2017 Product overview
2017Product overview
During these years, the activity of Emicon has been developed with the production of liquid chillers for air conditioning and industrial applications, close control units, heat pumps, roof top and, thanks to its considerable production flexibility, special tailor-made
units.
Presently, due to the great experience achieved in the market and the professionalism of its engineers, Emicon is a leader company between the international manufac-turers, able to give adequate and effective answers to all requirements of civil and industrial air conditioning.
The research of the environmental quality represents for Emicon AC a basic choice for all the technological applications realized each time. On this purpose, environmental compatibility means efficiency optimiza-tion, mainly facing two topical subjects: the sound level and the ozone problems.
It is the awareness of environmental issues who moved Emicon AC to persevere with research, development and certification, to add, to its ca-
talogue, units that use new refrigerants with low environmental impact such as HFO 1234ze with very high efficiency and low GWP (= 6) or the
ecological gas R290 (GWP = 3).
Different type of units are carefully checked in available laboratories and climatic chambers:
· Laboratory for the performances check of air and water cooled close control units.· Laboratory for the performances check of water cooled chillers and heat pumps and air
cooled water chillers.· Climatic chamber provided with a double circuit with chilled and hot water for testing air
and water cooled chillers and heat pumps, with desuperheater or total heat recovery, 4-pipe and split units.
· Two areas for acoustic tests; one inside room for close control and small size units and a wider outside room for measurements on units up to 1.500 kW.
Thanks to some webcams, after agreements with the sales department, it’s possible to remotely attend the standard factory test carried out on all units before their departure from our facilities.
Project air conditioningEvolution goes on
The environment Efficiency and sustainability
Emicon Labsnew climatic chambers
In order to assure the end customer satisfaction, keeping a leadership position on the market and at the same time aiming to a
continous improvement of the company internal working conditions and of its environmental performances, EMICON intends to
promote in its organization the culture of Quality and Environment Protection and it is therefore extremely important the pollution
preventing and the constant respect of the environmental regulations.
EMICON is perfectly aware that the market requests are the driving motor of the company activity and that an organization metho-
dically managed in its processes represents a topical factor for the customer satisfaction. In order to achieve such results, EMICON
believes it is important to develop and to improve its Quality and Environmental Service as the basic tool for supporting all the
company processes. On this purpose, it is really important for EMICON, for its own success, to aim to the training, the involvement
and the motivations of the whole staff working in a healthy environment and with the necessary facilities for a correct execution of
their own working activities.
EMICON Innovation and Comfort ,which is an EMICON AC SPA directly controlled subsidiary, designs, develops, produces and
supplies air cooled chillers mainly intended for residential air conditioning market.
Environmental Policy
Research & quality
Emicon Innovation and Comfort
BIBLIOTEQUE NAT
2010
Cooling Capacity KW
Close Control N°65
UNIVERSITY OF TURIN - HUMANISTIC FACULTY
2012
Cooling Capacity KW 3.800
Air Cooled Chillers Model N° 4 Units RAH 912 U Ka – SP Screw
EMIRATES IDENTITY AUTHORITY
