Top Banner
EVALUATION OF TENSILE AND COMPRESSIVE MEMBRANE ACTION IN ISOLATED SLAB COLUMN SPECIMEN A Thesis presented to the Faculty of the Graduate School of the University of Missouri-Columbia In Partial Fulfillment of the Requirements for Degree Master of Science by JOHN DAVID MARCANIK Dr. Sarah L. Orton, Thesis Supervisor December 2012
95

EVALUATION OF TENSILE AND COMPRESSIVE

Oct 31, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: EVALUATION OF TENSILE AND COMPRESSIVE

EVALUATION OF TENSILE AND COMPRESSIVE

MEMBRANE ACTION IN ISOLATED SLAB

COLUMN SPECIMEN

A Thesis presented

to the Faculty of

the Graduate School of the

University of Missouri-Columbia

In Partial Fulfillment of the Requirements

for Degree

Master of Science

by

JOHN DAVID MARCANIK

Dr. Sarah L. Orton, Thesis Supervisor

December 2012

Page 2: EVALUATION OF TENSILE AND COMPRESSIVE

The undersigned, appointed by the dean of the Graduate School, have examined the thesis entitled

EVALUATION OF TENSILE AND COMPRESSIVE MEMBRANE ACTION IN ISOLATED SLAB

COLUMN SPECIMEN

presented by John David Marcanik,

a candidate for the degree of Master of Science in Civil Engineering,

and hereby certify that, in their opinion, it is worthy of acceptance.

Professor Sarah Orton

Professor Vellore Gopalaratnam

Professor P. Frank Pai

Page 3: EVALUATION OF TENSILE AND COMPRESSIVE

DEDICATION

I'd like to dedicate this work to my mother and father for always being there

for support.

Page 4: EVALUATION OF TENSILE AND COMPRESSIVE

ii

ACKNOWLEDGEMENTS

I would like to thank the entire faculty and staff in the Civil & Environmental

Engineering Department at the University of Missouri-Columbia. I would like to extend

special thanks to my graduate advisor Dr. Sarah Orton for helping me along my entire

graduate career and allowing me to work for her. I would also like to thank Dr. Ying Tian

from the University of Nevada-Las Vegas for sharing his expertise and guidance in this

research.

I would also like to express my gratitude to Rex Gish, Brian Samuels, and Richard

Oberto of Engineering Technical Services for sharing their knowledge and experience. I

would like to extend gratitude to graduate students Matthew Wheeler, Matthew Muenks,

Matthew Wombacher, Aaron Saucier, and Zhonghau Peng for assisting me in my

research studies. Finally, I would like to thank undergraduate research assistants Garrett

Havens, Zach Treece, Kevin Gribble, Chris Henquinet, David Koenig, Kenneth Burton,

Scott Hamilton, and Spencer Bearden for their time and efforts.

Page 5: EVALUATION OF TENSILE AND COMPRESSIVE

iii

TABLE OF CONTENTS

ACKNOWLEDGEMENTS ................................................................................................ ii

LIST OF FIGURES .............................................................................................................v

LIST OF TABLES ............................................................................................................ vii

ABSTRACT .................................................................................................................... viii

1. INTRODUCTION .........................................................................................1

1.2. Objective and Research Plan .........................................................................3

1.3. Scope ..............................................................................................................4

2. LITERATURE REVIEW ..............................................................................6

2.1. Introduction to Punching Shear .....................................................................6

2.2. Past Punching Failures ...................................................................................7

2.3. Alternative Resistance Mechanisms ..............................................................9

2.3.1. Compressive Membrane Action ...............................................................11

2.3.2. Tensile Membrane Action ........................................................................13

2.4. Previous Research ........................................................................................14

2.4.1. Elstner and Hognestad .............................................................................14

2.4.2. Kinnunen and Nylander ...........................................................................16

2.4.3. Muttoni .....................................................................................................17

2.4.4. Guice and Rhomberg ...............................................................................18

2.4.5. Gardner and Shao .....................................................................................21

2.4.6. Post-Punching Capacity ...........................................................................23

2.5. Existing Standards .......................................................................................24

2.6. Strength Predictions Developed from Research ..........................................26

3. EXPERIMENT SETUP ...............................................................................28

3.1. Design of Prototype Building ......................................................................28

3.2. Design of Test Specimen .............................................................................31

3.3. Test Specimen Construction ........................................................................35

3.4. Test Setup Design ........................................................................................40

3.5. Instrumentation ............................................................................................47

3.6. Material Properties .......................................................................................53

Page 6: EVALUATION OF TENSILE AND COMPRESSIVE

iv

3.7. Punching Strength Predictions .....................................................................53

4. TEST RESULTS .........................................................................................56

4.1. Pre-punching Behavior ................................................................................56

4.2. Post-Punching Behavior ..............................................................................66

5. SUMMARY, CONCLUSIONS AND FUTURE RESEARCH ...................72

5.1. Summary ......................................................................................................72

5.2. Conclusions ..................................................................................................74

5.3. Future Research Goals .................................................................................75

REFERENCES ..................................................................................................................77

APPENDIX 1 .....................................................................................................................79

Page 7: EVALUATION OF TENSILE AND COMPRESSIVE

v

LIST OF FIGURES

Figure 1.1.1: Diagonal tension cracks from punching shear (Harris, 2004) ....................... 2

Figure 2.2.1: Damage from collapse in Jackson, MI (Aberdeen Group, 1956) .................. 7

Figure 2.2.2: Progressive collapse of Skyline Plaza Tower (Crowder, 2005) .................... 8

Figure 2.2.3: Collapse of Sampoong Department store (Gardner et al, 2002) ................... 9

Figure 2.3.1: Change in slab stresses due to loss of supporting column .......................... 10

Figure 2.3.1.1: Net tensile strain at centerline of slab (Vecchio and Tang, 1989) ........... 12

Figure 2.3.1.2: Compressive membrane action (Vecchio and Tang, 1989) ..................... 13

Figure 2.4.1.1: Sketch of slab specimens to be tested (Elstner and Hognestad, 1956) ..... 15

Figure 2.4.2.1: Load-rotation plot of different slabs (Kinnunen and Nylander, 1960) ..... 16

Figure 2.4.3.1: Relationship of slab thickness on strength and ductility (Muttoni, 2008) 18

Figure 2.4.4.2: Load-deflection plot with partial restraint (Guice and Rhomberg, 1989) 20

Figure 2.4.4.3: Load-deflection plot with full restraint (Guice and Rhomberg, 1989) ..... 21

Figure 2.4.5.1: Reinforcement layout for multi-panel test (Gardner and Shao, 1996) ..... 22

Figure 2.4.6.1: Response of isolated specimen showing residual capacity (Tian, 2008) . 24

Figure 3.1.1: Plan view of prototype building .................................................................. 29

Figure 3.1.2: Tension reinforcement in prototype building .............................................. 30

Figure 3.1.3: Compression reinforcement of prototype building ..................................... 31

Figure 3.2.1: Layout of tension reinforcement showing anchors ..................................... 32

Figure 3.2.2: Layout of compression reinforcement showing anchors ............................. 33

Figure 3.2.3: Elevation of slab showing section through column ..................................... 34

Figure 3.2.4: Hooked Reinforcement Detail for top and bottom bars .............................. 35

Figure 3.3.1: Formwork of slab ........................................................................................ 36

Figure 3.3.2: Formwork with top column stud and reinforcement ................................... 36

Figure 3.3.3: Column reinforcement as seen through the top column .............................. 37

Figure 3.3.4: Finished form with reinforcement ............................................................... 38

Figure 3.3.5: Reinforcement showing scale ...................................................................... 38

Figure 3.3.6: Poured concrete being vibrated ................................................................... 39

Figure 3.3.7: Finished concrete slab ................................................................................. 40

Figure 3.4.1: 2D view of final test setup ........................................................................... 41

Page 8: EVALUATION OF TENSILE AND COMPRESSIVE

vi

Figure 3.4.2: 3D view of final test setup ........................................................................... 41

Figure 3.4.3: Drawing of connection plan ........................................................................ 43

Figure 3.4.4: Finished assembly of connection to steel frames ........................................ 43

Figure 3.4.5: Details of anchorage design ........................................................................ 44

Figure 3.4.6: Anchorage assembly with PVC pipes ......................................................... 45

Figure 3.4.7: Hydraulic actuator with extension above slab ............................................. 46

Figure 3.5.1: Data acquisition system with connected instrumentation ........................... 47

Figure 3.5.2: Center load cell underneath hydraulic actuator ........................................... 48

Figure 3.5.3: Strain gage locations on tension reinforcement mat ................................... 49

Figure 3.5.4: Strain gage locations on compression reinforcement mat ........................... 50

Figure 3.5.5: South LVDT clamped to support ................................................................ 51

Figure 3.5.6: String pot locations underneath slab ........................................................... 52

Figure 3.5.7: String pots underneath slab ......................................................................... 52

Figure 4.1.2: Underneath slab immediately following punching failure .......................... 57

Figure 4.1.3: Load-displacement plots of all string pots .................................................. 58

Figure 4.1.4: Composite image of slab showing vertical movement of connections ....... 59

Figure 4.1.5: Load-displacement plot adjusted for rotational effects ............................... 60

Figure 4.1.6: Average horizontal loads vs. displacement ................................................. 61

Figure 4.1.7: Concrete compressive strains before punching ........................................... 62

Figure 4.1.8: Plot of tension reinforcement strains ........................................................... 63

Figure 4.1.9: Tension rebar strains at punching failure (in microstrains) ......................... 64

Figure 4.1.10: Plot of compression reinforcement strains ................................................ 65

Figure 4.1.11: Compression rebar strains at punching failure (in microstrains) .............. 66

Figure 4.2.1: Center load-displacement plot for entire test .............................................. 67

Figure 4.2.2: Top column stud after testing ...................................................................... 68

Figure 4.2.3: Fractured compression steel ........................................................................ 68

Figure 4.2.4: Deformation of exposed tension reinforcement .......................................... 69

Figure 4.2.5: Strain distribution across tension rebar ....................................................... 70

Figure 4.2.6: Underneath slab after unloading .................................................................. 71

Page 9: EVALUATION OF TENSILE AND COMPRESSIVE

vii

LIST OF TABLES

Table 1.2.1: Test matrix for research plan .......................................................................... 4

Table 3.6.1: Concrete cylinder strengths .......................................................................... 53

Page 10: EVALUATION OF TENSILE AND COMPRESSIVE

viii

EVALUATION OF TENSILE AND COMPRESSIVE MEMBRANE ACTION IN ISOLATED SLAB-COLUMN SPECIMEN

John Marcanik

Dr. Sarah Orton, Thesis Supervisor

ABSTRACT

Flat-plate buildings are susceptible to progressive collapse in which the failure of one

slab-column connection propagates to the other connections and causes a full collapse of

the building. The failure of the connection is commonly caused by the mechanism of

punching shear. Alternative resistance mechanisms such as compressive and tensile

membrane action may enhance the punching shear strength of a slab-column and arrest

the progression of the collapse. This thesis seeks to determine the effect of in-plane

lateral restraint on an isolated slab-column specimen with continuous reinforcement.

