EMERGENCYLIGHTING ANDORIENTATIONSYSTEMS

Page 2: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

With more than 20 years experience in the security sector in Turkey and especially in the production of emergency lighting systems, Arsel Elektronik Sistemler San. Tic. Ltd. Sti. We are proud to serve you in the world.

ARSEL It aims to be the solution partner preferred by its customers with its high-quality services that it provides electronically.

Our company aims to gain a good name in the sector with its professionally managed marketing staff.

• Emergency Lighting Fixtures• Emergency Guidance Fixtures• Emergency Battery Packs• Dali Compatible Emergency Lighting Fixtures• Dali Compatible Emergency Guidance Fixtures• Photoluminescent strips and plates

It continues to specialize in providing customized solutions to the needs with competitive prices.

Page 3: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ARSEL-3

Page 4: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

38 EMERGENCY GUIDANCE FIXTURES

39 ARSELLITE RECESSED MOUNT EMERGENCY GUIDANCE FIXTURE

41 ARSELLITE SURFACE EMERGENCY GUIDANCE FIXTURE

43 BETALITE SINGLE FACE EMERGENCY GUIDANCE FIXTURE

45 BETALITE DOUBLE SIDE EMERGENCY GUIDANCE FIXTURE

47 STARLITE EMERGENCY GUIDANCE FIXTURE

49 ORION EMERGENCY GUIDANCE FIXTURE

51 ORION RECESSED MOUNT EMERGENCY GUIDANCE FIXTURE

53 SFS EMERGENCY GUIDANCE FIXTURE

55 DEKOLITE EMERGENCY GUIDANCE FIXTURE

57 DEKOLITE DOUBLE FACE EMERGENCY GUIDANCE FIXTURE

59 DEKOLITE Z EMERGENCY GUIDANCE FIXTURE

61 DEKOLITE Z DOUBLE FACE EMERGENCY GUIDANCE FIXTURE

63 TWINLITE EMERGENCY GUIDANCE FIXTURE

65 ELITELITE EMERGENCY GUIDANCE FIXTURE

67 EKOLITE EMERGENCY GUIDANCE FIXTURE

71 EMERGENCY BATTERY PACK FOR FLUORESCENT'S 72 AK-468 EMERGENCY BATTERY PACK

74 AK-58 EMERGENCY BATTERY PACK

76 AK-54 EMERGENCY BATTERY PACK

4 CONTENS

6 EMERGENCY LIGHTING SYSTEMS TEST AND MAINTENANCE

EMERGENCY LIGHTING FIXTURES

78 EMERGENCY BATTERY PACK FOR LED'S

79 AK 312 EMERGENCY BATTERY PACK

81 AK 4600 EMERGENCY BATTERY PACK

83 AK-4600S-EKO EMERGENCY BATTERY PACK

85 AK-7200 EMERGENCY BATTERY PACK

87 AK-609 EMERGENCY BATTERY PACK

89 AK-2400 EMERGENCY BATTERY PACK

91 VS-12-L EMERGENCY BATTERY PACK

CONTENS

8

VERSALITE SINGLE SPOT EMERGENCY LIGHTING FIXTURE

GUIDANCE FİGURES

9

10

12 VERSALITE EMERGENCY LIGHTING FIXTURE

14 VERSALITE LED EMERGENCY LIGHTING FIXTURE

16 VERSALITE INOX EMERGENCY LIGHTING FIXTURE

18 VERSALITE IP-65 EMERGENCY LIGHTING FIXTURE

20 RUBELITE EMERGENCY LIGHTING FIXTURE

22 BETALITE EMERGENCY LIGHTING FIXTURE

24 STARLITE EMERGENCY LIGHTING FIXTURE

26 ROYALITE EMERGENCY LIGHTING FIXTURE

28 ROTALITE EMERGENCY LIGHTING FIXTURE

30 DESA EMERGENCY LIGHTING FIXTURE

32 STARLUX EMERGENCY LIGHTING FIXTURE

34 SPOTLITE EMERGENCY LIGHTING FIXTURE

36 ROYALED EMERGENCY LIGHTING FIXTURE

ARSEL-4

69 SEALITE EMERGENCY GUIDANCE FIXTURE

Page 5: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS
Page 6: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

All testing procedures should be carried out by a competent and knowledgeable person / institution and the results should be recorded. If there is an automatic test setup, the received data should be saved once a month. The test process should be done during the day and when the building is secluded, for example at weekends.

Daily ControlThis test is performed only for central battery-rated systems, checking whether the central battery unit is in normal condition by following the lighted indicators on the central battery unit.

Monthly TestThis test should be done for each device. For this, the supply voltage of the devices must be cut off from the central test key or lighting fuse or by pressing the test button on the device. Lighting and guidance devices should be tested in a short time, such as 5-10 minutes, when they are clearly visible and functioning properly. After this time, the supply voltage is applied to the devices again and the charge indicators must be checked and confirmed.

Annual TestThis test is the same as the monthly test, but it should also be checked that the devices remain in operation for as long as necessary. At the end of this period, the supply voltage is applied to the devices again and the charge indicators are checked and confirmed.

MaintenanceSome parts of the devices must be changed at certain intervals and should be taken from the care. Maintenance should be done during the annual test.

In continuous burning mode, the lamp runs 8,750 hours per year. The life of fluorescent lamps is usually between 7,500 and 10,000 hours, but it does not mean that the lamp will deteriorate after one year. The risk of failure after one year is considered to be increased and replaced with a new one every year.

The batteries used in the devices are not infinite life, and their capacities start to decrease after 3-5 years. During the annual test, the batteries must be replaced for products that do not pass the time test.

During maintenance, the inside and the outside dust must be cleaned. For safety, temperature and ultraviolet exposure of the mains connection terminal and lamp and battery socket should be observed.

The building should be a project prepared in accordance with the Electricity Facilities Project Regulation for emergency lighting, in which all related devices should be included and the changes made over time should be provided. A final registry of planned test and maintenance reports should be kept in the registry. The registry should include information such as system deployment, periodic testing and maintenance, interventions in case of malfunction, dates and personnel involved.

The accompanying table is included in the operating manuals of all products manufactured and sold by ARSEL ELEKTRONIK.

Keeping these records in check by the relevant personnel is very important in terms of traceability and security.

EMERGENCY LIGHTING SYSTEMS TEST AND MAINTENANCE

PRODUCT CODE SERIAL NO:

DECLARED DURATION:

LIGHTING TYPE:

LOCALE:

DATE OF INSTALLATION:

INSTALLER:

NSTALLATION FULL CHARGE DISCHARGE TEST, OPERATION DURATION:

1

2

3

4

5

6

7

8

9

10

11

12

MO. TEST

Function

Function

Function

Function

Function

1 Hour

Function

Function

Function

Function

Function

Dec. Duration

INSTALLATION AND OPERATION CHECK LIST

Confirm DATE

1.YEARConfirm DATE

1.YEARConfirm DATE

1.YEARConfirm DATE

1.YEARConfirm DATE

1.YEAR

ARSEL-6

Page 7: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS
Page 8: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ACİLÇIKIŞ

ACİLÇIKIŞ

ACİLÇIKIŞ

ACİLÇIKIŞ

ACİLÇIKIŞ

ACİLÇIKIŞ

ÇIKIŞEXIT

ÇIKIŞEXIT

ÇIKIŞEXIT

ÇIKIŞEXIT

ÇIKIŞEXIT

ÇIKIŞEXIT

ÇIKIŞ

EXIT

LY - 01 LY - 02 LY - 03

LY - 04 LY - 05 LY - 06

LY - 07 LY - 08 LY - 09

LY - 10 LY - 11 LY - 12

LY - 16 LY - 17 LY - 18

LY - 19 LY - 20 LY - 21

LY - 22 LY - 23 LY - 24

LY - 13 LY - 14 LY - 15

ARSEL-8

Page 9: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

EMERGENCY LIGHTING FIXTURES

Page 10: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

VERSALITE SINGLE SPOTEMERGENCY LIGHTING FIXTURE

• Wall mount, metal sheet case• High light emergency lighting• Halogen bulb lighting• Heat-resistant glass lens

• Versalite emergency luminaire can be used asfixed and mobile.• Spotlights illuminated fixture is activated onlywhen the power fails.• There are LEDs on the device indicating thepresence of mains voltage and the status of the charge.• On the device, there is a test button.• There is a lamp switch on the device.• The charger in the product is designed so that thebattery will not be damaged in case of continuous charging.• The mains supply voltage is standard 220 volts AC50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under 150volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

USAGE AREAS• Long corridors• Stairwells• Indoor Car Parks• Factories• Boiler rooms• Refuges• WarehousesLAMP OPTIONS• G4 - GY 6.35 socket, needle-legged halogen bulbs. 3000°K• 12 volt, 20-35-50wBODY STRUCTURE• Body - Powder white paintedsheet metal chassis• Spot - Transparent glass withmetal sheet frame, metal articulated spotlight• BATTERY - Dry TypeMaintenance-free Battery• Carrying handle - Aluminum,painted blackOPTIONS• Emergency mode only.• 1-3 hour emergency backuptimes• Optional mounting stand

ARSEL-10

Page 11: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

VS-1201

VS-1202

VS-1203

VS-1351

VS-1352

VS-1353

VS-1501

VS-1502

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

20 watt

20 watt

20 watt

35 watt

35 watt

35 watt

50 watt

50 watt

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

110x200x412mm

110x200x412mm

110x200x412mm

110x200x412mm

110x200x412mm

110x200x412mm

110x200x412mm

110x200x412mm

6,25kg

6,30kg

6,30kg

6,25kg

6,25kg

7,40kg

6,30kg

7,40kg

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

10w

10w

10w

10w

10w

10w

10w

10w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

DIMENSIONS

110mm

412m

m

200mm

VERSALITE SINGLE SPOT EMERGENCY LIGHTING FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-11

Page 12: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

VERSALITEEMERGENCY LIGHTING FIXTURE

• Wall mount, metal sheet case• High light emergency lighting• Halogen bulb lighting• Heat-resistant glass lens

USAGE AREAS• Long corridors• Stairwells• Indoor Car Parks• Factories• Boiler rooms

• Refuges• Warehouses

LAMP OPTIONS• G4 - GY 6.35 socket, needle-legged halogenbulbs. 3000°K• 12 volt, 20-35-50w

• Body - Powder white painted sheet metalchassis• Spot - Transparent glass with metal sheetframe, metal articulated spotlight• BATTERY - Dry Type Maintenance-free Battery• Carrying handle - Aluminum, painted blackOPTIONS• Emergency mode only.• 1-3 hour emergency backup times• Optional mounting stand

• Versalite emergency luminaire can beused as fixed and mobile.• Spotlights illuminated fixture isactivated only when the power fails.• There are LEDs on the deviceindicating the presence of mains voltage and the status of the charge.• On the device, there is a test button.• There is a lamp switch on the device.• The charger in the product isdesigned so that the battery will not be damaged in case of continuous charging.• The mains supply voltage is standard220 volts AC 50 Hz.• Charging time for first use is 24hours.• It can withstand fluctuations up to285 volts at mains voltage.• Switches to emergency lighting modeunder 150 volts, charging over 185 volts• It is manufactured according to TS8710 EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

BODY STRUCTURE

ARSEL-12

Page 13: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

VS-2201

VS-2202

VS-2203

VS-2351

VS-2352

VS-2353

VS-2501

VS-2501.5

VS-2503

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

2x20 Watt

2x20 Watt

2x20 Watt

2x35 Watt

2x35 Watt

2x35 Watt

2x50 Watt

2x50 Watt

2x50 Watt

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 90 m.

Emergency 180 m.

110x370x412mm

110x370x412mm

110x370x412mm

110x370x412mm

110x370x412mm

180x370x412mm

110x370x412mm

110x370x412mm

180x370x412mm

7,45kg

7,45kg

9,00kg

7,45kg

9,00kg

14,00kg

9,00kg

11,80kg

15,00kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

10w

10w

10w

10w

10w

50w

10w

10w

50w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

DIMENSIONS

370mm

110

412m

m

VERSALITE EMERGENCY LIGHTING FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-13

Page 14: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

VERSALITE LED EMERGENCY LIGHTING FIXTURE

• Wall mount, metal sheetcase• High-intensity emergencylighting• LED lamp lighting• Heat-resistant transparentpolycarbonate lens• DALI compatible models

USAGE AREAS• Long corridors• Stairwells• Indoor Car Parks• Factories• Boiler rooms• Refuges• WarehousesLAMP OPTIONS• LED 6500°K• 14-18-26 LED lamp modelsBODY STRUCTURE• Body - Electrostatic powder graypainted steel case• Spot - Transparent polycarbonateglazed ABS plastic case, articulated spotlight• Battery - Dry Type Maintenance-freeBattery• Reflektör - Spot chrome coatingreflector• Carrying handle - Aluminum, paintedblackOPTIONS• Emergency mode only.• 1-2-3 hour emergency backup times• Optional mounting stand

• Versalite ledli emergency luminaire can beused as fixed and mobile.• Spotlights illuminated fixture is activated onlywhen the power fails.• There are LEDs on the device indicating thepresence of mains voltage and the status of the charge.• On the device, there is a test button.• Plug-in type power supply cable is included.• The charger in the product is designed sothat the battery will not be damaged in case of continuous charging.• 2x26 LED model, 2x50W halogen bulb emitsequivalent light. (Lumen level 2x1000)• The mains supply voltage is standard 220volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 voltsat mains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts.• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-14

Page 15: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

VSL-214-1

VSL-214-3

VSL-218-1

VSL-218-3

VSL-226-1

VSL-226-3

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

2x14 led

2x14 led

2x18 Led

2x18 Led

2x26 Led

2x26 Led

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

85x340x345mm

85x340x345mm

85x340x345mm

85x340x345mm

85x340x345mm

85x340x345mm

3,28kg

3,63kg

3,63kg

3,85kg

3,63kg

3,85kg

40

40

40

40

40

40

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

5w

5w

5w

5w

5w

5w

220-240

220-240

220-240

220-240

220-240

220-240

VERSALITE LED

VSL-226-1 DALI

VSL-226-2 DALI

VSL-226-3 DALI

VSL-226-3 DALI

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

2x26 Led

2x26 Led

2x26 Led

2x26 Led

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

85x340x345mm

85x340x345mm

85x340x345mm

85x340x345mm

2,75kg

3,15kg

3,15kg

3,15kg

40

40

40

40

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

2w

2w

2w

2w

220-240

220-240

220-240

220-240

VERSALITE LED (DALI Compatible)

<1 lux

<2 lux

<5 lux

<20 lux

<70 lux 12

4

8

15

18

1 2 3 4 5 6 (metre) 9

2M4M8M15M18M

2,5M

3,5M

1Lux 2Lux 5Lux 20Lux 70Lux

340 mm 87 mm

120 mm

345

mm

175

mm

170

mm

75 mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

FOR 226 MODELS

FOR 226 MODELSARSEL-15

Page 16: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

VERSALITE INOX EMERGENCY LIGHTING FIXTURE

• Wall mount, inox sheetcase• Moblen + epoxy spots• Halogen bulb lighting• Acrylic lens.

