SHEET DRAWING DATE PROJECT PROJECT LICENSE NUMBER: ________ EXPIRATION DATE: __________ SEAL: ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS. (P) 410-344-1460 (F) 443-403-2460 (E) [email protected]WWW.MWSARCH.COM S T U D I O S 10839-D PHILADELPHIA RD WHITE MARSH, MD 21162 ARCHITECTURE + MASTER PLANNING 8/14/2018 1:09:44 PM BALTIMORE CITY ANIMAL SERVICES BUILDING 2490 GILES ROAD, BALTIMORE, 21225 NO. DESCRIPTION DATE 03-15-2019 17-023 100% CD I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE STATE OF MARYLAND. CONSULTANT: Engineering Infrastructure Solutions C.C. Johnson & Malhotra, P.C. 400 East Pratt Street, Suite 604 Baltimore, MD 21202 (P) 410-461-9920 | (F) (667)239-3534 | (E) [email protected]CCJM ELECTRICAL - NOTES, ABBREVIATIONS & LEGEND E001 FUSE , JUNCTION BOX CIRCUIT BREAKER SWITCH AND FUSE FUSED SWITCH GENERATOR MOTOR CONNECTION SAFETY SWITCH NONFUSED, SIZE AS INDICATED ELECTRICAL DEVICE AS INDICATED COMBINATION TYPE MOTOR STARTER, SIZE AS INDICATED SAFETY SWITCH FUSED, SIZE AS INDICATED DUPLEX RECEPTACLE 3 M WP RECEPTACLE WITH IN-USE BUBBLE COVER QUAD RECEPTACLE GFCI DUPLEX RECEPTACLE SPECIAL RECEPTACLE, SIZE AND TYPE AS NOTED , TS FS , , FIRE ALARM TAMPER SWITCH CONNECTION FIRE ALARM SYSTEM, VISUAL LIGHT/STROBE; WALL MTD (OR "C"-CEILING) FIRE ALARM SYSTEM FLOW SWITCH CONNECTION FIRE ALARM SYSTEM HEAT DETECTOR FIRE ALARM SYSTEM MANUAL PULL STATION FIRE ALARM SYSTEM SMOKE DETECTOR FIRE ALARM SYSTEM DUCT SMOKE DETECTOR DUPLEX RECEPTACLE FOR ELECTRIC WATER COOLER 480 VOLT PANELBOARD FIRE ALARM CONTROL PANEL FIRE ALARM ANNUNCIATOR PANEL FIXTURE SCHEDULE a 3 3 INDICATES CIRCUIT NUMBER 3 INDICATES CIRCUIT NUMBER A INDICATES TYPE OF LIGHTING FIXTURE REFER TO INDICATES SPECIAL / KEYED NOTE. UNLESS OTHERWISE A a 3 , 3 R-2,4 HOME RUN TO PANELBOARD UNLESS OTHERWISE NOTED. R INDICATES THE PANEL DISTRIBUTION EQUIPMENT AS INDICATED. 2,4 NUMBERS INDICATE SOPN NUMBER FOR PANEL DRAWING ON WHICH IT APPEARS. ELECTRICAL GENERAL NOTE APPLY TO ALL DRAWINGS, EGN-x NOTED, SPECIAL / KEYED NOTE APPLIES ONLY TO THE EGN-1 REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF CEILING MOUNTED LIGHTING FIXTURES, ETC. EGN-2 REFER TO MECHANICAL/PLUMBING DRAWINGS FOR EXACT LOCATIONS OF MECHANICAL/PLUMBING EQUIPMENT AND DEVICES. EGN-3 REFER TO ARCHITECTURAL DRAWINGS FOR BUILDING WALL, CEILING, FLOOR, ROOF AND OTHER TYPES OF CONSTRUCTION. EGN-4 UNLESS OTHERWISE NOTED, ALL WORK IN FINISHED OCCUPIED AREAS SHALL BE CONCEALED ABOVE CEILING, IN WALL AND/OR IN CHASES. EGN-5 ALL MATERIAL AND EQUIPMENT SHALL BE U.L. LISTED AS SUITABLE FOR THE LOCATION AND ENVIRONMENT FOR WHICH IT IS USED AND SHALL MEET OWNER'S FACILITY DESIGN STANDARDS. EGN-6 ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE 2014 EDITION OF NEC AND ALL OTHER APPLICABLE CODES. EGN-7 ALL EQUIPMENT AND WIRING THAT MAY REQUIRE SERVICING SHALL BE COMPLETELY ACCESSIBLE UPON COMPLETION OF PROJECT. JUNCTION BOXES AND PULL BOXES SHALL BE INSTALLED WHEREVER REQUIRED FOR A COMPLETE INSTALLATION OF BUILDING ELECTRICAL SYSTEMS. SIZE IN ACCORDANCE WITH NEC. EGN-8 BALANCE THE PANELBOARD LOADS ON EACH PHASE UNDER NORMAL OPERATING CONDITIONS, WITHIN 20% PLUS/MINUS TOLERANCE. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. CORRECTLY SPACE THE CIRCUITS IN THE PANEL AND BALANCE THE LOAD ON THE PHASES UNDER NORMAL OPERATING CONDITIONS. UPDATE ALL PANEL DIRECTORIES TO INCLUDE EXISTING AND NEW CIRCUITS INFORMATION. EGN-9 COORDINATE WITH ALL OTHER TRADES/CONTRACTORS FOR A COMPLETE INSTALLATION OF WORK. EGN-10 THOROUGHLY EXAMINE THE PREMISES AND OBSERVE ALL FIELD CONDITIONS UNDER WHICH THE WORK SHALL BE PERFORMED. VERIFY LOCATION AND DIMENSIONS OF ALL EQUIPMENT WITH OTHER TRADES AND OWNER, REQUIRING ELECTRICAL CONNECTIONS, BEFORE ANY ROUGH-IN. ANY DIFFICULTIES IN COMPLYING WITH THE DRAWINGS AND SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF ARCHITECT AND ENGINEER BEFORE BIDDING. EGN-11 PROVIDE GROUNDING CONNECTIONS FOR ALL ENCLOSURES, DEVICES AND EQUIPMENT PERMANENTLY AND EFFECTIVELY IN ACCORDANCE WITH NEC AND PROJECT SPECIFICATIONS. PROVIDE GROUNDING CONDUCTOR WITH EACH BRANCH CIRCUIT AND FEEDER. EGN-12 PROVIDE FIRE-STOPPING FOR EACH PENETRATION THROUGH FIRE RATED WALLS, FIRE RATED CEILINGS AND FIRE RATED FLOORS. EGN-13 UNLESS OTHERWISE NOTED, ALL WIRING CONDUCTORS SHALL BE COPPER, TYPE THWN/THHN INSULATION, RATED FOR 90 DEGREE C. AND IN METALLIC RACEWAYS. ARMORED CABLE WIRING SHALL NOT BE PERMITTED. REFER TO SPECIFICATIONS. EGN-14 DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO INDICATE THE GENERAL ARRANGEMENT. THEY ARE NOT INTENDED TO SHOW ALL DETAILS OF CONSTRUCTION OR EXACT LOCATIONS OF THE WORK. EGN-15 ALL OVERCURRENT PROTECTION DEVICES USED FOR MECHANICAL EQUIPMENT PROTECTION SHALL BE HACR RATED. CONTRACTOR SHALL VERIFY WIRE SIZES, CIRCUIT BREAKER AND FUSE RATINGS FOR ALL HVAC EQUIPMENT, AND BRING TO THE ATTENTION OF THE ARCHITECT/ ENGINEER ANY DISCREPANCIES AFFECTING THE WORK PRIOR TO PROCEEDING. EGN-16 THE CONTRACTOR SHALL RESTORE ALL AREAS AND SYSTEMS DISTURBED BY THEIR WORK TO ITS ORIGINAL CONDITIONS AND TO THE COMPLETE SATISFACTION OF ARCHITECT AND OWNER. EGN-17 VERIFY THAT ALL DOOR SWINGS ARE CORRECT BEFORE INSTALLING LIGHT SWITCH(ES). EGN-18 THE CORRECT NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS NECESSARY. PROVIDE ALL WIRES NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER INDICATED ON DRAWINGS OR NOT. NEUTRAL WIRES SHALL NOT BE SHARED. EGN-19 OPENINGS IN EXISTING BUILDING STRUCTURE FOR PASSAGE OF CONDUITS/CABLES SHALL NOT BE CUT UNTIL THE CONTRACTOR HAS ASKED FOR AND RECEIVED WRITTEN APPROVAL FROM THE OWNER. EGN-20 CONDUCTORS SHALL BE INSTALLED CONTINUOUS BETWEEN DEVICES, WITH SPLICES LOCATED ONLY IN JUNCTION BOXES OR IN CABINETS. CONDUCTORS SHALL BE OF SUFFICIENT LENGTH TO REACH THE FARTHEST TERMINAL IN PANELS. EGN-21 ALL RECEPTACLE/LIGHT SWITCH COVER PLATES SHALL BE LABELED WITH THE PANEL AND CIRCUIT NUMBER SERVING THE RECEPTACLE/LIGHT SWITCH. LETTERING SHALL BE A MINIMUM OF 1/8" IN HEIGHT. PROVIDE MACHINE PRINTED LABELS. HANDWRITTEN LABELS ARE NOT ALLOWED. EGN-22 NO POWER AND/OR SYSTEMS SHALL BE INTERRUPTED BY THE CONTRACTOR FOR ANY PURPOSE WITHOUT PRIOR WRITTEN APPROVAL OF THE OWNER. ALL OUTAGES SHALL COMPLY WITH THE OWNER'S REQUIREMENTS. RESTORE ALL EXISTING TO REMAIN EQUIPMENT, SYSTEMS, OR DEVICES IF INTERRUPTED BY DEMOLISHED CIRCUITS IN THE AREA. EGN-23 ALL EMPTY RACEWAYS SHALL HAVE PULL WIRE AND TERMINATED ABOVE CEILING AT AN ACCESSIBLE LOCATION WHERE INDICATED. EGN-24 FOR ELECTRICAL EQUIPMENT THAT MAY NEED EXAMINATION, ADJUSTMENT, SERVICING, OR MAINTENANCE WHILE ENERGIZED INCLUDING BUT NOT LIMITED TO PANELBOARDS, SPACE EQUAL TO THE WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT AND EXTENDING FROM THE FLOOR TO A STRUCTURAL CEILING, PLUS THE WORKING SPACE REQUIRED BY THE NEC, MUST BE DEDICATED TO THE ELECTRICAL INSTALLATION. NO PIPING, DUCTS, OR EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION MAY BE LOCATED IN THIS SPACE WITH THE EXCEPTION OF SUSPENDED CEILINGS WITH REMOVABLE PANELS. 208 VOLT PANELBOARD , E T UNDERGROUND COMMUNICATION LINES, AS NOTED TRANSFORMER, SIZE AS INDICATED UNDERGROUND ELECTRICAL LINES, AS NOTED CONDUIT, CONCEALED IN CEILING OR WALL OR CHASE , , LV LD TV SMOKE DETECTOR, SINGLE STATION GROUND ROD, COPPER WELD, 3/4" DIAMETER AND 10' LONG GROUNDING CABLE T DOWN CONDUCTOR WITH GROUND ROD LIGHTNING PROTECTION CABLE SYSTEM GROUND OR EQUIPMENT GROUND LP G RECEPTACLE WITH TOP OUTLET SWITCHED , WP GFI WC CROSS HATCH LINES INDICATE THE NUMBER OF CURRENT CARRYING CONDUCTORS CROSS HATCH LINES WITH DOT AT END INDICATES THE EQUIPMENT GROUNDING CONDUCTOR (GREEN WIRE) AND SHALL BE SIZED IN ACCORDANCE WITH NEC ARTICLE 250. GREEN GROUNDING WIRE SHALL BE PROVIDED WITH EACH CIRCUIT, AND/OR FEEDER. WHERE NO WIRES ARE INDICATED, PROVIDE 2 (TWO) CURRENT CARRYING # 12 AWG CONDUCTORS AND 1 (ONE) # 12 GROUND FOR BRANCH CIRCUIT WIRING IN MINIMUM 3/4" RACEWAY UNLESS OTHERWISE INDICATED IN THE SCHEDULES. SMOKE DETECTOR WITH HORN, SINGLE STATION a a INDICATES SWITCH LEG OR CONTROL ZONE FIRE ALARM SYSTEM HORN # # EQUIPMENT/DEVICE MOUNTING HEIGHT DUPLEX RECEPTACLE - CEILING , J J F OUTLET BOX FOR CARD READER CARD READER BY GC AND WIRING BY OWNER - PROVIDE OUTLET BOX WITH 1" RACEWAY, PULL WIRE AND TERMINATE AT AN ACCESSIBLE LOCATION 6" ABOVE CEILING DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS AND COVER PLATE WITH 1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE TWO (2) - 4 PAIR CAT 6 CABLE AND EXTEND TO NEAREST IT ROOM. OWNER WILL TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF, C = 9" ABOVE COUNTER MH TELEPHONE/DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS & COVER PLATE WITH 1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE: DATA - ONE (1) - 4 PAIR CAT 6 (BLACK) & VOICE - ONE (1) 4 PAIR CAT 5E (WHITE) CABLES AND EXTEND TO NEAREST IT ROOM. OWNER WILL TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF, C = 9" ABOVE COUNTER MH a INDICATES SWITCH LEG OR CONTROL ZONE USB WALL MOUNTED EMERGENCY LIGHTING L2 L3 FA1. PROVIDE FULL FIRE ALARM SYSTEM WITH MAIN FIRE ALARM CONTROL PANEL LOCATED IN IT ROOM OR AS DIRECTED BY OWNER (GAMEWELL FCI 7100 WITH SILENT KNIGHT 5129 4 CHANNEL COMMUNICATOR BY HONEYWELL). FA2. PROVIDE THE NEW FIRE ALARM SYSTEM FOR THE ENTIRE FACILITY TO COMPLY WITH NFPA 72, NFPA 70, AND TO MEET THE REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. FA3. MAINTAIN COMPLETE FIRE ALARM SYSTEM WITHIN AND ADJACENT OF WORK SPACES AS FULLY WORKING SYSTEM. FA4. THE CONTRACTOR SHALL BE RESPONSIBLE TO APPLY AND GET THE FIRE ALARM PERMIT FROM LOCAL AUTHORITY HAVING JURISDICTION. FA5. CONTRACTOR SHALL BE FULLY RESPONSIBLE TO PREPARE AND SUBMIT ALL DRAWINGS AND DOCUMENTATION AS REQUIRED BY LOCAL GOVERNMENT (AHJ) FOR FIRE ALARM SYSTEM PERMIT. ALL COSTS ASSOCIATED WITH PREPARING THE DRAWINGS AND OTHER DOCUMENTATION AND PERMIT FEES FOR PERMITS SHALL BE INCLUDED IN THE BASE BID. FA6. FACP SHALL HAVE MINIMUM 20% SPARE