® SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller 369-261d 1 02.09.12 Energi Savr NodeT The Energi Savr NodeT family is a group of modular products for the control of lighting loads. This document describes the following products: • Energi Savr NodeT for 0-10 V/Switching (model QSNE-4T10-D) • Energi Savr NodeT for Switching only (model QSNE-4S10-D) Features • Default configuration requires no commissioning. • System programming accomplished manually at the unit. • Two occupancy sensor inputs for automated control of lights in areas. • Two daylight sensor inputs automatically adjust light levels based on the amount of natural light entering through the windows. • Two IR receiver inputs for personal control. • Includes QS link for seamless integration of lights, motorized window treatments, and control stations. • Energi Savr NodeT units can be used in a QuantumR system to control and manage light in an entire building. N1771 Z096 QSNE-4T10-D QSNE-4S10-D System Example LUTRON LUTRON QS Link Energi Savr NodeT Energi Savr NodeT unit GRAFIK EyeR QS QS Contact Closure Interface QuantumR Panel Energi Savr NodeT Programming Interface seeTouchR QS Wallstation Wired IR Receiver IR Transmitter Wired Daylight Sensor 2 Wired Occupancy Sensor Contact Closure Input Up to 100 total QS devices 220-240 V~ Control Power One input group shown; connections available for two input groups Wireless Communication QS Sensor Module (QSM) QS Power Supply Radio Powr SavrT Occupancy Sensor (up to 10 per QSM) Radio Powr SavrT Daylight Sensor 2 (up to 10 per QSM) PicoR Wireless Controller (up to 10 per QSM) Wired Daylight Sensors 1, 2 Wired Occupancy Sensors 1 Wired IR Receivers 1 Note: Multiple QSMs can be added to increase the number of wireless inputs and PicoR wireless controllers. 4 switched outputs, 10 AX each (zones 1-4) 4 0-10 V outputs (zones 1-4) (model QSNE-4T10-D only) Notes: 1 Up to four wired inputs total (of any type). 2 See “Daylight Sensors” in “Specifications” section for sensor count options. IR Transmitter
18
Embed
Energi Savr Node T - Lutron Electronics Switching 0-10V 369… · ®SPECIFICA AL Page ob Name: ob Number: Model Numbers: Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
369-261d 1 02.09.12
Energi Savr NodeT
The Energi Savr NodeT family is a group of modular products for the control of lighting loads. This document describes the following products:
•EnergiSavrNodeT for 0-10 V/Switching (model QSNE-4T10-D)
•EnergiSavrNodeT for Switching only (model QSNE-4S10-D)
level (100%) when the occupancy sensor is in the occupied state (closed) and off when in the unoccupied state (open)
Daylight Sensors (Photo)•WhenutilizedinconjunctionwithaLutronoccupan-cysensor,correspondingzoneswillturnonwhenlight sensed by the daylight sensor falls below the factory preset level (if occupancy sensor indicates that area is occupied).
•QSNE-4S10-Donly:Correspondingzoneswillturnoff when light sensed by daylight sensor rises above the factory preset level.
•QSNE-4T10-Donly:Correspondingzonelightlevelswill raise or lower when light sensed by daylight sensor falls below or rises above the factory default setting.
IR Receivers (IR)•CorrespondingzonesrespondtoOn,Off,andScenecommandsfromcompatibleIRtransmitters(seeIRSensorliteratureforcompatibletransmitters).
•IftheCCIisopen,theEnergiSavrNodeT unit will enterEmergencyMode,whichwillturnonallloadsand disable local zone control and control from sen-sors and QS devices.
•WhentheCCIisclosedorjumpered,EnergiSavrNodeT unit zones will return to the settings or levels they were at prior to entering Emergency Mode.
Normal Mode Operation•Zoneandraise/lowerbuttonsontheunitcanbe
used to: — turn loads on and off (QSNE-4S10-D and
QSNE-4T10-D) — dim loads up and down (QSNE-4T10-D only).•SensorstatusLEDs(‘Occ’,‘Photo’,and‘IR’)verify
connections to control stations and sensors.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
the Energi Savr NodeT.•ManualProgramming:upto4occupancysensors
wired directly to the Energi Savr NodeT,upto4 occupancy sensors wired to a QS Sensor Module (QSM),andupto10wirelessoccupancysensorsthrough the same QSM; the total programmed to the Energi Savr NodeTcannotexceed16.
