ELECTRONIC 1
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
AnalogInputs
Program Block 1(Program 0..10)
Program Block 2(Program 0..10)
BlockSelection
PumpController
Stroke Feedback
Pressure Feedback
DigitalInput
DigitalOutputDiagnostics
AnalogOutput
1 Introduction
The EPC is a microcontroller-operated motion controller and
amplifier forservo controlled pumps and valves. The unit can be
configured for severaltypes of control applications including:n
Flow Controln Pressure Control or Load Controln Flow Control with
Pressure Limit (PQ-Control)n Horsepower Control (Pump Stroke and
Pressure)
2 Basic System Overview
The EPC allows one (1) single control axis with a power
amplifier to driveVS-, VV- and VM-controlled pumps and valves. The
basic pump controllerconfiguration allows for fast (up to a 1600Hz)
closed loop response withboth stroke position and pressure
feedback. In addition, two (2) independentfunction programs can be
dynamically selected with a digital input signal. The unit provides
a digitaloutput for simple diagnostics or a watchdog signal.
Two (2) general-purpose analog inputs are provided for command
and pressure feedback signals (± 10VDC, 0-to-20 mA, or 4-to-20 mA).
Additionally, one (1) analog input is provided as a dedicated
fine-adjustable LVDT or DCDT stroke feedback device. The module
allows for the option of a second LVDTor DCDT stroke feedback or a
low-power programmable output signal.
The device is configured by first assigning one of ten (10)
built-in function programs to each of the two(2) program blocks.
Typically, the output of the function programs is then passed to
the PumpController, which provides the valve command.
Figure 1: EPC Module
Figure 2: System Overview
-
ELECTRONIC 2
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
If the full features of the module are used, up to three (3)
independent closed loop PI (Proportional withIntegral) control
algorithms are utilized. Most function programs provide a closed
loop control algorithmfor pressure or stroke, while the Pump
Controller can be configured for both stroke and power
feedback.
The module is programmable either through the on-board keypad
and display, or optimally through thePC Interface software.
Table of Contents1 Introduction
.............................................................................................................................................
12 Basic System Overview
...........................................................................................................................
13 General
Instructions................................................................................................................................
4
3.1 Password Protection
.........................................................................................................................
43.2 LCD Display Groupings
..................................................................................................................
43.3 Menu Selection and Configuration
..................................................................................................
5
3.3.1 Changing the Menu Item Number
..........................................................................................
53.3.2 Changing the Menu Value
......................................................................................................
6
3.4 PC Interface
Groupings....................................................................................................................
64 Module Configuration
.............................................................................................................................
7
4.1 General Configuration
.....................................................................................................................
74.1.1 Password Protection (000)
.....................................................................................................
74.1.2 Operating Modes (200)
..........................................................................................................
7
4.1.2.1 Dynamic Function Selection with Fault Monitor
......................................................... 74.1.2.2
Dynamic Function Selection with Watchdog Monitor
................................................. 84.1.2.3 Static
Function Selection with Watchdog Daisy Chain
................................................ 8
4.1.3 Program Block Configuration (21x)
......................................................................................
84.2 Program Configuration
....................................................................................................................
9
4.2.1 Overview
................................................................................................................................
94.2.2 PI Control Algorithms
..........................................................................................................
104.2.3 Pressure Control Programs (40x, 41x)
.................................................................................
104.2.4 Flow with Pressure Limit Programs (42x, 43x)
...................................................................
124.2.5 Load Sense Control Programs (44x, 45x)
............................................................................
154.2.6 Simple Flow Control Programs (46x, 47x)
..........................................................................
184.2.7 Advanced Flow with Pressure Limit Programs (48x, 49x)
.................................................. 19
4.3 Pump Controller Configuration
.....................................................................................................
194.3.1 Overview
..............................................................................................................................
194.3.2
Configuration........................................................................................................................
19
4.3.2.1 Function Zero Stroke Command
................................................................................
194.3.2.2 Stroke Controller
.........................................................................................................
204.3.2.3 HP Limiter
..................................................................................................................
204.3.2.4 Output Polarity
............................................................................................................
214.3.2.5 Output Current Limit
..................................................................................................
21
4.3.3 Configuration Example
........................................................................................................
224.4 Analog IO Configuration
...............................................................................................................
23
4.4.1 General Purpose Analog Input Configuration
......................................................................
23
-
ELECTRONIC 3
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.4.2 LVDT/DCDT Fine-Adjustable Analog Input Configuration
............................................... 264.5 Ramp
Configuration
......................................................................................................................
274.6 Advanced Configuration
................................................................................................................
29
4.6.1 LVDT Adjustment Algorithm
..............................................................................................
294.6.1.1 Adjustment Mode
.......................................................................................................
294.6.1.2 Determining LVDT Configuration Range
..................................................................
314.6.1.3 Adjustment Algorithm
................................................................................................
32
4.6.2 HP Limit Factor Calculation
................................................................................................
344.6.2.1 Experimental HP Limit
Factor....................................................................................
344.6.2.2 Theoretical HP Limit Factor
.......................................................................................
35
5 Module Diagnostics
...............................................................................................................................
365.1 Diagnostic Representation of Numbers
.........................................................................................
36
5.1.1 DAC Counts
.........................................................................................................................
365.1.2 Voltage and Percentages
......................................................................................................
37
5.2 Basic Diagnostics
...........................................................................................................................
375.3 Programmable Output Diagnostic
.................................................................................................
375.4 Advanced Diagnostics
...................................................................................................................
38
5.4.1 Module Faults
.......................................................................................................................
385.4.2 Run-Time Messages
.............................................................................................................
39
6 Technical Data
.......................................................................................................................................
406.1 Module Pin-Out
.............................................................................................................................
406.2 Test Point, DIP-Switch, and Pot Settings
......................................................................................
416.3 Sample Connection Diagram
.........................................................................................................
426.4 Specifications
.................................................................................................................................
436.5 IO Summary
...................................................................................................................................
43
7 Technical Support
.................................................................................................................................
448 Ordering Information
...........................................................................................................................
45
-
ELECTRONIC 4
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
3 General Instructions
3.1 Password Protection
The EPC allows for edit protection of all programmable
parameters. Please refer to Section 4.1.1 fora thorough discussion
of Password Protection.
3.2 LCD Display Groupings
The EPC is designed for a variety of applications. A numerical
menu is provided to program thedevice through the on-board keypad
and display. The menu items range from 000 to 999 and areloosely
grouped in the following manner:
000 Password Protection2xx Program Selection and Digital IO
Configuration4xx Program Configuration80x, 81x Pump Controller
Configuration83x, 84x Fine-Adjustable Input Configuration
(LVDT/DCDT)85x, 86x General Purpose Input Configuration87x Ramp
Configuration90x, 91x, 92x, 93x General Diagnostics96x Factory
Preset Fine DAC Adjustment98x, 999 Fault Diagnostics
Most menu displays show three (3) items:n The Menu Item Number.n
A brief Text Description of the Menu Item.n The Configuration or
Diagnostic Value of the Menu Item.
Menu I temNumber
TextDescription
Configuration orDiagnostic Value
Figure 3: Standard Menu Layout
For some menu items, a graphical indicator bar corresponding to
the Configuration or DiagnosticValue is provided.
Menu I temNumber
TextDescription
Configuration orDiagnostic Value
Figure 4: Menu Layout with Graphical Indicator Bar
-
ELECTRONIC 5
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
3.3 Menu Selection and Configuration
The onboard keypad on the front panel allows for selection and
editing of menu items. The menuitems are defined by a number that
appears in the upper left corner of the display and is always
athree-digit number in the range of 000 to 999. The position of the
underscore indicates the editabledigit.
3.3.1 Changing the Menu Item Number
The cursor keys change the position of the editable digit
cursor. For instance, if the menu isinitially:
Figure 5
Pressing the right cursor key moves the editable digit cursor
right to the next digit:
Figure 6
Figure 7
Conversely, pressing the left cursor key moves the editable
digit cursor left to the previous digit:
Figure 8
Figure 9
If the editable digit cursor is under the Menu Item Number,
pressing the increment or decrementkeys changes the Menu Item
Number.
For example, if the menu and cursor position is initially:
Figure 10
Pressing the Increment key changes the Menu Item Number in the
forward direction.
Figure 11
Conversely, the Decrement key changes the Menu Item Number in
the reverse direction.
Figure 12
-
ELECTRONIC 6
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Note that only valid menu items can be selected so the increment
and decrement keys will notalways correspond to a normal numerical
order. For example, the user will increment directlyfrom menu item
000 to 200 since no other menu item exists between these two
items.
3.3.2 Changing the Menu Value
If the menu item refers to an editable field, the editable digit
cursor can be extended beyond themenu entry using the right cursor
key. For example, pressing the right cursor key for the menu:
Figure 13
extends the editable digit cursor into the value field.