CAPACITY. PROVIDE BATTERY WITH SPARE CAPACITY, EXPANSION MODULES AND NOTIFICATION APPLIANCE CIRCUITS ACCORDINGLY. ALL COSTS OF ANY AND ALL FIRE ALARM SYSTEM FOR THIS PROJECT SHALL BE INCLUDED IN BASE BID. FA7. PROVIDE FIRE ALARM SYSTEM EQUIPMENT, DEVICES, ENGINEERING, PROGRAMMING, INSPECTIONS, AND TESTS FOR A FULLY WORKING SYSTEM ACCEPTABLE TO AHJ AND OWNER. FA8. ALL CIRCUITS SHALL BE CLASS A AND SHALL BE RUN IN MINIMUM 3/4" METAL RACEWAYS. LABEL EACH RACEWAY. ALL NEW RACEWAYS AND BACK BOXES SHALL BE CONCEALED. ANY SURFACE MOUNTED RACEWAYS SHALL BE PAINTED TO MATCH ADJACENT SURFACE. ALL NEW JUNCTION BOXES SHALL HAVE RED PAINTED COVER PLATES. ALL JUNCTION BOXES SHALL HAVE A PERMANENT, MACHINE PRINTED LABEL READING “FIRE ALARM CIRCUIT” ON THE INSIDE COVER. ALL FIRE ALARM CONDUIT SHALL BE RED OR MARKED WITH 3/4 INCH WIDE RED BANDS EVERY 10 FEET AND AT EACH SIDE OF FLOORS, WALLS, AND CEILINGS. FA9. ALL DRAWINGS ARE CONCEPTUAL IN NATURE. DRAWINGS DO NOT SHOW EXACT LOCATIONS OF COMPONENTS NOR DO THEY SHOW ALL REQUIRED COMPONENTS. PROVIDE ALL COMPONENTS NECESSARY FOR A PROPERLY INSTALLED, FULLY FUNCTIONAL SYSTEM IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS. FA10. DURING THE PROJECT MAINTAIN ALL FIRE ALARM SYSTEMS, CONDUIT, CIRCUITS, AND DEVICES IN OPERATIONAL CONDITION. DURING CONSTRUCTION, NO AREA OF THE BUILDING SHALL BE LEFT WITHOUT AN OPERATIONAL FIRE ALARM SYSTEM EXCEPT THE PROJECT AREAS. FA11. PROVIDE ANNUNCIATOR PANEL AND GRAPHICS TO REFLECT ALL COMPONENTS INCLUDING BUT NOT LIMITED TO NEW LED PILOT LIGHTS FOR WATER FLOW AND TAMPER SWITCHES. ELECTRICAL LEGEND NOTE: LEGENDS ARE GENERAL, NOT ALL SYMBOLS, ABBREVIATIONS, AND/OR DESIGNATIONS MAY APPEAR ON THE DRAWINGS. ANNOTATIONS AS/AF AMPERES SWITCH & FUSE RATING A, AMP AMPERES ABBREV ABBREVIATIONS AC ALTERNATING CURRENT, ARMORED CABLE ACU AIR CONDITIONING UNIT AF AMPERE FRAME AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AHU AIR HANDLING UNIT AIC AMPERE INTERRUPTING CAPACITY ATC AUTOMATIC TEMPERATURE CONTROL ATS AUTOMATIC TRANSFER SWITCH AUX AUXILIARY AWG AMERICAN WIRE GAUGE BES BLDG ELECTRICAL SYSTEM BIL BASIC IMPLUSE LEVEL BLDG BUILDING BKBD BACKBOARD BRKR BREAKER C CONDUIT CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CKT CIRCUIT CR CARD READER CL CURRENT LIMITING CLG CEILING CPT CONTROL POWER TRANSFORMER CT CURRENT TRANSFORMER CUH CABINET UNIT HEATER CW COOL WHITE DGS DIESEL GENERATOR SET DIA DIAMETER DISC DISCONNECT DIST DISTRIBUTION DN DOWN DP DISTRIBUTION PANEL DVR DIGITAL VIDEO RECORDER DWG DRAWING E, EMERGENCY EBH ELECTRIC BASEBOARD HEATER EC EMPTY CONDUIT ECB ENCLOSED CIRCUIT BREAKER EF EXHAUST FAN EGS ELECTRIC GENERATOR SET EH ELECTRIC HEATER ELECT ELECTRICAL EMT ELECTRICAL METALLIC TUBING ENCL ENCLOSURE EQUIP EQUIPMENT ER EXISTING RELOCATED ETR EXISTING-TO-REMAIN EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER EX EXISTING EXH EXHAUST F FUSED OR FUSIBLE FA FRAME AMPERE FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL FADS FIRE ALARM AND DETECTION SYSTEM FBO FURNISHED BY OTHERS FCU FAN COIL UNIT FDR FEEDER FL, FLOOR FLUOR FLUORESCENT FSS FUSED SAFETY SWITCH FT, FOOT OR FEET FVNR FULL VOLTAGE NON REVERSING GFCI GROUND FAULT CURRENT INTERRUPTER GND GROUND GN GENERAL NOTE GRS GALVANIZED RIGID STEEL GWB GYPSUM WALL BOARD GW GROUND WIRE HC HANDICAP HD HEAVY DUTY HID, HIGH INTENSIFY DISCHARGE HOA HAND-OFF-AUTOMATIC HP, HORSE POWER HPS HIGH PRESSURE SODIUM HTR HEATER HV HIGH VOLTAGE HVAC HEATING, VENTILATING AND AIR CONDITIONING HZ HERTZ IE THAT IS IMC INTERMEDIATE METAL CONDUIT JB JUNCTION BOX KCMIL THOUSAND CIRCULAR MILLS KV, KILOVOLT KVA KILOVOLT-AMPERE KW KILOWATT KWH KILOWATT-HOUR LA LIGHTNING ARRESTOR LS LIMIT SWITCH LTG LIGHTING LV LOW VOLTAGE MAX, MAXIMUM MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MCP MOTOR CIRCUIT PROTECTOR MH MOUNTING HEIGHT MIN, MINIMUM ABBREVIATIONS MDP MAIN DISTRIBUTION PANEL MTD MOUNTED MLO MAIN LUGS ONLY MTG MOUNTING MUX MULTIPLEXER N NEUTRAL NC NORMALLY CLOSED NEC NATIONAL ELECTRICAL CODE NIC NOT-IN-CONTRACT NL NIGHT LIGHT NO NORMALLY OPEN NTS NOT TO SCALE NFSS NON FUSED SAFETY SWITCH OC ON CENTER OH OVERHEAD OL OVERLOAD P POLE OR POLES PF POWER FACTOR PH PHASE VT POTENTIAL TRANSFORMER PL PILOT LIGHT PNL PANELBOARD PVC POLYVINYL CHLORIDE R REMOVE RAF RETURN AIR FAN RECEPTACLE REQD REQUIRED RGS RIGID GALVANIZED STEEL RMS ROOT MEAN SQUARE RS RAPID START RVAT REDUCED VOLTAGE AUTOTRANSFORMER S/N SOLID NEUTRAL SD SMOKE DETECTOR SEC SECONDARY SFA SPRINKLER FLOW ALARM SMR SURFACE METAL RACEWAY SPEC SPECIFICATION ST SHUNT TRIP SS SUB STATION STR STARTER SW SWITCH SWBD SWITCHBOARD SWGR SWITCHGEAR SYS SYSTEM SYM SYMMETRICAL SOPN SPACE OR POLE NUMBER TA TRIP AMPERE TB TERMINAL BOX TC TIME CLOCK TD TIME DELAY TTB TELEPHONE TERMINAL BOARD/BLOCK TTC TELEPHONE TERMINAL CLOSET TYP TYPICAL TV TELEVISION UC UNDER COUNTER UG UNDERGROUND UH UNIT HEATER UOI UNLESS OTHERWISE INDICATED UON UNLESS OTHERWISE NOTED UL UNDERWRITER'S LABORATORY USB UNIVERSAL SERIAL BUS V VOLT (S) OR VOLTAGE VA VOLT AMPERE VFD VARIABLE FREQUENCY DRIVE W WIRE W/ WITH WP WEATHER PROOF, WORK PHONE WW WIREWAY XFMR TRANSFORMER PH PHASE ɸ # NUMBER C CENTER LINE @ AT # MOUNTING HEIGHTS SWITCHES, 48" RECEPTACLE-GENERAL 18" RECEPTACLE-SPECIAL 18" RECEPTACLE-SINGLE 18" RECEPTACLE-REST ROOM 9" ABOVE BASIN RECEPTACLE-COUNTER 8" ABOVE COUNTER RECEPTACLE- MONITOR (DISPLAY) 78" OR DIRECTED BY OWNER IN FIELD RECEPTACLE-EXTERIOR 30" CABLE TV OUTLET 78" UON TELEPHONE/DATA-GENERAL 18" TELEPHONE-WALL TYPE 54", (48" FOR ADA ACCESSIBLE) FIRE ALARM PULL STATION 48" FIRE ALARM AUDIO/VISUAL DEVICE 80" CARD READER 40" EXIT LIGHT WALL MOUNTED, 90" OR 12" ABOVE DOOR EXIT LIGHT CEILING MOUNTED 96" AFF SAFETY SWITCH, VFD, STARTER 72" TO HANDLE ENCLOSED CIRCUIT BREAKER 72" TO HANDLE PANELBOARD 72" TO TOP CB MANUAL MOTOR STARTER 48" PUSH BUTTON, 48" AUTOMATIC DOOR OPENER 36" EMERGENCY BATTERY UNIT - WALL 18" BELOW CEILING OR 8' AFF EXIT SIGN - WALL 6" ABOVE DOOR JAMB ,NO HIGHER THAN 8' AFF CONTACTOR 5' AFF DISCONNECT SWITCH 5' AFF PANELBOARD (6' TALL) TOP TRIM 6' AFF, OR FROM BOTTOM 6" AFF MOTION SENSOR - WALL 8' AFF OR MANUFACTURER SPECIFICATION CAMERA - WALL 7'-6" AFF INTERCOM STATION 48" AFF MONITOR - WALL 7'-6" AFF FIRE SYSTEM GENERAL NOTES LIGHTING SYMBOLS LED LIGHTING FIXTURE LED LIGHTING FIXTURE WITH BATTERY BACKUP WALL MOUNTED FIXTURE INDUSTRIAL TYPE LED FIXTURE INDUSTRIAL TYPE LED FIXTURE WITH BATTERY BACKUP CEILING MOUNTED DOWN LIGHT; NORMAL , WITH BATTERY BACKUP WALL MOUNTED LIGHTING FIXTURE WALL WASH/DOWN LIGHT, CEILING MOUNTED COVE FIXTURE. LENGTH AS SHOWN ON DRAWINGS TRACK LIGHT WITH FIXTURE FIRE ALARM SYMBOLS FIRE ALARM SYSTEM INDIVIDUAL HORN AND STROBE LIGHT EXIT LIGHT BACK MOUNTED & w/ DIRECTIONAL CHEVRON AS INDICATED LIGHTING / POWER CONTROLS SYMBOLS OS VS PS PP SINGLE POLE SWITCH THREE WAY SWITCH DOUBLE POLE DISCONNECT LOW VOLTAGE SWITCH LOW VOLTAGE DIMMER TWO BUTTON ENTRY ROOM CONTROL STATION (LIGHTING) THREE BUTTON ENTRY ROOM CONTROL STATION (LIGHTING) OCCUPANCY SENSOR CEILING, WALL VACANCY SENSOR PHOTO SENSOR POWER PACK TELEPHONE/DATA SYMBOLS POWER SYMBOLS C DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER ABOVE BACKSPLASH DUPLEX RECEPTACLE WITH (2) UNIVERSAL SERIAL BUS PORTS CONDUIT CONCEALED IN FLOOR OR UNDERFLOOR OR UNDERGROUND ELECTRICAL GENERAL NOTES # FIRE ALARM BELL # FIRE ALARM BELL AND STROBE FIRE ALARM SYSTEM COMBINATION HORN AND STROBE LIGHT ASSEMBLY FIRE ALARM SYSTEM CARBON MONOXIDE DETECTOR, M.H. 54" AFF FIRE ALARM - MAGNETIC DOOR HOLDER CO M METER 1. UNLESS INDICATED OTHERWISE ON THE PLANS OR AS DIRECTED BY THE OWNER, CENTERLINE OF DEVICE SHALL BE AS INDICATED ABOVE. 2. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED, THE CONTRACTOR SHALL INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT TO PROVIDE THE MAXIMUM HEADROOM POSSIBLE AND COMPLY WITH THE REQUIREMENTS OF EQUIPMENT MANUFACTURER, APPLICABLE CODES AND STANDARDS, AND AHJ REQUIREMENTS. WHERE EQUIPMENT IS INTENDED, SPECIFIED, OR NOTED TO BE MOUNTED OTHER THEN INDICATED ABOVE, MOUNT IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND AS DIRECTED. NOT ALL EQUIPMENT INDICATED WITH MOUNTING HEIGHTS ARE SHOWN ON THESE CONTRACT DOCUMENTS. 3. COORDINATE EXACT LOCATIONS AND MOUNTING HEIGHTS IN THE FIELD BEFORE ANY CORE DRILLING, CUTTING, AND ROUGH-INS. G FLR WALL FLOOR MOUNTED TELEPHONE/DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS & COVER PLATE WITH 1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE PROVIDE: DATA - ONE (1) - 4 PAIR CAT 6 (BLACK) & VOICE - ONE (1) 4 PAIR CAT 5E (WHITE) CABLES AND EXTEND TO NEAREST IT ROOM. OWNER WILL TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF CR C PA C SECURITY SYSTEM SYMBOLS SA UNDER-COUNTER (SILENT 911 ALARM), FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET BOX WITH 1" RACEWAY, PULL WIRE FROM 6" ABOVE ACCESSIBLE CEILING TO LOCATION UNDERNEATH DESK. PANIC ALARM BUTTON, FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET BOX WITH 1" RACEWAY AND PULL WIRE AND TERMINATE AT AN ACCESSIBLE LOCATION 6" ABOVE CEILING PANIC ALARM STROBE, FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET BOX WITH 1" RACEWAY AND PULL WIRE AND TERMINATE AT AN ACCESSIBLE LOCATION 6" ABOVE CEILING CEILING MOUNTED SECURITY CAMERA BY OWNER - PROVIDE JUNCTION BOX WITH 1" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. WALL MOUNTED SECURITY CAMERA BY OWNER - PROVIDE JUNCTION BOX WITH 1" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. PROVIDE 1-1/2" SLEEVE THROUGH THE WALL FOR LOW VOLTAGE WIRING. OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 60" AFF AND COORDINATED WITH ASSOCIATED RECEPTACLE DESIGNATED FOR TV. PROVIDE OUTLET BOX AND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED: * FUTURE COAX CONNECTION. PROVIDE 1" RACEWAY WITH PULL WIRE TO 6" ABOVE CONCEALED, ACCESSIBLE CEILING * (2) RJ-45 JACKS. PROVIDE 1-1/4" RACEWAY AND PULL STRING TO 6" ABOVE CONCEALED, ACCESSIBLE CEILING. DL DAYLIGHT SENSOR PL PLUG LOAD CONTROLLER OS N CAT 5 