USAGE AREAS• Food manufacturing• Stairwells• Indoor Car Parks• Factories• Boiler rooms• Refuges• WarehousesLAMP OPTIONS• G4 - GY 6.35 socket, needle-legged halogenbulbs. 3000°K• 12 volt, 20wBODY STRUCTURE• Body - Stainless steel resistant inox case• Spot - Clear acrylic glass with plastic hingedspot• BATTERY - Dry Type Maintenance-free Battery• Carrying handle - Aluminum, painted blackOPTIONS• Emergency mode only.• 1-3 hour emergency backup times• Optional mounting stand (inox)

• Versalite inox emergency luminaire canbe used as fixed and mobile.• Spotlights illuminated fixture is activatedonly when the power fails.• There are LEDs on the device indicatingthe presence of mains voltage and the status of the charge.• On the device, there is a test button.• There is a lamp switch on the device.• The charger in the product is designedso that the battery will not be damaged in case of continuous charging.• Standard production protection levelIP40. Optionally produced at IP65 level.• The mains supply voltage is standard220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285volts at mains voltage.• Switches to emergency lighting modeunder 150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-16

Page 17: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

VSI-2201

VSI-2202

VSI-2203

Emergency Light

Emergency Light

Emergency Light

Wall Mount

Wall Mount

Wall Mount

2x20 watt

2x20 watt

2x20 watt

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

110x370x430m

110x370x430m

110x370x430m

8,20kg

8,20kg

9,50kg

40

40

40

I

I

I

-16/+45°

-16/+45°

-16/+45°

10w

10w

10w

220-240

220-240

220-240

370mm 110

430m

m

VERSALITE INOX EMERGENCY LIGHTING FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-17

Page 18: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

VERSALITE IP65 EMERGENCY LIGHTING FIXTURE

• Wall mount, polyester case• High light emergencylighting• Halogen bulb lighting• Transparent glass lens

USAGE AREAS• Long corridors • Factories• Stairwells • Refuges• Indoor Car Parks • Warehouses• Boiler roomsLAMP OPTIONS• G4 - GY 6.35 socket, needle-leggedhalogen bulbs. 3000°K• 12 volt, 20-35-50wBODY STRUCTURE• Gövde - IP65 polyester case• Spot - Transparent glass with metalsheet frame, metal articulated spotlight• BATTERY - Maintenance-free drytype accumulator, ni-cd battery models• Carrying handle - Aluminum, paintedblackOPTIONS• Emergency mode only.• 1-2-3 hour emergency backup times• Accumulator and Ni-Cd batterymodel options

• Spotlights illuminated fixture is activated onlywhen the power fails.• There are LEDs on the device indicating thepresence of mains voltage and the status of the charge.• On the device, there is a test button.• There is a lamp switch on the device.• Standard production protection level IP65• Transparent button and switch covers areavailable as standard• The charger in the product is designed so thatthe battery will not be damaged in case of continuous charging.• The mains supply voltage is standard 220 voltsAC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-18

Page 19: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

VSP-2201

VSP-2202

VSP-2203

VSP-2351

VSP-2501

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

2x20 watt

2x20 watt

2x20 watt

2x35 watt

2x50 watt

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Rotatable Lamps

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 60 m.

160x400x440m

160x400x440m

160x400x440m

160x400x440m

160x400x440m

7,45kg

7,45kg

9,00kg

7,45kg

9,00kg

65

65

65

65

65

I

I

I

I

I

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

10w

10w

10w

10w

10w

220-240

220-240

220-240

220-240

220-240

VERSALITE IP-65 ACCUMULATOR BACKUP MODEL EMERGENCY LIGHTING FIXTURE

VSP-N-2201

VSP-N-2201,5

Emergency Light

Emergency Light

Wall Mount

Wall Mount

2x20 wat

2x20 wat

Rotatable Lamps

Rotatable Lamps

Emergency 60 m.

Emergency 90 m.

160x400x440m

160x400x440m

7,35kg

7,45kg

65

65

I

I

-16/+40°

-16/+40°

10w

10w

220-240

220-240

VERSALITE IP-65 Nİ-CD BACKUP MODEL EMERGENCY LIGHTING FIXTURE

400mm160

mm

440m

m

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-19

Page 20: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

RUBELITEEMERGENCY LIGHTING FIXTURE

• Waterproof typeemergency lighting fixture• IP65 included inprotection class• Transparent diffuser

USAGE AREAS• Indoor Car Parks• Warehouses• Fire ladders• Boiler rooms• Cabinet rooms• Out of the evacuation door

LAMP OPTIONS• 11 watt fluorescent lamp

BODY STRUCTURE• Polyester case• Transparent diffuser

OPTIONS• Continuous and emergency models• 1-2-3 hour emergency backuptimes

• Rubelite emergency luminaires included in thestandard IP65 protection class.• There are only 1 fluorescent lamp in bothmaintained and non maintained models. The same lamp continues to burn when there is an emergency.• The mains supply voltage is standard 220 volts AC50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under 150volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-20

Page 21: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AE-0111

AE-0112

AE-0113

AE-0211

AE-0212

AE-0213

Emergency Light

Emergency Light

Emergency Light

Maintained

Maintained

Maintained

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

11 wat

11 wat

11 wat

11 wat

11 wat

11 wat

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

85x295x100mm

85x295x100mm

85x295x100mm

85x295x100mm

85x295x100mm

85x295x100mm

2,35kg

2,35kg

2,50kg

2,65kg

2,65kg

2,80kg

65

65

65

65

65

65

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

15w

15w

15w

220-240

220-240

220-240

220-240

220-240

220-240

75 m

m

125 mm

360 mm

RUBELITE EMERGENCY LIGHTING FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-21

Page 22: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

BETALITEEMERGENCY LIGHTING FIXTURE

• Surface mounting,ABS plastic case• Economic exitmarking• Transparent acryliclight panel

USAGE AREAS• Fire ladders• Control center management rooms• Boiler rooms• Offices• Grocery stores• Corridors• Restaurants and bars• Universities, Student dormitories, Schools andcollegesLAMP OPTIONS• G5 socket T5 8w fluorescent bulb, 6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - ABS plastic case• Label panel - transparent acrylic panel whitelatex foil via printing application• Nickel-cadmium in all modelsOPTIONS• Continuous and emergency models• 1-2-3 hour emergency backup times

• It is designed for economic markingsthat can be used in the wall and door applications.• There are 2 fluorescent lamps withfluorescent lamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• In standard condition, IP65 is includedin the protection class• All plastic equipments provide necessaryflame-proof conditions• The mains supply voltage is standard220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285volts at mains voltage.• Switches to emergency lighting modeunder 150 volts, charging over 185 volts• It is manufactured according to TS8710 EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-22

Page 23: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AEB-03111

AEB-03112

AEB-03113

AEB-03113-L

AEB-03211

AEB-03212

AEB-03213

AEB-03213-L

AEB-03010-L

Combined m.

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat

8 wat

8 wat

20xF LED

2x8 wat

2x8 wat

2x8 wat

20xF LED

20xF LED

Single Side

Single Side

Single Side

Single Side

Single Side

Single Side

Single Side

Single Side

Single Side

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

-

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

0,760kg

0,760kg

1,00kg

0,760kg

1,10kg

1,10kg

1,40kg

0,770kg

0,710kg

65

65

65

65

65

65

65

65

65

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

1w

11w

11w

11w

2w

1w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

355 mm11

8 m

m

74mm

Emergency Light

BETALITE EMERGENCY LIGHTING FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Emergency Light

Emergency Light

Emergency Light

Combined m.

Combined m.

ARSEL-23

Page 24: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

STARLITEEMERGENCY LIGHTING FIXTURE

• Surface mounting, metalsheet case• 3mm acrylic diffuser• DALI compatible models

USAGE AREAS• Offices• Grocery stores• Corridors• Restaurants and bars• Universities, Student dormitories, Schools andcollegesLAMP OPTIONS• G5 socket T5 8w fluorescent bulb, 6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - Powder white painted sheet metalchassis• With label panel - 3 mm acrylic panel,application of latex on white foil• BATTERY - Nickel-cadmium in all modelsOPTIONS• Continuous and emergency models• 1-2-3 hour emergency backup times• DALI lighting control system compatiblemodels

• For door-top applications, suitable forstandards, for decorative emergency exit routing.• 8w T5 and LED lamp models• There are 2 fluorescent lamps withfluorescent lamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• The mains supply voltage is standard 220volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285volts at mains voltage.• Switches to emergency lighting modeunder 150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-24

Page 25: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AE-01111-L-DALI

AE-01112-L-DALI

AE-01113-L-DALI

AE-01211-L-DALI

AE-01212-L-DALI

AE-01213-L-DALI

Emergency Light

Emergency Light

Emergency Light

Maintained

Maintained

Maintained

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

500lm LED

500lm LED

500lm LED

500lm LED

500lm LED

500lm LED

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

0,80kg

0,85kg

0,90kg

0,80kg

0,85kg

0,90kg

40

40

40

40

40

40

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

1,2w

1,2w

1,2w

4,5w

4,5w

4,5w

220-240

220-240

220-240

220-240

220-240

220-240

STARLITE EMERGENCY LIGHTING FIXTURE (DALI compatible)

AE-01111

AE-01112

AE-01113

AE-01211

AE-01212

AE-01213

AE-01113-L

AE-01213-L

AE-01010

Emergency Light

Emergency Light

Emergency Light

Combined m.

Combined m.

Combined m.

Emergency Light

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat

8 wat

8 wat

2x8 wat

2x8 wat

2x8 wat

1000lm LED

1000lm LED

1000lm LED

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

1,70kg

1,85kg

1,90kg

2,00kg

2,15kg

2,20kg

1,90kg

1,90kg

1,55kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

5,5w

4,7w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

STARLITE EMERGENCY LIGHTING FIXTURE

350mm

145m

m

70mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-25

Page 26: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ROYALITEEMERGENCY LIGHTING FIXTURE

• Waterproof typeemergency lighting fixture• Mounted with mountingbracket• Transparent diffuser

USAGE AREAS• Indoor Car Parks• Warehouses• Corridors

LAMP OPTIONS• 18-36-58w fluorescent lamp

BODY STRUCTURE• Body - Polyester case, mountingbrackets• Light panel - transparentdiffuser• BATTERY - Nickel-cadmium inall models

OPTIONS• Continuous and emergencymodels• 1-2-3 hour emergency backuptimes

• Royalite, 18-58 watts, is the name of a model ofemergency lighting fittings in IP65 protection class.• For model range 18-58 wat lamp, the lampluminous efficacy is 20% at least in the emergency position.• Single lamp, double lamp, 18-58 wat fixtures can beused in accordance with the needs in use.• The mains supply voltage is standard 220 volts AC50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under 150volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-26

Page 27: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AE-81111

AE-81112

AE-81113

AE-83111

AE-83112

AE-83113

AE-85111

AE-85112

AE-85113

AE-81211

AE-81212

AE-81213

AE-81221

AE-81222

AE-81223

AE-83211

AE-83212

AE-83213

AE-83221

AE-83222

AE-83223

AE-85211

AE-85212

AE-85213

AE-85221

AE-85222

AE-85223

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Emergency Light

Maintained

Maintained

Maintained

Combined m.

Combined m.

Combined m.

Maintained

Maintained

Maintained

Combined m.

Combined m.

Combined m.

Maintained

Maintained

Maintained

Combined m.

Combined m.

Combined m.