A slab at 0.73 scale with continuous top and bottom reinforcement was cast and tested

with lateral restraint to evaluate the potential beneficial effects of in-plane compressive

forces. The isolated slab specimen had column studs on top and bottom to simulate a

progressive collapse scenario in which a nearby supporting column was removed.

The slab was able to achieve a centric load of 70 kips before the first punching failure

then achieved nearly the same residual capacity following the initial failure. It was found

that nearly all of the tension reinforcement had yielded before the punching failure

occurred and the bars located closest to the column were experiencing the most stress.

The compression reinforcement began fracturing around the column near the peak

Page 11: EVALUATION OF TENSILE AND COMPRESSIVE

ix

residual capacity due to amplified stresses as the tension bars were no longer resisting as

much of the load. In-plane compressive forces reached a maximum of 5 kips before the

punching failure which corresponded to a horizontal stiffness of 570 kip/in. Using a static

analysis on the compression arch action, it was found that the 5 kip lateral compressive

load increased the capacity of the slab by 0.5 kips, or a 1% overall increase.

In conclusion, the compressive membrane action only enhanced the punching shear

strength of the slab by about 1%. However, the horizontal stiffness was only 36% of what

was initially designed for, so changes in test setup design must be made to improve the

in-plane lateral restraint for future tests. The slab showed tremendous post-punching

capacity, as it reached a residual strength of 69 kips. The continuous tension and

compression reinforcement was able to develop the full tensile membrane action in the

slab and improve the ductility significantly. Future tests will be performed on 7 additional

isolated slab-column specimens to further investigate the effects of different

reinforcement ratios, in-plane lateral restraint, and dynamic loading on the punching

strength of flat-plates to better resist progressive collapse.

Page 12: EVALUATION OF TENSILE AND COMPRESSIVE

1

1. INTRODUCTION

Extreme events such as earthquakes and blast can have catastrophic consequences on

buildings, bridges, and other types of structures. One prevalent example is the potential

for progressive (or disproportionate) collapse. Progressive collapse can be defined as the

sequential collapse of a structural system following the failure of a primary member such

as a column or girder. The loss of a primary structural member can lead to a "domino"

effect that eventually results in complete failure of the entire system. Such catastrophic

failures can result in large losses of life, as evidenced in the collapse of the World Trade

Center in New York in 2001 and the Oklahoma City bombing in 1995.

Collapses originating from punching shear failures are of particular concern in slab-

column connections of older flat-plate reinforced concrete buildings. Punching shear

forces develop from high localized stresses at the slab-column connection and if the

connection is not strong enough, the punching failure could result in a progressive

collapse of the structure. The diagonal cracks that propagate through the slab resulting in

a punching failure are illustrated in Figure 1.1.1. Continuous reinforcement through the

column has been a common mitigation strategy to improve the overall ductility of a slab-

column connection when subject to punching shear forces. The continuous reinforcement

provides the amount of ductility needed to develop tensile membrane action, or the ability

for a slab to develop residual strength after first punching failure. In-plane lateral restraint

is another alternative resistance mechanism to punching shear in that compressive

membrane action can be developed to enhance the punching capacity.

Page 13: EVALUATION OF TENSILE AND COMPRESSIVE

2

Figure 1.1.1: Diagonal tension cracks from punching shear (Harris, 2004)

Design codes such as American Concrete Institute (ACI) 318 and American Society of

Civil Engineers (ASCE) 7 have developed procedures for designing slab-column

connections, but there are few specific strategies to design against progressive collapse.

There are also few standards in place that can predict the strength of a slab-column

connection when considering the beneficial effects of tensile membrane action and

compressive membrane action. Thus, this research studies the behavior of nearby slab-

column connections following the loss of a supporting column and seeks to determine if

in-plane lateral restraints improve the overall load-carrying capacity.

1.1. Problem

There exists little knowledge of the behavior of a flat slab attempting to resist progressive

collapse. The objective of this research is to obtain experimental data to better understand

the behavior of flat-plate slab-column connection subjected to amplified punching shear

stresses under progressive collapse. In particular, the effect of in-plane compressive

Page 14: EVALUATION OF TENSILE AND COMPRESSIVE

3

forces in the punching capacity of a slab-column connection and the residual strength that

develops after the initial punching failure was studied. It is hoped that upon completing

the research, specific mitigation strategies can be implemented in the design of safer

reinforced concrete buildings.

1.2. Objective and Research Plan

The main goal of this research is to analyze the punching shear capacity of a typical slab

that is subjected to the loss of a nearby supporting column. Evidence has shown that in-

plane lateral restraint can enhance the gravity load-carrying capacity of a slab-column

connection and this research will further investigate its effectiveness in combination with

continuous reinforcement through the column to resist progressive collapse.

This phase of the research tested one reinforced concrete slab with a 1% reinforcement

ratio to evaluate the effect of in-plane compressive forces on the punching shear capacity

of the slab when subjected to the loss of a supporting column. The slab was constructed

at a 0.73 scale to make it possible to test within the constraints of the lab. The slab had a

column stud on both the top and bottom face to simulate a nearby connection following

the loss of a supporting column in a progressive collapse scenario. The slab was

supported on all four sides with a threaded stud-nut connection assembly simulating the

in-plane lateral restraint. A hydraulic ram was used to statically load the specimen and

analyze the punching failure around the slab-column connection.

The test and results presented in this thesis are one part of a larger research goal to

evaluate the progressive collapse potential of flat-plate buildings. Seven more slabs will

Page 15: EVALUATION OF TENSILE AND COMPRESSIVE

4

be tested in the future to study the effects of using a smaller reinforcement ratio, the

exclusion of in-plane lateral restraint, and the effects of dynamic loading. The full test

matrix can be seen in Table 1.2.1. The isolated slab that was tested and will be discussed

in this thesis is Test 1 in the matrix.

Table 1.2.1: Test matrix for research plan

1.3. Scope

This research is organized into five chapters. Chapter 2 is the literature review detailing

historical examples of progressive collapse of flat-plate slabs, punching shear failures,

and past research performed on punching shear capacity and the effects of in-plane lateral

compressive forces. Chapter 3 describes the test setup and construction as well as specific

considerations for the design of the testing apparatus. Chapter 4 details the results from

the tests performed and chapter 5 summarizes the results and discusses conclusions that

Page 16: EVALUATION OF TENSILE AND COMPRESSIVE

5

can be drawn from the results. Finally, an appendix section and list of references

conclude this thesis.

Page 17: EVALUATION OF TENSILE AND COMPRESSIVE

6

2. LITERATURE REVIEW

This chapter will discuss some past punching shear failures in detail, possible alternative

resistance mechanisms to improve strength and previous research that has been

conducted on punching shear capacity of flat-plate slabs.

2.1. Introduction to Punching Shear

Structural failures at a slab-column connection are most commonly referred to as a

punching shear failure (or in some cases two-way shear failure). Stresses develop from

gravity loading on the slab that transfers to the slab-column connection, where the failure

mechanism is typically dominated by shear.

In flat-plates, flexural cracks form in a circular shape around the column which in turn

leads to inclined shear cracks to create a conical failure surface. Once these shear cracks

form, the majority of the shear stresses are transferred by inclined struts extending from

the bottom of the slab to the reinforcement at the top of the slab. The forces in the struts

are diagonal and the vertical component of the force pushes up on the rebar causing

stresses to form between the steel and the concrete. Eventually, these stresses cause the

concrete to crack in the plane of the bars which leads to a punching failure. A punching

failure is very brittle, so it occurs suddenly with little to no warning (Wight and

MacGregor, 2005).

Page 18: EVALUATION OF TENSILE AND COMPRESSIVE

7

2.2. Past Punching Failures

It is essential to examine past failures due to disproportionate collapse of flat-plate

structures to fully understand the resulting consequences. There have been several

incidents of progressive collapse due to punching failures in recent history. In 1956, an

office building in Jackson, Michigan collapsed during construction from punching shear

of the flat-plate slabs at the columns. It was speculated that the area provided for

punching shear was significantly reduced from duct and pipe openings at some of the

interior columns (Aberdeen Group, 1956). The punched slab through the column can be

seen in Figure 2.2.1.

Figure 2.2.1: Damage from collapse in Jackson, MI (Aberdeen Group, 1956)

Another instance of flat-plate progressive collapse during construction occurred in an

apartment building in Boston, Massachusetts in 1971. Four men were killed when a

failure on the roof caused a progressive collapse down to the basement, resulting in about

two thirds of the entire building collapsing. Inadequate concrete strength caused by poor

Location where column punched through slab

Page 19: EVALUATION OF TENSILE AND COMPRESSIVE

8

protection from cold weather ended up resulting in a punching shear failure of a flat-plate

slab on the roof (King and Delatte, 2004).

On March 2, 1973, the Skyline Plaza Tower collapsed during construction which lead to

14 deaths and 48 total casualties. The tower was a flat-plate reinforced concrete structure

that was scheduled to be opened in August of 1973. However, construction shoring was

removed earlier than required resulting in a punching shear failure of the slab around

multiple columns on the floor above (Crowder, 2005). The failure caused a progressive

collapse of the lower floors all the way down to the ground as seen in Figure 2.2.2.

Figure 2.2.2: Progressive collapse of Skyline Plaza Tower (Crowder, 2005)

Perhaps the most tragic incident, however, occurred in 1995 in Seoul, South Korea. The

5-story Sampoong Department Store collapsed as a result of a punching failure in service,

killing 501 people. Upon being converted to a department store, columns were removed

Page 20: EVALUATION OF TENSILE AND COMPRESSIVE

9

to make room for escalators. To add to the issue, the fifth and top floor was changed to

accommodate a restaurant which increased the dead load by 35% (Gardner et al, 2002).