CABLE (LIGHTING) WS1. WS2. WS3. PROVIDE 4 CIRCUIT FMC TO HARD-WIRED JUNCTION BOX/POWER IN-FEED. WS4. WS5. WS6. WS7. WS8. WS9. WS10. WORKSTATION NOTES FOR WALL FED POWER SOURCE, SURFACE OR FLUSH MOUNT JUNCTION BOX(S) AS CLOSE AS POSSIBLE TO THE FURNITURE'S POWER IN-FEED. POWER IN-FEED CORD AND CAP FURNISHED BY FURNITURE MANUFACTURE AND INSTALLED BY CONTRACTOR. FOR PROTECTION FROM DAMAGE, STRAP/SECURE IN-FEED CORD FIRMLY TO WALL AND FURNITURE AS DIRECTED BY THE FURNITURE MANUFACTURER. FOR WALL FED VOICE/DATA SERVICES, SURFACE OR FLUSH MOUNT JUNCTION BOX(S) AS CLOSE AS POSSIBLE TO THE FURNITURE'S BASE IN-FEED. PROVIDE GROMMET IN COVER PLATE TO PROTECT CABLES FROM DAMAGE. ROUTE CABLE THROUGH BASE OF WORKSTATION FURNITURE VIA HORIZONTAL CABLE SUPPORTS FURNISHED BY FURNITURE MANUFACTURER AND INSTALLED BY CONTRACTOR. CONCEAL CABLE IN FURNITURE. FOR VERTICAL STRAIN-RELIEF, FASTEN CABLE TO THE FURNITURE'S STRUCTURAL MEMBERS. THE WORKSTATION ELECTRICAL SYSTEM TO BE PROVIDED WILL UTILIZE A 3 UTILITY, 1 ISOLATED CIRCUIT, 8 WIRE SYSTEM WITH A COMMON (4) #12 LINE (2) #10 NEUTRAL AND (2) #12 GROUND. AT THE POINT OF TERMINATION FOR THE POWER IN-FEED CABLE, THE CONTRACTOR SHALL COMBINE THE NEUTRALS AND GROUNDS AS DIRECTED BY THE FURNITURE MANUFACTURER. PRIOR TO THE POINT OF TERMINATION, THE NEUTRALS AND GROUND SHALL REMAIN DEDICATED TO THE SPECIFIC CIRCUIT. FIRMLY ATTACH POWER IN-FEED CABLE AND FMC TO WALL JUNCTION BOX COVER VIA UL LISTED FITTINGS/CONNECTORS WITH INSULATED THROATS. DUPLEX RECEPTACLES WILL BE FURNISHED AND INSTALLED BY THE FURNITURE MANUFACTURER. VOICE/DATA CABLE AND OUTLETS PROVIDED IN BASE PATHWAY BY CONTRACTOR. INSTALL OUTLETS IN FURNITURE KNOCKOUTS IN THE LOCATION AS DIRECTED BY THE OWNER. PROVIDE 3 DATA AND 1 VOICE PORT PER OUTLET FOR EVERY SEAT AS SHOWN ON THE FURNITURE LAYOUT DRAWINGS. FURNITURE SHALL BE PROVIDED WITH METALLIC SEPARATION BETWEEN POWER WIRING AND VOICE/DATA CABLES. ALL JUNCTION BOXES SHALL BE MADE READILY ACCESSIBLE INCLUDING HARDWIRED JUNCTION BOXES FURNISHED BY THE MANUFACTURER. ALL POWER AND VOICE/DATA CABLING WORK WILL BE PERFORMED BY THE SYSTEM FURNITURE QUALIFIED INSTALLER. THE FURNITURE VENDOR WILL FURNISH AND INSTALL POWER IN-FEEDS (OR BASE FEEDS) AND RECEPTACLES (POWER OUTLETS). RECEPTACLES WILL BE CORCUITED/CONNECTED BY THE FURNITURE VENDOR AS SHOWN ON THE FLOOR PLANS WITH THE FINAL POWER IN-FEED SERVICE CONNECTION BY THIS CONTRACT. DATA AND VOICE PORTS (OUTLET JACKS) INCLUDING CABLING AND FINAL TERMINATIONS IN THE FURNITURE SHALL BE PROVIDED BY THE CONTRACTOR. CABLE COVER WILL BE FURNISHED AND INSTALLED BY MANUFACTURER / FURNITURE VENDOR. COORDINATE ROUTING OF CABLES WITH FURNITURE INSTALLER BEFORE PROCEEDING WITH ANY ROUGH-IN WORK. SEE FLOOR PLAN(S) FOR FURNITURE POWER AND VOICE/DATA SERVICE LOCATIONS. VERIFY LOCATION OF FURNITURE POWER IN-FEED POINT OF TERMINATION WITH THE WORKSTATION MANUFACTURER / FURNITURE VENDOR BEFORE PROCEEDING WITH ANY ROUGH-IN WORK. PROVIDE QUANTITY OF JUNCTION BOXES AS NECESSARY TO ACCOMMODATE THE POWER AND VOICE/DATA WIRING/CABLING NEEDS OF THE FURNITURE. NOT ALL SERVICE FEEDS/LOCATIONS MAY BE SHOWN. TO ACCOMMODATE CHANGES IN THE FINAL FURNITURE LAYOUT, INCREASE THE NUMBER OF SERVICE LOCATIONS SHOWN ON THE FLOOR PLANS BY ADDITIONAL 25 PERCENT. LIGHTNING PROTECTION CABLE LP POWER PACK PUSH PLATE FOR HANDICAPPED ACCESS DOOR PB PC PHOTOCELL PP REMOTE DIGITAL FIRE ALARM TRANSMITTER 110 110 THE NUMBER ADJACENT TO THE SYMBOL INDICATES PREFERRED CANDELA VALUE. STROBE SYMBOL WITHOUT IDENTIFICATION SHALL BE AS FOLLOWS: CORRIDORS/HALLWAYS - 30 CANDELA, ROOMS <= 2,000 SQFT - 75 CANDELA, ROOMS > 2,000 SQFT - 110 CANDELA. , , TV OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 60" AFF AND COORDINATED WITH ASSOCIATED RECEPTACLE DESIGNATED FOR TV. PROVIDE OUTLET BOX AND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED: * FUTURE COAX CONNECTION. PROVIDE 1" RACEWAY WITH PULL WIRE TO 6" ABOVE CONCEALED, ACCESSIBLE CEILING * (2) RJ-45 JACKS. PROVIDE 1-1/4" RACEWAY AND PULL STRING TO 6" ABOVE CONCEALED, ACCESSIBLE CEILING. * (2) HDMI OUTPUT. PROVIDE CABLING IN 1-1/4" RACEWAY TO CORRESPONDING HDMI INPUTS W TV OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 6" ABOVE COUNTER. COORDINATE EXACT LOCATION WITH OWNER. PROVIDE OUTLET AND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED: * - (1) HDMI INPUT. PROVIDE CABLING TO WALL MOUNTED WALL PLATE IN SAME ROOM. C TV FLOOR BOX MOUNTED CONNECTIONS TO HDTV AT MEETING ROOM. COORDINATE EXACT LOCATION WITH TELECOM FLOOR BOX AT SAME ROOM AND OWNER. PROVIDE OUTLET AND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED: * (1) HDMI INPUT. PROVIDE CABLING TO WALL MOUNTED WALL PLATE IN SAME ROOM. F DATA OUTLET FOR SYSTEMS FURNITURE, BY OTHERS. SIZE JUNCTION BOX FOR SYSTEM FURNITURE FOR THE QUANTITY OF DEVICES AS SHOWN. COORDINATE ALL WORK WITH OWNER AND SYSTEMS FURNITURE SUPPLIER. F QUAD RECEPTACLE - C = 9" ABOVE COUNTER C
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
SHEET
DRAWING
DATE
PROJECT
PROJECT
LICENSE NUMBER: ________
EXPIRATION DATE: __________
SE
AL
:
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY
BREAKER AND FUSE RATINGS FOR ALL HVAC EQUIPMENT, AND BRING TO THE ATTENTION
OF THE ARCHITECT/ ENGINEER ANY DISCREPANCIES AFFECTING THE WORK PRIOR TO
PROCEEDING.
EGN-16 THE CONTRACTOR SHALL RESTORE ALL AREAS AND SYSTEMS DISTURBED BY THEIR
WORK TO ITS ORIGINAL CONDITIONS AND TO THE COMPLETE SATISFACTION OF
ARCHITECT AND OWNER.
EGN-17 VERIFY THAT ALL DOOR SWINGS ARE CORRECT BEFORE INSTALLING LIGHT SWITCH(ES).
EGN-18 THE CORRECT NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY
THOSE WHERE CLARIFICATION IS NECESSARY. PROVIDE ALL WIRES NECESSARY FOR THE
PROPER FUNCTION OF THE SYSTEM WHETHER INDICATED ON DRAWINGS OR NOT.
NEUTRAL WIRES SHALL NOT BE SHARED.
EGN-19 OPENINGS IN EXISTING BUILDING STRUCTURE FOR PASSAGE OF CONDUITS/CABLES
SHALL NOT BE CUT UNTIL THE CONTRACTOR HAS ASKED FOR AND RECEIVED WRITTEN
APPROVAL FROM THE OWNER.
EGN-20 CONDUCTORS SHALL BE INSTALLED CONTINUOUS BETWEEN DEVICES, WITH SPLICES
LOCATED ONLY IN JUNCTION BOXES OR IN CABINETS. CONDUCTORS SHALL BE OF
SUFFICIENT LENGTH TO REACH THE FARTHEST TERMINAL IN PANELS.
EGN-21 ALL RECEPTACLE/LIGHT SWITCH COVER PLATES SHALL BE LABELED WITH THE PANEL AND
CIRCUIT NUMBER SERVING THE RECEPTACLE/LIGHT SWITCH. LETTERING SHALL BE A
MINIMUM OF 1/8" IN HEIGHT. PROVIDE MACHINE PRINTED LABELS. HANDWRITTEN LABELS
ARE NOT ALLOWED.
EGN-22 NO POWER AND/OR SYSTEMS SHALL BE INTERRUPTED BY THE CONTRACTOR FOR ANY
PURPOSE WITHOUT PRIOR WRITTEN APPROVAL OF THE OWNER. ALL OUTAGES SHALL
COMPLY WITH THE OWNER'S REQUIREMENTS. RESTORE ALL EXISTING TO REMAIN
EQUIPMENT, SYSTEMS, OR DEVICES IF INTERRUPTED BY DEMOLISHED CIRCUITS IN THE
AREA.
EGN-23 ALL EMPTY RACEWAYS SHALL HAVE PULL WIRE AND TERMINATED ABOVE CEILING AT AN
ACCESSIBLE LOCATION WHERE INDICATED.
EGN-24 FOR ELECTRICAL EQUIPMENT THAT MAY NEED EXAMINATION, ADJUSTMENT, SERVICING,
OR MAINTENANCE WHILE ENERGIZED INCLUDING BUT NOT LIMITED TO PANELBOARDS,
SPACE EQUAL TO THE WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT AND
EXTENDING FROM THE FLOOR TO A STRUCTURAL CEILING, PLUS THE WORKING SPACE
REQUIRED BY THE NEC, MUST BE DEDICATED TO THE ELECTRICAL INSTALLATION. NO
PIPING, DUCTS, OR EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION MAY BE
LOCATED IN THIS SPACE WITH THE EXCEPTION OF SUSPENDED CEILINGS WITH
REMOVABLE PANELS.
208 VOLT PANELBOARD
,
E
T UNDERGROUND COMMUNICATION LINES, AS NOTED
TRANSFORMER, SIZE AS INDICATED
UNDERGROUND ELECTRICAL LINES, AS NOTED
CONDUIT, CONCEALED IN CEILING OR WALL OR CHASE
,
,
LV
LD
TV
SMOKE DETECTOR, SINGLE STATION
GROUND ROD, COPPER WELD, 3/4" DIAMETER AND 10' LONG
GROUNDING CABLE
T
DOWN CONDUCTOR WITH GROUND ROD
LIGHTNING PROTECTION CABLE
SYSTEM GROUND OR EQUIPMENT GROUND
LP
G
RECEPTACLE WITH TOP OUTLET SWITCHED
,
WP
GFI
WC
CROSS HATCH LINES INDICATE THE NUMBER OF CURRENT
CARRYING CONDUCTORS CROSS HATCH LINES WITH DOT AT END
INDICATES THE EQUIPMENT GROUNDING CONDUCTOR (GREEN
WIRE) AND SHALL BE SIZED IN ACCORDANCE WITH NEC ARTICLE
250. GREEN GROUNDING WIRE SHALL BE PROVIDED WITH EACH
CIRCUIT, AND/OR FEEDER. WHERE NO WIRES ARE INDICATED,
PROVIDE 2 (TWO) CURRENT CARRYING # 12 AWG CONDUCTORS
AND 1 (ONE) # 12 GROUND FOR BRANCH CIRCUIT WIRING IN
MINIMUM 3/4" RACEWAY UNLESS OTHERWISE INDICATED IN THE
SCHEDULES.
SMOKE DETECTOR WITH HORN, SINGLE STATION
a
a INDICATES SWITCH LEG OR CONTROL ZONE
FIRE ALARM SYSTEM HORN
# #
EQUIPMENT/DEVICE
MOUNTING HEIGHT
DUPLEX RECEPTACLE - CEILING
,
JJ
F
OUTLET BOX FOR CARD READER CARD READER BY GC AND WIRING BY OWNER -
PROVIDE OUTLET BOX WITH 1" RACEWAY, PULL WIRE AND TERMINATE AT AN
ACCESSIBLE LOCATION 6" ABOVE CEILING
DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS AND COVER PLATE WITH
1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE
TWO (2) - 4 PAIR CAT 6 CABLE AND EXTEND TO NEAREST IT ROOM. OWNER WILL
TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF, C = 9" ABOVE COUNTER MH
TELEPHONE/DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS & COVER PLATE WITH1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILL PROVIDE: DATA -ONE (1) - 4 PAIR CAT 6 (BLACK) & VOICE - ONE (1) 4 PAIR CAT 5E (WHITE) CABLES AND EXTEND TONEAREST IT ROOM. OWNER WILL TERMINATE CABLES ON BOTH ENDS. MH = 18" AFF, C = 9"ABOVE COUNTER MH
a INDICATES SWITCH LEG OR CONTROL ZONE
USB
WALL MOUNTED EMERGENCY LIGHTING
L2
L3
FA1. PROVIDE FULL FIRE ALARM SYSTEM WITH MAIN FIRE ALARM CONTROL PANEL LOCATED IN IT
ROOM OR AS DIRECTED BY OWNER (GAMEWELL FCI 7100 WITH SILENT KNIGHT 5129 4
CHANNEL COMMUNICATOR BY HONEYWELL).
FA2. PROVIDE THE NEW FIRE ALARM SYSTEM FOR THE ENTIRE FACILITY TO COMPLY WITH NFPA
72, NFPA 70, AND TO MEET THE REQUIREMENTS OF THE AUTHORITIES HAVING
JURISDICTION.
FA3. MAINTAIN COMPLETE FIRE ALARM SYSTEM WITHIN AND ADJACENT OF WORK SPACES AS
FULLY WORKING SYSTEM.
FA4. THE CONTRACTOR SHALL BE RESPONSIBLE TO APPLY AND GET THE FIRE ALARM PERMIT
FROM LOCAL AUTHORITY HAVING JURISDICTION.