2014
Cooling Capacity KW 516
Close Control Unit Model N° 6 Units ED.X 1462 KA Scroll
ISOZAKI MILAN TOWER
2014/2016
Cooling Capacity KW 1.310
Close Control Unit Model N°7 Units ED.X + N°49 Units EDH
OSTRODA ARENA
2012
Cooling Capacity KW 1.668
Air Cooled Chillers N°5 Units RAE + Evaporating Units + Condensing Units
TOUR D2 PARIS
2012
Cooling Capacity KW 475
Close Control Unit N° 8 Units UW
VODAFONE MADRID
2013/2014
Cooling Capacity KW 1.032
Close Control N° 68 Units ED.X
Reference book
TIONALE DE FRANCE – PARIS
W 2.266
5 Units UW
CENTER MASDAR CITY
2016
Cooling Capacity KW 3.260
Water Cooled Chillers Models N°1 RWC + 2 RWH + 1RWE
PARK HOSPITAL ISTAMBUL
2016
Cooling Capacity KW 2.700
Air Cooled Chillers Model N° 2 Units RAH 1102 T Ka Screw
VW – WOLFSBURG
2009/2016
Cooling Capacity KW 1.700
Air Cooled Chillers Model N°2 Units RWE 4792 Kc Scroll - Water Cooled Chillers Model N°3 Units RAH 3602 FU Ka Screw
6
ED.X D 71 101 161 271 421 591 771 991 282 422 642 852 1122 1462
kW 6,7 9,3 15,8 24,8 39,5 55,6 72,5 94,1 24,6 40,2 61,1 80,1 104,2 138,4
kW 6,1 8,8 14,6 22,5 34,4 48,0 60,9 87,0 22,8 31,2 50,2 71,0 82,2 106,2
kW 1,7 2,2 3,8 5,5 9,5 12,3 16,2 21,3 5,8 9,7 14,5 19,1 25,2 32,5
% 91 94 92 91 87 86 84 92 93 78 82 89 79 77
kW/kW 3,20 3,52 3,48 3,73 3,48 3,56 3,62 3,51 3,28 3,49 3,43 3,49 3,36 3,45
m3h 2.330 2.330 3.500 5.610 7.880 13.820 16.550 21.600 7.800 7.880 13.820 16.550 21.600 27.200
AIR
H2O
U B
Direct expansion close control units
with remote air condensers
Cooling capacity from 6,7 to 138 kW
Available configurations,
related to the air
return and discharge
Discharge Discharge
Return
Return
Configurations
U Front air return, upflow air discharge
V Bottom air return, upflow air discharge
B Back air return, upflow air discharge
D Top air return, downflow air discharge
Versions
ED.X With remote air condenser
ED.H With water cooled condenser on board
ED.E With remote air condensing unit
Total Cooling Capacity (24°C - 50% U.R.)
Sensible Cooling Capacity (24°C - 50% U.R.)
Input power
SHR
EER
Air flow
AIR
ED.X VS 71 81 101 131 161 211 231 271 281 331 371 421
kW 5,5 8,0 10,6 12,5 16,4 20,5 23,1 26,5 26,2 30,5 32,8 29,2
kW 5,5 7,8 9,6 12,2 14,8 19,5 22,0 23,7 25,7 27,5 30,5 28,9
kW 1,2 2,0 2,3 2,8 3,7 5,4 4,9 6,1 6,1 7,1 7,2 5,6
% 100 97 90 97 90 95 95 89 98 90 92 98
kW/kW 3,79 3,51 4,05 3,83 3,89 3,35 4,02 3,81 3,67 3,74 3,92 4,33
m3h 2.580 2.580 2.580 3.800 3.800 6.050 6.050 6.050 8.150 8.150 8.150 8.150
V D
Discharge
Discharge
Return
Return
Direct expansion close control units
with Inverter regulation and remote air condenser
Cooling capacity from 5,5 to 29,2 kW
INVERTER technology
Total Cooling Capacity (24°C - 50% U.R.)
Sensible Cooling Capacity (24°C - 50% U.R.)
Input power
SHR
EER
Air flow
Operation limits
Ambient temperature from 18 to 35°C
Features
· BLDC Compressors (inverter)
· Energy saving
· Wide range of options
8
FC
ED.X F 211 331 501 771 921 332 502 772 922 1442 1462
kW 20,8 30,1 47,8 70,1 80,9 30,6 49,2 69,1 80,9 96,6 93,3
kW 20,2 28,3 47,8 65,2 76,6 28,5 49,2 64,8 76,6 94,3 92,9
kW 4,8 7,3 10,6 16,2 19,1 7,6 11,1 16,8 19,1 22,1 21,3
% 97 94 100 93 95 93 100 94 95 98 100
kW/kW 3,50 3,31 3,39 3,45 3,31 3,26 3,36 3,31 3,31 3,32 3,30
m3h 5.200 5.200 13.300 16.200 16.200 7.100 13.300 16.200 19.300 24.300 24.300
AIR
H2O
Direct expansion close control units
and free cooling coil
Cooling capacity from 20,8 to 93,3 kW
Configurations
U Front air return, upflow air discharge
V Bottom air return, upflow air discharge
B Back air return, upflow air discharge
D Top air return, downflow air discharge
Versions
ED.X F Free-cooling unit with remote air condenser
ED.H F Free-cooling unit with water cooled condenser
Compressor operation mode
Mixed operation mode
Free-coolingoperation mode
Total Cooling Capacity (24°C - 50% U.R.)
