8/8/2019 Ele_Pro_Sys
1/167
PAGE 1
CHAPTER-1
BASIC ASPECTS OF PROTECTION
1.0 Principles of RelaysEvery electrical equipment is designed to work under specified normal
conditions. In case of short circuits, earth faults etc., an excessive current will
flow through the windings of the connected equipment and cause abnormal
temperature rise, which will damage the winding. In a power station, non-
availability of an auxiliary, at times, may cause total shut down of the unit,
which will result in heavy loss of revenue.
So, in modern power system, to minimise damage to equipment two alternatives
are open to the designer, one is to design the system so that the faults cannot
occur and other is to accept the possibility of faults and take steps to guard
against the effect of these faults. Although it is possible to eliminate faults to a
larger degree, by careful system design, careful insulation coordination, efficient
operation and maintenance, it is obviously not possible to ensure cent percent
reliability and therefore possibility of faults must be accepted; and the equipment
are to be protected against the faults. To protect the equipment, it is necessary to
detect the fault condition, so that the equipment can be isolated from the fault
without any damage. This function is performed by a relay. In other words,
protective relays are devices that detect abnormal, conditions in electrical
circuits by constantly measuring the electrical quantities, which are different
under normal and faulty conditions. The basic quantities which may change
during faulty conditions are voltage, current, frequency, phase angle etc. Having
detected the fault relay operates to complete the trip circuit which results in the
opening of the circuit breaker thereby isolating the equipment from the fault.
The basic relay circuit can be seen inMg. No. 1. 1
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
2/167
8/8/2019 Ele_Pro_Sys
3/167
8/8/2019 Ele_Pro_Sys
4/167
Resetting Value : It is the value of the characteristic, quantity at which the relay returns
to its initial position.
Unrestricted Protection : It is a protection system which has no clearly defined zone of
operation and which achieves selective operation only by time grading.Basic Symbols: The equipments they represent are as given below:
Sr. No. Symbol Equipment Function
1 Circuit Breaker Switching during normal and abnormal conditions,interrupt the fault currents.
2 Isolator Disconnecting a part of the system from live partsunder no load conditions.
3 Earth switch Discharging the voltage on the lines to the earthafter disconnection.
4 LightingArrestor
Diverting the high voltage surges to earth.
5 CurrentTransformer Stepping down the current for measurement,protection, and control.
6 VoltageTransformer
Stopping down the voltage for the purpose ofprotection, measurement and control.
1.2 Functions of protective Relaying
To sound an alarm, so that the operator may take some corrective action and/or
to close the trip circuit of circuit breaker so as to disconnect a component during
an abnormal fault condition such as overload, under voltage, temperature rise
etc.
PAGE 5
To disconnect the faulty parts as quickly as possible so as to minimize the
damage to the faulty part. Ex: If a generator is disconnected immediately after a
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
5/167
winding fault only a few coils need replacement. If the fault is sustained, it may
be beyond repairable condition.
To localise the effect of fault by disconnecting the faulty part from the healthy
part, causing least disturbance to the healthy system. To disconnect the faulty part as quickly as possible to improve the system
stability and service continuity.
1.3 The requirements of protective relaying
* Speed: Protective relaying should disconnect a faulty element as quickly as
possible, in order to improve power system stability, decrease the amount of
damage and to increase the possibility of development of one type of fault
into other type. Modern high speed protective relaying has an operating
time of about 1 cycle.
* Selectivity : It is the ability of the protective system to determine the point
at which the fault occurred and select the nearest of the circuit breakers,
tripping of which leads to clearing of fault with minimum or no damage to
the system.
* Sensitivity : It is capability of the relaying to operate reliably under the
actual minimum fault condition. It is desirable to have the protection as
sensitive as possible in order that it shall operate for low value of actuating
quantity.
* Reliability : Protective relaying should function correctly at all times under
any kind of fault and abnormal conditions of the power system for which it
has been designed. It should also not operate on healthy conditions of
system.
* Simplicity : The relay should be as simple in construction as possible. As a
rule, the simple the protective scheme, less the
PAGE 6
number of relays, and contacts it contains, the greater will be the reliability.
* Economy : Cost of the protective system will increase directly with the
degree
of protection required. Depending on the situation a designer should strike
a
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
6/167
balance between with the degree of protection required and economy.
1.4 Classification of Relays
1.4.1 Depending upontheir principle ofoperation theyare classifted as:
Electromagnetic attraction type relays: These relays operate by the virtue of aplunger being drawn into a solenoid or an armature being attracted towards the
poles of an electromagnet.
Induction type Relays: In this type of relay, a metal disc or cup is allowed to
rotate or move between two electro-magnets. The fields produced by the two
magnets are displaced in space and phase. The torque is developed by
interaction of the flux of one of the magnets and the eddy current induced into
the disc/cup by the other.
Thermal Relays : They operate due to the action of heat generated by the
passage of current through the relay element. The strip consists of two metals
having different coefficients of expansions and firmly fixed together throughout
the length so that different rates of thermal expansion of two layers of metal
cause the strip to bend when current is passed through it.
Static Relays : It employs discrete electronic components like diodes,
transistors, zenners, resistors/capacitors or Integrated circuits and use electronic
measuring circuits like level detectors, comparators, integrators etc. to obtain
the required operating characteristics.
Moving Coil Relays : In this relay a coil is free to rotate in magnetic field of a
permanent magnet. The actuating current flows through the
PAGE 7
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
7/167
PAGE 8
coil. The torque is produced by the interaction between the field of the
permanent magnet and the field of the coil.
1.4.2 Relays canbe classified depending upon their application also.
Over voltage, over current and over power relays, in which operation takes place
when the voltage, current or power rises above a specified value.
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
8/167
Under voltage, under current under frequencies low power relays, in which
operation takes place when the voltage, current frequency or power fall below a
specified value.
Directional or reverse power relays: In which operation occurs when thedirection of the applied power changes.
Distance Relays : In this type, the relay operates when the ratio of the voltage
and current change beyond a specified limit.
Differential Relays : Operation takes place at some specific phase or magnitude
difference between two or more electrical quantities.
1.4.3 Relays can also be classifiedaccording totheir time ofoperation.
Instantaneous Relay : In which operation takes place after negligibly small
interval of time from the incidence of the current or other quantity causing
operation.
Derinite time lag Relay: This operates after a set time lag, during which the
threshold quantity of the parameter is maintained.
Inverse time lag Relay: This operates after a set time Lab, during which the
operating quantity of the parameter is maintained above its operating threshold.
1.5 Operating Principles of different types of Relays
1. 5. 1 Induction over current and earth fault relays
These are quite commonly used relays. Schematic diagram of induction disc
type relay is shown inMg. No. 1.2.
The output of the current transformer is fed to a winding (1) on the centre limb
of the E-shaped core, the second winding (2) on the limb
PAGE 9
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
9/167
PAGE 10
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
10/167
is connected to two windings on the poles of the E and U shaped cores. The
magnetic flux across the air gap induce currents in the disc, which in conjunction
with the flux produced by the lower magnet, produces'a rotational torque. A
magnet (3), is used to control the speed of the disc. The time of operation of therelay v aries inversely with the current fed into it by the current transformer of
the protected circuit. The permanent magnet used for breaking has a tendency to
attract iron filings, which can prevent operation. So care has to be taken while
manufacturing this type of relays. Time-current characteristics induction type
relays has been given in Fig. 1.3.
1.5. 2 Balanced Beam Relays
It,consists of a horizontal beam pivoted centrally, with one armature attached to
either side. There are two coils one on each side. The current in one coil gives
operating torque. The beam is given a slight mechanical bias by means of a
spring so that under normal conditions trip contacts will not make and the beam
remains in horizontal position. When the operating torque increases then the
beam tilts and closes the trip contacts. In current balance system both coils are
energised by current derived from CT's. In impedance relays, one coil is
energised by current and other by voltage. In these relays the force is
proportional to the square of the current, so it is very difficult to design the relay.