Figure 14
In addition to the position of the editable digit cursor, the
triangle to the left of the menu itemnumber indicates that the
controller is in edit mode. Pressing the Increment or Decrement
keysallows the user to change the menu value. Pressing the left
cursor field allows the user to returnthe editable digit cursor to
the menu item.
3.4 PC Interface Groupings
The PC interface provides a more optimal programming and
monitoring interface. A toolbar menuloosely groups functions in the
following manner:
File File, Print, and Communication CommandsGeneral Password and
Communication Setup,
Program Selection and Digital IO Configuration(menu items 000
and 2xx)
Program Program Configuration (menu items 4xx)Pump Controller
Pump Controller Configuration
(menu items 8xx)Diagnostics General Purpose Input Configuration,
Configuration Fine-Adjustable Input Configuration (LVDT/DCDT),
Diagnostics(menu items 83x, 84x, 85x, 86x, 92x, and 93x)
Diagnostics Ramp Configuration and Advanced HP Limit Setup
Advanced (menu items 87x and 810)Help User Help
Items are programmable either through Numeric Input boxes or
Drop-Down List boxes.
-
ELECTRONIC 7
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4 Module Configuration
4.1 General Configuration
General Configuration parameters include Password, Mode, and
Communication Setup Parameters.
4.1.1 Password Protection (000)Menu Item Range Description000 0
to 255 Password
Table 1: Password Protection
The EPC has a simple lockout password that can be used to
protect the program configurationfrom accidental changes. The
password is entered through menu item 000 or by typing apassword
from the General Configuration form of the PC interface.
If the password is set to 249, the user will be able to modify
any editable entry. Any otherpassword will place the device in
read-only mode. The user will not be able to modify any entryin
this mode.
4.1.2 Operating Modes (200)Menu Item Range Description200 0 to 2
Operating Mode:
0: Dynamic Function Selection with Fault Monitor1: Dynamic
Function Selection with Watchdog Monitor2: Static Function
Selection with Watchdog Daisy Chain
Table 2: Operating Modes
The EPC has three (3) operating modes. Depending on the
operating mode, the EPC reacts to thedigital input to make one of
the two program blocks active.
4.1.2.1 Dynamic Function Selection with Fault Monitor
This operating mode is selected by setting menu item 200 to 0,
or by choosing Mode 0:Dynamic Function Selection with Fault Monitor
from the General Configuration form of thePC Interface.
In this operating mode, the digital input selects which program
block is active. If the digitalinput is low ( 5VDC), Program Block
2 is made active and theprogram defined in menu 211 is used. Refer
to Section 4.1.3 for discussion of ProgramBlock Configuration
(21x).
The digital output provides standard condition status. If no
faults are present, the digitaloutput will be high (Vsupply); If
faults are present, the digital output will be low (0 VDC).Refer to
Section 5.4 for information on module fault and message
conditions.
-
ELECTRONIC 8
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.1.2.2 Dynamic Function Selection with Watchdog Monitor
This operating mode is selected by setting menu item 200 to 1,
or by choosing Mode 1:Dynamic Function Selection with Watchdog
Monitor from the General Configuration formof the PC Interface.
In this operating mode, the digital input selects which program
block is active. If the digitalinput is low ( 5VDC), Program Block
2 is made active and theprogram defined in menu 211 is used. Refer
to Section 4.1.3 for discussion of ProgramBlock Configuration
(21x).
The digital output provides a watchdog signal of approximately
100 Hz.
4.1.2.3 Static Function Selection with Watchdog Daisy Chain
This operating mode is selected by setting menu item 200 to 2,
or by choosing Mode 2: StaticFunction Selection with Watchdog Daisy
Chain from the General Configuration form of thePC Interface.
In this operating mode, Program Block 1 is always active and the
program defined in menu210 is used. Program Block 2 is always
inactive and menu item 211 has no function. Referto Section 4.1.3
for discussion of Program Block Configuration (21x).
The digital input is passed through the module into the digital
output. In this way, one singlewatchdog timer can be used for a
number of EPC modules. One EPC module would need tobe configured
for Mode 1: Dynamic Function Selection with Watchdog Monitor;
theremaining EPCs would be configured for Mode 2. Any module
failure would break the daisychain.
4.1.3 Program Block Configuration (21x)Menu Item Range
Description210 0 to 10 Program Selection for Program Block 1
0: No Program used for Block 1(refer to Section 4.3.2.1)
1-10: Program 1 to 10 used for Block 1
211 0 to 10 Program Selection for Program Block 20: No Program
used for Block 2
(refer to Section 4.3.2.1)1-10: Program 1 to 10 used for Block
2
Table 3: Program Block Configuration
The program block configuration parameters are used in
conjunction with the module operatingmodes (refer to Section 4.1.2)
to assign pre-defined programs to the two (2) program blocks.
-
ELECTRONIC 9
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Modes 0 and 1: For operating modes 0 (Dynamic Function Selection
with Fault Monitor) and 1(Dynamic Function Selection with Watchdog
Monitor) the digital input is used to make one ofthe two function
blocks active. Menu items 210 and 211, in turn, select which
pre-definedfunction program is made active for the function
block.
Example 1: Operating Mode (menu item 200) is set to 0 (Dynamic
Function Selection with FaultMonitor). Program Selection for
Program Block 1 (menu item 210) is set to 1 (Pressure Control)and
Program Selection for Program Block 2 (menu item 211) is set to 3
(Flow with PressureLimit Control).
If the digital input is low ( 5VDC), Program Block 2 is
madeactive and the active program is Program 3 (Flow with Pressure
Limit Control).
Example 2: Again, operating Mode is set to 0. Program Selection
for Program Block 1 (menuitem 210) is set to 1 (Pressure Control)
and Program Selection for Program Block 2 (menu item211) is set to
0 (No Program).
If the digital input is low ( 5VDC), Program Block 2 is
madeactive, but since no program is activated, the module uses a
special zero function command tocommand the pump controller (refer
to Section 4.3.2.1 for configuration of the Function ZeroStroke
Command).
Mode 2: For operating mode 2 (Static Function Selection with
Watchdog Daisy Chain) thedigital input is used as a watchdog input
signal. Therefore, no dynamic function selection ispossible. In
this mode, Program Block 1 is always active and menu 210 defines
the activefunction program. Menu 211 has no function in operating
mode 2.
The program blocks are selected from the General Configuration
form of the PC Interface.
4.2 Program Configuration
4.2.1 Overview
The EPC offers 10 pre-defined programs. The programs range from
simple flow control toadvanced functionality. Five different types
of programs exist, and the module provides twodistinct copies of
each program.
Programs 1 and 2 provide Pressure Control programs. Programs 3
and 4 provide Flow withPressure Limit Control programs. Programs 5
and 6 provide Load Sense Control programs.Programs 7 and 8 provide
Simple Flow Control programs. Finally, Programs 9 and 10
provideanother version of a Flow with Pressure Limit Control.
Under usual circumstances, the pre-defined programs are used as
outer loop control. The outputof the pre-defined programs is
normally passed through to the Pump Controller module (refer
toSection 4.3.1 for an overview of the Pump Controller).
-
ELECTRONIC 10
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.2.2 PI Control Algorithms
Most programs use a PI (Proportional with Integral) control
scheme. Although an advancedtutorial on digital control systems is
beyond the scope of this technical document some level ofknowledge
and experience is necessary to successfully implement the control
programs.
The basis of a PI controller is that an output signal is
produced due to a difference between acommand and feedback term
(the difference is usually referred to as Error). The output
signalfor a PI control is made of a proportional error signal
combined with an integral error signal.
4.2.3 Pressure Control Programs (40x, 41x)Menu Item Range
Description400 1 to 100 Program 1: Pressure Command Preset401 0 to
5 Program 1: Pressure Command Source402 1 to 5 Program 1: Pressure
Feedback Source403 0 to 1 Program 1: Program Output Destination404
0 to 100 Program 1: KP405 0 to 100 Program 1: KI
410 1 to 100 Program 2: Pressure Command Preset411 0 to 5
Program 2: Pressure Command Source412 1 to 5 Program 2: Pressure
Feedback Source413 0 to 1 Program 2: Program Output Destination414
0 to 100 Program 2: KP415 0 to 100 Program 2: KI
Table 4: Pressure Control Programs Configuration
Function Programs 1 and 2 provide for basic Pressure Control.
Program 1 is configured in menuitems 400 through 405 or from the
Program 1 form of the PC Interface. Program 2 is configuredin menu
items 410 through 415 or from the Program 2 form of the PC
Interface.
Pressure Command Preset: The Pressure Command Preset allows for
direct numeric input forthe control program. The preset is
configured as a percentage, with 0% being equivalent to a0VDC input
signal and 100% being equivalent to a +10VDC signal.