•HHD(Apple iPhone/iPod touch) Programming: upto16occupancysensorsfromanysource(wireddirectly to the Energi Savr NodeT,wiredtoanyotherEnergi Savr NodeT,orwired/wirelessfromanyQSMontheQSlink);thetotalprogrammedtotheEnergiSavr NodeTcannotexceed16.
•UseLutronoccupancysensorstocontroloneor more zones.
•UseLutronoccupancysensorsinvacancymodetoautomatically turn the lights off in an area after it becomes vacant.
•Eachzonecanbeprogrammedtoautomaticallyturnthe lights on when occupied and turn the lights off when vacant.
•EachEnergiSavrNodeT wired occupancy input can power one Lutron occupancy sensor.
with programmable effect on light output.•Twodaylightsensorscanbeconnecteddirectlyto
the Energi Savr NodeT unit.•UseLutronEC-DIR-WHsensorstocontroloneor
more zones.•Additionaldaylightsensorscanbeusedwiththe
Energi Savr NodeTunit.Refertothe“ProgrammingOptionsandFeatures”tableforsystemrules.
Communication with GRAFIK EyeR QS•EnergiSavrNodeTunitzonescanbeconfiguredtorespondtoGRAFIKEyeR QS scene buttons.
•EnergiSavrNodeT unitzonescanbeconfiguredto respond to scene commands initiated by the GRAFIKEyeR QSastronomictimeclock.
•EnergiSavrNodeT unit operates in afterhours modewhenassociatedwithaGRAFIKEyeR QS that is in afterhours mode.
Communication with QSE-IO•EnergiSavrNodeTunitzonescanbeconfigured
to respond to scene commands initiated by the QSE-IOinsceneselectionmode.
•EnergiSavrNodeTunitcanbeconfiguredtorespond to zone toggle or occupancy sensor commandsinitiatedbytheQSE-IOinzonetogglemode or occupancy sensor mode.
Communication with QSE-CI-NWK-E•IntegrateEnergiSavrNodeT units with touchscreens,PCs,A/Vsystemsorotherdigitalsystems and devices.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
369-261d 6 02.09.12
QSM (QS Sensor Module) - Integrating Wired and Wireless Sensors
•UsetheQSMtointegrateRadioPowrSavrT Occupancy/Vacancysensors,RadioPowrSavrT Daylightsensors,andPicoR Wireless Controllers to control zones on the Energi Savr NodeT unit.
QSE-CI-AP-D• Requires Apple iPod touch or iPhone mobile
digital device
Wired Daylight SensorsSystem Limits Maximum of 1 daylight sensor per zone
2 connect directly to the ESN unit Additional daylight sensors can connect to the QSM
Maximum of 2 daylight sensors per zone Up to 100 total daylight sensors per QS link (wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link
Disable daylighting in Scenes No Yes
Wireless Daylight SensorsSystem Limits Maximum of 1 daylight sensor per zone
Associate wireless daylight sensors to the QSM
Maximum of 2 daylight sensors per zone Associate up to 10 wireless daylight sensors per QSM Up to 100 total daylight sensors per QS link (wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same QS link
Disable daylighting in Scenes No Yes
PicoR Wireless ControllersCan be assigned to… Any zone on the local ESN unit Any number of zones or areas on ESN units on same
QS link
IR Receivers and WallstationsSystem Limits 2 connect directly to the ESN unit
Up to 4 wired to the QSMUp to 100 total controls per QS link (wired wallstations, IR receivers)
Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on same QS link
Emergency Contact Closure InputCan be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones
Emergency Light level Configurable Configurable
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredinthe U.S. and other countries.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
369-261d 14 02.09.12
Wiring: Emergency Contact Closure Input
PELV Emergency Contact Closure Input
•ContactClosureInput(CCI)wiringisPELV.Followallapplicable national and local codes for proper circuit separation and protection.
•Wheninemergencymode,allballastsandmoduleswill be at their programmed emergency light level (default is 100%). Sensors and controls will not affect units in emergency mode. Sensors and controls connected to a unit in emergency mode willcontinuetoaffectunitsonthelinkthatarenot in emergency mode.
•Emergencycontactclosureinputisnormallyclosed(NC). The Energi Savr NodeT unit is shipped with a jumperpre-installed.
Note: The Energi Savr NodeT unit will default toEmergencyModeiftheCCIisleftopen.IfnoEmergencycontactinputisrequired,pleaseleavethewirejumperintheCCIterminals.
