Environmental Controls Environmental Controls I/IG I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example
42

Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Dec 22, 2015

Download

Documents

Letitia Welch
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Environmental Controls I/IGEnvironmental Controls I/IGEnvironmental Controls I/IGEnvironmental Controls I/IG

Lecture 7

Upfeed SystemsPipe Sizing Procedure Pipe Sizing Example

Lecture 7

Upfeed SystemsPipe Sizing Procedure Pipe Sizing Example

Page 2: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Upfeed SystemsUpfeed SystemsUpfeed SystemsUpfeed Systems

Page 3: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Pressure in Upfeed SystemsPressure in Upfeed Systems

Fixture pressure head Static headFriction head lossMeter pressure loss

S: p. 913, F.21.13

Page 4: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Pressure in Upfeed SystemsPressure in Upfeed Systems

Proper fixture flow pressureA+ Pressure lost due to heightB+ Pressure lost due to frictionC+ Pressure lost through meterD Total street main pressure E

Page 5: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

A: FixtureA: FixtureFlow PressureFlow Pressure

Pressure needed to get water through fixture

S: p. 970, T.21.14

Page 6: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

B: Pressure lost due to B: Pressure lost due to heightheight

Weight of water column

S: p. 913, F.21.13

Page 7: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

C: Pressure loss due to C: Pressure loss due to frictionfriction

Initially unknown, must be calculated based on pressure remaining after accounting for the other factors

Page 8: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

D: Pressure lost through D: Pressure lost through metermeter

Make initial size assumption and then repeat to optimum size

S: p. 971, F.21.63a

Page 9: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

E: Total Street Main E: Total Street Main PressurePressure

Check with water company or fire department

Page 10: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Pipe Sizing ProcedurePipe Sizing ProcedurePipe Sizing ProcedurePipe Sizing Procedure

Page 11: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

1. Determine 1. Determine Supply Supply Fixture Fixture Units Units

Fixture units take into account usage diversity

S: p. 974, T.21.15

Page 12: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

2. Calculate Demand Flow2. Calculate Demand Flow

Use curve 1 for flush valve dominated systemUse curve 2 for flush tank dominated systems

S: p. 975, F.21.65a

Page 13: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

3. Determine the 3. Determine the “Most Critical Fixture (MCF)”“Most Critical Fixture (MCF)”

Highest and farthest from inlet main

Confirm pressure required (A)

Identify height (B)

S: p. 958, F.21.52

Page 14: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

4. Determine Developed 4. Determine Developed LengthLength

The total length of all horizontal and vertical pipes from the main to the MCF

S: p. 995, F.22.17

Page 15: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

5. Determine Total 5. Determine Total Effective Length (TEL)Effective Length (TEL)

Two approaches:

1. equivalent length or2. multiply DL x 1.5

TEL= DL x 1.5

S: p. 976, T.21.16a

Page 16: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

6. Determine Street 6. Determine Street Main Pressure (E)Main Pressure (E)

Contact utility company or fire department

Page 17: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

7. Determine Pressure 7. Determine Pressure Available for Friction Loss Available for Friction Loss

Proper fixture flow pressureA+ Pressure lost due to heightB+ Pressure lost due to frictionC+ Pressure lost through meter D Total street main pressure E

orC=E-A-B-D

Page 18: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Meter Loss (D)Meter Loss (D)

Since D is unknown, pick an initial size, do calculation, repeat as needed to optimize flow

C=E-A-B-D

S: p. 971, F.21.63a

Page 19: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

8. Determine Friction 8. Determine Friction loss/100’loss/100’

C=E-A-B-D

Δp/100’ = 100 x C/TEL

Page 20: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

9. Verify flow 9. Verify flow for meter sizefor meter size

If flow > Total Demand (#2) repeat 7-9 at smaller diameter

If flow < Total Demand (#2) repeat 7-9 at larger diameter

S: p. 972, F.21.64a

Page 21: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

10. Select final10. Select finalmeter sizemeter size

When flow > Total Demand (#2) stop

S: p. 972, F.21.64a

Page 22: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Pipe Sizing ExamplePipe Sizing ExamplePipe Sizing ExamplePipe Sizing Example

Page 23: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Given InformationGiven InformationSmall Office Building public numbers