FA5. CONTRACTOR SHALL BE FULLY RESPONSIBLE TO PREPARE AND SUBMIT ALL DRAWINGS AND
DOCUMENTATION AS REQUIRED BY LOCAL GOVERNMENT (AHJ) FOR FIRE ALARM SYSTEM
PERMIT. ALL COSTS ASSOCIATED WITH PREPARING THE DRAWINGS AND OTHER
DOCUMENTATION AND PERMIT FEES FOR PERMITS SHALL BE INCLUDED IN THE BASE BID.
FA6. FACP SHALL HAVE MINIMUM 20% SPARE CAPACITY. PROVIDE BATTERY WITH SPARE
CAPACITY, EXPANSION MODULES AND NOTIFICATION APPLIANCE CIRCUITS
ACCORDINGLY. ALL COSTS OF ANY AND ALL FIRE ALARM SYSTEM FOR THIS PROJECT SHALL
BE INCLUDED IN BASE BID.
FA7. PROVIDE FIRE ALARM SYSTEM EQUIPMENT, DEVICES, ENGINEERING, PROGRAMMING,
INSPECTIONS, AND TESTS FOR A FULLY WORKING SYSTEM ACCEPTABLE TO AHJ AND OWNER.
FA8. ALL CIRCUITS SHALL BE CLASS A AND SHALL BE RUN IN MINIMUM 3/4" METAL RACEWAYS.
LABEL EACH RACEWAY. ALL NEW RACEWAYS AND BACK BOXES SHALL BE CONCEALED. ANY
SURFACE MOUNTED RACEWAYS SHALL BE PAINTED TO MATCH ADJACENT SURFACE. ALL NEW
JUNCTION BOXES SHALL HAVE RED PAINTED COVER PLATES. ALL JUNCTION BOXES SHALL
HAVE A PERMANENT, MACHINE PRINTED LABEL READING “FIRE ALARM CIRCUIT” ON THE
INSIDE COVER. ALL FIRE ALARM CONDUIT SHALL BE RED OR MARKED WITH 3/4 INCH WIDE
RED BANDS EVERY 10 FEET AND AT EACH SIDE OF FLOORS, WALLS, AND CEILINGS.
FA9. ALL DRAWINGS ARE CONCEPTUAL IN NATURE. DRAWINGS DO NOT SHOW EXACT LOCATIONS
OF COMPONENTS NOR DO THEY SHOW ALL REQUIRED COMPONENTS. PROVIDE ALL
COMPONENTS NECESSARY FOR A PROPERLY INSTALLED, FULLY FUNCTIONAL SYSTEM IN
ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS.
FA10. DURING THE PROJECT MAINTAIN ALL FIRE ALARM SYSTEMS, CONDUIT, CIRCUITS, AND
DEVICES IN OPERATIONAL CONDITION. DURING CONSTRUCTION, NO AREA OF THE BUILDING
SHALL BE LEFT WITHOUT AN OPERATIONAL FIRE ALARM SYSTEM EXCEPT THE PROJECT
AREAS.
FA11. PROVIDE ANNUNCIATOR PANEL AND GRAPHICS TO REFLECT ALL COMPONENTS INCLUDING
BUT NOT LIMITED TO NEW LED PILOT LIGHTS FOR WATER FLOW AND TAMPER SWITCHES.
ELECTRICAL LEGEND
NOTE:
LEGENDS ARE GENERAL, NOT ALL SYMBOLS, ABBREVIATIONS, AND/OR
DESIGNATIONS MAY APPEAR ON THE DRAWINGS.
ANNOTATIONSAS/AF AMPERES SWITCH & FUSE RATING
A, AMP AMPERES
ABBREV ABBREVIATIONS
AC ALTERNATING CURRENT, ARMORED CABLE
ACU AIR CONDITIONING UNIT
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
ATC AUTOMATIC TEMPERATURE CONTROL
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BES BLDG ELECTRICAL SYSTEM
BIL BASIC IMPLUSE LEVEL
BLDG BUILDING
BKBD BACKBOARD
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CR CARD READER
CL CURRENT LIMITING
CLG CEILING
CPT CONTROL POWER TRANSFORMER
CT CURRENT TRANSFORMER
CUH CABINET UNIT HEATER
CW COOL WHITE
DGS DIESEL GENERATOR SET
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DP DISTRIBUTION PANEL
DVR DIGITAL VIDEO RECORDER
DWG DRAWING E, EMERGENCY
EBH ELECTRIC BASEBOARD HEATER
EC EMPTY CONDUIT
ECB ENCLOSED CIRCUIT BREAKER
EF EXHAUST FAN
EGS ELECTRIC GENERATOR SET
EH ELECTRIC HEATER
ELECT ELECTRICAL
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EQUIP EQUIPMENT
ER EXISTING RELOCATED
ETR EXISTING-TO-REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXISTING
EXH EXHAUST
F FUSED OR FUSIBLE
FA FRAME AMPERE
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FADS FIRE ALARM AND DETECTION SYSTEM
FBO FURNISHED BY OTHERS
FCU FAN COIL UNIT
FDR FEEDER FL, FLOOR
FLUOR FLUORESCENT
FSS FUSED SAFETY SWITCH FT, FOOT OR FEET
FVNR FULL VOLTAGE NON REVERSING
GFCI GROUND FAULT CURRENT INTERRUPTER
GND GROUND
GN GENERAL NOTE
GRS GALVANIZED RIGID STEEL
GWB GYPSUM WALL BOARD
GW GROUND WIRE
HC HANDICAP
HD HEAVY DUTY HID, HIGH INTENSIFY DISCHARGE
HOA HAND-OFF-AUTOMATIC HP, HORSE POWER
HPS HIGH PRESSURE SODIUM
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR CONDITIONING
HZ HERTZ
IE THAT IS
IMC INTERMEDIATE METAL CONDUIT
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILLS KV, KILOVOLT
KVA KILOVOLT-AMPERE
KW KILOWATT
KWH KILOWATT-HOUR
LA LIGHTNING ARRESTOR
LS LIMIT SWITCH
LTG LIGHTING
LV LOW VOLTAGE MAX, MAXIMUM
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MH MOUNTING HEIGHT MIN, MINIMUM
ABBREVIATIONSMDP MAIN DISTRIBUTION PANEL
MTD MOUNTED
MLO MAIN LUGS ONLY
MTG MOUNTING
MUX MULTIPLEXER
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NIC NOT-IN-CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
NFSS NON FUSED SAFETY SWITCH
OC ON CENTER
OH OVERHEAD
OL OVERLOAD
P POLE OR POLES
PF POWER FACTOR
PH PHASE
VT POTENTIAL TRANSFORMER
PL PILOT LIGHT
PNL PANELBOARD
PVC POLYVINYL CHLORIDE
R REMOVE
RAF RETURN AIR FAN RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RMS ROOT MEAN SQUARE
RS RAPID START
RVAT REDUCED VOLTAGE AUTOTRANSFORMER
S/N SOLID NEUTRAL
SD SMOKE DETECTOR
SEC SECONDARY
SFA SPRINKLER FLOW ALARM
SMR SURFACE METAL RACEWAY
SPEC SPECIFICATION
ST SHUNT TRIP
SS SUB STATION
STR STARTER
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYS SYSTEM SYM SYMMETRICAL
SOPN SPACE OR POLE NUMBER
TA TRIP AMPERE
TB TERMINAL BOX
TC TIME CLOCK
TD TIME DELAY
TTB TELEPHONE TERMINAL BOARD/BLOCK
TTC TELEPHONE TERMINAL CLOSET
TYP TYPICAL TV TELEVISION
UC UNDER COUNTER
UG UNDERGROUND
UH UNIT HEATER
UOI UNLESS OTHERWISE INDICATED
UON UNLESS OTHERWISE NOTED
UL UNDERWRITER'S LABORATORY
USB UNIVERSAL SERIAL BUS
V VOLT (S) OR VOLTAGE
VA VOLT AMPERE
VFD VARIABLE FREQUENCY DRIVE
W WIRE W/ WITH
WP WEATHER PROOF, WORK PHONE
WW WIREWAY
XFMR TRANSFORMER
PH PHASE ɸ
# NUMBER
C CENTER LINE
@ AT
#
MOUNTING HEIGHTS
SWITCHES, 48"
RECEPTACLE-GENERAL 18"
RECEPTACLE-SPECIAL 18"
RECEPTACLE-SINGLE 18"
RECEPTACLE-REST ROOM 9" ABOVE BASIN
RECEPTACLE-COUNTER 8" ABOVE COUNTER
RECEPTACLE- MONITOR (DISPLAY) 78" OR DIRECTED BY OWNER IN FIELD
RECEPTACLE-EXTERIOR 30"
CABLE TV OUTLET 78" UON
TELEPHONE/DATA-GENERAL 18"
TELEPHONE-WALL TYPE 54", (48" FOR ADA ACCESSIBLE)
FIRE ALARM PULL STATION 48"
FIRE ALARM AUDIO/VISUAL DEVICE 80"
CARD READER 40"
EXIT LIGHT WALL MOUNTED, 90" OR 12" ABOVE DOOR
EXIT LIGHT CEILING MOUNTED 96" AFF
SAFETY SWITCH, VFD, STARTER 72" TO HANDLE
ENCLOSED CIRCUIT BREAKER 72" TO HANDLE
PANELBOARD 72" TO TOP CB
MANUAL MOTOR STARTER 48" PUSH BUTTON, 48"
AUTOMATIC DOOR OPENER 36"
EMERGENCY BATTERY UNIT - WALL 18" BELOW CEILING OR 8' AFF
EXIT SIGN - WALL 6" ABOVE DOOR JAMB ,NO HIGHER THAN 8' AFF
CONTACTOR 5' AFF
DISCONNECT SWITCH 5' AFF
PANELBOARD (6' TALL) TOP TRIM 6' AFF, OR FROM BOTTOM 6" AFF
MOTION SENSOR - WALL 8' AFF OR MANUFACTURER SPECIFICATION
CAMERA - WALL 7'-6" AFF
INTERCOM STATION 48" AFF
MONITOR - WALL 7'-6" AFF
FIRE SYSTEM GENERAL NOTES
LIGHTING SYMBOLSLED LIGHTING FIXTURE
LED LIGHTING FIXTURE WITH BATTERY BACKUP
WALL MOUNTED FIXTURE
INDUSTRIAL TYPE LED FIXTURE
INDUSTRIAL TYPE LED FIXTURE WITH BATTERY BACKUP
CEILING MOUNTED DOWN LIGHT; NORMAL ,
WITH BATTERY BACKUP
WALL MOUNTED LIGHTING FIXTURE
WALL WASH/DOWN LIGHT, CEILING MOUNTED
COVE FIXTURE. LENGTH AS SHOWN ON DRAWINGS
TRACK LIGHT WITH FIXTURE
FIRE ALARM SYMBOLS
FIRE ALARM SYSTEM INDIVIDUAL HORN AND STROBE LIGHT
EXIT LIGHT BACK MOUNTED & w/ DIRECTIONAL
CHEVRON AS INDICATED
LIGHTING / POWER CONTROLS SYMBOLS
OS
VS
PS
PP
SINGLE POLE SWITCH
THREE WAY SWITCH
DOUBLE POLE DISCONNECT
LOW VOLTAGE SWITCH
LOW VOLTAGE DIMMER
TWO BUTTON ENTRY ROOM CONTROL STATION (LIGHTING)
THREE BUTTON ENTRY ROOM CONTROL STATION (LIGHTING)
OCCUPANCY SENSOR CEILING, WALL
VACANCY SENSOR
PHOTO SENSOR
POWER PACK
TELEPHONE/DATA SYMBOLSPOWER SYMBOLS
C
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
ABOVE BACKSPLASH
DUPLEX RECEPTACLE WITH (2) UNIVERSAL SERIAL
BUS PORTS
CONDUIT CONCEALED IN FLOOR OR UNDERFLOOR OR
UNDERGROUND
ELECTRICAL GENERAL NOTES
#
FIRE ALARM BELL
#
FIRE ALARM BELL AND STROBE
FIRE ALARM SYSTEM COMBINATION HORN AND STROBE LIGHT ASSEMBLY
FIRE ALARM SYSTEM CARBON MONOXIDE DETECTOR, M.H. 54" AFF
FIRE ALARM - MAGNETIC DOOR HOLDER
CO
MMETER
1. UNLESS INDICATED OTHERWISE ON THE PLANS OR AS DIRECTED BY THE OWNER, CENTERLINE OF
DEVICE SHALL BE AS INDICATED ABOVE.
2. WHERE MOUNTING HEIGHTS ARE NOT DETAILED OR DIMENSIONED, THE CONTRACTOR SHALL
INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT TO PROVIDE THE MAXIMUM HEADROOM
POSSIBLE AND COMPLY WITH THE REQUIREMENTS OF EQUIPMENT MANUFACTURER, APPLICABLE
CODES AND STANDARDS, AND AHJ REQUIREMENTS. WHERE EQUIPMENT IS INTENDED, SPECIFIED,
OR NOTED TO BE MOUNTED OTHER THEN INDICATED ABOVE, MOUNT IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS AND AS DIRECTED. NOT ALL EQUIPMENT INDICATED WITH
MOUNTING HEIGHTS ARE SHOWN ON THESE CONTRACT DOCUMENTS.
3. COORDINATE EXACT LOCATIONS AND MOUNTING HEIGHTS IN THE FIELD BEFORE ANY CORE
DRILLING, CUTTING, AND ROUGH-INS.
G
FLR WALL
FLOOR MOUNTED TELEPHONE/DATA OUTLET. PROVIDE OUTLET BOX, TWO (2) RJ-45 JACKS &COVER PLATE WITH 1-1/4" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. OWNER WILLPROVIDE PROVIDE: DATA - ONE (1) - 4 PAIR CAT 6 (BLACK) & VOICE - ONE (1) 4 PAIR CAT 5E(WHITE) CABLES AND EXTEND TO NEAREST IT ROOM. OWNER WILL TERMINATE CABLES ONBOTH ENDS. MH = 18" AFF
CR
C
PA
C
SECURITY SYSTEM SYMBOLS
SA
UNDER-COUNTER (SILENT 911 ALARM), FURNISHED AND INSTALLED BY OWNER -
PROVIDE OUTLET BOX WITH 1" RACEWAY, PULL WIRE FROM 6" ABOVE ACCESSIBLE
CEILING TO LOCATION UNDERNEATH DESK.
PANIC ALARM BUTTON, FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET
BOX WITH 1" RACEWAY AND PULL WIRE AND TERMINATE AT AN ACCESSIBLE
LOCATION 6" ABOVE CEILING
PANIC ALARM STROBE, FURNISHED AND INSTALLED BY OWNER - PROVIDE OUTLET
BOX WITH 1" RACEWAY AND PULL WIRE AND TERMINATE AT AN ACCESSIBLE
LOCATION 6" ABOVE CEILING
CEILING MOUNTED SECURITY CAMERA BY OWNER - PROVIDE JUNCTION BOX WITH
1" RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING.
WALL MOUNTED SECURITY CAMERA BY OWNER - PROVIDE JUNCTION BOX WITH 1"
RACEWAY, PULL WIRE AND EXTEND 6" ABOVE CEILING. PROVIDE 1-1/2" SLEEVE
THROUGH THE WALL FOR LOW VOLTAGE WIRING.
OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 60" AFF ANDCOORDINATED WITH ASSOCIATED RECEPTACLE DESIGNATED FOR TV. PROVIDE OUTLET BOXAND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED:
* FUTURE COAX CONNECTION. PROVIDE 1" RACEWAY WITH PULL WIRE TO 6" ABOVECONCEALED, ACCESSIBLE CEILING
* (2) RJ-45 JACKS. PROVIDE 1-1/4" RACEWAY AND PULL STRING TO 6" ABOVE CONCEALED,ACCESSIBLE CEILING.
DLDAYLIGHT SENSOR
PL
PLUG LOAD CONTROLLER
OS
N
CAT 5 CABLE (LIGHTING)
WS1.
WS2.
WS3.PROVIDE 4 CIRCUIT FMC TO HARD-WIRED JUNCTION BOX/POWER IN-FEED.
WS4.
WS5.
WS6.
WS7.
WS8.
WS9.
WS10.
WORKSTATION NOTESFOR WALL FED POWER SOURCE, SURFACE OR FLUSH MOUNT JUNCTION BOX(S) AS
CLOSE AS POSSIBLE TO THE FURNITURE'S POWER IN-FEED. POWER IN-FEED CORD
AND CAP FURNISHED BY FURNITURE MANUFACTURE AND INSTALLED BY
CONTRACTOR. FOR PROTECTION FROM DAMAGE, STRAP/SECURE IN-FEED CORD
FIRMLY TO WALL AND FURNITURE AS DIRECTED BY THE FURNITURE
MANUFACTURER.
FOR WALL FED VOICE/DATA SERVICES, SURFACE OR FLUSH MOUNT JUNCTION
BOX(S) AS CLOSE AS POSSIBLE TO THE FURNITURE'S BASE IN-FEED. PROVIDE
GROMMET IN COVER PLATE TO PROTECT CABLES FROM DAMAGE. ROUTE CABLE
THROUGH BASE OF WORKSTATION FURNITURE VIA HORIZONTAL CABLE SUPPORTS
FURNISHED BY FURNITURE MANUFACTURER AND INSTALLED BY CONTRACTOR.
CONCEAL CABLE IN FURNITURE. FOR VERTICAL STRAIN-RELIEF, FASTEN CABLE TO
THE FURNITURE'S STRUCTURAL MEMBERS.
THE WORKSTATION ELECTRICAL SYSTEM TO BE PROVIDED WILL UTILIZE A 3 UTILITY,
1 ISOLATED CIRCUIT, 8 WIRE SYSTEM WITH A COMMON (4) #12 LINE (2) #10
NEUTRAL AND (2) #12 GROUND. AT THE POINT OF TERMINATION FOR THE POWER
IN-FEED CABLE, THE CONTRACTOR SHALL COMBINE THE NEUTRALS AND GROUNDS AS
DIRECTED BY THE FURNITURE MANUFACTURER. PRIOR TO THE POINT OF
TERMINATION, THE NEUTRALS AND GROUND SHALL REMAIN DEDICATED TO THE
SPECIFIC CIRCUIT.
FIRMLY ATTACH POWER IN-FEED CABLE AND FMC TO WALL JUNCTION BOX COVER VIA
UL LISTED FITTINGS/CONNECTORS WITH INSULATED THROATS.
DUPLEX RECEPTACLES WILL BE FURNISHED AND INSTALLED BY THE FURNITURE
MANUFACTURER.
VOICE/DATA CABLE AND OUTLETS PROVIDED IN BASE PATHWAY BY CONTRACTOR.
INSTALL OUTLETS IN FURNITURE KNOCKOUTS IN THE LOCATION AS DIRECTED BY THE
OWNER. PROVIDE 3 DATA AND 1 VOICE PORT PER OUTLET FOR EVERY SEAT AS SHOWN
ON THE FURNITURE LAYOUT DRAWINGS. FURNITURE SHALL BE PROVIDED WITH
METALLIC SEPARATION BETWEEN POWER WIRING AND VOICE/DATA CABLES.
ALL JUNCTION BOXES SHALL BE MADE READILY ACCESSIBLE INCLUDING HARDWIRED
JUNCTION BOXES FURNISHED BY THE MANUFACTURER.
ALL POWER AND VOICE/DATA CABLING WORK WILL BE PERFORMED BY THE SYSTEM
FURNITURE QUALIFIED INSTALLER. THE FURNITURE VENDOR WILL FURNISH AND INSTALL
POWER IN-FEEDS (OR BASE FEEDS) AND RECEPTACLES (POWER OUTLETS). RECEPTACLES
WILL BE CORCUITED/CONNECTED BY THE FURNITURE VENDOR AS SHOWN ON THE FLOOR
PLANS WITH THE FINAL POWER IN-FEED SERVICE CONNECTION BY THIS CONTRACT.
DATA AND VOICE PORTS (OUTLET JACKS) INCLUDING CABLING AND FINAL
TERMINATIONS IN THE FURNITURE SHALL BE PROVIDED BY THE CONTRACTOR. CABLE
COVER WILL BE FURNISHED AND INSTALLED BY MANUFACTURER / FURNITURE VENDOR.
COORDINATE ROUTING OF CABLES WITH FURNITURE INSTALLER BEFORE PROCEEDING
WITH ANY ROUGH-IN WORK.
SEE FLOOR PLAN(S) FOR FURNITURE POWER AND VOICE/DATA SERVICE LOCATIONS.
VERIFY LOCATION OF FURNITURE POWER IN-FEED POINT OF TERMINATION WITH THE
WORKSTATION MANUFACTURER / FURNITURE VENDOR BEFORE PROCEEDING WITH ANY
ROUGH-IN WORK. PROVIDE QUANTITY OF JUNCTION BOXES AS NECESSARY TO
ACCOMMODATE THE POWER AND VOICE/DATA WIRING/CABLING NEEDS OF THE
FURNITURE. NOT ALL SERVICE FEEDS/LOCATIONS MAY BE SHOWN. TO ACCOMMODATE
CHANGES IN THE FINAL FURNITURE LAYOUT, INCREASE THE NUMBER OF SERVICE
LOCATIONS SHOWN ON THE FLOOR PLANS BY ADDITIONAL 25 PERCENT.
LIGHTNING PROTECTION CABLELP
POWER PACK
PUSH PLATE FOR HANDICAPPED ACCESS DOOR
PB
PC
PHOTOCELL
PP
REMOTE DIGITAL FIRE ALARM TRANSMITTER
110
110
THE NUMBER ADJACENT TO THE SYMBOL INDICATES PREFERRED CANDELA
VALUE. STROBE SYMBOL WITHOUT IDENTIFICATION SHALL BE AS FOLLOWS:
OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 60" AFF ANDCOORDINATED WITH ASSOCIATED RECEPTACLE DESIGNATED FOR TV. PROVIDE OUTLET BOXAND COVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED:
* FUTURE COAX CONNECTION. PROVIDE 1" RACEWAY WITH PULL WIRE TO 6" ABOVECONCEALED, ACCESSIBLE CEILING
* (2) RJ-45 JACKS. PROVIDE 1-1/4" RACEWAY AND PULL STRING TO 6" ABOVE CONCEALED,ACCESSIBLE CEILING.
* (2) HDMI OUTPUT. PROVIDE CABLING IN 1-1/4" RACEWAY TO CORRESPONDING HDMIINPUTS
W
TV
OUTLET BOX FOR CONNECTIONS TO HDTV AT MEETING ROOM, MOUNTED 6" ABOVE COUNTER.COORDINATE EXACT LOCATION WITH OWNER. PROVIDE OUTLET AND COVER PLATE FOR THEFOLLOWING AT THE LOCATION INDICATED:
* - (1) HDMI INPUT. PROVIDE CABLING TO WALL MOUNTED WALL PLATE IN SAME ROOM.
C
TV
FLOOR BOX MOUNTED CONNECTIONS TO HDTV AT MEETING ROOM. COORDINATE EXACTLOCATION WITH TELECOM FLOOR BOX AT SAME ROOM AND OWNER. PROVIDE OUTLET ANDCOVER PLATE FOR THE FOLLOWING AT THE LOCATION INDICATED:
* (1) HDMI INPUT. PROVIDE CABLING TO WALL MOUNTED WALL PLATE IN SAME ROOM.
F
DATA OUTLET FOR SYSTEMS FURNITURE, BY OTHERS. SIZE JUNCTION BOX FOR SYSTEMFURNITURE FOR THE QUANTITY OF DEVICES AS SHOWN. COORDINATE ALL WORK WITH OWNERAND SYSTEMS FURNITURE SUPPLIER.
F
QUAD RECEPTACLE - C = 9" ABOVE COUNTER
C
AutoCAD SHX Text
P
AutoCAD SHX Text
FCP
AutoCAD SHX Text
FSA
AutoCAD SHX Text
RDAT
15" SD8" SD
4" SD
6" SAN.
6" SAN.
6" SA
G
GGGGGGGG
GG
G G
6"W
4"W
6"W4"W
DR
D
JJ
E09
E11
E10E12E13
E14
E15
E16
SL1
SL1
SL1SL1SL1
SL1
SL1
SL1
OA
OA
OAOAOA
OA
OA
OA OA OA OA
E19
E20
PROPOSED FIRE AND DOMESTIC WATER INCOMING LOCATION
4' - 0"
4' -
0"
4' - 0"
4' -
0"
4' -
0"
4' - 0"
CR
PB
E60
E60
OA
SL1
OA
CLEARANCE (TYPICAL)
E37E38
E39
LP - 11
LP - 16
SERVER/DATA/TEL
125
ELECTRICAL202
LP - 16
LP - 16
LP - 16LP - 16LP - 16
LP - 16
LP - 16
LP - 16
E75
E75E76
EX
E83
E82
FOR INCOMING FIBER SERVICE. COORDINATE EXACT ROUTING AND LOCATIONWITH CIVIL DRAWINGS AND CITY.
OA
E92
E91
PP2-28,30,32
E92
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 5:
02:1
1 PM
E100
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - SITE PLAN
03-15-2019
17-023
100% CD
1" = 20'-0"1SITE PLAN - ELECTRICAL REFERENCED NOTES - SITE PLAN
E09 UTILITY PRECAST CONCRETE PAD-MOUNTED FOR BGETRANSFORMER. COORDINATE WITH BGE FOR THEIRREQUIREMENTS.
E10 RELOCATE EXISTING 60KW DIESEL GENERATOR FROM EXISTINGFACILITY. COORDINATE RELOCATION OF EXISTING GENERATORWITH OWNER. PROVIDE WEATHERPROOF, LEVEL 2 SOUNDATTENUATION ENCLOSURE WITH ASSOCIATED COMPATIBLEANCILLARY SUPPORT SYSTEMS INCLUDING BUT NOT LIMITED TOBATTERY CHARGER, BLOCK HEATER, AND RECEPTACLES.
E11 LOCATION FOR FUTURE STANDBY GENERATOR (NOT INCONTRACT).
E12 PROVIDE 4-WAY 4" SECONDARY DUCTBANK FROM BGETRANSFORMER TO PIT UNDERNEATH SWITCHBOARD INELECTRICAL ROOM. REFER TO DUCT BANK DETAILS.
E13 PROVIDE 4-WAY 4" DUCTBANK FOR FUTURE STANDBYGENERATOR (GENERATOR NOT IN CONTRACT) FROMSWITCHBOARD TO GENERATOR DOCKING STATION. PROVIDEWEATHERPROOF JUNCTION BOX AT DOCKING STATION PADFOR NON-FEEDER TERMINATIONS.
E14 PROVIDE 2-WAY 4" DUCT BANK FOR 60 KW GENERATOR. REFERTO DETAILS. COORDINATE WITH MANUFACTURE FOR EXACTTERMINATION.
E15 PROVIDE 3-WAY 4" DUCT BANK FOR TELECOM AND CABLE TVWIRING. REFER TO DETAILS.
E16 EXISTING TO REMAIN CABLE TV DUCT BANK. PROVIDE PULL BOXFOR NEW DATA CABLE.
E19 PROVIDE 2-WAY 4" PRIMARY DUCT BANK FOR BGETRANSFORMER. REFER TO DETAILS. TERMINATE ATAPPROXIMATELY 36" AWAY FROM MANHOLE. COORDINATE WITHBGE FOR EXACT TERMINATION.
E20 COORDINATE CONNECTION TO BGE INCOMING SERVICE WITHBGE PRIOR TO COMMENCING WORK.
E37 12x12x12 JUNCTION BOX FOR POWER FOR GATE. PROVIDEBRANCH CIRCUIT AS INDICATED.
E38 12x12x12 JUNCTION BOX FOR TELECOM WIRING FOR GATE.PROVIDE 1" RACEWAY TO TELECOM ROOM.
E39 1" RACEWAY TO TEL/ELEC ROOME60 PROVIDE TIMECLOCK FOR EXTERIOR LIGHTING CONTROL, SEE
DETAIL ELECTRICAL DRAWING E600.E75 1" EMPTY CONDUIT WITH PULL STRING FOR COMMUNICATION
WIRING.E76 1" EMPTY CONDUIT WITH PULL STRING FOR CONNECTION TO
GENERATOR ANCILLARY SYSTEMS INCLUDING BUT NOT LIMITEDTO BATTERY CHARGER, BLOCK HEATER, AND RECEPTACLE.
E82 1" CONDUIT FOR CONNECTION TO RELOCATED EXISTINGGENERATOR ANCILLARY SYSTEMS, INCLUDING BATTERYCHARGER, BLOCK HEATER AND RECEPTACLE. COORDINATEWIRING WITH GENERATOR ENCLOSURE SUPPLIER.
E83 PAD MOUNTED GENERATOR DOCKING STATION, PROVIDECONCRETE PAD. COORDINATE EXACT LOCATION ANDORIENTATION WITH OWNER AND DOCKING STATION SUPPLIER.
E91 COORDINATE DUCT BANK FOR FIBER WIRING, COORDINATEWITH CIVIL DRAWINGS.
E92 ALL RECEPTACLES IN THIS LOCATION TO BE WEATHERPROOFRATED.
T P
A. CONTRACTOR TO OBTAIN ALL PERMITS/PERMISSIONSREQUIRED BY OTHERS ON PRIVATE PROPERTY. ALL MATERIALS USED SHALL CONFORM TO BGE SPECIFICATIONS. ALL WORK MUST BE DONE IN ACCORDANCE WITH BGE'S STANDARDS AND SPECIFICATIONS. THE CONTRACTOR SHALL PAY ANY AND ALL FEES FOR SERVICE.
B. WORK SHALL BE DONE IN A MANNER ACCEPTABLE TO BGE AND INSPECTED BY THEIR CONDUIT DEPARTMENT BEFORE ENCASEMENT OR BACKFILLING. (CONTRACTOR MUST FIRST SUBMIT A DRAWING OF THE FACILITIES TO BE BUILT FOR THEIR APPROVAL). CALL IN ADVANCE TO ARRANGE INSPECTION. CALL BETWEEN 7.00 - 9.00 A.M. OR 3.00 - 4.00 P.M.
C. ALL RACEWAYS FOR MEDIUM VOLTAGE CONDUCTORS SHALL BE 6 INCH CONCRETE ENCASED. CONDUIT ROUTING SHALL BE BUILT IN ACCORDANCE WITH BGE SPECIFICATIONS. COORDINATE WITH BGE. ALL SERVICE CONDUCTOR CONDUITS SHALL BE 4 INCH PVC SCHEDULE 40 CONCRETE ENCASED.
