Top Banner
Bureau of Energy Efficiency Ministry of Power Ministry of Power Government of India Energy Conservation Building Code 2016
110

Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Jan 08, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Bureau of Energy Efficiency

Ministry of Power

Ministry of Power Government of India

Energy Conservation Building Code

2016

Page 2: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

This report is made possible by the support of the American People through the United States Agency for

International Development (USAID). The contents of this report are the sole responsibility of Nexant Inc., and do not necessarily reflect the views of USAID or the United States Government. This report was

prepared under Contract Number AID-386-C-12-00001.

Page 3: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Contents

List of Tables .................................................................................................................................... vii

List of Boxes ......................................................................................................................................ix

1. Purpose ...................................................................................................................................... 1

2. Scope ......................................................................................................................................... 2

2.1 Energy Efficiency Performance Levels ....................................................................................... 2

2.2 Regulated Building Systems ..................................................................................................... 2

2.3 Codes Take Precedence ........................................................................................................... 2

2.4 Reference Standards ............................................................................................................... 3

3. Compliance and Administration .................................................................................................... 4

3.1 Compliance Requirements ....................................................................................................... 4

3.1.1 Mandatory Requirements ................................................................................................. 4

3.1.2 New Buildings .................................................................................................................. 4

3.1.3 Additions to Existing Buildings .......................................................................................... 4

3.1.4 Alterations to Existing Buildings ........................................................................................ 4

3.2 Compliance Approaches........................................................................................................... 7

3.2.1 Energy Performance Index ............................................................................................... 7

3.2.2 Approved Analytical Tools ................................................................................................ 7

3.3 Administrative Requirements ................................................................................................... 7

3.3.1 Enforcement Jurisdiction .................................................................................................. 7

3.4 Compliance Documents ........................................................................................................... 9

3.4.1 Compliance Documents .................................................................................................... 9

3.4.2 Supplemental Information ................................................................................................ 9

4. Building Envelope ...................................................................................................................... 10

4.1 General ................................................................................................................................ 10

4.2 Mandatory Requirements ....................................................................................................... 10

4.2.1 Fenestration .................................................................................................................. 10

4.2.2 Opaque Construction ..................................................................................................... 10

4.2.3 Daylighting .................................................................................................................... 12

4.2.4 Building Envelope Sealing ............................................................................................... 12

4.3 Prescriptive Requirements ..................................................................................................... 15

4.3.1 Roofs ............................................................................................................................ 15

4.3.2 Opaque Walls ................................................................................................................ 15

4.3.3 Vertical Fenestration ...................................................................................................... 19

4.3.4 U-Value Exemption for Shaded Buildings ......................................................................... 21

Page 4: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

4.3.5 Skylights ....................................................................................................................... 21

4.3.6 Building Envelope Trade-Off Method ............................................................................... 22

5. Comfort Systems and Controls ................................................................................................... 23

5.1 General ................................................................................................................................ 23

5.2 Mandatory Requirements ....................................................................................................... 23

5.2.1 Ventilation ..................................................................................................................... 23

5.2.2 Minimum Space Conditioning Equipment Efficiencies ........................................................ 25

5.2.3 Minimum System Efficiency ............................................................................................ 27

5.2.4 Controls ........................................................................................................................ 27

5.2.5 Additional Controls for EE and Super EE Buildings ............................................................ 28

5.2.6 Additional Controls for Super EE Buildings ....................................................................... 29

5.2.7 Piping and Ductwork ...................................................................................................... 30

5.2.8 System Balancing .......................................................................................................... 31

5.2.9 Condensers ................................................................................................................... 32

5.2.10 Service Hot Water Heating ............................................................................................. 32

5.3 Prescriptive Requirements ..................................................................................................... 33

5.3.1 Fans ............................................................................................................................. 33

5.3.2 Pumps .......................................................................................................................... 34

5.3.3 Cooling Towers .............................................................................................................. 35

5.3.4 Economizers .................................................................................................................. 35

5.3.5 Variable Flow Hydronic Systems ..................................................................................... 36

5.3.6 Boilers .......................................................................................................................... 36

5.3.7 Low Energy Comfort Systems ......................................................................................... 36

5.3.8 Heat Recovery ............................................................................................................... 37

6. Lighting and Controls ................................................................................................................. 38

6.1 General ................................................................................................................................ 38

6.2 Mandatory Requirements ....................................................................................................... 38

6.2.1 Lighting Control ............................................................................................................. 38

6.2.2 Exit Signs ...................................................................................................................... 40

6.2.3 Exterior Building Grounds Lighting .................................................................................. 40

6.3 Prescriptive Requirements ..................................................................................................... 40

6.3.1 Interior Lighting Power .................................................................................................. 40

6.3.2 Building Area Method ..................................................................................................... 40

6.3.3 Space Function Method .................................................................................................. 43

6.3.4 Installed Interior Lighting Power ..................................................................................... 48

6.3.5 Exterior Lighting Power .................................................................................................. 48

Page 5: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

7. Electrical and Renewable Systems .............................................................................................. 50

7.1 General ................................................................................................................................ 50

7.2 Mandatory Requirements ....................................................................................................... 50

7.2.1 Transformers ................................................................................................................. 50

7.2.2 Energy Efficient Motors .................................................................................................. 51

7.2.3 DG Sets ........................................................................................................................ 52

7.2.4 Power Factor Correction ................................................................................................. 52

7.2.5 Check-Metering and Monitoring ...................................................................................... 52

7.2.6 Power Distribution Systems ............................................................................................ 53

7.2.7 Uninterruptible Power Supply (UPS) ................................................................................ 53

7.2.8 Renewable Energy Systems ............................................................................................ 53

8. Appendix A: Definitions, Abbreviations and Acronyms .................................................................. 55

8.1 General ................................................................................................................................ 55

8.2 Definitions ............................................................................................................................ 55

8.3 Abbreviations and Acronyms .................................................................................................. 67

8.4 SI to IP Conversion Factors ................................................................................................... 69

9. Appendix B: Whole Building Performance Method ........................................................................ 70

9.1 General ................................................................................................................................ 70

9.1.1 Scope ........................................................................................................................... 70

9.1.2 Compliance ................................................................................................................... 70

9.1.3 Annual Energy Use ........................................................................................................ 70

9.1.4 Trade-offs Limited to Building Permit .............................................................................. 70

9.1.5 Documentation Requirements ......................................................................................... 70

9.2 Simulation General Requirements ........................................................................................... 71

9.2.1 Energy Simulation Program ............................................................................................ 71

9.2.2 Climatic Data ................................................................................................................. 71

9.2.3 Compliance Calculations ................................................................................................. 71

9.3 Calculating the Energy Consumption of the Proposed Design and the Baseline Design............... 72

9.3.1 Energy Simulation Model ................................................................................................ 72

9.3.2 HVAC Systems ............................................................................................................... 72

10. Appendix C: Default Values for Typical Constructions .............................................................. 78

10.1 Procedure for Determining Fenestration Product U-Factor and Solar Heat Gain Coefficient ..... 78

10.2 Default U-Factors and Solar Heat Gain Coefficients for Unrated Fenestration Products ........... 79

10.2.1 Unrated Vertical Fenestration. ........................................................................................ 79

10.2.2 Unrated Sloped Glazing and Skylights ............................................................................. 79

10.3 Typical Roof Constructions ................................................................................................. 79

Page 6: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

10.4 Typical Wall Constructions ................................................................................................. 80

11. Appendix D: Building Envelope Tradeoff Method ..................................................................... 85

11.1 Envelope Performance Factor ............................................................................................. 85

11.2 Baseline Building Definition ................................................................................................ 87

12. Appendix E: Climate Zone Map of India .................................................................................. 88

13. Appendix F: Air-Side Economizer Acceptance Procedures Envelope Summary ........................... 90

13.1 Construction Inspection ..................................................................................................... 90

13.2 Equipment Testing ............................................................................................................ 90

14. Appendix G: Compliance Forms.............................................................................................. 91

14.1 Envelope Summary ............................................................................................................ 91

14.2 Building Permit Plans Checklist ........................................................................................... 92

14.3 Mechanical Summary ......................................................................................................... 93

14.4 Mechanical Checklist .......................................................................................................... 94

14.5 Lighting Summary ............................................................................................................. 95

14.6 Lighting Permit Checklist .................................................................................................... 96

15. Schedules ............................................................................................................................. 97

Page 7: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

List of Tables

Table 3.1 Bureau of Energy Efficiency Approved Software for Demonstrating Compliance with ECBC ...... 7

Table 4.1 Daylight Requirement ........................................................................................................ 12

Table 4.2 Daylight Extent Factors (DEF) for Calculating Daylight Area Manually ................................... 12

Table 4.3 Roof Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for ECBC

Buildings ......................................................................................................................................... 15

Table 4.4 Roof Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for EE

Buildings ......................................................................................................................................... 15

Table 4.5 Roof Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for Super

EE Buildings ..................................................................................................................................... 15

Table 4.6 Opaque Assembly U-factor (W/m2-ºC) and Insulation R-value (m2-ºC/W) Requirements for

ECBC Buildings ................................................................................................................................ 16

Table 4.7 Opaque Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for EE

Buildings ......................................................................................................................................... 16

Table 4.8 Opaque Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for

Super EE Buildings ........................................................................................................................... 16

Table 4.9 Vertical Fenestration U-value (W/m²- ºC), SHGC and VLT Requirements .............................. 19

Table 4.10 Shading Equivalent Factors for 28 ºN Latitude ................................................................... 20

Table 4.11 Shading E Equivalent Factors for 13 ºN Latitude ................................................................ 21

Table 4.12 U-Value (W/m2 -ºC) Requirements for Shaded Buildings .................................................... 21

Table 4.13 Skylight U-factor and SHGC Requirements (U-factor in W/m2-°C) ....................................... 21

Table 5.1 Minimum Energy Efficiency Requirements for Chillers in ECBC Buildings ............................... 25

Table 5.2 Minimum Energy Efficiency Requirements for Chillers in EE Buildings.................................... 25

Table 5.3 Minimum Energy Efficiency Requirements for Chillers in Super EE Buildings .......................... 26

Table 5.4 Minimum Efficiency Requirements for Unitary Air Conditioners in ECBC Buildings .................. 26

Table 5.5 Minimum Efficiency Requirements for Unitary Air Conditioners in EE Buildings ...................... 26

Table 5.6 Minimum Efficiency Requirements for Unitary Air Conditioners in Super EE Buildings ............. 26

Table 5.7 Minimum Efficiency Requirements for Variable Refrigerant Flow Air conditioners* ................. 27

Table 5.8 Minimum Efficiency Requirements for Precision Air Conditioners ........................................... 27

Table 5.9 Minimum System Efficiency* for ECBC Buildings .................................................................. 27

Table 5.10 Insulation Requirements for Pipes in ECBC Buildings.......................................................... 30

Table 5.11 Insulation Requirements for Pipes in EE Buildings .............................................................. 31

Table 5.12 Insulation Requirements for Pipes in Super EE Buildings .................................................... 31

Table 5.13 Ductwork Insulation (R value in m2 – ºC/W) Requirements ................................................ 31

Table 5.14 Mechanical and Motor Efficiency Requirements for Fans in ECBC Buildings .......................... 34

Table 5.15 Mechanical and Motor Efficiency Requirements for Fans in EE Buildings .............................. 34

Table 5.16 Mechanical and Motor Efficiency Requirements for Fans in Super EE Buildings .................... 34

Page 8: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Table 5.17 Pump Efficiency Requirements for ECBC Buildings ............................................................. 34

Table 5.18 Pump Efficiency Requirements for EE Buildings ................................................................. 35

Table 5.19 Pump Efficiency Requirements for Super EE Buildings ........................................................ 35

Table 5.20 Cooling Tower Efficiency Requirements for ECBC Buildings ................................................ 35

Table 5.21 Minimum Efficiency Requirements for Oil and Gas Fired Boilers .......................................... 36

Table 6.1 Interior Lighting Power for ECBC Buildings – Building Area Method ...................................... 42

Table 6.2 Interior Lighting Power for EE Buildings – Building Area Method ........................................... 42

Table 6.3 Interior Lighting Power for Super EE Buildings – Building Area Method ................................. 43

Table 6.4 Interior Lighting Power for ECBC Buildings – Space Function Method.................................... 44

Table 6.5 Interior Lighting Power for EE Buildings – Space Function Method ........................................ 45

Table 6.6 Interior Lighting Power for Super EE Buildings – Space Function Method .............................. 46

Table 6.7 Exterior Building Lighting Power for ECBC Buildings ............................................................. 48

Table 6.8 Exterior Building Lighting Power for EE Buildings ................................................................. 49

Table 6.9 Exterior Building Lighting Power for Super EE Buildings ....................................................... 49

Table 7.1Dry Type Transformers (to be updated as per the latest standard) ........................................ 50

Table 7.2 Permissible Losses for Oil Type Transformers. Total losses for oil type transformers should

confirm with Indian Standard IS 1180. (to be updated as per the latest standard) ............................... 51

Table 7.3 Sub Metering Requirements ............................................................................................... 53

Table 7.4 Energy Efficiency Requirements for UPS ............................................................................. 53

Table 7.5 Minimum Solar Zone Area Requirements for EE Buildings .................................................... 54

Table 7.6 Minimum Solar Zone Area Requirements for Super EE Buildings ........................................... 54

Table 9.1 Modeling Requirements for Calculating Proposed and Baseline Design .................................. 74

Table 9.2 HVAC Systems Map ........................................................................................................... 77

Table 10.1 Defaults for Unrated Vertical Fenestration (Overall Assembly including the Sash and Frame) 79

Table 10.2 Defaults for Effective U-factor for Exterior Insulation Layers ............................................... 80

Table 10.3 Defaults for Effective U-factor for Exterior Insulation Layers ............................................... 80

Table 10.4 Typical Thermal Properties of Common Building and Insulating Materials ............................ 81

Table 11.1 Envelope Performance Factor Coefficients – Composite Climate.......................................... 86

Table 11.2 Envelope Performance Factor Coefficients – Hot Dry Climate .............................................. 86

Table 11.3 Envelope Performance Factor Coefficients – Hot Humid Climate ......................................... 86

Table 11.4 Envelope Performance Factor Coefficients – Moderate Climate ........................................... 87

Table 11.5 Envelope Performance Factor Coefficients – Cold Climate .................................................. 87

Table 12.1Climate Zone for Major Indian Cities .................................................................................. 89

Table 15.1 Schedules for Baseline Design of School Buildings ............................................................. 97

Table 15.2 Schedules for Baseline Design of Assembly Buildings ......................................................... 98

Table 15.3 Schedules for Baseline Design of University Buildings (Non-Residential Only) ...................... 99

Table 15.4 Schedules for Baseline Design of Office Buildings ............................................................ 100

Page 9: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

List of Boxes

Box 3.1 Code Compliance Process ....................................................................................................... 8

Box 4.1 Building Typologies for ECBC 2016 ........................................................................................ 11

Box 4.2 Daylight Extent Factor and Useful Daylight Illuminance .......................................................... 13

Box 4.3 Wall Assemblies for Buildings ................................................................................................ 17

Box 5.1 Set points for Comfort Conditions ......................................................................................... 24

Box 6.1 Calculating Interior Lighting Power – Space Function Method ................................................. 47

Page 10: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design
Page 11: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Purpose

Energy Conservation Building Code 2016 1

1. Purpose

The purpose of this code is to provide minimum requirements for the energy-efficient design and

construction of buildings.

Page 12: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Scope

2. Scope

The code is applicable to commercial buildings or building complexes that have a connected load of 100

kW or greater or a contract demand of 120 kVA or greater. The code is recommended for all other

buildings.

This code would become mandatory as and when it is notified by the central and state government in the

official Gazette under clause (p) of Section 14 or clause (a) of Section 15 of the Energy Conservation Act

2001 (52 of 2001).

2.1 Energy Efficiency Performance Levels

Buildings will be able to demonstrate compliance with the code through the following three incremental

levels of energy efficiency listed below.

(a) ECBC buildings (compulsory level that fulfils the minimum energy efficiency requirements of the

code)

(b) Energy Efficient (EE) buildings (voluntary level wherein building (s) fulfils or exceeds the EE

performance levels stipulated in the code)

(c) Super Energy Efficient (Super EE) buildings (voluntary level wherein building (s) fulfils or exceeds

the Super EE performance levels stipulated in the code)

Buildings that do not meet the ECBC level shall be deemed as non-compliant with Energy Conservation

Building Code.

2.2 Regulated Building Systems

The provisions of this code apply to:

(a) Building envelopes, except for unconditioned storage spaces or warehouses,

(b) Mechanical systems and equipment, including heating, ventilating, and air conditioning, service

hot water heating,

(c) Interior and exterior lighting,

(d) Electrical power and motors, and renewable energy systems.

Exemptions to § 2.2: The provisions of this Code do not apply to:

(a) Equipment and portions of building systems that use energy primarily for manufacturing

processes

(b) Plug loads

(c) Vertical transportation

(d) Process loads

(e) Diesel generators

2.3 Codes Take Precedence

The following codes, programs, and policies will take precedence over ECBC 2016 in case of conflict:

(a) Safety, health, or environmental codes,

(b) Bureau of Energy Efficiency’s Star Rating Program for buildings and,

(c) Other policies programs like refrigerant phase out programs, future renewable energy programs,

BEEs norms and standards.

Page 13: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Scope

Energy Conservation Building Code 2016 3

2.4 Reference Standards

National Building Code 2005 is the reference document/ standard for lighting levels, HVAC, comfort

levels, natural ventilation, pump and motor efficiencies, transformer efficiencies and any other building

materials and system performance criteria.

Page 14: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Compliance and Administration

3. Compliance and Administration

3.1 Compliance Requirements

3.1.1 Mandatory Requirements

Compliance with the requirements of this energy code shall be mandatory for all applicable buildings

discussed in § 2.

3.1.2 New Buildings

3.1.2.1 Self-occupied

New buildings shall comply with either the provisions of §4 through §7 of this code or the Whole Building

Performance Method of Appendix B.

3.1.2.2 Core and Shell

New core and shell buildings shall demonstrate compliance with ECBC requirements for the following

base building systems:

(a) Building envelope

(b) Renewable energy systems

(c) Electrical systems (installed by developer/ owner)

(d) Comfort systems and controls (only those installed by developer/ owner)

(e) Lighting systems and controls (only those installed by developer/ owner)

Additionally, fit out manuals and lease agreements for the tenant shall have a legal undertaking that

interior fit outs made by tenants be ECBC compliant.

3.1.2.3 Mixed Use

Compliance requirements for individual systems in each building type in a new mixed use development

will be determined by the ECBC requirements for that building type.

Exceptions to § 3.1.2.3: Buildings in a mixed use development which are otherwise not under the scope

of ECBC will be exempt from demonstrating compliance.

3.1.3 Additions to Existing Buildings

Where the connected load demand of the addition plus the existing building exceeds 100 kW or 120 kVA,

the additions shall comply with the provisions of § 4 through § 7. Compliance may be demonstrated in

either of the following ways:

(a) The addition alone shall comply with the applicable requirements, or

(b) The addition, together with the entire existing building, shall comply with the requirements of

this code that would apply to the entire building, as a new building.

Exceptions to § 3.1.3: When space conditioning is provided by existing systems and equipment, the

existing systems and equipment need not comply with this code. However, any new equipment installed

must comply with specific requirements applicable to that equipment.

3.1.4 Alterations to Existing Buildings

Where the connected load demand of the existing building exceeds 100 kW or 120 kVA, portions of a

building and its systems that are being altered shall meet the provisions of §4 through §8. Specific

requirements for alterations are described in the following subsections.

Page 15: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Compliance and Administration

Energy Conservation Building Code 2016 5

Exception to § 3.1.4: When the entire building complies with all of the provisions of §4 through §7 as if it

were a new building.

3.1.4.1 Building Envelope

Alterations to the building envelope shall comply with the requirements of § 4 for fenestration, insulation,

and air leakage applicable to the portions of the buildings and its systems being altered.

Exception to § 3.1.4.1: The following alterations need not comply with these requirements provided such

alterations do not increase the energy usage of the building:

(a) Replacement of glass in an existing sash and frame, provided the U-factor and SHGC of the

replacement glazing are equal to or lower than the existing glazing,

(b) Modifications to roof/ceiling, wall, or floor cavities, which are insulated to full depth with

insulation, and

(c) Modifications to walls and floors without cavities and where no new cavities are created.

3.1.4.2 Heating, Ventilation and Air Conditioning

Alterations to building heating, ventilating, and air-conditioning equipment or systems shall comply with

the requirements of §5 applicable to the portions of the building and its systems being altered. Any new

equipment or control devices installed in conjunction with the alteration shall comply with the specific

requirements applicable to that equipment or control device.

3.1.4.3 Service Water Heating

Alterations to building service water heating equipment or systems shall comply with the requirements of

§ 0 applicable to the portions of the building and its systems being altered. Any new equipment or

control devices installed in conjunction with the alteration shall comply with the specific requirements

applicable to that equipment or control device.

3.1.4.4 Lighting

Alterations to building lighting equipment or systems shall comply with the requirements of § 6 applicable to

the portions of the building and its systems being altered. New lighting systems, including controls, installed

in an existing building and any change of building area type as listed in Table 6.1, Table 6.2 and

Page 16: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Compliance and Administration

Table 6.3 shall be considered an alteration. Any new equipment or control devices installed in

conjunction with the alteration shall comply with the specific requirements applicable to that equipment

or control device.

Exception to § 6: Alterations that replace less than 50% of the luminaires in a space need not comply

with these requirements provided such alterations do not increase the connected lighting load.

3.1.4.5 Electrical and Renewable Systems

Alterations to building electric power systems and motor shall comply with the requirements of § 7

applicable to the portions of the building and its systems being altered. Any new equipment or control

devices installed in conjunction with the alteration shall comply with the specific requirements applicable

to that equipment or control device.

Page 17: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Compliance and Administration

Energy Conservation Building Code 2016 7

3.2 Compliance Approaches

The building shall comply with the mandatory provisions (§ 4.2, § 5.2 , § 6.2, and § 7.2) and either of

the following:

(a) Prescriptive Method (§ 4.3, § 5.3, and § 6.3)

(b) Whole Building Performance Method (Appendix B)

3.2.1 Energy Performance Index

Buildings, whether following the prescriptive or the whole building method approach, shall have to report

their predicted energy performance index (EPI) to demonstrate compliance. EPI shall be calculated

through approved tools.

3.2.1.1 Core and Shell Buildings

EPI shall be calculated only for base building areas in core and shell buildings

3.2.1.2 Mixed Use Development

EPI shall be calculated separately for different building uses in a mixed use development. EPIs so

calculated shall demonstrate compliance with ECBC requirements for similar building types only. If whole

building performance approach is followed, area weighted averages shall comply with ECBC EPI

requirements.

3.2.2 Approved Analytical Tools

A building following the whole building performance approach shall be deemed compliant only

compliance is proven through the software listed in Table 3.1. Daylight requirements of § 4.2.3, if

calculated through software tools shall use software listed in Table 3.1.

Table 3.1 Bureau of Energy Efficiency Approved Software for Demonstrating Compliance with ECBC

Analysis Software

Whole Building Performance Analysis ECONirman Prescriptive, Equest, EnergyPlus

Daylighting Autodesk Ecotect Analysis, Daysim

3.3 Administrative Requirements

3.3.1 Enforcement Jurisdiction

Authorities having jurisdiction to enforce the Code shall be any of the following:

(a) Development authorities (DA)

(b) Sate designated agencies (SDA)

(c) Municipal corporations

(d) Urban local bodies

Administrative requirements relating to permit requirements, enforcement, interpretations, claims of

exemption, approved calculation methods, and rights of appeal are specified by the authority having

jurisdiction.

Page 18: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Compliance and Administration

Box 3.1 Code Compliance Process

Box 3.1 Code Compliance Process

Typical compliance approach followed for mature codes is a multistep process that begins with the

design phase and ends with an occupancy certificate to the code compliant building. Code

enforcement agencies integrate necessary approvals during building design and construction

phases in the process to ensure stringent code compliance.

In a project team, the responsibility of designing buildings as per the code and then constructing

accordingly rests on the architect, engineer, contractor and of course, the owner. Project teams

committed to constructing energy efficient buildings and, also knowledgeable about code

compliance procedural and technical requirements are imperative.

Architects and engineers with experience in designing and constructing code compliant buildings

prepare the documents required by code enforcement agency, attest them as accurate and, submit

them for checks. Design phase compliance documents include drawings with specifications of

materials and technologies, compliance forms/ checklists, preliminary building performance

analysis reports and worksheets to verify any manual calculations. The owner also adds his

undertaking to that of the design team.

Once the design has been approved by enforcement agencies based on the submitted

documentation, implementation of promised code compliance measures is checked through

scheduled field inspections at the construction site. At this stage, the project contractor has to

take the responsibility of demonstrating compliance along with the owner and design team.

A building owner can apply for completion/ occupancy certificate only after the completed and

operational building is approved by enforcement body as code compliant.

Certified ECBC compliance assessor to prepare the ECBC

compliance form

Compliance forms to be submitted to

authority along with the submissions

drawings

Owner of the building also needs to submit

a duly signed undertaking

Mandatory construction inspection by authorized

authority

After construction, owner of the building to re submit the

undertaking & compliance forms of as built ECBC

complied building

Final occupancy certificate

Page 19: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Compliance and Administration

Energy Conservation Building Code 2016 9

3.4 Compliance Documents

3.4.1 Compliance Documents

Plans and specifications shall show all pertinent data and features of the building, equipment, and

systems in sufficient detail to permit the authority having jurisdiction to verify that the building complies

with the requirements of this code. Details shall include, but are not limited to:

(a) Building Envelope: insulation materials and their R-values; fenestration U-factors, solar heat gain

coefficients (SHGC), visible light transmittance (if the trade-off procedure is used), and air

leakage; overhangs and sidefins, building envelope sealing details;

(b) Heating, Ventilation, and Air Conditioning: system and equipment types, sizes, efficiencies, and

controls; economizers; variable speed drives; piping insulation; duct sealing, insulation and

location; requirement for balance report;

(c) Service Hot Water and Pumping: solar water heating system

(d) Lighting: lighting schedule showing type, number, and wattage of lamps and ballasts; automatic

lighting shutoff, occupancy sensors, and other lighting controls; lamp efficacy for exterior lamps;

(e) Electrical Power: electric schedule showing transformer losses, motor efficiencies, and power

factor correction devices; electric check metering and monitoring system.