Pressure Command Source: The Pressure Command Source selects the
source of the pressurecommand for the program. Valid entries are
(0) Preset Value, (1) Analog Input 1, (2) AnalogInput 2, (3) LVDT 1
(Analog Input 3), (4) LVDT 2 (Analog Input 4), or (5) Ramp 1. If
the PresetValue is chosen, the Pressure Command Preset is used as
the program command.
Pressure Feedback Source: The Pressure Feedback Source selects
the source of the pressurefeedback for the program. Valid entries
are (1) Analog Input 1, (2) Analog Input 2, (3) LVDT 1(Analog Input
3), (4) LVDT 2 (Analog Input 4), or (5) Ramp 1.
Program Output Destination: The Program Output Destination
selects the output of theprogram. Valid entries are (0) Pump
Controller or (1) Direct. If the Pump Controller is chosen,
-
ELECTRONIC 11
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
the output of the Program will be the input to the Pump
Controller module. If Direct is chosen,the output of the Program
will by-pass the Pump Controller module and is passed directly to
theservo driver. Under most circumstances, the Pump Controller
should be chosen as the outputdestination.
KP and KI : KP and KI provide the proportional and integral
constants, respectively, for the PIcontrol algorithm. Both terms
are expressed as 0 to 100% of a maximum value. The PI controlloop
can be made a P-only control loop by setting the KI term to 0.
Likewise, the PI control loopcan be made an I-only control loop by
setting the KP term to 0.
Program Overview: The Pressure Control Program is a
straightforward PI control algorithm.Comparing the command to the
feedback value produces an error value. The error is multipliedby
the KP and KI constants to produce the Yp and Yi contributions to
the program output.
Figure 15: Pressure Control Program
Example: Figure 15 shows the Program 1 form of the PC Interface.
The Pressure CommandSource is Analog Input 1 (menu 401=1) and the
Pressure Feedback Source is Analog Input 2(menu 402=2). The
Pressure Command Preset has a value of 50% (menu 400=50) although
it isnot used for this particular example.
The error signal is produced by comparing the command to the
feedback signals: 3068 - 3031 =37 (all display values are in DAC
counts, refer to Section 5.1 for a discussion of the
DiagnosticRepresentation of Numbers) The Yi and Yp signals are
produced from the PI controller and theprogram output is roughly
equal to their sum: 1280 + 27 = 1307. The Program Output is set to
thePump Controller (menu 403=0).
-
ELECTRONIC 12
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.2.4 Flow with Pressure Limit Programs (42x, 43x)Menu Item
Range Description420 0 to 100 Program 3: Flow Command Preset421 1
to 100 Program 3: Pressure Limit Preset422 0 to 5 Program 3: Flow
Command Source423 0 to 5 Program 3: Pressure Limit Source424 1 to 5
Program 3: Pressure Feedback Source425 0 to 1 Program 3: Program
Output Destination426 0 to 100 Program 3: KP427 0 to 100 Program 3:
KI428 Program 3: Spare429 Program 3: Spare
430 0 to 100 Program 4: Flow Command Preset431 1 to 100 Program
4: Pressure Limit Preset432 0 to 5 Program 4: Flow Command
Source433 0 to 5 Program 4: Pressure Limit Source434 1 to 5 Program
4: Pressure Feedback Source435 0 to 1 Program 4: Program Output
Destination436 0 to 100 Program 4: KP437 0 to 100 Program 4: KI438
Program 4: Spare439 Program 4: Spare
Table 5: Flow with Pressure Limit Programs Configuration
Function Programs 3 and 4 provide for Flow with Pressure Limit
Control. Program 3 isconfigured in menu items 420 through 429 or
from the Program 3 form of the PC Interface.Program 4 is configured
in menu items 430 through 439 or from the Program 4 form of the
PCInterface.
Flow Command Preset: The Flow Command Preset allows for direct
numeric input for thecontrol program. The preset is configured as a
percentage, with 0% being equivalent to a 0VDCinput signal and 100%
being equivalent to a +10VDC signal.
Pressure Limit Preset: The Pressure Limit Preset allows for
direct numeric input for the controlprogram. The preset is
configured as a percentage, with 0% being equivalent to a 0VDC
inputsignal and 100% being equivalent to a +10VDC signal.
Flow Command Source: The Flow Command Source selects the source
of the flow commandfor the program. Valid entries are (0) Preset
Value, (1) Analog Input 1, (2) Analog Input 2, (3)LVDT 1 (Analog
Input 3), (4) LVDT 2 (Analog Input 4), or (5) Ramp 1. If the Preset
Value ischosen, the Flow Command Preset is used as the flow
command.
-
ELECTRONIC 13
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Pressure Limit Source: The Pressure Limit Source selects the
source of the pressure limitcommand for the program. Valid entries
are (0) Preset Value, (1) Analog Input 1, (2) AnalogInput 2, (3)
LVDT 1 (Analog Input 3), (4) LVDT 2 (Analog Input 4), or (5) Ramp
1. If the PresetValue is chosen, the Pressure Limit Preset is used
as the pressure limit command.
Pressure Feedback Source: The Pressure Feedback Source selects
the source of the pressurefeedback for the program. Valid entries
are (1) Analog Input 1, (2) Analog Input 2, (3) LVDT 1(Analog Input
3), (4) LVDT 2 (Analog Input 4), or (5) Ramp 1.
Program Output Destination: The Program Output Destination
selects the output of theprogram. Valid entries are (0) Pump
Controller or (1) Direct. If the Pump Controller is chosen,the
output of the Program will be the input to the Pump Controller
module. If Direct is chosen,the output of the Program will by-pass
the Pump Controller module and is passed directly to theservo
driver. Under most circumstances, the Pump Controller should be
chosen as the outputdestination.
KP and KI : KP and KI provide the proportional and integral
constants, respectively, for the PIcontrol algorithm. Both terms
are expressed as 0 to 100% of a maximum value. The PI controlloop
can be made a P-only control loop by setting the KI term to 0.
Likewise, the PI control loopcan be made an I-only control loop by
setting the KP term to 0.
Program Overview: The Flow with Pressure Limit Control Program
is a flow limit algorithm;the PI Control algorithm is only used if
the pressure feedback is greater than the pressure limit.Comparing
the command to the feedback value produces an error value. The
error is multipliedby the KP and KI constants to produce tpe Yp and
Yi contributions to the pressure limit signal.This signal, in turn,
is used to limit the flow command to the program output. If the
pressurelimit command is greater than the feedback signal, no
pressure limit command will be added tothe Flow command; the flow
command will be transposed directly through to the program
output.
-
ELECTRONIC 14
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Figure 16: Flow with Pressure Limit Program
Example: Figure 16 shows the Program 3 form of the PC Interface.
The Flow Command Sourceis Analog Input 1 (menu 422=1). The Flow
Command Preset is set to 10% (menu 420=10)although the Flow Command
Preset is not used in this example.
The Pressure Limit Command Source is the Preset Value (menu
423=0), therefore the pressurelimit command is set at a 50% level
(menu 421=50). The Pressure Feedback Source is AnalogInput 2 (menu
424=2).
The error signal is produced by comparing the Command to the
Feedback signals: 3071 - 3087 =-16 (all displays values are in DAC
counts, refer to Section 5.1 for a discussion of the
DiagnosticRepresentation of Numbers). The Yi and Yp signals are
produced from the PI controller and thePressure Limit value is
roughly equal to their sum: -108 + -11 = -119.
The Pressure Limit Value is used to decrease the flow command:
2382 - 119 = 2263. Finally, theProgram Output is set to the Pump
Controller (menu 425=0)
-
ELECTRONIC 15
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.2.5 Load Sense Control Programs (44x, 45x)Menu Item Range
Description440 1 to 100 Program 5: Pressure Point 2 Preset441 1 to
100 Program 5: Delta Pressure Preset442 1 to 100 Program 5:
Pressure Limit Preset443 0 to 5 Program 5: Pressure Point 2
Source444 0 to 5 Program 5: Delta Pressure Source445 0 to 5 Program
5: Pressure Limit Source446 1 to 5 Program 5: Pressure Point 1
Source447 0 to 1 Program 5: Program Output Destination448 0 to 100
Program 5: KP449 0 to 100 Program 5: KI
450 1 to 100 Program 6: Pressure Point 2 Preset451 1 to 100
Program 6: Delta Pressure Preset452 1 to 100 Program 6: Pressure
Limit Preset453 0 to 5 Program 6: Pressure Point 2 Source454 0 to 5
Program 6: Delta Pressure Source455 0 to 5 Program 6: Pressure
Limit Source456 1 to 5 Program 6: Pressure Point 1 Source457 0 to 1
Program 6: Program Output Destination458 0 to 100 Program 6: KP459
0 to 100 Program 6: KI
Table 6: Load Sense Programs Configuration
Function Programs 5 and 6 provide for Load Sense Control.