Sensible Cooling Capacity (24°C - 50% U.R.)
Input power
SHR
EER
Air flow
Discharge Discharge Discharge
Return Return Return
Operation limits
Ambient temperature from 19 to 35°C
FC
ED.P 51 71 131 161 191 261
kW 6,5 8,8 11,9 14,5 18,5 22,3
kW 6,1 8,3 10,7 13,7 17,1 20,1
kW 2,0 3,0 4,1 5,2 6,1 8,0
% 93 94 89 94 92 90
kW/kW 3,25 2,93 2,90 2,79 3,03 2,79
m3h 1.600 2.200 2.400 3.000 3.400 3.900
AIR
H2O
Compressor operation mode
Mixed operation mode
Free-coolingoperation mode
External air External
airExternal air
Condensingair
Condensing/ambientair
Treated air Treated
airTreated air
Ambient air
Ambient air
Outlet for ambient
Direct expansion or chilled water close control units
with free-cooling system for telecom centres
Cooling capacity from 6,5 to 23,0 kW
Packaged version
ED.P SF.E displacement air diffusion
ED.P SF.U upflow
ED.P SF.D downflow
Split version with remote condenser
ED.A SF.E displacement air diffusion
ED.A SF.U upflow
ED.A SF.D downflow
Chilled water version
UV SF.E displacement air diffusion
UV SF.U upflow
UV SF.D downflow
Total Cooling Capacity (27°C - 45% U.R.)
Sensible Cooling Capacity (27°C - 45% U.R.)
Input power
SHR
EER
Air flow
Operation limits
Ambient temperature from 20°C to 37°C
10
UW D/ UWL D UW70 UW180 UW290 UW490 UW670 UW1240 UW1400 UW1810 UW2250 UWL860 UWL1700 UWL1900 UWL2400 UWL3000
kW 5,0 11,0 18,1 32,3 44,7 83,7 95,7 122,4 154,2 60,8 112,3 130,3 168,1 210,5
kW 5,0 8,9 14,6 25,7 36,1 67,4 76,0 98,3 124,2 48,9 89,8 103,9 136,1 169,2
m3h 0,8 1,9 3,1 5,5 7,7 14,4 16,4 21,0 26,5 10,4 19,3 22,4 28,8 36,1
% 100 81 81 80 81 81 79 80 81 80 80 80 81 80
m3h 2.030 2.030 3.280 5.700 8.200 15.200 16.700 22.050 28.000 11.000 20.000 23.000 31.000 38.000
H2O
Close control units with chilled water coil
Cooling capacity from 5 to 210,5 kW
Total Cooling Capacity (24°C - 50% U.R.)
Sensible Cooling Capacity (24°C - 50% U.R.)
Input power
SHR
Air flow
SLIMVersion
Only in D configuration, available in two working modes:
Return
Discharge Discharge
HP High performance: setting of the fans,
maximizing the heat exchange through the hy-
drophilically treated coil.
ES Energy saving: setting of the fans, maxi-
mizing their energy saving.
Configurations
U Front air return, up flow air discharge (only UW)
V Bottom air return, upflow air discharge (only UW)
D Top air return, downflow air discharge
Versions
UW Close control units with chilled water coil
UWL Close control units with chilled water coil SLIM version
Operation limits
Ambient temperature from 18 to 35°C
FC
AIR
H2O
iR 10 15 20 25kW 10,2 15,3 21,0 24,0
kW 9,2 13,8 18,9 21,6
kW 4,45 6,60 9,00 11,00
% 90 90 90 90
m3h 2.500 3.200 4.000 4.500
mm 300 300 300 300
Rack In-row
close control units inRoW Direct expansion or cooled waterCooling capacity from 10 to 25 kw
Total cooling capacity (External Temperature 35°C - Internal Temperature 35°C - 30% U.R.)
