Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading
40

Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Jan 11, 2016

Download

Documents

Clinton Craig
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Feng Xiong PhDProfessor of Civil

Engineering Sichuan University

Nonlinear Finite Element Analysis for Precast Short

Column Connections Under Cyclic Loading

Page 2: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Background and MotivationP03

Seismic Behavior Testing of Precast short columnsP04

Finite Element Analysis of Precast Short ColumnsP18

Comparing of Shear Strength Formulas of Precast Column Joint between Chinese and Japanese Codes

P37

ConclusionP39

CONTENTS

Page 3: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Background and Motivation

With the development of industrialized building, precast concrete structures are currently applied since the advantages in low costing, better quality, and quickly constructing;

The short columns with shear-span ratio less than 2.0 frequently occur in high-rise precast concrete frame structures with increasing of column section size;

The one concern in precast column design is the shear strength of joints in the column bottom. Does the shear failure occur along the joints when using wet connections, i.e. sleeve grouting connection?

In the new Chinese "Technical specification for precast concrete

structures”(JGJ 1-2014), a shear strength formula is first given. But it is quite different from in Japanese codes

Page 4: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

No Concrete pouring Rebar connecting Joint configuration

PSC-A-1 Cast-in-place No No joint

PSC-D-2 Cast-in-place Sleeve grouting No joint

PSC-E-3 Precast Sleeve grouting Joint with shear key

PSC-C-4 Precast Sleeve groutingJoint filled in grouting

material

PSC-B-6 Precast Sleeve grouting Joint filled in concrete

Two cast-in-place short columns and three precast short columns were tested under cyclic loading to investigate the effects of sleeve grouting connection and joint configurations on the behaviors of the column 。

Seismic Behavior Testing of Precast Short Columns

• Testing Objective

• Test specimens

Page 5: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Specimen PSC-A-1 Specimen PSC-D-2

Testing specimen elevations

Page 6: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Specimen PSC-E-3 Specimen PSC-C-4 Specimen PSC-B-6

Testing specimen elevations

Page 7: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

( 1 ) Concrete

No ConcreteAge ( da

y)Cube Strength

fcu(MPa)Cuboid Strength

fc(MPa)

PSC-A-1

C45

42 45.24 34.39

PSC-D-2 55 46.26 35.16

PSC-E-3 31 50.07 38.06

PSC-C-4 48 45.89 34.88

PSC-B-6 35 51.08 38.82

Materials of testing specimen

( 2 ) Steel rebar

DiameterYield

strength

fy(MPa)

Ultimate strength fst

(MPa)

Elastic modulus

Es(MPa)Remarks

18(1) 432 615 191606 In member PSC-D-2、 PSC-E-3、PSC-C-4、 PSC-B-6

18(2) 517 657 202228 In member PSC-A-1

6 450 583 180304 Stirrups

Page 8: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Testing Equipment

Page 9: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Loading System

The design axial compression ratio of all testing specimens is 0.6. The axial loads calculated as the measured concrete strength were exerted as the table following ;

Horizontal cyclic loading was controlled by the displacement as the figure.

Specimen

Axial Compression Calculated

kN

Axial Compression

Exerted

kN

PSC-A-1 1466 1466

PSC-D-2 1498 1498

PSC-E-3 1629 1460

PSC-C-4 1466 1466

PSC-B-6 1661 1460

Page 10: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Testing process and observation

• Horizontal bending cracks occurred on the top ;

• When loading at displacement of±5.25m, diagonal cracks occurred in the cross shape ;

• When getting to ultimate loading, diagonal cracks distributed in whole column ;

• When loading at displacement of ±21mm concrete began to crush ;

• Finally loading at displacement of±42mm, concrete crushed and rebar exposed , indicated column damage.

Crack at 1.3125mm

Crack at 5.25mm

Crack at 10.5mm

to ultimate loading

Crack at 42mm

when damaging

Specimen PSC-A-1 (cast in place)

Page 11: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

• Horizontal bending cracks occurred on the top at ±1.3125mm, with the joint at the bottom cracking ;

• Similar process occurred as the cast in place specimen ;

• Finally loading at displacement of±42mm, concrete crushed and rebar exposed , but the joint crack didn’t go through.

