Engine Room Ventilation Design and Requirements Engine Room Ventilation Design Engine Room Ventilation Design and Requirements and Requirements University of Wisconsin-Madison Todd B. Jekel, Ph.D. Research Scientist Industrial Refrigeration Consortium University of Wisconsin-Madison  ASHRAE 2002 Winter Meeting  ASHRAE 2002 Winter Meeting  Atlantic City, NJ  Atlantic City, NJ
21

Engine Room Ventilation Design and Requirements

Apr 05, 2018

Download

Documents

texpectations
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 1/21

Engine Room Ventilation Designand RequirementsEngine Room Ventilation DesignEngine Room Ventilation Designand Requirementsand Requirements

University of Wisconsin-Madison

Todd B. Jekel, Ph.D.Research ScientistIndustrial Refrigeration ConsortiumUniversity of Wisconsin-Madison

ASHRAE 2002 Winter Meeting ASHRAE 2002 Winter Meeting Atlantic City, NJ Atlantic City, NJ

Page 2: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 2/21

DisclaimerTHIS INFORMATION WAS PRESENTED AT AN ASHRAE SEMINARHELD IN CINCINNATI, OH. THE SEMINAR FORMAT IS TO PRESENTINFORMATION OF CURRENT INTEREST AND TO PROVIDE A VENUEFOR INTERACTION BETWEEN ASHRAE MEMBERS. THESESEMINARS SHOULD NOT BE CONSIDERED PEER-REVIEWED (ORTHE FINAL WORD ON ANY SUBJECT). ASHRAE HAS NOTINVESTIGATED, AND ASHRAE EXPRESSLY DISCLAIMS ANY DUTYTO INVESTIGATE ANY PRODUCT, SERVICE, PROCESS, PROCEDURE,DESIGN, OR THE LIKE WHICH MAY BE DESCRIBED HEREIN. THEAPPEARANCE OF ANY TECHNICAL DATA OR EDITORIALMATERIAL IN THIS PRESENTATION DOES NOT CONSTITUTEENDORSEMENT, WARRANTY, OR GUARANTY BY ASHRAE OF ANYPRODUCT, SERVICE, PROCESS, PROCEDURE, DESIGN, OR THELIKE. NEITHER ASHRAE, THE AUTHORS OR THEIR EMPLOYERSWARRANT THAT THE INFORMATION IN THIS PRESENTATION ISFREE OF ERRORS. THE ENTIRE RISK OF THE USE OF ANYINFORMATION IN THIS PRESENTATION IS ASSUMED BY THE USER.BEFORE MAKING ANY DECISION OR TAKING ANY ACTION ON THIS

SUBJECT, YOU SHOULD CONSULT A QUALIFIED PROFESSIONALADVISOR.

Page 3: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 3/21

Introduction

Codes and StandardsDefinition of machinery (engine) room

Purpose of machinery room ventilationCode required ventilation amountsExampleOther considerations

Page 4: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 4/21

Codes and Standards

ASHRAE 15-1994 Safety Code for Mechanical Refrigeration

IIAR 2-1999

Equipment, Design, and Installation of Ammonia MechanicalRefrigerating Systems

International Mechanical Code (2000)Uniform Mechanical Code (1997)

Page 5: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 5/21

Machinery Room Definitions

ASHRAE 15 - 1994

Space that is designedto safely housecompressors andpressure vessels

Page 6: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 6/21

Machinery Room VentilationFunctions

Limit excessive temperature risedue to equipment-generated heat

Provides fresh air for machineryroom occupants

Purges refrigerant vapor fromthe machinery room inemergency situations

Page 7: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 7/21

Page 8: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 8/21

Ammonia as a Refrigerant

Toxic and flammableNIOSH IDLH 300 ppmLFL ~ 16% (by volume), UFL ~ 25% (by volume)