This type of relay is fast and instantaneous. In modern relays electromagnets are
used in place of coils (See Mg.. 1.4.).
1.5.3 Permanent - MagnetMoving - Coil Relgys:
There are two general types of moving coil relays. One type is similar to that of
a moving coil indicating instrument, employing a coil rotating.between the poles
of a permanent magnet. The other is, employing a coil moving at right angles to
the plane of the poles of a permanent magnet. Only direct current measurement
is possible with both the types.
PAGE 11
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
11/167
PAGE 12
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
12/167
The action of a rotating coil type is shown in the Fig. 1.5. A light rectangular coil
is pivoted so that its sides lie in the gap between the two poles of a permanent
magnet and a soft iron core. The passage of current through the coil produces a
deflecting torque by the reaction between the permanent magnetic field and thefield of the coil
(See Fig. 1. 5)
The moving contact is carried on an arm which is attached to the moving coil
assembly. A phosper bronze spiral spring provides the resetting torque.
Increasing the contact gap and thus increasing the tension of the spring permits
variation in the quantity required to close the contacts.
Time current characteristic of a typical moving coil permanent magnetic relays is
shown in Fig. 1. 6.
1.5. 4 Attracted armaturerelays :
It is required to clear the faults in power system as early as possible. Hence, high-
speed relay operation is essential. Attracted armature relays have a coil or an
electromagnet energised by a coil. The,coil is energised by the operating quantity
which may be proportional to circuit current or voltage. A plunger or a rotating
vane is subjected to the action of magnetic field produced by the operating
quantity. It is basically single actuating quantity relay.
Attracted armature relays respond to both AC and DC quantities. They are very
fast in operation. Their operating time will not vary much with the amount of
current. Operating time of the relay is as low as 10-15 m seconds and resetting
time is as low as 30 m sec can be obtained in these relays. These relays are non-
directional and are simple type of relays. Examples of attracted armature type
relays are given in Fig.1.7
1.5.5 Time Lag Relays:
These are commonly used in protection schemes as a means of time
discrimination. They are also frequently used in control, delayed
PAGE 13
auto-reclosing and alarm scheme to allow time for the required sequence of
operations to take place, and to measure the duration of the initial condition to
ensure that it is not merely transient.
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
13/167
Various methods are used to obtain a time lag between the initiation of the relay
and the operation of its contact mechanism. These includes gearing, permanent
magnet damping, friction, thermal means or R.C. circuits. In some cases the time
lag in operation of the contacts is achieved by a separate mechanism released by avoltage operated elements. The release mechanism may be an attracted armature
or solenoid and plunger. The operating time of such relay is independent of the
voltage applied to the relay coil. One of the simplest forms of time lag relay is
provided by a 'Mercury switch in which the flow of mercury is impeded by a
constriction in the mercury bulb. The switch is tilted by a simple attracted
armature mechan,iwn. The time setting of such a relay is fixed by the design of
the tube. Another method of obtaining short time delays is to delay operation of a
normally instantaneous relay by means of a device which delays the build up or
decay of the flux in the operating magnet. The device consists of a copper ring
(slug) around the magnet and can produce delay on pickup as well as delay on
reset.
1.6 Testing and Maintenance of Protective Relays :
Unlike other equipment, the protective relays remain without any operation until a
fault develops. However, for a reliable service and to ensure that the relay is
always vigilant, proper maintenance is a must. Lack of proper maintenance may
lead to failure to operate.
It is possible for dirt and dust created by operating conditions in the plant to get
accumulated around the moving parts of the relay and prevent it from operating.
To avoid this, relays are to be cleaned periodically.
In general, overload relays sense over load by means of thermal element. Loose
electrical connections can cause extra heat and may
PAGE 14
result in false operation of the relay. To avoid this, all the relay connections are to
be tightened every now and then.
To confirm that the relay operation at the particular setting under particular
conditions for which the relay is meant for operating, we should perform number
of tests on the relays. Quality control is given foremost consideration in
manufacturing of relay. Tests can be grouped into following five classes:
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
14/167
8/8/2019 Ele_Pro_Sys
15/167
* Measuring insulation resistance of circuits.
* Checking C.T. Ratios
* Checking P.T. ratio, polarity and phasing
* Conducting secondary injection test on relays.* Conducting primary injection test
* Checking tripping and alarm circuits.
* Stability check for balanced protections like differential/REF.
1.6.3Maintenance Tests
Maintenance tests are done in field periodically. The performance of a relay is
ensured by better maintenance. Basic requirements of sensitivity, selectivity,
reliability and stability can be satisfied only if the maintenance is proper.
The relay does not deteriorate by. normal use; but other adverse conditions cause
the deterioration. Continuous vibrations can damage the pivots or bearings.
Insulation strength is reduced because of absorption of moisture; polluted
atmosphere affects the relay contacts, rotating systems etc., Relays room,
therefore, be maintained dust proof. Insects may cause mal-operation of the
relay. Relay maintenance generally consists of
a) Inspection of contacts
b) Foreign matter removal
c) Checking adjustments
PAGE 16
d) Checking of breaker operations by manual contact closing of relays.
e) Cleaning of covers etc.
1.6.4 Maintenance Schedule:
1. Continuous Supervision: Trip circuit supervision, pilot supervision, relay,
auxiliary voltage supervision, Battery supervision, CT circuit supervision.
2. Relay flags are to be checked and resetted in every shift.
3. Carrier current protection testing is to be carried out once in a week.
4. Six monthly inspections : Tripping tests, insulation resistance tests, etc.
Secondary injection tests are to be carried out at least once in a year.
The following tests are to be performed during routine maintenance:
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
16/167
Inspection : Before the relay cover is removed, a visual check of the cover is
necessary. Excessive dust, dirt, metallic material deposited on the cover should
be removed. Removing such material will prevent it from entering the relay
when the cover is removed. Fogging of the cover glass should be noted andremoved when the cover has been removed. Such fogging is due to volatile
material being driven out of coils and insulating materials. However, if the
fogging is excessive, cause is to be investigated. Since most of the relays are
designed to operate at 400C, a check of the ambient temperature is advisable.
The voltage and current carried by the relay are to be checked with that of the
name plate details.
1.6. 5 Mechanical, adjustments and Inspection:
The relay connections are to be tight, otherwise it may. cause overheating at the
connections. It will cause relay vibrations also. All gaskets should be free from
foreign matter. If any foreign matter is found gaskets are to'be checked and
replaced if required.,
Contact gaps and pressure are to be measured and compared with the previous
readings. Large variation in these measurements will
PAGE 17
indicate excessive wear, in which case worn contacts are to be replaced.
Contacts alignment is to be checked for proper operation.
1.6.6 Electrical Tests and Adjustments
Contact function : Manually close or open the contacts and observe that they
perform their required function.
Pick up: Gradually apply actuating quantity (current or voltage) to see that
pickup is within limits.
Drop out or reset: Reduce the actuating quantity (current or voltage) until the
relay drops out or fully resets. This test will indicate excess friction.
Repair tests involve recalibration, and are performed after major repairs.
Manufacturers tests include development tests, type and routine tests.
1.7 Test Equipment
1.7. 1 Primary current injection test sets:
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
17/167
Generally protective gear is fed from a current transformer on the equipments to
be protected and primary current injection testing checks all parts of the
protection system by injecting the test current through the primary circuit. The
primary injection tests can be carried out by means of primary injection test sets.The sets are comprising current supply unit, control unit and other accessories.