The slab-column connections were not adequate to resist the additional loading ultimately

resulting in catastrophic failure of the building as seen in Figure 2.2.3. The Sampoong

Department Store failure escalated the need to better understand the punching shear

failure mechanisms of slab-column connections to prevent further significant tragedies.

Figure 2.2.3: Collapse of Sampoong Department store (Gardner et al, 2002)

2.3. Alternative Resistance Mechanisms

To resist progressive collapse, several measures can be taken to improve the strength and

ductility of a flat-plate slab-column connection. Upon the loss of a supporting column,

the column axial loads are increased by 23%. As seen in Figure 2.3.1, the stresses at a

slab-column connection can be significantly increased as a result of the loss of a

supporting column underneath.

Page 21: EVALUATION OF TENSILE AND COMPRESSIVE

10

Typical Structure

Structure with Missing Column

Figure 2.3.1: Change in slab stresses due to loss of supporting column

Alternative resistance mechanisms such as compressive membrane action and tensile

membrane action have been known to exist and can help improve the load-carrying

capacity of reinforced concrete slabs (Guice and Rhomberg, 1988). Elevated stresses

resulting from the loss of a supporting column can lead to very uneconomical designs so

Page 22: EVALUATION OF TENSILE AND COMPRESSIVE

11

the effects of the alternative resistance mechanisms must be thoroughly investigated.

Compressive membrane action relates to the effects of in-plane lateral compressive forces

to increase the punching shear capacity. Tensile membrane action is the capacity of a

slab-column connection to develop residual strength after initial punching failure,

typically done with the inclusion of continuous reinforcement.

2.3.1. Compressive Membrane Action

Compressive membrane action is a phenomenon that can result in increased flexural

capacity of reinforced concrete slabs due to in-plane lateral forces. When a reinforced

concrete slab is subjected to gravity loads the extreme fiber of the concrete cracks upon

reaching its modulus of rupture. Afterwards, the bottom reinforcement goes into tension

and begins to stretch. At increased loading, the overall tensile stress in the bottom face of

the slab is much greater than the compressive stress in the top face, resulting in a net

tensile stress at the centerline of the slab shown in Figure 2.3.1.1.

Page 23: EVALUATION OF TENSILE AND COMPRESSIVE

12

Figure 2.3.1.1: Net tensile strain at centerline of slab (Vecchio and Tang, 1989)

The outward expansion of the slab is restrained by the stiffness of the connection to the

column at the end of span, which in turn induces lateral compressive forces in the slab.

These in-plane compressive forces result in an increase of nominal flexural capacity of

the slab, leading to a larger load-carrying capacity (Vecchio and Tang, 1989). The

increased moment capacity of a slab from induced lateral compression forces is

illustrated in Figure 2.3.1.2.

Page 24: EVALUATION OF TENSILE AND COMPRESSIVE

13

Figure 2.3.1.2: Compressive membrane action (Vecchio and Tang, 1989)

2.3.2. Tensile Membrane Action

After punching failure, a flat-plate reinforced concrete slab can develop enhanced

capacity from a phenomenon known as tensile membrane action. Tensile membrane

action occurs at very large displacements in concrete slabs and is generally a result of

continuous reinforcement through the column. At large displacements, net tensile stresses

occur at the center of a slab which leads to an increase in load carrying (Bailey, 2000). At

large displacements, tensile membrane action can be very beneficial in improving the

post-punching capacity of flat-plate slabs.

Page 25: EVALUATION OF TENSILE AND COMPRESSIVE

14

2.4. Previous Research

The effects of punching shear in a disproportionate collapse situation has yet to be

extensively examined, but the punching shear capacity of flat-plate slabs has been

investigated increasingly since the 1950s. Specifically, studies have been done on

isolated slab specimens to examine punching shear capacity of reinforced concrete slabs

with varying flexural reinforcement ratios, the addition of transverse reinforcement,

maximum aggregate size, and varying slab thicknesses. Some research has also been

conducted on the effect of in-plane lateral compressive forces and the use of multi-panel

slab systems to develop better punching shear strength relationships. Lastly, studies

investigating the post-punching capacity after initial failure of reinforced concrete slabs

have also been considered.

2.4.1. Elstner and Hognestad

Early research includes tests done by Elstner and Hognestad in 1956 to examine the shear

strength of reinforced concrete slabs subjected to a centrally located concentrated load.

The research consisted of testing 39 different 6 foot square, 6 inch thick concrete slabs to

be loaded centrally through a top column stud as shown in Figure 2.4.1.1.

Page 26: EVALUATION OF TENSILE AND COMPRESSIVE

15

Figure 2.4.1.1: Sketch of slab specimens to be tested (Elstner and Hognestad, 1956)

Some of the variables included concrete strength (ranging from about 2000 psi to about

6500 psi), percentage of tension reinforcement (also known as the reinforcement ratio),

percentage of compression reinforcement, boundary supports, and inclusion of shear

reinforcement. It was found that 34 out of the 39 slabs failed in shear, which was most

likely due to punching shear phenomena. It was also observed that of 34 shear failures,

the ultimate failure of the slab occurred after the first yielding of the steel reinforcement

in the vicinity of the column (Elstner and Hognestad, 1956). This was an obvious alert to

the existence of punching shear near the column and how it affects the failure

mechanisms of the slab. However, one shortcoming of the tests was that the exclusion of

a column stud beneath the slab prevented the researchers from obtaining accurate

representations of the stress distributions.

Page 27: EVALUATION OF TENSILE AND COMPRESSIVE

16

2.4.2. Kinnunen and Nylander

In the early 1960s Kinnunen and Nylander conducted research on the punching effects on

several slabs to study how, amongst other parameters, the flexural reinforcement affected

the punching shear strength. They came to several conclusions, but the most prevalent

was the effect of the reinforcement ratio on the punching shear and overall capacity of the

slab. The load-displacement plots from their findings can be seen in Figure 2.4.2.1.

Figure 2.4.2.1: Load-rotation plot of different slabs (Kinnunen and Nylander, 1960)

It was found that for low reinforcement ratios (about 0.5%), the slabs failed in a very

ductile manner but the strength of the slab was flexure-dependent. Thus, the punching

failure only occurred after extreme plastic deformations. Conversely, they found that a

higher reinforcement ratio (about 2.1%) results in a punching failure to occur before

yielding of reinforcement causing the slab to fail in a very brittle manner (Kinnunen and

Page 28: EVALUATION OF TENSILE AND COMPRESSIVE

17

Nylander, 1960). From the results, Kinnunen and Nylander were able to postulate that the

punching shear capacity is related to the critical rotation of the slab, Ψ, which is

illustrated in Figure 2.4.2.1. It can be observed from the plot that slabs with lower

reinforcement ratios exhibited lower punching shear capacity but a higher overall

ductility whereas the slabs with high reinforcement ratio behaved in the opposite manner.

While Kinnunen and Nylander's model provided a reasonable estimation of the punching

strength of flat-plate reinforced concrete slabs, it was slightly too complex to be used in

design codes at the time and did not take size effects into account.

2.4.3. Muttoni

Kinnunen and Nylander's research provided much insight of how slab-column

connections in flat-plate buildings behave, but tests done on thicker slabs showed that

there was a significant size effect to account for the punching shear capacity. Muttoni

postulated that the punching shear strength is a function of the critical shear crack

opening. He found that the shear transferred across is directly dependent of the roughness

of the crack, or specifically the maximum aggregate size. Ultimately, he was able to

conclude that the overall punching shear capacity of a flat-plate slab was related to the

slab rotation from the loading, the thickness of the slab, and the maximum aggregate size

(Muttoni, 2008). It was found in general that the slab exhibited lower punching capacity

for thicker slabs with low reinforcement ratios, which can be seen in Figure 2.4.3.1.

Page 29: EVALUATION OF TENSILE AND COMPRESSIVE

18

Figure 2.4.3.1: Relationship of slab thickness on strength and ductility (Muttoni, 2008)

The results also show that thicker slabs (30 inches and greater) did not exhibit as much

ductility as slabs that were thinner (10 inches and lower). Muttoni concluded that this low

level of ductility for thicker slabs was undesirable, so the only reasonable solution was to

include some level of shear reinforcement near the slab-column interface. This research

hopes to utilize the benefits of in-plane lateral restraint to avoid having to include

separate shear reinforcement in the slab.

2.4.4. Guice and Rhomberg

Investigation of the effects of in-plane compressive forces on the load-carrying capacity

of flat-plate reinforced concrete slabs are few, but one such study was done by Guice and

Rhomberg in 1988. Before this study, it was not well understood what kind of boundary

conditions were necessary to develop the full benefits of compressive membrane forces.

Guice and Rhomberg constructed a testing apparatus that allowed for the slab to be

Page 30: EVALUATION OF TENSILE AND COMPRESSIVE

19

partially restrained; that is, the slabs were restrained against rotation and translation. They

tested 16 different slabs with varying thickness and reinforcement ratios to investigate the

effects of compressive membrane action in several different situations. It was concluded

that some rotational restraint is necessary to develop the full potential for compressive

membrane action. Small rotational freedoms also enhanced the potential for tensile

membrane action to develop. It can be seen from Figure 2.4.4.1 that initially, slabs with

smaller freedoms for rotation developed increased load-carrying capacity from

compressive membrane action. Then, when tensile membrane action began to take over,

the slabs with greater freedom for rotation showed higher capacities.

Figure 2.4.4.1: Load-deflection plots of slabs with restraints (Guice and Rhomberg, 1988)

Page 31: EVALUATION OF TENSILE AND COMPRESSIVE

20

Guice and Rhomberg suggested that a consistent freedom for rotation should be designed

for slabs in service to develop the full benefits of both compressive membrane action and

tensile membrane action simultaneously.

In another study, Guice and Rhomberg investigated the effect of fully restrained slabs on

the load-carrying capacity of flat plates. Another support structure was constructed to

provide rigid supports for the slab and eliminate any lateral movement. 31 slab specimens

were tested with rigid supports and it was found that the flexural capacity of the slab

increased by about 80% over slabs with only partial restraint. It is also shown in Figures

2.4.4.2 and 2.4.4.3 that the tensile membrane action benefit associated with full in-plane

restraint is significantly increased.