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

18 wat

18 wat

18 wat

36 wat

36 wat

36 wat

58 wat

58 wat

58 wat

18 wat

18 wat

18 wat

2x18 wat

2x18 wat

2x18 wat

36 wat

36 wat

36 wat

2X36 wat

2X36 wat

2X36 wat

58 wat

58 wat

58 wat

2x58 wat

2x58 wat

2x58 wat

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

90x660x100mm

90x660x100mm

90x660x100mm

90x1280x100mm

90x1280x100mm

90x1280x100mm

90x1570x100mm

90x1570x100mm

90x1570x100mm

90x660x100mm

90x660x100mm

90x660x100mm

150x660x100mm

150x660x100mm

150x660x100mm

90x1280x100mm

90x1280x100mm

90x1280x100mm

140x1280x100mm

140x1280x100mm

140x1280x100mm

90x1570x100mm

90x1570x100mm

90x1570x100mm

150x1570x100mm

150x1570x100mm

150x1570x100mm

1,10kg

1,30kg

1,30kg

3,30kg

3,50kg

3,50kg

4,10kg

4,30kg

4,30kg

1,40kg

1,60kg

1,60kg

1,80kg

2,00kg

2,00kg

3,30kg

3,50kg

3,50kg

5,10kg

5,30kg

5,30kg

4,50kg

4,60kg

4,60kg

6,50kg

6,70kg

6,70kg

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

65

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

3w

3w

3w

3w

3w

3w

21w

21w

21w

39w

39w

39w

39w

39w

39w

75w

75w

75w

61w

61w

61w

119w

119w

119w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

ROYALITE IP-65 EMERGENCY LIGHTING FIXTURE

660mm10

0 m

m

90 mm1x18

1280mm

100

mm

90 mm1x36

1570mm

100

mm

90 mm1x58

660mm

100

mm

150 mm2x18

1280mm

100

mm

140 mm2x36

1570mm

100

mm

150 mm2x58

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-27

Page 28: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ROTALITEEMERGENCY LIGHTING FIXTURE

• Flush mounting, metal sheetcase• Flush mounting, emergencylighting fixture• Prismatic transparent or flatfogged acrylic light panel

USAGE AREAS• Offices• Grocery stores• Corridors

LAMP OPTIONS• G5 socket T5 8w fluorescent bulb,6500°K• White light LED bulb, 6500°K

BODY STRUCTURE• Body - Electrostatic powdercoated metal sheet case, asma tavan montaj yayları• Light panel - Prismatic transparentor flat fogged acrylic light panel.• BATTERY - Nickel-cadmium in allmodels

OPTIONS• Continuous and emergencymodels• 1-2-3 hour emergency backuptimes

• In suspended ceiling applications, used as ceilingtype and recessed.• There are only 1 fluorescent lamp in bothmaintained and non maintained models. The same lamp continues to burn when there is an emergency.• The mains supply voltage is standard 220 volts AC50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under 150volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-28

Page 29: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AE-9111

AE-9112

AE-9113

AE-9211

AE-9212

AE-9213

AE-9113-L

AE-9213-L

AE-9010

AE-9213L MINI

Emergency Light

Emergency Light

Emergency Light

Maintained

Maintained

Maintained

Emergency Light

Maintained

Mains Light

Maintained

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

8 wat

8 wat

8 wat

8 wat

8 wat

8 wat

1000lm LED

1000lm LED

8 wat

10XF LED

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

105x350x75mm

105x350x75mm

105x350x75mm

105x350x75mm

105x350x75mm

105x350x75mm

105x350x75mm

105x350x75mm

105x350x75mm

72x328x77mm

1,75kg

1,75kg

1,75kg

2,10kg

2,00kg

2,00kg

1,95kg

1,95kg

1,80kg

1,55kg

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

5,5w

8w

2w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

355m

m

110mm

395mm135mm

350mm

80m

m

102mm

ROTALITE RECESSED MOUNT EMERGENCY LIGHTING FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Flush Mounting Hole

ARSEL-29

Page 30: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DESA-SENSOREMERGENCY LIGHTING FIXTURE

• Surface mounting, metalsheet case, glass diffuser• Combined emergencylighting fixture with radar sensor• Matte white glass lightpanel

USAGE AREAS• Stairwells• CorridorsLAMP OPTIONS• White light LED bulb, 6500°KBODY STRUCTURE• Body - Electrostatic powdercoated metal sheet case.• Lıght panel - Matte whiteglass light panel• BATTERY - Nickel-cadmium inall modelsOPTIONS• Continuous and emergencymodels

• A product with a radar sensor that can be used instairwells and corridors.• LED lamps are used as lighting elements.• 36 leds are used for sensor-controlled mainslighting(75 watt incandescent light bulb gives high, 1200 lm).• Provides 6 LED emergency lighting at power failure(210 lm).• The radar sensor is not affected by thermal changesand makes the same sensitivity everywhere.• The charger in the product is designed so as not todamage the battery in case of continuous charging.• The mains supply voltage is standard 220 volts AC 50Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mainsvoltage.• Switches to emergency lighting mode under 150 volts,charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-30

Page 31: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

RLG-M

RLG-S

Sensor + Battery

Sensör

Ceiling Mount

Ceiling Mount

LED

LED

Single Side

Single Side

Emergency 120 m.

_

280x110mm

280x110mm

1,40kg

1,30kg

40

40

I

I

-16/+40°

-16/+40°

9,5w

8,5w

220-240

220-240

DESA-SENSOR EMERGENCY LIGHTING FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-31

Page 32: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

• Self-testing feature• Recessed mounting led emergency lighting fixture

USAGE AREAS• Fire alarm button region• Fire hose or extinguisher tube area• Areas with rising or falling groundlevel• CorridorsLAMP OPTIONS• White light LED bulb, 6500°KBODY STRUCTURE• Body - Electrostatic powder coatedmetal sheet case. Ceiling mounting with spring• Electronic module - Aluminum profilebody, ABS plastic side cover• BATTERY - Nickel-cadmium in allmodelsOPTIONS• Emergency mode only.• 1-3 hour emergency backup times

• Includes battery, power supply unit and LED spot..• Power module chassis with aluminum profile housing• Plug-in type battery connection with anti-plug protection.• Emergency mode only• Mounting hole diameter 75 mm• Continuous charging method keeps the battery pack full and ready.• The mains supply voltage is standard 220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mains voltage.• Switches to emergency lighting mode under 150 volts, charging over 185 volts• It is manufactured according to TS 8710 EN60598-2-22 standard in theframework of ISO 9001-2000 quality management system.

STARLUX RECESSED MOUNTEMERGENCY LIGHTING FIXTURE (SELF-TEST)

ARSEL-32

Page 33: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

STARLUX Emergency Light Ceiling Mount 2W LED Single Face Emergency 180 m. 85x23mm 400gr 30 I -16/+45° 1,5w 220-240

85 mm

72 mm

23 m

m

STARLUX RECESSED MOUNT EMERGENCY LIGHT

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

BATTERY DIMENSIONS

WORKING METHOD• Performs a functional test every 15 days after installation. The function test is performed automatically or by pressing andholding the button for 1 second.• Switches the device to emergency mode for 60 seconds, tests the lamp, battery and other functions.• Duration test once a year makes. Time test is done automatically or by pressing the button more than 3 seconds. Checkswhether the device provides the declared feed time.• Green LED, with different burning modes, displays the commands given by charge, test and button.• Red led shows different burning modes and battery and LED faults.• The device may show battery and LED malfunctions even in stand-by mode.• Button is used to test function and malfunction reset operation. (red led contains fault memory, must be reset when faultis cleared)• The device only allows for manual testing if it is sufficiently charged. Otherwise it just tests the function.• The device safety is never compromised by the control circuit. Even if the controls are not running, the device will operatenormally in emergency mode.

ARSEL-33

Page 34: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

SPOTLITE RECESSED MOUNTEDEMERGENCY LIGHTING FIXTURE

• Recessed mounting ledemergency lighting fixture

USAGE AREAS• Fire alarm button region• Fire hose or extinguisher tube area• Areas with rising or falling groundlevel• Corridors

LAMP OPTIONS• White light LED bulb, 6500°K

BODY STRUCTURE• Body - Electrostatic powder coatedmetal sheet case. Ceiling mounting with spring• Electronic module - Aluminum profilebody, ABS plastic side cover• BATTERY - Nickel-cadmium in allmodels

OPTIONS• Continuous and emergency models• 1-3 hour emergency backup times

• Includes battery, power supply unit and LEDspot.• Power module chassis with aluminum profilehousing• Plug-in type battery connection with anti-plugprotection.• Maintained Model also includes Led driver• In maintained models, the application-specificillumination line is separate, the emergency illumination supply line must also be withdrawn• Mounting hole diameter 75 mm• Continuous charging method keeps thebattery pack full and ready.• The mains supply voltage is standard 220volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-34

Page 35: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

SP-301-3

SP-301M-3

SP-303-3

SP-303M-3

SP-301-5

SP-301M-5

SP-303-5

SP-303M-5

Emergency Light

Maintained

Emergency Light

Maintained

Emergency Light

Maintained

Emergency Light

Maintained

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

3W LED

3W LED

3W LED

3W LED

5W LED

5W LED

5W LED

5W LED

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 60 m.

Emergency 180 m.

Emergency 180 m.

Emergency 60 m.

Emergency 60 m.

Emergency 180 m.

Emergency 180 m.

87x52mm

87x52mm

87x52mm

87x52mm

87x52mm

87x52mm

87x52mm

87x52mm

415gr

445gr

490gr

520gr

415gr

445gr

490gr

520gr

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

1,5w

4,5w

1,5w

4,5w

1,5w

6,5w

1,5w

6,5w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

SPOTLITE RECESSED MOUNTED EMERGENCY LIGHTING FIXTURE

85 mm

72 mm

23 m

m

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-35

Page 36: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ROYALEDEMERGENCY LIGHTING FIXTURE

• Aluminum profile IP65 caseemergency lighting• Long Life LED lighting• White acrylic diffuser

• Royaled, high light intensity, LED lampemergency lighting fittings in IP 65 protection class.• At the emergency position, the light outputof the lamp is at least 15%• Continuous charging method keeps thebattery pack full and ready.• The charger in the product is designed so asnot to damage the battery in case of continuous charging.• The mains supply voltage is standard 220volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 voltsat mains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

USAGE AREAS• Indoor Car Parks• Warehouses• Corridors• Fire ladders

LAMP OPTIONS• White light LED bulb, 6500°K

BODY STRUCTURE• Aluminum body,• acrylic diffuser,• aluminum casting caps• BATTERY - Nickel-cadmium in allmodels

OPTIONS• Continuous and emergency models• 1-3 hour emergency backup times

ARSEL-36

Page 37: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

RL-8111

RL-8113

RL-8010

Emergency Light

Emergency Light

Mains Light

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

LED

LED

LED

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 180 m.

-

60x1200x75mm

60x1200x75mm

60x1200x75mm

2,40kg

2,50kg

2,20kg

65

65

65

I

I

I

-16/+45°

-16/+45°

-16/+45°

54w

54w

52w

220-240

220-240

220-240

ROYALED EMERGENCY LIGHTING FIXTURE

75 m

m

60 mm

75 m

m

1200 mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-37

Page 38: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

EMERGENCY GUIDANCE FIXTURES

Page 39: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ARSELLITE RECESSED MOUNTED EMERGENCY GUIDANCE LUMINAIRE

• Recessed mounted sheet metalmain body• 8 mm thick acrylic light panel• Models with high light options• DALI compatible models

USAGE AREAS• Offices• Meeting rooms• Reception areas• Shopping malls• Hotels and bars• Restaurants• Clubs• Universities, Student dormitories, Schools andcolleges

LAMP OPTIONS• G5 socket T5 8w fluorescent bulb, 6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - Powder white painted sheet metal chassis• Spring mounting bracket for plaster ceiling mount• Label panel - 8 mm transparent acrylic panel,latex printing on white foil• BATTERY - Nickel-cadmium in all models

OPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times• Pantograph can be applied on plexiglass• DALI lighting control system compatible models

• In gypsum and similar suspendedceiling applications, the body is mounted by being embedded in the ceiling• Continuous charging method keeps thebattery pack full and ready.• The mains supply voltage is standard220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285volts at mains voltage.• Switches to emergency lighting modeunder 150 volts, charging over 185 volts• It is manufactured according to TS8710 EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-39

Page 40: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AE-2121

AE-2122

AE-2123

AE-2221

AE-2222

AE-2223

AE-2123 L

AE-2223 L

AE-2020

Non-maintained

Non-maintained

Non-maintained

Maintained

Maintained

Maintained

Non-maintained

Maintained

Mains Light

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

8 wat

8 wat

8 wat

8 wat

8 wat

8 wat

500lm LED

500lm LED

500lm LED

Double Side Emergency 60 min.

Emergency 120 min..

Emergency 180 min..

Emergency 60 min.

Emergency 120 min.

Emergency 180 min.

Emergency 180 min.

Emergency 180 min.

110x360x75mm

110x360x75mm

110x360x75mm

110x360x75mm

110x360x75mm

110x360x75mm

110x360x75mm

110x360x75mm

110x360x75mm

2,20kg

2,20kg

2,20kg

2,50kg

2,50kg

2,50kg

2,40kg

2,40kg

2,00kg

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

5,5w

4,7w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

ARSELLITE RECESSED MOUNTED

MODEL CODE LIGHTING STYLE MOUNTING STYLE

LAMP LIGHT FACE DURATION WEIGHTIP

CLASSISOLATION

CLASSOPERATION

TEMPPOWER

CONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

TECHNICAL DRAWINGS

visible distance 28 meter

AE-2221 L DALI

AE-2222 L DALI

AE-2223 L DALI

Maintained

Maintained

Maintained

Ceiling Mount

Ceiling Mount

Ceiling Mount

500lm LED

500lm LED

500lm LED

Emergency 60 min.

Emergency 120 min.

Emergency 180 min.