The test set can give variable output current. The output current can be varied
by means of built-in auto transformer. The primary injection test set is
connected to AC single phase supply. The output is connected to primary circuit
of CT. The primary current of CT can be varied by means of the test set. By
using this test one can find at what value of current the relay is picking up and
dropping out.
1.7.2 Secondary current injectiontest set:
It checks the operation of the protective gear but does not check the overall
system including the current transformer. Since it is a rare
PAGE 18
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
18/167
PAGE 19occasion for a fault to occur in CT, the secondary test is sufficient for most
routine maintenance. The primary test is essential when commissioning a new
installation, as it checks the entire system. A simple test circuit is given inMg.
1. 8.
1.7.3 Test Benches
Test benches comprise calibrated variable current and voltage supplies and timing
devices. These benches can be conveniently used for testing relays and obtaining
their characteristics.
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
19/167
1.8 Static Relaying Concepts
1.8. 1 Introduction
Static Relay is a relay in which the comparison or measurement of electrical
quantities is done by stationary network which gives a tripping signal when thethreshold value is crossed. In simple language static relay is one in which there
are no moving parts except in the output device. The static relay includes
electronic devices, the output circuits of which may be electric, semiconductor or
even electromagnetic. But the output device does not perform relay
measurement, it is essentially a tripping device. Static relay employs electronic
circuits for the purpose of relaying. The entity voltage, current etc. is rectified
and measured. When the output device is triggered, the current flows in the trip
circuit of the circuit breaker.
With the inventions of semiconductors devices like diodes, transistors, thyristors,
zener diodes etc., there has been a tremendous leap in the field of static relays.
The development of integrated circuits has made an impact in static relays. The
static relays and static protection has grown into a special branch.
1.8.2 Advantages of Static Relays:
The static relays compared to the electromagnetic relays have many advantages
bind a few limitations.
PAGE 20
1.8. 3 Low Power Consumption
Static relays provide less burden on CTs and PTs as compared to conventional
relays. In other words, the power consumption in the measuring circuits of static
relays is generally much lower than that for the electromechanical versions. The
consumption of one milli-VA is quite common in static over current relay
whereas as equivalent electromechanical relay can have consumption of about 2-
3 VA. Reduced consumption has the following merits.
a) CTs and PTs of less ratings are sufficient
b) The accuracy of CTs and F'Ts are increased
c) Air gaped CTs can be used
d) Problems arising out of CT saturation are avoided
e) Overall reduction in cost.
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
20/167
1.8.4 Operating time
The static relays do not have moving parts in their measuring circuits, hence
relay times of low values can be achieved. Such low relay times are impossible
with conventional electromagnetic relays.By using special circuits the resetting, times and the overshoot time can be
improved and also high value of drop off to pick up ratio can also be achieved.
1.8.5 Compact
Static relays are compact. The use of integrated circuit have further reduced
their size. Complex protection schemes may be obtained by using logic circuits
or matrix. Static relays can be designed with good repeat accuracies. Number of
characteristics can be obtained in a single execution, unlike in case of their
Electro-mechanical counter parts.
Most of the components in static relays including the auxiliary relays in the
output stage are relatively immune to vibrations and shocks. The risk of
unwanted tripping is therefore less with static relays as
PAGE 21
compared to electromagnetic relays. So, these can be applied in earthquake prone
areas, ships, vehicles, aeroplanes etc.
1.8. 6 Transducers
Several non-electrical quantities can be converted into electrical quantities and
then fed to static relays. Amplifiers are used wherever necessary.
1.8.7 Limitations
Auxiliary voltage requirement : This disadvantage is not of any importance as
auxiliary voltage can be obtained from station battery supply and conveniently
stepped down to suit load requirements.
Static relays are sensitive to voltage spikes or voltage transients. Special
measures are taken to overcome this difficulty. These include use of surge
supressors and filter circuits in relays, use of screened cables in input circuits,
use of galvanically isolated auxiliary power supplies like d.c./d.c. convertors, use
of isolating transformers with grounded screens for C.T./P.T. input circuits etc.
1.8.8 Temperature Dependence of Static Relays
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
21/167
The characteristic of semiconductors are influenced by ambient temperatures.
For example, the amplification factor of a transistor, the forward voltage drop of
a diode etc., changes with. Temperature variation. This was a serious limitation
of static relays in the beginning. Accurate measurement of relay should not beaffected by temperature variation. Relay should be accurate over a wide range
of temperature. (-200C to +50
OC) this difficulty is overcome by
a) Individual components in circuits are used in such a way that change in
characteristic of component does not affect the characteristic of the
complete relay.
b) Temperature compensation is provided by thermistor circuits.
Extra precaution for quality control of the components has to be taken. As the
failure rate is highest in early period of components life, artificial ageing of the
components is normally done by heat soaking.
PAGE 22
PAGE 23
1.8. 9 Level Detectors
A relay operates when the measured quantity changes, either from its normal
value or in relation to another quantity. The operating quantity in most
protective relays is the current entering the protected circuit. The relay may
operate on current level against a standard bias or restrain, or it may compare the
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
22/167
current with another quantity of the circuit such as the bus voltage or the current
leaving the protected circuit (Fig. 1. 9).
In a simple electromagnetic relay-used as level detector, gravity or a spring can
provide the fixed bias or reference quantity, opposing the force produced by theoperating current in electromagnet. In static relays the equivalent is a D.C.
voltage bias.
E.g. In the semiconductor circuit (See Fig.1.10) the transistor is reverse biased in
normal conditions. No current flows through the relay coil. Under fault
conditions capacitor will be charged to +ve potential at the base side. If this
potential exceeds that of the emitter,, the B-E junction will be forward biased
and transistor will conduct there by tripping the relay. Thus the comparison is
made against the D.C. fixed bias.
1.8.10 Comparators
In order to detect a fault or abnormal conditions of the power system, electrical
quantities or a group of electric quantities are compared in magnitude or phase
angle and the relay operates in response to an abnormal relation of these
quantities. The quantities to be compared are fed into a comparators as two or
more inputs; in complex relays each input is the vectorial sum or difference of
two currents or voltages of the protected circuit, which may be shifted in phase -
or, changed in magnitude before being compared.
1.8.11 Types of comparators :
Basically there are two types of comparators, viz.
PAGE 24
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
23/167
PAGE 25
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
24/167
8/8/2019 Ele_Pro_Sys
25/167
PAGE 26
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
26/167
PAGE 27
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
27/167
8/8/2019 Ele_Pro_Sys
28/167
8/8/2019 Ele_Pro_Sys
29/167
PAGE 29
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
30/167
a) Those whose output is a D.C. voltage proportional to the vector product
of the two A.C. input quantities;
b) Those which give an output whose polarity depends upon the phase
relation of the inputs. The later are sometimes called coincidence type and canbe direct acting or integrating.
1.8.13 Operating Principles of Static Time Current Relays:
Fig. 1. 1 7 shows the block diagram of a static time current relay. The auxiliary
C.T. has taps on the primary for selecting the desire pickup and current range.
Its rectified output is supplied to, a fault detector and an RC timing circuit.
When the voltage of the timing capacitor has reached the value for triggering the
level detector, tripping occurs.
Operation ofa typical static time current relay : The current from the main 0,.T.
is first rectified and smoothed by the capacitor 'Cs' and then passed through the
tapped resistor 'Rs' so that the voltage across it is proportional to the secondary
current. The spike filter RC protects the rectifier bridge against transient over
voltages in the incoming current signal, Fig. 1. 18.
1.8.14 Timing Circuit
The rectified voltage across the 'Rs' charges the capacitor 'Ct' through resistor
'Rt'. When the capacitor voltage exceeds the base emitter voltage 'Vt' the
transistor 'T2' in the Fig. 1,20 becomes conductive, triggering transistor 'T3' and
operating the tripping relay.