Figure 2.4.4.2: Load-deflection plot with partial restraint (Guice and Rhomberg, 1989)

Page 32: EVALUATION OF TENSILE AND COMPRESSIVE

21

Figure 2.4.4.3: Load-deflection plot with full restraint (Guice and Rhomberg, 1989)

2.4.5. Gardner and Shao

Tests done on multi-panel slab systems are few, but a specific study was done in 1996 by

Gardner and Shao. Gardner and Shao investigated the punching shear events in flat-plate

multi-panel slab system for early stages in the life of the slab such as during construction.

At times, construction loads can equal or even exceed loads that are seen by the slab in

service. Thus, Gardner and Shao sought to examine the punching shear capacity of slab-

column connections when subjected to simulated construction loads. A two-bay-by-two-

bay slab was constructed and tested to failure to investigate the punching shear behavior

of continuous slab-column connections and the differences in capacity of interior, edge,

and corner slab-column connections. A schematic of the two-bay by two-bay slab with

reinforcement layouts can be seen in Figure 2.4.5.1 (dimensions in millimeters).

Page 33: EVALUATION OF TENSILE AND COMPRESSIVE

22

Figure 2.4.5.1: Reinforcement layout for multi-panel test (Gardner and Shao, 1996)

Forty concentrated loads were applied throughout the slab to simulate a distributed

construction loading over the entire slab system. They found that the interior slab-column

connection is more critical than both the corner and edge connections. It was also

observed that although the failures occurred in shear, the failures occurred at locations

were flexure cracks were present. This indicates that punching shear failures occur at

locations of high moment and can be considered a combined flexural-shear event

(Gardner and Shao 1996). Future tests in this research study will test multi-panel

specimens for punching strength and resistance mechanisms against progressive collapse.

Page 34: EVALUATION OF TENSILE AND COMPRESSIVE

23

2.4.6. Post-Punching Capacity

Some research has also been done on the post-punching capacity of flat-plate slab-

column connections. Tests are few because the previous tests done stopped immediately

following a punching failure. Tests done by Pan and Moehle in 1992 and more recently

Tian in 2008 found residual capacity directly related to the slab bottom reinforcement.

Pan and Moehle concluded that the doweling action of the slab bottom bars provides

some tensile membrane action after punching failure. Tian found that specimens that did

not contain continuous bottom reinforcement into the column still showed a residual

capacity of more than 30% of its punching strength. This residual capacity for the

isolated slab specimen in Tian's study is shown in Figure 2.4.6.1. However, the research

is somewhat incomplete because it is not known whether the slabs would still perform

under very large deformations without continuous reinforcement into the column. It is

believed that bars extended into the column might allow the slab to fully develop

maximum residual capacity.

Page 35: EVALUATION OF TENSILE AND COMPRESSIVE

24

Figure 2.4.6.1: Response of isolated specimen showing residual capacity (Tian, 2008)

2.5. Existing Standards

There are existing criteria in use today to design against progressive collapse as well as

shear in flat-plate reinforced concrete slabs. To resist progressive collapse, the current

ACI Building Code (318-08) requires that the bottom reinforcement be continuous

through the column and at least two bottom bars pass through the region in the column

bounded by its longitudinal reinforcement. In general, disproportionate collapse criteria

are developed by the Department of Defense (DoD) and are based on different two

methods: Direct Design and Indirect Design (DoD, 2009). Indirect design is a simple

approach that involves providing minimum amounts of reinforcement to provide tie

forces that can achieve satisfactory levels of strength, continuity, and ductility. Indirect

design is not an approach that considers specific threats, so it is assumed that a standard

amount of reinforcing will decrease the risk of progressive collapse. Direct Design,

however, is a more thorough analysis of a structure that is missing a primary load-bearing

Page 36: EVALUATION OF TENSILE AND COMPRESSIVE

25

member. An alternate load path is created to redistribute loads following the loss of a

supporting column so that the remaining structure can bridge over the failed member.

To determine the punching shear capacity of a slab-column connection, ACI defines the

shear strength of a non-prestressed slab without shear reinforcement as the least of the

following:

𝑉𝑐 = �2 + 4𝛽� 𝜆�𝑓′𝑐𝑏𝑜𝑑 Equation 1

𝑉𝑐 = (𝛼𝑠𝑑𝑏𝑜

+ 2)𝜆�𝑓′𝑐𝑏𝑜𝑑 Equation 2

𝑉𝑐 = 4𝜆�𝑓′𝑐𝑏𝑜𝑑 Equation 3 where 𝑉𝑐 is the slab shear strength, β is the ratio of the long side of the column to the

short side, 𝛼𝑠 is 40 for interior columns, and 𝑏𝑜is the perimeter of the critical section of

the slab. In the case of square or rectangular columns, the critical section can be assumed

to be at a distance 𝑑 2� from the face of the column on all sides (ACI 318, 2008).

The ACI slab shear strength equations are empirically based on the work of Moe in 1961.

Moe tested a series of slabs and found that the punching strength has a direct relationship

to the compressive strength of the concrete, but did not factor in the amount of

reinforcement or size effects.

Page 37: EVALUATION OF TENSILE AND COMPRESSIVE

26

The Eurocode EC-2 defines the shear strength of a flat-plate as the following:

𝑉𝑐𝑢 = [0.167(1.6 − 𝑑)𝑓′𝑐(1.2 + 40𝜌)]𝑏𝑤𝑑 Equation 4

where 𝜌 is the reinforcement ratio and the depth to the steel 𝑑 is in millimeters. One

important difference in the EC-2 code versus the ACI-318 is that the EC-2 considers the

amount of steel in the slab when calculating the shear strength.

The Model Code 90 considers various parameters such as concrete strength, rotation of

the slab at failure, and yield strength of the flexural reinforcement to predict the shearing

strength of flat-plate slabs. The equation formulated for use in the Model Code 90 to

estimate the shear strength provided by the concrete is given as the following:

𝑉𝑐 = 𝑘𝛹�𝑓′𝑐𝛾𝑐

𝑏0𝑑 Equation 5

where 𝑘𝛹 is a coefficient that considers the rotation of the slab at failure, 𝑏0 is the

perimeter of the critical failure section, and γc is a partial safety factor for concrete taken

as 0.67 (Gardner, 2011).

2.6. Strength Predictions Developed from Research

Expressions have also been developed by researchers to estimate the punching shear

strength of flat-plates in recent years. Based on tests done on isolated slab-column

Page 38: EVALUATION OF TENSILE AND COMPRESSIVE

27

specimens by Tian in 2008, he derived the following expression for the shear strength of

a slab-column connection:

𝑉𝑛 = 2.3ξ𝐴𝑐�(𝜌𝑓𝑦�𝑓′𝑐) Equation 6

where ξ = �𝑑𝑐 and d is the depth to the reinforcing steel, c is the width of the column, 𝑓𝑦

is the yield strength of the reinforcing steel, and 𝐴𝑐 is the area of the critical section as

defined by ACI. Unlike the ACI, Eurocode, or Model Code standards, the equation

developed by Tian considers both reinforcement ratio and the yield strength of the

reinforcement.

A more complex expression was developed by Gardner in 2011 based on a combination

of previous tests done on isolated slab-column specimens and supplemental analysis. The

equation he proposed for the shear strength is the following:

𝑣𝑟 = 0.55λ �1 + �250ℎ�12� � ℎ

4𝑐�1/2

�𝛷𝑠𝜌𝑓𝑦𝛷𝑐𝑓′𝑐�1/3

Equation 7

where 𝑣𝑟 is the allowable shear stress, λ = 1.0 for normal weight concrete, 𝛷𝑠 is a partial

safety factor for concrete equal to 0.87, and 𝛷𝑐 is another partial safety factor for concrete

equal to 0.67. The equation is empirical and must be used with the International System

of Units (SI).

Page 39: EVALUATION OF TENSILE AND COMPRESSIVE

28

3. EXPERIMENT SETUP

One reinforced concrete slab was designed, constructed, and tested for this particular

phase of the research. The tested slab was Test 1 from the test matrix shown previously in

Table 1.2.1.

This chapter will discuss the design of the prototype building, the design of the test

specimen, and predictions on the punching shear capacity of the isolated test specimen

based on equations derived from previous tests. Lastly, the design and construction of the

test setup will be detailed.

3.1. Design of Prototype Building

The prototype building was designed to resemble an older flat-plate reinforced concrete

building. It was designed per the 1971 version of the ACI concrete building code in order

to closely simulate an older flat-plate structure. The prototype building is five stories tall

with a 4-bay by 4-bay layout. The spans are all 20 feet in both directions and the assumed

concrete cover for the reinforcing steel is 0.75 inches. The concrete is designed to have a

unit weight of 150 lb/ft³ with a compressive strength of 4000 psi. The reinforcing steel is

assumed to be Grade 60, with a design yield stress of 60 ksi. A minimum slab thickness

was calculated per ACI 318-71 and a thickness of 7.5 inches was chosen to satisfy the

minimum requirement of 6.875 inches. The minimum requirement of 6.875 inches was

calculated as a function of the building geometry and the yield strength of the

reinforcement. The column was chosen to be a square shape with sides of 15 inches long.

Page 40: EVALUATION OF TENSILE AND COMPRESSIVE

29

The prototype building was designed to resist superimposed dead loads, self-weight of

the slab, and live loads. The design superimposed dead load was 20 psf while the design

live load was 50 psf. A bending moment was calculated and used to design the tension

and compression reinforcement in the slab using the direct design procedure. A plan view

of the prototype building can be seen in Figure 3.1.1.

Figure 3.1.1: Plan view of prototype building

It was determined from design that a reinforcement ratio of 0.57% was needed to resist

the applied moment in the column strip in the negative direction and 0.24% in the

positive direction. Therefore, for an interior span column strip, #4 bars spaced at 5 inches

were chosen for the tension reinforcement and #4 bars spaced at 9 inches were chosen for

Page 41: EVALUATION OF TENSILE AND COMPRESSIVE

30

the compression reinforcement. A final layout of an interior span column strip with

reinforcement details can be seen in Figures 3.1.2 and 3.1.3. However, the interest of this

research lies in the punching strength and ductility of flat-plates which is highly

dependent on the reinforcement ratio. Thus, reinforcement ratios were chosen for testing

in the range of 0.5% and 1%. The specimen tested in this research is at the higher end

with a reinforcement ratio of 1%. The 1% reinforcement ratio is associated with the

percentage of steel in a given area of concrete.