Sensible cooling capacity (External Temperature 35°C - Internal Temperature 35°C - 30% U.R.)
Maximum input power
SHR
Nominal air flow
Width
Hot aisle / cold aisleMode
Internal recirculation inside rack cabinet mode
Hot aisle
Cold aisle
configurations
Hot aisle / cold aisleInternal recirculation inside the rack cabinet
Features
· Compressor with inverter technology – Brushles type - vers. Twin Rotary· Precision temperature control with electronic PLC· Condensation / evaporation fans of the EC type· Electronic expansion valve· High energy efficiency· Remote connections for alarm management· Acoustic attenuation of the optimized type
12
AIR
RAE 801 1001 1301 1501 1702 2002 2302 2502 2902 3202 3402 3602 3802 4102 4902 5202 5602 6102
kW 77,4 101,6 131,7 146,9 168,1 206,2 228,0 250,0 291,0 323,0 346,0 367,0 383,0 406,0 496,0 538,0 572,0 623,0
kW 27,6 34,4 42,2 49,6 54,0 73,2 82,2 91,2 100,4 114,8 117,2 120,8 129,4 136,0 166,2 187,8 192,8 198,0
kW/kW 2,80 2,95 3,12 2,96 3,11 2,82 2,77 2,74 2,90 2,81 2,95 3,04 2,96 2,99 2,98 2,86 2,97 3,15
m3h 13,3 17,5 22,7 25,3 28,9 35,5 39,2 43,0 50,1 55,6 59,5 63,1 65,9 69,8 85,3 92,5 98,4 107,2
kPa 54 58 54 65 72 59 69 76 79 83 65 77 60 64 76 81 72 81
n° 1 1 2 2 2 3 3 3 3 3 4 4 4 5 5 6 8 8
dB(A) 66 68 68 69 69 69 70 70 71 71 71 71 71 72 72 72 72 73
FC
Air cooled chiller
with scroll compressors and axial fans
Cooling capacity from 5 to 664 kW
Version with copper/aluminum coil arranged as an inverted “M“ (RAE)
Versions
RAE Standard
RAE S Low noise
RAE U Ultra low noise
RAE F Standard with free cooling
RAE FS Low noise with free cooling
RAE MC Standard with microchannel coil aluminum/aluminum
RAE MC S Low noise with microchannel coil aluminum/aluminum
RAE MC HE High efficiency with microchannel coil aluminum/aluminum
Operation limits
Standard unit
Air: from 10 to 42°C; Water (out from evaporator): from 5 to 15°C
Free Cooling unit
Air: from 0 to 42°C; Water (out from evaporator): from 5 to 15°C (from -5 to 15°C with glycol)
Cooling capacity
Absorbed power
EER
Water flow
Pressure drop
Fans
Sound pressure
AIR
FC
RAH 431 521 602 702 802 922 1032 1102 1202
kW 401,5 518,6 579,4 672,7 768,2 883,2 1015,6 1102,4 1187,0
kW 117,8 156,6 181,2 217,4 247,2 289,2 321,8 359,2 395,6
kW/kW 3,41 3,31 3,20 3,09 3,11 3,05 3,16 3,07 3,00
m3h 69,0 89,1 99,6 115,7 132,3 152,0 174,6 189,5 204,1
kPa 30 32 31 27 28 30 35 41 41
n° 8 8 10 10 10 12 14 16 16
dB(A) 78 80 80 80 80 81 82 82 82
Air cooled chillers
with screw compressors and axial fans
Cooling capacity from 387 to 1220 kW
Version with copper/aluminum coil arranged as an inverted “M“ (RAH)
Operation limits
Standard unit
Air: from 15 to 45°C - Water (out from evaporator): from 5 to 15°C
Low noise unit:
Air: from 15 to 40°C - Water (out from evaporator): from 5 to 15°C
Free Cooling unit:
Air: from 0 to 42°C - Water (out from evaporator): from 5 to 15°C (from -5 to 15°C with glycol)
MC Unit:
Air: from 15 to 48°C - Water (out from evaporator): from 5 to 15°C