(f) Renewable energy systems: system generation capacity, technical specifications, solar zone area

3.4.2 Supplemental Information

The authority having jurisdiction may require supplemental information necessary to verify compliance

with this code, such as calculations, worksheets, compliance forms, manufacturer’s literature, or other

data.

Page 20: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

4. Building Envelope

4.1 General

The building envelope shall comply with the mandatory provisions of § 4.2 and the prescriptive criteria of

§ 4.3.

4.2 Mandatory Requirements

4.2.1 Fenestration

4.2.1.1 U-Factors

U-factors shall be determined for the overall fenestration product (including the sash and frame) in

accordance with ISO-15099, as specified in Appendix C, by an accredited independent laboratory, and

labeled and certified by the manufacturer or other responsible party. U-factors for sloped glazing and

skylights shall be determined at a slope of 20 degrees above the horizontal. For unrated products, use

the default table in Appendix C.

4.2.1.2 Solar Heat Gain Coefficient

SHGC shall be determined for the overall fenestration product (including the sash and frame) in

accordance with ISO-15099, as specified in Appendix C, by an accredited independent laboratory, and

labeled and certified by the manufacturer or other responsible party.

Exceptions to § 4.2.1.2:

(a) Shading coefficient (SC) of the center glass alone multiplied by 0.86 is an acceptable alternate

for compliance with the SHGC requirements for the overall fenestration area.

(b) Solar heat gain coefficient (SHGC) of the glass alone is an acceptable alternate for compliance

with the SHGC requirements for the overall fenestration product.

4.2.2 Opaque Construction

U-factors shall be determined from the default tables in Appendix C or determined from data or

procedures contained in the ASHRAE Fundamentals, 2005.

Page 21: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Energy Conservation Building Code 2016 11

Box 4.1 Building Typologies for ECBC 2016

Box 4.1 Building Typologies for ECBC 2016

Energy efficiency requirements for ECBC 2016 are derived after analysing 16 different non-

residential building typologies (shown below) which in turn are based on building classifications

in National Building Code of India. Spatial layouts, material specifications, façade

characteristics and occupancy patterns have an impact on energy efficiency of a building and

differ for these typologies. Potential for reducing energy use with technology and materials thus

varies from building type to type. By analysing this potential, ECBC energy efficiency

requirements are now sensitive to building typologies and to the extent possible, unrealistic

requirements have been avoided.

Maximum impact of the climatic conditions of a location is felt on the building envelope. It is

after all the layer that is meant to provide protection against extreme conditions of the external

environment. ECBC analytical studies were conducted across the five climatic zones followed for

building design in India:

Hot and Dry

Composite

Warm and Humid

Temperate

Cold

Refer Appendix D for climate map of India and climate zones in which major Indian cities and

towns are located.

Figure 1 Building Typologies Analyzed for ECBC 2016

Hospitality

Large hotel

(Star hotels)

Small hotel

(No Star)

Resort

Educational

College/ university

Primary School

Secondary school

Health care

Hospital

Out patient heath care

Commercial Shopping Complex

Shopping malls

Stand alone retails

Open gallery mall

Super market

Business

Large office (> 30,000

m2)

Medium office

(10,000 -30,000 m2)

Small office ( <10,000

m2)

Assembly

Multiplex

Theatre

Page 22: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

4.2.3 Daylighting

Buildings shall have daylight areas designed to meet or exceed the useful daylight illuminance (UDI) and

area requirements listed in Table 4.1. Compliance shall be demonstrated either through whole building

performance method or the manual method. Only BEE approved software shall be used to demonstrate

compliance through the whole building performance method.

Table 4.1 Daylight Requirement

Daylight extent factors (DEF) described in Table 4.2 shall be used for calculating compliance with

daylighting requirements manually. Day light extent shall be marked on the architectural plan to estimate

the final percentage area.

Table 4.2 Daylight Extent Factors (DEF) for Calculating Daylight Area Manually

Latitude Window type

Shading VLT < 0.3 VLT ≥ 0.3

North South/ East West North South/ East West

> 15 degrees

All window types

No shading 1.4 1.0 0.5 1.5 1.1 0.7

< 15 degrees

1.5 1.3 0.6 1.6 1.5 .8

Non West West Non West West

All latitude types

Vision window

All shading types with PF>0.4

1.5 1.1 1.8 1.5

Clerestory 1.8 1.6 2.1 1.8

DEF shall be multiplied with the head height of the vertical fenestration to compute the daylight penetration potential

4.2.4 Building Envelope Sealing

The following areas of the enclosed building envelope shall be sealed, caulked, gasketed, or weather-

stripped to minimize air leakage:

(a) Joints around fenestration and door frames,

(b) Openings between walls and foundations and between walls and roof and wall panels,

(c) Openings at penetrations of utility services through, roofs, walls, and floors

(d) Site-built fenestration and doors,

(e) Building assemblies used as ducts or plenums, and

(f) All other openings in the building envelope

Building Category % above grade area meeting the UDI requirement for

90% of the time in an year

ECBC EE Super EE

All buildings

except resorts

and shopping

malls

< 3 story building (above grade) 40% 55% 70%

>= 3 story building (above grade) 45% 60% 75%

Resort All type 45% 60% 75%

Shopping malls/

complex

All type 10% 15% 20%

Page 23: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Energy Conservation Building Code 2016 13

Box 4.2 Daylight Extent Factor and Useful Daylight Illuminance

Box 4.2 Daylight Extent Factor and Useful Daylight Illuminance

UDI is defined as the annual occurrence of daylight between 100 lux to 2,000 lux on a work plane. This daylight is most useful to occupants, glare free and when available, eliminates the need for artificial lighting.

Application of UDI and Daylight Extent Factor

A 7,200 m2 four story office building in Delhi is trying to achieve ECBC level compliance. Building is

oriented along east west axis. It has a rectangular layout (60 m x 30 m), Total built up area is

distributed evenly across all floors above grade. VLT of glazing in all orientations is less than 0.3.

Windows have no shading and head height is 2.4 m.

Table 4.1 lists the minimum daylight area requirements for ECBC buildings. Row 2 of the table

specifies that all ECBC buildings other than resorts and shopping malls and, more than 3 stories

above the ground shall have a minimum of 45% of its floor area exposed to daylight in range of 100 –

2,000 lux for at least 90% of the year.

This office building must then have at least 3, 240 m2 (45% of 7,200 m2) of floor area fulfilling the

UDI requirements. Across each floor plate, this should be then 3,240/ 4 = 810 m2.

Compliance with § 4.2.3 Daylight Requirements can be checked for through two approaches. Each is

concurrent with the overall approach chosen for demonstrating code compliance (§ 3.2)

a) Analysis through software

If the whole building performance approach is used, compliance for daylighting requirements

can be checked by analyzing the façade and floor plate design in an analytical software approved

by BEE (§ 3.2.2). These are Ecotect and DaySim. Image below illustrates the output from

Ecotect. It specifies the lux levels and time period of an year during which these would be

available. With this information, designers can check if the required minimum area as per §

4.2.3 has the required daylight levels.

b) Manual method of demonstrating compliance

This approach will be suitable for projects adopting the prescriptive compliance approach. From

Table 4.2, determine the daylight extent factor (DEF) for the building. For a building with

glazing of VLT < 0.3 and no shading, located in Delhi (latitude > 15 degrees), DEFs for windows

in north = 1.4, in south/ east = 1.0, west = 0.5. Head height is 2.4 m. Area that would comply

with UDI requirements is in table below.

Calculations show that only 1,632 m2 of area will meet the UDI requirements. This is just 22.6% of

7,200 m2 against the required proportion of 45%. Thus, the building does not comply with mandatory

requirement. Adding shading, increasing the VLT of glazing, and reducing floor plate width can be

considered to ensure compliance.

Page 24: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Orientation DEF Window/

Fenestration

Width

X

(daylight area

extension into floor

plate perpendicular

to fenestration)

Y

(daylight area extension

into floor plate parallel to

fenestration)

Above grade area

meeting the UDI

requirement for

90% of the time

in an year

( X x Y)

North 1.4 45 m 1.4 x 2.4 = 3.36 50 m (50 x 3.36) m2

South 1.0 45 m 1.0 x 2.4= 2.4 m 50 m (50 x 2.4) m2

East 1.0 25 m 1.0 x 2.4 = 2.4 m 28 m (28 x 2.4) m2

West 0.5 0 m (service

zone)

0 0

Total daylight area per floor meeting UDI requirement during 90% of the year 408 m2

Total daylight area in building meeting UDI requirement during 90% of the year 408 x 2 = 1632m2

Daylight area should be indicated in floor plans submitted to code enforcement authorities as shown

in image below.

Page 25: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Energy Conservation Building Code 2016 15

4.3 Prescriptive Requirements

4.3.1 Roofs

Roofs shall comply with either the maximum assembly U-factors or the minimum insulation R-values in

Table 4.3 through Table 4.5. R-value is for the insulation alone and does not include building materials or

air films. The roof insulation shall not be located on a suspended ceiling with removable ceiling panels.

Table 4.3 Roof Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for ECBC

Buildings

Composite Hot and dry Warm & humid Temperate Cold

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

Daytime Buildings

All Buildings 0.30 0.30 0.30 0.30 0.28

School buildings <

10,000 m2

0.54 0.54 0.54 0.54 0.3

24 Hours Buildings

All Buildings 0.30 0.30 0.30 0.30 0.28

Hospitality Buildings 0.19 0.19 0.19 0.30 0.19

Table 4.4 Roof Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for EE

Buildings

Composite Hot and dry Warm & humid Temperate Cold

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

Daytime EE

Buildings

0.25 0.25 0.25 0.25 0.20

24 Hours EE

Buildings

0.20 0.20 0.20 0.20 0.20

U Values are maximum values allowed and R values are minimum values allowed

Table 4.5 Roof Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for Super EE

Buildings

Composite Hot and dry Warm & humid Temperate Cold

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

Daytime Super EE

Buildings

0.18 0.18 0.18 0.18 0.18

24 Hours Super EE

Buildings

0.18 0.18 0.18 0.18 0.18

U Values are maximum values allowed and R values are minimum values allowed

4.3.1.1 Cool Roofs

Roofs with slopes less than 20 degrees shall have an initial solar reflectance of no less than 0.70 and an

initial emittance no less than 0.75. Solar reflectance shall be determined in accordance with ASTM E903-

96 and emittance shall be determined in accordance with ASTM E408-71 (RA 1996).

4.3.2 Opaque Walls

Opaque walls shall comply with either the maximum assembly U-factors or the minimum insulation R-

values in Table 4.6Error! Reference source not found. through Table 4.8. R-value is for the insulation

alone and does not include building materials or air films.

Page 26: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Table 4.6 Opaque Assembly U-factor (W/m2-ºC) and Insulation R-value (m2-ºC/W) Requirements for ECBC

Buildings

Composite Hot and dry Warm & humid Temperate Cold

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

Daytime Buildings

All Buildings 0.4 2.15 0.4 2.15 0.4 2.15 0.55 0.34

Office and School <

10,000 m2

0.63 0.63 0.63 0.63 0.4

24 Hour Buildings

All Buildings 0.4 0.4 0.4 0.4 0.34

U Values are maximum values allowed and R values are minimum values allowed

Table 4.7 Opaque Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for EE

Buildings

Composite Hot and dry Warm & Humid Temperate Cold

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

Daytime EE Buildings 0.34 0.34 0.34 0.4 0.22

24 Hours EE Buildings 0.34 0.34 0.34 0.34 0.22

U Values are maximum values allowed and R values are minimum values allowed

Table 4.8 Opaque Assembly U-factor (W/m2 - ºC) and Insulation R-value (m2-ºC/W) Requirements for Super

EE Buildings

Composite Hot and dry Warm & Humid Temperate Cold

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

U

Value

R

value

Daytime Super EE

Buildings

0.34 0.34 0.34 0.34 0.22

24 Hours Super EE

Buildings

0.22 0.22 0.22 0.22 0.22

U Values are maximum values allowed and R values are minimum values allowed

Page 27: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Energy Conservation Building Code 2016 17

Box 4.3 Wall Assemblies for Buildings

Box 4.3 Wall Assemblies for Buildings

ECBC specifies the maximum U values for wall assemblies. Assemblies that meet or exceed these U

Value requirements are mentioned below for reference. All the wall assemblies mentioned in the box

are used across energy efficient buildings India.

Wall Assembly Combinations for U Value of 0.4 W/m2 -ºC

Assembly Composition Insulation Assembly Thickness (mm)

Fly Ash Brick Wall (200 mm) with

external insulation

Expanded polystyrene (thermocol)

(EPS) 75 mm

275

Fly Ash Brick Wall (200 mm) with

internal insulation

Expanded polystyrene (thermocol)

(EPS) 75 mm

275

Fly Ash Brick Wall (200 mm, 100

mm) with external heavy mass

Extruded polystyrene (XPS) 50 mm 350

Fly Ash Brick Wall (200 mm, 100 mm)

with internal heavy mass

Extruded polystyrene (XPS) 50 mm 350

Hollow Concrete Block Wall (200 mm)

with external insulation

Glass fiber and mineral fiber 50 mm 250

Hollow Concrete Block Wall (200 mm)

with internal insulation

Glass fiber and mineral fiber 50 mm 250

Gypsum Board Bonded Mineral wool (Rock/ glass

wool) 75 mm

100

Wall Assembly Combinations for U Value of 0.55 W/m2 -ºC

Assembly Composition Insulation Assembly Thickness (mm)

Fly Ash Brick Wall (200 mm) with

external insulation

Expanded polystyrene (thermocol)

(EPS) 50 mm

250

Fly Ash Brick Wall (200 mm) with

internal insulation

Expanded polystyrene (thermocol)

(EPS) 50 mm

250

Wall Assembly Combinations for U Value of 0.63 W/m2 -ºC

Assembly Composition Insulation Assembly Thickness (mm)

Fly Ash Brick Wall (200 mm) with

external insulation

Polyurethane 25 mm 225

Fly Ash Brick Wall (200 mm) with

internal insulation

Polyurethane 25 mm 225

Fly Ash Brick Wall (200 mm, 100 mm)

with external heavy mass

Extruded polystyrene (XPS) 25 mm 325

Fly Ash Brick Wall (200 mm, 100 mm)

with internal heavy mass

Extruded polystyrene (XPS) 25 mm 325

Autoclaved Aerated Concrete Block

Wall

NA 200

Gypsum Board Expanded polystyrene (thermocol)

(EPS) 50 mm

75

Page 28: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Wall Assembly Combinations for U Value of 0.34 W/m2 -ºC

Assembly Composition Insulation Assembly Thickness (mm)

Brick wall (230 mm, 115mm) with

external heavy mass

Glass fiber and mineral fiber 75 mm 420

Brick wall (230 mm, 115mm) with

internal heavy mass

Glass fiber and mineral fiber 75 mm 420

Brick wall (230 mm, 230 mm) Polyurethane 50 mm 510

Cement Stabilized Brick (250 mm,

125 mm) & external heavy mass

Bonded Mineral wool (Rock/ glass wool)

75 mm

450

Cement Stabilized Brick (250 mm,

125 mm) & internal heavy mass

Bonded Mineral wool (Rock/ glass wool)

75 mm

450

Fly Ash Brick Wall (200 mm, 100

mm) with external heavy mass

Bonded Mineral wool (Rock/ glass wool)

75 mm

375

Fly Ash Brick Wall (200 mm, 100

mm) with external heavy mass

Glass fiber and mineral fiber 75 mm 375

Fly Ash Brick Wall (200 mm, 100

mm) with internal heavy mass

Bonded Mineral wool (Rock/ glass wool)

75 mm

375

Fly Ash Brick Wall (200 mm, 100

mm) with internal heavy mass

Glass fiber and mineral fiber 75 mm 375

Hollow Concrete Block Wall (200

mm) with external insulation

Expanded polystyrene (thermocol)

(EPS) 75 mm

275

Hollow Concrete Block Wall (200

mm) with internal insulation

Expanded polystyrene (thermocol)

(EPS) 75 mm

275

ACC Block Wall (200 mm, 100

mm) with external heavy mass

Expanded polystyrene (thermocol)

(EPS) 25 mm

325

ACC Block Wall (200 mm, 100 mm)

with internal heavy mass

Expanded polystyrene (thermocol)

(EPS) 25 mm

325

Gypsum Board Extruded polystyrene (XPS) 75 mm 100

Gypsum Board Expanded polystyrene (thermocol)

(EPS) 100 mm

125

Wall Assembly Combinations for U Value of 0.22 W/m2 -ºC

Assembly Composition Insulation Assembly Thickness (mm)

Fly Ash Brick Wall (200 mm, 200 mm) Extruded polystyrene (XPS) 100 mm 500

Hollow Concrete Block Wall (200 mm)

with external insulation

Extruded polystyrene (XPS) 100 mm 300

Hollow Concrete Block Wall (200 mm)

with internal insulation

Extruded polystyrene (XPS) 100 mm 300

ACC Block Wall (200 mm, 100 mm) with

external heavy mass

Bonded Mineral wool (Rock/ glass

wool) 75 mm

375

ACC Block Wall (200 mm, 100 mm) with

external heavy mass

Glass fiber and mineral fiber 75 mm 375

ACC Block Wall (200 mm, 100 mm) with

internal heavy mass

Bonded Mineral wool (Rock/ glass

wool) 75 mm

375

ACC Block Wall (200 mm, 100 mm) with

internal heavy mass

Glass fiber and mineral fiber 75 mm 375

ACC Block Wall (200 mm, 200 mm) Bonded Mineral wool (Rock/ glass

wool) 50 mm

450

ACC Block Wall (200 mm, 200 mm) Glass fiber and mineral fiber 50 mm 450

Gypsum Board Polyurethane 100 mm 125

Page 29: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Energy Conservation Building Code 2016 19

4.3.3 Vertical Fenestration

Vertical fenestration shall comply with the maximum area weighted U-factor and maximum area

weighted SHGC requirements of Table 4.9. Vertical fenestration area is limited to a maximum of 40% of

the gross wall area for the prescriptive requirement.

Vertical fenestration product shall have the minimum Visual Light Transmittance (VLT), defined as

function of Window Wall Ratio (WWR), where Effective Aperture > 0.1, equal to or greater than the

minimum VLT requirements of Table 4.9.

EE and Super EE buildings shall achieve a minimum selectivity ratio of 1.5 and 1.75 respectively in

addition to meeting or exceeding all the requirements listed in Table 4.9.

Table 4.9 Vertical Fenestration U-value (W/m²- ºC), SHGC and VLT Requirements

Exception to § 4.3.3:

(a) Overhangs and/or side fins may be applied in determining the SHGC for the proposed design. An

adjusted SHGC, accounting for overhangs and/or side fins, is calculated by multiplying the SHGC of

the unshaded fenestration product with a multiplication (M) factor. M factors shall be determined for

each orientation and shading device type as per Equation 4.1.

Equation 4.1: 𝑀 = (𝐶3 × 𝑃𝐹3) + (𝐶2 × 𝑃𝐹2) + (𝐶1 × 𝑃𝐹) + 𝐶0

Where

PF is the projection factor for overhangs and side-fins, to be calculated as per Appendix A.

C3, C2, C1 and C0 are shading equivalent factors (SEFs), listed in Table 4.10 and

Composite Hot and dry Warm & humid Temperate Cold

WWR 40% 40% 40% 40% 40%

Maximum U-factor

3.3 3.3 3.3 3.3 2.8

Maximum SHGC Non-North

.27 .27 .27 .27 .62

Maximum SHGC North

.5 .5 .5 .5 .62

Minimum VLT .27 .27 .27 .27 .27

SHGCnorth is applicable for latitude ≥ 15°; for latitude < 15°, SHGCnorth to be same as SHGCnon north

See Appendix C for default values of unrated fenestration.

Page 30: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Table 4.11.

Table 4.10 Shading Equivalent Factors for 28 ºN Latitude

Overhang + Fin Overhang Fin

Coefficients C3 C2 C1 C0 C3 C2 C1 C0 C3 C2 C1 C0

North -0.03 -0.23 1.09 0.99 -0.02 -0.10 0.43 0.99 0.14 -0.39 0.62 0.99

East 4.49 -6.35 4.70 0.52 -0.05 0.42 0.66 1.02 0.12 -0.35 0.57 0.99

South -4.09 8.14 -0.73 1.32 -1.01 1.91 0.24 1.12 0.53 -1.35 1.48 0.88

West -1.21 3.92 -0.56 1.28 1.52 -2.51 2.30 0.76 0.02 -0.15 0.46 1.01

North-East -0.95 1.50 0.84 1.18 2.19 -3.78 2.62 0.72 -1.64 3.07 -1.05 1.30

South-East 2.67 -4.99 5.68 0.32 -0.93 1.37 0.76 0.99 0.68 -1.47 1.35 0.88

South-West -0.50 1.36 2.45 0.73 -3.23 5.61 -1.56 1.32 1.86 -3.81 2.71 0.69

North-West -6.85 11.7 -3.92 1.89 -0.22 0.19 0.74 1.01 -2.02 2.63 -0.18 1.14

Page 31: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

Energy Conservation Building Code 2016 21

Table 4.11 Shading E Equivalent Factors for 13 ºN Latitude

Overhang + Fin Overhang Fin

Coefficients C3 C2 C1 C0 C3 C2 C1 C0 C3 C2 C1 C0

North -0.09 -0.29 1.41 1.05 -0.05 -0.10 0.54 1.02 0.10 -0.40 0.77 1.01

East -0.55 0.89 1.28 0.97 -0.62 0.88 0.51 1.02 0.15 -0.41 0.56 0.98

South -4.09 6.98 -1.92 1.41 -2.49 4.89 -2.45 1.43 1.57 -3.35 2.62 0.59

West -1.99 3.82 -0.19 1.18 -0.16 0.10 0.89 0.97 0.06 -0.22 0.48 0.99

North-East -1.73 3.45 -0.02 1.23 0.10 -0.55 1.15 0.92 -0.26 0.30 0.48 1.02

South-East -2.06 4.32 -0.96 1.41 -0.60 0.90 0.37 0.94 0.83 -1.42 1.22 0.92

South-West -2.06 4.48 -1.13 1.40 -0.39 0.50 0.60 0.87 1.56 -3.17 2.41 0.73

North-West -0.53 0.72 1.79 0.93 0.10 -0.38 0.96 0.96 0.24 -0.57 0.90 0.97

(b) Vertical fenestration located more than 2.2 m above the level of the floor are exempt from the SHGC

requirement in Table 4.9, if the following conditions are complied with:

i. Total Effective Aperture: The total Effective Aperture for the elevation is less than 0.25, including

all fenestration areas greater than 1.0 m above the floor level; and,

ii. An interior light shelf is provided at the bottom of this fenestration area, with an interior projection factor not less than:

1. 1.0 for E-W, SE, SW, NE, and NW orientations

2. 0.5 for S orientation, and

0.35 for N orientation when latitude is < 23 degrees.

4.3.4 U-Value Exemption for Shaded Buildings

Opaque areas of non-north façades in shaded buildings can have maximum U-value of 5 W/m2- ºC

provided they fulfil conditions indicated in Table 4.12.

Table 4.12 U-Value (W/m2 -ºC) Requirements for Shaded Buildings

Building Type Climate zone Orientation SHGC Shading

Projection Factor

Day time buildings and

naturally ventilated buildings

All except cold

climate

Non North 0.27 >=0.4

4.3.5 Skylights

Skylights shall comply with the maximum U-factor and maximum SHGC requirements of Table 4.13.

Skylight area is limited to a minimum of 5% of the gross roof area for the prescriptive requirement.

Table 4.13 Skylight U-factor and SHGC Requirements (U-factor in W/m2-°C)

Climate Maximum U-factor Maximum SHGC

With Curb w/o Curb 0-2% SRR 2.1-5% SRR

Composite 11.24 7.71 0.40 0.25

Hot and Dry 11.24 7.71 0.40 0.25

Warm and Humid 11.24 7.71 0.40 0.25

Moderate 11.24 7.71 0.61 0.4

Cold 11.24 7.71 0.61 0.4

SRR = Skylight roof ratio which is the ratio of the total skylight area of the roof, measured to the outside of the frame, to the gross exterior roof.

See Appendix C § 10.2.2 for typical complying skylight constructions.

Page 32: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Building Envelope

4.3.6 Building Envelope Trade-Off Method

The building envelope complies with the code if the building envelope performance factor (EPF) of the

proposed design is less than the standard design, where the standard design exactly complies with the

criteria in § 4.3. Equation 11.1 in Appendix D should be referred for calculating envelope trade-off.

Page 33: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Energy Conservation Building Code 2016 23

5. Comfort Systems and Controls

5.1 General

All heating, ventilation, air conditioning equipment and systems and, their controls shall comply with the

mandatory provisions of § 5.2 and the prescriptive criteria of § 5.3.

All service water heating equipment and systems shall comply with the mandatory provisions of § 5.2.

5.2 Mandatory Requirements

5.2.1 Ventilation

(a) All habitable spaces shall be ventilated with outdoor air in accordance with the requirements of §

5.2.1 and guidelines specified in National Building Code 2005, Part 8, Section 1 and Section 3.