Resetting circuit : In order that the relay sha.11 have an instantaneous reset, the
capacitor 'Ct' must be discharged as quickly as possible. This is achieved by the
detector as follows (Fig. 1. 1 9).
The base of the transistor 'Tl' is normally kept sufficiently positive relative to
emitter to keep it conductive and hence short circuiting the timing capacitor 'Ct'
at YY in Fig. 1.20. When a fault occurs the over current through the resistor 'Rs'
makes the base of 'Tl' negative and cuts it off leaving 'Ct' free to be charged.
When the fault is cleared the
PAGE 30
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
31/167
PAGE 31
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
32/167
current falls to zero and the negative bias on 'Tl' disappears so that 'Ct'is again
short circuited and discharged immediately.
A weakness of very fast instantaneous units is the tendency to over sensitivity on
off-set current waves. The instantaneous unit can be made insensitive to theD.C. off set component by making the auxiliary C.T. saturate just above the
pickup current value and connecting the capacitor and a resistor across the
rectified input to the level detector. This prevents tripping until both halves of
the current wave are above pickup valve. That is, until the off set has gone, the
short delay thus entailed is acceptable with time current relaying.
PAGE 32
CHAPTER-2
INDUCTION DISC TYPE IDMT
OVER CURRENT RELAYS
2.1 Introduction
Induction types relays are most widely used for protective relaying purposes
involving A.C. quantities. Torque is produced in these relays when alternating
flux reacts with eddy currents induced in a disc by another alternating flux of the
same frequency but displaced in time and space. These relays are used as over
current or earth fault relay. In its simplest form, such a relay consists of a
metallic disc which is free to rotate between the poles of two electromagnets
(Fig. 2. 1).
The spindle of this disc carries a moving contact which bridges two fixed
contacts when the disc rotates through an angle which is adjustable. By
adjusting this angle the travel of the moving contact can be adjusted so that the
relay can be given any desired time setting which is indicated by a pointer on a
time setting dial. The dial is calibrated from 0 to 1. These figures do not
represent the actual .operating times but are multipliers to be used to convert the
time known from the relay name plate curve into the actual operating time.
The upper electromagnet has a primary and a secondary winding. The primary
is connected to the secondary of a C.T. in the line to be protected and is provided
with tappings. These tappings are connected to a plug setting bridge which isusually arranged to giv@, seven selections of tapping, the over current range
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
33/167
8/8/2019 Ele_Pro_Sys
34/167
PAGE 34
desired tapping and, therefore, current setting can be selected by inserting a pin
between the spring loaded jaws of the bridge type socket at the appropriate tap
value. When the pin is withdrawn for the purpose of changing the setting while
the relay is in service, the relay automatically adopts a high setting, thus ensuring
that the C.T. secondary is not open circuited and that the relay remains operative
for faults during the process of changing the settings. The secondary winding
surrounds the limbs of the lower electromagnet as well. The torque exerted on
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
35/167
the disc is due to the interaction, of eddy currents produced therein by means of
the leakage flux from the upper electromagnet and the flux from the lower
electromagnet: these two fluxes having a phase displacement between them.
2.2 Characteristic CurveA set of typical time current characteristic curves of this type of relay is shown
in Fig. 2.2. The curve shows the relation between the operating current in terms
of current setting multiplier along the x-axis and operating time in seconds along
the y-axis. A current setting multiplier indicates the number of times the relay
cut-rent is in excess of the current setting. The current setting multiplier is also
referred to as plug setting multiplier (P. S. M.). Thus
P.S.M. = Primary CurrentPrimary Setting Current
= Primary Current
Relay Current Setting XC.T.Ratio
where, as is usually the case, the rated current of the relay is equal to the rated
secondary current of C.T. From the figure the operating time, when current
setting multiplier is 10 and the time multiplier is sea at 1, is 3 seconds. This is
sometimes called the basic 3/ 10 curve.
It is evident that at the same current setting but the time multiplier set at 0.8, the
time of operation is 2.4 seconds. Thus to get the actual time of operation a ainst
any particular time multiplier setting, 9
multiply the time of operation of the basic curve by the multiplier
PAGE 35
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
36/167
PAGE 36
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
37/167
setting. Thus in this example the time of operation is 3 x 0.8 2.4 secs.
The time current characteristics ofFYg. 2.2 are the inverse definite minimum
time (I.D.M.T.) type since the time of operation is approximately inversely
proportional to smaller values of current and tends to a definite minimum time asthe current increases above 10 times the setting current.
The D.M.T. characteristic is obtained by saturating the iron in the upper magnet
so that there is practically no increase in flux after current has reached a certain
value. This results in the flattening out of the current time curve.
Example : An I.D.M.T. over current relay has a current setting of 150% and has
a time multiplier setting of 0.5. The relay is connected in the circuit through a
C.T. having ratio 500:5 amps. Calculate the time of operation of the relay if the
circuit carries a fault current of 6000 A. The relay characteristic is shown is Fig.
2.3.
Solution: Sec fault current 6000 X 5 60A
500
Plug Setting multiplier (P. S. M.) = Actual Current in Relay = 60 = 8
Setting Current 5 x 1.5
Time from graph against this multiplier of 8 = 3 15 sec.
Operating time = 3. 1 5 x 0. 5 = 1. 575 sec.
PAGE 37
CHAPTER - 3
MOTOR PROTECTION
Electrical Motor is an important component of an industry. Squirrel cage
induction motor is most widely used in power stations and industries. To protectthe motor from different faults condition various protection are provided, which
are as listed below.
3.1 Overload Protection
A motor may get overloaded during its operation because of excessive
mechanical load; (b) Single phase; (c) Bearing fault. An overloaded' motor
draws overcurrent resulting in overheating of the winding insulation. A
reasonable degree of overload protection can be provided by Bi-metallic thermal
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
38/167
8/8/2019 Ele_Pro_Sys
39/167
8/8/2019 Ele_Pro_Sys
40/167
starting of all motors together, when the supply is subsequently restored. Thus,
prevents stressing of the supply source.
Composite Motors Protection Relays (Conventional analog types) provide
following protection functions.a) Thermal overload (Alarm/Trip) - ITH
b) Short circuit (Isc)
c) Single Phasing (I2)
d) Earth Fault (I0)
e) Stalling (lIt)
Numerical versions are now available which offer following additional
protection functions, besides those given above.
f) Prolonged starting time
g) Too many start
h) Loss of load
The Numerical versions have data acquisition capabilities and provide useful
service Data (such as load currents, I2/I. content in load current, thermal status
etc.), historic data fault data on operation. These relays have programmable
settings, programmable output relays and continuous self monitoring against any
internal failures.
PAGE 40
CHAPTER - 4
TRANSFORMER PROTECTIONS
4.1 Transformer protections are provided
a) against effects of faults in the system to which the transformer isconnected.
b) against effects of faults arising in the transformer itself.
4.1.2 Protections against faultsin the System
a) Short Circuits
b) High Voltage, high frequency disturbance
c) Flure Earth Faults.
4.1.3 System Short Circuits
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
41/167
A short circuit may occur across any two phases (phase to phase) or between any
one line and earth neutral (phase to earth). The effect is excessive over current
and electromagnetic stresses proportional to square of short circuit current. For
these type of faults additional reactance and additional bracing of the transformerwinding and end leads is resorted to. This reactance may be incorporated in the
design itself or separate series reactance with primary of transformer is provided.
4.1.4 High Voltage High frequency surges:
These surges may be due to arching grounds, switching operation surges or
atmospheric disturbances. These surges have very high amplitudes, steep wave
front currents and high frequencies. Because of this, the breakdowns of the
transformer turns adjacent to line terminals occurs causing short circuit between
the turns.
To take care of this, the transformer winding is to be designed to withstand the
impulse surge voltages as specified below and then protect it by surge divertors.