Figure 3.1.2: Tension reinforcement in prototype building

Page 42: EVALUATION OF TENSILE AND COMPRESSIVE

31

Figure 3.1.3: Compression reinforcement of prototype building

3.2. Design of Test Specimen

For this research, an isolated slab-column specimen was tested to replicate an older flat-

plate reinforced concrete structure. The test specimen was constructed at 0.73 scale in

order to test the slab within the constraints of the testing facility. The prototype building

slab is only 27% larger than the test specimen. Testing at near full scale decreases the

issues that arise from size effects and allows for better understanding of the behavior of

the real structure. With the 0.73 scale, the test slab was 5.5 inches thick with a square

column that was 11 inches long in both directions. The slab itself was 70 inches square

with a 9 inch long column stud on both the top and bottom faces. Including column studs

on both faces allowed for accurate depictions of the stress distributions around the

column. To match the prototype design reinforcement ratio and double it to 1%, #4 bars

spaced at 4.5 inches were used for the tension reinforcement and #3 bars spaced at 4.5

inches were used for the compression reinforcement. In addition, all the bars in the slab

were made continuous to better develop the tensile membrane action following punching

Page 43: EVALUATION OF TENSILE AND COMPRESSIVE

32

failure. The two-way slab consisted of reinforcement in both directions for the top and

bottom mats. A layout of the slab with reinforcement details can be seen in Figures 3.2.1

and 3.2.2. The column was designed considering only gravity loads (no lateral loads) and

a standard layout of 4 #6 longitudinal bars with #3 ties spaced at 3 inches was used. An

elevation view of the slab showing the column reinforcement is shown in Figure 3.2.3.

All bars were hooked at both ends with 180 degree bends and a 3.5 inch hook as shown

in Figure 3.2.4. The concrete cover was 0.5 inches on all sides.

Figure 3.2.1: Layout of tension reinforcement showing anchors

Page 44: EVALUATION OF TENSILE AND COMPRESSIVE

33

Figure 3.2.2: Layout of compression reinforcement showing anchors

Page 45: EVALUATION OF TENSILE AND COMPRESSIVE

34

Elevation of slab

Section A-A through column

Figure 3.2.3: Elevation of slab showing section through column

Page 46: EVALUATION OF TENSILE AND COMPRESSIVE

35

Hooked Rebar Detail for #4 bars

Hooked Rebar Detail for #3 bars

Figure 3.2.4: Hooked Reinforcement Detail for top and bottom bars

3.3. Test Specimen Construction

The construction of the test slab was broken down into a few phases. The first step was

construction of the formwork for the slab. The slab was designed to have a 5.5 inch

thickness so 2 by 6's (which actually have a 5.5 inch width) were used to create the side

forms of the slab. The bottom was simply 3/4 inch plywood which was placed on a grid

of 2 by 4's and 2 by 6's to accommodate the bottom column stud. The bottom column

stud was also constructed using plywood and was able to sit on the floor with the rest of

the slab raised off the ground using the grid as shown in Figure 3.3.1. Triangular braces

were used around the sides of the form to stiffen the form against the weight of the wet

concrete when it was time to pour. The top column stud was constructed out of plywood

and was supported on 2 by 6's that sat on the sides of the form, illustrated in Figure 3.3.2.

Page 47: EVALUATION OF TENSILE AND COMPRESSIVE

36

Figure 3.3.1: Formwork of slab

Figure 3.3.2: Formwork with top column stud and reinforcement

Page 48: EVALUATION OF TENSILE AND COMPRESSIVE

37

The tied reinforcement mats were placed in the form and positioned in such a way to

allow for a half inch cover on all sides. To provide the half inch over on the bottom of the

slab, several small pieces of #4 rebar (which has a nominal diameter of 0.5 inches) were

tied to the bottom of the cage to act as chairs. The column reinforcement was not

significantly important to the test, but was included to keep the concrete together in the

column when the slab approached the punching failure load. The column reinforcement

consisted of 4 #6 longitudinal bars at the corners with #3 ties spaced at 3 inches. A

photograph of the finished column reinforcement with strain gage wires from the slab

reinforcement out the top can be seen in Figure 3.3.3. The form with all reinforcement

and anchorage assembly can be seen in Figure 3.3.4.

Figure 3.3.3: Column reinforcement as seen through the top column

Page 49: EVALUATION OF TENSILE AND COMPRESSIVE

38

Figure 3.3.4: Finished form with reinforcement

Figure 3.3.5: Reinforcement showing scale

After all of the reinforcement was placed in position inside the form, the slab could be

poured. Wet concrete was poured into the form and a vibrating tool was used to

Page 50: EVALUATION OF TENSILE AND COMPRESSIVE

39

consolidate the concrete as shown in Figure 3.3.6. While the slab was being poured, 8

cylinders were also filled with wet concrete and capped for determining exact

compressive strength after the curing time. After pouring, the concrete was carefully

finished on the top of the slab and the top of the column to create a smooth surface. The

strain gage wires from all of the reinforcement were strung through the top of the slab

and wrapped to prevent any potential damage from moisture. Finally, to avoid shrinkage

issues, the slab was covered to keep the moisture inside. The slab was also hydrated for

the next several days to maintain that level of moisture.

Figure 3.3.6: Poured concrete being vibrated

Page 51: EVALUATION OF TENSILE AND COMPRESSIVE

40

Figure 3.3.7: Finished concrete slab

3.4. Test Setup Design

The test setup needed to be designed to closely resemble that of the real structure. An

analysis was performed at the University of Nevada-Las Vegas in order to estimate the

needed value of in-plane lateral restraint. A schematic of the final test setup design with

the slab attached is shown in Figure 3.4.1. A three dimensional view of the test setup

design can be seen in Figure 3.4.2.

Page 52: EVALUATION OF TENSILE AND COMPRESSIVE

41

Figure 3.4.1: 2D view of final test setup

Figure 3.4.2: 3D view of final test setup

Page 53: EVALUATION OF TENSILE AND COMPRESSIVE

42

The test setup was designed to provide a lateral stiffness of about 1600 k/in. Large

W14x132 wide flange sections that were connected to the lab floor were connected to the

slab on each side and were determined to provide sufficient horizontal stiffness. The

connection of the slab to the steel columns needed careful consideration. The connection

was designed considering the axial load that would be applied to the slab and the

resulting induced lateral forces. An 8x8x1 angle section supporting the slab was bolted to

a bracket-female clevis assembly with a threaded stud attached to the female clevis. The

clevis was connected to the bracket with a pin to allow for rotational translation in the

slab. The threaded stud was supported with a HSS 6x4x3/8 section with two 1/4 inch

plates welded to each side to provide some extra stiffness. A nut on the outer edge was

tightened to simulate the lateral restraint. However, the assembly was designed so that if

the nut was omitted, the threaded stud would be free to move laterally to simulate an

unrestrained condition. The connection design also allowed for load cells to measure the

in-plane forces. A schematic and photograph of the finished assembly can be seen in

Figures 3.4.3 and 3.4.4.

Page 54: EVALUATION OF TENSILE AND COMPRESSIVE

43

Figure 3.4.3: Drawing of connection plan

Figure 3.4.4: Finished assembly of connection to steel frames

Page 55: EVALUATION OF TENSILE AND COMPRESSIVE

44

In addition, a simulation of headed rebar was used as anchorage in the slab to provide the

tensile in-plane lateral restraint. The headed rebar were simulated using 5/8 inch diameter

threaded rods with 2.5 inch by 2.5 inch, 0.75 inch thick steel plates attached to one end.

The bars were cast into the concrete with an embedment length of 9 inches. One half inch

plates were attached to the top of the concrete with 5/8 inch diameter threaded rods to

provide additional friction resistance and confine the concrete in the region of the anchor.

To accommodate the threaded rods through the slab, polyvinyl chloride (PVC) pipes

were cast in with the concrete. A schematic of the anchorage and connections can be seen

in Figure 3.4.5 and a photo of the final assembly in shown in Figure 3.4.6.

Figure 3.4.5: Details of anchorage design

5/8” threaded

rod

Page 56: EVALUATION OF TENSILE AND COMPRESSIVE

45

Figure 3.4.6: Anchorage assembly with PVC pipes

A hydraulic actuator was then attached above the slab to the cross beams to be used to

load the specimen. The hydraulic ram was attached to an extension so that it could reach

the top of the column stud. A 1 inch steel plate was placed on top of the column stud to

more evenly distribute the load over the entire area of the column. The attached ram and

extension can be seen in Figure 3.4.7. The completed setup of the testing apparatus with

the specimen is shown in Figure 3.4.8.

Page 57: EVALUATION OF TENSILE AND COMPRESSIVE

46

Figure 3.4.7: Hydraulic actuator with extension above slab

Figure 3.4.8: Complete construction of test setup

Page 58: EVALUATION OF TENSILE AND COMPRESSIVE

47

3.5. Instrumentation

In order to collect data from the test, several forms of instrumentation were attached to

the specimen and were connected to a data acquisition system. Load cells, reinforcement

strain gages, concrete strain gages, linear variable differential transducers (LVDT), and

string pots were among the forms of instrumentation used in the testing. The data

acquisition system with all of the instrumentation connected is shown in Figure 3.5.1.

Figure 3.5.1: Data acquisition system with connected instrumentation

Five load cells were used in the testing of the specimen: one on the center column stud,

two tension load cells (one in each direction) and two compression load cells (one in each

direction) on the sides of the slab. The center load cell measured the applied center load

to the specimen, while the compression and tension load cells measured the induced

Page 59: EVALUATION OF TENSILE AND COMPRESSIVE

48

lateral forces on the slab. The center load cell can be seen in Figure 3.5.2 and the

compression and tension load cells are shown in Figure 3.4.4 which was shown

previously in this chapter.