Program 5 is configured in menuitems 440 through 449 or from the
Program 5 form of the PC Interface. Program 6 is configuredin menu
items 450 through 459 or from the Program 6 form of the PC
Interface.
Pressure Point 2 Preset: The Pressure Point 2 Preset allows for
direct numeric input for thecontrol program. The preset is
configured as a percentage, with 0% being equivalent to a 0VDCinput
signal and 100% being equivalent to a +10VDC signal.
Delta Pressure Preset: The Delta Pressure Preset allows for
direct numeric input for the controlprogram. The preset is
configured as a percentage, with 0% being equivalent to a 0VDC
inputsignal and 100% being equivalent to a +10VDC signal.
Pressure Limit Preset: The Pressure Limit Preset allows for
direct numeric input for the controlprogram. The preset is
configured as a percentage, with 0% being equivalent to a 0VDC
inputsignal and 100% being equivalent to a +10VDC signal.
-
ELECTRONIC 16
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Pressure Point 2 Source: The Pressure Point 2 Source selects the
source of the pressure point 2signal for the program. Valid entries
are (0) Preset Value, (1) Analog Input 1, (2) Analog Input2, (3)
LVDT 1 (Analog Input 3), (4) LVDT 2 (Analog Input 4), or (5) Ramp
1. If the PresetValue is chosen, the Pressure Point 2 Preset is
used as the delta pressure point 2 command.
Delta Pressure Source: The Delta Pressure Source selects the
source of the delta pressure signalfor the program. Valid entries
are (0) Preset Value, (1) Analog Input 1, (2) Analog Input 2,
(3)LVDT 1 (Analog Input 3), (4) LVDT 2 (Analog Input 4), or (5)
Ramp 1. If the Preset Value ischosen, the Delta Pressure Preset is
used as the delta pressure command.
Pressure Limit Source: The Pressure Limit Source selects the
source of the pressure limitcommand for the program. Valid entries
are (0) Preset Value, (1) Analog Input 1, (2) AnalogInput 2, (3)
LVDT 1 (Analog Input 3), (4) LVDT 2 (Analog Input 4), or (5) Ramp
1. If the PresetValue is chosen, the Pressure Limit Preset is used
as the pressure limit command.
Pressure Point 1 Source: The Pressure Point 1 Source selects the
source of the pressurefeedback for the program. Valid entries are
(1) Analog Input 1, (2) Analog Input 2, (3) LVDT 1(Analog Input 3),
(4) LVDT 2 (Analog Input 4), or (5) Ramp 1.
Program Output Destination: The Program Output Destination
selects the output of theprogram. Valid entries are (0) Pump
Controller or (1) Direct. If the Pump Controller is chosen,the
output of the Program will be the input to the Pump Controller
module. If Direct is chosen,the output of the Program will by-pass
the Pump Controller module and is passed directly to theservo
driver. Under most circumstances, the Pump Controller should be
chosen as the outputdestination.
KP and KI : KP and KI provide the proportional and integral
constants, respectively, for the PIcontrol algorithm. Both terms
are expressed as 0 to 100% of a maximum value. The PI controlloop
can be made a P-only control loop by setting the KI term to 0.
Likewise, the PI control loopcan be made an I-only control loop by
setting the KP term to 0.
EPC
P
U
P
U
Pressure P1 Pressure P2
Orifice
∆P = P1 - P2
Figure 17: Load Sense Circuit
-
ELECTRONIC 17
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Program Overview: The Load Sense Control Program is one of the
more complex controlalgorithms supplied with the EPC. The goal of
the load sense control is to maintain a pressuredifference across
an orifice (refer to Figure 17). Typically, two pressure
transducers would beused to monitor two points in the hydraulic
circuit. The pump flow would be controlled such that∆P = P1 -
P2.
In addition to this basic control, a pressure limiter is added
to ensure that the down-flow pressureat P2 does not reach a
critical point. The controller command is the sum of the Point 2
Pressureand Delta Pressure signals, limited by the Pressure Limit
Command. Comparing this commandwith the Point 1 Pressure signal
results in an error value. The error is multiplied by the KP andKI
constants to produce the Yp and Yi contributions to the program
output signal.
Figure 18: Load Sense Program
Example: Figure 18 shows the Program 5 form of the PC Interface.
The Delta Pressure Source isset to the Delta Pressure Preset Value
of 10% (menu 444=0 and menu 441=10). The PressurePoint 2 Source is
Analog Input 1 (menu 443=1), therefore the command is 2383 + 204 =
2587(all displays values are in DAC counts, refer to Section 5.1
for a discussion of the DiagnosticRepresentation of Numbers).
The Pressure Limit Source is set to the Pressure Limit Preset
Value of 50% (menu 445=0 andmenu 442=50). In this case, the
previous command value is not limited, since the command(2587) is
less than the Pressure limit command (3071).
The error signal is produced by comparing the Command to the
Pressure Point 1 signals: 2587 -2501 = 86. The Yi and Yp signals
are produced from the PI controller and the Program Output
isroughly equal to their sum: 2109 + 69 = 2178. The Program Output
is set to the Pump Controller(menu 447=0)
-
ELECTRONIC 18
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.2.6 Simple Flow Control Programs (46x, 47x)Menu Item Range
Description460 0 to 100 Program 7: Flow Command Preset461 0 to 5
Program 7: Flow Command Source464 0 to 1 Program 7: Program Output
Destination
470 0 to 100 Program 8: Flow Command Preset471 0 to 5 Program 8:
Flow Command Source474 0 to 1 Program 8: Program Output
Destination
Table 7: Simple Flow Programs Configuration
Function Programs 7 and 8 provide for Simple Flow Control.
Program 7 is configured in menuitems 460 through 464 or from the
Program 7 form of the PC Interface. Program 8 is configuredin menu
items 470 through 474 or from the Program 8 form of the PC
Interface.
Flow Command Preset: The Flow Command Preset allows for direct
numeric input for thecontrol program. The preset is configured as a
percentage, with 0% being equivalent to a 0VDCinput signal and 100%
being equivalent to a +10VDC signal.
Flow Command Source: The Flow Command Source selects the source
of the flow commandfor the program. Valid entries are (0) Preset
Value, (1) Analog Input 1, (2) Analog Input 2, (3)LVDT 1 (Analog
Input 3), (4) LVDT 2 (Analog Input 4), or (5) Ramp 1. If the Preset
Value ischosen, the Flow Command Preset is used as the flow
command.
Program Output Destination: The Program Output Destination
selects the output of theprogram. Valid entries are (0) Pump
Controller or (1) Direct. If the Pump Controller is chosen,the
output of the Program will be the input to the Pump Controller
module. If Direct is chosen,the output of the Program will by-pass
the Pump Controller module and passed directly to theservo driver.
Under most circumstances, the Pump Controller should be chosen as
the outputdestination.
Program Overview: The Simple Flow Control Program is by far the
least complex controlalgorithm. In fact in does little more than
transfer an analog or fixed input directly to the
PumpController.
Figure 19: Simple Flow Program
Example: Figure 19 shows the Program 7 form of the PC Interface.
The Flow Command Sourceis Analog Input 1 (menu 461=1). The Flow
Command Preset is set to 12% (menu 460=12)although the preset is
not used in this example. The Program Output is set to the
PumpController (menu 464=0).
-
ELECTRONIC 19
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.2.7 Advanced Flow with Pressure Limit Programs (48x, 49x)
Currently, the Advanced Flow with Pressure Limit Programs are
identical to the previouslymentioned Flow with Pressure Limit
Programs (refer to Section 4.2.4).
4.3 Pump Controller Configuration
4.3.1 Overview
The Pump Controller provides the basic functionality of the
module: to provide closed loopstroke feedback control for the servo
valve. In addition to stroke feedback, the Pump Controllermodule
can be configured for horsepower limitation.
Under usual circumstances, the pre-defined programs are used as
outer loop control while thePump Controller provides inner loop
control. The output of the pre-defined programs is verynearly
always passed through to the Pump Controller module (refer to
Section 4.2.1 for anoverview of the pre-defined Program
modules).
4.3.2 ConfigurationMenu Item Range Description800 0 to 5 Pump
Controller and HP Limiter:
Stroke Feedback Source801 0 to 100 Pump Controller:
Function Zero Stroke Command802 0 to 1 Pump Controller: Output
Polarity803 15 to 100 Pump Controller: Output Current Limit804 0 to
100 Pump Controller: KP805 0 to 100 Pump Controller: KI
810 0 to 100 HP Limiter: Reference811 0 to 5 HP Limiter:
Pressure Feedback Source812 HP Limiter: Spare813 0 to 100 HP
Limiter: KP814 0 to 100 HP Limiter: KI
Table 8: Pump Controller Configuration
4.3.2.1 Function Zero Stroke Command
Normally, the Active Program Block provides the command to the
Pump Controller. Forcertain applications, it might be desirable to
have the ability to switch between two functionprograms, and the
EPC provides that feature by allowing two program blocks selectable
bythe digital input.