(b) Ventilated spaces shall be provided with outdoor air using either of the following:

1. Natural ventilation

2. Mechanical ventilation

3. Mixed mode ventilation

5.2.1.1 Natural Ventilation Air Quantity Design Requirements

Naturally ventilated spaces shall:

(a) Comply with guidelines provided for natural ventilation in Section 1 of Part 8, National Building

Code of India 2005

(b) Have permanent roof or wall openings, windows, doors, louvres to the outdoors etc., the

openable area of which shall not be less than 5% of the floor area of the naturally ventilated

space. Openable area shall be calculated on basis of free unobstructed area through the opening

(c) Be within 14 feet of roof or wall openings to outdoors

(d) Have minimum 3 star rated ceiling fans if provided with ceiling fans

Exceptions to § 5.2.1.1: Naturally ventilated spaces in hotel/ motel guest rooms shall be open to and

within 8 meters of operable wall or roof openings to outdoors.

5.2.1.2 Mechanical Ventilation Air Quantity Design Requirements

Spaces not ventilated naturally shall be ventilated with mechanical ventilation systems. Mechanical

systems shall

(a) provide outdoor air rate no less than the conditioned floor area of the space times the applicable

ventilation rate from National Building Code of India 2005

(b) comply with guidelines provided for mechanical ventilation in Section 1 and Section 3 of Part 8,

National Building Code of India 2005

Exceptions to § 5.2.1.2: Air could be transferred from other ventilated spaces if

(a) The space from which air is transferred does not have any sources of indoor air contamination.

(b) The outdoor air that is supplied to all spaces combined is sufficient to meet the requirements of

NBC for each space individually.

Page 34: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Box 5.1 Set points for Comfort Conditions

Box 5.1 Adaptive Thermal Comfort

Human body has the ability to adapt to environmental conditions and become accustomed to them

over time. People accustomed to the variability of environmental parameters in non-air-conditioned

buildings can live and work through a larger temperature range without experiencing thermal

discomfort. This logic informs the adaptive thermal comfort model for buildings. Adaptive comfort

models offer an opportunity to reduce energy use as buildings can be operated at more moderate

temperatures. Energy used to maintain stringent comfort conditions through mechanical equipment

can thus be avoided. CEPT, India, has developed an adaptive comfort model for India. Operative

temperatures for the model can be calculated using the formulae below.

Naturally Ventilated Buildings

Indoor Operative Temperature = (0.54 x outdoor temperature) + 12.83

Where, indoor operative temperature (°C) is neutral temperature, & outdoor temperature is

the 30-day outdoor running mean air temperature (°C).

The 90 percent acceptability range for the India specific adaptive models for naturally

ventilated buildings is ± 2.38°C.

For example, Indoor Operative Temperature for a naturally ventilated building in Delhi

= (0.54 x 33.0) + 12.83 = 30.68 oC

Mixed Mode Buildings

Indoor Operative Temperature = (0.28 x outdoor temperature) + 17.87

Where indoor operative temperature (°C) is neutral temperature & outdoor temperature is

the 30-day outdoor running mean air temperature (°C).

The 90 percent acceptability range for the India specific adaptive models for mixed-mode

buildings is ± 3.46°C.

For example, Indoor Operative Temperature for a mixed mode building in Delhi

= (0.28 x 33.0) + 17.87 = 27.1 oC

Air conditioned Buildings

Indoor Operative Temperature = (0.078 x outdoor temperature) + 23.25

Where indoor operative temperature (°C) is neutral temperature & outdoor temperature is

the 30-day outdoor running mean air temperature (°C).

The 90 percent acceptability range for the adaptive models for conditioned buildings is

±1.5°C.

For example, Indoor Operative Temperature for an air conditioned building in Delhi

= (0.078 x 33.0)+ 23.25 = 25.8 oC

Reference: Manu, S., Shukla, Y., Rawal, R., de Dear, R., & Thomas, L. E. (2014). Developing an India Model for Adaptive (Thermal) Comfort: IMAC 2014. Ahmedabad, India: Centre for Advanced Research in Building Science and Energy (CARBSE), CEPT University. Submitted to the Ministry of New and Renewable Energy, Govt. of India and Shakti Sustainable Energy Foundation.

Page 35: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Energy Conservation Building Code 2016 25

5.2.1.3 Operational Controls for Minimum Outdoor Air

Mechanical ventilation systems shall provide the minimum required quantities of outdoor air as per §

5.2.1.2 at all times of occupancy.

Exception to § 5.2.1.3:

(a) Spaces provided with demand control ventilation are exempt.

(b) Temporary reduction in air supply is allowed if the average rate for each hour is greater than or

equal to required ventilate rate.

5.2.1.4 Demand Control Ventilation

Mechanical ventilation systems shall have demand control ventilation if they provide outdoor or fresh air

to a space with occupant density exceeding 40 people per 100 m².

Exceptions to § 5.2.1.4: Following shall be exempt from installing demand control ventilation system:

(a) Classrooms, call centers, continuously occupied office spaces, healthcare facilities and medical

buildings, and public areas of social services buildings

(b) Spaces that have processes or operations that generate dusts, fumes, mists, vapors, or gases

and are not provided with local exhaust ventilation, such as indoor operation of internal

combustion engines or areas designated for unvented food service preparation, or beauty salons

(c) Spaces with an area of less than 15 m2, or a design occupancy of less than 10 people per NBC

standard recommendations.

5.2.2 Minimum Space Conditioning Equipment Efficiencies

5.2.2.1 Chillers

Chillers shall meet or exceed the minimum efficiency requirements presented in Error! Reference

ource not found. through Table 5.3.

Table 5.1 Minimum Energy Efficiency Requirements for Chillers in ECBC Buildings

Equipment Class Constant VSD

Air Cooled Chiller <530 kW 3.0 2.7

≥530 kW 3.0 2.7

Water cooled chiller <530 kW 5.5 5.0

≥530 & <1050 kW 5.8 5.2

≥1050kW 6.1 (5.8) 5.5

≥2110 kW 6.3 5.7

Table 5.2 Minimum Energy Efficiency Requirements for Chillers in EE Buildings

Equipment Class COP

Air Cooled Chiller <530 kW 3.3

≥530 kW 3.3

Water cooled chiller <530 kW 5.8

≥530 & <1050 kW 6.1

≥1050kW 6.3

≥2110 kW 6.5

Page 36: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Table 5.3 Minimum Energy Efficiency Requirements for Chillers in Super EE Buildings

Equipment Class COP

Air Cooled Chiller <530 kW NA

≥530 kW NA

Water cooled chiller <530 kW 6.1

≥530 & <1050 kW 6.3

≥1050kW 6.5

≥2110 kW 6.7

5.2.2.2 Unitary Air-conditioners

Unitary air-conditioners shall meet or exceed the efficiency requirements presented in Table 5.4 through

Table 5.6. Window and split air conditioners shall be certified under BEE’s Star Labeling Program.

Table 5.4 Minimum Efficiency Requirements for Unitary Air Conditioners in ECBC Buildings

Cooling Capacity Efficiency

kWr Water Cooled Air Cooled

≤ 10.5 NA BEE 3 Star

> 10.5 and < 17.5 3.55 3.28

> 17.5 and < 26.25 3.55 3.28

> 26.25 and < 35 3.55 3.28

> 35 and < 52.5 3.55 3.28

> 52.5 3.55 3.28

Table 5.5 Minimum Efficiency Requirements for Unitary Air Conditioners in EE Buildings

Cooling Capacity Efficiency

kWr Water Cooled Air Cooled

≤ 10.5 NA BEE 4 Star

> 10.5 and < 17.5 3.72 3.45

> 17.5 and < 26.25 3.72 3.45

> 26.25 and < 35 3.72 3.45

> 35 and < 52.5 3.72 3.45

> 52.5 3.72 3.45

Table 5.6 Minimum Efficiency Requirements for Unitary Air Conditioners in Super EE Buildings

Cooling Capacity Efficiency

kWr Water Cooled Air Cooled

≤ 10.5 NA BEE 5 Star

> 10.5 and < 17.5 3.88 3.62

> 17.5 and < 26.25 3.88 3.62

> 26.25 and < 35 3.88 3.62

> 35 and < 52.5 3.88 3.62

> 52.5 3.88 3.62

Page 37: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Energy Conservation Building Code 2016 27

5.2.2.3 Variable Refrigerant Flow

Variable Refrigerant Flow systems shall meet or exceed the efficiency requirements specified in Table

5.7.

Table 5.7 Minimum Efficiency Requirements for Variable Refrigerant Flow Air conditioners*

5.2.2.4 Precision Air Conditioners

Precision air conditioners in buildings with built up area greater than 20,000 m2 shall meet or exceed the

energy efficiency requirements listed in Table 5.8.

Table 5.8 Minimum Efficiency Requirements for Precision Air Conditioners

5.2.3 Minimum System Efficiency

Building

cooling

systems

shall

meet or

exceed

minimu

m

efficienc

y

require

ments as specified in Table 5.9.

Table 5.9 Minimum System Efficiency* for ECBC Buildings

System type Peak building cooling load (kW)

<3516 kW ≥ 3516 kW

Central chilled water plant (Water cooled)1 0.21(kW/ kWr) 0. 20 (kW/ kWr)

*Minimum system efficiency (total installed equipment per cooling capacity)

5.2.4 Controls

ECBC, EE and Super EE buildings shall comply with requirements of § 5.2.4.1 through § 5.2.4.5.

5.2.4.1 Timeclock

1 Central chilled water plant includes chillers, chilled water, chilled and condenser water pumps, and

cooling towers.

Equipment type Size category Minimum Efficiency

VRF Air Conditioners, Air cooled <19 kW 3.28 COP

>=19 kW and < 40 kW 3.29 COP

>= 40 kW and < 70 kW 3.26 COP

>= 70 kW 3.02 COP

Equipment type Net Sensible Cooling

Capacitya

Minimum SCOP-127b

Downflow Upflow

Air Conditioners, Air cooled <19 kW 2.20 2.09

>=19 kW and < 70 kW 2.10 1.99

>=70 kW 1.90 1.79

Air Conditioners, Water cooled <19 kW 2.60 2.49

>=19 kW and < 70 kW 2.50 2.39

>=70 kW 2.40 2.29

a. Net Sensible cooling capacity = Total gross cooling capacity - latent cooling capacity – Fan power b. Sensible coefficient of performance (SCOP-127): A ratio calculated by dividing the net sensible

cooling capacity in watts by the total power input in watts (excluding reheater and dehumidifier) at conditioned defined in ASHRAE standard 127)

Page 38: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Mechanical cooling and heating systems in universities and, all offices and malls with built up area

greater than 15,000 m2 shall be controlled by timeclocks that:

(a) Can start and stop the system under different schedules for three different day-types per week,

(b) Are capable of retaining programming and time setting during loss of power for a period of at

least 10 hours, and

(c) Include an accessible manual override that allows temporary operation of the system for up to 2

hours.

Exceptions to § 5.2.4.1:

(a) Cooling systems < 17.5 kW

(b) Heating systems < 5 kW

5.2.4.2 Temperature Controls

Mechanical heating and cooling equipment in office buildings and mass with built up area greater than

20,000 m2 shall be installed with controls to manage the temperature inside the conditioned zones.

These controls should meet the following requirements:

(a) where a unit provides both heating and cooling, controls shall be capable of providing a

temperature dead band of 3°C within which the supply of heating and cooling energy to the zone

is shut off or reduced to a minimum

(b) where separate heating and cooling equipment serve the same temperature zone, thermostats

shall be interlocked to prevent simultaneous heating and cooling

(c) in warm and humid climates, thermostat controls shall also be programmed to maintain humidity

at 60%

(d) thermostat controls shall be installed in all guest rooms of hotels and motels and, all rooms less

than 25 m²

5.2.4.3 Occupancy Controls

Occupancy controls shall be installed to de-energize the system when there are no occupants in the

following:

(a) Hotel guest rooms

(b) Toilets in hotel and offices with more than 2 water closets and/ or 3 urinals

(c) Conference and meeting rooms in offices

(d) Any room in a school and university of size more than 80 m²

5.2.4.4 Fan Controls

Cooling towers and closed circuit fluid coolers in buildings with built up area greater than 20,000 m2 shall

have:

(a) Either two speed motors, pony motors, or variable speed drives controlling the fans.

(b) Controls capable to reduce the fan speed to at least two third of installed fan power

5.2.4.5 Dampers

All air supply and exhaust equipment shall have dampers that automatically close upon

(a) Fan shutdown, or,

(b) When spaces served are not in use

5.2.5 Additional Controls for EE and Super EE Buildings

EE and Super EE buildings shall comply with requirements of § 5.2.5.1 through § 5.2.5.3 in addition to

complying with requirements of § 5.2.4.

Page 39: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Energy Conservation Building Code 2016 29

5.2.5.1 Centralized Demand Shed Controls

EE and Super EE buildings with built up area greater than 20,000 m2 shall have a building management

system. All mechanical cooling and heating systems in EE and Super EE buildings with direct digital

control (DDC) to the zone level shall have the following control capabilities to manage centralized

demand shed in noncritical zones:

(a) Automatic demand shed controls that can implement a centralized demand shed in non-critical zones

during the demand response period on a demand response signal.

(b) Controls that can remotely decrease or increase the operating temperature set points by four

degrees or more in all noncritical zones on signal from a centralized control point

(c) Controls that can provide an adjustable rate of change for the temperature setup and reset

The centralized demand shed controls shall have additional capabilities to

i. Be disabled by facility operators

ii. Be manually controlled from a central point by facility operators to manage heating and cooling

set points

5.2.5.2 Supply Air Temperature Reset

Multi zone mechanical cooling and heating systems in EE and Super EE buildings shall have controls that

automatically reset the supply-air temperature in response to building loads or to outdoor air

temperature. Controls shall reset the supply air temperature to at least 25% of the difference between

the design supply air temperature and the design room air temperature.

Exception to § 5.2.5.2 : EE and Super EE buildings in warm humid climate zone.

5.2.5.3 Chilled Water Temperature Reset

Chilled water systems with a design capacity exceeding 87.5 kW supplying chilled water to comfort

conditioning systems in EE and Super EE buildings shall have controls that automatically reset supply

water temperatures by representative building loads (including return water temperature) or by outdoor

air temperature.

Exceptions to § 5.2.5.3: Controls to automatically reset chilled water temperature shall not be required:

(a) Where the supply temperature reset controls causes improper operation of equipment.

(b) In hydronic systems that uses variable flow to reduce pumping energy.

5.2.6 Additional Controls for Super EE Buildings

Super EE buildings shall comply with requirements of § 5.2.6.1 and § 5.2.6.2 in addition to complying

with requirements of § 5.2.4 and § 5.2.5.

5.2.6.1 Variable Air Volume Fan Control

Fans in VAV systems in Super EE buildings shall have controls or devices that will result in fan motor

demand of no more than 30 % of their design wattage at 50 % of design airflow when static pressure

set point equals one-third of the total design static pressure, based on manufacturer’s certified fan data.

5.2.6.2 Air Side Economizer Control

Air side economizers in Super EE buildings shall comply with the following requirements:

(a) Dampers in air side economizers shall be sequenced with the mechanical cooling equipment and

shall not be controlled by only mixed air temperature.

(b) Air side economizers shall be capable of automatically reducing outdoor air intake to the design

minimum outdoor air quantity when outdoor air intake will no longer reduce cooling energy

usage.

(c) High-limit shutoff shall be specified.

Page 40: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

5.2.7 Piping and Ductwork

5.2.7.1 Piping Insulation

Piping for heating, space conditioning and service hot water systems shall meet the insulation

requirements listed in Table 5.10 through Table 5.12. Insulation exposed to weather shall be protected

by aluminum sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as

above, or be painted with water retardant paint.

Exceptions to § 5.2.7.1:

(a) Reduction in insulation R value by 0.2 (compared to values in Table 5.10, Table 5.11 and Table

5.12) to a minimum insulation level of R-0.4 shall be permitted for any pipe located in partition

within a conditioned space or buried

(b) Insulation R value shall be increased by 0.2 over and above the requirement stated in Table 5.10

through Table 5.12 for any pipe located in a partition outside a building with direct exposure to

weather

(c) Reduction in insulation R value by 0.2 (compared to values in Table 5.10, Table 5.11 and Table

5.12) to a minimum insulation level of R-0.4 shall be permitted for buildings in temperate climate

zone

Table 5.10 Insulation Requirements for Pipes in ECBC Buildings

Operating Temperature (ºC) Pipe size (mm)

<25 >=40

Insulation R value (m2-ºC/W)

Heating System

94°C to 121°C 0.9 1.2

60°C to 94°C 0.7 0.7

40°C to 60°C 0.4 0.7

Cooling System

4.5°C to 15°C 0.4 0.7

< 4.5°C 0.9 1.2

Refrigerant Piping (Split systems)

4.5°C to 15°C 0.4 0.7

< 4.5°C 0.9 1.2

Page 41: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Energy Conservation Building Code 2016 31

Table 5.11 Insulation Requirements for Pipes in EE Buildings

Operating Temperature (ºC)

Pipe size (mm)

< 40 >=40

Insulation R value (m2-ºC/W)

Heating System

94°C to 121°C 1.1 1.3

60°C to 94°C 0.8 0.8

40°C to 60°C 0.5 0.9

Cooling System

4.5°C to 15°C 0.5 0.9

< 4.5°C 1.1 1.3

Refrigerant Piping (Split Systems)

4.5°C to 15°C 0.5 0.9

< 4.5°C 1.1 1.3

Table 5.12 Insulation Requirements for Pipes in Super EE Buildings

Operating Temperature (ºC)

Pipe size (mm)

< 40 >=40

Insulation R value (m2-ºC/W)

Heating System

94°C to 121°C 1.5 1.5

60°C to 94°C 1.0 1.3

40°C to 60°C 0.7 1.1

Cooling System

4.5°C to 15°C 0.7 1.2

< 4.5°C 1.5 1.5

Refrigerant Piping (Split Systems)

4.5°C to 15°C 0.4 0.7

< 4.5°C 1.5 1.5

5.2.7.2 Ductwork Insulation

Ductwork shall be insulated in accordance with Table 5.13.

Table 5.13 Ductwork Insulation (R value in m2 – ºC/W) Requirements

Duct Location Supply ducts Return ducts

Exterior R -1.4 R -0.6

Unconditioned Space R -0.6 None

Buried R -0.6 None

5.2.8 System Balancing

5.2.8.1 General

All HVAC systems shall be balanced in accordance with generally accepted engineering standards.

Construction documents shall include a balance report provided to the owner or the designated

representative of the building owner for HVAC systems serving zones with a total conditioned area

exceeding 500 m2.

5.2.8.1.1 Air System Balancing

Page 42: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Air systems shall be balanced in a manner to first minimize throttling losses. Then, for fans with fan

system power greater than 0.75 kW, fan speed shall be adjusted to meet design flow conditions.

5.2.8.1.2 Hydronic System Balancing

Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses; then

the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions.

Exceptions to § 5.2.8.1.2:

(a) Impellers need not be trimmed nor pump speed adjusted for pumps with pump motors of 7.5 kW

or less,

(b) Impellers need not be trimmed when throttling results in no greater than 5% of the nameplate horsepower draw, or 2.2 kW, whichever is greater.

5.2.9 Condensers

5.2.9.1 Condenser Locations

Care shall be exercised in locating the condensers in such a manner that heat sink is free of interference

from heat discharge by devices located in adjoining spaces and also does not interfere with such other

systems installed nearby.

5.2.9.2 Treated Water for Condensers

All high-rise buildings using centralized cooling water system shall use soft water for the condenser and

chilled water system.

5.2.10 Service Hot Water Heating

5.2.10.1 Solar Water Heating

Hotels and hospitals with a centralized system shall have solar water heating equipment installed to

provide for:

(a) at least 20% of the design capacity in other buildings if building area < 20,000 m²

(b) at least 40% of the design capacity in other buildings if building area > 20,000 m²

Exception to § 5.2.10.1: Systems that use heat recovery for at least 40% of the design hot water

capacity.

5.2.10.2 Solar Water Heating Equipment Efficiency

Service water heating equipment shall meet or exceed the performance and minimum efficiency

requirements presented in available Indian Standards

(a) Solar water heater shall meet the performance/ minimum efficiency level mentioned in IS 13129

Part (1&2)

(b) Gas Instantaneous Water heaters shall meet the performance/minimum efficiency level

mentioned in IS 15558 with above 80% thermal efficiency.

Electric water heater shall meet the performance / minimum efficiency level mentioned in IS 2082.

5.2.10.3 Supplementary Water Heating System

Supplementary heating system shall be designed to maximize the energy efficiency of the system and

shall incorporate the following design features in cascade:

(a) Maximum heat recovery from hot discharge system like condensers of air conditioning units,

(b) Use of gas fired heaters wherever gas is available, and

(c) Electric heater as last resort.

Page 43: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Energy Conservation Building Code 2016 33

5.2.10.4 Piping Insulation

Piping insulation shall comply with § 5.2.7.1. The entire hot water system including the storage tanks,

pipelines shall be insulated conforming to the relevant IS standards on materials and applications.

5.2.10.5 Heat Traps

Vertical pipe risers serving storage water heaters and storage tanks not having integral heat traps and

serving a non-recirculating system shall have heat traps on both the inlet and outlet piping as close as

practical to the storage tank.

5.2.10.6 Swimming Pools

Heated pools shall be provided with a vapor retardant pool cover on or at the water surface. Pools

heated to more than 32°C shall have a pool cover with a minimum insulation value of R-4.1.

Exception to § 5.2.10.6: Pools deriving over 60% of their energy from site-recovered energy or solar

energy source.

5.3 Prescriptive Requirements

Compliance shall be demonstrated with the requirements in § 5.3.1 through § 5.3.8 for HVAC systems

that meet the following criteria:

(a) Serves a single zone,

(b) Cooling (if any) is provided by a unitary packaged or split-system air conditioner or heat pump,

(c) Heating (if any) is provided by a unitary packaged or split-system heat pump, fuel-fired furnace,

electric resistance heater, or baseboards connected to a boiler, and

(d) Outside air quantity is less than 1,400 l/s and less than 70% of supply air at design conditions.

5.3.1 Fans

Supply, exhaust and return or relief fans with motor power exceeding .37 kW shall meet or exceed the

minimum energy efficiency requirements specified in Table 5.14 through Table 5.16.

Page 44: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Table 5.14 Mechanical and Motor Efficiency Requirements for Fans in ECBC Buildings

System type Fan Type Mechanical Efficiency Motor Efficiency

(As per IS 12615)

Central system and

Ductable VRVs

Supply 60% IE 2

Return & Exhaust 55% IE 2

Applies to fans with free inlet and with a duct fitted to its outlet or with a duct fitted to its inlet and outlet. Efficiency is total efficiency of the fan based on measurements of total fan pressure.

Table 5.15 Mechanical and Motor Efficiency Requirements for Fans in EE Buildings

System type Fan Type Mechanical Efficiency Motor Efficiency

(As per IS 12615)

Central system and

Ductable VRVs

Supply 65% IE 3

Return and Exhaust 60% IE 3

Applies to fans with free inlet and with a duct fitted to its outlet or with a duct fitted to its inlet and outlet. Efficiency is total efficiency of the fan based on measurements of total fan pressure.

Table 5.16 Mechanical and Motor Efficiency Requirements for Fans in Super EE Buildings

5.3.2 Pumps

Chilled

and

condens

er water

pumps

shall meet or exceed the minimum energy efficiency requirements specified in Table 5.17 through Table

5.19. Requirements for pumps in district chiller systems are limited to the installed efficiency requirement

of individual pump equipment only.

Exceptions to § 5.3.2: Pumps used in processes e.g. service hot water, chilled water used for

refrigeration etc.

Table 5.17 Pump Efficiency Requirements for ECBC Buildings

System Type Fan Type Mechanical Efficiency Motor Efficiency (As per IS 12615)

Central system

and

Ductable VRVs

Supply 70% IE 4

Return & Exhaust 65% IE 4

Applies to fans with free inlet and with a duct fitted to its outlet or with a duct fitted to its inlet and outlet. Efficiency is total efficiency of the fan based on measurements of total fan pressure.

Equipment ECBC 2016

Chilled Water Pump (Primary

and Secondary)

18.2 W/ kWr with VSD

Condenser Water Pump 17.7 W/ kWr

Pump Efficiency With 70% efficiency

Page 45: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Energy Conservation Building Code 2016 35

Table 5.18 Pump Efficiency Requirements for EE Buildings

Equipment EE Building

Chilled Water Pump (Primary

and Secondary)

16.9 W/ kWr with VSD

Condenser Water Pump 16.5 W/ kWr

Pump Efficiency With 75% efficiency

Table 5.19 Pump Efficiency Requirements for Super EE Buildings

Equipment Super EE Building

Chilled Water Pump (Primary

and Secondary)

14.9 W/ kWr with VSD

Condenser Water Pump 14.6 W/ kWr

Pump Efficiency With 85% efficient pumps

5.3.3 Cooling Towers

Cooling towers shall meet or exceed the minimum efficiency requirements specified in Table 5.20. EE and

Super EE buildings shall have additional VFD installed in the cooling towers.

Table 5.20 Cooling Tower Efficiency Requirements for ECBC Buildings

Equipment type Rating Condition Efficiency*

Propeller or axial fan

open/ closed -circuit cooling towers

35°C entering water

29°C leaving water

24°C WB outdoor air

0.017 kW/kWr

0.31 kW/ L/s

Centrifugal fan

open/ closed -circuit cooling towers

35°C entering water

29°C leaving water

24°C WB outdoor air

0.034 kW/kWr

(0.59 kW/ L/s)

*Tonnage considered is the cooling capacity.