Cooling capacity
Absorbed power
EER
Water flow
Pressure drop
Fans
Sound pressure
Versions
RAH Standard
RAH S Low noise
RAH F Standard with free cooling
ERAH MC With microchannel coil aluminum/aluminum
ERAH MC HE High efficiency with microchannel coil aluminum/aluminum
14
FC
AIR
RAC 351 411 451 512 562 602 642 682 752 812 853 893 983 1083 1203 1283 1404
kW 359 410 445 510 560 604 640 680 750 810 850 892 984 1084 1190 1280 1398
kW 92,3 113,0 121,0 135,8 151,0 159,2 161,4 173,4 195,0 220,6 221,1 237,9 245,1 271,8 308,7 350,1 367,6
kW/kW 3,89 3,63 3,68 3,76 3,71 3,79 3,97 3,92 3,85 3,67 3,84 3,75 4,01 3,99 3,85 3,66 3,80
m3h 61,7 70,5 76,5 87,7 96,3 103,9 110,1 117,0 129,0 139,3 146,2 153,4 169,2 186,4 204,7 220,2 240,5
kPa 26 21 24 60 68 52 59 65 64 73 53 58 69 61 73 68 81
n° 8 8 8 8 10 10 10 10 12 12 14 14 14 16 20 20 20
dB(A) 71 71 71 72 74 74 74 74 74 74 74 74 74 76 75 75 75
Air cooled chillers
with brushless oil-free compressors and axial fans
Cooling capacity from 359 to 1398 kW
Versions
RAC Standard
RAC U Ultra low noise
RAC HE High-efficiency
RAC FS Low noise with Free Cooling
Operation limits
AIR: from -8°C to +42°C
AIR: from -20°C to +42°C with EC brushless fans (option)
WATER (out from evaporator): from 4 to 25°C
Features
· External installation with very low sound level
· Cooling circuit with no lubricating oil entrainment
· High capacities and compact design
· Frequency controlled capacity regulation with a remarkable precision on the adjustment of the discharge temperature
· Slight inrush current
· Maximum efficiency with remarkable ESEER values
Cooling capacity
Absorbed power
EER
Water flow
Pressure drop
Fans
Sound pressure
H2O
RWH Ka 281 321 361 421 452 491 562 551 601 642 732 852 992 1102 1202
kW 279,9 321,1 365,5 424,4 448,6 489,0 558,3 551,4 601,5 654,8 731,4 848,3 994,3 1111,3 1227,6
kW 56,4 64,7 74,2 86,2 94,4 97,4 111,9 113,3 124,1 129,9 148,1 170,3 192,8 226,2 245,8
kW/kW 4,96 4,96 4,93 4,92 4,75 5,02 4,99 4,87 4,85 4,97 4,94 4,98 5,16 4,91 4,99
m3h 48,0 55,1 62,7 72,8 77,0 83,9 95,8 94,6 103,2 110,8 125,5 145,6 170,7 190,7 210,7
kPa 15,6 18,0 22,3 29,9 22,7 19,9 32,1 23,9 28,8 38,7 30,8 36,5 43,3 50,1 36,3
dB(A) 75,5 75,7 75,6 75,7 75,4 75,4 78,8 75,7 77,8 77,6 77,8 77,8 77,7 78,1 78,8
Water cooled water chillers
Potenza frigorifera da 5 A 2104 kW
RWE Kc - RWE Ka - With SCROLL compressors
(from 5 to 475 kW)
Versions
RWE Ka with ecological refrigerant charge R134a
RWE Kc with ecological refrigerant charge R410A
Operation limits
EVAPORATOR (OUT): from 5 to 15°C
CONDENSER (OUT): from 30 to 55°C
RWH Ka - with SCREW compressors
(from 280 to 1228 kW)
RWH Ka with ecological refrigerant charge R134a
Operation limits(standard units)
EVAPORATOR (out): from 5 to 15°C
CONDENSER (out): from 30 to 58°C
RWC Ka - With brushless oil-free compressors
(da 282 a 2104 kW)
RWC Ka with ecological refrigerant charge R134a
Operation limits(standard units)
EVAPORATOR (out): from 5 to 20°C
CONDENSER (out): from 25°C to 50°C
Cooling capacity