In some circumstances, a second program is not needed but some
type of state is desired. Aprime example would be a stand-by mode
in which a fixed stroke would be commanded. In
-
ELECTRONIC 20
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
this circumstance, the user could place a pre-defined program in
block 1 and select program 0for block 2 (please refer to Section
4.1.3 regarding Program Block Configuration (21x)).
The Function Zero Stroke Command is configured by menu item 801
or from the PumpController form of the PC interface. It is
expressed as a value from 0 to 100%, where 0equals full negative
current, 100 equals full positive current, and 50 represents
neutral or nocurrent. A Function Zero Stroke Command of 75, for
instance, would provide a 50% strokecommand to the valve.
4.3.2.2 Stroke Controller
The Stroke Controller portion of the Pump Controller is
configured by selecting a StrokeFeedback Source (menu item 800) and
setting values for KP (menu 804) and KI (menu 805)for the Stroke PI
Controller. These values can be optimal adjusted from the Pump
Controllerform of the PC Interface.
Stroke Feedback Device: The Stroke Feedback Device determines
which signal thecommand to the Stroke Controller is compared to.
Valid entries are (0) Open Loop, (1)Analog Input 1, (2) Analog
Input 2, (3) LVDT 1 (Analog Input 3), (4) LVDT 2 (Analog Input4),
or (5) Ramp 1. If Open Loop is chosen, the stroke controller is
disabled and the commandis passed directly through to the
output.
KP and KI : KP and KI provide the proportional and integral
constants, respectively, for thePI control algorithm. Both terms
are expressed as 0 to 100% of a maximum value. The PIcontrol loop
can be made a P-only control loop by setting the KI term to 0.
Likewise, the PIcontrol loop can be made an I-only control loop by
setting the KP term to 0.
The command to the stroke controller is from either the Active
Program or the Function ZeroStroke Command (or by the HP-limited
adjustment of this command, please refer to Section4.3.2.3). An
error signal is produced by comparison of this command to the
stroke feedbacksignal. The PI loop produces Yp and Yi, determined
by the error signal and the KP and KIconstants, respectively. The
stroke controller output is made by the summation of Yp and Yi.The
Stroke Controller is disabled if the Stroke Feedback Source (menu
item 800) is selectedas 0 (Open Loop).
The Pump controller relies on the stroke feedback device being
configured correctly. Pleaserefer to Section 4.6.1 regarding the
LVDT Adjustment Algorithm.
4.3.2.3 HP Limiter
The HP Limiter can be configured to limit the command to the
stroke controller (refer toSection 4.3.2.2). This portion of the
Pump Controller is configured by selecting a StrokeFeedback Source
(menu item 800), Pressure Feedback Device (menu item 811) and
settingvalues for KP (menu 813) and KI (menu 814) for the HP
Limiter PI Controller. Additionally,a HP Limit Factor (menu item
810) must be entered (please refer to Section 4.6.2 regardingthe HP
Limit Factor Calculation). These values can be optimal adjusted
from the PumpController form of the PC Interface.
-
ELECTRONIC 21
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Stroke Feedback Source: The Stroke Feedback Source determines
which stroke signal isused in the HP calculation (this is the same
stroke feedback used in the Stroke Controller,refer to Section
4.3.2.2). Valid entries are (0) Open Loop, (1) Analog Input 1, (2)
AnalogInput 2, (3) LVDT 1 (Analog Input 3), (4) LVDT 2 (Analog
Input 4), or (5) Ramp 1. If OpenLoop is chosen, the stroke
controller is inactive, but the HP Limiter can be active, as long
asa Pressure Feedback Source is configured. In this case, the
module uses the pump controllercommand as the stroke feedback.
Pressure Feedback Source: The Pressure Feedback Source
determines which pressuresignal is used in the HP calculation.
Valid entries are (0) No HP Limit, (1) Analog Input 1,(2) Analog
Input 2, (3) LVDT 1 (Analog Input 3), (4) LVDT 2 (Analog Input 4),
or (5) Ramp1. If No HP Limit is chosen, the HP Limiter is inactive
and the pump controller commandwill be passed directly to the
stroke controller.
KP and KI : KP and KI provide the proportional and integral
constants, respectively, for thePI control algorithm. Both terms
are expressed as 0 to 100% of a maximum value. The PIcontrol loop
can be made a P-only control loop by setting the KI term to 0.
Likewise, the PIcontrol loop can be made an I-only control loop by
setting the KP term to 0.
The product of Pressure and Stroke signals is compared to the HP
Limit Factor (menu item810). If the product is greater than the
factor, the feedback HP is greater than the allowedHP, and the pump
controller command is adjusted through the Yp and Yi contributions
of theHP Limiter PI controller. The HP Limiter works only as a
limiter; the pump controllercommand is not manipulated if the HP
Limit Factor is greater than the calculated HP.
The HP Limiter relies on the HP Limit Factor being configured
correctly. Please refer toSection 4.6.2 regarding the HP Limit
Factor Calculation.
4.3.2.4 Output Polarity
Module Polarity is selected from menu item 802 or from the Pump
Controller form of the PCInterface. Polarity is either Normal (menu
802=0) or Inverted (menu 802=1).
4.3.2.5 Output Current Limit
The Module can be current limited to protect the valve or limit
stroke. The current limit isselected from menu item 803 or from the
Pump Controller form of the PC Interface and isexpressed as 0 to
100% of the maximum current of the module (200 or 250mA, depending
onthe part number).
Current is limited in each direction, so a Current Limit of 50%
will limit the current to -50%to +50% of the maximum.
-
ELECTRONIC 22
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.3.3 Configuration Example
Figure 20: Pump Controller Configuration
Figure 20 shows the PC Interface Diagnostic Screen for the Pump
Controller Module. TheDiagnostic screen shows that Program 3 is
active and passes the command of 3071 to the PumpController (all
display values are in DAC counts, refer to Section 5.1 for a
discussion of theDiagnostic Representation of Numbers). The
Function Zero Stroke is set to 50% (menu 801=50),so if no program
was active a neutral stroke would be the Pump Controller command
signal.
The Pressure Feedback Source is Analog Input 1 (menu 811=1) and
the Stroke Feedback Sourceis LVDT 1 (menu 800=3). The internal HP
calculation based on these pressure and stroke signalsresults in a
value of 671. The HP Limit Factor of 28% results in a value of 574
DAC counts, sothe actual HP is greater than the allowed HP. The
error signal is the difference of thesecalculated numbers (574 -
671 = -97) and the HP Limit is made up of the Yi and Yp
contributionscomputed from the HP Limiter PI controller.
The resulting Command with HP Limit is 3071 - 100 = 2971 DAC
counts. This command, alongwith the Stroke Feedback signal is
passed to the Stroke Controller, where the error signal is 2971-
3013 = -42. This error signal is used for the Stroke Controller PI
calculations, and the output isequal to the Yi and Yp contributions
(1843 - 667 = 1176).
Menu 802 is set to Invert the module output (menu 202=1) so the
1176 signal becomes 2918.Finally, the current is limited to 15% of
maximum, so the 2918 signal becomes 2367.
-
ELECTRONIC 23
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.4 Analog IO Configuration
The EPC module provides four analog inputs: Analog Inputs 1 and
2 are referred to as GeneralPurpose Analog Inputs and have a
maximum input range of -10VDC to +10VDC.
Analog Inputs 3 and 4 are usually referred to as LVDT Input 1
and 2, respectively. These inputs areintended for sinusoidal LVDT
input.
4.4.1 General Purpose Analog Input ConfigurationMenu Item Range
Description850 0 to 200 Analog Input 1: Offset851 1 to 32 Analog
Input 1: Gain852 0 to 1 Analog Input 1: Polarity853 0 to 1 Analog
Input 1: Current Fault Enable
860 0 to 200 Analog Input 2: Offset861 1 to 32 Analog Input 2:
Gain862 0 to 1 Analog Input 2: Polarity863 0 to 1 Analog Input 2:
Current Fault Enable
Table 9: General Purpose Analog Input Configuration
Menu items 850 through 853 are used to configure Analog Input 1
while menu items 860 through863 are used to configure Analog Input
2. Optimally, the Analog Inputs can be configured fromthe Analog
Input Configuration Form (select menu Diagnostics and then
Configuration) of thePC Interface.
Offset: A voltage offset can be applied to the Analog Input. The
voltage offset can be in therange of -10VDC to +10VDC at 0.1VDC
increments. The PC interface allows for the directentry of a
voltage offset, while valid menu entries are from 0 to 200 using
the following equation:
1.0
] (Volts)Offset Voltage [100] ENTRY MENU [ +=
Reversing the equation, the offset voltage can be determined
from the menu item by the equation:
( ) 1.0100- ] ENTRY MENU [ (Volts)Offset Voltage ×=The resulting
offset voltage is limited to the -10VDC to +10VDC range.