5.3.4 Economizers

5.3.4.1 Air Side Economizer

Each individual cooling fan system that has a design supply capacity over 1,200 l/s and a total

mechanical cooling/ heating capacity over 15.8 kW shall include either:

(a) An air economizer capable of modulating outside-air and return-air dampers to supply 100

percent of the design supply air quantity as outside-air; or (b) A water economizer capable of providing 100% of the expected system cooling load at outside

air temperatures of 10°C dry-bulb/7.2°C wet-bulb and below.

Exception to § 5.3.2:

(a) Projects in warm-humid climate zones are exempt.

(b) Projects with only daytime occupancy in the hot-dry are exempt.

(c) Individual ceiling mounted fan systems < 3,200 l/s are exempt.

5.3.4.2 Partial Cooling

Where required by § 5.3.2 economizers shall be capable of providing partial cooling even when additional

mechanical cooling is required to meet the cooling load.

Page 46: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

5.3.4.3 Controls

Air economizer shall be equipped with controls

(a) That allow dampers to be sequenced with the mechanical cooling equipment and not be

controlled by only mixed air temperature.

(b) capable of automatically reducing outdoor air intake to the design minimum outdoor air quantity

when outdoor air intake will no longer reduce cooling energy usage.

5.3.4.4 Testing

Air-side economizers shall be tested in the field following the requirements in Appendix G to ensure

proper operation.

Exception to § 5.3.4.4: Air economizers installed by the HVAC system equipment manufacturer and

certified to the building department as being factory calibrated and tested per the procedures in

Appendix G §14.4 and § 14.3 .

5.3.5 Variable Flow Hydronic Systems

5.3.5.1 Variable Fluid Flow

Chilled or hot-water systems shall be designed for variable fluid flow and shall be capable of reducing

pump flow rates to no more than the larger of:

(a) 50% of the design flow rate, or (b) the minimum flow required by the equipment manufacturer for proper operation of the chillers or

boilers.

5.3.5.2 Isolation Valves

Water cooled air-conditioning or heat pump units with a circulation pump motor greater than or equal to

3.7 kW shall have two-way automatic isolation valves on each water cooled air-conditioning or heat

pump unit that are interlocked with the compressor to shut off condenser water flow when the

compressor is not operating.

5.3.5.3 Variable Speed Drives

Chilled water or condenser water systems that must comply with either § 5.3.5.1 or § 5.3.5.2 and that

have pump motors greater than or equal to 3.7 kW shall be controlled by variable speed drives.

5.3.6 Boilers

Gas and oil fired boilers shall meet or exceed the minimum efficiency requirements specified in Table

5.21.

Table 5.21 Minimum Efficiency Requirements for Oil and Gas Fired Boilers

5.3.7 Low Energy Comfort Systems

Building

s that

have

any of

the low

Equipment Type Sub Category Size Category Minimum Efficiency

Boilers, Hot Water Gas fired <88 kW 80% AFUE

>=88 kW and <=732 kW 75% Et

>732 kW 80% Ec

Oil fired <88 kW 80% AFUE

>=88 kW and <=732 kW 78% Et

>732 kW 83 % Ec

AFUE - annual fuel utilization efficiency Ec - combustion efficiency (100% less flue losses) Et - Thermal efficiency

Page 47: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Comfort Systems and Controls

Energy Conservation Building Code 2016 37

energy comfort systems listed below shall be exempt from all requirements of § 5.2 except § 5.2.7 and §

5.2.8:

(a) Evaporative Cooling

(b) Desiccant cooling system

(c) Solar air conditioning

(d) Tri- generation (Waste to heat)

(e) Radiant cooling system

(f) Ground source heat pump

(g) Adiabatic cooling system

5.3.8 Heat Recovery

All systems of capacity greater than 2100 l/s and minimum outdoor air supply of 70% shall have air-to-

air heat recovery equipment with minimum 70% recovery effectiveness

At least 50% of heat shall be recovered from diesel and gas fired DG sets Heat installed in hotel and

office buildings with built up area greater than 20,000 m2.

Page 48: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

6. Lighting and Controls

6.1 General

Lighting systems and equipment shall comply with the mandatory provisions of § 6.2 and the prescriptive

criteria of § 6.3 and § 6.3.4. The lighting requirements in this section shall apply to:

(a) Interior spaces of buildings,

(b) Exterior building features, including facades, illuminated roofs, architectural features, entrances,

exits, loading docks, and illuminated canopies, and,

(c) Exterior building grounds lighting that is provided through the building's electrical service.

Exceptions to § 6.1:

(a) Emergency lighting that is automatically off during normal building operation and is powered by

battery, generator, or other alternate power source; and,

(b) Lighting in dwelling units.

6.2 Mandatory Requirements

6.2.1 Lighting Control

6.2.1.1 Automatic Lighting Shutoff

Interior lighting systems in office spaces larger than 300 m² shall be equipped with automatic control

devices. Occupancy sensors shall also be provided in:

(a) All office spaces less than 30 m² enclosed by walls or ceiling height partitions

(b) Storage spaces more than 15 m²

(c) Hotel public toilets more than 25 m²

(d) Hotel and hospital corridors

(e) Conference rooms, and laboratories

For other spaces, Automatic control device shall function on either

(a) A scheduled basis at specific programmed times. An independent program schedule shall be

provided for areas of no more than 2,500 m2 and not more than one floor; or,

(b) Occupancy sensors that shall turn the lighting off for only 95% of the lighting fixtures within 15

minutes of an occupant leaving the space. Light fixtures controlled by occupancy sensors shall

have a wall-mounted, manual switch capable of turning off lights when the space is occupied.

Exception to § 6.2.1.1: Lighting systems designed for emergency and firefighting purposes.

6.2.1.2 Space Control

Each space enclosed by ceiling-height partitions shall have at least one control device to independently

control the general lighting within the space. Each control device shall be activated either manually by an

occupant or automatically by sensing an occupant. Each control device shall

(a) Control a maximum of 250 m2 for a space less than or equal to 1,000 m2, and a maximum of

1,000 m2 for a space greater than 1,000 m2.

(b) Be capable of overriding the shutoff control required in § 6.2.1.1 for no more than 2 hours, and

(c) Be readily accessible and located so the occupant can Super EE the control.

Page 49: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

Energy Conservation Building Code 2016 39

Exception to § 6.2.1.2 (c): The required control device may be remotely installed if required for reasons

of safety or security. A remotely located device shall have a pilot light indicator as part of or next to the

control device and shall be clearly labeled to identify the controlled lighting.

6.2.1.3 Control in Daylight Areas

Luminaires in daylight areas shall be equipped with either a manual or automatic control device that:

(a) Is within a distance of 5 meters from the window

(b) Has a set point between 50 to 1,000 lux,

(c) Has a delay of greater than 2 minutes and differential of greater than 50 lux,

(d) Is capable of dimming or stepping up to 50% of total power, and

(e) Controls only the luminaires located entirely within the daylight area.

Daylight controls shall also be provided in corridors, lobbies and toilets. Overrides to the daylight controls

shall not be allowed. Lighting Power Density adjustment factor of 20% shall be allowed to all spaces with

more than 70% of their area under daylight controls.

6.2.1.4 Centralized Controls for EE and Super EE Buildings

EE and Super EE buildings shall have centralized control systems for daylight sensors, manual or

automatic dimmers and, schedule based automatic lighting shutoff switches.

6.2.1.5 Exterior Lighting Control

Lighting for all exterior applications not exempted in § 6.3.5 shall be controlled by a photo sensor or

astronomical time switch that is capable of automatically turning off the exterior lighting when daylight is

available or the lighting is not required.

Universities, Information Technology campus and other buildings with built up area greater than 15,000

m² shall have-

(a) Average light source efficacy not greater than 70 lm/ W, and

(b) On/off or 50% dimmable motion detectors for at least 80% of landscape and street lighting.

Façade lighting and signage shall have separate time switches.

Exemption to § 6.2.1.5: Exterior emergency lighting.

6.2.1.6 Additional Control

The following lighting applications shall be equipped with a control device to control such lighting

independently of general lighting:

(a) Display/Accent Lighting. Display or accent lighting greater than 300 m2 area shall have a

separate control device.

(b) Case Lighting. Lighting in cases used for display purposes greater than 300 m2 area shall be

equipped with a separate control device.

(c) Hotel and Motel Guest Room Lighting. Hotel and motel guest rooms and guest suites shall have a

master control device at the main room entry that controls all permanently installed luminaires

and switched receptacles.

(d) Task Lighting. Supplemental task lighting including permanently installed under shelf or under

cabinet lighting shall have a control device integral to the luminaires or be controlled by a wall-

mounted control device provided the control device complies with § 6.2.1.2 (c).

(e) Nonvisual Lighting. Lighting for nonvisual applications, such as plant growth and food-warming,

shall be equipped with a separate control device.

(f) Demonstration Lighting. Lighting equipment that is for sale or for demonstrations in lighting

education shall be equipped with a separate control device accessible only to authorized

personnel.

Page 50: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

6.2.2 Exit Signs

Internally-illuminated exit signs shall not exceed 5 W per face.

6.2.3 Exterior Building Grounds Lighting

Lighting for exterior building grounds luminaires which operate at greater than 100 W shall contain lamps

having a minimum efficacy of 60 lm/W unless the luminaire is controlled by a motion sensor or exempt

under § 6.1.

6.3 Prescriptive Requirements

6.3.1 Interior Lighting Power

The installed interior lighting power for a building or a separately metered or permitted portion of a

building shall be calculated in accordance with § 6.3.4 and shall not exceed the interior lighting power

allowance determined in accordance with either § 6.3.2 or § 6.3.3. Tradeoffs of interior lighting power

allowance among portions of the building for which a different method of calculation has been used are

not permitted.

Exception to § 6.3: The following lighting equipment and applications shall not be considered when

determining the interior lighting power allowance, nor shall the wattage for such lighting be included in

the installed interior lighting power. However, any such lighting shall not be exempt unless it is an

addition to general lighting and is controlled by an independent control device.

(a) Display or accent lighting that is an essential element for the function performed in galleries,

museums, and monuments,

(b) Lighting that is integral to equipment or instrumentation and is installed by its manufacturer,

(c) Lighting specifically designed for medical or dental procedures and lighting integral to medical

equipment,

(d) Lighting integral to food warming and food preparation equipment,

(e) Lighting for plant growth or maintenance,

(f) Lighting in spaces specifically designed for use by the visually impaired,

(g) Lighting in retail display windows, provided the display area is enclosed by ceiling-height

partitions,

(h) Lighting in interior spaces that have been specifically designated as a registered interior historic

landmark,

(i) Lighting that is an integral part of advertising or directional signage,

(j) Exit signs,

(k) Lighting that is for sale or lighting educational demonstration systems,

(l) Lighting for theatrical purposes, including performance, stage, and film or video production, and

(m) Athletic playing areas with permanent facilities for television broadcasting.

6.3.2 Building Area Method

Determination of interior lighting power allowance (watts) by the building area method shall be in

accordance with the following:

Determine the allowed lighting power density for each appropriate building area type from Table 6.1 for

ECBC buildings, from Table 6.2, for EE buildings and from

Page 51: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

Energy Conservation Building Code 2016 41

(a) Table 6.3 for Super EE buildings.

(b) Calculate the gross lighted floor area for each building area type.

(c) The interior lighting power allowance is the sum of the products of the gross lighted floor area of

each building area times the allowed lighting power density for that building area types.

Page 52: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

Table 6.1 Interior Lighting Power for ECBC Buildings – Building Area Method

Table 6.2 Interior Lighting Power for EE Buildings – Building Area Method

Building Area Type LPD (W/m2) Building Area Type LPD (W/m2)

Office Building 9.5 Motion picture theater 9.43

Hospitals 9.7 Museum 10.2

Hotels 9.5 Post office 10.5

Shopping Mall 14.1 Religious building 12

University and Schools 11.2 Sports arena 9.7

Library 12.2 Transportation 9.2

Dining: bar lounge/leisure 12.2 Warehouse 7.08

Dining: cafeteria/fast food 11.5 Performing arts theater 16.3

Dining: family 10.9 Police station 9.9

Dormitory 9.1 Workshop 14.1

Fire station 9.7 Automotive facility 9

Gymnasium 10 Convention center 12.5

Manufacturing facility 12 Parking garage 3

In cases where both a general building area type and a specific building area type are listed, the specific building

area type shall apply.

Building Area Type LPD (W/m2) Building Area Type LPD (W/m2)

Office Building 7.6 Motion picture theater 7.5

Hospitals 7.8 Museum 8.2

Hotels 7.6 Post office 8.4

Shopping Mall 11.3 Religious building 9.6

University and Schools 9.0 Sports arena 7.8

Library 9.8 Transportation 7.4

Dining: bar lounge/leisure 9.8 Warehouse 5.7

Dining: cafeteria/fast food 9.2 Performing arts theater 13.0

Dining: family 8.7 Police station 7.9

Dormitory 7.3 Workshop 11.3

Fire station 7.8 Automotive facility 7.2

Gymnasium 8.0 Convention center 10.0

Manufacturing facility 9.6 Parking garage 2.4

In cases where both a general building area type and a specific building area type are listed, the specific building

area type shall apply.

Page 53: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

Energy Conservation Building Code 2016 43

Table 6.3 Interior Lighting Power for Super EE Buildings – Building Area Method

6.3.3 Space Function Method

Determination of interior lighting power allowance (watts) by the space function method shall be in

accordance with the following:

(a) Determine the appropriate building type and the allowed lighting power density from Table 6.4

for ECBC buildings, Table 6.5 for EE buildings and, Table 6.6 for Super EE buildings.

(b) For each space enclosed by partitions 80% or greater than ceiling height, determine the gross

interior floor area by measuring to the center of the partition wall. Include the floor area of

balconies or other projections. Retail spaces do not have to comply with the 80% partition height

requirements.

(c) The interior lighting power allowance is the sum of the lighting power allowances for all spaces.

The lighting power allowance for a space is the product of the gross lighted floor area of the

space times the allowed lighting power density for that space.

Building Area Type LPD (W/m2) Building Area Type LPD (W/m2)

Office Building 5.0 Motion picture theater 4.7

Hospitals 4.9 Museum 5.1

Hotels 4.8 Post office 5.3

Shopping Mall 7.0 Religious building 6.0

University and Schools 6.0 Sports arena 4.9

Library 6.1 Transportation 4.6

Dining: bar lounge/leisure 6.1 Warehouse 3.5

Dining: cafeteria/fast food 5.8 Performing arts theater 8.2

Dining: family 5.5 Police station 5.0

Dormitory 4.6 Workshop 7.1

Fire station 4.9 Automotive facility 4.5

Gymnasium 5.0 Convention center 6.3

Manufacturing facility 6.0 Parking garage 1.5

In cases where both a general building area type and a specific building area type are listed, the specific building

area type shall apply.

Page 54: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

Table 6.4 Interior Lighting Power for ECBC Buildings – Space Function Method

Lamp category LPD (W/m2) Lamp category LPD (W/m2)

Office Spaces

Enclosed 10.0 Restrooms 7.7

Open Plan 10.0 Stairway 5.5

Banking Activity Area 12.6 Storage 6.8

Conference/ Meeting 11.5 Electrical/Mechanical 7.1

For Elevator 9.1 Workshop 17.1

Corridor/Transition 7.1 Service/Repair 6.8

Hospital Spaces

Emergency 22.8 Recovery 8.6

Exam/Treatment 13.7 Storage 5.5

Nurses’ Station 9.4 Laundry/Washing 7.5

Operating Room 21.8 Lounge/Recreation 8.0

Patient Room 7.7 Medical Supply 13.7

Pharmacy 10.7 Nursery 5.7

Physical Therapy 9.7 Corridor/Transition 9.1

Radiology/Imaging 9.1

Hotel

Hotel Dining 9.1 Hotel Lobby 10.9

For Bar Lounge/ Dining 14.1 Motel Dining 9.1

For food preparation 12.1 Motel Guest Rooms 7.7

Hotel Guest Rooms 9.1

Shopping Mall

Mall Concourse 12.8 For Family Dining 10.9

Sales Area 18.3 For food preparation 12.1

Motion Picture Theater 9.6 Elevator / lobby 9.1

Bar Lounge/ Dining 14.1 Electrical/Mechanical 7.1

School/ University

Classroom/Lecture 13.7 Card File and Cataloging 9.1

For Classrooms 13.8 Stacks (Lib) 18.3

Laboratory 15.1 Corridor/Transition 4.6

Reading Area (Lib) 10.0 Electrical/Mechanical 7.1

Page 55: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

Energy Conservation Building Code 2016 45

Table 6.5 Interior Lighting Power for EE Buildings – Space Function Method

Lamp category LPD (W/m2) Lamp category LPD (W/m2)

Office Spaces

Enclosed 8.6 Restrooms 6.1

Open Plan 8.6 Stairway 4.4

Banking Activity Area 9.3 Storage 5.4

Conference/ Meeting 9.2 Electrical/Mechanical 5.7

For Elevator 7.3 Workshop 13.7

Corridor/Transition 3.6 Service/Repair 5.5

Hospital Spaces

Emergency 18.2 Recovery 7.0

Exam/Treatment 10.9 Storage 4.4

Nurses’ Station 7.5 Laundry/Washing 6.0

Operating Room 17.5 Lounge/Recreation 6.4

Patient Room 6.1 Medical Supply 10.9

Pharmacy 8.5 Nursery 4.6

Physical Therapy 7.8 Corridor/Transition 7.3

Radiology/Imaging 7.3

Hotel

Hotel Dining 7.3 Hotel Lobby 8.8

For Bar Lounge/ Dining 11.3 Motel Dining 7.3

For food preparation 12.1 Motel Guest Rooms 6.1

Hotel Guest Rooms 7.3

Shopping Mall

Mall Concourse 10.2 For Family Dining 8.8

Sales Area 14.6 For food preparation 12.1

Motion Picture Theater 10.3 Elevator / lobby 7.3

Bar Lounge/ Dining 11.3 Electrical/Mechanical 5.7

School/ University

Classroom/Lecture 10.9 Card File and Cataloging 7.3

For Classrooms 11.0 Stacks (Lib) 14.6

Laboratory 12.1 Corridor/Transition 3.6

Reading Area (Lib) 9.2 Electrical/Mechanical 5.7

Page 56: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

Table 6.6 Interior Lighting Power for Super EE Buildings – Space Function Method

Lamp category LPD (W/m2) Lamp category LPD (W/m2)

Office Spaces

Enclosed 5.4 Restrooms 3.8

Open Plan 5.4 Stairway 2.7

Banking Activity Area 5.8 Storage 3.4

Conference/ Meeting 5.7 Electrical/Mechanical 3.5

For Elevator 4.6 Workshop 8.6

Corridor/Transition 2.3 Service/Repair 3.4

Hospital Spaces

Emergency 11.4 Recovery 4.4

Exam/Treatment 6.8 Storage 2.7

Nurses’ Station 5.0 Laundry/Washing 3.8

Operating Room 10.9 Lounge/Recreation 4.6

Patient Room 3.8 Medical Supply 6.8

Pharmacy 5.3 Nursery 2.9

Physical Therapy 4.9 Corridor/Transition 4.6

Radiology/Imaging 4.6

Hotel

Hotel Dining 4.6 Hotel Lobby 5.5

For Bar Lounge/ Dining 7.0 Motel Dining 4.6

For food preparation 7.5 Motel Guest Rooms 3.8

Hotel Guest Rooms 4.6

Shopping Mall

Mall Concourse 6.4 For Family Dining 5.5

Sales Area 9.2 For food preparation 7.5

Motion Picture Theater 6.5 Elevator / lobby 4.6

Bar Lounge/ Dining 7.0 Electrical/Mechanical 3.5

School/ University

Classroom/Lecture 6.8 Card File and Cataloging 4.6

For Classrooms 6.9 Stacks (Lib) 9.2

Laboratory 7.5 Corridor/Transition 2.3

Reading Area (Lib) 5.7 Electrical/Mechanical 3.5

Page 57: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

Energy Conservation Building Code 2016 47

Box 6.1 Calculating Interior Lighting Power – Space Function Method

Box 6.1 Calculating Interior Lighting Power – Space Function Method

A four story building has retail on the ground floor and offices on the top three floors. Area is 3600

square meters. Space types and their respective areas are mentioned below. What will be the

interior lighting power allowance a ECBC building? Use the space function method.

Space Function Area (square feet) Space Function Area (square feet)

Office Retail

Office - enclosed 5,750 General

sales area

7,200

Office – open plan 16,000 Offices -

enclosed

200

Meeting Rooms 1,000 Restrooms 50

Lobbies 1,000 Corridors 100

Restrooms 400 Active

Storage

1,450

Corridors 1,350

Dining Area 300

Food preparation 150

Electrical/ Mechanical 150

Staircase 900

Answer:

Areas are mentioned in IP units (square feet). For each of the space type, look up the corresponding

Lighting Power Density (LPD) values from Table 6.4 in Energy Conservation Building Code 2016.

These are listed in the table below. Multiply the area with the LPD values. So these will have to be

first converted in to SI units (meter). Add the lighting power allowance for each space type to

estimate the lighting power allowance for the whole building. It is 45,655 W. Space Function LPD (W/ m²) Area (m²) Lighting Power Allowance

(W)

Office

Office - enclosed 11.8 575 6785

Office – open plan 11.8 1600 18880

Meeting Rooms 14 100 1400

Lobbies 14 100 1400

Restrooms 9.7 40 388

Corridors 5.4 135 729

Dining Area 9.7 30 291

Food preparation 12.9 15 193.5

Electrical/

Mechanical

16.1 15 241.5

Staircase 6.5 90 585

Total 30893 W

Retail

General sales area 18.3 720 13176

Offices - enclosed 11.8 20 236

Restrooms 9.7 5 48.5

Corridors 5.4 10 54

Active Storage 8.6 145 1247

Total 14762

Building Total 45655 W

Page 58: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

6.3.4 Installed Interior Lighting Power

The installed interior lighting power calculated for compliance with § 6.3 shall include all power used by

the luminaires, including lamps, ballasts, current regulators, and control devices except as specifically

exempted in § 6.1.

Exception to § 6.3.4: If two or more independently operating lighting systems in a space are controlled

to prevent simultaneous user operation, the installed interior lighting power shall be based solely on the

lighting system with the highest power.

6.3.4.1 Luminaire Wattage

Luminaire efficacy shall be above 0.7 or above. Luminaire wattage incorporated into the installed interior

lighting power shall be determined in accordance with the following:

(a) The wattage of incandescent luminaires with medium base sockets and not containing

permanently installed ballasts shall be the maximum labeled wattage of the luminaires.

(b) The wattage of luminaires containing permanently installed ballasts shall be the operating input

wattage of the specified lamp/ballast combination. Operating input wattage can be either values

from manufacturers’ catalogs or values from independent testing laboratory reports.

(c) The wattage of all other miscellaneous luminaire types not described in (a) or (b) shall be the

specified wattage of the luminaires.

(d) The wattage of lighting track, plug-in busway, and flexible-lighting systems that allow the

addition and/or relocation of luminaires without altering the wiring of the system shall be the

larger of the specified wattage of the luminaires included in the system or 135 W/m (45 W/ft.).

Systems with integral overload protection, such as fuses or circuit breakers, shall be rated at

100% of the maximum rated load of the limiting device.

6.3.5 Exterior Lighting Power

Connected lighting power of exterior lighting applications shall not exceed the lighting power limits

specified in Table 6.7 for ECBC buildings, Table 6.8 for EE buildings and Table 6.9 for Super EE Buildings.

Trade-offs between applications are not permitted. Exterior lighting for all applications not listed in Table

6.7 through Table 6.9 (except those included in the Exceptions to § 6.3.4) shall comply with the

requirements of § 6.2.3.

Table 6.7 Exterior Building Lighting Power for ECBC Buildings

Exterior lighting application Power limits

Building entrance (with canopy) 10 W/m2 of canopied area

Building entrance (w/o canopy) 90 W/ linear m of door width

Building exit 60 W/lin m of door width

Building façade 5 W/m2 of vertical façade area

Emergency signs, ATM kiosks, Security areas façade 1 W/m2

Parking areas (covered/ basement) 2.2 W/m2

Driveways (covered/ basement) 3 W/m2

Driveways and parking (open/ external) 1.6 W/m2

Pedestrian walkways 2.0 W/m2

Stairways 10.0 W/m2

Landscaping 0.5 W/m2

Outdoor sales area 9.0 W/m2

Page 59: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Lighting and Controls

Energy Conservation Building Code 2016 49

Table 6.8 Exterior Building Lighting Power for EE Buildings

Table 6.9 Exterior Building Lighting Power for Super EE Buildings

Exterior lighting application Power limits

Building entrance (with canopy) 5 W/m2 of canopied area

Building entrance (w/o canopy) 45 W/ linear m of door width

Building exit 30 W/lin m of door width

Building façade 2.5 W/m2 of vertical façade area

Emergency signs, ATM kiosks, Security areas façade .5 W/m2

Parking areas (covered/ basement) 1.1 W/m2

Driveways (covered/ basement) 1.5 W/m2

Driveways and parking (open/ external) .8 W/m2

Pedestrian walkways 1 W/m2

Stairways 5 W/m2

Landscaping 0.25 W/m2

Outdoor sales area 4.5 W/m2

Exterior lighting application Power limits

Building entrance (with canopy) 8 W/m2 of canopied area

Building entrance (w/o canopy) 72 W/ linear m of door width

Building exit 48 W/lin m of door width

Building façade 4 W/m2 of vertical façade area

Emergency signs, ATM kiosks, Security areas façade .8 W/m2

Parking areas (covered/ basement) 1.75 W/m2

Driveways (covered/ basement) 2.5 W/m2

Driveways and parking (open/ external) 1.3 W/m2

Pedestrian walkways 1.6 W/m2

Stairways 8 W/m2

Landscaping 0.4 W/m2

Outdoor sales area 7.2 W/m2

Page 60: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Electrical and Renewable Systems

7. Electrical and Renewable Systems

7.1 General

All electric and renewable energy equipment and systems shall comply with the mandatory requirements

of § 7.2.