Crackingat 1.3125mm

Diagonal cracks

occurred at 5.25mm

At 10.5mmGot to ultimate

loading

At 42mmSpecimen damaged

Specimen PSC-E-3 (Precast)

Testing process and observation

Page 12: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Hysteretic Curves

PSC-A-1 PSC-D-2 PSC-E-3

PSC-C-4 PSC-B-6 5 specimens including cast-in-place and precast columns have the similar hysteretic behavior and energy absorbed.

Page 13: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Skeleton curve

Comparing with PSC-A-1and PSC-D-2 , it is indicated that the sleeve has few effects on initial stiffness . With loading increases, the stiffness of sleeve column (PSC-D-2) decreases but ultimate strength increases. There is a longer platform at ultimate strength to slow down the stiffness degrading.

PSC-A-1 vs PSC-D-2Sleeve effects

Page 14: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Comparing with PSC-E-3 and PSC-C-4, it shows that the specimen with shear key has lower strength but better deformation and slower stiffness degrading than the specimen with the smooth joint.

PSC-E-3 vs PSC-C-4Shear key effect

Skeleton curve

Page 15: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Comparing with PSC-C-4 and PSC-B-6 , it shows that the specimen filled in high-strength grouting material in the joint has higher strength but less deformation than the specimen filled in concrete in the joint.

PSC-C-4 vs PSC-B-6Grouting material effect

Skeleton curve

Page 16: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Ultimate Strength

No fc(MPa) Vu+(kN) Vu

-(kN) Vu+/fcbh0 Vu

-/fcbh0 Failure

PSC-A-1 34.39 472.7 -406.9 0.112 0.097 Shear

PSC-D-2 35.16 504.2 -396.1 0.117 0.092 Shear

PSC-E-3 38.06 520.6 -493.3 0.112 0.106 Shear

PSC-C-4 34.88 517.7 -438.8 0.121 0.103 Shear

PSC-B-6 38.82 520.3 -472.5 0.109 0.099 Shear

It is shown that the precast specimens have the similar strength and failure modes as the cast-in-place specimens.

Page 17: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Testing Conclusion

The rebar connected by the sleeve can insure the loading transfer, and the sleeve has no bad effect on the columns;

The precast columns using three horizontal joint configurations have the similar seismic behavior as the cast-in-place columns;

Since the limit specimens, the shear behavior and failure mode along the joints can not be obtained. The test just proves that the precast column has the behavior equal to cast-in-place column.

To investigate if the shear failure occurs along the joint for precast short columns, numerical analysis is employed.

Page 18: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Finite Element Analysis of Precast Short Columns

Attaching the material property Concrete: Damaged plastic model

Reinforcement: Bi-linear model

• Finite element modeling

Modeling componentsas the dimension

Page 19: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Finite Element Modeling

1.划分网格,指定单元类型。

Defining interface and assembling each component

Tie

Tie (Cast-in-place) orFriction contact (Precast)

Embedded region

Specifying boundary condition

Encastre

Constraining Z translation and three rotations

Exerting loadings

Loading• Finite element modeling

Modeling componentsas the dimension

Attaching the material property

Page 20: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Meshing and specifying element

Concrete: three-dimensional linear brick elements

Reinforcement: truss elements

• Finite element modeling

Finite Element Modeling

Defining interface and assembling each component

Specifying boundary condition

Exerting loadings

Modeling componentsas the dimension

Attaching the material property

Page 21: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Verifying the finite element model

Taking the PSC-A-1 as a example. When observing the equivalent plastic tension strain ( PEEQT ), it shows the process of“bending cracks occurring—diagonal cracks occurring—diagonal cracks developing—damaging in shear mode” , and has a good agreement with the testing observation 。

1.3125mm 5.25mm 10.5mm 42mm

( 1 ) Failure process and mode

Page 22: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

The contact elements specified in the interface of joint indicates that cracks occurred along the joints of specimens PSC-E-3、 PSC-C-4、 PSC-B-6, but didn’t go through the joints. It states that the damage was not resulted by the shear sliding of the joints and agrees with the test observation.