Odor perceptible at very low concentrations (5-15 ppm) Ventilation is essential to purge vapor in leak scenario

ammonia vapor is lighter than air

attempts to prevent the concentration from reaching LFL tominimize the probability of a deflagrationNFPA requires sufficient ventilation to maintain concentrations below25% of the LFL (or 4% for ammonia)

Page 9: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 9/21

Page 10: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 10/21

Emergency VentilationRequirements

Other codes/standards:IMC (2000), UMC (1997)

Same as ASHRAE 15

IIAR 2-1999 (ammonia) ASHRAE 15 amount, or 12 ACH, whichever is greater

Other checkslocal code requirement(s)insurance carrier requirements (if applicable)

Page 11: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 11/21

Non-emergency VentilationRequirements

Other codes/standards:IMC (2000), IIAR 2-1999

Same as ASHRAE 15

UMC (1997)Negative pressure of 0.05 in H 2O relative to adjacentspaces

Room temperature must be less than 104 oF

Page 12: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 12/21

Other guidance

IIAR Bulletin 111-1991 (ammonia)Recommends

EmergencyRecommends 10 cfm/ft 2 with a minimum of 20,000 cfm

Continuous1-2 cfm/ft 2

Considered industry best practice for ammonia

Page 13: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 13/21

Page 14: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 14/21

ASHRAE 15 Design Ventilation Rates

EmergencyNon-emergency

Intermittent1,095 hp of 93% efficient motors = 195,000 Btu/hrHigh-stage oil separators and discharge gas piping heat gainestimate = 10,000 Btu/hrMiscellaneous = 20,000 Btu/hr

Continuous †

0.5 cfm/ft 2 = 1,250 cfm

cfm200,14000,20100 ==emergencyCFM

( ) ( ) cfm800,111808.1

000,225

08.1 ==∆=−

ER

equipment emergencynon T

qCFM

† May require heat depending on location.

Page 15: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 15/21

Other Checks

EmergencyIIAR 2-1999: Check 12 ACH12,500 cfm

IIAR Bulletin 111-1991 : (10 cfm/ft 2)25,000 cfm

Non-emergency (continuous)IIAR Bulletin 111-1991 : 1-2 cfm/ft 2

2,500-5,000 cfm

Page 16: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 16/21

Ventilation Placement

Inlet location for exhaust fans shouldconsider where vapors will concentrateExhaust fan location should considerprevailing weather conditions andsurrounding buildings

Avoid recirculation between inlets and outlets

Page 17: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 17/21

Ventilation Control

Refrigerant detectorsSet to initiate emergency ventilation at:

50% of IDLH ( UMC )150 ppm ammonia

80% of cardiac sensitization level ( ASHRAE 15 †)42,000 ppm R-2260,000 ppm R-134a

† From Table 1 of allowable refrigerant quantities.

Page 18: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 18/21

Recap

ASHRAE 15 is widely referenced by codeauthorities and local jurisdictionsKeep in mind that code values for emergencyventilation are minimums

Always double check proposed design for

compliance with local code requirement(s)insurance underwriter

Page 19: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 19/21

Page 20: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 20/21

Ammonia Ventilation Rule-of-thumb

Ventilating ammonia to keep concentrationbelow 4% (25% of LFL) requires:24 volumes of fresh air for each volume of

ammonia vapor generated in the engine roomtotal exhaust volume is 25

generated vapor ammoniaexhaust CFM CFM = 25

Source: IIAR Bulletin 111, 1991

Page 21: Engine Room Ventilation Design and Requirements

7/31/2019 Engine Room Ventilation Design and Requirements

http://slidepdf.com/reader/full/engine-room-ventilation-design-and-requirements 21/21

Halocarbon Ventilation Rule-of-thumb

Ventilating halocarbon to keep concentrationbelow 7% (19.5% oxygen) requires:13 volumes of fresh air for each volume of

ammonia vapor generated in the engine roomtotal exhaust volume is 14

generated vapor halocarbonexhaust CFM CFM = 14