110x360x75mm

110x360x75mm

110x360x75mm

2,10kg

2,15kg

2,20kg

30

30

30

I

I

I

-16/+45°

-16/+45°

-16/+45°

4,5w

4,5w

4,5w

220-240

220-240

220-240

ARSELLITE RECESSED MOUNTED (DALI compatible)

MODEL CODE LIGHTING STYLE LAMP LIGHT FACE DURATION WEIGHTIP

CLASSISOLATION

CLASS

72 mm

75 m

m

7 m

m

110 mm

8 mm

143

mm

325 mm

75 m

m

7 m

m

286 mm14

3 m

m

360 mm

85 m

m

330 mm

MOUNTING STYLE

DIMENSIONS(W-L-H)mm

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

ARSEL-40

Page 41: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ARSELLITE SURFACE EMERGENCY GUIDANCE FIXTURE

• Main body of modernappearance aluminum profile• 8 mm thick acrylic lightpanel• Connection box for easeof installation and connection• Models with high lightoptions• DALI compatible models

USAGE AREAS• Offices• Meeting rooms• Reception areas• Shopping malls• Hotels and bars• Restaurants• Clubs• Universities, Student dormitories, Schools andcollegesLAMP OPTIONS• G5 socket T5 8w fluorescent bulb, 6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - white painted aluminum profile,• Flame-resistant ABS side flaps.• White painted metal mounting bracket andcover plate• Label panel - 8 mm transparent acrylic panel,latex printing on white foil• BATTERY - Nickel-cadmium in all modelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times• Pantograph can be applied on plexiglass• DALI lighting control system compatible models

• It is suitable for all internationalstandards in terms of size and technical specifications.• is an independent emergency exitorientation luminaire located within the battery and power supply..• Continuous charging method keeps thebattery pack full and ready.• The mains supply voltage is standard220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285volts at mains voltage.• Switches to emergency lighting modeunder 150 volts, charging over 185 volts• It is manufactured according to TS8710 EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-41

Page 42: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AE-1121

AE-1123

AE-1221

AE-1223

AE-1121-LC

AE-1123-LC

AE-1221-LC

AE-1223-LC

AE-1020

AE-1020-LC

Emergency Light

Emergency Light

Constant Light

Constant Light

Emergency Light

Emergency Light

Constant Light

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

8 watt

8 watt

8 watt

8 watt

8 watt

8 watt

8 watt

8 watt

8 watt

8 watt

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Emergency 60 m

Emergency 180 m

Emergency 60 m

Emergency 180 m

Emergency 60 m

Emergency 180 m

Emergency 60 m

Emergency 180 m

-

-

55X340X290mm

55X340X290mm

55X340X290mm

55X340X290mm

55x430x340mm

55x430x340mm

55x430x340mm

55x430x340mm

55X340X290mm

55x430x340mm

1,30kg

1,40kg

1,50kg

1,60kg

1,40kg

1,50kg

1,60kg

1,70kg

1,30kg

1,40kg

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

1,5w

1,5w

9,5w

9,5w

1,5w

1,5w

9,5w

9,5w

8w

8w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

ARSELLITE SURFACE FLUORESCENT

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

AE-1221-S-DALI

AE-1222-S-DALI

AE-1223-S-DALI

AE-1221-LC-DALI

AE-1222-LC-DALI

AE-1223-LC-DALI

Constant Light

Constant Light

Constant Light

Constant Light LC

Constant Light LC

Constant Light LC

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

500lm LED

500lm LED

500lm LED

500lm LED

500lm LED

500lm LED

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Emergency 60 m

Emergency 120 m

Emergency 180 m

Emergency 60 m

Emergency 120 m

Emergency 180 m

55X340X290mm

55X340X290mm

55X340X290mm

55x430x340mm

55x430x340mm

55x430x340mm

0,75kg

0,80kg

0,86kg

0,85kg

0,90kg

0,96kg

30

30

30

30

30

30

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

4,5w

4,5w

4,5w

4,5w

4,5w

4,5w

220-240

220-240

220-240

220-240

220-240

220-240

ARSELLITE SURFACE LED (DALI compatible)

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Dimensions

AE-1221-S

AE-1223-S

AE-1221-L

AE-1223-L

AE-1220-S

AE-1220-L

Constant Light

Constant Light

Constant Light LC

Constant Light LC

Mains Light

Mains Light LC

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

500lm LED

500lm LED

500lm LED

500lm LED

500lm LED

500lm LED

Double Side

Double Side

Double Side

Double Side

Double Side

Double Side

Emergency 60 m

Emergency 180 m

Emergency 60 m

Emergency 180 m

-

-

55X340X290mm

55X340X290mm

55x430x340mm

55x430x340mm

55X340X290mm

55x430x340mm

1,40kg

1,60kg

1,80kg

2,00kg

1,20kg

1,60kg

30

30

30

30

30

30

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

5,5w

5,5w

5,5w

5,5w

5,5w

4,7w

220-240

220-240

220-240

220-240

220-240

220-240

ARSELLITE SURFACE LED (500 lumen)

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Visible distanceS model 26 meterL model 34 meter

53

46

157m

m10

5mm

25mm

342 mm240 mm

310 mm

432 mm

400 mm

215

mm

AE-1323-S

AE-1323-L

AE-1320-S

AE-1320-L

Constant Light

Constant Light LC

Mains Light

Mains Light LC

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

120lm LED

120lm LED

120lm LED

120lm LED

Double Side

Double Side

Double Side

Double Side

Emergency 180 m

Emergency 180 m

-

-

55X340X290mm

55x430x340mm

55X340X290mm

55x430x340mm

1,40kg

1,80kg

1,20kg

1,60kg

30

30

30

30

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

1,5w

1,5w

1w

1w

220-240

220-240

220-240

220-240

ARSELLITE SURFACE LED (120 lumen)

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Ceiling Mount

Constant Light

Mains Light

Mains Light

ARSEL-42

Page 43: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

BETALITE SINGLE SIDE EMERGENCY GUIDANCE FIXTURE

• Surface mountingABS plastic case• Economic exitmarking• Transparent acryliclight panel

USAGE AREAS• Fire ladder• Control center management rooms• Boiler room• Office• Grocery store

Corridor•Restaurants and bar•Universities, Student dormitories, Schools and•

collegesLAMP OPTIONS

G5 socket T5 8w fluorescent bulb, 6500°•White light LED bulb, 6500°•

BODY STRUCTURE• Body - ABS plastic case

Label panel - transparent acrylic panel white•latex foil via printing application

Nickel-cadmium in all models•OPTIONS• Continuous and emergency models

1-2-3 hour emergency backup times•

• It is designed for economic markingthat can be used in the wall and door applications.• There are 2 fluorescent lamps witfluorescent lamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• In standard condition, IP65 is includein the protection class

All plastic equipments provide necessary•flame-proof conditions• The mains supply voltage is standard220 volts AC 50 Hz.

Charging time for first use is 24 hours•It can withstand fluctuations up to 285•

volts at mains voltage.Switches to emergency lighting mode•

under 150 volts, charging over 185 volts• It is manufactured according to TS8710 EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-43

Page 44: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AEB-03111

AEB-03112

AEB-03113

AEB-03113-L

AEB-03211

AEB-03212

AEB-03213

AEB-03213-L

AEB-03010-L

Combined m.

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat

8 wat

8 wat

20xF LED

2x8 wat

2x8 wat

2x8 wat

20xF LED

20xF LED

Single Side

Single Side

Single Side

Single Side

Single Side

Single Side

Single Side

Single Side

Single Side

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

-

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

74x355x118mm

0,760kg

0,760kg

1,00kg

0,760kg

1,10kg

1,10kg

1,40kg

0,770kg

0,710kg

65

65

65

65

65

65

65

65

65

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

1w

11w

11w

11w

2w

1w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

Visible Distance 23 meter

355 mm11

8 m

m

74mm

Emergency Light

BETALITE EMERGENCY LIGHTING FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Emergency Light

Emergency Light

Emergency Light

Combined m.

Combined m.

ARSEL-44

Page 45: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

BETALITE DOUBLE FACED EMERGENCY GUIDANCE FIXTURE

• Surface mounting, ABSplastic case• Economic exit marking• Transparent acrylic lightpanel

USAGE AREAS• Offices• Grocery stores• Corridors• Dining Halls• Restaurants and bars• Universities, Student dormitories,Schools and collegesLAMP OPTIONS• G5 socket T5 8w fluorescent bulb,6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - ABS plastic case• Label panel - transparent acrylicpanel white latex foil via printing application• BATTERY - Nickel-cadmium in allmodelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times

• It is a stylish and economical product that can beused in ceiling mounting applications.• There are 2 fluorescent lamps with fluorescentlamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• In standard condition, IP65 is included in theprotection class.• All plastic equipments provide necessary flame-proof conditions.• is an independent emergency exit orientationluminaire located within the battery and power supply..• Continuous charging method keeps the batterypack full and ready.• The mains supply voltage is standard 220 voltsAC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under 150volts, charging over 185 volts.• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-45

Page 46: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AEB-03121

AEB-03122

AEB-03123

AEB-03123-L

AEB-03221

AEB-03222

AEB-03223

AEB-03223-L

AEB-03020-L

Emergency light

Emergency light

Emergency light

Emergency light

Combined m.

Combined m.

Combined m.

Maintained

Mains light

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

8 wat

8 wat

8 wat

20xF LED

2x8 wat

2x8 wat

2x8 wat

20xF LED

20xF LED

Double face

Double face

Double face

Double face

Double face

Double face

Double face

Double face

Double face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

-

118x355x215mm

118x355x215mm

118x355x215mm

118x355x215mm

118x355x215mm

118x355x215mm

118x355x215mm

118x355x215mm

118x355x215mm

1,01kg

1,01kg

1,25kg

1,01kg

1,35kg

1,35kg

1,65kg

1,02kg

1,02kg

65

65

65

65

65

65

65

65

65

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

1w

11w

11w

11w

2w

1w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

215m

m

355mm118mm

Visible Distance 30 metre

BETALITE DOUBLE FACED EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-46

Page 47: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

STARLITEEMERGENCY GUIDANCE FIXTURE

• Surface mounting, metalsheet case• 3mm acrylic diffuser• DALI compatible models

USAGE AREAS• Offices• Grocery stores• Corridors• Restaurants and bars• Universities, Student dormitories, Schoolsand colleges LAMP OPTIONS• G5 socket T5 8w fluorescent bulb, 6500°K • White light LED bulb, 6500°KBODY STRUCTURE• Body - Powder white painted sheet metalchassis• With label panel - 3 mm acrylic panel,application of latex on white foil • BATTERY - Nickel-cadmium in all modelsOPTIONS• Continuous and emergency models• 1-2-3 hour emergency backup times• DALI lighting control system compatiblemodels

• For door-top applications, suitable forstandards, for decorative emergency exit routing.• There are 2 fluorescent lamps withfluorescent lamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• The mains supply voltage is standard220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285volts at mains voltage.• Switches to emergency lighting modeunder 150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-47

Page 48: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

350mm145m

m

70mm

DIMENSIONS

AE-01111-L-DALI

AE-01112-L-DALI

AE-01113-L-DALI

AE-01211-L-DALI

AE-01212-L-DALI

AE-01213-L-DALI

Emergency Light

Emergency Light

Emergency Light

Maintained

Maintained

Maintained

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

500lm LED

500lm LED

500lm LED

500lm LED

500lm LED

500lm LED

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

0,80kg

0,85kg

0,90kg

0,80kg

0,85kg

0,90kg

40

40

40

40

40

40

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

1,2w

1,2w

1,2w

4,5w

4,5w

4,5w

220-240

220-240

220-240

220-240

220-240

220-240

STARLITE EMERGENCY GUIDANCE FIXTURE (DALI compatible)

AE-01111

AE-01112

AE-01113

AE-01211

AE-01212

AE-01213

AE-01113-L

AE-01213-L

AE-01010

Emergency Light

Emergency Light

Emergency Light

Combined m.

Combined m.

Combined m.

Emergency Light

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat

8 wat

8 wat

2x8 wat

2x8 wat

2x8 wat

1000lm LED

1000lm LED

1000lm LED

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

70x350x145mm

1,70kg

1,85kg

1,90kg

2,00kg

2,15kg

2,20kg

1,90kg

1,90kg

1,55kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

5,5w

4,7w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

STARLITE EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Visible Distance 28 metre

ARSEL-48

Page 49: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ORION SURFACE EMERGENCY GUIDANCE FIXTURE

• Aluminum profile body,ABS plastic covers• Economic exit marking• Transparent acrylic lightpanel

USAGE AREAS• Fire exit doors• Offices• Meeting rooms• Reception areas• Shopping malls• Hotels and bars• Restaurants• Clubs• Universities, Student dormitories,Schools and collegesLAMP OPTIONS• White light LED bulb, 6500°KBODY STRUCTURE• Body - Aluminum profile body, ABSplastic side covers• Label panel - transparent acrylic panelwhite latex foil via printing application• BATTERY - Nickel-cadmium in all modelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times.

• It is designed for economic markings thatcan be used in ceiling wall and door applications.• For ceiling or wall mount, swivel joint 90,hides in the power cable and the connector.• All plastic equipments provide necessaryflame-proof conditions.• 5mm transparent acrylic diffuser.• Light source LEDs radiate through theprofile, through the diffuser, illuminate the figure on it.• is an independent emergency exit orientationluminaire located within the battery and power supply.• Continuous charging method keeps thebattery pack full and ready.• The mains supply voltage is standard 220volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 voltsat mains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-49

Page 50: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AEB-24223-L

AEB-24020-L

AEB-30223-L

AEB-30020-L

AEB-39223-L

AEB-39020-L

Maintained

Mains Light

Maintained

Mains Light

Maintained

Mains Light

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

Wall-Ceiling

8xF LED

8xF LED

10xF LED

10xF LED

20xF LED

20xF LED

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Emergency 180 m.

-

Emergency 180 m.

-

Emergency 180 m.