( 2 ) Cracking in the joints of precast column

PSC-E-3 PSC-C-4 PSC-B-6

Verifying the finite element model

Page 23: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

( 3 ) Skeleton Curves

Verifying the finite element modelSince the sleeve and shear key are not modeled In order to simplify the numerical analysis, a few errors can be observed from numerical results.

Page 24: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

( 4 ) Ultimate Strength

Specimen PSC-A-1 PSC-D-2 PSC-E-3 PSC-C-4 PSC-B-6

Testing( kN) 472.70 504.20 520.60 517.70 520.30

FE results( kN) 446.09 447.37 480.19 453.50 488.40

Relative Errors(%) 5.63 11.27 7.76 12.40 6.13

Testing ( kN ) -406.90 -396.10 -493.30 -438.80 -472.50

FE results ( kN ) -423.29 -428.69 -421.02 -411.06 -418.24

Relative errors( % ) 4.03 8.23 14.65 6.32 11.48

Testing ( kN ) 439.80 450.15 506.95 478.25 496.40

FE results ( kN ) 434.67 438.03 450.60 432.28 453.32

Relative errors( % ) 1.16 2.69 11.12 9.61 8.68

uV

-uV

uV

Verifying the finite element model

The comparing between numerical analysis and testing results indicates that the finite element models work well. It can be used to stimulate the precast short columns

Page 25: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Parameter Analysis To extend the test study, finite element parameter analysis is conducted. For precast short columns the two important parameters to effect joint shear behaviors are the axial compression ratio and shear-span ratio. By use of the verified model, 9 numerical models are defined as the changes of axial compression ratio and shear-span ratio.

Model shear-span ratio

Column height ( m

m )

axial compression

ratio

Axial compression

( kN )n0.6-1.5 1.5 1050 0.6 1290

n0.3-1.5 1.5 1050 0.3 645

n0.1-1.5 1.5 1050 0.1 215

n0.6-1.0 1.0 700 0.6 1290

n0.3-1.0 1.0 700 0.3 645

n0.1-1.0 1.0 700 0.1 215

n0.6-0.5 0.5 350 0.6 1290

n0.3-0.5 0.5 350 0.3 645

n0.1-0.5 0.5 350 0.1 215

Page 26: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Equivalent plastic strain

Comparing of columns with fixed shear-span ratio of 1.5 and different axial compression ratiosn0.6-1.5

n0.1-1.5

n0.3-1.5

With the decrease of axial compression ratio, the plastic strains increases and implies that cracks develop quickly and damages occur early.

Page 27: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

n0.6-1.5

n0.6-0.5

n0.6-1.0

With the decrease of shear-span ratio, the cracks occur from the middle column and develop diagonally in a cross shape. But the final failure modes are similar and all in the shear damage.

Equivalent plastic strain

Comparing of columns with fixed axial compression ratio of 0.6 and different shear-span ratios

Page 28: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Joint states at failure stage

n0.6-1.5 n0.3-1.5 n0.1-1.5

n0.6-1.0 n0.3-1.0 n0.1-1.0

n0.6-0.5 n0.3-0.5 n0.1-0.5

• When the axial compression ratio changes from 0.6 to 0.3, no sliding is observed along the bottom joints. It indicates that precast columns fail as the cast-in-place columns;

• When axial compression ratio decreases to 0.1, the obvious sliding occurs along the joints. The failure of precast column is resulted by Insufficient shear strength of joints. The failure belongs to connection failure.

Page 29: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Rebar stresses at failure stage

n0.6-0.5 n0.3-0.5 n0.1-0.5

Stirrups yield but vertical rebar is in low stress when columns damage. It indicates that the column damage is the shear failure and dowel action of rebar through joints doesn’t indicate.

Stirrups and rebar through the joint yield. The column damage comes from the shear failure of the joint .

