction

NOTE: Entire school unsafe (currently in use) *Good - good structural condition but bad general conditions, exhausted building Reconstruction/Rehabilitation – schools with more buildings with different levels of damages