7.2 Mandatory Requirements

7.2.1 Transformers

7.2.1.1 Maximum Allowable Power Transformer Losses

Power transformers of the proper ratings and design must be selected to satisfy the minimum acceptable

efficiency at 50% and full load rating.

Permissible total loss values shall not exceed

(a) 5% of the maximum total loss values mentioned in IS 1180 for oil type transformers in voltage

class above 11 kV but not more than 22 kV

(b) 7½ percent of the maximum total loss values mentioned in above IS 1180 for oil type

transformers in voltage class above 22 kV and up to and including 33 kV

(c) values listed in Table 7.1 for dry type transformers

In addition, the transformer must be selected such that it minimizes the total of its initial cost in addition

to the present value of the cost of its total lost energy while serving its estimated loads during its

respective life span.

Table 7.1Dry Type Transformers (to be updated as per the latest standard)

Rating

(kVA)

Impedance

(percent)

Max. Total Loss (W)

ECBC 2015 EE Building SUPER EE Building

50 %

Load

100%

Load

50 %

Load

100%

Load

50 %

Load

100%

Load

16 4.5 150 480 135 440 120 400

25 4.5 210 695 190 635 175 595

63 4.5 380 1250 340 1140 300 1050

100 4.5 520 1800 475 1650 435 1500

160 4.5 770 2200 670 1950 570 1700

200 4.5 890 2700 780 2300 670 2100

250 4.5 1050 3150 980 2930 920 2700

315 4.5 1100 3275 1025 3100 955 2750

400 4.5 1300 3875 1225 3450 1150 3330

500 4.5 1600 4750 1510 4300 1430 4100

630 4.5 2000 5855 1860 5300 1745 4850

1000 5 3000 9000 2790 7700 2620 7000

1250 5 3600 10750 3300 9200 3220 8400

1600 6.25 4500 13500 4200 11800 3970 11300

2000 6.25 5400 17000 5050 15000 4790 14100

Page 61: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Electrical and Renewable Systems

Energy Conservation Building Code 2016 51

Table 7.2 Permissible Losses for Oil Type Transformers. Total losses for oil type transformers should confirm

with Indian Standard IS 1180. (to be updated as per the latest standard)

Rating

(kVA)

Impedance

(percent)

Max. Total Loss (W)

ECBC 2015 EE Building SUPER EE Building

50 %

Load

100% Load 50 %

Load

100% Load 50 %

Load

100% Load

16 4.5 150 480 135 440 120 400

25 4.5 210 695 190 635 175 595

63 4.5 380 1250 340 1140 300 1050

100 4.5 520 1800 475 1650 435 1500

160 4.5 770 2200 670 1950 570 1700

200 4.5 890 2700 780 2300 670 2100

250 4.5 1050 3150 980 2930 920 2700

315 4.5 1100 3275 1025 3100 955 2750

400 4.5 1300 3875 1225 3450 1150 3330

500 4.5 1600 4750 1510 4300 1430 4100

630 4.5 2000 5855 1860 5300 1745 4850

1000 5 3000 9000 2790 7700 2620 7000

1250 5 3600 10750 3300 9200 3220 8400

1600 6.25 4500 13500 4200 11800 3970 11300

2000 6.25 5400 17000 5050 15000 4790 14100

2500 6.25 6500 20000 6150 18500 5900 17500

Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS 1180 i.e., average winding temperature rise as given in Column 2 of Table 8.2 plus 300C. An increase of 7% on total for thermal class H is allowed.

7.2.1.2 Measurement and Reporting of Transformer Losses

All measurement of losses shall be carried out by using calibrated digital meters of class 0.5 or better

accuracy and certified by the manufacturer. All transformers of capacity of 500 kVA and above would be

equipped with additional metering class current transformers (CTs) and potential transformers (PTs)

additional to requirements of Utilities so that periodic loss monitoring study may be carried out.

7.2.1.3 Voltage Drop

Voltage drop for feeders shall not exceed 2% at design load. Voltage drop for branch circuit shall not

exceed 3% at design load.

7.2.2 Energy Efficient Motors

Motors shall also comply with the following:

(a) Three phase induction motors shall conform to Indian Standard (IS) 12615 and shall fulfill the

following efficiency requirements:

2500 6.25 6500 20000 6150 18500 5900 17500

Total loss values given in above table are applicable for thermal classes E, B and F and have component of load loss at reference temperature according to Clause 17 of IS 1180 i.e., average winding temperature rise as given in Column 2 of Table 8.2 plus 300C. An increase of 7% on total for thermal class H is allowed.

Page 62: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Electrical and Renewable Systems

i. ECBC buildings shall have motors of IE 2 (high efficiency) class or a higher class

ii. EE buildings shall have IE 3 (premium efficiency) class motors or higher class

iii. Super EE buildings shall have IE 4 (super premium efficiency) class motors

(b) All permanently wired polyphase motors of 0.375 kW or more serving the building and all

permanently wired polyphase motors of 50kW or more serving the building shall have a minimum

acceptable nominal full load motor efficiency not less than levels specified in the latest version of

IS 12615.

(c) Motors of horsepower differing from those listed in the table shall have efficiency greater than

that of the next listed kW motor.

(d) Motor horsepower ratings shall not exceed 20% of the calculated maximum load being served.

(e) Motor nameplates shall list the nominal full-load motor efficiencies and the full-load power factor.

(f) Motor users should insist on proper rewinding practices for any rewound motors. If the proper

rewinding practices cannot be assured, the damaged motor should be replaced with a new,

efficient one rather than suffer the significant efficiency penalty associated with typical rewind

practices. Rewinding practices from BEE guideline for energy efficient motors shall be followed.

(g) Certificates shall be obtained and kept on record indicating the motor efficiency. Whenever a

motor is rewound, appropriate measures shall be taken so that the core characteristics of the

motor is not lost due to thermal and mechanical stress during removal of damaged parts. After

rewinding, a new efficiency test shall be performed and a similar record shall be maintained.

7.2.3 DG Sets

BEE star rated DG sets shall be used in all compliant buildings. DG sets in buildings greater than 20,000

m2 shall have:

(a) minimum 3 star rating in ECBC buildings

(b) minimum 4 star rating in EE buildings

(c) minimum 5 star rating in Super EE buildings

7.2.4 Power Factor Correction

All electricity supplies exceeding 100 A, 3 phase shall maintain their power factor at the point of

connection as follows:

(a) .97 for ECBC building

(b) .98 for EE building

(c) .99 for Super EE building

7.2.5 Check-Metering and Monitoring

(a) Services exceeding 1000 kVA shall have permanently installed electrical metering to record

demand (kVA), energy (kWh), and total power factor. The metering shall also display current (in

each phase and the neutral), voltage (between phases and between each phase and neutral),

and total harmonic distortion (THD) as a percentage of total current.

(b) Services not exceeding 1000 kVA but over 65 kVA shall have permanently installed electric

metering to record demand (kW), energy (kWh), and total power factor (or kVARh).

(c) Services not exceeding 65 kVA shall have permanently installed electrical metering to record

energy (kWh).

Page 63: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Electrical and Renewable Systems

Energy Conservation Building Code 2016 53

Table 7.3 Sub Metering Requirements

7.2.6 Power Distribution Systems

The power cabling shall be sized so that the distribution losses do not exceed

(a) 3% of the total power usage in ECBC Buildings

(b) 2% of the total power usage in EE buildings

(c) 1.5% of total power usage in Super EE buildings

Record of design calculation for the losses shall be maintained. Load calculation shall be calculated up to

the panel level.

7.2.7 Uninterruptible Power Supply (UPS)

UPS equipment shall be installed in buildings with area greater than 10,000 m2. UPS shall meet or exceed

the energy efficiency requirements listed in Table 7.4. Any standard and labeling program by BEE shall

take precedence over requirements listed in this section.

Table 7.4 Energy Efficiency Requirements for UPS

7.2.8 Renewable Energy Systems

All buildings shall

have provisions for

installation of

renewable energy systems in the future on rooftops or the site.

7.2.8.1 Solar Zone

A dedicated solar zone equivalent to at least 10% of roof area or area required for generation of energy

equivalent to 1% of total peak demand or connected load of the building, whichever is less, shall be

provided in all buildings.

120 kVA to 250 kVA 250 kVA to 600 kVA More than 600 kVA

Minimum requirement for metering of electrical load

Energy kWh Required Required Required

Demand kVA Required Required Required

Total power factor Required Required Required

Minimum requirement for separation of Electrical Load

HVAC system and components Required Required Required

Lighting (interior and exterior)* Not required Required Required

Domestic hot water Not required Required Required

Plug loads Not required Required Required

Renewable power source Required Required Required

Mandatory requirement for building type over the requirement stated above

Commercial mall/ retail Façade lighting Elevator, escalators, moving walks

Offices Data centers

Hotels Commercial kitchens

In case of tenant based building, metering should be provided as per the above requirement at a location from where

each tenant could attach the services.

* Hotel guestrooms and hospital in patient areas are exempted from the lighting sub-metering requirements.

UPS Size Energy Efficiency Requirements on 100% Load

kVA< 20 90.2%

20<=kVA <= 100 91.9%

kVA > 100 93.8%

Page 64: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Electrical and Renewable Systems

The solar zone shall be free of any obstructions within its boundaries and from shadows cast by objects

adjacent to the zone.

EE and Super EE buildings shall fulfill the additional requirements listed in Table 7.5.

Exception to § 7.2.8.1: Projects with solar hot water and/ or solar power generation systems.

Table 7.5 Minimum Solar Zone Area Requirements for EE Buildings

Building Type Minimum Electricity to be Generated in Solar Zone

All Buildings Minimum 2% of total electricity demand

Hotels/ motels > 25,000 m²

Resorts > 12,500 m2

Universities > 30,000 m²

IT parks and offices >30,000 m²

Minimum 3% of total electricity demand

Table 7.6 Minimum Solar Zone Area Requirements for Super EE Buildings

Building Type Minimum Electricity to be Generated in Solar Zone

All Buildings Minimum 4% of total electricity demand

Hotels/ motels > 25,000 m² Resorts > 12,500 m2

Universities > 30,000 m² IT parks and offices >30,000 m²

Minimum 6% of total electricity demand

7.2.8.2 Main Electrical Service Panel

Minimum rating shall be displayed on the main electrical service panel. Space shall be reserved for the

installation of a double pole circuit breaker for a future solar electric installation.

7.2.8.3 Demarcation on Documents

The following shall be indicated in design and construction documents:

(a) Location for inverters and metering equipment,

(b) Pathway for routing of conduit from the solar zone to the point of interconnection with the

electrical service,

(c) Routing of plumbing from the solar zone to the water-heating system and,

Structural design loads for roof dead and live load

Page 65: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Energy Conservation Building Code 2016 55

8. Appendix A: Definitions, Abbreviations and Acronyms

8.1 General

Certain terms, abbreviations, and acronyms are defined in this section for the purposes of this code.

These definitions are applicable to all sections of this code. Terms that are not defined shall have their

ordinarily accepted meanings within the context in which they are used. Webster's Third New

International Dictionary of the English Language, Unabridged, copyright 1986, shall be considered as

providing ordinarily accepted meanings.

8.2 Definitions

Addition: an extension or increase in floor area or height of a building outside of the existing building

envelope

Alteration: any change, rearrangement, replacement, or addition to a building or its systems and

equipment; any modification in construction or building equipment

Annual fuel utilization efficiency (AFUE): an efficiency description of the ratio of annual output

energy to annual input energy as developed in accordance with requirements of U.S. Department of

Energy (DOE) 10CFR Part 430

Area: See roof and wall, conditioned floor, day lit, façade, fenestration, lighted floor

Astronomical time switch: an automatic time switch that makes an adjustment for the length of the

day as it varies over the year

Authority having jurisdiction: the agency or agent responsible for enforcing this standard

Automatic: self-acting, operating by its own mechanism when actuated by some non-manual influence,

such as a change in current strength, pressure, temperature, or mechanical configuration.

Automatic control device: a device capable of automatically turning loads off and on without manual

intervention

Balancing, air system: adjusting airflow rates through air distribution system devices, such as fans and

diffusers, by manually adjusting the position of dampers, splitters vanes, extractors, etc., or by using

automatic control devices, such as constant air volume or variable air volume boxes

Balancing, hydronic system: adjusting water flow rates through hydronic distribution system devices,

such as pumps and coils, by manually adjusting the position valves, or by using automatic control

devices, such as automatic flow control valves

Ballast: a device used in conjunction with an electric-discharge lamp to cause the lamp to start and

operate under proper circuit conations of voltage, current, waveform, electrode heat, etc.

Boiler: a self-contained low-pressure appliance for supplying steam or hot water

Boiler, packaged a boiler that is shipped complete with heating equipment, mechanical draft

equipment, and automatic controls; usually shipped in one or more sections. A packaged boiler includes

factory-built boilers manufactured as a unit or system, disassembled for shipment, and reassembled at

the site.

Building: a structure wholly or partially enclosed within exterior walls, or within exterior and party walls,

and a roof, affording shelter to persons, animals, or property.

Building, base: includes building structure, building envelope, common areas, circulation areas,

parking, basements, services area, plant room and its supporting areas and, open project site area.

Page 66: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Building, core and shell: buildings where the developer or owner will only provide the base building

and its services.

Building, existing: a building or portion thereof that was previously occupied or approved for

occupancy by the authority having jurisdiction

Building complex: a group of buildings in a contiguous area under single ownership

Building entrance: any doorway, set of doors, turnstiles, or other form of portal that is ordinarily used

to gain access to the building by its users and occupants

Building envelope: the exterior plus the semi-exterior portions of a building. For the purposes of

determining building envelope requirements, the classifications are defined as follows:

(a) Building envelope, exterior: the elements of a building that separate conditioned spaces from the

exterior

(b) Building envelope, semi-exterior: the elements of a building that separate conditioned space

from unconditioned space or that enclose semi-heated spaces through which thermal energy

may be transferred to or from the exterior, or to or from unconditioned spaces, or to or from conditioned spaces

Building exit: any doorway, set of doors, or other form of portal that is ordinarily used only for

emergency egress or convenience exit

Building grounds lighting: lighting provided through a building’s electrical service for parking lot, site,

roadway, pedestrian pathway, loading dock, and security applications

Building material: any element of the building envelope through which heat flows and that heat is

included in the component U-factor calculations other than air films and insulation

Circuit breaker: a device designed t open and close a circuit by nonautomatic means and to open the

circuit automatically at a predetermined over-current without damage to itself when properly applied

within its rating

Class of construction: for the building envelope, a subcategory of roof, wall, floor, slab-on-grade floor,

opaque door, vertical fenestration, or skylight

Coefficient of Performance (COP) – cooling: the ratio of the rate of heat removal to the rate of

energy input, in consistent units, for a complete refrigerating system or some specific portion of that

system under designated operating conditions

Coefficient of Performance (COP) – heating: the ratio of the rate of heat delivered to the rate of

energy input, in consistent units, for a complete heat pump system, including the compressor and, if

applicable, auxiliary heat, under designated operating conditions

Commercial building: all buildings except for multi-family buildings of three stories or fewer above

grade and single-family buildings

Construction documents: drawings and specifications used to construct a building, building systems,

or portions thereof

Control: to regulate the operation of equipment

Control device: a specialized device used to regulate the operation of equipment

Cool roof: a property of a surface that describes its ability to reflect and reject heat. Cool roof surfaces

have both a light color (high solar reflectance) and a high emittance (can reject heat back to the

environment)

Page 67: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Energy Conservation Building Code 2016 57

Daylight area: the daylight illuminated floor area under horizontal fenestration (skylight) or adjacent to

vertical fenestration (window), described as follows

(a) Horizontal Fenestration: the area under a skylight, monitor, or sawtooth configuration with an effective aperture greater than 0.001 (0.1%). The daylight area is calculated as the horizontal

dimension in each direction equal to the top aperture dimension in that direction plus either the

floor-to-ceiling height (H) for skylights, or 1.5 H for monitors, or H or 2H for the sawtooth configuration, or the distance to the nearest 1000 mm or higher opaque partition, or one-half the

distance to an adjacent skylight or vertical glazing, whichever is least, as shown in the plan and section figures below.

(b) Vertical Fenestration: the floor area adjacent to side apertures (vertical fenestration in walls)

with an effective aperture greater than 0.06 (6%). The daylight area extends into the space perpendicular to the side aperture a distance equal to daylight extension factor (DEF) multiplied

by the head height of the side aperture or to the nearest 1.35 m or higher opaque partition,

whichever is less. In the direction parallel to the window, the daylight area extends a horizontal dimension equal to the width of the window plus either 1 m on each side of the aperture, the

distance to an opaque partition, or one-half the distance to an adjacent skylight or window, whichever is least.

Ceiling height

opaque partition

Plan

Skylight H

H

Daylight Area

Section

H H H Daylight Area

Skylight

2H H Daylight Area

Sawtooth

1.5H 1.5H H

Daylight Area

Monitor

Page 68: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Daylight Extension Factor (DEF): A factor to compute the daylight area manually. It is to be

multiplied by the head height of windows.

Dead band: the range of values within which a sensed variable can vary without initiating a change in

the controlled process

Demand: the highest amount of power (average kW over an interval) recorded for a building or facility

in a selected time frame

Design capacity: output capacity of a system or piece of equipment at design conditions

Design conditions: specified environmental conditions, such as temperature and light intensity,

required to be produced and maintained by a system and under which the system must operate

Distribution system: a device or group of devices or other means by which the conductors of a circuit

can be disconnected from their source of supply

Door: all operable opening areas (which are not fenestration) in the building envelope, including

swinging and roll-up doors, fire doors, and access hatches. Doors that are more than one-half glass are

considered fenestration. For the purposes of determining building envelope requirements, the

classifications are defined as follows:

(a) Door, non-swinging: roll-up sliding, and all other doors that are not swinging doors.

(b) Door, swinging: all operable opaque panels with hinges on one side and opaque revolving doors.

Door area: total area of the door measured using the rough opening and including the door slab and

the frame.

Dwelling unit: a single unit providing complete independent living facilities for one or more persons,

including permanent provisions for living, sleeping, eating, coking, and sanitation

Economizer, air: a duct and damper arrangement and automatic control system that together allow a

cooling system to supply outdoor air to reduce or eliminate the need for mechanical cooling during mild

or cold weather

Economizer, water: a system by which the supply air of a cooling system is cooled indirectly with

water that is itself cooled by heat or mass transfer to the environment without the use of mechanical

cooling

EE Building: ECBC compliant building with efficiency greater than that of ECBC buildings but less than

that of Super EE buildings. It is a voluntary level of compliance.

Effective aperture: Visible Light Transmittance x window-to-wall Ratio. (EA = VLT x WWR)

1 m

1 m, or to nearest

opaque partition

Luminaries in

Daylight Area

Page 69: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Energy Conservation Building Code 2016 59

Effective aperture, horizontal fenestration: a measure of the amount of daylight that enters a

space through horizontal fenestration (skylights). It is the ratio of the skylight area times the visible light

transmission divided by the gross roof area above the daylight area. See also daylight area.

Effective aperture, vertical fenestration: a measure of the amount of daylight that enters a space

through vertical fenestration. It is the ratio of the daylight window area times its visible light transmission

plus half the vision glass area times its visible light transmission and the sum is divided by the gross wall

area. Daylight window area is located 2.2 m or more above the floor and vision window area is located

above 1 m but below 2.2 m. The window area, for the purposes of determining effective aperture shall

not include windows located in light wells when the angle of obstruction () of objects obscuring the sky

dome is greater than 70o, measured from the horizontal, nor shall it include window area located below a

height of 1 m. See also daylight area.

Efficacy: the lumens produced by a lamp/ballast system divided by the total watts of input power

(including the ballast), expressed in lumens per watt

Efficiency: performance at a specified rating condition

Efficiency, thermal: ratio of work output to heat input

Efficiency, combustion: efficiency with which fuel is burned during the combustion process in

equipment

Remittance: the ratio of the radiant heat flux emitted by a specimen to that emitted by a blackbody at

the same temperature and under the same conditions

Enclosed building: a building that is totally enclosed by walls, floors, roofs, and openable devices such

as doors and operable windows

Energy: the capacity for doing work. It takes a number of forms that may be transformed from one into

another such as thermal (heat), mechanical (work), electrical, and chemical. Customary measurements

are watts (W)

Energy Efficiency Ratio (EER): the ratio of net cooling capacity in kW to total rate of electric input in

watts under designated operating conditions

Energy Factor (EF): a measure of water heater overall efficiency

Envelope performance factor: the trade-off value for the building envelope performance compliance

option calculated using the procedures specified in Appendix D. For the purposes of determining building

envelope requirements the classifications are defined as follows:

(a) Base envelope performance factor: the building envelope performance factor for the base design

(b) Proposed envelope performance factor: the building envelope performance factor for the proposed design

Obstruction Angle

Page 70: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Equipment: devices for comfort conditioning, electric power, lighting, transportation, or service water

heating including, but not limited to, furnaces, boilers, air conditioners, heat pumps, chillers, water

heaters, lamps, luminaires, ballasts, elevators, escalators, or other devices or installations

Equipment, existing: equipment previously installed in an existing building

Facade area: area of the façade, including overhanging soffits, cornices, and protruding columns,

measured in elevation in a vertical plane, parallel to the plane of the face of the building. Nonhorizontal

roof surfaces shall be included in the calculations of vertical façade area by measuring the area in a plane

parallel to the surface.

Fan system power: the sum of the nominal power demand (nameplate W or HP) of motors of all fans

that are required to operate at design conditions to supply air from the heating or cooling source to the

conditioned space(s) and return it to the source of exhaust it to the outdoors.

Fenestration: all areas (including the frames) in the building envelope that let in light, including

windows, plastic panels, clerestories, skylights, glass doors that are more than one-half glass, and glass

block walls.

(a) Skylight: a fenestration surface having a slope of less than 60 degrees from the horizontal plane.

Other fenestration, even if mounted on the roof of a building, is considered vertical fenestration.

(b) Vertical fenestration: all fenestration other than skylights. Trombe wall assemblies, where glazing

is installed within 300 mm of a mass wall, are considered walls, not fenestration.

Fenestration area: total area of the fenestration measured using the rough opening and including the

glazing, sash, and frame. For doors where the glazed vision area is less than 50% of the door area, the

fenestration area is the glazed vision area. For all other doors, the fenestration area is the door area.

Floor area gross: the sum of the floor areas of the spaces within the building including basements,

mezzanine and intermediate-floored tiers, and penthouses with headroom height of 2.5 m or greater. It

is measured from the exterior faces of exterior walls or from the centerline of walls separating buildings,

but excluding covered walkways, open roofed-over areas, porches and similar spaces, pipe trenches,

exterior terraces or steps, chimneys, roof overhangs, and similar features.

(a) Gross building envelope floor area: the gross floor area of the building envelope, but excluding

slab-on-grade floors.

(b) gross conditioned floor area: the gross floor area of conditioned spaces

(c) Gross lighted floor area: the gross floor area of lighted spaces.

(d) Gross semiheated floor area: the gross floor area of semiheated spaces.

Flue damper: a device in the flue outlet or in the inlet of or upstream of the draft control device of an

individual, automatically operated, fossil fuel-fired appliance that is designed to automatically open the

flue outlet during appliance operation and to automatically close the flue outlet when then appliance is in

standby condition.

Fossil fuel: fuel derived from a hydrocarbon deposit such as petroleum, coal, or natural gas derived

from living matter of a previous geologic time.

Fuel: a material that may be used to produce heat or generate power by combustion.

Generally accepted engineer standard: a specification, rule, guide, or procedure in the filed of

engineer, or related thereto, recognized and accepted as authoritative.

Grade: the finished ground level adjoining a building at all exterior walls.

Guest room: any room or rooms used or intended to be used by a guest for sleeping purposes.

Page 71: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Energy Conservation Building Code 2016 61

Heat capacity: the amount of heat necessary to raise the temperature of a given mass 1°C.

Numerically, the heat capacity per unit area of surface (W/m2-°C) is the sum of the products of the mass

per unit area of each individual material in the roof, wall, or floor surface multiplied by its individual

specific heat.

Heating Seasonal Performance Factor (HSPF): the total heating output of a heat pump during its

normal annual usage period for heating (in Btu) divided by the total electric energy input during the

same period.

Historic: a building or space that has been specifically designed as historically significant.

HVAC system: the equipment, distribution systems, and terminals that provide, either collectively or

individually, the processes of heating, ventilating, or air conditioned to a building or portion of a building.

Infiltration: the uncontrolled inward air leakage through cracks and crevices in any building element

and around windows and doors of a building caused by pressure differences across these elements due

to factors such as wind, inside and outside temperature differences (stack effect), and imbalance

between supply and exhaust air systems.

Installed interior lighting power; the power in watts of all permanently installed general, task, and

furniture lighting systems and luminaires.

Integrated part-load value (IPLV): a single number figure of merit based on part-load EER, COP, or

KW/ton expressing part-load efficiency for air-conditioning and heat pump equipment on the basis of

weighted operation at various load capacities for the equipment.

Kilovolt-ampere (kVA): where the term “kilovolt-ampere” (kVA) is used in this standard, it is the

product of the line current (amperes) times the nominal system voltage (kilovolts) times 1.732 for three-

phase currents. For single-phase applications, kVA is the product of the line current (amperes) times the

nominal system voltage (kilovolts).

Kilowatt (kW): the basic unit of electric power, equal to 1000 W.

