VENT THROUGH ROOF. CONNECTING TO OTHER VENT PIPING IS NOT I I 4" STANDPIPE OR ALLOWED.~ VENTED RECEPTOR 1 ~ VENT OPTION #1 I ~----7 I I I I I I OPTION #2 I I I ' , .... -----,...ACCESSIBLE I GATE VALVE OR I FULL-PORT I BALL VALVE I I I I IACESSIBLE 1 I I CHECK VALVE "-_ELEVATOR PIT THE SUMP, PUMP, AND DISCHARGE PIPING MUST COMPLY WITH THE REQUIREMENTS OF M.R. CHAPTER DRAIN 4714, SECTION 710. SUMP PUMP----t '-. "-----4" PIPE L______. "--- SUMP BASIN M.R. CHAPTER 4714. SECTION 418.6 AND M. R. PART 1307.0067: - AN ELEVATOR PIT DRAIN MUST DISCHARGE TO THE SANITARY SEWER USING AN INDIRECT CONNECTION THAT PRECLUDES THE POSSIBILITY OF SEWAGE BACKUP INTO THE PIT. IF A SUMP IS USED, IT MUST BE LOCATED OUTSIDE OF THE PIT WITH A DRY PAN DRAIN FLOWING TO IT. - SIZING OF PIT DRAINS AND SUMP PUMPS MUST BE AT LEAST 3,000 GALLONS PER HOUR (50 GALLONS PER MINUTE) FOR EACH ELEVATOR INTENDED FOR EMERGENCY FIRE SERVICE (SEE MINNESOTA RULES, CHAPTER 1307, AND ASME STANDARD A17.1-2010) . M.R. CHAPTER 4714. SECTION 804.1 : - PLUMBING FIXTURES OR RECEPTORS RECEIVING THE DISCHARGE OF INDIRECT WASTE PIPES MUST BE OF SUCH SHAPE AND CAPACITY AS TO PREVENT SPLASHING OR FLOODING. Elevator Pit Drain 1/18 ii DEPARTMENT OF I LABOR AND INDUSTRY Telephone: (651) 284-5063 www.dli.mn.gov/ccld/planplumbing.asp
1

Elevator Pit DrainOUTSIDE OF THE PIT WITH A DRY PAN DRAIN FLOWING TO IT. - SIZING OF PIT DRAINS AND SUMP PUMPS MUST BE AT LEAST 3,000 GALLONS PER HOUR (50 GALLONS PER MINUTE) FOR EACH

Jun 23, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Elevator Pit DrainOUTSIDE OF THE PIT WITH A DRY PAN DRAIN FLOWING TO IT. - SIZING OF PIT DRAINS AND SUMP PUMPS MUST BE AT LEAST 3,000 GALLONS PER HOUR (50 GALLONS PER MINUTE) FOR EACH

VENT THROUGH ROOF. CONNECTING TO OTHER VENT PIPING IS NOT

I I

4" STANDPIPE OR ALLOWED.~VENTED RECEPTOR 1

~ VENT OPTION #1

I

~----7 I I I I I I OPTION #2I I

I '

,....-----,...ACCESSIBLEI GATE VALVE ORI FULL-PORT

I BALL VALVE

I I I ~ I IACESSIBLE 1 I I CHECK VALVE

"-_ELEVATOR PIT

THE SUMP, PUMP, AND DISCHARGE PIPING MUST COMPLY WITH THE REQUIREMENTS OF M.R. CHAPTER DRAIN 4714, SECTION 710. SUMP

PUMP----t '-. "-----4" PIPE L______. "--- SUMP BASIN

M.R. CHAPTER 4714. SECTION 418.6 AND M.R. PART 1307.0067: - AN ELEVATOR PIT DRAIN MUST DISCHARGE TO THE SANITARY SEWER USING AN INDIRECT CONNECTION THAT

PRECLUDES THE POSSIBILITY OF SEWAGE BACKUP INTO THE PIT. IF A SUMP IS USED, IT MUST BE LOCATED OUTSIDE OF THE PIT WITH A DRY PAN DRAIN FLOWING TO IT.

- SIZING OF PIT DRAINS AND SUMP PUMPS MUST BE AT LEAST 3,000 GALLONS PER HOUR (50 GALLONS PER MINUTE) FOR EACH ELEVATOR INTENDED FOR EMERGENCY FIRE SERVICE (SEE MINNESOTA RULES, CHAPTER 1307, AND ASME STANDARD A17.1-2010) .

M.R. CHAPTER 4714. SECTION 804.1 : - PLUMBING FIXTURES OR RECEPTORS RECEIVING THE DISCHARGE OF INDIRECT WASTE PIPES MUST

BE OF SUCH SHAPE AND CAPACITY AS TO PREVENT SPLASHING OR FLOODING.

Elevator Pit Drain 1/18ii DEPARTMENT OF I LABOR AND INDUSTRY

Telephone: (651) 284-5063 www.dli.mn.gov/ccld/planplumbing.asp