Top Banner
PRESENTED BY ERIK SCHELLENBERG IDAHO POWER Fault Locating
38

Fault Location

Nov 06, 2015

Download

Documents

Distance Relay Design
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • PRESENTED BY

    ER IK SCHELLENBERGIDAHO POWER

    FaultLocating

  • Topics

    ImpedanceBased ReactanceMethod TakagiMethod ModificationstoTakagiMethod TWS&DoubleEndedNegativeSequence

  • OneLine

    EquivalentTheveninSources Bus Line RelaywithCT&CCVT

  • RadialLine

    Applyafaultmdistancedownaradialline

    misapercentage oftheline.Forexampleifthefaultis25%fromBusSthen(1m)yields75%,foratotallineimpedance,ZL ,of100%

  • V/I=mZL (sometimes)

    UsingohmslawthefaultlocatoratScancalculatetheimpedance,(mZL),thatthevoltageVisbeingdroppedacrossforthreephaseboltedfaults.

  • V/ICalculation

    TheequivalentcircuitwithrespecttoBusSclearlyshowsthatthemeasuredvoltageVisbeingdroppedacrosstheportionofthetransmissionlinetothefaultpoint.

    (m)ZL =V/I(Ohms)

    (V/I)ZL

    m= (%)

    FaultLocation=m(LineLength)(miles)

  • V/I&FaultResistance

    Assumethefaulthassomeresistance,Randthetransmissionlineispurelyinductive.

  • SimplifiedV/IwithsomeR

    LetIs =100A,XL =10,&RF =5 VLINE =100(1090)=10090V VF =100 (50)=500V Vs =VLINE +VF =11263V Distance=VS/IS=1163 mZLDistance

    Is

    Vs =VLINE+VF

    VF

    VLINE

    XL

    RF

    Distance

  • V/ILimitations

    Usingohmslawdirectlyasfaultlocatorisimpracticalforavarietyofreasons.Someoftheseinclude:

    Onlyworksonthreephasefaults Onlyworksonradiallines Onlyworksonboltedfaults ImpactedbyLoad

  • SimpleReactanceMethod

    Transmissionslineimpedance,Z,istypicallydominatedbythereactivecomponent,X.

    Faultimpedanceistypicallydominatedbytheresistivecomponent,R.

  • FaultResistance&ReactanceMethod

    Letslookattheradialexamplewithfaultresistanceagain.

    Theforwardvoltagedropmeasuredbythefaultlocatoris Vs =mZL(Is)+Is(RF)

  • MinimizetheEffectofRFusingReactance

    DividebythemeasuredcurrentIs

    Retainonlytheimaginarycomponentofeachquantity

  • ReactanceMethodwithRemoteSource

    Nolongeristhesystemradial

    ThecurrentflowingthroughRF isnowthesumofthelocalsource,Is,andtheremotesource,IR

  • SameReactanceTechnique:NowwithIR

    Writetheforwardvoltagedropequation,

    DividebyIs tocalculateameasuredImpedance,

    Taketheimaginarycomponentofeachtermtomitigatefaultresistance,

  • HomogenousSystem&Reactance

    IfyouhaveahomogenoussystemthenbothIS andIR willhavethesameangleandtheimaginarypartof(If/Is)Rf iszero.

    Is

    IRIf=IS+IR

  • NonHomogenousSystem&Reactance

    IS andIR willnothavethesameangleandtheimaginarypartof(If/Is)Rf willshowupinthefaultlocationcalculationasanerrorterm.

    lS

    lR

    lf

  • SimpleReactanceSummary

    ThesimplereactancemethodwasanimprovementoverthestraightOhmsLawcalculationbutitstillhassomedrawbacks:

    ImpactedbyLoad Nonhomogenoussystemsintroduceerrorinfaultresistanceterm

  • TakagiMethod

    In1979ToshioTakagiandYukinari Yamakoshi filedforaU.S.Patentforanewsingleendedfaultlocatingmethod.

    In1982Takagi,etal.delivertheirpaper.

    T.Takagi,Y.Yamakoshi,M.Yamaura,R.Kondow,T.Matsushima,DevelopmentofaNewTypeFaultLocatorUsingtheOneTerminalVoltageandCurrentData,IEEETransactionsonPowerApparatusandSystems,Vol.PAS101,No.8,August1982.

  • Superposition

    ThekeytotheTakagimethodistheideaofsuperposition

    +

    Load PureFaultNetwork

    CompositeFaultNetwork

  • TakagiLocal&RemoteCurrent

    CompositeFaultNetwork PureFaultNetwork

    Voltageequationforthelefthandside Voltageequationfortherighthandside

    BothequationsequalVF.SettheLeftsideequaltotherightside

  • NoFaultCurrentinLoadCircuit

    If =If becausethereisnofaultbranchcurrentinthepureloadstate

    +

    Load PureFaultNetwork

    CompositeFaultNetwork

  • TakagiFaultCurrent

    FromthepreviousslidewecalculatedIR intermsofIS

    PlugintoIF equation

  • ForwardVoltageDrop&Takagi

    Fromthepreviousfaultlocationalgorithmswedevelopedtheforwardvoltagedropequationwithrespecttofaultlocator:

    Pluginournewequationforthefaultbranchcurrent,If:+

    =

  • PauseforError

    willbezeroifthenumeratoranddenominatorhavethesamephaseangle,(homogeneoussystem)

    Ifthereisloadflowonthesystem willbenonzerobutifthemagnitudeoffaultdutyismuchgreaterthanload,theangle willapproachzero.