-

38x240x170mm

38x240x170mm

38x300x220mm

38x300x220mm

38x390x260mm

38x390x260mm

0,570kg

0,505kg

0,600kg

0,535kg

0,865kg

0,800kg

40

40

40

40

40

40

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

2w

1w

2w

1w

2w

1w

220-240

220-240

220-240

220-240

220-240

220-240

24 cm model Visible Distance 24 m

30 cm model Visible Distance 30 m

39 cm model Visible Distance 34 m

100mm

50 m

m

240 mm

170

mm

44 mm

38 mm

130

mm

100mm

50 m

m

300 mm

220

mm

44 mm

38 mm

160

mm

100mm

50 m

m

390 mm

260

mm

44 mm

38 mm

200

mm

ORION SURFACE MOUNT EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-50

Page 51: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ORION RECESSED MOUNTED EMERGENCY GUIDANCE FIXTURE

• Aluminum profile body,ABS plastic covers• Installation under plaster• Economic exit marking• Transparent acrylic lightpanel

USAGE AREAS• Fire exit doors• Offices• Meeting rooms• Reception areas• Shopping malls• Hotels and bars• Restaurants• Clubs• Universities, Student dormitories,Schools and collegesLAMP OPTIONS• White light LED bulb, 6500°KBODY STRUCTURE• Body - Aluminum profile body, ABSplastic side covers• Recessed mounted apparatus -Electrostatic powder painted white hair, easy installation spring.• Label panel - transparent acrylic panelwhite latex foil via printing application• BATTERY - Nickel-cadmium in allmodelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times.

• Can be used in recessed mount applications,designed for economic markings in accordance with standards.• All plastic equipments provide necessary flame-proof conditions.• 5mm transparent acrylic diffuser.• Light source LEDs radiate through the profile,through the diffuser, illuminate the figure on it.• is an independent emergency exit orientationluminaire located within the battery and power supply..• Continuous charging method keeps the batterypack full and ready.• The mains supply voltage is standard 220 voltsAC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-51

Page 52: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

24 cm model Visible Distance 24 m

30 cm model Visible Distance 30 m

DIMENSIONS

AEB-24223-L

AEB-24020-L

AEB-30223-L

AEB-30020-L

AEB-39223-L

AEB-39020-L

Maintained

Mains Light

Maintained

Mains Light

Maintained

Mains Light

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

8xF LED

8xF LED

10xF LED

10xF LED

20xF LED

20xF LED

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Emergency 180 m.

-

Emergency 180 m.

-

Emergency 180 m.

-

70x310x130mm

70x310x130mm

70x390x180mm

70x390x180mm

70x460x220mm

70x460x220mm

0,90kg

0,80kg

1,20kg

1,10kg

1,50kg

1,40kg

40

40

40

40

40

40

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

2w

1w

2w

1w

2w

1w

220-240

220-240

220-240

220-240

220-240

220-240

Flush Mounting Hole

270 mm50

mm

61 m

m

56 m

m

45 mm

130

mm

240 mm

65 mm

335 mm

50 m

m

56 m

m

45 mm65 mm

164

mm

300 mm

61 m

m

ORION RECESSED MOUNTED EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Flush Mounting Hole

ARSEL-52

Page 53: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

SFSEMERGENCY GUIDANCE FIXTURE

• Aluminum profile body,ABS plastic covers• Recessed mounting partoptional• Economic exit marking• Transparent acrylic lightpanel

USAGE AREAS• Fire exit doors• Offices• Meeting rooms• Reception areas• Shopping malls• Hotels and bars• Restaurants• Clubs• Universities, Student dormitories, Schools andcollegesLAMP OPTIONS• White light LED bulb, 6500°KBODY STRUCTURE• Aluminum profile body, ABS plastic sidecovers• Hinged mounting part - ABS plastic, suitablefor fixing to the ceiling or wall• Label panel - transparent acrylic panel whitelatex foil via printing application• BATTERY - Nickel-cadmium in all modelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times.• Optional flush mounting apparatus -Electrostatic powder white painted hair, easy assembly with spring.

• It is designed for economic markings thatcan be used in ceiling wall and door applications.• All plastic equipments provide necessaryflame-proof conditions.• 5mm transparent acrylic diffuser.• Light source LEDs radiate through theprofile, through the diffuser, illuminate the figure on it.• is an independent emergency exitorientation luminaire located within the battery and power supply..• Continuous charging method keeps thebattery pack full and ready.• The mains supply voltage is standard220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285volts at mains voltage.• Switches to emergency lighting modeunder 150 volts, charging over 185 volts.• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-53

Page 54: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

SFS EMERGENCY GUIDANCE FIXTURE

SFS-24

SFS-30

Constant Light

Constant Light

Ceiling-Wall

Ceiling-Wall

6xF LED

6xF LED

Double Side

Double Side

Emergency 180 m

Emergency 180 m

38x240x169mm

38x300x201mm

0,450kg

0,550kg

40

40

I

I

-16/+45°

-16/+45°

1,5w

1,5w

220-240

220-240

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

24 cm modelvisible distance22 meter

30 cm modelvisible distance28 meter

ARSEL-54

Page 55: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DEKOLITE EMERGENCY GUIDANCE FIXTURE

• Surface mounting, metalsheet case• At the bottom, 4 roundlighted windows for floor lighting• 3 mm thick acrylic lightpanel

USAGE AREAS• Offices• Grocery stores• Corridors• Restaurants and bars• Universities, Student dormitories,Schools and colleges LAMP OPTIONS• G5 socket T5 8w fluorescent bulb,6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - Powder white painted sheetmetal chassis• With label panel - 3 mm acrylic panel,application of latex on white foil• BATTERY - Nickel-cadmium in allmodelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times.

• For door-top applications, suitable forstandards, for decorative emergency exit routing.• There are 2 fluorescent lamps withfluorescent lamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• is an independent emergency exit orientationluminaire located within the battery and power supply.• Continuous charging method keeps thebattery pack full and ready.• The mains supply voltage is standard 220volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 voltsat mains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts.• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-55

Page 56: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AE-3111

AE-3112

AE-3113

AE-3211

AE-3212

AE-3213

AE-3113-L

AE-3213-L

AE-3010

Emergency Light

Emergency Light

Emergency Light

Combined m.

Combined m.

Combined m.

Emergency Light

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat

8 wat

8 wat

2x8 wat

2x8 wat

2x8 wat

20xF LED

20xF LED

8 wat

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

70x325x185mm

70x325x185mm

70x325x185mm

70x325x185mm

70x325x185mm

70x325x185mm

70x325x185mm

70x325x185mm

70x325x185mm

1,60kg

1,60kg

1,60kg

1,95kg

1,95kg

1,95kg

1,30kg

1,40kg

1,60kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

2w

8w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

Visible Distance 32 meter

325mm

70m

m

185mm

DEKOLITE EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-56

Page 57: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DEKOLITE DOUBLE FACED EMERGENCY GUIDANCE FIXTURE

• Surface mounting,metal sheet case• At the bottom, 4 roundlighted windows for floor lighting• 3 mm thick acrylic lightpanel

USAGE AREAS• Offices• Grocery stores• Corridors• Restaurants and bars• Universities, Student dormitories,Schools and colleges LAMP OPTIONS• G5 socket T5 8w fluorescent bulb,6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - Powder white painted sheetmetal chassis• With label panel - 3 mm acrylicpanel, application of latex on white foil• BATTERY - Nickel-cadmium in allmodelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times.

• Where the emergency exit is not directly visible,two-way marking is required, corridor and similar applications are used.• There are 2 fluorescent lamps with fluorescentlamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• is an independent emergency exit orientationluminaire located within the battery and power supply..• Continuous charging method keeps the batterypack full and ready.• The mains supply voltage is standard 220 voltsAC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under 150volts, charging over 185 volts.• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-57

Page 58: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AE 3121

AE 3122

AE-3123

AE-3221

AE-3222

AE-3223

AE-3123-L

AE-3223-L

AE-3020

Emergency Light

Emergency Light

Emergency Light

Combined m.

Combined m.

Combined m.

Emergency Light

Maintained

Mains Light

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

8 wat

8 wat

8 wat

2x8 wat

2x8 wat

2x8 wat

20xF LED

20xF LED

8 wat

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

1,60kg

1,60kg

1,60kg

2,00kg

2,00kg

2,00kg

1,35kg

1,50kg

1,60kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

2w

8w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

Visible Distance 28 meter

DEKOLITE DOUBLE SIDE EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-58

Page 59: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DEKOLITE-ZEMERGENCY GUIDANCE FIXTURE

• Surface mounting,extruded aluminum profile body, ABS plastic corners.• 3mm acrylic diffuser• Different size options• Electrostatic powder whitepainted back metal sheet panel

USAGE AREAS• Offices• Grocery stores• Warehouses• Parking lots and large areas• Hospitals• Corridors• Restaurants and bars• Universities, Student dormitories, Schoolsand colleges LAMP OPTIONS• G5 socket T5 8w fluorescent bulb, 6500°K• G13 socket T8 18w fluorescent bulb,6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - Extruded aluminum profile body,ABS plastic brackets• With label panel - 3 mm acrylic panel,application of latex on white foil• BATTERY - Nickel-cadmium in all modelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times.

• Can be used in door-top applications, withaluminum profile body, fluorescent bulb and LED option, decorative emergency exit directional fitting.• The model table is divided into 3 according tothe measurement. Electrostatic powder coated aluminum profile and rear mounting plate combined with ABS brackets• There are 2 fluorescent lamps with fluorescentlamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• is an independent emergency exit orientationluminaire located within the battery and power supply..• Continuous charging method keeps the batterypack full and ready.• The mains supply voltage is standard 220 voltsAC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-59

Page 60: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

Z30 MODELVisible Distance 30 meter

Z40 MODELVisible Distance 34 meter

Z50 MODELVisible Distance 60 meter

AE-3111

AE-3112

AE-3113

AE-3211

AE-3212

AE-3213

AE-3113-L

AE-3213-L

AE-3010

Emergency Light

Emergency Light

Emergency Light

Combined m.

Combined m.

Combined m.

Emergency Light

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat

8 wat

8 wat

2x8 wat

2x8 wat

2x8 wat

500lm LED

500lm LED

8 wat

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

75x325x187mm

75x325x187mm

75x325x187mm

75x325x187mm

75x325x187mm

75x325x187mm

75x325x187mm

75x325x187mm

75x325x187mm

1,60kg

1,75kg

1,80kg

2,00kg

2,15kg

2,20kg

2,10kg

2,10kg

1,50kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

5,5w

8w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

DEKOLITE Z30 SERIES WALL MOUNT

AE-4111

AE-4112

AE-4113

AE 4211

AE 4212

AE-4213

AE-4113 -L

AE-4213 -L

AE-4010

Emergency Light

Emergency Light

Emergency Light

Combined m.

Combined m.

Combined m.

Emergency Light

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat

8 wat

8 wat

2x8 wat

2x8 wat

2x8 wat

500lm LED

500lm LED

8 wat

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

75x422x200mm

75x422x200mm

75x422x200mm

75x422x200mm

75x422x200mm

75x422x200mm

75x422x200mm

75x422x200mm

75x422x200mm

1,90kg

2,05kg

2,10kg

2,30kg

2,45kg

2,50kg

2,40kg

2,40kg

1,80kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

5,5w

8w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

DEKOLITE Z40 SERIES WALL MOUNT

AE-5111

AE-5112

AE 5113

AE-5211

AE-5212

AE-5213

AE-5113-L

AE-5213 -L

AE-5010 -L

Emergency Light

Emergency Light

Emergency Light

Maintained

Maintained

Maintained

Emergency Light

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

18 wat

18 wat

18 wat

18 wat

18 wat

18 wat

1000lm LED

1000lm LED

1000lm LED

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

75x672x370mm

75x672x370mm

75x672x370mm

75x672x370mm

75x672x370mm

75x672x370mm

75x672x370mm

75x672x370mm

75x672x370mm

4,50kg

4,65kg

4,70kg

4,90kg

5,05kg

5,10kg

5,40kg

5,40kg

4,50kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

21w

21w

21w

2w

11w

9,5w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

DEKOLITE Z50 SERIES WALL MOUNT

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

ARSEL-60

Page 61: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DEKOLITE-Z DOUBLE FACED EMERGENCY GUIDANCE FIXTURE

• Surface mounting,extruded aluminum profile body, ABS plastic corners.• 3mm acrylic diffuser• Different size options• İki yüzü ışıklı panelarmatür

USAGE AREAS• Offices• Grocery stores• Warehouses• Parking lots and large areas• Hospitals• Corridors• Restaurants and bars• Universities, Student dormitories, Schools andcollegesLAMP OPTIONS• G5 socket T5 8w fluorescent bulb, 6500°K• G13 socket T8 18w fluorescent bulb, 6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - Extruded aluminum profile body, ABSplastic brackets• With label panel - 3 mm acrylic panel,application of latex on white foil• BATTERY - Nickel-cadmium in all modelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times.

• It can be used in ceiling mount applications,with aluminum profile body, fluorescent bulb and LED, decorative emergency exit directional fitting.• The model table is divided into 3 according tothe measurement. Electrostatic powder coated aluminum profile and rear mounting plate combined with ABS brackets• There are 2 fluorescent lamps with fluorescentlamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• is an independent emergency exit orientationluminaire located within the battery and power supply..• Continuous charging method keeps the batterypack full and ready.• The mains supply voltage is standard 220volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts.• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-61

Page 62: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AE 3121

AE 3122

AE-3123

AE-3221

AE-3222

AE-3223

AE-3123-L

AE-3223-L

AE-3020

Emergency Light

Emergency Light

Emergency Light

Kombine Sürekli

Combined m.

Combined m.

Emergency Light

Maintained

Mains Light

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

8 wat

8 wat

8 wat

2x8 wat

2x8 wat

2x8 wat

500lm LED

500lm LED

8 wat

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

75x320x165mm

1,75kg

1,90kg

1,95kg

2,15kg

2,30kg

2,35kg

2,25kg

2,25kg

1,65kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

5,5w

8w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

DEKOLITE Z30 SERIES DOUBLE FACED CEILING MOUNT

AE-4121

AE-4122

AE-4123

AE 4221

AE 4222

AE-4223

AE-4123 -L

AE-4223 -L

AE-4020

Emergency Light

Emergency Light

Emergency Light

Kombine Sürekli

Combined m.