-
ELECTRONIC 24
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Gain: A limited gain factor can be applied to the Analog Input.
Values in the range of a 0.125attenuation to a ×4 gain at 0.125
increments are available. The PC interface allows for the
directentry of a gain, while the following table may be used to
configure the module directly throughthe display menu.
Menu Menu Menu MenuEntry Gain Entry Gain Entry Gain Entry Gain1
0.125 9 1.125 17 2.125 25 3.1252 0.250 10 1.250 18 2.250 26 3.2503
0.375 11 1.375 19 2.375 27 3.3754 0.500 12 1.500 20 2.500 28 3.5005
0.625 13 1.625 21 2.625 29 3.6256 0.750 14 1.750 22 2.750 30 3.7507
0.875 15 1.875 23 2.875 31 3.8758 1.000 16 2.000 24 3.000 32
4.000
Table 10: Analog Input Gain Settings
The resulting voltage is limited to the -10VDC to +10VDC
range.
Polarity : The Polarity setting is set to either Normal (0) or
Inverted (1). Inverting the input inthis way would be equivalent to
reversing wire leads to the module. In fact, a better long
termsolution to using the invert setting would be to reverse the
wire leads to the module.
Current Fault Enable: The Current Fault is set to either
Disabled (0) or Enabled (1) and isdesigned for use when a 4-to-20mA
input device is used. The EPC module has DIP switches thatcan be
set to place a 500Ω resistor in parallel to the analog input
terminal pins (refer to Section6.2 regarding Test Point,
DIP-Switch, and Pot Settings). If used, a 4-to-20mA input device
willresult in a voltage from +2VDC (4mA) to +10VDC (20mA) to the
module. If the Current Faultis enabled, the module will set a
System Message if this voltage falls below +1.5VDC(approximately
3mA).
The four configuration settings are used together to configure
the general purpose analog inputs.The order of
monitoring/configuration is:
(1) A Fault is reported if the Current Mode Fault is enabled and
the current supplied to themodule falls below 3mA.
(2) Offset Voltage by Offset Setting.(3) Multiply Voltage by
Gain Setting.(4) Invert Analog Input (if Polarity Invert set).
Example 1: A user wants a 4-20mA signal at Analog Input 1 to
control a bi-directional pump(command range of +/- 10VDC).
First the user would enable the current fault for Analog Input 1
(menu 853=1) and place theADC1 I/U DIP switch to the I (Current)
setting (refer to Section 6.2). This will create a +2VDCto +10VDC
voltage at the terminals and generate a fault if the voltage drops
below 1.5VDC (3mA).
-
ELECTRONIC 25
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Second, the user would set the Analog Input Offset to generate a
–6VDC offset. This creates a –4VDC to +4VDC voltage from the
original +2VDC to +10VDC voltage. The user would set thisdirectly
if using the PC interface. If entered through the on-board keypad
and display, the userwould convert the offset voltage to the menu
entry value:
40
-601001.0
6.0-100
1.0
] (Volts)Offset Voltage [100] 850 [
=+=
+=
+=
Next, the user would set the gain to 2.5. This creates a –10VDC
to +10VDC voltage from theoffset voltage of –4VDC to +4VDC. If
using the PC interface, the user selects 2.500 from thelist. If
entered from the menu, the user sets menu 851 to the setting from
Table 10. In this case,a menu entry of 20 corresponds to a 2.500
gain.
Finally, the user would set the input polarity to normal (menu
852=0), so the input is notinverted.
Example 2: A user wants a 0-5VDC signal at Analog Input 1 to
control a unidirectional pump(command range of 0 to +10VDC).
First the user would disable the current fault for Analog Input
1 (menu 853=0) and place theADC1 I/U DIP switch to the U (Voltage)
setting (refer to Section 6.2).
Second, the user would configure the input for 0VDC voltage
offset since the input voltage needsno offset for this particular
example. The offset is entered directly through the PC interface,
orthe menu entry is determined from the equation:
100
01001.0
0100
1.0
] (Volts)Offset Voltage [100] 850 [
=+=
+=
+=
Next, the user would set the gain to 2 to create a 0 to +10VDC
voltage from the offset voltage of0 to +5VDC. If using the PC
interface, the user selects 2.000 from the list. If entered from
themenu, the user sets menu 851 to the setting from Table 10. In
this case, a menu entry of 16corresponds to a 2.000 gain.
Finally, the user would set the input polarity to normal (menu
852=0), so the input is notinverted.
-
ELECTRONIC 26
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.4.2 LVDT/DCDT Fine-Adjustable Analog Input ConfigurationMenu
Item Range Description830 0 to 63 LVDT 1: Course Gain831 0 to 63
LVDT 1: Fine Gain832 0 to 1023 LVDT 1: Offset833 0 to 3 LVDT 1:
Offset (High Byte) For PC Interface
Menu Entry should not be Changed directly834 0 to 255 LVDT 1:
Offset (Low Byte) For PC Interface
Menu Entry should not be Changed directly835 0 to 1 LVDT 1:
Polarity
839 0 to 1 Pump Controller Adjustment Mode
840 0 to 63 LVDT 2: Course Gain841 0 to 63 LVDT 2: Fine Gain842
0 to 1023 LVDT 2: Offset843 0 to 3 LVDT 2: Offset (High Byte) For
PC Interface
Menu Entry should not be Changed directly844 0 to 255 LVDT 2:
Offset (Low Byte) For PC Interface
Menu Entry should not be Changed directly845 0 to 1 LVDT 2:
Polarity
849 SpareTable 11: LVDT/DCDT Input Configuration
Menu items 830 through 835 are used to configure LVDT 1 while
menu items 840 through 845are used to configure LVDT 2. Optimally,
the LVDT Inputs can be configured from the AnalogInput
Configuration Form (select menu Diagnostics and then Configuration)
of the PC Interface.
Menu item 839 allows the module to be placed in Pump Controller
Adjust Mode . This is aspecial operating mode designed for
adjustment of the LVDT inputs. Please refer to Section4.6.1 for a
thorough discussion of this adjustment mode.
Course and Fine Gains: Since greater resolution is needed to
scale and offset the input of thesinusoidal LVDT input signals, the
gain and offset are not done directly in the microcontroller,but
performed through electrical circuitry. Typically the Course Gain
increases over the range of0 to 63 and the Fine Gain decreases over
the range of 0 to 63. The LVDT or DCDT should beconfigured using
the algorithm discussed in Section 4.6.1.
Offset: The LVDT offset, like the course and fine gains,
manipulates hardware circuitry. Anoffset signal ranges from 0 to
1023. Note that the menu contains entries that are only used
inconjunction with the PC interface and should not be manipulated
directly by the user. Pleaserefer to Section 4.6.1 for a discussion
of the LVDT Adjustment Algorithm.
-
ELECTRONIC 27
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Polarity : The Polarity setting is set to either Normal (0) or
Inverted (1). Inverting the input inthis way would be equivalent to
reversing wire leads to the module. In fact, a better long
termsolution to using the invert setting would be to reverse the
wire leads to the module.
4.5 Ramp ConfigurationMenu Item Range Description870 0 to 4 Ramp
1: Source871 1 to 255 Ramp 1: Acceleration Rate872 1 to 255 Ramp 1:
Acceleration Step873 1 to 255 Ramp 1: Deceleration Rate874 1 to 255
Ramp 1: Deceleration Step
Table 12: Ramp Configuration
The EPC module provides one ramp module and is configured by
menu items 870 through 874.Optimally, the ramp can be configured
from the Advanced Configuration form (select Diagnosticsand then
Advanced) of the PC Interface.
Source: The Source selects the Analog Input used as the ramp
input. Valid entries are No Ramp (0),(1) Analog Input 1, (2) Analog
Input 2, (3) LVDT 1 (Analog Input 3), or (4) LVDT 2 (Analog
Input4). If No Ramp is selected, the ramp module will be disabled
and the ramp function will be equal to2048 DAC counts.
Rate and Step: The Ramp module provides different ramping rates
for acceleration and deceleration.Acceleration is defined as
increasing stroke, while Deceleration is defined as decreasing
stroke.Ramping from +5V to +10V is acceleration, while ramping from
+10V to +5V is deceleration.Ramping from -5V to -10V is also
acceleration, since -10V provides greater stroke than
-5V.Conversely, ramping from -10V to -5V is deceleration.
Since the EPC is a digital controller, the ramp is actually a
staircase-like signal. The Rate describesthe time length of each
step and is expressed in whole number multiples of the closed loop
updaterate. The Step describes the potential step at each interval
and is expressed as DAC counts.