PAGE 41
System Voltage KV(RMS) Impulse voltage withstand level(Peak value)
7.2 KV 60 MV
12.5 KV 75 KV
33 KV 170 KV
66 KV 250 KV
145 KV 550 KV
245 KV 900 KV
400 KV 1350 KV
Surge divertors are provided from each line to earth. These consist of several spark
gaps in series with a non-linear resistance. This spark gap breakdown when surge
reaches the divertor and disturbance is discharged to earth through nonlinear resistance
since at high voltage divertors resistance is low. These surge divertors should have
rapid response, non-linear characteristics, high thermal capacity, high system flow
current interrupting capacity and consistent characteristics under all conditions.
4.1.5 System Earth Faults
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
42/167
a) When neutral of the system is earthed :-It represents short circuit across the
phase. Hence, same protection as for short circuit can be provided.
b) When neutral is not earthed transformer is used. :-Surge divertor gears in
front of transformer is used.4.2 Protection against Internal Faults
a) Electrical faults which cause serious immediate damage but are detectable
by unbalance of current or voltage.
i) Phase to Earth Fault or phase to phase faults on HV and LV external
terminals.
ii) Phase to earth faults or phase to phase faults on HV & LV winding.
iii) Short circuit between turns on HV & LV winding (inter turn faults)
iv) Earth faults on tertiary winding or short circuit between turn of tertiary
winding.
v) Problem in tap changer gear.
PAGE 42
b) Incipient faults : These are initially minor but subsequently develops
itself resulting into damage to the transformer. These may be due. to -
i) Poor electrical connection of conductors due to breakdown of insulation of
laminations, core bolt faults, clampings, rings etc.
ii) Coolant failure
iii) Blocked oil flow causing local hot spot on winding.
iv) Continuous uneven load sharing between transformers in parallel causing
overheating due to circulating current.
4.3 Principles of Protection System Principles used are -
i) Overheating
ii) Over current
iii) Un-restricted earth faults
iv) Restricted earth-faults
v) Percentage bias differential protection
vi) Gas detection due to incipient faults
vii) Over fluxing
viii) Tank earth current detection
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
43/167
ix) Over voltage
x) Tap changer problems.
4.4 Gas Detection
a) Buchholz relay protectionb) Pressure relief valves/switches (for heavy internal faults)
4.4.1 Buchholz Protection
This is for two types of faults inside the transformer.
a) for incipient faults because of -
i) bolt insulation failure
ii) short circuit in laminations
iii) local over heating because of clogging of oil
iv) Excess ingress of air in oil system
PAGE 43
v) loss of oil due to heavy leakage
vi) Uneven load sharing between two transformers in parallel causing
overheating due to circulating current.
These generate gases causing operation of upper float and energises the alarm
circuits.
b) For serious faults inside the transformer due to -
i) short circuit between phases
ii) winding earth faults
iii) puncture on bushing
iv) tap changer problems
These types of faults are of serious nature and operate both the floats provided in
the buchholz relay and trip out the transformer.
4.4.2 Principles ofBuchholz Relay Operation (Fig. 4. 1)
This relay is provided in the connecting pipe from transformer tank to
conservator. Two floats are provided inside the relay and are connected to
mercury switches. Normally the relay is full of oil and in case of gas collection
the floats due to their buyopancy, rotate on their supports until they engage their
respective stops. Initially fault develops slowly an heat is produced locally
which begins to decompose solid or liquid insulating material and thus produce
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
44/167
inflammable gases. Gas bubbles are collected in relay causing oil level to lower
down. The upper float rotates as the oil level in the relay goes down and when
sufficient oil is displaced the mercury switch contacts close and initiates alarm.
For serious faults as described above, gas generation is more violent and the oildisplaced by gas bubbles flows through connecting pipe to conservator. This
abnormal flow of oil causes deflection of both float and trip out the transformer.
Recently the dissolved gas analysis technique (gas chromatography) is in use for
pre-detection of type of slowly develo ing faults inside the transformer which
helps to decide whether the transformer maintenance/internal inspection is
required to be
PAGE 44
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
45/167
PAGE 45
carried out or otherwise, and thus helps to predict transformer damage in future.
4.4.3 Dissolved Gas Analysis
The inflammable gases dissolved in the transformer oil are mainly hydrocarbongases (methane CH4, Ethane C2H6, Ethylene C2H4, Acetylene C2H2, Propane,
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
46/167
hydrogen, carbon monoxide and carbon dioxide). With the help of dissolved gas
analysis equipment the concentration of these gases in PPM can be known and
can be cross checked with the IS standard. Also with the help of Roger's ratio
method, the type of probable incipient fault can be judged and corrective actioncan be taken in advance to prevent failure of the transformer (Ref. Annex. 1 &,
H).
4.5 Over Heating Protection
Protection is mainly required for continuous over load of the transformer.
a) Protection is based on measurement of winding temperature which is
measured by thermal image technique.
b) Thermal sensing element is placed in small pocket located near the top
transformer tank in the hot oil. A small heater fed from a current
transformer (winding temp. C.T.) in the lower voltage terminal of one
phase, is also located in this pocket and produces a local temp. rise,
similar to that of main winding and proportional to copper losses, above
general temp. of oil.
c) Winding temperature high alarm/trip is provided through mercury
switches in the winding temp. indicators.
d) By thermometers, mercury switches heat sensing silicon resistance are
also used for sensing the temp. rise.
e) Thermisters are provided mainly in the dry type transformers for
temperature sensing.
Temperature of 550 above ambient of 500C is generally provided for tripping.
PAGE 46
4.6 Over Current & Earth leakage protection
4.6.1 EarthLeakage Protection
In case of transformer earthed through resistance or earthed through impedance.
Resistance Grounding : The earth fault current in faulty winding in resistance
grounded transformer depends on voltage between neutral and fault point and is
inversely proportional to neutral resistance.
10kv x P
ly = 3. Rn
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
47/167
Where ly is earth fault current; P = percentage of winding to be protected; KV -
line to line voltage and Rn = Neutral Grounding resistance. Suitable earth fault
relay can be provided across C.T. in the neutral of the transformer depending
upon the minimum earth fault current to be detected.Impedance Grounding Transformer neutral is connected to the primary of
neutral grounding transformer. The suitable resistance is connected in parallel
with the secondary of this neutral grounding transformer. The earth fault relay
(neutral displacement relay) is connected across this resistance. The earth fault
relay can be set at about 2.5 percent of maximum neutral voltage The relay is
time delayed for transient free operation.
4.6.2 Overcurrent protection
i) HRC fuses are provided for small distribution transformer.
ii) Over current relays are used for power transformers, considering
the following:
a) IDMT relays should be chosen
b) Discrimination with circui t protection of secondary side should be
provided;
c) instantaneous trip f@cility for high speed clearance of terminals short
circuit should be provided.
PAGE 47
d) Setting depends on transformer reactance or percentage impedance,
faults MVA, type of relay used.
e) Setting of over current relays can be slightly higher than rated full load
current (say 120 percent of FL) with proper discrimination.