Absorbed power
EER
Water flow
Pressure drop
Sound pressure
16
AIR
FC
RAS 601 801 1301 1601 1701 2002 2302 2502 2802 3002 3302 3502 4304
kW 57,7 79,2 114,1 150,5 171,1 190,9 225,3 244,5 276,3 300,6 326,1 342,6 426,5
kW 15,6 21,9 32,1 46,0 51,5 55,0 65,3 75,5 86,5 93,4 99,8 103,1 133,3
kW/kW 3,70 3,62 3,55 3,27 3,32 3,47 3,45 3,24 3,19 3,22 3,27 3,32 3,20
m3h 9,9 13,7 19,6 25,8 29,4 32,8 38,7 42,0 47,5 51,7 56,0 58,9 73,3
kPa 56 33 46 57 56 32 35 36 38 39 36 36 35
n° 1 1 2 2 2 2 3 3 3 3 4 4 4
dB(A) 68 70 72 74 75 74 73 75 76 76 76 76 76
Air cooled water chillers
with semi-hermetic reciprocating compressors and axial fans, with natural refrigerant
Cooling capacity from 56 to 426 kW
Versions
RAS Standard
RAS S Low noise
RAS F Standard with free cooling
Features
· Liquid solution chillers.
· Outdoor installation.
· ATEX Semi-hermetic reciprocating compressors.
· Axial fans.
· Natural refrigerant units with no environmental impact.
· Maximum efficiency, minimum sound emissions.
· Wide range of options.
Operation limits
Standard unit
AIR: from 10°C to +40°C WATER (out from evaporator): from 5 to 15°C.
Free Cooling unit:
AIR: from 0°C to +40°C WATER: from 5 to 15°C (from -5 to +15°C with glycol).
Cooling capacity
Absorbed power
EER
Water flow
Pressure drop
Fans
Sound pressure
FC
RWC Kh 281 502 562 602 702 863 923
kW 254,0 452,4 502,2 544,4 634,6 776,4 808,2
kW 52,6 91,4 103,8 116,6 127,0 161,7 177,9
kW/kW 4,83 4,95 4,84 4,67 5,00 4,80 4,66
dB(A) 75 78 78 78 79 80 80
RAC Kh 512 562 602 853 893
kW 460 504 544 765 803
kW 135,8 151,0 159,2 221,1 237,9
kW/kW 3,39 3,34 3,42 3,46 3,38
dB(A) 72 74 74 74 74
AIR
H2O
Cooling capacity
Absorbed power
EER
Sound pressure
Cooling capacity
Absorbed power
EER
Sound pressure
Air and water cooled chiller
with brushless oil-free compressors and axial fans
RAC Kh: Cooling capacity from320 to 1258 kW · RWC Kh: Cooling capacity from 250 to 1890 kW
Versions
RAC Standard
RAC U Ultra low noise
RAC HE High efficiency
RAC FS Ultra low noise with Free Cooling
Operation limits RAC Kh
AIR: from -8°C to +42°C with fans regulated by inverter
AIR: from -20°C to +42°C with EC brushless fans (option)
WATER (out from evaporator): from 4 to 25°C
Operation limit for free-cooling version: RAC FS Kh
AIR: from -8°C a +42°C with fans regulated by inverter
AIR: from -20°C a +42°C with EC brushless fans (option)
WATER (out from evaporator): from 4 to 25°C
Operation limits RAC Kh
EVAPORATOR: Max water temperature inlet 25°C
CONDENSER: Min. /max. inlet water temperature 20°C / 50°C
Features
· External installation with very low sound level
· Cooling circuit with no lubricating oil entrainment
· High capacities and compact design
· Frequency controlled capacity regulation with a remarkable precision on the adjustment of the discharge temperature
· Slight inrush current
· Maximum efficiency with remarkable ESEER values
18
AIR
PAH Ka 431 521 602 702 802 922 1032 1102
kW 463,8 595,0 678,6 795,6 901,3 1050,2 1189,1 1297,4