Depending on the module, the closed loop response is either 1600
Hz or 1200 Hz. The Ramp Ratecan be expressed in Volts/second with
the equation
Rate
Step××= 004884.0] Response Loop Closed [(Volts/s) Rate Ramp
The larger the ramp rate or step is, the more course the ramp
stair casing will be. The time length ofeach step can be computed
from the Rate setting:
] Response Loop Closed [(seconds)Length Time
Rate=
The Potential Step can be computed from the Step setting:
004884.0(Volts) Step Potential ×= Step
-
ELECTRONIC 28
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Example 1: A Rate of 255 and a Step of 1 is used for a 1600 Hz
module. The Ramp Rate in Volts/second is
Ramp Rate = 1600 × 0.004884 × (1 / 255) = 0.03064 Volts/secondso
a 10 Volt step would ramp over a period of 326 seconds (5
minutes:26 seconds).
The same rate and step for a 1200 Hz module results in a
rampRamp Rate = 1200 × 0.004884 × (1 / 255 = 0.02298 Volts/secondso
a 10 Volt step would ramp over a period of 435 seconds (7
minutes:15 seconds).
The setting of Rate = 255 and Step = 1 results in the slowest
ramping rate.
Example 2: A Rate of 1 and a Step of 255 is used for a 1600 Hz
module. The Ramp Rate in Volts/second is
Ramp Rate = 1600 × 0.004884 × (255 / 1) = 1993 Volts/secondso a
10 Volt step would ramp in only 5 milliseconds.
The same rate and step for a 1200 Hz module results in a
rampRamp Rate = 1200 × 0.004884 × (255 / 1) = 1495 Volts/secondso a
10 Volt step would ramp in only 7 milliseconds.
The setting of Rate = 1 and Step = 255 results in the quickest
ramping rate.
A user should select a ramp rate that is close to a desired
value, while not producing an undesirablestep. Generally, the lower
the values for rate and step, the smaller the step.
Example 3: Which of the following are the optimal settings for a
0.5 Volt/second ramp?(a) Rate = 15, Step = 1(b) Rate = 31, Step =
2(c) Rate = 47, Step = 3(d) Rate = 125, Step = 8
Assuming a 1600 Hz closed loop response, the settings for (a)
result in:Ramp Rate = 1600 × 0.004884 × (1 / 15) = 0.5210
Volts/secondor a 1 × 0.004884 = 5mV step every 15/1600 = 9
milliseconds.
Similarly, the settings for (b), (c), and (d) result in(b) Ramp
Rate = 0.5042 Volts/second (10mV step every 19 milliseconds)(c)
Ramp Rate = 0.4988 Volts/second (15mV step every 29
milliseconds)(d) Ramp Rate = 0.5001 Volts/second (39mV step every
78 milliseconds)
The optimal setting depends on the ramp requirements and system
dynamics. If time is not critical,the settings for (a) which have
the smallest step size would be optimal. If time is critical and
thesystem dynamics allow for a larger step size, the settings in
(d) should be used since the ramping iscloser to the desired value
(0.5001 V/s rather than 0.5210 V/s).
Deductive reasoning can be used to find the rate and step values
for a desired ramp.
-
ELECTRONIC 29
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Example 4: What settings would be used to produce a 5-second
ramp for a 0 to 10 Volt stepcommand?
A 10 Volt / 5 second = 2 Volt/second ramp is desired. Since both
the Rate and Step have values from1 to 255, an arbitrary value of
10 is chosen for the Step and the Rate value is calculated:
Ramp Rate = [ Closed Loop Response ] × 0.004884 × Step /
RateRate = [ Closed Loop Response ] × 0.004884 × Step / [Ramp
Rate]
= 1600 × 0.004884 × ( 10 / 2 ) = 39
A step of 10 and rate of 39 make a 2.0037 Volt/second ramp (48
mV step every 24 milliseconds).Because 10/39 is approximately 1/4,
we would expect a step of 1 and a rate of 4 to be close to theramp
rate, yet provide a smaller staircase. Accordingly, a step of 1 and
a rate of 4 create a 1.95 Volt/second ramp, this time with a 5 mV
step every 0.6 milliseconds.
PC Interface: The PC interface contains a worksheet for ramp
values (Advanced Diagnostics form).The user selects a desired ramp
rate and one of five resolution factors. The worksheet
calculationfunction will display the results of the most optimal
settings.
4.6 Advanced Configuration
4.6.1 LVDT Adjustment Algorithm
Both the HP Limiter and Stroke Controller portions of the Pump
Controller module rely on theLVDT being configured correctly.
Typically, there are three (4) configuration parameters foreach
LVDT (Refer to Section 4.4.2 for a complete overview):n Polarityn
Offsetn Course Gainn Fine Gain
The general sequence of operations for LVDT scaling is ton Set
LVDT polarity to normal. The LVDT polarity toggle is intended for
short-term
diagnostics. The long-term solution to the LVDT inversion is to
swap wire leads into thecontroller (refer to Section 4.4.2).
n Place the EPC in Adjust mode.n Alternately Adjust the LVDT
Offset and Gains until configured.n Return EPC to normal operation
mode.
4.6.1.1 Adjustment Mode
The Pump Controller Adjustment Mode is a special operation mode
in which a Togglecommand controls the servo driver output rather
than the Pump Controller or Active functionblock.
-
ELECTRONIC 30
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
The Adjustment mode works optimally with Main pumps off and
Pilot Pumps pressurized.Adjustment mode is set by setting menu item
839 to 1, or by pressing the Adjust Modecommand button from the
Analog Input Configuration form of the PC interface.
Adjust mode is indicated by the PC interface noting a system
message and by the LCDDisplay on the front panel of the module
turning red.
The Adjust Mode Command Toggle is a special function available
in Adjustment mode thatwill alternately command full negative,
neutral, and full positive current to the driver. If inAdjustment
mode, the menu items for LVDT adjustment (refer to Section 4.4.2)
will show agraphic representation of the current toggle in the
upper right corner of the menu display.
The menu and graphic will appear as in Figure 21 when the toggle
is at maximum positivecurrent:
Figure 21
The menu and graphic will appear as in Figure 22 when the toggle
is at neutral (zero) current:
Figure 22
Finally, the menu and graphic will appear as in Figure 23 when
the toggle is at maximumnegative current:
Figure 23
Initially, the output toggle is at the neutral (zero) current
position. The toggle can be changedthrough the front keypad and
display by pressing the right cursor arrow key while in
therightmost position of the menu value for one of the LVDT
adjustment items. For example,pressing the right cursor key for the
display:
Figure 24
will toggle the Adjustment command from neutral to full positive
current:
Figure 25
If the user presses the right cursor key again, the Adjustment
command will change from fullpositive to full negative current:
Figure 26
-
ELECTRONIC 31
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
The Adjustment toggle command can be monitored from the PC
interface as well. TheConfiguration form of the PC interface has a
toggle command button. The display and bargraph indicator will show
the value of the toggle.
The PC interface admittedly makes the LVDT configuration easier
to work with thanworking directly with the front keypad and
display
4.6.1.2 Determining LVDT Configuration Range
The LVDT input should be scaled to match the range of stroke
command. The range ofstroke command is a factor of whether the pump
is designed for uni- or bi-directional flow.
Servo valves are commanded with current: a positive current
command will move the valvein one direction while a negative
current command will move the valve in the oppositedirection. A
neutral (zero) current command will remove command to the valve:
the valvemight stay in its current state, or it may move in either
direction.
For a uni-directional pump, only one port is available and the
stroke can supply 0 to 100%of the rated flow. The LVDT should be
configured so that the maximum positive togglecommand will produce
the equivalent of a +10VDC command for the LVDT input. Themaximum
negative toggle command should produce the equivalent of a 0 VDC
command atthe LVDT input. The range of 0 to +10VDC corresponds to
DAC values of 2048 to 4095, ora percentage of 0 to +100% (refer to
Section 5.1 for a discussion of the DiagnosticRepresentation of
Numbers).
For a uni-directional pump, the midpoint command is +5VDC (DAC
value of 3072 or +50%stroke).
For a bi-directional pump, two ports are available and the
stroke can supply 0 to 100% ofrated flow in each direction. Like
the uni-directional valve, the LVDT should be configuredso that the
maximum positive toggle command will produce the equivalent of a
+10VDCcommand for the LVDT input. The maximum negative toggle
command, however, shouldproduce the equivalent of a -10VDC command
for the LVDT input. The range of -10VDC to+10VDC corresponds to DAC
values of 0 to 4095, or a percentage of -100% to +100% (referto
Section 5.1 for a discussion of the Diagnostic Representation of
Numbers).
For a bi-directional pump, the midpoint command is 0VDC (DAC
value of 2048 or 0%stroke).
-
ELECTRONIC 32
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.6.1.3 Adjustment Algorithm
The following algorithm may be used to optimally configure the
unit. The PC Interfaceincludes a Microsoft Excel ™ template
(EPCConfig.xlt) that can be used to optimize thesetup. The Excel
template is also available through e-mail by request
[email protected].