Figure 3.5.2: Center load cell underneath hydraulic actuator

Thirty-one strain gages were designed to be placed on the reinforcement to monitor the

strain of the bars during testing. Twenty-one gages were placed on the tension

reinforcement mat and 10 gages were applied to the compression reinforcement mat. To

accommodate the gages, bar deformations were ground down in the specified locations

where the strain gages were going to be placed. Then, the gages were applied to the rebar

using a standard procedure involving surface preparation and adhering. The location of

the strain gages were chosen based on the fact that the punching failure will be located in

the vicinity of the column. To allow for some redundancy, gages were placed in similar

locations around the perimeter of the column stud. In addition, gages were placed on

alternate bars if too many gages needed to be placed too close together to reduce the

Page 60: EVALUATION OF TENSILE AND COMPRESSIVE

49

susceptibility of bond distress between the concrete and reinforcing bar. The final layout

of the strain gages on the reinforcing bars can be seen in Figure 3.5.3 and 3.5.4.

Figure 3.5.3: Strain gage locations on tension reinforcement mat

Page 61: EVALUATION OF TENSILE AND COMPRESSIVE

50

Figure 3.5.4: Strain gage locations on compression reinforcement mat

There were also 8 strain gages applied to the threaded studs to show the deformation in

the studs from the in-plane lateral forces. Four total concrete strain gages were also

applied to the surface of the concrete in the proximity of the top column stud to monitor

the behavior of the concrete prior to punching. One concrete gage was applied parallel to

the column face and another was perpendicular. To add some redundancy, the same

configuration of gages was applied to another perpendicular side of the column resulting

in the 4 total concrete gages.

Page 62: EVALUATION OF TENSILE AND COMPRESSIVE

51

To measure the horizontal displacement of the slab, LVDT's were placed on each edge of

the specimen resulting in 4 total LVDT's. The LVDT's were attached to short columns

that were independent of the test setup to ensure that the data was accurate. A photograph

of the LVDT on the south edge of the slab can be seen in Figure 3.5.5

Figure 3.5.5: South LVDT clamped to support

Finally, 5 string pots were used to measure the vertical deflection of the slab while being

loaded. They were calibrated when connected to the data acquisition system and placed

underneath the slab. The string pots were connected to small threaded rods that were cast

in the concrete and stuck out through the bottom of the slab. One string pot was placed

directly underneath the center column stud with the other 4 on orthogonal sides stemming

out from the center as shown in Figure 3.5.6. Since the concrete would be continuously

falling off from the slab after failure, the center string pot was protected with a steel

covering.

Page 63: EVALUATION OF TENSILE AND COMPRESSIVE

52

Figure 3.5.6: String pot locations underneath slab

Figure 3.5.7: String pots underneath slab

Page 64: EVALUATION OF TENSILE AND COMPRESSIVE

53

3.6. Material Properties

Material properties for the test were determined according to American Society of

Testing and Materials (ASTM) standards. The only property determined for this test was

the actual compressive strength of the batch that was used to construct the specimen. The

batch had a specified strength of 4000 psi, but the cylinders tested showed slightly higher

strengths. Four concrete cylinders were tested according to ASTM C39 and had strengths

ranging from 4100 psi to 4600 psi with an average strength of 4405 psi. All of the

strength values can be found in Table 3.7.1. The steel reinforcing bars had a specified

yield strength of 60 ksi but have not yet been tested in tension. In interpreting the results,

the reinforcing bars are assumed to have a yield strength of 60 ksi.

Table 3.6.1: Concrete cylinder strengths

3.7. Punching Strength Predictions

Upon using the formulas presented in Section 2.5, the punching shear strength of the

isolated test slab specimen for this research could be estimated. ACI 318-08 provides 3

Cylinder # Load Applied (lb) Strength (psi)

1 57,405 4,570

2 52,425 4,174

3 56,475 4,496

4 55,110 4,388

Average 55,354 4,405

Page 65: EVALUATION OF TENSILE AND COMPRESSIVE

54

equations to predict the punching shear strength of the slab. Calculation of the strength

using Equation 3 results in the smallest value of 74 kips. Eurocode EC-2 considers the

amount of reinforcement in the concrete and the predicted strength of the isolated

specimen was calculated to be 93.3 kips (Equation 4). The Model Code 90 implements

different parameters than both ACI 318 and Eurocode EC-2 as it considers the rotation of

the slab at the time of punching failure. The design capacity of the isolated slab test

specimen for this test using the Model Code 90 expression was 73 kips (Equation 5).

An expression that was developed from Tian’s research included the yield strength of the

reinforcement as well as the reinforcement ratio in addition to the compressive strength

of the concrete, the column size and the slab depth (Equation 6). Using this equation the

capacity of the slab was estimated to be 80.6 kips. This is the first equation that was used

which took into account the strength and volume of steel that was used as reinforcement

in the slab. The reinforcement is accounted for because the flexural reinforcement can

help to slow the growth of the inclined shear cracks that eventually lead to failure.

Gardner conducted a study on the punching strength of reinforced concrete slab-column

connections in 1996 to better understand the mechanisms of the failure. He used a control

perimeter around the loaded column area to obtain an expression for the allowable shear

stress of a slab-column connection. The equation considers concrete strength,

reinforcement yield strength, reinforcement ratio, depth of the slab and some concrete

safety factors. The shear strength of the test specimen according to equation developed by

Gardner is 87.9 kips, shown previously in Equation 7.

Page 66: EVALUATION OF TENSILE AND COMPRESSIVE

55

Some of the differences in the predicted capacities occur because of the equations taking

into account different factors. However all of the equations used take into account what

is called the critical section; ACI 318 defines this area differently than Tian did in his

study. ACI 318 has a definition of the critical section that is much smaller, as Tian

suggested that the conical failure surface on the slab is larger than what ACI 318

anticipates. The critical section of the slab-column connection for the calculation using

Gardner's formula was assumed to be the same definition as what ACI 318 uses. Finally,

ACI 318 calculates the strength only considering the compressive strength of the

concrete.

Page 67: EVALUATION OF TENSILE AND COMPRESSIVE

56

4. TEST RESULTS

A restrained flat-plate reinforced concrete isolated slab-column connection with

continuous tension and compression reinforcement was tested in negative bending. The

results from that test will be presented and discussed in this chapter. Due to some

instrumentation malfunctions, the results in this chapter will be separated between the

behavior of the slab up until the first punching failure and the post-punching behavior.

4.1. Pre-punching Behavior

The slab was tested at a rate of about 0.4 kips/sec up until the initial punching failure. As

shown in Figure 4.1.1, the slab exhibited near linear-elastic behavior until a load of about

10 kips. At this load, cracking began in the slab which resulted in a loss in stiffness. The

slab then continued behaving in a linear-elastic manner until the first punching failure.

About a minute and a half into the test, a plate in the test setup shifted which caused a

momentary loss in load which can be seen in Figure 4.1.1 at a load of around 50 kips. At

punching failure, the slab was briefly unloaded before the test continued. Figure 4.1.2

shows the failure underneath the slab (top of the slab in the real structure) just after the

punching failure. As seen in the figure the punching failure takes the typical form of a

conical crack around the column.

Page 68: EVALUATION OF TENSILE AND COMPRESSIVE

57

Figure 4.1.1: Load vs. center displacement plot before punching

Figure 4.1.2: Underneath slab immediately following punching failure

0

10

20

30

40

50

60

70

80

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6

Cent

er L

oad

(k)

Vertical Displacement (in)

Page 69: EVALUATION OF TENSILE AND COMPRESSIVE

58

The vertical displacement (Figure 4.1.3) was measured at 5 locations on the slab. As seen

in the figure all of the displacements are fairly consistent around the area of the slab. The

center string pot showed the largest displacement and all of the other string pots showed

similar displacements. The "1" locations are slightly closer to the column than the "2"

locations. In fact, the "1" string pots are located inside the critical failure section so it was

expected that they would closely follow the center deflection. The displacements show

that the entire slab was displacing vertically. After viewing the video of the test, it can be

seen that the threaded stud connecting the clevis to the steel column is rotating. This is

allowing the slab to deflect more around the "2" locations.

Figure 4.1.3: Load-displacement plots of all string pots

0

10

20

30

40

50

60

70

80

0 0.5 1 1.5 2

Cent

er L

oad

(k)

Vertical Displacement (in)

Center

North 1

North 2

East 1

East 2

Page 70: EVALUATION OF TENSILE AND COMPRESSIVE

59

A photograph of the slab at one point in the test transposed on top of an image of the slab

from a point in time later in the test is shown in Figure 4.1.4 to illustrate the connection

movement. In the figure, the supporting angles move downward from their initial position

at the beginning of the test. Figure 4.1.5 shows the adjusted vertical displacement of the

slab considering the rotation at the connections by subtracting the East 2 displacements

from the center displacement. From the figure, it can be determined that the slab actually

vertically displaced 0.44 inches at the time of punching failure. Comparing with Tian's

study of isolated slab-column specimens with 1% reinforcement ratio, the total

displacement in this test only reached 46% of the displacement in his test at punching

failure. However, it was found that the slab rotated 0.0149 radians at the time of punching

failure which is fairly consistent with Kinnunen and Nylander's results from slabs with

1% reinforcement ratio (Figure 2.4.2.1).

Figure 4.1.4: Composite image of slab showing vertical movement of connections

Page 71: EVALUATION OF TENSILE AND COMPRESSIVE

60

Figure 4.1.5: Load-displacement plot adjusted for rotational effects

In order to examine the effects of the in-plane lateral restraint, compression load cells,

tension load cells, and LVDT’s were used around the edges of the slab. Upon loading on

the center column stud, the slab wants to expand outward which induces lateral

compression forces. However, due to the rotation of the threaded stud connection

assembly, it is believed that the load cells were reading some flexural loads rather than

straight axial loads. A plot of the average horizontal compression loads and the average

LVDT displacements is shown in Figure 4.1.6. It can be seen from the figure that the

compressive forces on the slab reached a maximum of 5 kips and the corresponding

horizontal stiffness was 570 kip/in. This stiffness was only 36% of the desired horizontal

stiffness, indicating that the compressive membrane action was not fully developed to

enhance the capacity of the slab to its full potential. Using a static analysis, it was

determined that the 5 kip lateral compressive force enhanced the load capacity of the slab

by 0.5 kips, or a 1% increase. As shown in the figure, the slab expanded outward up until

0

10

20

30

40

50

60

70

80

0 0.1 0.2 0.3 0.4 0.5

Load

(k)

Center - East 2 Displacement (in)

Page 72: EVALUATION OF TENSILE AND COMPRESSIVE

61

a load of 5 kips then retracted back inward. However, the compressive load on the slab

continued to increase which was due to the flexural forces acting on the compression load

cell from the rotation.