Labeled: equipment or materials to which a symbol or other identifying mark has been attached by the

manufacturer indicating compliance with specified standard or performance in a specified manner.

Lamp: a generic term for man-made light source often called bulb or tube.

Lighted floor area, gross: the gross floor area of lighted spaces.

Lighting, decorative: lighting that is purely ornamental and installed for aesthetic effect. Decorative

lighting shall not include general lighting.

Lighting, emergency: lighting that provides illumination only when there is a general lighting failure.

Lighting, general: lighting that provides a substantially uniform level of illumination throughout an

area. General lighting shall not include decorative lighting or lighting that provides a dissimilar level of

illumination to serve a specialized application or feature within such area.

Luminous Efficacy (LE): the quotient of the total lumens emitted from a lamp or lamp/ballast

combination divided by the watts of input power, expressed in lumens per watt.

Lighting system: a group of luminaires circuited or controlled to perform a specific function.

Lighting power allowance:

(a) Interior lighting power allowance: the maximum lighting power in watts allowed for the interior of a building

(b) Exterior lighting power allowance: the maximum lighting power in watts allowed for the exterior

of a building

Page 72: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Lighting Power Density (LPD): the maximum lighting power per unit of area of a building

classification of space function.

Low-rise residential: single-family houses, multi-family structures of three stories or fewer above

grade, manufactured houses (mobile homes), and manufactured houses (modular).

Luminaires: a complete lighting unit consisting of a lamp or lamps together with the housing designed

to distribute the light, position and protect the lamps, and connect the lamps to the power supply.

Manual (non-automatic): requiring personal intervention for control. Non-automatic does not

necessarily imply a manual controller, only that personal intervention is necessary.

Manufacturer: the company engaged in the original production and assembly of products or equipment

or a company that purchases such products and equipment manufactured in accordance with company

specifications.

Mean temperature: one-half the sum of the minimum daily temperature and maximum daily

temperature.

Mechanical cooling: reducing the temperature of a gas or liquid by using vapor compression,

absorption, desiccant dehumidification combined with evaporative cooling, or another energy-driven

thermodynamic cycle. Indirect of direct evaporative cooling alone is not considered mechanical cooling.

Metering: instruments that measure electric voltage, current, power, etc.

Mixed mode building: Buildings that use mixed mode ventilation, i.e. natural ventilation is employed

as the primary mode of ventilating the building and, air conditioning is deployed as and when required.

Mixed use development: a single building or a group of buildings housing a combination of residential,

commercial, business, educational, hospitality and assembly uses

Multifamily high-rise: multifamily structures of four or more stories above grade

Multifamily low-rise: multifamily structures of three or less stories above grade

Naturally ventilated building: A building that does not use mechanical equipment to supply air to and

exhaust air from indoor spaces. It is primarily ventilated by drawing and expelling air through operable

openings in the building envelope.

Non-automatic: See manual.

Occupant sensor: a device that detects the presence or absence of people within an area and causes

lighting, equipment, or appliances to be regulated accordingly.

Opaque: all areas in the building envelope, except fenestration and building service openings such as

vents and grilles.

Orientation: the direction an envelope element faces, i.e., the direction of a vector perpendicular to and

pointing away from the surface outside of the element. For vertical fenestration, the two categories are

north-oriented and all other.

Outdoor (outside) air: air that is outside the building envelope or is taken from the outside the

building that has not been previously circulated through the building.

Overcurrent: any current in excess of the rated current of the equipment of the ampacity of the

conductor. It may result from overload, short circuit, or ground fault.

Packaged Terminal Air Conditioner (PTAC): a factory-selected wall sleeve and separate unencased

combination of heating and cooling components, assemblies, or sections. It may include heating

Page 73: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Energy Conservation Building Code 2016 63

capability by hot water, steam, or electricity, and is intended for mounting through the wall to service a

single room or zone.

Party wall: a firewall on an interior lot line used or adapted for joint service between two buildings.

Permanently installed: equipment that is fixed in place and is not portable or movable.

Plenum: a compartment or chamber to which one or more ducts are connected, that forms a part of the

air distribution system, and that is not used for occupancy or storage. A plenum often is formed in part

or in total by portions for the building.

Pool: any structure, basin, or tank containing an artificial body of water for swimming, diving, or

recreational bathing. The terms include, but no limited to, swimming pool, whirlpool, spa, hot tub.

Precision air conditioners: air conditioning equipment that provides precision cooling by maintaining

space temperature and humidity within a narrow range. Major application is in data centers where

dissipating heat generated by equipment takes precedence over comfort cooling for occupants.

Process load: the load on a building resulting form the consumption or release of process energy.

Projection factor, overhang: the ratio of the horizontal depth of the external shading projection

divided by the sum of the height of the fenestration and the distance from the top of the fenestration to

the bottom of the farthest point of the external shading projection, in consistent units.

Projection Factor = H / V

HV

Projection factor, sidefin: the ratio of the horizontal depth of the external shading projection divided

by the distance from the window jamb to the farthest point of the external shading projection, in

consistent units.

R-value (thermal resistance): the reciprocal of the time rate of heat flow through a unit area induced

by a unit temperature difference between two defined surfaces of material or construction under steady-

state conditions. Units of R value are m2-°C/W. For the prescriptive building envelope option, R-value is

for the insulation alone and does not include building materials or air films.

Readily accessible: capable of being reached quickly for operation, renewal, or inspections without

requiring those to whom ready access is requisite to climb over or remove obstacles or to resort to

portable ladders, chairs, etc. In public facilities, accessibility may be limited to certified personnel through

locking covers or by placing equipment in locked rooms.

Recirculating system: a domestic or service hot water distribution system that includes a close

circulation circuit designed to maintain usage temperatures in hot water pipes near terminal devices

(e.g., lavatory faucets, shower heads) in order to reduce the time required to obtain hot water when the

terminal device valve is opened. The motive force for circulation is either natural (due to water density

variations with temperature) or mechanical (recirculation pump).

Reflectance: the ratio of the light reflected by a surface to the light incident upon it

Page 74: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Resistance, electric: the property of an electric circuit or of any object used as part of an electric

circuit that determines for a given circuit the rate at which electric energy is converted into heat or

radiant energy and that has a value such that the product of the resistance and the square of the current

gives the rate of conversion of energy

Reset: automatic adjustment of the controller set point to a higher or lower value

Residential: spaces in buildings used primarily for living and sleeping. Residential spaces include, but

are not limited to, dwelling units, hotel/motel guest rooms, dormitories, nursing homes, patient rooms in

hospitals, lodging houses, fraternity/sorority houses, hostels, prisons, and fire stations.

Roof: the upper portion of the building envelope, including opaque areas and fenestration, that is

horizontal or tilted at an angle of less than 60° from horizontal

Roof area, gross: the area of the roof measured from the exterior faces of walls or from the centerline

of party walls

Service: the equipment for delivering energy from the supply or distribution system to the premises

served

Service water heating: heating water for domestic or commercial purposes other than space heating

and process requirements

Set point: point at which the desired temperature (°C) of the heated or cooled space is set

Shading Coefficient (SC): the ratio of solar heat gain at normal incidence through glazing to that

occurring through 3 mm thick clear, double-strength glass. Shading coefficient, as used herein, does not

include interior, exterior, or integral shading devices

Shading Efficiency Factor: Coefficient for calculating effective SHGC of fenestrations shaded by

overhangs or fins

Simulation program: a computer program that is capable of simulating the energy performance of

building systems

Single-zone system: an HVAC system serving a single HVAC zone

Site-recovered energy: waste energy recovered at the building site that is used to offset consumption

of purchased fuel or electrical energy supplies

slab-on-grade floor: that portion of a slab floor of the building envelope that is in contact with ground

and that is either above grade or is less than or equal to 300 mm below the final elevation of the nearest

exterior grade

Solar energy source: source of thermal, chemical, or electrical energy derived from direction

conversion of incident solar radiation at the building site.

Solar Heat Gain Coefficient (SHGC): the ratio of the solar heat gain entering the space through the

fenestration area to the incident solar radiation. Solar heat gain includes directly transmitted solar heat

and absorbed solar radiation, which is then reradiated, conducted, or convected into the space.

Solar zone: area dedicated for installation of solar photovoltaic and solar thermal systems either om

rooftop or elsewhere within site boundary

Space: an enclosed space within a building. The classifications of spaces are as follows for the purpose

of determining building envelope requirements.

(a) Conditioned space: a cooled space, heated space, or directly conditioned space.

(b) Semi-heated space: an enclosed space within a building that is heated by a heating system

whose output capacity is greater or equal to 10.7 W/m2 of floor area but is not a conditioned

Page 75: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Energy Conservation Building Code 2016 65

space.

(c) Non conditioned space: An enclosed space within a building that is not conditioned space or a semi-heated space. Crawlspaces, attics, and parking garages with natural or mechanical

ventilation are not considered enclosed spaces.

Story: portion of a building that is between one finished floor level and the next higher finished floor

level or the roof, provided, however, that a basement or cellar shall not be considered a story.

Super EE building: Code compliant building with efficiency greater than that of ECBC and EE buildings.

It is a voluntary level of compliance with ECBC.

System: a combination of equipment and auxiliary devices (e.g., controls, accessories, interconnecting

means, and terminal elements) by which energy is transformed so it performs a specific function such as

HVAC, service water heating, or lighting.

System, existing: a system or systems previously installed in an existing building.

Terminal: a device by which energy form a system is finally delivered, e.g., registers, diffusers, lighting

fixtures, faucets, etc.

Thermal block: a collection of one or more HVAC zones grouped together for simulation purposes.

Spaces need not be contiguous to be combined within a single thermal block.

Thermostat: an automatic control device used to maintain temperature at a fixed or adjustable set

point.

Tinted: (as applied to fenestration) bronze, green, or grey coloring that is integral with the glazing

material. Tinting does not include surface applied films such as reflective coatings, applied either in the

field or during the manufacturing process.

Transformer: a piece of electrical equipment used to convert electric power from one voltage to

another voltage

Useful Daylight Illuminance: daylight that falls on the work plane level with illuminance in the range

of 100 lux to 2,000 lux. It is the minimal glare, most useful daylight for occupants.

U-factor (Thermal Transmittance): heat transmission in unit time through unit area of a material or

construction and the boundary air films, induced by unit temperature difference between the

environments on each side. Unit of U value is W/m2-oC.

Variable Air Volume (VAV) system: HVAC system that controls the dry-bulb temperature within a

space by varying the volumetric flow of heated or cooled supply air to the space

Vent damper: a device intended for installation in the venting system or an individual, automatically

operated, fossil fuel-fired appliance in the outlet or downstream of the appliance draft control device,

which is designed to automatically open the venting system when the appliance is in operation and to

automatically close off the venting system when the appliance is in standby or shutdown condition.

Ventilation: the process of supplying or removing air by natural or mechanical means to or from any

space. Such air is not required to have been conditioned.

Wall: that portion of the building envelope, including opaque area and fenestration, that is vertical or

tilted at an angle of 60° from horizontal or greater. This includes above- and below-grade walls, between

floor spandrels, peripheral edges of floors, and foundation walls.

(a) wall, above grade: a wall that is not below grade

(b) wall, below grade: that portion of a wall in the building envelope that is entirely below the finish

grade and in contact with the ground

Page 76: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Wall area, gross: the overall area off a wall including openings such as windows and doors, measured

horizontally from outside surface to outside service and measured vertically from the top of the floor to

the top of the roof. If roof insulation is installed at the ceiling level rather than the roof, then the vertical

measurement is made to the top of the ceiling. (Note that § Error! Reference source not found. does

ot allow roof insulation to be located on a suspended ceiling with removable ceiling panels.) The gross

wall area includes the area between the ceiling and the floor for multi-story buildings.

Water heater: vessel in which water is heated and is withdrawn for use external to the system.

Zone, HVAC: A space or group of spaces within a building with heating and cooling requirements that

are sufficiently similar so that desired conditions (e.g., temperature) can be maintained throughout using

a single sensor (e.g., thermostat or temperature sensor).

Page 77: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Energy Conservation Building Code 2016 67

8.3 Abbreviations and Acronyms

AFUE Annual fuel utilization efficiency

ANSI American National Standards Institute

ARI Air-Conditioning and Refrigeration Institute

ASHRAE American Society of Heating, Refrigerating and Air-Conditioning

Engineers

ASTM American Society for Testing and Materials

BIS Bureau of Indian Standards

Btu British thermal unit

Btu/h British thermal units per hour

Btu/h-ft2-°F British thermal units per hour per square foot per degree Fahrenheit

C Celsius

cfm cubic feet per minute

cm centimeter

COP coefficient of performance

DOE U.S. Department of Energy

EER energy efficiency ratio

EF energy factor

EPI energy performance index

F Fahrenheit

ft foot

h hour

HC heat capacity

h-ft2-°F/Btu hour per square foot per degree Fahrenheit per British thermal unit

h-m2-°C/W hour per square meter per degree Celsius per Watt

hp horsepower

HVAC heating, ventilation, and air conditioning

I-P inch-pound

in. inch

IPLV integrated part-load value

kVA kilovolt-ampere

kW kilowatt

kWR kilowatt of refrigeration

kWh kilowatt-hour

l/s liter per second

LE luminous efficacy

lin linear

lin ft linear foot

lin m linear meter

lm lumens

Lm/W lumens per watt

LPD lighting power density

m meter

mm millimeter

Page 78: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

m2 square meter

m2 – ºC/W square meter degree Celsius per watt

PF projection factor

PTAC packaged terminal air conditioner

R R-value (thermal resistance)

SC shading coefficient

SHGC solar heat gain coefficient

SL standby loss

TR tons of refrigeration

UPS uninterruptible power supply

VAV variable air volume

VLT visible light transmission

W watt

W/ft2 watts per square feet

W/m2 watts per square meter

W/m2-°C watts per square meter per degree Celsius

W/m2 watts per hour per square meter

W/m-°C watts per lineal meter per degree Celsius

W/m2-°C watts per hour per square meter per degree Celsius

Wh watthour

Page 79: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix A: Definitions, Abbreviations and Acronyms

Energy Conservation Building Code 2016 69

8.4 SI to IP Conversion Factors SI Unit IP Unit

1m 3.28 ft

1m 39.37 in

1mm 0.039 in

1 l/s 2.12 cfm

1 m2 10.76 ft2

1 W/m2 10.76 W/ ft2

1 W/ lin m 3.28 W/ ft

1 W/m2 - ºC 5.678 Btu/ h-ft2-°F

1 m2 – ºC/W 0.1761 ft2-h-ºF/ Btu

1 ºC ((ºC X 9/5) + 32) ºF

1 kWR 0.284 TR

1 kW 1.34 hp

1 kW 3412.142 Btu/hr

Page 80: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix B: Whole Building Performance Method

9. Appendix B: Whole Building Performance Method

9.1 General

9.1.1 Scope

The whole building performance method is an alternative to the prescriptive requirements contained in §

0 through § 7 of this standard. It applies for all building types covered by the standard.

9.1.2 Compliance

A building complies with the whole building performance method when the estimated annual energy use

of the proposed design is less than the baseline design, even though it may not comply with the specific

requirements of the prescriptive requirements in § 4 trough § 7. The mandatory requirements of § 4

through § 7 (§ 4.2, § 5.2, § 6.2, and § 7.2) shall be satisfied with the whole building performance

method.

9.1.3 Annual Energy Use

Annual energy use for the purposes of the whole building performance method shall be calculated in

kilowatt-hours (kWh) of electricity use per year. Energy sources other than electricity which are used is

used in the building shall be converted to kWh of electric energy at the rate of 0.75 kWh per mega Joule.

Note: The Annual Energy Use calculation as per the Whole Building performance method is not a

prediction of the actual energy use of the building once it gets operational. Actual energy performance of

a building depends on a number of factors like weather, occupant behavior, equipment performance and

maintenance etc. which are not covered by this Code.

9.1.4 Trade-offs Limited to Building Permit

The whole building performance method may be used for building permit applications that include less

than the whole building; however, any design parameters that are not part of the building permit

application shall be identical for both the proposed design and the baseline design. Future improvements

to the building shall comply with both the mandatory and prescriptive requirements of concurrent code.

9.1.5 Documentation Requirements

Compliance shall be documented and submitted to the authority having jurisdiction. The information

submitted shall include, at a minimum, the following:

(a) Summary describing the results of the analysis including the annual energy use for the proposed design and the baseline design, and software used.

(b) Brief description of the project with location, number of stories, space types, conditioned and unconditioned areas, hours of operation.

(c) List of the energy-related building features of the proposed design. This list shall also document features different from the baseline design.

(d) List showing compliance with the mandatory requirements of this code.

(e) The input and output report(s) from the simulation program including a breakdown of energy usage by at least the following components: lights, internal equipment loads, service water

heating equipment, space heating equipment, space cooling and heat rejection equipment, fans, and other HVAC equipment (such as pumps). The output reports shall also show the amount of

time any loads are not met by the HVAC system for both the proposed design and baseline

design.

(f) Explanation of any significant modeling assumptions made.

(g) Explanation of any error messages noted in the simulation program output.

Page 81: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix B: Whole Building Performance Method

Energy Conservation Building Code 2016 71

(h) Building floor plans, building elevations and site plan

9.2 Simulation General Requirements

9.2.1 Energy Simulation Program

The simulation program shall be a computer-based program for the analysis of energy consumption in

buildings and be approved by the authority having jurisdiction. The simulation program shall, at a

minimum, have the ability to explicitly model the following:

(a) Energy flows on an hourly basis for all 8,760 hours in the year,

(b) Hourly variations in occupancy, lighting power, miscellaneous equipment power, thermostat setpoints, and HVAC system operation, defined separately for each day of the week and holidays,

(c) Thermal mass effects,

(d) Ten or more thermal zones,

(e) Part-load and temperature dependent performance of heating and cooling equipment,

(f) Air-side and water-side economizers with integrated control, and

(g) All of the baseline design characteristics specified in this chapter.

In addition to the above, the simulation tool shall be able to produce hourly reports of energy use by energy source and shall be capable of performing design load calculations to determine required HVAC

equipment capacities, air and water flow rates in accordance with § 5 for both the proposed and baseline building designs.

The simulation program shall be tested according to Standard 140 and the results shall be furnished by

the software provider.

9.2.2 Climatic Data

The simulation program shall use hourly values of climatic data, such as temperature and humidity from

representative climatic data, for the city in which the proposed design is to be located. For cities or urban

regions with several climatic data entries, and for locations where weather data are not available, the

designer shall select available weather data that best represent the climate at the construction site.

9.2.3 Compliance Calculations

The proposed design and baseline design shall be calculated using the following:

(a) Same simulation program,

(b) Same weather data, and

(c) Same building operation assumptions (thermostat setpoints, schedules, internal gains, occupant

loads, etc.) unless an exception is allowed by this code/ authority having jurisdiction for the respective category.

Page 82: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix B: Whole Building Performance Method

9.3 Calculating the Energy Consumption of the Proposed Design and the Baseline Design

9.3.1 Energy Simulation Model

The simulation model for calculating the proposed design and the baseline design shall be developed in

accordance with the requirements in Table 9.1.

9.3.2 HVAC Systems

The HVAC system type and related performance parameters for the baseline design shall be determined

from Table 9.1 and the following rules:

Other Components: Components and parameters not listed in

Page 83: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix B: Whole Building Performance Method

Energy Conservation Building Code 2016 73

Table 9.2 HVAC Systems Map

(a) or otherwise specifically addressed in this subsection shall be identical to those in the proposed

design.

Exception to § 9.3.2(a): Where there are specific requirements in § 5.2.2, the component

efficiency in the standard design shall be adjusted to the lowest efficiency level allowed by the

requirement for that component type.

(b) All HVAC and service water heating equipment in the baseline design shall be modeled at the minimum efficiency levels, both part load and full load, in accordance with § 5.2.2.

(c) Where efficiency ratings, such as EER and COP, include fan energy, the descriptor shall be

broken down into its components so that supply fan energy can be modeled separately.

(d) Minimum outdoor air ventilation rates shall be the same for both the baseline design and the

proposed design.

(e) The equipment capacities for the baseline design shall be sized proportionally to the capacities in

the proposed design based on sizing runs; i.e., the ratio between the capacities used in the

annual simulations and the capacities determined by the sizing runs shall be the same for both the proposed design and baseline design. Unmet load hours for the proposed design shall not

differ from unmet load hours for the standard design by more than 50 hours. Maximum number of unmet hours shall not exceed 300 for either case.

Page 84: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix B: Whole Building Performance Method

Table 9.1 Modeling Requirements for Calculating Proposed and Baseline Design

Case Proposed Building Baseline Design

1. Design Model (a) The simulation model of the proposed design shall be consistent with the design documents, including proper accounting of fenestration and opaque envelope types and area; interior lighting power and controls; HVAC system types, sizes, and controls; and service water heating systems and controls.

(b) When the whole building performance method is applied to buildings in which energy-related features have not yet been designed (e.g., a lighting system), those yet-to-be-designed features shall be described in the proposed design so that they minimally comply with applicable mandatory and prescriptive requirements from § 0 through § 7.

The baseline design shall be developed by modifying the proposed design as described in this table. Except as specifically instructed in this table, all building systems and equipment shall be modeled identically in the baseline design and proposed design.

2. Space Use Classification

The building type or space type classifications shall be chosen in accordance with § 6.3.2 or § 6.3.3. More than one building type category may be used in a building if it is a mixed-use facility.

Same as proposed design.

3. Schedules Standardized schedules (hourly variations in occupancy, lighting power, equipment power, temperature set points, HVAC equipment operation etc.) as per Appendix 15, shall be modeled for showing compliance.

Same as proposed design.

Exception: Schedules may be allowed to differ between the Baseline and Proposed models wherever it is necessary to model nonstandard efficiency measures and/or measures which can be best approximated by a change in schedule. Measures that may warrant a change in operating schedules include but are not limited to automatic controls for lighting, natural ventilation, demand controlled ventilation systems, controls for service water heating load reduction. Schedule change is not allowed for manual controls under any category. This is subject to approval by the authority having jurisdiction.

4. Building Envelope All components of the building envelope in the proposed design shall be modeled as shown on architectural drawings or as installed for existing building envelopes.

Exceptions: The following building elements are permitted to differ from architectural drawings.

(a) Any envelope assembly that covers less than 5% of the total area of that assembly type (e.g., exterior walls) need not be separately described. If not separately described, the area of an envelope assembly must be added to the area of the adjacent assembly of that same type.

(b) Exterior surfaces whose azimuth orientation and tilt differ by no more than 45 degrees and are otherwise the same may be described as either a single surface or by using multipliers.

(c) For exterior roofs other than roofs with ventilated attics, the reflectance and emittance of the roof surface shall be modeled. The reflectance and emittance shall be tested in accordance with § 4.3.1.1.

(d) Manually operated fenestration shading devices such as blinds or shades shall not be modeled. Permanent shading devices such as fins, overhangs, and light shelves shall be modeled.

The baseline design shall have identical conditioned floor area and identical exterior dimensions and orientations as the proposed design, except as noted in (a), (b), (c), and (d) below.

(a) Orientation. The baseline building performance shall be generated by simulating the building with its actual orientation and again after rotating the entire building 90, 180, 270 degrees, then averaging the results. The building shall be modeled so that it does not shade itself.

(b) Opaque assemblies such as roof, floors, doors, and walls shall be modeled as having the same heat capacity as the proposed design but with the minimum U-factor required in § 4.3.1 and § 4.3.2Error! Reference ource not found..

(c) Fenestration— Fenestration areas shall equal that in the proposed design or 40% of gross above grade wall area, whichever is smaller, and shall be distributed on each face in the same proportions as in the proposed design. No shading projections are to be modeled; fenestration shall be assumed to be flush with the exterior wall or roof. Manually operated fenestration shading devices such as blinds or shades shall not be modeled. Fenestration U-factor shall be the minimum required for the climate, and the solar heat gain coefficient shall be the maximum allowed for the climate and orientation.

(d) Roof albedo. All roof surfaces shall be modeled with a reflectivity of 0.30

5. Lighting Lighting power in the proposed design shall be determined as follows:

Lighting power in the baseline design shall be determined using the same categorization

Page 85: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix B: Whole Building Performance Method

Energy Conservation Building Code 2016 75

(a) Where a complete lighting system exists, the actual lighting power shall be used in the model.

(b) Where a lighting system has been designed, lighting power shall be determined in accordance with either § 6.3.2 or § 6.3.3.

(c) Where no lighting exists or is specified, lighting power shall be determined in accordance with the § 6.3.2Error! eference source not found. for the appropriate building type.

(d) Lighting system power shall include all lighting system components shown or provided for on plans (including lamps, ballasts, task fixtures, and furniture-mounted fixtures).

procedure (building area or space function) and categories as the proposed design with lighting power set equal to the maximum allowed for the corresponding method and category in either § 6.3.2 or § 6.3.3 . Power for fixtures not included in the lighting power density calculation shall be modeled identically in the proposed design and baseline design. Lighting controls shall be the minimum required.

6. HVAC Systems The HVAC system type and all related performance parameters, such as equipment capacities and efficiencies, in the proposed design shall be determined as follows:

(a) Where a complete HVAC system exists, the model shall reflect the actual system type using actual component capacities and efficiencies.

(b) Where an HVAC system has been designed, the HVAC model shall be consistent with design documents. Mechanical equipment efficiencies shall be adjusted from actual design conditions to the standard rating conditions specified in § 5, if required by the simulation model.

(c) Where no heating system exists or no heating system has been specified, the heating system shall be assumed to be electric. The system characteristics shall be identical to the system modeled in the standard design.

(d) Where no cooling system exists or no cooling system has been specified, the cooling system and its characteristics shall be identical to the system modeled in the baseline design.