4.6.3 Combined overcurrent and unrestricted EIP Protection (Ref. -Kg. 4.2)
a) Typical over current/earth fault protection is shown for a Delta/start
transformer in Fig. 4.2.
b) IDMT O/C elements on delta and star side, primarily serve as back up
protection against downstream short circuits and are time coordinated
with downstream O/C protections.
c) The high set instantaneous O/C elements on Delta side (connected to
source) are provided to detect severe terminal short circuits and quickly
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
48/167
isolate the transformer. These are set over and above the maximum
short circuit current infeeds of the transformer for star side faults.
d) The start side earth fault protection (IDMT) serves as a backup against
downstream earth faults and is required to be suitably time graded. Thiscan either be residually connected across the phase C.Ts or operated off
a C.T. in the Neutral Earth connection (standby earth fault relay). The
latter is considered to be advantageous since it can detect star winding
earth faults, beside providing backup for downstream earth faults. Since
the neutral C.T. ratio is not tied up with the load current, a lower C.T.
ratio consistent with the maximum E/F current limited by NGR can be
provided. This renders good sensitivity for the standby E/F protection.
e) The E/F protection on delta side is inherently restricted to delta winding
earth faults and does not respond to earth faults on the star side, due to
zero sequence isolation provided by the delta connection. The delta side
E/-F protection, therefore, assumes the form of REF
PAGE 48
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
49/167
PAGE 49
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
50/167
protection, enabling sensitive setting and instantaneous operation. The relay is
connected in high impedance mode with a series stabilizing resistor, as shown.
4.6.4 Restricted EarthFault Protection : (Ref. Mg. 4.3)
a) REF protection is used to supplement the differential protection,particularly where star neutral of the transformer is grounded through a
neutral grounding resistor to limit the earth fault current. REF protection
provides increased coverage to the star winding against earth faults.
b) The REF protection operates on the principle of Kirchoff's law and
requires CTs of identical ratio and ratings as the phases and neutral
earth connection. The relay is connected across the parallel combination
of the CTs in High Impedance mode.
c) For external earth fault, the associated CTs have dissimilar polarities
forming a series connection. Thus, the resulting current through the
relay is negligible. For internal fault, however, the CTs have similar
polarities, forming a parallel connection, thus adding up the current in the
relay branch. This ensures positive operation of the relay.
4.7 Percentage Bias Differential Protection
a) In this protection, operating current is a function of differential current.
b) The value of restraining current depends on 2nd and 5th harmonic
component of differential current during magnetic inrush and over excited
operation.
c) Bias current is a function of through current (external fault current) and
stabilizes the relays against heavy external fault.
4.7. 1 Basic Consideration for differentiazprotection
a) Transformer ratio : the current transformers should match to the rated
currents of the primary windings.
PAGE 50
b) Transformer Connection: In delta star connected transformer, the phase
shift of 300C between primary and secondary. side current exist. Also
zero sequence current flowing on the star side will not produce the
reflected current. in the delta on the other side. To eliminate zero
sequence compo nent on star side the current transformer must be
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
51/167
connected in delta and the current transformer of delta: side must be
connected in start.
c) For star/star transformer CTs on both sides should be connected in . delta.
d) In order that secondary currents from two groups of CTs may have thesame.magnitude (i.e.. primary side CTs and secondary side CTs). The
ratio of star connected CTs if 5 Amp, then those of delta connected group
may be 5/ @3 2.89 Amps.
e) The operating current is a appropriate percentage of reflected through
fault current in the. restraining (bias) coils and the ratio is termed as
percentage slope.
f) Operating coil is provided with vectors sum of the currents in the
transformer windings and the bias coil sees the average scaler sum of the.
reflected through fault current. Spill current required to operate the relay
is expressed as percentage of through current.
g) The relay is also provided with an unrestrained differential high set, to
protect against heavy faults which are en ough to saturate the line current
transformers. The settin of this high set unit is kept above the maximum
in rush current magnitude. This will operate in typically one cycle for
heavy internal faults.
4.7.2 Operating Principlesfor Internalfault & externalfaults
During external fault condition (through fault) (Fig. 4.4):
Current in pilot wires would pass, through whole of bias coils and only .ou@t of
balance current due tb mis-match caused by OLTC and C.T. errors
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
52/167
8/8/2019 Ele_Pro_Sys
53/167
PAGE 52
would flow through operating coil. Under this condition biasing effect
predominates and prevents the relay operation.
During Internal faults: (FYg. 4. 5)In this case, the reflected current flows through only one half of bias coil and the
operating coil and back to CT neutral connection. Here the operating quantity
predominates resulting into operation of the relay.
4.8 Over Voltage Protection
a) Two stage protection is provided
b) the delayed trip is set at 1 10 percent of the rated voltage with two second
time delay (typical).
c) Instantaneous setting is kept at 1 15 - 120 percent of the rated voltage
d) During voltage fluctuations the AVR (Automatic Voltage Regulator) will
take care to avoid over voltage condition if fluctuations are within its
operating limits (for Generator step-up transformer).
4.9 C)ver Fluxing Protection
a) This protection is commonly used for Generator Transformers and large
inter connecting transformers in the Grid.
b) This condition arises during abnormal operating conditions i.e. heavy
voltage fluctuations at lower frequency conditions. This condition is
experienced by the transformer during heavy power swings, cascade
tripping of the generator sets and HT line in the Grid, interstate system
separation conditions and due to AVR malfunctioning during start-up or
shutting down in case of Generator Transformers.
c) The power frequency over -voltage cause both stress on insulation and
proportionate increase in the magnetising flux inside the transformer due to
which the iron losses are increased and the core bolts get maximum
component of flux, thereby rapidly heating and damaging its own
insulation and coil insulation. Reduction in frequency during high voltage
fluctuation has the same effect.
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
54/167
PAGE 53
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
55/167
PAGE 54
d) Transformer should be isolated within one or two minutes or as
recommended by the manufacturer.
e) The core flux @ V/f where V- impressed voltage and f- frequency. Theindex of over fluxing is, therefore, V/f. Over fluxing relays having variable
V/f setting and time delays are used for this protection.
4.10 Overall DifferentialProtection
a) This is provided for complete protection of generator, and generator
transformer and as such is a compound overall differential protection.
b) In addition to normal differential protection of generator, overall biased
differential protection relay is connected to protect the unit as shown, in Mg. 4.6.
c) 200/o pickup and 20% bias setting is provided.(The values are typical).
d) This is a supplementary protection for individual differential protection of
the generator.
e) Unit auxiliary transformers . are provided with separate differential
protection.
PAGE 55
ANNEXURE-I
PERMISSIBLE CONCENTRATIONS OF DISSOLVED
GASES IN THE OIL OF HEALTHY TRANSFORMER
(TRANSFORMERS UNIO AG)
GasLess than four
years in service4-10 years in
serviceMore than 10
years in service
Hydrogen 100 / 150 ppm 200 / 300 ppm 200 / 300 ppm
Methane 50 / 70 ppm 100 / 150 ppm 200 / 300 ppm
Acetylene 20 / 30 ppm 30 / 50 ppm 100 / 150 ppm
Ethylene 100 / 150 ppm 150 / 200 ppm 200 / 400 ppm
Ethane 30 / 40 ppm 100 / 150 ppm 800 / 1000 ppm
CarbonMonoxide 200 / 300 ppm 400 / 500 ppm 600 / 700 ppm
Carbondioxide 3000 / 3500 ppm 4000 / 5000 ppm 9000 / 12000 ppm
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
56/167
PAGE 56
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
57/167
PAGE 57
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
58/167
CHAPTER - 5
GENERATOR PROTECTIONS
5.1 Introduction
Generators are designed to run at a high load factor for. a large number of yearsand permit certain incidences of abnormal working conditions. The machine and
its auxiliaries are supervised by monitoring devices to keep the incidences of
abnormal working conditions down to a minimum. Despite of this monitoring,
electrical and mechanical faults may occur, and the generators must be provided
with protective relays, which in case' of a fault, quickly initiate a disconnection
of the machine from the system and, if necessary, initiate a complete shut-down
of the machine.
The following are the various types of protections provided for a 200 / 2 1 0 MW
Generator.