Combined m.

Emergency Light

Maintained

Mains Light

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

8 wat

8 wat

8 wat

2x8 wat

2x8 wat

2x8 wat

500lm LED

500lm LED

8 wat

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

75x400x180mm

75x400x180mm

75x400x180mm

75x400x180mm

75x400x180mm

75x400x180mm

75x400x180mm

75x400x180mm

75x400x180mm

2,10kg

2,25kg

2,30kg

2,50kg

2,65kg

2,70kg

2,60kg

2,60kg

2,00kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

5,5w

8w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

DEKOLITE Z40 SERIES DOUBLE FACED CEILING MOUNT

AE-5121

AE-5122

AE-5123

AE-5221

AE-5222

AE-5223

AE-5123-L

AE-5223 -L

AE-5010 -L

Emergency Light

Emergency Light

Emergency Light

Sürekli Yanan

Maintained

Maintained

Emergency Light

Maintained

Mains Light

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

Ceiling Mount

18 wat

18 wat

18 wat

18 wat

18 wat

18 wat

1000lm LED

1000lm LED

1000lm LED

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

Double Face

75x650x350mm

75x650x350mm

75x650x350mm

75x650x350mm

75x650x350mm

75x650x350mm

75x650x350mm

75x650x350mm

75x650x350mm

4,80kg

4,95kg

5,00kg

5,20kg

5,35kg

5,40kg

5,70kg

5,70kg

4,80kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

21w

21w

21w

2w

11w

9,5w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

DEKOLITE Z50 SERIES DOUBLE FACED CEILING MOUNT

Z30 MODEL Z40 MODELVisible Distance 34 meter

Z50 MODELVisible Distance 60 meterVisible Distance 30 meter

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

ARSEL-62

Page 63: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

TWINLITEEMERGENCY GUIDANCE FIXTURE

• Surface mounting, metal sheetcase• Combined emergency lightingand orientation• LED spotlights for emergencylighting• 3 mm thick acrylic light panel

USAGE AREAS• Offices• Grocery stores• Corridors• Restaurants and bars• Universities, Student dormitories,Schools and colleges LAMP OPTIONS• G5 socket T5 8w fluorescent bulb,6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - Powder white painted sheetmetal chassis• With label panel - 3 mm acrylicpanel, application of latex on white foil• BATTERY - Nickel-cadmium in allmodelsOPTIONS• Continuous and emergency models.• 1-2-3 hour emergency backuptimes.

• A 8 wat fluorescent bulb is used for guidance panelillumination.• There are only 1 fluorescent lamp in bothmaintained and non maintained models. The same lamp continues to burn when there is an emergency,.• Spot lighting is activated only when the power fails.• Articulated spot light provides limited guidance• is an independent emergency exit orientationluminaire located within the battery and power supply..• Continuous charging method keeps the batterypack full and ready.• The mains supply voltage is standard 220 volts AC50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under 150volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-63

Page 64: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

TW-111

TW-112

TW-113

TW-121-L

TW-122-L

TW-123-L

Emergency Light

Emergency Light

Emergency Light

Maintained

Maintained

Maintained

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat+LED

8 wat+LED

8 wat+LED

LED+LED

LED+LED

LED+LED

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 90 m.

Emergency 120 m.

Emergency 180 m.

Emergency 90 m.

Emergency 120 m.

Emergency 180 m.

55x324x270mm

55x324x270mm

55x324x270mm

55x324x270mm

55x324x270mm

55x324x270mm

1,90kg

1,90kg

1,90kg

2,00kg

2,00kg

2,00kg

40

40

40

40

40

40

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

4w

4w

4w

12w

12w

12w

220-240

220-240

220-240

220-240

220-240

220-240

Visible Distance 28 meter

324 mm

270m

m

55

TWINLITE EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-64

Page 65: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

ELITELITEEMERGENCY GUIDANCE FIXTURE

• Surface mounting, metalsheet case• 5 round light windows atthe bottom for floor lighting• 3 mm thick acrylic lightpanel

USAGE AREAS• Offices• Grocery stores• Corridors• Restaurants and bars• Universities, Student dormitories,Schools and colleges LAMP OPTIONS• G5 socket T5 8w fluorescent bulb,6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - Powder white painted sheetmetal chassis• With label panel - 3 mm acrylicpanel, application of latex on white foil• BATTERY - Nickel-cadmium in allmodelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times.

• The fixture, which can be mounted on the wallor one top the door, It also provides under floor lighting through round windows.• There are 2 fluorescent lamps with fluorescentlamps and continuous lighting. One of the lamps is on line voltage and the other is power failure.• is an independent emergency exit orientationluminaire located within the battery and power supply..• Continuous charging method keeps the batterypack full and ready.• The mains supply voltage is standard 220 voltsAC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts.• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-65

Page 66: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AE-4111

AE-4112

AE-4113

AE 4211

AE 4212

AE-4213

AE-4113 -L

AE-4213 -L

AE-4010

Emergency Light

Emergency Light

Emergency Light

Combined m.

Combined m.

Combined m.

Emergency Light

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat

8 wat

8 wat

2x8 wat

2x8 wat

2x8 wat

20xF LED

20xF LED

8 wat

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

70x400x185mm

70x400x185mm

70x400x185mm

70x400x185mm

70x400x185mm

70x400x185mm

70x400x185mm

70x400x185mm

70x400x185mm

2,20kg

2,20kg

2,20kg

2,60kg

2,60kg

2,60kg

1,95kg

2,00kg

2,25kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

2w

8w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

ELITELITE EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

Visible Distance 32 metre

ARSEL-66

Page 67: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

EKOLITEEMERGENCY GUIDANCE FIXTURE

• Surface mounting, metalsheet case• Economic exit marking• 3 mm thick acrylic lightpanel

USAGE AREAS• Offices• Grocery stores• Corridors• Restaurants and bars• Universities, Student dormitories,Schools and colleges LAMP OPTIONS• G5 socket T5 8w fluorescent bulb,6500°K• White light LED bulb, 6500°KBODY STRUCTURE• Body - Powder white painted sheetmetal chassis• With label panel - 3 mm acrylicpanel, application of latex on white foil• BATTERY - Nickel-cadmium in allmodelsOPTIONS• Continuous and emergency models.• 1-3 hour emergency backup times.

• The armature, which can be mounted on thewall door, is designed for economic markings according to the standards.• There are only 1 fluorescent lamp in bothmaintained and non maintained models. The same lamp continues to burn when there is an emergency,• is an independent emergency exit orientationluminaire located within the battery and power supply..• Continuous charging method keeps the batterypack full and ready.• The mains supply voltage is standard 220 voltsAC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under 150volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-67

Page 68: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AE-6111

AE-6112

AE-6113

AE-6211

AE-6212

AE-6213

AE-6113-L

AE-6213-L

AE-6010 -L

Emergency Light

Emergency Light

Emergency Light

Maintained

Maintained

Maintained

Emergency Light

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

8 wat

8 wat

8 wat

8 wat

8 wat

8 wat

20xF LED

20xF LED

20xF LED

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 180 m.

Emergency 180 m.

55x324x173mm

55x324x173mm

55x324x173mm

55x324x173mm

55x324x173mm

55x324x173mm

55x324x173mm

55x324x173mm

55x324x173mm

1,45kg

1,65kg

1,70kg

1,75kg

1,95kg

2,00kg

1,45kg

1,45kg

1,30kg

40

40

40

40

40

40

40

40

40

I

I

I

I

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

3w

3w

3w

11w

11w

11w

1w

2w

8w

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

Visible Distance 28 meter

55mm

324mm

173m

m

EKOLITE EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

ARSEL-68

Page 69: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

S ITEEMERGENCY GUIDANCE FIXTURE

USAGE AREAS• Fire ladders• Control center management rooms• Boiler rooms• Offices• Grocery stores• Corridors• Restaurants and bars• Universities, Student dormitories,Schools and collegesLAMP OPTIONS• White light LED bulb, 6500°KBODY STRUCTURE• Body - ABS plastic case• Label panel - transparent acrylicpanel.• BATTERY - Nickel-cadmium in allmodels

OPTIONS• Continuous and emergency models• 1-3 hour emergency backup times

• It is designed for economic markings that canbe used in the wall and door applications.• For easy connection, the latching terminal isleft in the slot behind the luminaire.• All plastic equipments provide necessaryflame-proof conditions.• Continuous charging method keeps thebattery pack full and ready.• The mains supply voltage is standard 220volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

• Surface mounting, ABSplastic case• Transparent acrylic lightpanel

ARSEL-69

Page 70: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AS-3111

AS-3113

AS-3211

AS-3213

AS-3010

Emergency Light

Emergency Light

Maintained

Maintained

Mains Light

Wall Mount

Wall Mount

Wall Mount

Wall Mount

Wall Mount

20x F LED

20x F LED

20x F LED

20x F LED

20x F LED

Single Face

Single Face

Single Face

Single Face

Single Face

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

30x320x140mm

30x320x140mm

30x320x140mm

30x320x140mm

30x320x140mm

0,52kg

0,72kg

0,57kg

0,76kg

0,47kg

40

40

40

40

40

I

I

I

I

I

-16/+45°

-16/+45°

-16/+45°

-16/+45°

-16/+45°

0,5w

0,5w

3w

3w

2w

220-240

220-240

220-240

220-240

220-240

SEALITE EMERGENCY GUIDANCE FIXTURE

MODEL CODE LIGHTING STYLE MOUNTING STYLE LAMP LIGHT FACEDURATION(minute) WEIGHT

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

DIMENSIONS(W-L-H)mm

--

Visible Distance 28 meter

ARSEL-70

Page 71: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

EMERGENCY BATTERY PACK FOR FLUORESCENT'S

Page 72: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AK-4681, 4683 EMERGENCYBATTERY PACK FORFLUORESCENT'S

• Emergency backup units forfluorescent lamps• It can be used with anarmature mounted inside or with an external box.• Supplied with Ni-Cd Battery.

USAGE AREAS• 4-6-8 wat Fluorescent BulbFixtures• Emergency lighting andguidance fittings

BODY STRUCTURE• Body - Electrostatic powdercoated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Nickel-cadmium inall models OPTIONS• Model choices according tolamp type and power• 1-2-3 hour emergencybackup times.

• Provides power failure backup for fluorescentlamps.• It can work with all magnetic and electronicballasts.• Mounted within the housing of the fittings that isused for lighting, emergency lighting is provided to do.• The lamp's 4 connections are switched at once.• With fully insulated supply circuit and the lampcontacts, there is no damage due to the different phase connections.• Appropriate kit should be selected according tothe lamp.• Plug-in type latching type terminals are used foreasy installation.• The mains supply voltage is standard 220 volts AC50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under 150volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-72

Page 73: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AK-468-1

AK-468-2

AK-468-3

AK581

AK582

AK583

AK-141

AK-143

AK541

AK543

AK581-E

AK583-E

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

6-8W T5 Fluoresan

6-8W T5 Fluoresan

6-8W T5 Fluoresan

18-58w T8 ---- 7-26w PL

18-58w T8 ---- 7-26w PL

18-58w T8 ---- 7-26w PL

13-14W T5 Fluoresan

13-14W T5 Fluoresan

18-58wT8, 7-26wPL, 28-54wT5

18-58wT8, 7-26wPL, 28-54wT5

18-36w T8 ---- 7-18w PL

18-36w T8 ---- 7-18w PL

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

3 cell AA size

3 cell SC size

3 cell SC size

3 cell SC size

3 cell D size

3 cell D size

5 cell SC size

2X5 cell SC size

5 cell SC size

5 cell D size

3 cell SC size

2x3 cell SC size

0,28kg

0,35kg

0,38kg

0,39kg

0,6kg

0,6kg

0,44kg

0,67kg

0,45kg

0,75kg

0,35kg

0,55kg

30

30

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

I

I

>%30

>%30

>%30

>%19

>%19

>%19

>%40

>%40

>%22

>%22

>%19

>%19

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

1,5 watt

1,5 watt

1,5 watt

3,2 watt

3,2 watt

3,2 watt

1,5 watt

1,5 watt

3,2 watt

3,2 watt

1,5 watt

1,5 watt

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

EMERGENCY BATTERY PACKS FOR FLUORESCENT LIGHTS

MODEL CODE LIGHTING STYLEUSAGE TYPE LAMP DURATION

WEIGHT(Batt inc.)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUPTION

OPERATINGVOLTAGEBATTERY BLF

TİP T5 T8 SE-DE COMPACT DULUX L-F CIRCLINEGÜÇ 6 8 13 14 36 54 18 36 58 7 9 13 18 26 36 54 22T5 40T5

KIT SELECTION TABLES FOR LAMP

468-1 X X468-2 X X468-3 X X581-E X X583-E X X581 XX582 X X583 XX141 X X143 X X541542543

X XX XX XX X

X XX X

X XX XX XX X

X

XX

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

ARSEL-73

Page 74: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AK-581, 583 EMERGENCYBATTERY PACK FORFLUORESCENT'S

• Emergency backup units forfluorescent lamps• It can be used with an armaturemounted inside or with an external box.• Supplied with Ni-Cd Battery.

USAGE AREAS• 18-36 wat T8 FluorescentBulb Fixtures• Emergency lighting andguidance fittings• Downlight type, PL bulblighting fixtures

BODY STRUCTURE• Body - Electrostaticpowder coated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Nickel-cadmium in all models

OPTIONS• Model choices accordingto lamp type and power• 1-2-3 hour emergencybackup times.