The HVAC system type and related performance parameters for the standard design shall be determined from Table § 9.3.2. Equipment performance shall meet the requirements of § 5.

7. Service Hot Water

The service hot water system type and all related performance parameters, such as equipment capacities and efficiencies, in the proposed design shall be determined as follows:

(a) Where a complete service hot water system exists, the model shall reflect the actual system type using actual component capacities and efficiencies.

(b) Where a service hot water system has been designed, the service hot water model shall be consistent with design documents.

(c) Where no service hot water system exists or is specified, no service hot water heating shall be modeled.

The water heating system shall be of the same type of the proposed design.

For residential facilities, hotels and hospitals the standard design shall have a solar system capable of meeting 20% of the design load.

Systems shall meet the efficiency requirements of § 5.2.10.2, the pipe insulation requirements of § 5.2.10.4 and incorporate heat traps in accordance with § 5.2.10.5Error! eference source not found..

8. Miscellaneous Loads

Receptacle, motor, and process loads shall be modeled and estimated based on the building type or space type category. These loads shall be included in simulations of the building and shall be included when calculating the baseline design and proposed design. All end-use load components within and associated with the building shall be modeled, unless specifically excluded, but not limited to, exhaust fans, parking garage ventilation fans, exterior building lighting, swimming pool heaters and pumps, elevators and escalators, refrigeration equipment, and cooking equipment.

Receptacle, motor and process loads shall be modeled the same as the proposed design. The water heating system shall be of the same type of the proposed design.

9. Daylight The simulation program shall use hourly values of climatic data such as direct normal radiation, diffuse horizontal radiation, cloud cover from representative climatic data, for the city in which the proposed design is to be located. for cities or urban regions with several climatic data entries, and for locations where weather data are not available, the designer shall select available weather data that best represents the climate at the construction site. The period of analysis shall be fixed for 10 hours per day i.e. from 08:00 AM to 06:00 PM local time, which results in 3650 hours for all building types covered by the standard except for school buildings 08:00 AM to 03:00 PM is to be used. Windows and Skylight shall be modelled with actual visible light transmission as per the details provided in the material specification sheet

Same as proposed design.

Page 86: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix B: Whole Building Performance Method

UDI measures availability of useful daylight across a space based on the point-by-point grid values and shall be calculated for at least one point each square meter of floor area. A maximum 1m2 grid must be overlaid over the floor plan at a height of 0.9m above finished floor or above the highest regular task level to determine these points. Surrounding/nearby buildings, structure, trees etc. which are in direct line of view of each major facade while doing the UDI calculation shall be modeled. A reflectance of 30% must be taken for all vertical surfaces if the reflectance of surface is not known. Interior surface reflectance shall be modelled based on the material specification, or if not known, use the following default values (a) Wall or Vertical Internal Surfaces reflectance: 50% (b) Ceiling Reflectance: 70% (c) Floor Reflectance: 20% (d) Furniture Reflectance: 50%

9. Modeling Limitations to the Simulation Program

If the simulation program cannot model a component or system included in the proposed design, one of the following methods shall be used with the approval of the authority having jurisdiction:

(a) Ignore the component if the energy impact on the trade-offs being considered is not significant.

(b) Model the component substituting a thermodynamically similar component model.

(c) Model the HVAC system components or systems using the baseline design’s HVAC system in accordance with Section 6 of this table.

Whichever method is selected, the component shall be modeled identically for both the proposed design and baseline design models.

Same as proposed design.

Page 87: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix B: Whole Building Performance Method

Energy Conservation Building Code 2016 77

Table 9.2 HVAC Systems Map

Code System type

Fan control

Cooling type

Heating type

Resid

en

tial

Guestrooms (hotels, motels, resorts), Hospital in patient area

System A

Split AC Constant Volume

Direct expansion

1. Electric resistance where - no heating system exists, or, - no heating system has been specified, or, - a heating system exists and an electric heating system has been specified in the proposed building design 2. Fossil Fuel Boiler where - a heating system exists and a fossil fuel hot water boiler has been specified in the proposed building design

No

n R

esid

en

tial

Less than 7,500 m²

System B

VRF : Variable Refrigerant Flow

Constant volume

Direct expansion

1. Heat Pump where - no heating system exists, or, - no heating system has been specified, or, - heating system exists and an electric heating system has been specified in the proposed building design 2. Fossil Fuel Boiler where - heating system exists and a fossil fuel hot water boiler has been specified in the proposed building design

7,500 to 15,000 m²

System C

CAV : Central cooling plant with constant volume AHU for each zone

Constant volume

Chilled Water

1. Electric resistance where - no heating system exists, or, - no heating system has been specified, or, - a heating system exists and an electric heating system has been specified in the proposed building design 2. Fossil Fuel Boiler where - a heating system exists and a fossil fuel hot water boiler has been specified in the proposed building design

More than 15,000 m²

System D

VAV : Central cooling plant with variable volume AHU for each zone

Variable volume

Chilled Water

1. Electric resistance where - no heating system exists, or, - no heating system has been specified, or, - a heating system exists and an electric heating system has been specified in the proposed building design 2. Fossil Fuel Boiler where - a heating system exists and a fossil fuel hot water boiler has been specified in the proposed building design

Data centre/ server/computer rooms

System E

PAC : Precision air conditioners

Constant volume

Direct Expansion

NA

Notes: • Residential building types include Hotels, Motels, Hostels/dormitories and multifamily/serviced apartments. Residential space types include Hospital patient rooms, Hotel guest rooms and Resorts/Villas, sleeping quarters. Other building and space types are considered Non Residential. • If the proposed building has an air cooled chiller/system then the budget building shall have air cooled chiller otherwise the budget case shall have water cooled chillers. If the building has a mix of air and water cooled chillers then the baseline building shall have a mix of air and water cooled chillers in the same proportion as the proposed design building. However, this clause applies only for minimum ECBC compliance. EE and Super EE buildings are not allowed to have air cooled Chillers in the standard building design under any circumstances. • Where attributes make a building eligible for more than one system type; use the predominant condition to determine the baseline system type except as noted in Exemption XXXX.

Page 88: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix C: Default Values for Typical Constructions

10. Appendix C: Default Values for Typical Constructions

10.1 Procedure for Determining Fenestration Product U-Factor and Solar Heat Gain Coefficient

§ 4.2.1.1 and § 4.2.1.2 require that U-factors and solar heat gain coefficients (SHGC) be determined for

the overall fenestration product (including the sash and frame) in accordance with ISO 15099. The

building envelope trade-off option in § 0 requires the use of visible light transmittance (VLT).

In several cases, ISO 15099 suggests that individual national standards will need to be more specific and

in other cases the ISO document gives users the choice of two options. This section clarifies these

specific issues as they are to be implemented for this code:

(a) § 4.1: For calculating the overall U-factor, ISO 15099 offers a choice between the linear thermal transmittance (4.1.2) and the area weighted method (4.1.3). The area weighted method (4.1.3)

shall be used.

(b) § 4.2.2: Frame and divider SHGC’s shall be calculated in accordance with § 4.2.2. The alternate

approach in § 8.6 shall not be used.

(c) § 6.4 refers the issue of material properties to national standards. Material conductivities and

emissivity shall be determined in accordance with Indian standards.

(d) § 7 on shading systems is currently excluded.

(e) § 8.2 addresses environmental conditions. The following are defined for India:

For U-factor calculations:

Tin = 24 C

Tout = 32 C

V = 3.35 m/s

Trm,out=Tout

Trm,in=Tin

Is=0 W/m2

For SHGC calculations:

Tin = 24 C

Tout = 32 C

V = 2.75 m/s

Trm,out=Tout

Trm,in=Tin

Is=783 W/m2

(f) § 8.3 addresses convective film coefficients on the interior and exterior of the window product.

In § 8.3.1, simulations shall use the heat transfer coefficient based on the center of glass temperature and the entire window height; this film coefficient shall be used on all indoor

surfaces, including frame sections. In § 8.3.2, the formula from this section shall be applied to all outdoor exposed surfaces.

(g) § 8.4.2 presents two possible approaches for incorporating the impacts of self-viewing surfaces

Page 89: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix C: Default Values for Typical Constructions

Energy Conservation Building Code 2016 79

on interior radiative heat transfer calculations. Products shall use the method in § 8.4.2.1 (Two-

Dimensional Element to Element View Factor Based Radiation Heat Transfer Calculation). The alternate approach in § 8.4.3 shall not be used.

10.2 Default U-Factors and Solar Heat Gain Coefficients for Unrated Fenestration Products

All fenestration with U-factors, SHGC, or visible light transmittance determined, certified, and labeled in

accordance ISO 15099 shall be assigned those values.

10.2.1 Unrated Vertical Fenestration.

Unlabeled vertical fenestration, both operable and fixed, shall be assigned the U-factors, SHGCs, and

visible light transmittances in Table 10.2.1.

Table 10.1 Defaults for Unrated Vertical Fenestration (Overall Assembly including the Sash and Frame)

Clear Glass Tinted Glass

Frame Type Glazing Type

U-Factor (W/m2-oC) SHGC VLT

U-Factor (W/m2-oC) SHGC VLT

All frame types Single Glazing 7.1 0.82 0.76 7.1 0.70 0.58

Wood, vinyl, or fiberglass frame

Double Glazing 3.3 0.59 0.64 3.4 0.42 0.39

Metal and other frame type

Double Glazing 5.1 0.68 0.66 5.1 0.50 0.40

10.2.2 Unrated Sloped Glazing and Skylights

Unrated sloped glazing and skylights, both operable and fixed, shall be assigned the SHGCs and visible

light transmittances in Table 10.2.1. To determine the default U-factor for unrated sloped glazing and

skylights without a curb, multiply the values in Table 10.2.1 by 1.2. To determine the default U-factor for

unrated skylights on a curb, multiply the values in Table 10.2.1 by 1.6.

10.3 Typical Roof Constructions

For calculating the overall U-factor of a typical roof construction, the U-factors from the typical wall

construction type and effective U-factor for insulation shall be combined according to the following

equation:

ulationTyipcalInsfTypicalRoo

TotalRoof

UU

U11

1

where

UTotalRoof Total U-factor of the roof with insulation

UTypical Roof U-factor of the roof

UTypical Insulation U-factor of the effective insulation from Table 10.2

Page 90: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix C: Default Values for Typical Constructions

Table 10.2 Defaults for Effective U-factor for Exterior Insulation Layers

Thickness R-value U-factor (W/m²-°K)

15 mm (0.5”) 0.70 (4) 1.420

20 mm (0.75”) 1.06 (6) 0.946

25 mm (1.0”) 1.41 (8) 0.710

40 mm (1.5”) 2.11 (12) 0.568

50 mm (2.0”) 2.82 (16) 0.406

65 mm (2.5”) 3.52 (20) 0.284

75 mm (3.0”) 3.70 (21) 0.270

Also Super EE Appendix for default thermal properties of building materials.

10.4 Typical Wall Constructions

For calculating the overall U-factor of a typical wall construction, the U-factors from the typical wall

construction type and effective U-factor for insulation shall be combined according to the following

equation:

ulationTyipcalInslTypicalWal

TotalWall

UU

U11

1

where

UTotalWall Total U-factor of the wall with insulation

UTypical Wall U-factor of the wall

UTypical Insulation U-factor of the effective insulation from Table 10.3 or Error! Reference source

not found.

Table 10.3 Defaults for Effective U-factor for Exterior Insulation Layers

Thickness R-value U-factor (W/m²-°C)

15 mm (0.5”) 0.70 (4) 1.262

20 mm (0.75”) 1.06 (6) 0.874

25 mm (1.0”) 1.41 (8) 0.668

40 mm (1.5”) 2.11 (12) 0.454

50 mm (2.0”) 2.82 (16) 0.344

65 mm (2.5”) 3.52 (20) 0.277

75 mm (3.0”) 3.70 (21) 0.264

Page 91: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix C: Default Values for Typical Constructions

Energy Conservation Building Code 2016 81

Table 10.4 Typical Thermal Properties of Common Building and Insulating Materials2

Name Form Density kg/m³ Thermal Conductivity

W/(mC)

Specific Heat MJ/m³C

Acrylic Sheet Board 1145 0.2174 1.5839

Armor Insulation 270 0.0678 0.1578

Asbestos Cement Board Board 1404 0.4709 0.7218

Asbestos Sheet -Shera Board 1377 0.5128 1.2043

Autodaved Aerated Concrete Block (AAC)

Block 642 0.1839 0.794

Bamboo Wood 913 0.1959 0.6351

Brass Metal 8500 106.48 11.1164

Calcium Silicate Board Board 1016 0.281 0.8637

Composite Marble Stone 3146 2.44 2.1398

Cement Board Board 1340 0.4384 0.8113

Cement Bonded Particle Board Board 1251 0.3275 1.1948

Ceramic Fiber Blanket Insulation 128 0.0491 0.1093

Cement Fiber Board

Board 1276 0.388 0.8973

Cement Plaster 278 1.208 0.9719

Cement Powder Powder 1070 0.1137 0.7943

Ceramic Blue Tile Tile 2707 1.372 1.2082

Ceramic Frit Glass Glass 2520 0.6882 0.7859

Ceramic Tile - Bathroom Tile 2549 0.8018 1.6168

Ceramic Tile Tile 2700 1.5996 1.1438

Chile Wood Wood 362 0.1422 0.4102

Chitodio Stone 3209 3.7512 2.1223

Clay Tile Tile 2531 0.6323 1.4253

Float Glass/ Clear Glass Glass 2477 1.0522 1.9654

Concrete Block 25/50 Block 2427 1.3957 0.4751

Concrete Block 30/60 Block 2349 1.4107 0.7013

Corian Board 1750 1.012 2.0921

Crystal White Tile Tile 2390 1.5094 1.9427

Dholpuri Stone Stone 2262 3.084 1.583

2 Thermo-Physical-Optical Property Database of Construction Materials, U.S.- India Joint Center for Building Energy Research and

Development (CBERD) and Ministry of New and Renewable Energy (MNRE).

Page 92: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix C: Default Values for Typical Constructions

Name Form Density kg/m³ Thermal Conductivity

W/(mC)

Specific Heat MJ/m³C

Distilled Water Water 1000 0.6134 3.8165

Engineered Wood Floor Tiles Tile 571 0.2527 1.423

Extruded Polystyrene XPS Insulation 30 0.0321 0.0374

Fiber Reinforced Plastic (FRP ) Board 1183 0.2252 1.693

Fire Brick Brick 2049 1.2729 1.2887

Floor Board Board 954 0.2654 1.1423

Foam Cement Block Block 581 0.1588 0.5359

Ghana Teak Wood Wood 529 0.2062 0.5769

Glasswool Insulation 49 0.0351 0.0339

Black Fine Granite Stone 3535 2.4351 2.2511

Black Coarse Granite Stone 3473 2.5433 2.1996

Green Marble Stone 2650 2.372 2.5275

Green Rockwool Insulation 96 0.045 0.1089

Gypsum Board Board 623 0.2527 0.6033

Gypsum Powder Powder 588 0.202 1.1918

Gypsum Powder from Board Powder 542 0.1033 0.626

Italian Black Granite Stone 2911 2.3636 2.2349

Italian Marble Stone 2630 2.7752 2.1869

Jaisalmer Yellow Stone Stone 3006 2.7447 2.0954

Jalore Stone 2982 3.4412 1.9617

Kota Stone Stone 3102 3.0229 2.0732

Laminated Particle Board Board 656 0.1841 1.2621

Lime Powder Powder 607 0.1286 0.7078

Mangalore Roof Tile Tile - Roof 2531 0.6051 1.2809

Ambaji Marble Stone 3128 2.8108 2.1943

Medium Density Fiberboard (MDF) Board 133 0.2045 0.961

Melamine Fiberboard Board 807 0.2459 0.6509

Mild Steel (MS) Metal 7823 44.117 4.1896

Mineral Fiber - Celling Board 364 0.071 0.3222

Mineral Fiber - Plain Board 773 0.2739 0.6427

Page 93: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix C: Default Values for Typical Constructions

Energy Conservation Building Code 2016 83

Name Form Density kg/m³ Thermal Conductivity

W/(mC)

Specific Heat MJ/m³C

Oak Laminated Floor Tiles Tile 949 0.2652 1.3389

Concrete Paver Tiles Tile 2210 1.7248 1.3413

Paver Tile Tile 2612 1.4763 1.2737

Plain & Prelaminated Particle Board Board 902 0.271 0.974

Plaster of Paris (POP) Powder Powder 1000 0.1353 0.9526

Plywood Board 697 0.221 0.7258

Polyisocyanurate (PIR) Insulation 40 0.0364 0.0685

Polymer (Anisotropic) Plastic 1743 0.5027 1.6968

Polyurethane Foam (PUF) Insulation 40 0.0372 0.0704

POP Board Board 1080 0.4994 1.2167

Porcelain Tile Tile 2827 1.5331 1.6259

Pumice Square - Bronze Tile

Tile 2327 0.9907 0.4382

Quartz Stone 2359 3.7603 1.8277

Rajnagar Marble Stone 3332 5.6405 2.777

Rigid Polyurethane (40 Kg/m3)

Insulation 40 0.0269 0.0766

Rigid Polyurethane (25 Kg/m3)

Insulation 25 0.0384 0.0763

Rockwool Insulation 64 0.0461 0.0904

Rubber - Foam Insulation 89 0.0561 0.1486

Rubber Wood Wood 472 0.1679 0.5034

Saag Wood Wood 959 0.2886 1.0258

Sand Powder 1600 0.3075 1.1343

Sandstone Stone 2530 3.0097 1.5957

Serpentine Green Granite Stone 3068 2.1363 2.4484

Soft Board Board 274 0.0943 0.2753

Soft Board-High Density Board 353 0.0983 0.2621

Stainless Steel (SS) Metal 7950 13.5633 3.6351

Steam Beech Wood Wood 241 0.2331 0.5512

Straw Board Board 760 0.2237 0.7098

Teak Wood Wood 665 0.2369 0.8412

Tempered Glass Glass 2500 1.0493 1.9227

Page 94: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix C: Default Values for Typical Constructions

Name Form Density kg/m³ Thermal Conductivity

W/(mC)

Specific Heat MJ/m³C

Tinted Glass Glass 2500 1.0428 1.8904

Udaipur Brown Marble Stone 3197 2.921 2.2184

V-Board Board 1191 0.2977 0.8245

Veneered Particle Board Board 788 0.2363 0.7075

Vitrified Tile Tile 2719 1.4786 1.8049

Resource Efficient Bricks (REB) Brick 1520 0.6314 0.9951

Wood Wood 802 0.2652 0.8715

Wood Pattern Chitodio Stone 3126 3.4258 2.2852

Page 95: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix D: Building Envelope Tradeoff Method

Energy Conservation Building Code 2016 85

11. Appendix D: Building Envelope Tradeoff Method

11.1 Envelope Performance Factor

The envelope performance factor shall be calculated using the following equations.

Equation 11.1: 𝐸𝑃𝐹 𝑇𝑜𝑡𝑎𝑙 = 𝐸𝑃𝐹𝑅𝑜𝑜𝑓 + 𝐸𝑃𝐹𝑊𝑎𝑙𝑙 + 𝐸𝑃𝐹 𝐹𝑒𝑛𝑒𝑠𝑡

𝐸𝑃𝐹𝑅𝑜𝑜𝑓 = 𝑐𝑅𝑜𝑜𝑓 ∑ 𝑈𝑠𝐴𝑠

𝑛

𝑠=1

𝐸𝑃𝐹𝑊𝑎𝑙𝑙 = 𝑐𝑊𝑎𝑙𝑙,𝑀𝑎𝑠𝑠 ∑ 𝑈𝑠𝐴𝑠

𝑛

𝑠=1

+ 𝑐𝑊𝑎𝑙𝑙,𝑂𝑡ℎ𝑒𝑟 ∑ 𝑈𝑠𝐴𝑠

𝑛

𝑠=1

𝐸𝑃𝐹𝐹𝑒𝑛𝑒𝑠𝑡 = 𝑐1𝐹𝑒𝑛𝑒𝑠𝑡,𝑁𝑜𝑟𝑡ℎ ∑ 𝑈𝑤𝐴𝑤

𝑛

𝑤=1

+ 𝑐2𝐹𝑒𝑛𝑒𝑠𝑡,𝑁𝑜𝑟𝑡ℎ ∑ 𝑆𝐻𝐺𝐶𝑤𝑀𝑤𝐴𝑤

𝑛

𝑤=1

+ 𝑐1𝐹𝑒𝑛𝑒𝑠𝑡,𝑆𝑜𝑢𝑡ℎ ∑ 𝑈𝑤𝐴𝑤

𝑛

𝑤=1

+ 𝑐2𝐹𝑒𝑛𝑒𝑠𝑡,𝑆𝑜𝑢𝑡ℎ ∑ 𝑆𝐻𝐺𝐶𝑤𝑀𝑤𝐴𝑤

𝑛

𝑤=1

+ 𝑐1𝐹𝑒𝑛𝑒𝑠𝑡,𝐸𝑎𝑠𝑡 ∑ 𝑈𝑤𝐴𝑤

𝑛

𝑤=1

+ 𝑐2𝐹𝑒𝑛𝑒𝑠𝑡,𝐸𝑎𝑠𝑡 ∑ 𝑆𝐻𝐺𝐶𝑤𝑀𝑤𝐴𝑤

𝑛

𝑤=1

+ 𝑐1𝐹𝑒𝑛𝑒𝑠𝑡,𝑊𝑒𝑠𝑡 ∑ 𝑈𝑤𝐴𝑤

𝑛

𝑤=1

+ 𝑐2𝐹𝑒𝑛𝑒𝑠𝑡,𝑊𝑒𝑠𝑡 ∑ 𝑆𝐻𝐺𝐶𝑤𝑀𝑤𝐴𝑤

𝑛

𝑤=1

+ 𝑐1𝐹𝑒𝑛𝑒𝑠𝑡,𝑆𝑘𝑦𝑙𝑖𝑔ℎ𝑡 ∑ 𝑈𝑤𝐴𝑤

𝑛

𝑤=1

+ 𝑐2𝐹𝑒𝑛𝑒𝑠𝑡,𝑆𝑘𝑦𝑙𝑖𝑔ℎ𝑡 ∑ 𝑆𝐻𝐺𝐶𝑤𝐴𝑤

𝑛

𝑤=1

EPFRoof Envelope performance factor for roofs. Other subscripts include walls and fenestration.

As, Aw The area of a specific envelope component referenced by the subscript "s" or for

windows the subscript "w".

SHGCw The solar heat gain coefficient for windows (w). SHGCs refers to skylights.

Mw A multiplier for the window SHGC that depends on the projection factor of an overhang

or sidefin.

Us The U-factor for the envelope component referenced by the subscript "s".

cRoof A coefficient for the "Roof" class of construction. Values of "c" are taken from Table 12-1

through Table 12-5 for each class of construction.

Cwall A coefficient for the "Wall"

C1 Fenes A coefficient for the "Fenestration U-value"

C2 Fenes A coefficient for the "Fenestration SHGC"

Values of "C" are taken from Table 11.1 through Table 11.5 for each class of construction.

Page 96: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix D: Building Envelope Tradeoff Method

Table 11.1 Envelope Performance Factor Coefficients – Composite Climate

Daytime Occupancy 24 Hour Occupancy

U-factor (W/m2 –

ºC)

SHGC U-factor (W/m2 –

ºC)

SHGC

Mass Walls 6.04 - 10.39 -

Curtain Walls,

Other

7.83 - 10.32 -

Roofs 15.13 - 28.94 -

North Windows 4.31 55.51 3.94 73.39

South Windows 2.65 193.26 4.11 230.08

East Windows 3.78 140.49 5.15 198.87

West Windows 3.38 140.62 4.80 192.80

Table 11.2 Envelope Performance Factor Coefficients – Hot Dry Climate

Daytime Occupancy 24 Hour Occupancy

U-factor (W/m2 –

ºC)

SHGC U-factor (W/m2 –

ºC)

SHGC

Mass Walls 7.91 - 13.30 -

Curtain Walls,

Other

9.58 - 12.30 -

Roofs 15.52 - 31.70 -

North Windows 4.10 76.37 4.46 91.26

South Windows 4.62 229.30 6.95 260.68

East Windows 5.25 187.83 9.92 240.45

West Windows 4.40 186.59 6.89 242.94

Table 11.3 Envelope Performance Factor Coefficients – Hot Humid Climate

Daytime Occupancy 24 Hour Occupancy

U-factor (W/m2 –

ºC)

SHGC U-factor (W/m2 –

ºC)

SHGC

Mass Walls 6.02 - 10.13 -

Curtain Walls,

Other

7.98 - 13.32 -

Roofs 13.95 - 26.31 -

North Windows 2.13 86.35 1.93 101.93

South Windows 2.73 206.55 3.75 226.25

East Windows 3.01 163.94 3.76 202.52

West Windows 2.08 162.34 3.30 190.61

Page 97: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix D: Building Envelope Tradeoff Method

Energy Conservation Building Code 2016 87

Table 11.4 Envelope Performance Factor Coefficients – Moderate Climate

Daytime Occupancy 24 Hour Occupancy

U-factor (W/m2 –

ºC)

SHGC U-factor (W/m2 –

ºC)

SHGC

Mass Walls 3.18 - 5.61 -

Curtain Walls,

Other

4.50 - 7.29 -

Roofs 11.56 - 22.62 -

North Windows 0.24 72.42 -0.46 89.23

South Windows 0.53 154.17 0.84 190.42

East Windows 1.67 169.76 3.26 230.36

West Windows 0.62 162.81 1.75 224.41

Table 11.5 Envelope Performance Factor Coefficients – Cold Climate

Daytime Occupancy 24 Hour Occupancy

U-factor (W/m2 –ºC)

SHGC U-factor (W/m2 –ºC)

SHGC

Mass Walls 12.90 - 17.63 -

Curtain Walls,

Other

14.36 - 17.65 -

Roofs 15.49 - 31.72 -

North Windows 16.89 -52.74 20.09 11.22

South Windows 7.68 20.29 7.68 103.30

East Windows 13.09 -9.39 21.37 203.24

West Windows 13.90 0.92 15.98 87.50

11.2 Baseline Building Definition

The following rules shall be used to define the budget building.