1. Stator ground (earth) fault protection
a) 95% stator ground fault protection
b) 100% stator ground fault protection
2. Rotor earth fault protection
a) First rotor earth fault protection
b) Second rotor earth fault protection
3. Generator Interturn fault protection
4. Generator Negative phase sequence protection
5. Generator Loss of excitation protection
6. Generator Minimum Impedance (MHO backup) protection
7. Generator Differential protection
8. Generator Overall differential protection
9. Generator Reverse power protection
10. Generator Over frequency protection
11. Generator Under frequency protection
12. Generator Thermal overload protection
13. Generator Over voltage protection
14. Generator out of step (Pole slipping) Protection
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
59/167
8/8/2019 Ele_Pro_Sys
60/167
8/8/2019 Ele_Pro_Sys
61/167
8/8/2019 Ele_Pro_Sys
62/167
c) D.C. injection method
5.3.1 Potentiometer Method(Fig. 5.3)
In this scheme, a centre tapped resistor is connected in parallel with the main
field winding as shown in Fig. 5.3. The centre point of the resistor is connectedto earth through a voltage relay. An earth fault on the field winding will produce
a voltage across the relay. The maximum voltage occurring for faults at the ends
of the winding.
A 'blind spot'exists at the centre of the field winding, this point being at a
potential equal to that of the tapping point on the potentiometer. To avoid a fault
at this location remaining undetected, the tapping point on the potentiometer is
varied by a push button or switch. It is essential that station instructions be
issued to make certain that the blind spot is checked at least once per shift. The
scheme is simple in that no auxiliary supply is needed. A relay with a setting 5%
of the exciter voltage is adequate. The potentiometer will dissipate about 60
volts.
5.3.2 A. C. InjectionMethod(Mg. 5. 4)
This scheme is shown in Fig. 5.4. It comprises of an auxiliary supply
transformer, the secondary of which is connected between earth and one side of
the field circuit through an interposed capacitor and a relay coil.
The field circuit is subjected to an alternating potential at the same level through
out, so that an earth fault anywhere in the field system will give rise to a current
which is detected by the relay. The capacitor limits the magnitude of the current
and blocks the normal field voltage, preventing the discharge of a large direct
current through the transformer.
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
63/167
PAGE 62
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
64/167
8/8/2019 Ele_Pro_Sys
65/167
This scheme has an advantage over the potentiometer method in that there is no
blind spot in the supervision of the field system. It has the disadvantage that
some current will flow to earth continuously through the capacitance of the field
winding. This current may flow through the machine bearings, causing erosionof the bearing surface. It is a common practice to insulate the bearings and to
provide an earthing brush for the shaft. and if this is done the capacitance current
would be harmless.
5.3.3 D. C. InjectionMethod(FYg. 5. 5)
The capacitance current ob ection to the a.c. injection scheme is' overcome by
rectifying the injection voltage as shown in Fig. 5.5. The d.c. out put of a
transformer rectifier power unit is arranged to bias the positive side of the field
circuit to a negative voltage relative to earth. The negative side of the field
system is at a greater negative voltage to earth, so an earth fault at any point in
the field winding will cause current to flow through the power unit. The current
is limited by including a high resistance in the circuit and a sensitive relay is
used to detect the current.
The fault current varies with fault position, but this is not detrimental provided
the relay can detect the minimum fault current and withstand the maximum.
The relay must have enough resistance to limit the fault current to a harmless
value and be sufficiently sensitive to respond to a fault which at the low injection
voltage may have a fairly high resistance. The relay must not be so sensitive as
to operate with the normal insulation leakage current, taking into account of the
high voltage to earth at the negative end of the winding and any over voltage due
to field forcing and so on.
5.3.4 (a) SecondRotor Earth Fault Protection 64R2 (FYg. 5.5 a)
In this test system is replaced by a replica field system in the form of potential
divider, two IK potentiometers in parallel with station D.C. is used as shown in
Figure 5.5 (a) with SWI at lst rotor E/F position. Close switch S 1 check that 1
st rotor E/ F relay VAEM (64R 1) operated.
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
66/167
PAGE 64
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
67/167
8/8/2019 Ele_Pro_Sys
68/167
8/8/2019 Ele_Pro_Sys
69/167
PAGE 67
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
70/167
8/8/2019 Ele_Pro_Sys
71/167
8/8/2019 Ele_Pro_Sys
72/167
8/8/2019 Ele_Pro_Sys
73/167
8/8/2019 Ele_Pro_Sys
74/167
8/8/2019 Ele_Pro_Sys
75/167
5.6.1 Out of Step Protection ofGenerator
A generator may lose synchronism with the power system, without failure of the
excitation system, because of a severe system fault disturbance or operation at a
high load with a leading power factor and hence a relatively weak field. In thiscondition, which is quite different from the failure of field system, the machine
is subject to violent oscillations of torque, with vide variations, in current, power
and power factor. Synchronism can be regained if the load is sufficiently
reduced but if this does not occur within a few seconds it is necessary to isolate
the generator and then resynchronize.
The impedance of the generator measured at the 'stator terminals changes mostly
when synchronism is lost. by the machine. The terminal voltage will begin to
decrease and the current to increase, resulting in a decrease of impedance and
also a change in power factor.
A pole slipping protection comprising of two ohm relays is used to detect out of
step operation. The relay monitors the load impedance at the machine terminals
and operates when the terminal impedance locus sequentially crosses both ohm
relay characteristics which corresponds to one pole slip between the defaulting
machine and the system.
5.7 Generator Minimum Impedance (MHO Back) Protection (2101, G2, G3):
The Generator minimum impedance protection (or Impedance back-up
protection) is primarily provided to protect the Generator against uncleared
external short circuits on the lines emanating from the station bus bars. The
relay has an impedance or offset MHO characteristic and is set to cover the
impedance of the longest line. The Generator transformer being delta/star,
introduces a 300 phase shift on @the HV side. To ensure correct impedance
measurement of the lines, the machine voltage fed to the relay (via Generator
V.TS), is phase corrected by using Interposing voltage transformers (delta/ star)
connected in the same vector group as that of the Gen.Transformer.
PAGE 72
The relay operation is delayed by using external or built-in timer so as to
discriminate with line back-up protections.
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
76/167
Over current type of back-up protection is also used for Generator. This is
usually of voltage restraint or voltage controlled type where the voltage input
from the Generator V.T. is used to sensitise the over current protection on fault.
This ensures positive operation even though the sustained fault current is lessthan the full load current of the machine due to the effect of armature reaction.
The over current backup is also set with adequate time delay to coordinate with
down stream backup protections.
5.8 Generator Differential Protection (87A,B,C) (Fig. 5. 10)
5.8.1 Principle of Operation
Current transformers at each end of the protected zone are interconnected by an
auxiliary pilot circuit as shown in Fig. 5. 1 0. Current transmitted through the
zone causes secondary current to circulate round the pilot circuit without
producing any current in the relay. A fault within the protected zone will cause
secondary currents of opposite relative phase as compared with the through fault
condition. The summated value of these currents will. flow in the relay, thus
energizes the relay. The relay voltage setting is decided from the secondary load
drop by the following formula.
Vmax = I11(RcT + RL) where
I11
= Secondary subtransient short circuit current.
RL = resistance of pilot wire between current transformer (CT) and relay.
RcT = resistance of the secondar-y winding of the saturated current
transformer.
The relay operating voltage is set higher than Vmax. The minimum operating
current depends mainly on the current setting of the relay, the magnetizing
characteristics current of the associated CTs and CT Ratio.
For internal faults, the fault current equal to or above the minimum operating
value of the relay, the voltage across the relay goes upto the
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
77/167
PAGE 73
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
78/167
8/8/2019 Ele_Pro_Sys
79/167
8/8/2019 Ele_Pro_Sys
80/167
PAGE 75
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
81/167
PAGE 76
Inrush restraint is also required when the unit transformer energized from the HV
bus.