• Provides power failure backup for fluorescentlamps.• It can work with all magnetic and electronicballasts.• Mounted within the housing of the fittings thatis used for lighting, emergency lighting is provided to do.• The lamp's 4 connections are switched atonce.• With fully insulated supply circuit and the lampcontacts, there is no damage due to the different phase connections.• Appropriate kit should be selected accordingto the lamp.• Plug-in type latching type terminals are usedfor easy installation.• The mains supply voltage is standard 220 voltsAC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts atmains voltage.• Switches to emergency lighting mode under150 volts, charging over 185 volts• It is manufactured according to TS 8710EN60598-2-22 standard in the framework of ISO 9001-2000 quality management system.

ARSEL-74

Page 75: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AK-468-1

AK-468-2

AK-468-3

AK581

AK582

AK583

AK-141

AK-143

AK541

AK543

AK581-E

AK583-E

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

6-8W T5 Fluoresan

6-8W T5 Fluoresan

6-8W T5 Fluoresan

18-58w T8 ---- 7-26w PL

18-58w T8 ---- 7-26w PL

18-58w T8 ---- 7-26w PL

13-14W T5 Fluoresan

13-14W T5 Fluoresan

18-58wT8, 7-26wPL, 28-54wT5

18-58wT8, 7-26wPL, 28-54wT5

18-36w T8 ---- 7-18w PL

18-36w T8 ---- 7-18w PL

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

3 cell AA size

3 cell SC size

3 cell SC size

3 cell SC size

3 cell D size

3 cell D size

5 cell SC size

2X5 cell SC size

5 cell SC size

5 cell D size

3 cell SC size

2x3 cell SC size

0,28kg

0,35kg

0,38kg

0,39kg

0,6kg

0,6kg

0,44kg

0,67kg

0,45kg

0,75kg

0,35kg

0,55kg

30

30

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

I

I

>%30

>%30

>%30

>%19

>%19

>%19

>%40

>%40

>%22

>%22

>%19

>%19

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

1,5 watt

1,5 watt

1,5 watt

3,2 watt

3,2 watt

3,2 watt

1,5 watt

1,5 watt

3,2 watt

3,2 watt

1,5 watt

1,5 watt

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

EMERGENCY BATTERY PACKS FOR FLUORESCENT LIGHTS

MODEL CODE LIGHTING STYLEUSAGE TYPE LAMP DURATION

WEIGHT(Batt inc.)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUPTION

OPERATINGVOLTAGEBATTERY BLF

TİP T5 T8 SE-DE COMPACT DULUX L-F CIRCLINEGÜÇ 6 8 13 14 36 54 18 36 58 7 9 13 18 26 36 54 22T5 40T5

KIT SELECTION TABLES FOR LAMP

468-1 X X468-2 X X468-3 X X581-E X X583-E X X581 XX582 X X583 XX141 X X143 X X541542543

X XX XX XX X

X XX X

X XX XX XX X

X

XX

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

XX

X

ARSEL-75

Page 76: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AK-541, 543 EMERGENCY BATTERY PACK FOR FLUORESCENT'S

• Emergency backup unitsfor fluorescent lamps• It can be used with anarmature mounted inside or with an external box.• Supplied with Ni-Cd Battery.

USAGE AREAS• 18-36 wat T8, 36-80watT5 Fluorescent Bulb Fixtures• Emergency lighting andguidance fittings• Downlight type, PL bulblighting fixturesBODY STRUCTURE• Body - Electrostaticpowder coated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Nickel-cadmium in all models

OPTIONS• Model choices accordingto lamp type and power• 1-2-3 hour emergencybackup times.

• Provides power failure backup for fluorescent lamps.• It can work with all magnetic and electronic ballasts.• Mounted within the housing of the fittings that is usedfor lighting, emergency lighting is provided to do.• The lamp's 4 connections are switched at once.• With fully insulated supply circuit and the lamp contacts,there is no damage due to the different phase connections.• Appropriate kit should be selected according to thelamp.• Plug-in type latching type terminals are used for easyinstallation.• The mains supply voltage is standard 220 volts AC 50Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mainsvoltage.• Switches to emergency lighting mode under 150 volts,charging over 185 volts• It is manufactured according to TS 8710 EN60598-2-22standard in the framework of ISO 9001-2000 quality management system.

ARSEL-76

Page 77: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

AK-468-1

AK-468-2

AK-468-3

AK581

AK582

AK583

AK-141

AK-143

AK541

AK543

AK581-E

AK583-E

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

6-8W T5 Fluoresan

6-8W T5 Fluoresan

6-8W T5 Fluoresan

18-58w T8 ---- 7-26w PL

18-58w T8 ---- 7-26w PL

18-58w T8 ---- 7-26w PL

13-14W T5 Fluoresan

13-14W T5 Fluoresan

18-58wT8, 7-26wPL, 28-54wT5

18-58wT8, 7-26wPL, 28-54wT5

18-36w T8 ---- 7-18w PL

18-36w T8 ---- 7-18w PL

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

3 cell AA size

3 cell SC size

3 cell SC size

3 cell SC size

3 cell D size

3 cell D size

5 cell SC size

2X5 cell SC size

5 cell SC size

5 cell D size

3 cell SC size

2x3 cell SC size

0,28kg

0,35kg

0,38kg

0,39kg

0,6kg

0,6kg

0,44kg

0,67kg

0,45kg

0,75kg

0,35kg

0,55kg

30

30

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

I

I

>%30

>%30

>%30

>%19

>%19

>%19

>%40

>%40

>%22

>%22

>%19

>%19

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

1,5 watt

1,5 watt

1,5 watt

3,2 watt

3,2 watt

3,2 watt

1,5 watt

1,5 watt

3,2 watt

3,2 watt

1,5 watt

1,5 watt

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

EMERGENCY BATTERY PACKS FOR FLUORESCENT LIGHTS

MODEL CODE LIGHTING STYLEUSAGE TYPE LAMP DURATION

WEIGHT(Batt inc.)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUPTION

OPERATINGVOLTAGEBATTERY BLF

TİP T5 T8 SE-DE COMPACT DULUX L-F CIRCLINEGÜÇ 6 8 13 14 36 54 18 36 58 7 9 13 18 26 36 54 22T5 40T5

KIT SELECTION TABLES FOR LAMP

468-1 X X468-2 X X468-3 X X581-E X X X X X X583-E X X X X X X581 X X X X X X X582 X X X X X X X583 X X X X X X X141 X X143 X X541 X X X X X X X X X X X X X X542 X X X X X X X X X X X X X X543 X X X X X X X X X X X X X X

ARSEL-77

Page 78: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

EMERGENCY BATTERY PACK FOR LED'S

Page 79: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AK-312 EMERGENCY BATTERY PACK FOR LED'S

• Emergency backup units forLED lamps• It can be used with anarmature mounted inside or with an external box.• Supplied with Ni-Cd Battery.

USAGE AREAS• LED lighting fixtures• Emergency lighting andguidance fittings• Waterproof type LEDlighting fixtures• Special design ledlighting fixtures• Recessed typeluminaires

BODY STRUCTURE• Body - Electrostaticpowder coated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Nickel-cadmium in all models OPTIONS• Model choicesaccording to lamp type and power• 1-2-3 hour emergencybackup times

AK-312 model emergency backup modules;• The LED is connected between the driver and the led panel.• It can switch the maximum 2 a dc led current.• 3,6 volt ni-cd battery, are plug-in type terminals.• It should be installed inside the armature or in the externalbox.• It does not have standard output current, special productionaccording to lamp, backup time and lamp safety are provided in this way.• Provides power failure backup for LED lamps.• Battery charging indicator.• The lamp's 2 connections are switched at once.• With fully insulated supply circuit and the lamp contacts, thereis no damage due to the different phase connections.• Continuous charging method keeps the battery pack full andready.• Appropriate kit should be selected according to the lamp.• Plug-in type latching type terminals are used for easyinstallation.• The mains supply voltage is standard 220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mains voltage.• Switches to emergency lighting mode under 150 volts,charging over 185 volts• It is manufactured according to TS 8710 EN60598-2-22standard in the framework of ISO 9001-2000 quality management system.

ARSEL-79

Page 80: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

EMERGENCY BACKUP UNITS FOR LED LAMPS

AK-312-1

AK-312-2

AK-312-3

AK-4600-1

AK-4600-3

AK-7200-1

AK-7200-2

AK-7200-3

AK-609W-1

AK-609W-2

AK-4600S-1

AK-4600S-3

AK-4600S-EKO

AK-2400

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

12 volt led lamp

12 volt led lamp

12 volt led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

110-220 volt AC led lamp

110-220 volt AC led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

12-65 volt led lamp

220 volt <25w lamp

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 60 m.

Emergency 180 m.

Emergency 180 m.

-

0,28kg

0,35kg

0,38kg

0,27kg

0,37kg

0,33kg

0,5kg

0,5kg

0,45kg

0,75kg

0,27kg

0,30kg

0,27kg

0,5kg

30

30

30

30

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

I

I

I

I

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

3,5 watt

3,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

3 cell AA size

3 cell SC size

3 cell SC size

4 cell AA size

4 cell SC size

6 cell AA size

6 cell SC size

6 cell SC size

5 cell SC size

5 cell D size

6 cell AA size

6 cell AA size

6 cell AA size

MODEL CODE LIGHTING STYLE USAGE TYPE

LAMP DURATION WEIGHT(Batt inc.)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUPTION

OPERATINGVOLTAGEBATTERY

BATTERIES

ARSEL-80

Page 81: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AK-4600-1, 4600-3 EMERGENCY BATTERYPACK FOR LED'S

• Emergency backup unitsfor LED lamps• It can be used with anarmature mounted inside or with an external box.• Supplied with Ni-CdBattery.

USAGE AREAS• LED lighting fixtures• Emergency lightingand guidance fittings• Waterproof type LEDlighting fixtures• Special design ledlighting fixtures• Recessed typeluminaires

BODY STRUCTURE• Body - Electrostaticpowder coated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Nickel-cadmium in all models

OPTIONS• Model choicesaccording to lamp type and power

AK-4600 model emergency backup modules;• The LED is connected between the driver and the led panel.• It can switch the maximum 2 a dc led current.• The LEDs are driven with a current controlled dc 50kHz 0-70V. Nosetting required by the lamp• 4,8 volt ni-cd battery, are plug-in type terminals.• It should be installed inside the armature or in the external box.• It has a standard output current. (90ma max)• It can illuminate all led panels working in 3-65 volts range(3v-70ma, 65v-15ma)• It makes a backup at power failure.• Battery charging indicator.• The lamp's 2 connections are switched at once.• With fully insulated supply circuit and the lamp contacts, there isno damage due to the different phase connections.• Continuous charging method keeps the battery pack full andready.• Appropriate kit should be selected according to the lamp.• Plug-in type latching type terminals are used for easy installation.• The mains supply voltage is standard 220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mains voltage.• Switches to emergency lighting mode under 150 volts, chargingover 185 volts• It is manufactured according to TS 8710 EN60598-2-22 standardin the framework of ISO 9001-2000 quality management system.

ARSEL-81

Page 82: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

EMERGENCY BACKUP UNITS FOR LED LAMPS

AK-312-1

AK-312-2

AK-312-3

AK-4600-1

AK-4600-3

AK-7200-1

AK-7200-2

AK-7200-3

AK-609W-1

AK-609W-2

AK-4600S-1

AK-4600S-3

AK-4600S-EKO

AK-2400

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

12 volt led lamp

12 volt led lamp

12 volt led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

110-220 volt AC led lamp

110-220 volt AC led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

12-65 volt led lamp

220 volt <25w lamp

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 60 m.

Emergency 180 m.

Emergency 180 m.

-

0,28kg

0,35kg

0,38kg

0,27kg

0,37kg

0,33kg

0,5kg

0,5kg

0,45kg

0,75kg

0,27kg

0,30kg

0,27kg

0,5kg

30

30

30

30

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

I

I

I

I

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

3,5 watt

3,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

3 cell AA size

3 cell SC size

3 cell SC size

4 cell AA size

4 cell SC size

6 cell AA size

6 cell SC size

6 cell SC size

5 cell SC size

5 cell D size

6 cell AA size

6 cell AA size

6 cell AA size

MODEL CODE LIGHTING STYLE USAGE TYPE

LAMP DURATION WEIGHT(Batt inc.)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUPTION

OPERATINGVOLTAGEBATTERY

BATTERIES

ARSEL-82

Page 83: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AK-4600S-EKO EMERGENCY BATTERYPACK FOR LED'S

• Emergency backupunits for LED lamps• It can be used withan armature mounted inside or with an external box.• Supplied with Ni-CdBattery.

USAGE AREAS• LED lighting fixtures• Emergency lighting andguidance fittings• Waterproof type LEDlighting fixtures• Special design led lightingfixtures• Recessed type luminaires

BODY STRUCTURE• Body - Electrostaticpowder coated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Nickel-cadmium in all models OPTIONS• Model choices accordingto lamp type and power• 1-2-3 hour emergencybackup times

• The LED is connected between the driver and the led panel.• It should not be used with non-resistive led panels. Not suitable forsingle LED connection.• 22 mm profile height.• It can switch the maximum 1 a dc led current. (relay-free,semiconductor routing)• The LEDs are driven with a current controlled dc 5kHz 12-70V. Nosetting required by the lamp• 7,2 volt ni-cd battery, are plug-in type terminals.• It should be installed inside the armature or in the external box.• It has a standard output current. (90ma max)• It can illuminate all led panels working in 12-65 volts range(12v-65ma,65v-10ma)• It makes a backup at power failure.• Battery charging indicator.• With fully insulated supply circuit and the lamp contacts, there is nodamage due to the different phase connections.• Continuous charging method keeps the battery pack full and ready.• Appropriate kit should be selected according to the lamp.• Plug-in type latching type terminals are used for easy installation.• The mains supply voltage is standard 220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mains voltage.• Switches to emergency lighting mode under 150 volts, charging over185 volts• It is manufactured according to TS 8710 EN60598-2-22 standard inthe framework of ISO 9001-2000 quality management system.