N1771Z096
N1771Z096
CCI Common
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
369-261d 15 02.09.12
Wiring: QS Link
IEC PELV QS Link Wiring
•LinkcommunicatesusingPELVwiring.
•Followallapplicablenationalandlocalcodesforproper circuit separation and protection.
•Wiringmaybedaisychainedort-tapped.
•TotallengthofQSlinkmustnotexceed600m.
•Forlengthsunder150m,usetwo1,0mm2 conductors for control power (24 V-,COM).
•Forlengthsover150m,usetwo4,0mm2 conductors for control power (24 V-,COM).
•Useone,twisted-shieldedpairof1,0mm2 for data link(MUX,MUX).
N1771Z096
N1771Z096
(1) COM(2) 24 V-
(3) MUX(4) MUX
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
369-261d 16 02.09.12
Wiring: QS Link (continued)
Onlyterminals1,3,and4connected between devices that supply PDUs
Terminal 2 NEVER connected between devices that supply PDUs
Terminal 2 (+24 V) NEVERconnected*
Devices that supply PDUs
Devices that consume PDUs
COM+24 VMUXMUX
COM
MUXMUX
Energi Savr NodeT unit
Energi Savr NodeT unit
QS Input/ Output Interface
Wired QS Keypad
QSM
QSMQSMWired QS Keypad
Wired QS Keypad
Wired QS Keypad
QS Input/ Output Interface
QS Link power supply
QSLink;all 4 terminals
QSLink;
no te
rmin
al 2
QSLink;
no te
rmin
al 2
QSLink;all 4 terminals
QSLink;all 4 terminals
Terminal 2 (+24 V) NEVERconnected*
Terminal 2 (+24 V) NEVERconnected* **
All4terminalsconnectedtoQSlink devices that consume PDUs
QS Link Wiring Rules * Terminal2(+24V)shouldNEVERbeconnectedbetweendevicesthatsupplyPDUs.** ForQSLinkpowersupplywiringconnectiondetails,refertotheinstallationinstructions
for the specific power supply model being used.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
369-261d 17 02.09.12
Wiring: PELV InputsElectrical Contractors and Engineers
•AllinputwiringisPELV.Followallapplicablenationaland local codes for proper circuit separation and protection.
* Note: Only one IR device may be connected per input group. If the IR signal from a daylight sensor is connected, another control may not be connected to the same input, and vice-versa.
** Connect the gray wire on -R Occupancy Sensor models.
IR Transmitter
20 V – 20 V-
IR – IR Receiver *
Photo – Daylight Sensor
Occ – Occupancy Sensor
Com – Common
20 V
– 20 V
-
IR – I
R Re
ceive
r *Co
m –
Com
mon
NOTE: There are two input groups. Each group has the same inputs as shown in the diagram above.
Input Group A Input Group B
Occupancy SensorDaylight/IR Sensor*
Red
Red
Blac
k
Blac
k
Blue
/Gra
y**
Yello
w Red
Blac
kW
hite
*
Whi
te*
IR Receiver*LUTRONR
LUTRONR
LUTRON
IR Transmitter
Group A shown Group B shown
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeT QSNE Switching / 0-10 V Fixture Controller
Manual Programming: •Use buttons on the front of the Energi Savr NodeT unit.•Use manual programming in installations with only one Energi Savr NodeT unit and with one QS Sensor Module(QSM)orfewerontheQSlink.
HHD Programming
•RequiresESNProgrammingInterface(QSE-CI-AP-D).•RequiresApple iPod touch or iPhone mobile digital device.•Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with
multiple Energi Savr NodeTunitsandQSMsontheQSlink.
•WirelessrouteronlyrequiredforprogrammingwithanApple iPod touch or iPhone.•Wirelessroutermayberemovedfornormaloperation.•EthernetconnectionmaybemadeviaananEnergiSavrNodeTProgrammingInterface(QSE-CI-AP-D)oran
Energi Savr NodeTunitwithintegralEthernetjack.•LutronrecommendsthatanEnergi Savr NodeTProgrammingInterface(orEnergi Savr NodeT unit with Ether-netjack)bewiredtoanEthernetjackinthespaceforeaseofaccessandproximitytopowerforthewirelessrouter.
•Workswithanystandardwirelessrouterthatsupportsmulticastpackets.•Apple iPod touch or iPhone can program all Energi Savr NodeT units connected to an Energi Savr NodeT ProgrammingInterfaceviatheQSLink(exceptwhenpartofaQuantumR system).