The over excitation restraint is important since there is a possibility of overvoltage when load is suddenly disconnected in which, the differential relay may
trip the generator and the voltage remains high until the automatic voltage
regulator (AVR) brought it back to the normal value.
The relay has an unrestrained differential high set unit. The unrestrained
operation must be set higher than the maximum inrush current of the transformer.
It gives fast tripping (10-20m sec.) The CT and relay connections are shown in
Fig. 5.1 1.
5.10 Generator Reverse Power Protection (32) (Flg. 5.12)
This is basically/the protection provided for the prime mover i.e. turbine. If the
driving torque becomes less such as closure of main steam valves in case of
steam turbo generator, the generator starts to work as a synchronous
compensator, taking the necessary active power from the network. The
reduction of steam flow reduces the cooling effect on the turbine blades and
overheating may occur. The work done by the entrapped steam in the turbine is
then zero. As generator is not designed to run as a motor it should be
immediately tripped when the steam flow to the turbine is stopped and to avoid
damage to the turbine blades.
The generator currents remain balanced when the machine is working as a
motor. For large turbo-generator, where the reverse power may be substantially
less than 1%, reverse power protection is obtained by a minimum power relay,
which normally is set to trip the machine when the active power out put is less
than 1% of rated value.
The relay contains directional current relay which measures the product IX coso,
where 0 is the angle between the polarizing voltage and the, current to the relay.
The scale range used is 5-2OmA for 1A and 30-120 mA for 5A rated CT
secondary currents. Time delay of 2 seconds is provided. The detail
connections of CT and relay are shown in Fig. 5.12.
PAGE 77
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
82/167
8/8/2019 Ele_Pro_Sys
83/167
8/8/2019 Ele_Pro_Sys
84/167
8/8/2019 Ele_Pro_Sys
85/167
5.14 Generator Over voltage Protection (I/II(59A/59B) (Fig. 5.14)
During the starting up of a generator, prior to synchronization, the Generator
terminal voltage is obtained by the proper operation of the automatic voltage
regulator (AVR). After synchronization, the terminal voltage of the machinewill be dictated by its own AVR and also by the voltage level of the system and
the AVRS of nearby machines. It is not possible for one machine to cause any
appreciable rise in the terminal voltage as long as it is connected to the system.
Increasing the field excitation, owing to a fault in the AVR, merely increases the
reactive MVAR output, which may ultimately lead to tripping of the impedance
relay or the V/Hz. Relay. Maximum excitation limit prevents the rotor field
current and the reactive output power from exceeding the design limits.
This protection is used for the insulation level of the generator stator windings.
Severe over voltage will occur, if the generator circuit 'breaker is tripped while
the machine is running at full load and rated power factor, the subsequent
increase in terminal voltage will normally be limited by a quick acting AVR.
However, if the AVR faulty or at this particular time switched over to manual
control, over voltage will occur. This voltage rise will be further increased if
simultaneous over speeding should occur, owing to a slow acting turbine
governor.
Modern unit transformers with high magnetic qualities have a relatively sharp
and well defined saturation level, with a knee point voltage between 1.2 and 1.25
times the rated voltage (Un). A suitable setting of the over voltage relay is,
therefore, between 1. 15 and 1.2 times Un and with a definite delay of 1 to 3 sec.
An instantaneous high set voltage relay can be included to trip the generator
quickly in case of excessive over voltage following a sudden loss of load and
generator over speeding.
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
86/167
PAGE 80
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
87/167
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
88/167
8/8/2019 Ele_Pro_Sys
89/167
PAGE 82
6.2.5 Sensitivity
The protection should be adequately sensitive to clear low in feed ,faults,particularly during minimum generating conditions.
6.2.5 Suitable for use with moderate C. T. ratings
This is necessary since the CTs have to handle high fault currents, worst case
being faults approaching switchgear breaking capacity.
6.2.6 Conftgurable to different Busbar arrangements
The busbar arrangement may undergo changes such as sectionalisation and
additional circuits may be connected in future. The protection should be
extendable to such configuration changes.
6.3 Types of Bus Bar Protection
The most commonly used bus bar protection system are :
1) System Protection covering Busbar
2) Differential protection
6.3.1 System Protections Covering Busbar
These are primarily local or remote backup protection such as over current/earth
fault relay on feeders/transformers or distance protection provided on lines.
The distance protection for example, provides backup protection to remote
busbars in time delayed zone 2 or backup to local busbars in time delayed zone 3
with a small reverse reach. The IDMT overcurrent. Earth fault relays also
provide similar backup protection to the connected circuits against bus faults.
However, these cannot be considered as primary protection for busbar, being
time delayed and non-selective.
6.3.2 Differential Protection
The differential protection is the primary protection for bus bar against both
phase and earth faults. Practical bus differential schemes have all the ingredient
as spelled out under 6.2 above.
6.3.2.1 Operating Principleof DifferentialProtection
The protection uses a circulating current arrangement, with CTs of identical ratio
and ratings on all incoming and outgoing circuits having heir secondaries
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
90/167
8/8/2019 Ele_Pro_Sys
91/167
8/8/2019 Ele_Pro_Sys
92/167
PAGE 85
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
93/167
PAGE 86
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
94/167
2. This type of protection requires special class PS CTs (with low turns ratio
errors) of identical ratio and ratings on all circuits. Exclusive CT cores
are required for high impedance schemes which cannot share common CT
cores with other protections.3. High impedance schemes are primarily fundamental frequency turned,
over current or over voltage relays and hence simple in design and
execution.
6.3.2.3 Supervision
The differential protection has a fail safe design. Consequently, the relay
becomes potentially unstable for any open circuit or cross connection in the CT
secondary of the associated feeders. The maloperation of the Busbar protection
can be prevented on load under the above condition by setting the pick up
threshold of the differential element over and above the maximum loaded circuit
current. However, the relay may still maloperate on a through fault, if the CT
secondary open circuit goes undetected. A maloperation of busbar protection
could be catastrophic, particularly in interconnected system and hence
continuous supervision of CT secondary is required as an additional safeguard.
The supervision relay is an AC voltage relay, connected across the differential
relay branch, having a sensitive setting range (usually 2 -14 volts) and a fixed
time delay to prevent transient operation on internal faults. The relay is
connected to sound an alarm and short CT secondary Bus wires, on operation.
Typical circuit arrangement for CT supervision relay is shown in Fig. 6.3.2.3.
6.3.2.4 Check Feature
Since stability is a very critical parameter of busbar protection, additional check
feature is usually provided in high impedance schemes to enhance security
against possible maloperation.
The check feature is o erated off a separate CT core on all incoming and
outgoing circuits connected to the bus and is a virtual duplication of the main
differential system. The contacts of the main and check
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
95/167
PAGE 87
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
96/167
8/8/2019 Ele_Pro_Sys
97/167
8/8/2019 Ele_Pro_Sys
98/167
8/8/2019 Ele_Pro_Sys
99/167
PAGE 91
PDF created with pdfFactory Pro trial version www.pdffactory.com
http://www.pdffactory.com/http://www.pdffactory.com/8/8/2019 Ele_Pro_Sys
100/167
Besides, the control breakers are provided with duplicated trip coils. All these
measures, undoubtedly improve the reliability of fault detection and isolation.
However, the possibility of mechanical failures of the switchgear or
interrupter flash overs can not be covered by these means for obvious reasons.A failure of the breaker may therefore, result inspite of correct operation of
the protection and energisation of trip coils. This situation can be corrected
by providing local breaker backup (LBB) or breaker fail protection.
6.5.2 Operating Principle
LBB protection comes into operation, only if, the breaker fails to trip, following
energisation of its trip coil, through the circuit trip relays. The main ingredient
of LBB protection, is a. current check relay initiated by the circuit trip relays and
a follower timer. The current check relay, on initiation, check the presence of