Figure 4.1.6: Average horizontal loads vs. displacement

The compressive strain in the concrete itself has been known to be a good indicator of

when punching will occur. It has been experimentally shown in previous studies that

upon reaching a compressive strain of 0.0008 in/in, microcracks begin to form parallel to

the compression direction which can propagate to the connection to the column and cause

punching failure (Broms, 1990). From Figure 4.1.7, it can indeed be seen that once the

compression face of the concrete reached a strain of 0.0008 in/in, the strain appeared to

exponentially grow until the punching failure occurred. This specific phenomenon was

only evident with the concrete gages oriented parallel to the column face. Thus, cracks

-10

-9

-8

-7

-6

-5

-4

-3

-2

-1

00 0.002 0.004 0.006 0.008 0.01 0.012

Com

pres

sion

Loa

d (k

)

Displacement (in)

Page 73: EVALUATION OF TENSILE AND COMPRESSIVE

62

formed around this critical strain value and propagated through the critical section of the

slab-column connection that eventually led to the punching failure.

Figure 4.1.7: Concrete compressive strains before punching

The strain distribution of the reinforcement in the slab was a good indicator of how the

rebar was behaving around the instant of punching. It was found that 19 out of 20

functional gages on the tension reinforcement mat had yielded at time of punching

failure. From Figures 4.1.8 and 4.1.9, it is also apparent that the reinforcement closest to

the vicinity of the column experienced the most deformation prior to the punch. Gage

"T1" was located at the slab-column interface and all of the following gages (2, 3, 4, 5

and 6) were placed extending outward from the column (reference Figure 3.6.3). The

rebar with the T1 gage applied to it also is a continuous bar through the column, and it

can be seen in Figure 4.1.8 that it experiences significant strains up until the punching

0

0.0002

0.0004

0.0006

0.0008

0.001

0.0012

0.0014

0.0016

0 20 40 60 80

Conc

rete

Str

ain

(in/i

n)

Center Load (k)

West Parallel

West Perp

North Parallel

North Perp

Page 74: EVALUATION OF TENSILE AND COMPRESSIVE

63

failure. It is also the first bar to yield (at a load of 40 kips) by a fairly large margin

compared to the other bars. Figure 4.1.9 also shows how in general, the strains at the

punching failure were highest around the slab-column interface and decreased as they

moved outward from the column. In Tian's study, the strains in the tension reinforcement

bars were consistently around 0.003 in/in at the time of punching failure. He did not,

however, use continuous reinforcement through the column so it is reasonable to see the

strains on bars passing through the column are much larger. The bars that did not extend

through the column experienced strains closer to 0.003 in/in at the time of punching

failure.

Figure 4.1.8: Plot of tension reinforcement strains

0

0.002

0.004

0.006

0.008

0.01

0.012

0 20 40 60 80

Reba

r Str

ain

(in/i

n)

Center Load (k)

T1

T2

T3

T4

T5

T6

Page 75: EVALUATION OF TENSILE AND COMPRESSIVE

64

Figure 4.1.9: Tension rebar strains at punching failure (in microstrains)

Even though there were fewer gages on the compression reinforcement, they follow the

same behavior as that of the tension reinforcement. The gages located closest to the

column stud showed the reinforcement experiencing the most strain (Figure 4.1.10 and

4.1.11). Gages C1, C3, C4, C6, C7, and C9 were all located at the slab-column interface

or very close to it. It can be seen from Figure 4.1.10 that the bars were only stressed in

compression for a short time and then went into tension. This would suggest that once the

Page 76: EVALUATION OF TENSILE AND COMPRESSIVE

65

slab cracked due to flexural action, the shear dominated response of the slab produced

tension in the bars. It can also be seen from the figure that none of the compression bars

reached yield before the punching failure (at 0.002 in/in of strain).

Figure 4.1.10: Plot of compression reinforcement strains

From Figure 4.1.11, it can be seen that the rebar with the C1 gage applied had a much

larger strain than that of the rebar with the C7 gage applied even though they were both

located at the slab-column interface. The two reinforcement bars were oriented in

different directions (orthogonal to each other, Figure 3.6.4), suggesting that the slab was

being stressed more in one direction versus the other due to different levels of the

reinforcement.

-0.0005

0

0.0005

0.001

0.0015

0.002

0 20 40 60 80

Reba

r Str

ain

(in/i

n)

Center Load (k)

C1

C2

C3

C4

C5

C6

C7

C8

C9

C10

Page 77: EVALUATION OF TENSILE AND COMPRESSIVE

66

Figure 4.1.11: Compression rebar strains at punching failure (in microstrains)

4.2. Post-Punching Behavior

Upon reaching the punching failure load some of the data was skewed due to some

instrumentation malfunctions. When the column punched through the slab, it is believed

that one of the strain gage wires was ripped out and came into contact with a reinforcing

bar. This in turn resulted in intermittent shorting in the electrical circuits, causing the

excitation voltage to fluctuate. Some of the data was salvageable by determining what the

Page 78: EVALUATION OF TENSILE AND COMPRESSIVE

67

excitation voltage was at a particular instant and back-calculating what the new data

should be. Thus, the following results are a result of some manipulation of the data and

the validity of it can be considered questionable. The plot of the load versus the center

displacement for the entire test is shown in Figure 4.2.1.

Figure 4.2.1: Center load-displacement plot for entire test

In the figure, the data that was considered good is in blue and the data that needed to be

manipulated as a result of the excitation voltage issue are in different colors (red, green,

and purple). Due to an operator error, the slab was temporarily unloaded after the first

punching failure. From the plot, it can be shown that the behavior of the slab after the

first punching failure followed a noisier trend than that of the pre-punching behavior. In

general, it can be seen that the slab achieved a residual capacity of nearly the first

punching capacity of 70 kips. This would indicate that the continuous reinforcement was

able to develop full tensile membrane action in the slab. It can be seen in Figure 4.2.2 that

0

10

20

30

40

50

60

70

80

0 1 2 3 4 5 6

Load

(k)

Displacement (in)

True data

Manipulated

Manipulated

Manipulated

Page 79: EVALUATION OF TENSILE AND COMPRESSIVE

68

the column displaced a significant amount through the slab. Figure 4.2.1 shows drops in

load capacity following the peak residual capacity which can be associated with

compression reinforcement bars fracturing. During the test, the fracturing of the #3 bars

could be heard when the slab reached a residual load of 60 kips. 3 #3 compression

reinforcement bars fractured during the test. A photo of a fractured #3 rebar near the

column can be seen in Figure 4.2.3.

Figure 4.2.2: Top column stud after testing

Figure 4.2.3: Fractured compression steel

Original #3 bar location

Fractured #3

Page 80: EVALUATION OF TENSILE AND COMPRESSIVE

69

Many of the tension mat reinforcement gages were damaged at the punching failure so

their post-punching data was compromised. However, several gages did continue reading

strains following the punching failure. As with the behavior of the reinforcement prior to

the punching failure, the rebar strains were greatest in the vicinity of the column stud

throughout the whole test. The gage that was closest to the column (T10) experienced the

most strain after the punching failure whereas the gages farther away from the column

stud (T14 and T20) showed smaller deformations. The bar with the T10 gage attached

showed strains reaching nearly 0.007 in/in. Figure 4.2.4 shows the extreme deformations

of the tension reinforcement. These large strains indicate that tensile membrane action

was being developed to its full potential in providing the slab with significant ductility.

Figure 4.2.4: Deformation of exposed tension reinforcement

Page 81: EVALUATION OF TENSILE AND COMPRESSIVE

70

As seen in Figure 4.2.5, the strain in the reinforcement grows larger in the vicinity of the

column. The figure shows strain data on a bar extending through the column from a point

during the test when tensile membrane action is being developed. The centerline of the

column is located approximately at the centerline of the rebar, which is at 34.5 inches.

The gage with the highest reading (T10) was at the slab-column interface at a distance

6.75 inches from the centerline of the rebar, or 1.25 inches from the face of the column.

Figure 4.2.5: Strain distribution across tension rebar

The compression reinforcement behaved in a similar way following the punching failure

as the highest strains were found in the vicinity of the column. It was found that 3 of the

#3 compression bars had fractured during the test, but the data only shows one gage (C4)

even showed yielding towards the end of the test. Due to the increased spalling of the

concrete, the tension reinforcement no longer was confined in the slab leading to the

0

0.001

0.002

0.003

0.004

0.005

0.006

0 10 20 30 40 50 60

Stra

in (i

n/in

)

Distance along rebar (in)

Page 82: EVALUATION OF TENSILE AND COMPRESSIVE

71

compression reinforcement taking most of the load. This eventually led to the bars

fracturing, seen previously in Figure 4.2.3.

Figure 4.2.6: Underneath slab after unloading

As stated earlier, due to the electrical problems with the instrumentation extensive results

on the post-punching behavior of the slab cannot be accurately analyzed. It is worth

noting, however, that the tensile membrane action was fully engaged in achieving a

residual load capacity of nearly 70 kips. The residual capacity was significantly greater

due to the inclusion of continuous reinforcement through the column.

Page 83: EVALUATION OF TENSILE AND COMPRESSIVE

72

5. SUMMARY, CONCLUSIONS AND FUTURE RESEARCH

5.1. Summary

The main objective of this research project as a whole is to evaluate the punching failure

mechanisms of a flat-plate reinforced concrete slab subjected to the loss of a nearby

supporting column. Upon removal of the column there are increased stresses in the

nearby columns which could possibly lead to a progressive collapse. Standards

implemented to design against progressive collapse are few, so the goal is to better

understand how flat-plate structures can resist the progression of the collapse. The main

focus of this part of the research is to evaluate the punching shear capacity of a flat-plate

slab with continuous reinforcement through the column and utilizing the potential

benefits of in-plane lateral restraint. This will allow better understanding of how the

mechanisms of compressive membrane action and tensile membrane action can improve

the punching capacity of a flat-plate as well as the post-punching residual capacity.