D. SWEEP BENDS SHALL COMPLY WITH BGE REQUIREMENTS.
E. NYLON PULL LINES SHALL BE INSTALLED IN EACH DUCT FOR FUTURE CABLE INSTALLATION.
F. NO MORE THAN 180° OF BENDS OF DUCT LINE IS ALLOWED.
G. DUCT BANKS MUST HAVE MINIMUM OF THREE FEET (3') OF COVER (TOP OF DUCT TO FINISHED GRADE).
H. CONDUIT SHALL BE ENCASED IN MINIMUM 3000 PSI CONCRETE WITH PEA GRAVEL. NO METALLIC MATERIALS (REBARS, HOLD DOWN WIRES, ETC.) SHALL BE PERMITTED IN SPACES BETWEEN EACH DUCT.
I. CONTRACTOR SHALL ROD ALL CONDUITS, CLEAR ANY OBSTRUCTIONS AND PROVIDE NYLON PULL LINES PRIOR TO THE INSTALLATION OF BGE CABLES.
J. FOR LOCATIONS OF UTILITIES, CALL 24 HOURS A DAY 1-800-257-7777, 48 HOURS IN ADVANCE OF ANY WORK IN THIS VICINITY.
K. ALL METERING CURRENT TRANSFORMER MOUNTING DIMENSIONS, DRILLINGS, SPACING AND STUDS MUST COMPLY WITH BGE SPECIFICATIONS. THE MINIMUM ACCEPTABLE DIMENSIONS, DRILLINGS, ETC. FOR BGE LINE CONNECTIONS TO C/T CABINETS/COMPARTMENTS (INCLUDING SAFETY BARRIER WHERE APPLICABLE).
L. BGE SHALL BE NOTIFIED 48 HOURS (2 WORKING DAYS) BEFORE POURING OF ANY CONCRETE AND/OR THE BACK FILLING OF ANY TRENCH TO MAKE ARRANGEMENTS FOR THE INSPECTION AND APPROVAL OF YOUR ON SITE SERVICE CONNECTION STRUCTURAL EQUIPMENT.
M. ALL OTHER UNDERGROUND UTILITIES IN THE VICINITY SHALL BE SHOWN BY THE CONTRACTOR. MAINTAIN THE MINIMUM HORIZONTAL AND VERTICAL CLEARANCES SET BY BGE. MAINTAIN 5'-0" MINIMUM (HORIZONTAL) AND 1'-0" (VERTICAL) CLEARANCE FROM ALL UNDERGROUND UTILITIES.
N. CALL BGE FOR BGE INSPECTIONS AND COORDINATION.
A. CONTRACTOR SHALL BE RESPONSIBLE TO CALL AND COORDINATE WITH BGE TO GET THE ELECTRICAL AND GAS SERVICES TO THE SITE.
B. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH BGE TO TERMINATE NEW RACEWAYS UNDER TRANSFORMER PAD.
C. CONTRACTOR SHALL COORDINATE WITH BGE TO PROVIDE THE PAD FOR TRANSFORMER. IF INSTALLED IN THE FIELD, ALL PADS SHALL MEET BGE REQUIREMENTS AND SHALL BE APPROVED BY BGE.
D. CONTRACTOR SHALL SUBMIT THE SHOP DRAWINGS FOR SERVICE INCOMING SWITCHBOARDS WITH INCOMING SECTION, AND DISTRIBUTION SECTIONS TO BGE FOR THEIR APPROVAL. CONTRACTOR SHALL NOT ORDER THE EQUIPMENT UNTIL WRITTEN APPROVAL BY BGE.
BGE PROPOSED CLASS OF SERVICE CONDITIONS
GENERAL NOTES:
25'-0
"2'-
0"6'-
0"
24"DIA.
LEVELING NUTS, SHIMS, ETC.
FINISHED GRADE
GROUND LUG
GROUNDING BUSHING
BASE COVER
3000 PSI CONCRETE USESONOTUBE TO FORM
UPPER PORTION OF BASE
POLE AS SPECIFIED
CIRCUIT CONDUCTORS AND CONDUITHANDHOLE-PROVIDE BUSSMAN TYPE HLR
IN-LINE TYPE FUSE WITHIN POLE. LOCATE SOFUSE IS ACCESSIBLE THROUGH HANDHOLE.
AMPACITY SHALL BE APPROPRIATE FORAPPLICATION
1/2" CHAMFER ON TOP OFEDGE IF CONCRETE BASE IS
RAISED
ANCHOR BOLTS SHALL BE ASRECOMMENDED BY
MANUFACTURER
#4 INSULATED COPPERGROUND IN CONDUIT
ATTACHED TO INTERNAL LUGWELDED TO INTERIOR OF
POLE
REBAR CAGE 4 #4 WITH#3 TIES AT 12" O.C.
CONDUIT(S) AS NOTEDPLAN
10'-0" LONG, 3/4" DIA.SOLID COPPER
GROUNDING ROD. LAIDHORIZONTALLY (AS DEEP
AS POSSIBLE) PER NECSTANDARDS.
EXPOSED PORTIONOF FOUNDATIONSHALL BE RUBBEDSMOOTH
3"
21.0"
6" 6"
3"
3" 3"
12"
3"
12"
WARNING ANDIDENTIFICATION TAPE
FINISHED GRADE
MIN.
36"
WASHEDGRAVEL FILL
4" MIN
.
2 WAY - 4 INCH DUCT BANK, TYPICALSCALE: NONE
PVC SCHEDULE 40 CONDUIT (TYP)
CONCRETE ENCASED (3000 PSI,RED COLOR)
COMPACTED BACKFILL
PARKING LOT LIGHTING POLE BASESCALE: NONE
4 WAY - 4 INCH DUCT BANKSCALE: NONE
3"
4"
3"
3" 3"
22"
3"
12"
WARNING ANDIDENTIFICATION TAPE
FINISHED GRADE
MIN.
36"
4" MIN.
PVC SCHEDULE 40 CONDUIT (TYP)
CONCRETE ENCASED (3000 PSI,RED COLOR)
COMPACTED BACKFILL
4"
4"4"
WASHEDGRAVEL FILL
3
8 9
12" DIA.
48" M
IN.
3" MIN.
36" M
IN. /
48" M
AX.
6" MIN.
1" C, TO GATE OPERATORCONTROL PANEL
NOTES:1. NEW CARD READER SHALL BE INSTALLED FOR GATE ENTRY/ACCES.
2. INCLUDE #12 AWG EQUIPMENT GROUND WIRE TO CARD READER.
3. VERIFY FINAL CARD READER UNIT ELEVATION WITH OWNER.
CURB LINE
3000 PSI CONCRETEUSE SONOTUBE TO FORMUPPER PORTION OF BASE
1/2" CHAMFERON TOP OF EDGE
ANCHOR BOLTS PERMANUFACTURERRECOMMENDATION (MIN. OF 4)
FINISHED GRADE
ADDITIONAL CONDUIT(S) TOPEDESTAL AS APPLICABLE
CARD READER OR OTHERACCESS CONTROL UNIT.INCLUDE HARDWARE FORPEDESTAL INSTALLATION
GOOSENECK PEDESTAL
CARD READER PEDESTAL DETAIL, TYPICALSCALE: NONE
2
EXISTING STREET LIGHTING TO REMAIN: SEE CIVIL DRAWING
3 WAY - 4 INCH AND 2 WAY - 1" DUCT BANK
3" 3" 3"
12"
MIN
.
3"
3"
28.0"
4" 4"
3"
WARNING ANDIDENTIFICATION TAPE
FINISHED GRADE
WASHED GRAVEL FILL
4"
SCALE: NONE
PVC SCHEDULE 40 CONDUIT (TYP)
CONCRETE ENCASED (3000 PSI,RED COLOR)
COMPACTED BACKFILL
7
4" 12"
MIN.
36"
3"
1"
1"
3"
11.0"
3"
3" 3"
12"
3"
12"
WARNING ANDIDENTIFICATION TAPE
FINISHED GRADE
MIN.
36"
4" MIN
.
PVC SCHEDULE 80 CONDUIT (TYP)FOR POWER
CONCRETE ENCASED (3000 PSI,RED COLOR)
COMPACTED BACKFILL
1" 1"
WASHEDGRAVEL FILL
2 WAY - 1 INCH DUCT BANK, TYPICALSCALE: NONE
5
1" CONDUIT FORSITE LIGHTING
1"
12"
WARNING ANDIDENTIFICATION TAPE
FINISHED GRADE
MIN.
36"
WASHEDGRAVEL FILL
4" MIN
.
CONDUIT DETAIL WITHOUT CONCRETE ENCASEMENT, TYPICALSCALE: NONE
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 6:
04:3
9 PM
E101
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - FIRSTFLOOR PLAN - LIGHTING
03-15-2019
17-023
100% CD
1/8" = 1'-0"1ELECTRICAL - FIRST FLOOR PLAN - LIGHTING
T P
REFERENCED NOTES - LIGHTING NEW WORKE21 CONNECT ALL EXIT LIGHTS ON THE BRANCH CIRCUIT INDICATED AND UPSTREAM OF
SWITCH.E24 SEE ELECTRICAL DRAWING E402 - FIRST FLOOR POWER PLAN FOR ADDITIONAL
LIGHTING IN THIS AREA.E84 PROVIDE SWITCH FOR FREEZER LIGHTING CONTROL, COORDINATE WITH FREEZER
MANUFACTURER FOR SPECIFICATION PRIOR TO INSTALLATION.
DS
A. PROVIDE ALL ADDITIONAL ACCESSORIES FOR A COMPLETE AND FULLY FUNCTIONING LIGHTING CONTROL SYSTEM INCLUDING BUT NOT LIMITED TO THE FOLLOWING:- POWER PACKS- 0 - 10V LOW VOLTAGE WIRING/RACEWAY
B. SEE LIGHTING CONTROL DIAGRAMS ON SHEETS E400-E402 FOR ADDITIONAL INFORMATION.
C. FOR PANEL SCHEDULES, REFER TO DRAWINGS E-601 & E-602. FOR LIGHTING FIXTURE SCHEDULE, REFER TO E-602.
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 5:
02:4
0 PM
E102
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - FIRSTFLOOR PLAN - POWER
03-15-2019
17-023
100% CD
1/8" = 1'-0"1ELECTRICAL - FIRST FLOOR PLAN - POWER
T P
REFERENCED NOTES - POWERE64 PROVIDE 1" RACEWAY TO OUTDOOR UNIT FOR POWER CONTROL WIRING.E70 PROVIDE 60 AMP, 208V, 3POLE, NEMA 4 FSS @ 45A.E73 PROVIDE DEDICATED 1P-120V RECEPTACLE JOHNSON CONTROL DEVICE.E78 PROVIDE 480V, 3Ø, 30A DISCONNECT SWITCH FUSED AT 20A FOR DAC-1.E80 PROVIDE 120V, 1Ø, JUNCTION BOX FOR SIGNAGE, COORDINATE WITH ARCHITECTURAL
DRAWINGS PRIOR TO INSTALLATION.E81 PROVIDE (6) 120V, NEMA 5-20R AND (6) 208V, NEMA 6-15R RECEPTACLE(S) IN CLEANING
EQUIPMENT STORAGE. ALL RECEPTACLES IN THIS AREA SHALL BE GFCI UNLESS OTHERWISE NOTED. COORDINATE WITH CLEANING EQUIPMENT MANUFACTURER PRIOR TOINSTALLATION FOR INSTALLATION REQUIREMENTS.
E85 PROVIDE 2P, 208V RECEPTACLE, COORDINATE EXACT TYPE AND LOCATION WITHOWNER'S IT SUPPLIER.
E86 RECEPTACLES INSTALLED IN THIS AREA SHALL BE COORDINATED WITH OWNER'S REPPRIOR TO INSTALLATION FOR EXACT MOUNTING LOCATIONS.
E87 PROVIDE 120V JUNCTION BOX FOR HEAT TRACE.E88 PROVIDE CEILING MOUNTED RECEPTACLE IN THIS LOCATION FOR PROJECTOR FOR
FUTURE. (PROJECTOR NOT IN CONTRACT).
REFERENCED NOTES - POWERE32 PROVIDE PLUG LOAD CONTROLLER AND ALL ASSOCIATED WIRING/RACEWAY TO
CONTROL ONE CIRCUIT POWERING FURNITURE SYSTEM RECEPTACLES. PROVIDE ALLCONTROL WIRING TO OCCUPANCY SENSOR SERVING THIS ROOM/AREA CONTROLLEDRECEPTACLES. LOCATE THE CONTROLLER AT A FULLY ACCESSIBLE LOCATION ABOVECEILING.
E33 PROVIDE PLUG LOAD CONTROLLER AND ALL ASSOCIATED WIRING/RACEWAY TOCONTROL ONE RECEPTACLE PER EVERY 50 SQ. FT OF THE OFFICE. PROVIDE ALLCONTROL WIRING TO OCCUPANCY SENSOR SERVING THIS ROOM/AREA CONTROLLEDRECEPTACLES. LOCATE THE CONTROLLER AT A FULLY ACCESSIBLE LOCATION ABOVECEILING.
E34 PROVIDE PLUG LOAD CONTROLLER AND ALL ASSOCIATED WIRING/RACEWAY TOCONTROL ONE RECEPTACLE PER DATA OUTLET IN THE COPY ROOM. PROVIDE ALLCONTROL WIRING TO OCCUPANCY SENSOR SERVING THIS ROOM/AREA CONTROLLEDRECEPTACLES. LOCATE THE CONTROLLER AT A FULLY ACCESSIBLE LOCATION ABOVECEILING.
E35 PROVIDE PLUG LOAD CONTROLLER AND ALL ASSOCIATED WIRING/RACEWAY TOCONTROL ONE COUNTERTOP RECEPTACLE IN THE BREAK ROOM/LOUNGE. PROVIDE ALLCONTROL WIRING TO OCCUPANCY SENSOR SERVING THIS ROOM/AREA CONTROLLEDRECEPTACLES. LOCATE THE CONTROLLER AT A FULLY ACCESSIBLE LOCATION ABOVECEILING.
REFERENCED NOTES - POWERE01 INSTALL ELECTRICAL RECEPTACLES AT 36 INCHES ABOVE FINISHED IN THIS AREA
UNLESS NOTED OTHERWISE.E05 JUNCTION BOX FOR WALK-IN COOLER FREEZER, COORDINATE SPECIFICATIONS WITH
MANUFACTURER PRIOR TO INSTALLATION.E06 PROVIDE 480V, 3Ø, 60A DISCONNECT SWITCH FUSED AT 50A FOR ANALOG SYSTEM FOR
XRAY. PROVIDE 3#4 AWG + 1#8 G IN 1" RACEWAY TO SWITCHBOARD.E07 PROVIDE JUNCTION BOX WITH (4) #12 LINE, (2) #10 NEUTRAL AND (2) #12 GROUND FOR 8
WIRE SYSTEM FURNITURE IN THIS LOCATION. COORDINATE WITH MANUFACTURERPRIOR TO INSTALLATION.
E27 PROVIDE RECEPTACLE FOR SCAVENGING VACUUM PUMP, COORDINATE EXACT HEIGHTAND MOUNTING LOCATION WITH VACUUM PUMP SUPPLIER.