2 Flush valve toilets2 Lavatories2 Drinking fountains1 Service sink

DL: 92’MCF: Flush Valve Toilet, 16’ above water mainStreet Main Pressure: 44.1 psi

Page 24: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

1. Determine 1. Determine Supply Supply Fixture Fixture Units Units

Fixture units take into account usage diversity

S: p. 974, T.21.15

Page 25: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

1. Determine Supply Fixture 1. Determine Supply Fixture UnitsUnits

Cold Hot Total2 Flush valve toilets 20.00 --- 20.02 Lavatories 3.00 3.00 4.02 Drinking fountains 0.50 --- 0.51 Service sink 2.25 2.25 3.0

25.75 5.25 27.5

Page 26: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

2. Calculate Demand Flow2. Calculate Demand Flow20 WSFU out of 27.5 WSFU are flush valves Use curve 1 for flush valve dominated system

40 gpmS: p. 975, F.21.65a

Page 27: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

3. Determine 3. Determine the Most the Most Critical Critical Fixture Fixture

Confirm pressure required (A)

15 psi

Height above main (B)

16’ 7.0 psiS. p. 970, T.21.14

Page 28: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

4. Determine Developed 4. Determine Developed LengthLength

Developed length

92’

S: p. 975, F.22.17

Note: this figure for generic reference only and does not illustrate the example problem

Page 29: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

5. Determine Total 5. Determine Total Effective Length (TEL)Effective Length (TEL)

TEL= DL x 1.5 = 92 x 1.5 = 138’

Page 30: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

6. Determine Street 6. Determine Street Main Pressure (E)Main Pressure (E)

44.1 psi

Page 31: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

7. Determine Pressure 7. Determine Pressure Available for Friction Loss Available for Friction Loss

Proper fixture flow pressureA15.0+ Pressure lost due to heightB7.0+ Pressure lost due to frictionC ?+ Pressure lost through meter D?

Total street main pressure E44.1

Page 32: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Meter Loss (D)Meter Loss (D)

Pick an initial size

2” diameter… 1.4 psi

S: p. 971, F.21.63a

Page 33: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

8. Determine Friction 8. Determine Friction loss/100’loss/100’

C=E-A-B-D = 44.1-15.0-7.0-1.4 = 20.7 psi

Δp/100’=100 x 20.7/138 = 15 psi/100’

Page 34: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

9. Verify flow 9. Verify flow for meter sizefor meter size

At 2” Flow=150 gpm > Total Demand 40 gpm

At 1-1/2”Flow=60 gpm > Total Demand 40 gpm

(Δp/100’= 13.1)

At 1”Flow=13 gpm < Total Demand 40 gpm

(Δp/100’= 5.1)S: p. 972 F.21.64a

Page 35: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

9. Verify flow 9. Verify flow for meter sizefor meter size

When flow > Total Demand (#2) stop

At 1-1/2”Flow=60 gpm > Total Demand 40 gpm

(Δp/100’= 13.1)

S: p. 972 F.21.64a

Page 36: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Pipe SizingPipe SizingUse Δp/100’= 13.1 psi/100’

Use fixture units to determine flow

S: p. 972 F.21.64a

Page 37: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Pipe SizingPipe Sizing

Use fixture units to determine flow

Pay attention to flush valve domination

S: p. 972 F.21.65a

Page 38: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Pipe SizingPipe SizingUse Δp/100’= 13.1 psi/100’

Use fixture units to determine flow

Select size which does not exceed 13.1 psi/100’

20 gpm, use 1” 10 gpm, use ¾”

Use runout sizes at each fixture

S: p. 972, F.21.64a

Page 39: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Runout Runout Pipe SizingPipe Sizing

Use actual flow to size runouts

Lavatory: 2 gpm

S: p.970, T.21.14

Page 40: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Runout Runout Pipe SizingPipe Sizing

Use Δp/100’= 13.1 psi/100’

Lavatory: 2 gpm

S: p. 972, F.21.64a

Page 41: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.

Notation SystemNotation System

Suggested for organizing data

WSFU CurveFlow Diam.

S: p. 995, F.22.17

3.6 2 4 ¾”

2.7 2 3 ½”

Page 42: Environmental Controls I/IG Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing Example Lecture 7 Upfeed Systems Pipe Sizing Procedure Pipe Sizing.