(a) The budget building shall have the same building floor area, gross wall area and gross roof area

as the proposed design. If the building has both 24-hour and daytime occupancies, the

distribution between these shall be the same as the proposed design.

(b) The U-factor of each envelope component shall be equal to the criteria from § 4.3 for each class

of construction.

(c) The vertical fenestration area shall be equal to the proposed design or 40% of the gross exterior

wall area, whichever is less. The skylight area shall be equal to the proposed design or 5% of the

gross exterior roof area, whichever is less.

(d) The SHGC of each window or skylight component shall be equal to the criteria from § 4.3.

Page 98: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix E: Climate Zone Map of India

12. Appendix E: Climate Zone Map of India

Page 99: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix E: Climate Zone Map of India

Energy Conservation Building Code 2016 89

Table 12.1Climate Zone for Major Indian Cities

City Climate Type City Climate Type

Ahmedabad Hot & Dry Kurnool Warm & Humid

Allahabad Composite Leh Cold

Amritsar Composite Lucknow Composite

Aurangabad Hot & Dry Ludhiana Composite

Bangalore Temperate Madras Warm & Humid

Barmer Hot & Dry Manali Cold

Belgaum Warm & Humid Mangalore Temperate

Bhagalpur Warm & Humid Mumbai Warm & Humid

Bhopal Composite Nagpur Composite

Bhubaneshwar Warm & Humid Nellore Warm & Humid

Bikaner Hot & Dry New Delhi Composite

Chandigarh Composite Panjim Warm & Humid

Chitradurga Warm & Humid Patna Composite

Dehradun Composite Pune Temperate

Dibrugarh Warm & Humid Raipur Composite

Guwahati Cold Rajkot Composite

Gorakhpur Composite Ramgundam Warm & Humid

Gwalior Composite Ranchi Composite

Hissar Composite Ratnagiri Warm & Humid

Hyderabad Composite Raxaul Warm & Humid

Imphal Warm & Humid Saharanpur Composite

Indore Composite Shillong Warm & Humid

Jabalpur Composite Sholapur Hot & Dry

Jagdelpur Warm & Humid Srinagar Cold

Jaipur Composite Sundernagar Cold

Jaisalmer Hot & Dry Surat Hot & Dry

Jalandhar Composite Tezpur Warm & Humid

Jamnagar Warm & Humid Tiruchirappalli Warm & Humid

Jodhpur Hot & Dry Trivandrum Warm & Humid

Jorhat Warm & Humid Tuticorin Warm & Humid

Kochi Warm & Humid Udhagamandalam Cold

Kolkata Warm & Humid Vadodara Hot & Dry

Kota Hot & Dry Veraval Warm & Humid

Kullu Cold Vishakhapatnam Warm & Humid

Page 100: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix F: Air-Side Economizer Acceptance Procedures Envelope Summary

13. Appendix F: Air-Side Economizer Acceptance Procedures Envelope Summary

13.1 Construction Inspection

Prior to Performance Testing, verify and document the following:

(a) System controls are wired correctly to ensure economizer is fully integrated (i.e. economizer will

operate when mechanical cooling is enabled).

(b) Economizer lockout control sensor location is adequate (open to air but not exposed to direct

sunlight nor in an enclosure; away from sources of building exhaust; at least 8 m away from

cooling towers).

(c) System is provided with barometric relief, relief fan or return fan to control building pressure.

13.2 Equipment Testing

Step 1: Simulate a cooling load and enable the economizer by adjusting the lockout control setpoint.

Verify and document the following:

(a) Economizer damper modulates opens to 100% outside air.

(b) Return air damper modulates closed and is completely closed when economizer damper is 100%

open.

(c) Economizer damper is 100% open before mechanical cooling is enabled.

(d) Relief fan or return fan (if applicable) is operating or barometric relief dampers freely swing

open.

Step 2: Continue from Step 1 and disable the economizer by adjusting the lockout control setpoint. Verify

and document the following:

(a) Economizer damper closes to minimum ventilation position.

(b) Return air damper opens to at or near 100%.

(c) Relief fan (if applicable) shuts off or barometric relief dampers close. Return fan (if applicable) may still operate even when economizer is disabled.

Page 101: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix G: Compliance Forms

Energy Conservation Building Code 2016 91

14. Appendix G: Compliance Forms

14.1 Envelope Summary

Envelope Summary ENVELOPE Summary2005 India Energy Conservation Building Code Compliance Forms Draft 1, 27 March 2005

Project Info Project Address Date

For Building Department Use

Applicant Name:

Applicant Address:

Applicant Phone:

Project Description

Compliance Option

Total Vertical Fenestration

Area

(rough opening) divided by

Gross Exterior

Wall Area times 100 equals

% Vertical

Fenestration

X 100 =

Total Skylight Area

(rough opening) divided by

Gross Exterior

Wall Area times 100 equals % Skylight

X 100 =

Hospital, hotel, call center (24 hour) Other building type (daytime)

OPAQUE ASSEMBLY OPAQUE ASSEMBLY

Roof Minimum Insulation R-value Roof Minimum Insulation R-value

Wall Minimum Insulation R-value Wall Minimum Insulation R-value

FENESTRATION FENESTRATION

Vertical Vertical

Maximum U-factor Maximum U-factor

Maximum SHGC (or SC) Maximum SHGC (or SC)

Overhang (yes or no) Overhang (yes or no)

If yes, enter Projection Factor If yes, enter Projection Factor

Side fins (yes or no) Side fins (yes or no)

If yes, enter Projection Factor If yes, enter Projection Factor

Skylight Skylight

Maximum U-factor Maximum U-factor

Maximum SHGC (or SC) Maximum SHGC (or SC)

Vertical Fenestration Area

Calculation

Skylight Area Calculation

Note: Vertical fenestration area can not exceed

40% of the gross wall area for prescriptive option.

Check here if using this option and if project meets all requirements for the Concrete/Masonry Option. See

New Building Addition Alteration Change of Use

Prescriptive Envelope Trade-Off (Appendix D) Systems Analysis

Hospital, hotel, call center (24 hour) Other building types (daytime)

Note: Skylight area can not exceed 5% of the gross

roof area for prescriptive compliance.

Page 102: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix G: Compliance Forms

14.2 Building Permit Plans Checklist

Building Permit Plans Checklist ENVELOPE Checklist2005 India Energy Conservation Building Code Compliance Forms Draft 1, 27 March 2005

Project Address Date

Applicability Code Location Building Department

(yes, no, n.a.) Section Component Information Required on Plans Notes

MANDATORY PROVISIONS (Section 4.2)

4.2.1 Fenestration rating

4.2.1.1 U-factor Specify whether per 4.2.1.1 or default in Appendix C

4.2.1.2 SHGC Specify whether per 4.2.1.2 or default in Appendix C

4.2.1.3 Air leakage Specify leakage rates

4.2.2 Opaque U-factors Specify whether per default in Appendix C or ASHRAE

4.2.3 Bldg. env. sealing Indicate sealing, caulking, gasketing, and weatherstripping

PRESCRIPTIVE COMPLIANCE OPTION (Section 4.3)

4.3.1 Roof Indicate R-values on roof sections

4.3.2 Cool roof Indicate minimum reflectance and emittance on plans

4.3.3 Roof Indicate R-values on wall sections

4.3.4 Vertical fenestration

(1) Indicate U-factors on fenestration schedule. Indicate if

values are rated or default. If values are default, then specify

frame type, glazing layers, gapwidth, low-e.

(2) Indicate SHGC or SC on fenestration schedule. Indicate if

values are rated or default.

(3) Indicate if overhangs or side fins are used for compliance

purposes. If so, provide projection factor calculation.

4.3.5 Skylights

(1) Indicate U-factors on fenestration schedule. Indicate if

values are rated or default. If values are default, then specify

frame type, glazing layers, gapwidth, low-e.

(2) Indicate SHGC or SC on fenestration schedule. Indicate if

values are rated or default.

BUILDING ENVELOPE TRADE-OFF OPTION (Section 4.4)

Provide calculations

The following information is necessary to check a building permit application for compliance with the building envelope requirements in the

2005 India Energy Conservation Building Code.

Page 103: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix G: Compliance Forms

Energy Conservation Building Code 2016 93

14.3 Mechanical Summary

Mechanical Summary MECHANICAL Summary2005 India Energy Conservation Building Code Compliance Forms Draft 1, 27 March 2005

Project Info Project Address

For Building Dept. Use

Applicant Name:

Applicant Address: 0

Applicant Phone: 0

Project Description

Briefly describe mechanical

system type and features.

FALSE

Compliance Option

Equipment Schedules

Cooling Equipment ScheduleEquip.

ID Brand Name Model No.

Capacity

kW Total L/s

OSA CFM

or Econo?

SEER

or EER IPLV Location

Heating Equipment ScheduleEquip.

ID Brand Name Model No.

Capacity

kW Total L/s

OSA cfm

or Econo? Input kW Output kW Efficiency

Fan Equipment ScheduleEquip.

ID Brand Name Model No. Total L/s SP kW Flow Control Location of Service

The following information is required to be incorporated with the mechanical equipment schedules on the plans.

For projects without plans, fill in the required information below.

Simple System Complex System Systems Analysis

Includes Plans

Date

Page 104: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix G: Compliance Forms

14.4 Mechanical Checklist

Mechanical Permit Checklist MECHANICAL Checklist2005 India Energy Conservation Building Code Compliance Forms Draft 1, 27 March 2005

Project Address Date

Applicability Code Location Building Department

(yes, no, n.a.) Section Component Information Required on Plans Notes

HEATING, VENTILATING, AND AIR CONDITIONING (Chapter 5)

MANDATORY PROVISIONS (Section 5.2)

5.2.1 Equipment effficiency Provide equipment schedule with type, capacity, efficiency

5.2.2 Controls

5.2.2.1 Timeclocks

Indicate thermostat with night setback, 3 different day types,

and 2-hour manual override

5.2.2.2 Temp. & deadband

Indicate temperature control with 3 degree C deadband

minimum

5.2.2.3 Clg.tower, fluid cooler

Indicate two-speed motor, pony motor, or variable speed drive

to control the fans

5.2.3 Piping & ductwork Indicate sealing, caulking, gasketing, and weatherstripping

5.2.3.1 Piping insulation Indicate R-value of insulation

5.2.3.2 Ductwork insulation Indicate R-value of insulation

5.2.3.3 Ductwork sealing Specify sealing types and locations

5.2.4 System balancing Specify system balancing

PRESCRIPTIVE COMPLIANCE OPTION (Section 5.3)

5.3

Indicate whether project is complying with ECBC Prescriptive

Option OR with ASHRAE Standard 90.1-2004

5.3.1 Economizer

5.3.3.1 Air economizer Indicate 100% capability on schedule

5.3.3.2 Integrated operation Indicate capability for partial cooling

5.3.3.3 Field testing Specify tests

5.3.2 Variable flow hydronic

5.3.3.1 Pump flow rates Indicate variable flow capacity on schedules

5.3.3.2 Isolation valves Indicate two-way automatic isolation valves

5.3.3.3 Variable speed drive Indicate variable speed drive

SERVICE WATER HEATING AND PUMPING (Chapter 6)

MANDATORY PROVISIONS (Section 6.2)

6.2.1 Solar water heating Provide calculations to justify capacity to meet 20% threshold

6.2.2 Equipment effficiency Provide equipment schedule with type, capacity, efficiency

6.2.3 Piping insulation Indicate R-value of insulation

6.2.4 Heat traps

Indicate heat trap on drawings or provide manufacturers

specifications to show that equipment has internal heat trap

6.2.5 Pool covers Provide vapor retardant cover for pools

6.2.5 Pools over 32 C Provide R-2.1 insulation

The following information is necessary to check a building permit application for compliance with the mechanical requirements in the 2005

India Energy Conservation Building Code.

Page 105: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix G: Compliance Forms

Energy Conservation Building Code 2016 95

14.5 Lighting Summary

Lighting Summary LIGHTING Summary2005 India Energy Conservation Building Code Compliance Forms Draft 1, 27 March 2005

Project Info Project Address Date

For Building Department Use

Applicant Name:

Applicant Address: 0

Applicant Phone:

Project Description

Compliance Option

Alteration Exceptions Less than 50% of the fixtures are new and installed lighting wattage is not being increased

(check box, if appropriate)

Maximum Allowed Lighting Wattage (Interior, Section 7.3)Location

(floor/room no.) Occupancy Description

Allowed

Watts per m2 ** Area in m

2Allowed x Area

0.0

0.0

0.0

** Document all exceptions Total Allowed Watts 0.0

Proposed Lighting Wattage (Interior)Location

(floor/room no.) Fixture Description

Number of

Fixtures

Watts/

Fixture

Watts

Proposed

0.0

0.0

0.0

Total Proposed Watts may not exceed Total Allowed Watts for Interior Total Proposed Watts 0.0

Maximum Allowed Lighting Wattage (Exterior, Section 7.4)

Location Description

Allowed Watts

per m2 or per lm

Area in m2

(or lm for perimeter)

Allowed Watts

x m2 (or x lm)

0.0

0.0

0.0

0.0

0.0

Total Allowed Watts 0.0

Proposed Lighting Wattage (Exterior)

Location Fixture Description

Number of

Fixtures

Watts/

Fixture

Watts

Proposed

0.0

0.0

0.0

Total Proposed Watts may not exceed Total Allowed Watts for Exterior Total Proposed Watts 0.0

Change of UseNew Building Addition Alteration

Prescriptive Systems Analysis

Page 106: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Appendix G: Compliance Forms

14.6 Lighting Permit Checklist

Lighting Permit Checklist LIGHTING Checklist2005 India Energy Conservation Building Code Compliance Forms Draft 1, 27 March 2005

Project Address Date

Applicability Code Location Building Department

(yes, no, n.a.) Section Component Information Required on Plans Notes

LIGHTING (Chapter 7)

MANDATORY PROVISIONS (Section 7.2)

7.2.1 Controls

7.2.1.1 Automatic shutoff Indicate automatic shutoff locations or occupancy sensors

7.2.1.2 Space control Provide schedule with type, indicate locations

7.2.1.3 Daylight zones Provide schedule with type and features, indicate locations

7.2.1.4 Ext. lighting control Indicate photosensor or astronomical time switch

7.2.1.5 Additional control Provide schedule with type, indicate locations

7.2.2 Tandem wiring Show wiring on schedule

7.2.3 Exit signs Indicate 5 watts maximum

7.2.4 Ext. bldg.grounds ltg. Indicate minimum efficacy of 60 lumens/Watt

PRESCRIPTIVE INTERIOR LIGHTING POWER COMPLIANCE OPTION (Section 7.3)

7.3

Indicate whether project is complying with the Building Area

Method (7.3.1) or the Space Function Method (7.3.2)

7.3.1 Building area method

Provide lighting schedule with wattage of lamp and ballast and

number of fixtures. Document all exceptions.

7.3.2 Space function method

Provide lighting schedule with wattage of lamp and ballast and

number of fixtures. Document all exceptions.

7.3.3 Luminaire wattage Indicate on plans

PRESCRIPTIVE EXTERIOR LIGHTING POWER COMPLIANCE OPTION (Section 7.4)

7.4 Building area method

Provide lighting schedule with wattage of lamp and ballast and

number of fixtures. Document all exceptions.

ELECTRICAL POWER (Chapter 8)

MANDATORY PROVISIONS (Section 8.2)

8.2.1 Transformers Provide schedule with transformer losses

8.2.2 Motor efficiency Provide equipment schedule with motor capacity, efficiency

8.2.3 Power factor correctionProvide schedule with power factor correction

8.2.4 Check metering Provide check metering and monitoring

The following information is necessary to check a building permit application for compliance with the lighting requirements in the 2005 India

Energy Conservation Building Code.

Page 107: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Schedules

Energy Conservation Building Code 2016 97

15. Schedules

Table 15.1 Schedules for Baseline Design of School Buildings

Schedule Type Applicable on

00-0

1

01-0

2

02-0

3

03-0

4

04-0

5

05-0

6

06-0

7

07-0

8

08-0

9

09-1

0

10-1

1

11-1

2

12-1

3

13-1

4

14-1

5

15-1

6

16-1

7

17-1

8

18-1

9

19-2

0

20-2

1

21-2

2

22-2

3

23-2

4

Occupancy Schedule

Student Zones* 5D_Occ 0 0 0 0 0 0 0 0.7 0.9 0.9 0.9 0.2 0.9 0.9 0 0 0 0 0 0 0 0 0 0

Back office** 5D_Occ 0 0 0 0 0 0 0 0 0.9 0.9 0.9 0.9 0.9 0.2 0.9 0.9 0.9 0.5 0 0 0 0 0 0

Lighting Schedule

Student Zones 5D_Light 0 0 0 0 0 0 0 0.9 0.9 0.9 0.9 0.2 0.9 0.9 0 0 0 0 0 0 0 0 0 0

Back office 5D_Light 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.9 0.9 0.9 0.9 0.9 0.3 0.9 0.9 0.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Equipment Schedule

Student Zones 5D_Equip 0 0 0 0 0 0 0 0.35 0.95 0.95 0.95 0.2 0.95 0.95 0 0 0 0 0 0 0 0 0 0

Back office 5D_Equip 0 0 0 0 0 0 0 0.35 0.95 0.95 0.95 0.95 0.95 0.4 0.95 0.95 0.95 0.25 0 0 0 0 0 0

Elevator

HVAC

Student Area 5D_HVAC 0 0 0 0 0 0 0 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0

Back office 5D_HVAC 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0

External Lighting

Ext Light 7D_Ext Light 0.5 0.5 0.5 0.5 0.5 0.5 0 0 0 0 0 0 0 0 0 0 0 0 0.5 0.5 0.5 0.5 0.5 0.5

*Student area is operational for 9 months. ** Back office is operational for 11 months

Page 108: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Schedules

Table 15.2 Schedules for Baseline Design of Assembly Buildings

Schedule Type Applicable on

00-0

1

01-0

2

02-0

3

03-0

4

04-0

5

05-0

6

06-0

7

07-0

8

08-0

9

09-1

0

10-1

1

11-1

2

12-1

3

13-1

4

14-1

5

15-1

6

16-1

7

17-1

8

18-1

9

19-2

0

20-2

1

21-2

2

22-2

3

23-2

4

Occupancy Schedule

All All days_Occ 0 0 0 0 0 0 0 0 0.2 0.2 0.2 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.5 0.2 0.2 0.2 0.1 0.1

Lighting Schedule

All All Days_Light 0 0 0 0 0 0 0 0 0.4 0.75 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.4 0.4 0.4 0.1 0.1

Equipment Schedule

All All days_Equip 0 0 0 0 0 0 0 0 0.3 0.5 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.5 0.3 0.3 0.3 0 0

Elevator

All All days_Elev 0 0 0 0 0 0 0 0 0.2 0.5 0.5 0.15 0.15 0.15 0.15 0.15 0.35 0.5 0.5 0.4 0.2 0.2 0 0

HVAC

All All days_HVAC 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0

External Lighting

All All days_Ext Light 0.5 0.5 0.5 0.5 0.5 0.5 0 0 0 0 0 0 0 0 0 0 0 0 0.5 0.5 0.5 0.5 0.5 0.5

Service Hot Water N/A

Basement Ventilation N/A

Basement Lighting N/A

Page 109: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Schedules

Energy Conservation Building Code 2016 99

Table 15.3 Schedules for Baseline Design of University Buildings (Non-Residential Only)

Schedule Type Applicable on

00-0

1

01-0

2

02-0

3

03-0

4

04-0

5

05-0

6

06-0

7

07-0

8

08-0

9

09-1

0

10-1

1

11-1

2

12-1

3

13-1

4

14-1

5

15-1

6

16-1

7

17-1

8

18-1

9

19-2

0

20-2

1

21-2

2

22-2

3

23-2

4

Occupancy Schedule

Student area 5D_Occ 0 0 0 0 0 0 0 0.4 0.9 0.9 0.9 0.9 0.9 0.1 0.9 0.9 0.9 0.4 0 0 0 0 0 0

Back office 5D_Occ 0 0 0 0 0 0 0 0 0.9 0.9 0.9 0.9 0.9 0.2 0.9 0.9 0.9 0 0 0 0 0 0 0

Library and comp center 7D_Occ 0 0 0 0 0 0 0 0 0.3 0.4 0.5 0.5 0.5 0.2 0.5 0.5 0.5 0.5 0.6 0.6 0.6 0.6 0.6 0

Lighting Schedule

Student area 5D_Light 0 0 0 0 0 0 0 0.9 0.9 0.9 0.9 0.9 0.9 0.6 0.9 0.9 0.9 0.9 0 0 0 0 0 0

Back office 5D_Light 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.9 0.9 0.9 0.9 0.9 0.3 0.9 0.9 0.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Library and comp center 7D_Light 0 0 0 0 0 0 0 0 0.9 0.9 0.9 0.9 0.9 0.2 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.0

Equipment Schedule

Student area 5D_Equip 0 0 0 0 0 0 0 0.35 0.95 0.95 0.95 0.95 0.95 0.2 0.95 0.95 0.95 0.95 0 0 0 0 0 0

Back office 5D_Equip 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.35 0.95 0.95 0.95 0.95 0.95 0.4 0.95 0.95 0.95 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Library and comp center 7D_Equip 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.8 0.8 0.8 0.8 0.8 0.8 0

Elevator N/A

HVAC

Student Area 5D_HVAC 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0

Back office 5D_HVAC 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0

Library and comp center 7D_HVAC 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0

External Lighting

Ext Light 7D_Ext Light 0.5 0.5 0.5 0.5 0.5 0.5 0 0 0 0 0 0 0 0 0 0 0 0 0.5 0.5 0.5 0.5 0.5 0.5

Service Hot Water N/A

Basement Ventilation N/A

Basement Lighting N/A

*Student area is operational for 9 months **Back office area is operational for 11 months

Page 110: Energy Conservation Building Code · Energy Conservation Building Code 2016 1 1. Purpose The purpose of this code is to provide minimum requirements for the energy-efficient design

Schedules

Table 15.4 Schedules for Baseline Design of Office Buildings

Schedule Type

Applicable on

00-0

1

01-0

2

02-0

3

03-0

4

04-0

5

05-0

6

06-0

7

07-0

8

08-0

9

09-1

0

10-1

1

11-1

2

12-1

3

13-1

4

14-1

5

15-1

6

16-1

7

17-1

8

18-1

9

19-2

0

20-2

1

21-2

2

22-2

3

23-2

4

Occupancy Schedule

Office (8 hrs) Weekdays_Occ 0 0 0 0 0 0 0 0.1 0.2 0.95

0.95

0.95

0.95

0.5 0.95

0.95

0.95

0.95

0.3

0.1 0.1 0.1 0 0

Office (24 hrs) All Days_Occ 0.9 0.9 0.9 0.9 0.5 0.2 0.1 0.1 0.9 0.9 0.9 0.9 0.9 0.2 0.9 0.9 0.9 0.9 0.9

0.2 0.9 0.9 0.9 0.9

Lighting Schedule

Office (8 hrs) Weekdays_Light 0.05

0.05

0.05

0.05

0.05

0.05

0.1 0.3 0.9 0.9 0.9 0.9 0.9 0.5 0.9 0.9 0.9 0.95

0.5

0.3 0.3 0.2 0.1 0.05

Office (24 hrs) All Days_Light 0.9 0.9 0.9 0.9 0.5 0.05

0.05

0.9 0.9 0.9 0.9 0.9 0.9 0.5 0.9 0.9 0.9 0.9 0.9

0.9 0.9 0.9 0.9 0.9

Equipment Schedule

Office (8 hrs) Weekdays_Equip 0 0 0 0 0 0 0 0 0.1 0.9 0.9 0.9 0.9 0.8 0.9 0.9 0.9 0.9 0.5

0.1 0.1 0 0 0

Office (24 hrs) All days_Equip 0.95

0.95

0.95

0.95

0 0 0 0.95

0.95

0.95

0.95

0.95

0.95

0.2 0.95

0.95

0.95

0.95

0.2

0.95

0.95

0.95

0.95

0.2

Elevator

Office (8 hrs) Weekdays_Elev 0.05

0.05

0.05

0.05

0.05

0.05

0.2 0.4 0.5 0.5 0.35

0.15

0.15

0.15

0.15

0.15

0.15

0.35

0.5

0.5 0.4 0.3 0.05

0.05

Office (24 hrs) All days_Elev 0.15

0.15

0.15

0.15

0.35

0.5 0.2 0.4 0.5 0.35

0.15

0.15

0.15

0.15

0.15

0.15

0.35

0.5 0.5

0.35

0.15

0.15

0.15

0.15

HVAC

Office (8 hrs) Weekdays_HVAC 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0

Office (24 hrs) All days_HVAC 1 1 1 1 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

External Lighting

Basement All days_Ext Light 0.5 0.5 0.5 0.5 0.5 0.5 0 0 0 0 0 0 0 0 0 0 0 0 0.5

0.5 0.5 0.5 0.5 0.5

Basement Ventilation

Basement All days_Basem Vent

0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0

Basement Lighting

Basement All days_Basem Light

0.05

0.05

0.05

0.05

0.05

0.05

0.05

0.05

1 1 1 1 1 1 1 1 1 1 1 1 1 0.05

0.05

0.05

(schedules for other buildings to be added in similar format)