E28 PROVIDE 3-GANG JUNCTION BOX FLUSH WITH FINISHED WALL. COORDINATE EXACTLOCATION AND CONTROL WIRING WITH SCAVENGING ALARM PANEL SUPPLIER.
E29 PROVIDE 120V JUNCTION BOX FOR LIGHTING CIRCUIT IN WALKING FREEZER,COORDINATE SPECIFICATIONS WITH MANUFACTURER PRIOR TO INSTALLATION.
E31 PROVIDE JUNCTION BOX ABOVE CEILING WITH BRANCH CIRCUIT WIRING/RACEWAY ASINDICATED FOR LOW VOLTAGE FLUSH VALVES CONTROLS. PROVIDE ALL LOW VOLTAGEWIRING IN THE WALL TO THE PLUMBING DEVICES.
1/4" = 1'-0"2 PARTIAL FLOOR PLAN - REPTILE/WILDLIFE AND SMALL MAMMALS ROOMS
NO. DESCRIPTION DATE
REF
REF
REF
REF
REF
FEC
FEC
FEC
FEC
FEC
FEC
FEC
FEC
FEC
FECFEC FEC
REF
REF
TVTV
J
J
J
J
TV
J
J
TV TV
CR CRCRCRCRCRCRCR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CRCR
CR CRCR
CR
C C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
CR
SASA
E22
E22
E22
+60" AFF
DOG ROOM153
DOG ROOM154
DOG ROOM155 DOG
OBSERVATION156
DOGQUARANTINE
157
DOGISOLATION &
SICK158
ELECTRICAL202
T&S 3199
T&S 4201
WOMEN'SLOCKER ROOM
198
MEN'S LOCKERROOM
197
T&S 1195
T&S 2196
TRAPSTORAGE
194CORRIDOR160
AC SUPPLIES/EVIDENCE
192
AC GARAGE193
DOG INTAKE175
AC RADIOLOCKER/
EQUIPMENT191
OFFICE189
OFFICE188
OFFICE187
AC BREAKROOM
190
CAT INTAKE176
CAT EXAM174
DOG EXAM173
VET OFFICE172
CLEANING/EQUIPMENTSTORAGE
171
SURGERYCORRIDOR
159
TNR CATHOLDING
169
SURGERY170
SURGERYPREP168
DOGRECOVERY
(BEACH)165
CATRECOVERY
164
CAT HOLDING163
DOG HOLDING161
DOG HOLDING162
CATOBSERVATION
152CAT ISOLATION
151
CAT BITEQUARANTINE
150
COMMERCIALLAUNDRY
149
DOG & CATFOOD & LITTER
STORAGE148
DOG & CATKITCHEN
147
GROOMING143
REPTILE/WILDLIFE
142
SMALLMAMMALS
141
CAT ROOM144
CAT ROOM145
CAT ROOM146
CORRIDOR132
CORRIDOR132
CORRIDOR107
GENERALSTORAGE
124
SERVER/DATA/TEL
125
TOILET131
TOILET130
JAN129
VET GROUPOFFICE
122
FILE ROOM123
VET TECHGROUP
121
COPY/ WORKROOM
119
WATER120
MEETINGROOM
103
TOILET126
TOILET127
TOILET104
TOILET105
LOUNGE128
PUBLIC LOBBY101
OBEDIENCETRAINING
102
CAT COMM133
CAT COMM134
CAT COMM135
CAT COMM136
GETACQUAINTED/
ADOPTIONCLASSROOM
137
SURRENDER/FOSTER EXAM
138
FOSTER/SURRENDER
LOBBY139
SURRENDER/FOSTER EXAM
140
LAB/PHARMACY
177
X-RAY RM178
LAUNDRY &CLEANUP
179MEDICALSTORAGE
180
STORAGE182
EUTHANASIA181
TOILET183
TOILET184
CORRIDOR160
OPENWORKSTATIONS
185DIR AC
186
FRONT OFFICE106
OFFICEMANAGER
108
VOLUNTEERMANAGER
109
EXEC DIR110
EXEC ASST111
DIR OF OPS112
MARKETINGAND PRCOORD
113
HR MANAGER114
ACCT115
DIR OF DEV117
OPENWORKSTATIONS
118
CORRIDOR107
P P P P P P P
P
PPP
P
P
P
3015 15
15 15
15 15
75
1515
15
15
3030
15 15
151530
15
15
15 15
15
15
15
7515
15
15
151515
3030303030
151515
1515
151515
1515
15
15151515
15
30
15
15
30
15
15
15
15
15
15
15
15
30
30
30
FSA
FCP
E22
C
CRCRCR
C
C
C C C
C
C
CC
C
C
C
C
C
C
C
C
C
CRCRCRCRCRCR
FS
FS
TSTS
TSFSTS
CO CO CO CO CO CO
CR
30
15
15
30
15
15
15
15
15
P
PA PA PA PA
PA
PA
PA PA PA PA PA PA
PA
PA
PA
PA
DOAS-04
DOAS-03
DOAS-01
DOAS-02
15151515151515151515
15
15
15
15
15
15
15
15
15
15
E7115
15
15
15
15
15
E72
E74
1515
1515
E77
DR DR
DR
DR
E79
E79
E79
C
E36
15
1515
110WP
F F F
FF F
F F F
FFF
FFF
FFF
F F F
W
CF
E89
E89
E90
C C C
C
C
C
C
C
E92 E92 E92 E92 E92 E92
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 5:
04:5
6 PM
E103
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - FIRSTFLOOR PLAN - SYSTEMS
03-15-2019
17-023
100% CD
1/8" = 1'-0"1 ELECTRICAL - FIRST FLOOR PLAN - SYSTEMS
T P
REFERENCED NOTES - SYSTEMSE22 PROVIDE VOICE/DATA JUNCTION BOX FOR SYSTEM FURNITURE AT THIS LOCATION.
COORDINATE WITH OWNER AND SYSTEMS FURNITURE MANUFACTURER FOR SYSTEMFURNITURE POWER AND DATA REQUIREMENTS.
E36 PROVIDE DATA OUTLETS FOR HVAC CONTROL PANEL, COORDINATE WITH MECHANICALDRAWINGS FOR EXACT MOUNTING LOCATION.
E71 PROVIDE JUNCTION BOX FOR DOOR RELEASE BUTTON, COORDINATE EXACT MOUNTINGLOCATION WITH SECURITY CONTRACTOR.
E72 PROVIDE (2) 4" EMPTY CONDUITS WITH PULL STRING FOR TELECOM AND CABLE TVWIRING TO BE STUBBED UP IN THIS LOCATION.
E74 PROVIDE JUNCTION BOX IN THIS LOCATION FOR DOOR BUZZER.E77 PROVIDE 4' X 8', 3/4" PLYWOOD BOARD FOR TELEPHONE TERMINAL.E79 PROVIDE PUSH BUTTON FOR OVERHEAD DOORS AT THE LOCATION INDICATED.
COORDINATE PHOTOELECTRIC SENSOR AND TWO WIRE SAFETY EDGE WITH OVERHEADDOOR MANUFACTURER.
E89 UNDERGROUND CONDUIT FOR DATA CONNECTION. PROVIDE 1-1/4” EMPTY CONDUITWITH PULL STRING TO WALL AS INDICATED. TERMINATE CONDUIT 6” ABOVE ACCESSIBLECEILING. COORDINATE CONDUIT PATH WITH POWER CONDUIT IN SAME ROOM.
E90 UNDERGROUND CONDUIT FOR CARD READER DATA CONNECTION. PROVIDE 1-1/4”EMPTY CONDUIT WITH PULL STRING TO WALL AS INDICATED. TERMINATE CONDUIT 6” ATINSIDE OF THE BUILDING ABOVE ACCESSIBLE CEILING. COORDINATE EXACTTERMINATION LOCATION WITH OWNER SECURITY CONSULTANT.
E92 ALL RECEPTACLES IN THIS LOCATION TO BE WEATHERPROOF RATED.
NO. DESCRIPTION DATE1 Permit Comments 3.12.19
G,WP
G,WP
G,WP
G,WP
G,WP
G,WPG,WP
G,WP
HPU-03
HPU-01
DOAS-03
DOAS-04
DOAS-02
HPU-02
HPU-04
ACU-1
MH1-26,28,30HSB-6
HSB-10
HSB-8
HSB-3
MH1-14,16,18
MH1-13,15,17
MH1-25,27,29
MH1-19,21,23 MH1-20,22,24EF-1 EF-2
EF-6
EF-5
EF-3
EF-4
ML1-11
ML1-10
ML1-4
ML1-3
ML1-1
EL1-31,33
EL1-30
DOAS-01
ML1-23
EF-7
WP
WPWP
WP
E56
E56
E56
E56
E62
E62
E62
E62
E66
E66
E66
E68
E68
E68
E68E67 E67
E69
E62E62
E62
RP1 - 29
RP1 - 29
E66
E66RP1 - 29
RP1 - 29
E66E66
RP2 - 51RP2 - 51
RP2 - 51
RP2 - 51E66
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 5:
05:1
4 PM
E104
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - ROOFPLAN
03-15-2019
17-023
100% CD
1/8" = 1'-0"1ELECTRICAL - ROOF PLAN
T P
REFERENCED NOTES - LIGHTING NEW WORKE56 DOAS UNIT FURNISHED WITH WEATHER PROOF RECEPTACLE AND DISCONNECT
SWITCH, COORDINATE WITH DOAS UNIT MANUFACTURER FOR SPECIFICATION.E62 DISCONNECT AND SPEED CONTROL BY MANUFACTURER UNLESS OTHERWISE NOTED.E66 PROVIDE GFCI, WP RECEPTACLE WITH BRANCH CIRCUIT AS INDICATED. PROVIDE
INDEPENDENT SUPPORTS.E67 PROVIDE 60 AMP, 480V, 3POLE, NEMA 4 NFSS.E68 PROVIDE 30 AMP, 480V, 3POLE, NEMA 4 NFSS.E69 PROVIDE 30 AMP, 208V, 2POLE, NEMA 4 NFSS.
NO. DESCRIPTION DATE
LV
LV
LVLV
LVLV
LD
LVLV
LVLV
LV
LV
LV
LVLV
a
a
a
a
d d d d d
b
b
b
b
c
c
c
c
e
e
e
e
e
e
e
e
a,b,c,d,e
DL DL
DLDL
PP
E21
DOG ROOM154
E57
E57
E57
N N N N
N N N N
NN N N
NNNN
NN N N
N
N
N
N
N
N
N
N
N
E51
E51 E51
E51
E52
E53
E55
D1 D D1 D D1
D D D D D
D D D D D
DDDDD
D D D1 D D PP
PP
EXEC DIR110
VOLUNTEERMANAGER
109
N
N
N
N
E52
E52
E53
E55
A A
AA
E55
N
N
N
N
E58
E58
DL
PP
NN
N
N
NN
N
N
NE52
E51
N
E53E55
DC DC
DCDC
DC DC
DCDC
E50
a a
b b
a a
b b
d d d
a a a
a a a
b b b
b b b
c c c c
OS
OS
OS
OS
E21
PP
E21
E57
OPENWORKSTATIONS
118
N
N
N N
N
N
N N
N
N
N N N N
NNN
N
N
N
N
N
N
N
E52E53
E54
E54
E55
A1 A A
AAA
A A A
AAA
A1 A A
SC2 SC2 SC2 SC2
E57
E54
E54
DOG ROOM
MODE 1
MODE 2
ON
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
B. MODE 1: ZONE(S) a,b,c,d,e at 100%C. MODE 2: ZONE(S) - a,b,c,d at 100% / ZONE e - OFF
F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE e WHEN NATURAL LIGHT FROM SKY LIGHT HAS REQUIRED FC, AND DIM REMAINING ZONES AT50%.
OFF
MODE 3
MODE 4
DIM UP
DIM DN
D. MODE 3: ZONE(S) - a,b,c,d,e at 50% E. MODE 4: ZONE(S) - a,b,c,e OFF / ZONE d AT 50%
OPEN WORKSTATION
MODE 1
MODE 2
ON
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
B. MODE 1: ZONE(S) a,b,c at 100%C. MODE 2: ZONE(S) - a,c at 100% / ZONE b - OFF
OFF
MODE 3
MODE 4
DIM UP
DIM DN
D. MODE 3: ZONE(S) - b,c, at 100% / ZONE a - OFFE. MODE 4: ZONE(S) - c at 100% / ZONE a,b - OFF
F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE d WHEN NATURAL LIGHT FROM SKY LIGHT HAS REQUIRED FC, AND DIM REMAINING ZONES AT50%.
CAT ROOM
ON/OFF
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
B. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE b
DIM UP/DNON/OFF
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
OFFICE
ON/OFF
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 5:
05:2
2 PM
E400
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - ENLARGEDSCALE PLANS - LIGHTINGCONTROLS I
03-15-2019
17-023
100% CD
1/4" = 1'-0"1 ELECTRICAL - TYPICAL DOG ROOM - LIGHTING CONTROL1/4" = 1'-0"2 ELECTRICAL - TYPICAL OFFICE - LIGHTING CONTROL
1/4" = 1'-0"4ELECTRICAL - TYPICAL CAT ROOM - LIGHTING CONTROL
1/4" = 1'-0"6 ELECTRICAL - OPEN WORKSTATION - LIGHTING CONTROL
1/4" = 1'-0"7 SEQUENCE OF OPERATION - TYPICAL DOG ROOM
REFERENCED NOTES - LIGHTING NEW WORKE21 CONNECT ALL EXIT LIGHTS ON THE BRANCH CIRCUIT INDICATED AND UPSTREAM OF
SWITCH.E50 PROVIDE ON/OFF + DIMMING LOW VOLTAGE SWITCH LIGHTING CONTROL BY ACUITY
CONTROLS OR APPROVED EQUAL. SEE SEQUENCE OF OPERATION BELOW FORLIGHTING SCENE SCHEMATIC.
E51 PROVIDE DAYLIGHT HARVESTING PHOTOCELL LIGHTING CONTROL IN THIS AREA. SEESEQUENCE OF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.
E52 PROVIDE DIMMING/RELAY POWER PACK BY ACUITY CONTROLS OR APPROVED EQUAL,LOCATED IN ACCESSIBLE CEILING SPACE OF ROOM NEAR ENTRY DOOR. SEE SEQUENCEOF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.
E53 277V LIGHTING CIRCUIT FROM DIMMING/RELAY POWER PACK BY ACUITY CONTROLS ORAPPROVED EQUAL. REFER FOR ELECTRICAL DRAWING E101 FOR DESIGNATED LIGHTCIRCUITS.
E54 PROVIDE CEILING MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.
E55 PROVIDE AND CONNECT CAT-5 NETWORK CABLE TO BRIDGE DEVICE BY ACUITYCONTROLS OR APPROVED EQUAL.
E57 PROVIDE NLIGHT ENABLED TOGGLE AND/OR RAISE/LOWER VOLTAGE SWITCH WITHUSER DEFINED LOCAL CONTROL OF A LIGHTING ZONE.
E58 PROVIDE WALL MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.