Page 30: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Hysterical Curves

When axial compression ration decreasing to 0.1, the deformation decreases and the areas covered by hysterical curve decrease. It implies that the shear damage of joint is less ductile than shear damage of whole column.

Page 31: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

With the decrease of shear-span ratio, the stiffness increases but plastic deformation decreases.

Under low axial compression ratio and shear-span ratio ( n0.1-0.5 ), joint sliding occurs in the first loading cycle.

Hysterical Curves

Page 32: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Skeleton curves

The ultimate strength decreases with the axial compression ratio deceasing. The ultimate deformation under axial compression ratio of 0.1 is more less than that of 0.3 to 0.6

Page 33: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Under the same axial compression ratio, the ultimate strength increases and deformation capacity decreases with the shear-span decreasing.

Skeleton curves

Page 34: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Ultimate strength

Page 35: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

The ultimate strength deceases with the axial compression ratio deceasing; and increases with the shear-span ratio deceasing.

Ultimate strength

Page 36: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Numerical analysis conclusion

The axial compression ratio is the key factor to effect the shear failure of joints. It decides if the precast short column fails in the connection or in the column self equal to the cast-in-place column.

For the precast short columns the shear failure will occur along the joints when the axial compression ratio is low, i.e. 0.1. The failure is very brittle with less deformation. Therefore when designing the precast short columns with low axial compression ratio, it is necessary to check the shear capacity for the joints.

The shear-span ratio affects the initial stiffness, deformation ability and ultimate strength for precast short columns. With the decrease of shear-span ratio, the initial stiffness and ultimate strength will enhanced, but deformation will reduce.

Page 37: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Comparing of Shear Strength Formulas of Precast Column Joint between Chinese and Japanese Codes

• Japanese code

docuE VVV , max

2165.1 ycsddo ffAV

NVc

docuE VVV

• Chinese codeShear resistance from friction along joint:

Shear resistance from rebar dowel action force:

Friction coefficient:

Area of dowel rebar:

Tensile rebar is neglected 。

Friction coefficient :

0.8 for all

Area of dowel rebar:

All the rebar through the joint is considered.

Page 38: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Calculating the shear strength of 9 models as the Chinese code and Japanese code respectively ( taking the same friction coefficient of 0.8 ) , the results are shown in the table following :

No.Axial

compression ratio

Shear-span ratio

Numerical results(kN)Calculations as

Japanese code(kN)Calculations as

Chinese code(kN)

n0.1-1.50.1

1.5 277.03 228.46 537.54n0.1-1.0 1.0 293.70 228.46 537.54n0.1-0.5 0.5 345.26 228.46 537.54n0.3-1.5

0.31.5 310.17 516.00 881.54

n0.3-1.0 1.0 333.49 516.00 881.54n0.3-0.5 0.5 387.93 516.00 881.54n0.6-1.5

0.61.5 339.02 1032.00 1397.54

n0.6-1.0 1.0 378.67 1032.00 1397.54n0.6-0.5 0.5 425.26 1032.00 1397.54

Comparing of Shear Strength Formulas of Precast Column Joint between Chinese and Japanese Codes

When axial compression ratios are 0.3 and 0.6, the calculation results are higher than numerical predictions for two codes. It indicates that the failure occurs in the columns. When axial compression ratio is 0.1, Japanese code has a good agreement with numerical results.

Page 39: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

Conclusion

The test of 5 specimens indicates that the precast columns with wet connections have the similar strength, deformation and Energy consumption ability as the cast-in-place columns.

Numerical analysis indicates that shear failure occurs along the joint when axial compression is low. This damage is very brittle with less deformation. To avoid the shear failure along the joint, the shear strength of horizontal joints has to be checked when designing.

By comparing with Chinese code and Japanese code of precast structures, the shear strength formula of Chinese code is overestimate by considering both contact friction and rebar dowel action together.

Page 40: Feng Xiong PhD Professor of Civil Engineering Sichuan University Nonlinear Finite Element Analysis for Precast Short Column Connections Under Cyclic Loading.

THANKS谢谢聆听