  • TakagiDistance

    Ifwe:MultiplybythecomplexconjugateofIs, Taketheimaginarypartoftheequationtoeliminatefaultresistance, Assumethesystemistotallyhomogeneous,andfinally Solveform

    Wewillgetthefollowingequation:

  • Zero&NegativeSequenceTakagi

    TheTakagicanusethezerosequencetermforgroundfaults,eliminatingtheneedforprefaultdata

    Thenegativesequencecanalsobeused

  • MutualCoupling

    Thereismagneticcouplingbetweenphasesonacurrentcarryingtransmissionline,Zm.

  • MutualCoupling

    Applyaboltedfaultsomelengthmdowntheline.

    Avoltageisinducedineachphasethroughthemutualcoupling.HereZm iswrittenexplicitlyasZab andZac.

  • VoltageEquation

    Theforwardvoltagedropequationforthefaultedphaseis

    Adding&Subtractingthesamequantity0

    Gatheringterms

  • VoltageEquationContd

    RecognizethatIa+Ib+Ic istheresidualorzerosequencecurrent

    Zm isadifficultquantitytohandledirectly.ThroughtheuseofSymmetricalComponenttheoryitcanbeshownthat:

    SolvingforZs intheZL0 equationandpluggingthisintotheZL1 equationyieldsaZm thatisequalto:

  • Va andthemysteriousk

    Va isnowexpressedintermsofpositiveandzerosequencelineparameterswhichcanbeloadedintoarelayassettings

    FactoroutmZL1,(thedistancetothefault)

    Definektomaketheequationprettier

  • ModifiedTakagi

    OnceagaintaketheimaginarycomponentofbothsidesandsolveformZL1

  • TwoTerminalMethods

    Moreaccuratethansingleendedmethods

    Minimizes/Eliminateseffectsof FaultResistance Loading LineChargingCurrent

    Moreoverhead.Datamustbegatheredorsharedfrommultiplelocations

  • TravelingWave

    Afaultwillcauseatransienttopropagatealongthelineasawave

    Thewaveisacompositeoffrequencieswithafastrisingfrontandslowerdecayingtail

    Thewavestravelatnearthespeedoflightandeventuallydecay

    Bytimetaggingthewavefrontsastheycrossbothterminalsaveryprecisefaultlocationcanbecalculated

  • WavePropagation

    Thewavesleavethedisturbedareatravelingatthevelocityofpropagationwhichisalittlelessthanthespeedoflight

  • NegativeSequenceQuadratic

    In1999Demetrios A.Tziouvaras,JeffRoberts,andGabrielBenmouyal ofSELintroducedanewdoubleendedtechniquethatusesthenegativesequencequantitiesfrombothterminalstofaultlocate.

    D.A.Tziouvaras,J.B.Roberts,G.Benmouyal,NewMultiEndedFaultLocationDesignForTwo orThreeTerminalLines,presentedatCIGREConference,1999,http://www.selinc.com/techpprs/6089.pdf.

  • DoubleEndedNegativeSequence

    ByusingthenegativesequencemethodologyproposedbySELthefollowingsourcesoferroraremitigated:

    Prefault load Zerosequencemutualcoupling Zerosequenceinfeedfromlinetaps FaultResistance

  • References

    T.Takagi,Y.Yamakoshi,M.Yamaura,R.Kondow,andT.Matsushima,DevelopmentofaNewTypeFaultLocatorUsingtheOneTerminalVoltageandCurrentData,IEEETransactionsonPowerApparatusandSystems,Vol.PAS101,No.8,August1982.

    W.A.Elmore,ZeroSequenceMutualEffectsonGroundDistanceRelaysandFaultLocators,Proceedingsofthe19thAnnualWesternProtectiveRelayConference,Spokane,WA,October1992.

    E.O.SchweitzerIII,EvaluationandDevelopmentofTransmissionLineFaultLocatingTechniquesWhichUseSinusoidalSteadyStateInformation,Proceedingsofthe9thAnnualWesternProtectiveRelayConference,Spokane,WA,October1982.

    K.Zimmerman,andD.Costello,ImpedanceBasedFaultLocationExperience,Proceedingsofthe31stWesternProtectiveRelayConference,Spokane,WA,October2004.

    J.Glover,MSarma,andT.Overbye,PowerSystemAnalysisandDesign,GlobalEngineering,2008.

    W.Stevenson,andJ.Grainger,PowerSystemAnalysis,McGrawHillSeriesinElectricalandComputerEngineering,1994

    HewlettPackard,TravelingWaveFaultLocationinPowerTransmissionSystems,ApplicationNote1285