kW/kW 4,17 4,08 3,95 4,00 4,06 4,06 4,07 3,90
dB(A) 78 80 80 80 80 81 81 82
PAE Kc 801 1002 1302 1502 1702 2002 2302 2502 2902 3202 3402 3602 3802 4102 4902 5202 5602 6102
kW 99,3 132,8 162,4 187,9 213,4 262,9 293,7 326,9 373,3 411,0 433,9 462,9 486,1 504,4 619,9 684,5 720,3 782,2
kW/kW 3,5 3,1 3,2 3,4 3,4 3,4 3,4 3,4 3,5 3,5 3,4 3,5 3,5 3,6 3,5 3,5 3,5 3,6
dB(A) 75 78 78 79 79 80 80 80 82 81 82 83 83 84 82 81 84 84
Heating capacity
COP
Sound pressure
Cooling capacity
COP
Sound pressure
Air cooled heat pumps
with SCROLL or SCREW compressors and axial fans
PAE Kc Heating capacity from 99 to 782 kW · PAH Ka Heating capacity from 197 to 778 kW
Versions
PAE Kc Standard
PAE S Kc Low noise
Versions
PAH Ka Standard
PAH S Ka Low noise
PAH U Ka Ultra low noise
Operation limits
Summer mode:
AIR: from 10°C to +42°C WATER (out from evaporator): from 5 to 15°C
Winter mode:
AIR: from 20°C to -8°C WATER: (out from evaporator): max 40°C
AIR: from 20°C to -5°C WATER: (out from evaporator): max 45°C
AIR: from 20°C to 0°C WATER: (out from evaporator): max 50°C
Operation limits
Summer mode:
AIR: from 10°C to +42°C WATER: (out from evaporator): from 5 to 15°C
Winter mode:
AIR: from 20°C to -8°C WATER: (out from evaporator): max 40°C
AIR: from 20°C to -5°C WATER: (out from evaporator): max 45°C
AIR: from 20°C to 0°C WATER: (out from evaporator): max 50°C
FC
AIR
H2O
RTR 2S 572 692 842 812 992 1102 1302 1292 1472 1662 1992 2322 2492 2802 3102 3662
kW 57,4 68,9 83,6 81,4 99,4 111,0 130,0 129,0 140,0 166,0 199,0 229,0 249,0 286,0 310,0 366,0
kW 40,8 51,6 62,8 58,2 73,6 79,1 92,7 91,9 105,7 129,6 146,5 168,6 178,5 202,7 219,3 253,0
kW 16,3 18,6 24,4 22,6 29,2 35,0 38,0 39,4 44,6 48,8 61,0 71,1 80,8 86,0 93,2 117,0
m3h 11000 13200 15400 17600 19800 20900 22000 27500 30800 33000 38500 41000 44000 49500 55000 66000
kPa 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
dB(A) 73 74 75 76 76 76 77 76 77 78 78 79 80 82 82 84
Packaged air to air and air to water roof-top units
with scroll compressors
Cooling capacity from 64 to 406 kW
3S Configuration
Expulsion
Ambient airinlet
Treated airoutlet
External air
Versions
RTR Only cooling
RTR W Only cooling, water condensed
RTP Heat pump version heating/cooling mode
RTP W Heat pump version heating/cooling mode, water condensed
Configurations
2S Mixing of re-circulating and external air (2 dampers)
3S Mixing of re-circulating and fresh air and exhaust of the exceeding internal air through a suitable fan (3 dampers)
TR All re-circulating air (no mixing between re-circulating and external air)
TES Possible mixing with heat recovery and free-cooling (not available for all units)
Total cooling capacity *
Sensible cooling capacity *
Total absorbed power
Air flow
Available pressure
Sound pressure
* Ambient air temperature 27°C / 50% HR - External air 35°C
EMICON A.C. S.p.A. Via A. Volta, 49 - 47014 Meldola (FC) - Tel. (39) 0543 495611 - Fax (39) 0543 495612 - E-mail: [email protected]
1601
0003
2EN
Rev
. 17/
01