ARSEL-83

Page 84: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

EMERGENCY BACKUP UNITS FOR LED LAMPS

AK-312-1

AK-312-2

AK-312-3

AK-4600-1

AK-4600-3

AK-7200-1

AK-7200-2

AK-7200-3

AK-609W-1

AK-609W-2

AK-4600S-1

AK-4600S-3

AK-4600S-EKO

AK-2400

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

12 volt led lamp

12 volt led lamp

12 volt led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

110-220 volt AC led lamp

110-220 volt AC led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

12-65 volt led lamp

220 volt <25w lamp

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 60 m.

Emergency 180 m.

Emergency 180 m.

-

0,28kg

0,35kg

0,38kg

0,27kg

0,37kg

0,33kg

0,5kg

0,5kg

0,45kg

0,75kg

0,27kg

0,30kg

0,27kg

0,5kg

30

30

30

30

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

I

I

I

I

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

3,5 watt

3,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

3 cell AA size

3 cell SC size

3 cell SC size

4 cell AA size

4 cell SC size

6 cell AA size

6 cell SC size

6 cell SC size

5 cell SC size

5 cell D size

6 cell AA size

6 cell AA size

6 cell AA size

MODEL CODE LIGHTING STYLE USAGE TYPE

LAMP DURATION WEIGHT(Batt inc.)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUPTION

OPERATINGVOLTAGEBATTERY

BATTERY

ARSEL-84

Page 85: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AK-7200-1, 7200-3 EMERGENCY BATTERYPACK FOR LED'S

• Emergency backupunits for LED lamps• It can be used withan armature mounted inside or with an external box.• Supplied with Ni-CdBattery.

USAGE AREAS• LED lighting fixtures• Emergency lighting andguidance fittings• Waterproof type LEDlighting fixtures• Special design ledlighting fixtures• Recessed typeluminaires

BODY STRUCTURE• Body - Electrostaticpowder coated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Nickel-cadmium in all models

OPTIONS• Model choicesaccording to lamp type and power• 1-2-3 hour emergencybackup times

AK-7200 model emergency backup modules;• The LED is connected between the driver and the led panel.• It can switch the maximum 2 a dc led current.• The LEDs are driven with a current controlled dc 50kHz 0-200V.No setting required by the lamp• 7,2 volt ni-cd battery, are plug-in type terminals.• It should be installed inside the armature or in the external box.• It has a standard output current.(70ma max)• It can illuminate all led panels working in 3-65 voltsrange(3v-200ma, 200v-15ma)• Provides power failure backup for LED lamps.• It makes a backup at power failure.• Battery charging indicator.• The lamp's 2 connections are switched at once.• With fully insulated supply circuit and the lamp contacts, there isno damage due to the different phase connections.• Continuous charging method keeps the battery pack full andready.• Plug-in type latching type terminals are used for easy installation.• The mains supply voltage is standard 220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mains voltage.• Switches to emergency lighting mode under 150 volts, chargingover 185 volts• It is manufactured according to TS 8710 EN60598-2-22 standardin the framework of ISO 9001-2000 quality management system.

ARSEL-85

Page 86: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

EMERGENCY BACKUP UNITS FOR LED LAMPS

AK-312-1

AK-312-2

AK-312-3

AK-4600-1

AK-4600-3

AK-7200-1

AK-7200-2

AK-7200-3

AK-609W-1

AK-609W-2

AK-4600S-1

AK-4600S-3

AK-4600S-EKO

AK-2400

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

12 volt led lamp

12 volt led lamp

12 volt led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

110-220 volt AC led lamp

110-220 volt AC led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

12-65 volt led lamp

220 volt <25w lamp

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 60 m.

Emergency 180 m.

Emergency 180 m.

-

0,28kg

0,35kg

0,38kg

0,27kg

0,37kg

0,33kg

0,5kg

0,5kg

0,45kg

0,75kg

0,27kg

0,30kg

0,27kg

0,5kg

30

30

30

30

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

I

I

I

I

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

3,5 watt

3,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

3 cell AA size

3 cell SC size

3 cell SC size

4 cell AA size

4 cell SC size

6 cell AA size

6 cell SC size

6 cell SC size

5 cell SC size

5 cell D size

6 cell AA size

6 cell AA size

6 cell AA size

MODEL CODE LIGHTING STYLE USAGE TYPE

LAMP DURATION WEIGHT(Batt inc.)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUPTION

OPERATINGVOLTAGEBATTERY

BATTERIES

ARSEL-86

Page 87: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AK-609-1, 609-2 EMERGENCY BATTERY PACK FOR LED'S

• Emergency backupunits for LED lamps• It can be used withan armature mounted inside or with an external box.• Supplied with Ni-CdBattery.

USAGE AREAS• LED lighting fixtures• Emergency lighting andguidance fittings• Waterproof type LEDlighting fixtures• Special design led lightingfixtures• Recessed type luminaires

BODY STRUCTURE• Body - Electrostaticpowder coated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Nickel-cadmium in all models

OPTIONS• Model choices accordingto lamp type and power• 1-2 hour emergencybackup times

• 9w is connected to the supply input of the LED drivers which canoperate with DC voltage below.• There are models connected between the led drive and the ledpanel or directly connected to the led driver input.• Maximum 5 may switch the DC LED current.• 6 volt ni-cd battery, are plug-in type terminals.• It should be installed inside the armature or in the external box.• It does not have standard output current, special productionaccording to lamp, backup time and lamp safety are provided in this way.• Provides power failure backup for LED lamps.• It makes a backup at power failure.• Battery charging indicator.• The lamp's 2 connections are switched at once.• With fully insulated supply circuit and the lamp contacts, there isno damage due to the different phase connections.• Continuous charging method keeps the battery pack full andready.• Appropriate kit should be selected according to the lamp.• Plug-in type latching type terminals are used for easy installation.• The mains supply voltage is standard 220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mains voltage.• Switches to emergency lighting mode under 150 volts, chargingover 185 volts• It is manufactured according to TS 8710 EN60598-2-22 standardin the framework of ISO 9001-2000 quality management system.

ARSEL-87

Page 88: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

EMERGENCY BACKUP UNITS FOR LED LAMPS

AK-312-1

AK-312-2

AK-312-3

AK-4600-1

AK-4600-3

AK-7200-1

AK-7200-2

AK-7200-3

AK-609W-1

AK-609W-2

AK-4600S-1

AK-4600S-3

AK-4600S-EKO

AK-2400

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

12 volt led lamp

12 volt led lamp

12 volt led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

110-220 volt AC led lamp

110-220 volt AC led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

12-65 volt led lamp

220 volt <25w lamp

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 60 m.

Emergency 180 m.

Emergency 180 m.

-

0,28kg

0,35kg

0,38kg

0,27kg

0,37kg

0,33kg

0,5kg

0,5kg

0,45kg

0,75kg

0,27kg

0,30kg

0,27kg

0,5kg

30

30

30

30

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

I

I

I

I

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

3,5 watt

3,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

3 cell AA size

3 cell SC size

3 cell SC size

4 cell AA size

4 cell SC size

6 cell AA size

6 cell SC size

6 cell SC size

5 cell SC size

5 cell D size

6 cell AA size

6 cell AA size

6 cell AA size

MODEL CODE LIGHTING STYLE USAGE TYPE

LAMP DURATION WEIGHT(Batt inc.)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUPTION

OPERATINGVOLTAGEBATTERY

BATTERIES

ARSEL-88

Page 89: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

AK-2400EMERGENCY BATTERYPACK FOR LED'S

• Emergency backupunits for LED lamps• It can be used withan armature mounted inside or with an external box.• Supplied with Ni-CdBattery.

USAGE AREAS• LED lighting fixtures• Emergency lighting andguidance fittings• Waterproof type LEDlighting fixtures• Special design led lightingfixtures• Recessed type luminaires

BODY STRUCTURE• Body - Electrostaticpowder coated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Nickel-cadmium in all models

OPTIONS• Model choices accordingto lamp type and power• 1-2 hour emergencybackup times

AK-2400 model emergency backup modules;• It is connected to the supply input of the LED drivers, whichcan operate with AC voltage below 25 watts.• Maximum 5 may switch the DC LED current.• 12 volt ni-cd battery, are plug-in type terminals.• Backup output 220 volts 50 Hz 25 w maximum• It should be installed inside the armature or in the externalbox.• Provides power failure backup for LED lamps.• Battery charging indicator.• The lamp's 2 connections are switched at once.• With fully insulated supply circuit and the lamp contacts, thereis no damage due to the different phase connections.• Continuous charging method keeps the battery pack full andready.• Appropriate kit should be selected according to the lamp.• Plug-in type latching type terminals are used for easyinstallation.• The mains supply voltage is standard 220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mains voltage.• Switches to emergency lighting mode under 150 volts,charging over 185 volts• It is manufactured according to TS 8710 EN60598-2-22standard in the framework of ISO 9001-2000 quality management system.

ARSEL-89

Page 90: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

EMERGENCY BACKUP UNITS FOR LED LAMPS

AK-312-1

AK-312-2

AK-312-3

AK-4600-1

AK-4600-3

AK-7200-1

AK-7200-2

AK-7200-3

AK-609W-1

AK-609W-2

AK-4600S-1

AK-4600S-3

AK-4600S-EKO

AK-2400

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Non-Maintained

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

Internal

12 volt led lamp

12 volt led lamp

12 volt led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

3,5-200 volt led lamp

110-220 volt AC led lamp

110-220 volt AC led lamp

3,5-70 volt led lamp

3,5-70 volt led lamp

12-65 volt led lamp

220 volt <25w lamp

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 180 m.

Emergency 60 m.

Emergency 120 m.

Emergency 60 m.

Emergency 180 m.

Emergency 180 m.

-

0,28kg

0,35kg

0,38kg

0,27kg

0,37kg

0,33kg

0,5kg

0,5kg

0,45kg

0,75kg

0,27kg

0,30kg

0,27kg

0,5kg

30

30

30

30

30

30

30

30

30

30

30

30

30

30

I

I

I

I

I

I

I

I

I

I

I

I

I

I

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

-16/+40°

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

3,5 watt

3,5 watt

1,5 watt

1,5 watt

1,5 watt

1,5 watt

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

220-240

3 cell AA size

3 cell SC size

3 cell SC size

4 cell AA size

4 cell SC size

6 cell AA size

6 cell SC size

6 cell SC size

5 cell SC size

5 cell D size

6 cell AA size

6 cell AA size

6 cell AA size

MODEL CODE LIGHTING STYLE USAGE TYPE

LAMP DURATION WEIGHT(Batt inc.)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUPTION

OPERATINGVOLTAGEBATTERY

BATTERIES

ARSEL-90

Page 91: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

VS-12-LEMERGENCY BATTERY PACKS FOR LED'S

• 12 volt DC EmergencyBackup Unit• It can be used with anarmature mounted inside or with an external box.

USAGE AREAS• 12 volt halogenspots• 12 volt led spots• Led strips

BODY STRUCTURE• Body - Electrostaticpowder coated aluminum case. ABS plastic covers.

BATTERY• BATTERY - Dry TypeMaintenance-free Battery

OPTIONS• Battery Price NotIncluded• Battery selectionmust be made according to lamp power and backup duration.

VS-12 L model emergency backup modules;• For lamps operating with 12 volt DC, power is supplied atpower supply interruption.• Maximum 5 may switch the DC LED current.• 12 volt dry type maintenance-free battery, plug-in type latchingterminals.• It should be installed inside the armature or in the external box.• It does not have the standard output current, battery selectionaccording to the lamp.• 12 volt DC bulbs are backed up at power failure.• It makes a backup at power failure.• Battery charging indicator.• The lamp's 2 connections are switched at once.• With fully insulated supply circuit and the lamp contacts, thereis no damage due to the different phase connections.• Appropriate kit should be selected according to the lamp.• Plug-in type latching type terminals are used for easyinstallation.• The mains supply voltage is standard 220 volts AC 50 Hz.• Charging time for first use is 24 hours.• It can withstand fluctuations up to 285 volts at mains voltage.• Switches to emergency lighting mode under 150 volts,charging over 185 volts• It is manufactured according to TS 8710 EN60598-2-22standard in the framework of ISO 9001-2000 quality management system.

ARSEL-91

Page 92: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

DIMENSIONS

VS-12-LEMERGENCY BATTERY PACKS FOR LED'S

VS-12-L

MODEL CODE

Internal

USAGETYPE

0,35kg

WEIGHT

30 I -16/+40° 9 watt 220-2400,1,2 -12 AH/12V AKU

BATTERY

AKU OPTIONS

1,2Ah

2 Ah

4 Ah

7 Ah

12 Ah

10W

1h

2h

4h

7h

10h

20W

-

1h

2h

3h

5h

30W

-

-

1,5h

2h

3h

50W

-

-

-

1h

2h

75W

-

-

-

-

1,5h

100W

-

-

-

-

1h

0,58 kg

0,95 kg

1,75 kg

2,65 kg

4,05 kg

CAPACITY WEIGHTBACKUP CAPACITY (hour)

IPCLASS

ISOLATIONCLASS

OPERATIONTEMP

POWERCONSUMPTION

OPERATINGVOLTAGE

ARSEL-92

Page 93: EMERGENCY LIGHTING AND ORIENTATION SYSTEMS

www.arselelektronik.com.tr

+90 (212) 2107650