1. Place the module in Adjustment mode (refer to Section
4.6.1.1).2. Use an Initial setting of Offset = 512, Course Gain =
0, and Fine Gain = 63.3. Toggle the Pump Command and note the LVDT
readings at the maximum positive
and negative toggle commands (refer to Section 4.6.1.1 regarding
toggle command).4. Determine the midpoint of these two LVDT
readings and compare with the desired
midpoint reading (see previous Section).5. Adjust the LVDT
offset so that the two LVDT readings have the desired midpoint
reading.6. Adjust the LVDT course gain upwards from the initial
setting such that the positive
and negative toggle commands produce LVDT signals as large as
possible withouteither toggle command producing an LVDT signal out
of the LVDT configurationrange..
7. Repeat steps 3 through 6 until a one-digit course gain change
is unable to produceLVDT signals within the configuration range.
For a uni-directional pump, a positivetoggle command should produce
an LVDT signal slightly less than +10VDC and anegative toggle
command should produce an LVDT signal slightly greater than0VDC.
For a bi-directional pump, a positive toggle command should produce
anLVDT signal slightly less than +10VDC and a negative toggle
command shouldproduce an LVDT signal slightly greater than
-10VDC.
8. Once the Course gain is found, adjust the fine gain downward
from the initial setup.Do not adjust the course gain and fine gain
concurrently since the two do notfunction together in a
straightforward linear fashion. Also note that while increasingthe
value of the course gain increases the overall LVDT signal gain,
the fine gainworks in the reverse direction.
9. Determine the midpoint of these two LVDT readings and compare
with the desiredmidpoint reading (see previous Section).
10. Adjust the LVDT offset so that the two LVDT readings have
the desired midpointreading.
11. Adjust the LVDT fine gain downward from the initial setting
until one of the twopump toggle commands is just under the pump
range.
12. Repeat steps 9 through 11 until a one digit fine gain change
produces LVDT signalsspanning the entire configuration range. For a
uni-directional pump, a positivetoggle command should produce an
LVDT signal of +10VDC and a negative togglecommand should produce
an LVDT signal of 0VDC. For a bi-directional pump, apositive toggle
command should produce an LVDT signal of +10VDC and a
negativetoggle command should produce an LVDT signal of -10VDC.
-
ELECTRONIC 33
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
Example 1: Balance an LVDT for a bi-directional pump (The
example can be followed fromthe Example 1 sheet of the Excel
template.)
Toggling with the initial values produces a low reading of
-92.50% and a high reading of -40.60%. These readings should be
offset to produce a low reading of -25.95% and a highreading of
+25.95%. This is calculated by finding the midpoint of the current
readings (-90.50 + -40.60)/2 = -66.55 and comparing that to the
desired midpoint (a bi-directional pumpshould have a midpoint at
0). Adding 65.55 to each value results in -90.50 + 65.55 =
-25.92and -40.60 + 66.55 = 25.95. This setting is reached when the
Balance is set to 411 (low andhigh readings of 25.90 and 26.20,
respectively). Notice that at this point approximate valuesare good
enough.
The user then attempts to adjust the gain to near saturation. At
a Course gain = 30 the lowreading is -91.60% while the high reading
is -9.20%. The next gain (31) actually saturatesthe low reading to
-100%, so 30 is used.
The user then attempts to offset the readings to low=-41.20% and
high=+41.20%. The userfinds this at Offset=334.
In a similar fashion, the user continues alternately selecting
offset and course gain values. Atstep 6, a change in course gain
saturates the low reading, so the user has successfully foundthe
optimal setting for course gain. The user continues as before, but
this time uses the finegain to set the near saturation gains.
At step seven the user finds that a fine gain change from 45 to
46 saturates both readings.LVDT configuration is complete.
Example 2: Balance an LVDT for a unit-directional pump. The only
difference between this andthe previous example would be that the
midpoint would be +50% rather than 0%. The user isinvited to view
the Example 2 sheet of the Excel template for this example.
-
ELECTRONIC 34
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
4.6.2 HP Limit Factor Calculation
Figure 27: PQ (HP) Limit Curve
The horsepower limit factor can be used to limit the power
consumed by the hydraulic pump. Tolimit horsepower, the user first
enters a value for the HP factor: this factor produces a
PQ(pressure-flow) curve that defines a certain horsepower region
(Figure 27). The user then sets thePump Controller module with the
proper settings for stroke and pressure feedback (see
Section4.3.2.3).
The horsepower limit factor can be determined in two ways:
experimentally or theoretically.
4.6.2.1 Experimental HP Limit Factor
For the Experimental HP Limit Factor, the user builds up
pressure and increases stroke untilthe motor supplies the maximum
rated current. This procedure requires a program thatallows for
direct stroke command, so a good function program to use would be
the SimpleFlow Program (refer to Section 4.2.6).
To determine the HP Limit Factor, the user must first configure
the EPC for stroke feedback(Section 4.4.2) and connect a pressure
transducer to an available analog input. An additionalanalog input
can be used for stroke command.
The user then sets the HP factor to an initial setting of 100%
and rigs the hydraulic circuit tobuild maximum pressure. Once this
achieved, the user uses a current transducer and
-
ELECTRONIC 35
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
multimeter to measure motor current. Stroke to the pump is
slowly increased, and themultimeter is monitored until the current
to the motor is at the maximum rated current. Atthis point, the
user notes the DAC reading for pressure and stroke.
The HP factor is determined by the formula:
( )( )( )( ) %10020462048
20482048 ×−−= DACDACfactorPQ
HP
The PC interface allows a one-touch solution from the Advanced
Configuration form. Theuser simply presses the HP Experiment
pushbutton once the maximum current is reached.
4.6.2.2 Theoretical HP Limit Factor
The HP limit factor can also be determined by the theoretical
formulas. For metric units thehorsepower factor is determined by
the equation:
η×××=NPD
PowerHP
XDCRMAXfactor
7100.6
wherePower is the motor rating in kWD
MAX is the maximum displacement of the Pump in ml/rev
PXDCR
is the maximum measured pressure in Bars(i.e., the pressure
corresponding to a 10VDC or 20mA reading)
N is the speed in rpmand η is the pump efficiency
The user may also use conventional English units:
η×××=NPD
PowerHP
XDCRMAXfactor
7100.4
wherePower is the motor rating in horsepowerD
MAX is the maximum displacement of the Pump in in3/rev
PXDCR
is the maximum measured pressure in PSI(i.e., the pressure
corresponding to a 10VDC or 20mA reading)
N is the speed in rpmand η is the pump efficiency
Example 1: What HP factor would be used for a PVG075 powered by
a 25 HP motorrotating at 1500 rpm. The EPC uses a 5000 PSI pressure
transducer to measure pressure.
From Oilgear Bulletin 47019, a PVG075 has a maximum displacement
of 4.60 in3/rev and anoverall efficiency of 80% at maximum
pressure. These values are used in the formula:
-
ELECTRONIC 36
Telephone:Fax:E-Mail:
(414) 327-1700(414) [email protected]
Oilgear Automation Systems2300 So. 51st. Street
Milwaukee, WI USA 53219
Issued: September 1999Bulletin 836100A
TECHNICAL DOCUMENT
EPCSERVO AMPLIFIER MODULE
Part Number L723888-xxx
( )( )( )23
80.01500500060.4
25100.4
100.4
7
7
=
×××=
×××= ηNPD
PowerHP
XDCRMAXfactor
Example 2: What HP factor would be used for a PVG100 powered by
a 50 kW motorrotating at 1500 rpm. The EPC uses a 400 Bar pressure
transducer to measure pressure.
From Oilgear Bulletin 47019, a PVG100 has a maximum displacement
of 98.3 ml/rev and anoverall efficiency of 85% at maximum pressure.
These values are used in the formula:
( )( )( )43
85.015004003.98
50100.6
100.6
7
7
=
×××=
×××= ηNPD
PowerHP
XDCRMAXfactor
Once again the PC interface provides an easier method. From the
Advanced Configurationform, the user enters each of the variables
in the desired system of units. Once this is done,the use presses
the HP Theory command button to create a new value for the HP
factor.
5 Module Diagnostics
The EPC has diagnostics available through both the On-Board
display/keypad and PC interface. Due tothe extensive features of
the controller, however, the PC interface is the recommended setup
anddiagnostic tool.
5.1 Diagnostic Representation of Numbers
Throughout this manual, reference has been made to DAC counts,
percentages, and voltages. DACcount representation is the basis for
all other diagnostic representation, since all internal numbers
arerepresented within the controller as DAC (Digital-to-Analog
Converter) counts.
5.1.1 DAC Counts
Most Diagnostic numbers are stored as a 12-Bit number from 0 to
4095. For an input or outputvariable, 0 DAC counts is equivalent to
-10VDC while 4095 DAC counts is equivalent to+10VDC. 2048 DAC
counts represents the midpoint of -10VDC