ACI 318-08 implements simple equations to calculate the punching shear capacity of a

non-prestressed reinforced concrete slab, and it was determined that the test specimen

should have achieved a peak load of 74 kips. However, this capacity is only an empirical

function of concrete strength and does not include other important factors such as

reinforcement ratio. Tian developed a relationship that took the yield strength of the

reinforcement as well as the reinforcement ratio into account when calculating punching

strength. The capacity of the test specimen using this equation was 80.6 kips. Although

these values were adequate in estimating the punching strength of the slab, there are no

extensive tests performed that can be used to predict the post-punching capacity of a flat-

Page 84: EVALUATION OF TENSILE AND COMPRESSIVE

73

plate slab. There are also no expressions that have been developed that consider in-plane

lateral restraint and how it quantitatively enhances the punching capacity.

The slab was loaded at a static rate of 0.4 kip/sec and achieved a punching capacity of 70

kips. Cracking began to occur at a load of 10 kips resulting in a loss in stiffness in the

slab. The horizontal compression force on the slab reached a maximum of 5 kips and

0.009 inches of displacement resulting in a horizontal stiffness of 570 kip/in. This

stiffness was only 36% of the design stiffness of 1600 kip/in, suggesting that the setup

design was not sufficient in achieving the stiffness necessary to develop the full potential

of compressive membrane action. Using a static analysis, it was determined that the slab

achieved an extra load capacity of 0.5 kips from compressive arch action with a peak

horizontal compressive load of 5 kips. All of the tension reinforcement bars with gages

applied experienced yield at early times in the test. The bars that were continuous through

the column yielded well before the bars located more on the outer edge of the slab; the

continuous bars though the column yielded at a center load of 36 kips, or about half of the

peak punching load near the slab-column interface. The top compression reinforcement

bars were only in compression for a short period of time before they all went into tension

at a center load of 43 kips. As with the tension reinforcement, the compression bars

experienced the most stress at the slab-column interface.

In summary, the slab performed very well following the initial punching failure, reaching

a peak residual capacity of 69 kips. However, the validity of the data following the initial

punching failure is in question because of a malfunction associated with the

Page 85: EVALUATION OF TENSILE AND COMPRESSIVE

74

instrumentation. The continuous reinforcement through the slab provided sufficient

ductility to develop the tensile membrane action to its full potential. The tensile

reinforcement reached strains up to 0.007 in/in, indicating they were plastically

deforming by a significant amount. During the test, there were drops in loading around

the peak residual capacity which was associated with 3 of the #3 bars fracturing. Because

the tensile reinforcement bars ripped out of the slab, they were able to achieve a longer

catenary curve and reduce the stress in the bars. The compression reinforcement was not

able to rip out of the concrete and its deformation was limited to a small length near the

column stud. Therefore the compression reinforcement carried the majority of the tensile

membrane action. The smaller sized rebar fractured under the increased stresses in the

vicinity of the column stud. In typical older reinforced concrete slabs the compression

reinforcement would not be continuous and the slab would not be able to see the high

residual capacity as seen in this test.

5.2. Conclusions

The conclusions drawn from the results of this research phase are:

• The specimen performed reasonably well in achieving a punching capacity that is

fairly consistent with past tests and estimations. The in-plane lateral restraint is

believed to have enhanced the load-carrying capacity by a small amount through

compression. Based on static analysis, the compressive membrane action only

enhanced the capacity of the test specimen by about 1%. However, the lateral

stiffness was not sufficient enough during the test to develop the full benefits of

the compressive membrane action mechanism.

Page 86: EVALUATION OF TENSILE AND COMPRESSIVE

75

• Following the punching failure, the specimen performed very well in developing a

residual capacity of nearly 70 kips. The continuous reinforcement through the

column was sufficient in developing the full benefit of tensile membrane action.

The specimen showed a tremendous amount of ductility following the initial

punching failure. The high residual strength achieved through this specimen

shows that one way to arrest the progression of collapse could be to provide

continuous compression reinforcement.

5.3. Future Research Goals

The results and conclusions drawn from this test highlight the need for the following

future research:

• For the remaining slab tests in this research plan, the horizontal stiffness of the

test setup must be improved in order to develop the full benefits of compressive

membrane action.

• The effect of reinforcement ratio on the punching capacity will be analyzed with

slabs with lower reinforcement ratios (0.5%) tested without continuous

compression reinforcement.

• To better understand the benefits of compressive membrane action, slabs will be

tested without in-plane lateral restraint.

• The effects of dynamic loading on the punching capacity of flat-plates will be

studied.

• The results from the above testing parameters will be compiled to better

understand how flat-plates behave in a progressive collapse scenario. Thus,

Page 87: EVALUATION OF TENSILE AND COMPRESSIVE

76

appropriate mitigation strategies can be implemented to help design against

progressive collapse in flat-plate reinforced concrete buildings.

Page 88: EVALUATION OF TENSILE AND COMPRESSIVE

77

REFERENCES

Aberdeen Group, The. (1956). "Construction Failure at Jackson, Michigan." Jackson, MI. 1956.

American Concrete Institute. (1971). “Building Code Requirements for Reinforced Concrete (318-71).” Detroit, MI. American Concrete Institute. (2008). “Building Code Requirements for Structural Concrete (318-08).” Farmington Hills, MI. Bailey, Colin G. (2000). "Membrane action of unrestrained lightly reinforced concrete

slabs at large displacements." Engineering Structures 23, 470-483. Broms, Carl E. (1990). "Punching of Flat Plates - A Question of Concrete Properties in

Biaxial Compression and Size Effect." ACI Structural Journal, No. 87-S30, June 1990.

Calavera, J. (2001). "Comparison of Eurocode 2, Model Code 90 and ACI 318-99 with

regard to shear and punching provisions for footings." Structural Concrete, Vol. 2 (4), December 2001, pp. 183-186.

Crowder, Brian. (2005). "Progressive Collapse - Historical Perspective." Naval Facilities

Engineering Command. Power-point presentation, 2005. Elstner, Richard C. and Hognestad, Eivind. (1956). "Shearing Strength of Reinforced

Concrete Slabs." ACI Journal, July 1956. Gardner, N.J. (2011). "Verification of Punching Shear Provisions for Reinforced

Concrete Flat Slabs." ACI Structural Journal, No. 108-S54, October 2011. Gardner, N.J., Chung, Lan, and Huh, Jungsuck. (2002). "Lessons from the Sampoong

department store collapse." Cement & Concrete Composites 24, 523-529. Gardner, N.J. and Shao, Xiao-yun. (1996). "Punching Shear of Continuous Flat

Reinforced Concrete Slabs." ACI Structural Journal, No. 93-S20, April 1996. Guice, Leslie K. and Rhomberg, Edward J. (1988). "Membrane Action in Partially

Restrained Slabs." ACI Structural Journal, No. 85-S34, August 1988. Guice, Leslie K., Rhomberg, Edward J., and Slawson, Thomas R. (1989). "Membrane

Analysis of Flat Plate Slabs." ACI Structural Journal, No. 85-S10, February 1989. Harris, Devin K. (2004). "Characterization of Punching Shear Capacity of Thin UHPC

Plates." Masters Thesis, 2004.

Page 89: EVALUATION OF TENSILE AND COMPRESSIVE

78

International Federation for Structural Concrete. (2010). "Model Code 2010". Lausanne,

Switzerland. King, S. and Delatte, N. (2004). ”Collapse of 2000 Commonwealth Avenue: Punching

Shear Case Study.” J. Perform. Constr. Facil., 18(1), 54–61. Kinnunen, S., and Nylander, H., “Punching of Concrete Slabs Without Shear

Reinforcement,” Transactions of the Royal Institute of Technology, No. 158, Stockholm, Sweden, 1960, 112 pp. Muttoni, Aurelio. (2008). "Punching Shear Strength of Reinforced Concrete Slabs

without Transverse Reinforcement." ACI Structural Journal, No. 105-S42, August 2008.

Tian, Ying, Jirsa, James O., Bayrak, Oguzhan, Widianto, and Argudo, Jaime F. (2008).

"Behavior of Slab-Column Connections of Existing Flat-Plate Structures." ACI Structural Journal, No. 105-S52, October 2008.

Vecchio, F.J. and Tang, K. (1989). "Membrane action in reinforced concrete slabs."

Toronto, Ont., Canada. 1989. Wight J. and MacGregor, J. (2005). "Reinforced Concrete Mechanics and Design." Upper

Saddle River. New Jersey, 2005.

Page 90: EVALUATION OF TENSILE AND COMPRESSIVE

79

APPENDIX 1

Figure A.1: Center load vs. Time plot until punching failure

Figure A.2: Center Displacement vs. Time plot until punching failure

0

10

20

30

40

50

60

70

80

0 20 40 60 80 100 120 140 160

Load

(kip

)

Time

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

0 20 40 60 80 100 120 140 160

Disp

lace

men

t (in

)

Time

Page 91: EVALUATION OF TENSILE AND COMPRESSIVE

80

Figure A.3: LVDT displacements vs. Center Displacement plot until punching failure

Figure A.4: Center Load vs. Time for entire test

-0.04

-0.02

0

0.02

0.04

0.06

0.08

0.1

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6

Late

ral D

ispl

acem

ent (

in)

Center Displacement (in)

East

South

West

0

10

20

30

40

50

60

70

80

0 100 200 300 400 500

Load

(kip

)

Time (s)

Page 92: EVALUATION OF TENSILE AND COMPRESSIVE

81

Figure A.5: Load Cell data vs. Time for entire test

Figure A.6: Rebar Strains vs. Center Displacement for entire test

-20-10

01020304050607080

0 100 200 300 400 500

Load

Time (s)

East Comp. Load - 100 kip

North Tension Load - 50 kip

North Comp Load - 100 kip

CntrLdCell

0

0.001

0.002

0.003

0.004

0.005

0.006

0.007

0 1 2 3 4 5 6

Reba

r Str

ain

(in/i

n)

Center Displacement (in)

T10

T14

T15

T20

Page 93: EVALUATION OF TENSILE AND COMPRESSIVE

82

Figure A.7: Final test setup

Figure A.8: Angle supporting slab with bracket and clevis connection

Page 94: EVALUATION OF TENSILE AND COMPRESSIVE

83

Figure A.9: Underneath slab following punching failure

Figure A.10: Underneath slab at end of test

Page 95: EVALUATION OF TENSILE AND COMPRESSIVE

84

Figure A.11: Fracture #3 compression steel

Figure A.12: Displaced top column stud after loading