1/4" = 1'-0"8 SEQUENCE OF OPERATION- OPEN WORKSTATION
1/4" = 1'-0"9SEQUENCE OF OPERATION - TYPICAL CAT ROOM
1/4" = 1'-0"10 SEQUENCE OF OPERATION - TYPICAL OFFICE
NO. DESCRIPTION DATE
LD
LD
LDLV
OS
OS
LVLVDL
DL
PP
PP
E51 E51E21 E21
N
N
NN
N N N
N
N
N
N
N
N
N
N
N
N
N
N
N
E52
E52
PS
PS
PS PS PS
PS1
PSPSPS1
PS
PS
PS
PSPS1
PS
OBEDIENCETRAINING
102
PUBLIC LOBBY101
E53
E55E55
E21
A1 A
E50
E50
E50
E21
b b b
aa a
a
a a
a aa
b b
b
PP
PP
N
N
N
N
N
E52
E52
TOILET183
TOILET184
E58
E55
N
E55
A1
A1
E58
E53
N
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
RESTROOM
ON/OFF
CAT ROOM
ON/OFF
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
B. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE b
DIM UP/DNON/OFF
PP
PP
NN
NN
N
N
NN
NN N
NN
N N
N
N
N
DOG INTAKE175
CAT INTAKE176
E55
E53
E52
E52
D D
DD
D D
DD
D D
DDD
D D D
CAT INTAKE
ON/OFF
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
DIM UP/DNON/OFF
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 5:
05:3
0 PM
E401
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - ENLARGEDSCALE PLANS - LIGHTINGCONTROLS II
03-15-2019
17-023
100% CD
REFERENCED NOTES - LIGHTING NEW WORKE21 CONNECT ALL EXIT LIGHTS ON THE BRANCH CIRCUIT INDICATED AND UPSTREAM OF
SWITCH.E50 PROVIDE ON/OFF + DIMMING LOW VOLTAGE SWITCH LIGHTING CONTROL BY ACUITY
CONTROLS OR APPROVED EQUAL. SEE SEQUENCE OF OPERATION BELOW FORLIGHTING SCENE SCHEMATIC.
E51 PROVIDE DAYLIGHT HARVESTING PHOTOCELL LIGHTING CONTROL IN THIS AREA. SEESEQUENCE OF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.
E52 PROVIDE DIMMING/RELAY POWER PACK BY ACUITY CONTROLS OR APPROVED EQUAL,LOCATED IN ACCESSIBLE CEILING SPACE OF ROOM NEAR ENTRY DOOR. SEE SEQUENCEOF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.
E53 277V LIGHTING CIRCUIT FROM DIMMING/RELAY POWER PACK BY ACUITY CONTROLS ORAPPROVED EQUAL. REFER FOR ELECTRICAL DRAWING E101 FOR DESIGNATED LIGHTCIRCUITS.
E55 PROVIDE AND CONNECT CAT-5 NETWORK CABLE TO BRIDGE DEVICE BY ACUITYCONTROLS OR APPROVED EQUAL.
E58 PROVIDE WALL MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.
1/4" = 1'-0"1ELECTRICAL - PUBLIC LOBBY/OBEDIENCE TRAINING - LIGHTING CONTROLS
3/8" = 1'-0"2ELECTRICAL - TYPICAL RESTROOMS - LIGHTING CONTROL
1/4" = 1'-0"3 SEQUENCE OF OPERATION - RESTROOMS1/4" = 1'-0"4 SEQUENCE OF OPERATION - PUBLIC LOBBY/OBEDIENCE TRAINING
1/4" = 1'-0"5 ELECTRICAL - CAT INTAKE - LIGHTING CONTROL
1/4" = 1'-0"6 SEQUENCE OF OPERATION - CAT INTAKE
NO. DESCRIPTION DATE
LV
LV
LVLV
LV
LV
LV
LV
LV
OS
LD LD
LV
LDLV
LV
LD
LD
PP
PP
PP
PP
PP
PP
PP
PP
N
N
NN
NN
N
N
NN
NN
N
N
N
N
N
N
NN
N N
N N
N N
N
N N
N N
N
N NNN
N
N
N
N
NN
N
N
NN
N
E21
E21
N
N
N
N
NN
N
N
N
N
DOG HOLDING161
DOG HOLDING162
DOGRECOVERY
166
DOGRECOVERY
(BEACH)165
CATRECOVERY
164
CAT HOLDING163
SURGERYPREP168
TNR CATHOLDING
169
SURGERY170
OXYGENSTORAGE
167
N N
N N
N
N
N
N
E55
E52
E53
E53E55
E52
E52
E55
E55
E55
E52
E55
D12 D12 D12
D12D12D12
D12 D12 D12
D12D12D12
D12 D12 D12
D12 D12 D12
D12
D12
D12
DR DR
DRDR
DR DR
DRDR
DRDR
DR
DR
DRDR
DR DR
AC
AC
AC AC
AC
AC
DRDR
DRDR
DRDR
DRDR
AC AC
AC
AC
E55
E55 E52
E52
E52
E52
GL
E59E59
E59
E59
E59
E59
N
E59
E59
E59
E59
E58
E50
E50
N
N
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
B. MODE 1: ZONE(S) a,b,c,d,e at 100%C. MODE 2: ZONE(S) - a,b,c,d at 100% / ZONE e - OFF
F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE E WHEN NATURAL LIGHT FROM SKY LIGHT IS REQUIRED FC, AND DIM REMAINING ZONES AT50%.
D. MODE 3: ZONE(S) - a,b,c,d,e at 50% E. MODE 4: ZONE(S) - a,b,c,e OFF / ZONE d AT 50%
OFF
ON
ON/OFF
DIM UP/DNON/OFF
PP
N
NN
NN N
N N
N
N
A
A
A
A
A
A
A
A1
E53
E52 E55
E21
FRONT OFFICE106
E57
E57
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
B. MODE 1: ZONE(S) a,b,c,d,e at 100%C. MODE 2: ZONE(S) - a,b,c,d at 100% / ZONE e - OFF
F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE E WHEN NATURAL LIGHT FROM SKY LIGHT IS REQUIRED FC, AND DIM REMAINING ZONES AT50%.
D. MODE 3: ZONE(S) - a,b,c,d,e at 50% E. MODE 4: ZONE(S) - a,b,c,e OFF / ZONE d AT 50%
ON/OFF
DIM UP/DNON/OFF
MEETINGROOM
103
MP8
MP8 MP81
MP8
PPN
N
N
N
N
N E55 E52
E53
E21
E50
OS
E54
E50
GENERAL NOTES FOR STATIONS CONFIGURATION:
A. PROVIDE CUSTOM ENGRAVING AS DIRECTED BY OWNER ON EACH BUTTON OF EACHDEVICE TO MATCH THE FUNCTIONS OF THE SPACE. DEVICE LABELS SHOWN ARE GENERICIN NATURE AND DO NOT REPRESENT THE EXACT FINAL EXPECTED ENGRAVING.
B. MODE 1: ZONE(S) a,b,c,d,e at 100%C. MODE 2: ZONE(S) - a,b,c,d at 100% / ZONE e - OFF
F. DAYLIGHT SENSOR: UNLESS OTHERWISE INDICATED, TURN LIGHTS TURNS OFF ZONE E WHEN NATURAL LIGHT FROM SKY LIGHT IS REQUIRED FC, AND DIM REMAINING ZONES AT50%.
D. MODE 3: ZONE(S) - a,b,c,d,e at 50% E. MODE 4: ZONE(S) - a,b,c,e OFF / ZONE d AT 50%
ON/OFF
DIM UP/DNON/OFF
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 5:
05:3
8 PM
E402
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - ENLARGEDSCALE PLANS - LIGHTINGCONTROLS III
03-15-2019
17-023
100% CD
1/4" = 1'-0"1ELECTRICAL - SURGERY SUITE - LIGHTING CONTROLS
1/4" = 1'-0"2SEQUENCE OF OPERATION - SURGERY SUITE
REFERENCED NOTES - LIGHTING NEW WORKE21 CONNECT ALL EXIT LIGHTS ON THE BRANCH CIRCUIT INDICATED AND UPSTREAM OF
SWITCH.E50 PROVIDE ON/OFF + DIMMING LOW VOLTAGE SWITCH LIGHTING CONTROL BY ACUITY
CONTROLS OR APPROVED EQUAL. SEE SEQUENCE OF OPERATION BELOW FORLIGHTING SCENE SCHEMATIC.
E52 PROVIDE DIMMING/RELAY POWER PACK BY ACUITY CONTROLS OR APPROVED EQUAL,LOCATED IN ACCESSIBLE CEILING SPACE OF ROOM NEAR ENTRY DOOR. SEE SEQUENCEOF OPERATION BELOW FOR LIGHTING SCENE SCHEMATIC.
E53 277V LIGHTING CIRCUIT FROM DIMMING/RELAY POWER PACK BY ACUITY CONTROLS ORAPPROVED EQUAL. REFER FOR ELECTRICAL DRAWING E101 FOR DESIGNATED LIGHTCIRCUITS.
E54 PROVIDE CEILING MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.
E55 PROVIDE AND CONNECT CAT-5 NETWORK CABLE TO BRIDGE DEVICE BY ACUITYCONTROLS OR APPROVED EQUAL.
E57 PROVIDE NLIGHT ENABLED TOGGLE AND/OR RAISE/LOWER VOLTAGE SWITCH WITHUSER DEFINED LOCAL CONTROL OF A LIGHTING ZONE.
E58 PROVIDE WALL MOUNTED OCCUPANCY SENSOR SWITCH BY ACUITY CONTROLS ORAPPROVED EQUAL, IN THIS AREA. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTINGSCENE SCHEMATIC.
E59 PROVIDE ON/OFF LOW VOLTAGE SWITCH LIGHTING CONTROL BY ACUITY CONTROLS ORAPPROVED EQUAL. SEE SEQUENCE OF OPERATION BELOW FOR LIGHTING SCENESCHEMATIC.
1/4" = 1'-0"3ELECTRICAL - FRONT OFFICE - LIGHTING CONTROLS
TRANSFORMER GENERAL NOTES:1. UNLESS OTHERWISE NOTED, ALL TRANSFORMERS TO BE DRY-TYPE, DELTA-WYE TYPE TRANSFORMERS. SEE SPECIFICATION FOR ADDITIONAL DETAILS
2. PROVIDE CONCRETE PAD FOR TRANSFORMERS. SEE ARCHITECTURAL EQUIPMENT PAD DETAILS FOR ADDITIONAL INFORMATION.
3. SECONDARY OVERCURRENT PROTECTION DEVICE SHALL BE LOCATED SUCH THAT THE MAXIMUM LENGTH OF SECONDARY CONDUCTORS DOES NOT EXCEED 10 LINEAR FEET.
4. PROVIDE GROUNDING ELECTRICAL CONDUCTOR TO BUILDING PER NEC
T4RP1
300A
200A
PP2
200A
4#4/0 + 1#4G IN 2-1/2"C
4#1 + 1#6 IN 1-1/2"C
M
M
M
M
SPD
SERVER/DATA/TEL 125
4#1 + 1#6G IN 2"C
M
PAD MOUNTED GENERATOR DOCKING STATION, TRYSTAR
GDS-125P-LM-JK
ESTIMATE HANDHOLE
T1
PNL EL1
T2
RP1 - 27
PNL RP1
T3
MH1 - 18
EHUH-2HSB
ELECTRICAL202
DISCONNECT SWITCH T1
ATS-1DISCONNECT
SWITCH T3, 250A, 3P
PNL PP1
T4
15' - 8"
4' -
8"
0' - 6"
4' -
0"
3' - 6" 3' - 6" 2' - 0" 3' - 0" 3' - 0"
1' - 7"
1 2 3 4 5
15' - 0"
4' -
0"
3' -
0"
3' -
0"
3' -
5"
4' - 5 1/2" 4' - 4 1/2"
1' -
5"
NORTHFACE
CONNECT TO
PANEL "LP1"
277V, 20A CIRCUITA B C
LOADTO LIGHTING
ELECTRONIC ASTRONOMICALTIME CLOCK WITH MANUALOVERRIDE CAPABILITY
TIME CLOCK WITH 8 CIRCUITRELAY CONTROL. MOUNTEDINSIDE NEMA-4X, STAINLESS
STEEL, LOCKABLE ENCLOSURE.
PHOTO CELL
NOTES:1. ELECTRICAL CONTRACTOR SHALL PROGRAM THE TIME CLOCK BASED ON OWNER'S
DIRECTION. (INCLUDING INDIVIDUAL ZONES). THE PARKING LOT LIGHTS SHALL AUTOMATICALLY SWITCH-OFF FROM MIDNIGHT TO 6 AM, UNLESS DIRECTED OTHERWISE.
ON ROOFPC
CT
C
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 5:
05:4
3 PM
E600
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - POWERRISER DIAGRAM
03-15-2019
17-023
100% CD
SCALE: NONE1ELECTRICAL RISER DIAGRAM
1/4" = 1'-0"2ELECTRICAL PARTIAL FLOOR PLAN - ELECTRICAL RM 202
SCALE: NONE3SWITCHBOARD HSB ELEVATION
SCALE: NONE4TIME-CLOCK SCHEMATIC
NO. DESCRIPTION DATE
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 5:
05:4
9 PM
E601
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL -SCHEDULES I
03-15-2019
17-023
100% CD
1. DOUBLE SECTION PANELNotes:
Total Est. Demand: 87 AReceptacle 51470 VA 59.71% 30735 VA Total Conn.: 144 APower 0 VA 0.00% 0 VA Total Est. Demand: 31235 VAMotor 0 VA 0.00% 0 VA Total Conn. Load: 51970 VAHVAC 500 VA 100.00% 500 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 148 A 143 A 142 ATotal Load: 17780 VA 17100 VA 17090 VA
83 SPACE -- -- -- 0 VA 0 VA -- -- -- -- 8481 SPACE -- -- -- 0 VA 0 VA -- -- -- -- 8279 SPACE -- -- -- 0 VA 0 VA 3 30 A SPD 8077 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7875 SPARE 20 A 1 0 VA 0 VA -- -- -- SPACE 7673 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 7471 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 7269 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 0 VA 1 20 A SPARE 7067 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6865 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6663 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6461 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6259 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 6057 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 5855 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 5653 RECEP (REPTILE, MAMMALS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP (REPTILE, MAMMALS) 5451 RECEP. (ROOF) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 5249 RECEP (WATER 120) 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 5047 GFI (WATER 120) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 4845 RECEP. TV (LOBBY 101) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 1600 VA 1 20 A SYSTEMS FURNITURE FEED 4643 RECEP. TV (LOBBY 101) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 4441 RECEP. (LOBBY, OBEDIENCE) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 4239 RECEP. (OFF 112, 113, 114, 115,... 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 4037 RECEP. (OFF 108, 109, 110, 111) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 800 VA 1 20 A SYSTEMS FURNITURE FEED 3835 EQ-16 MONITOR (MEETING 103) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 940 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU, FLOOR (OFFICE 115, 117) 3633 RECEP. (MEETING 103) 2#12+1#12 G IN 3/4"C 20 A 1 940 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICES 114, 115) 3431 RECEP. (CORRIDOR) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICE 112, 113, 114) 3229 RECEP. (CORRIDOR, STORAGE) 2#12+1#12 G IN 3/4"C 20 A 1 1190 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICE 111, 112, 113) 3027 RECEP. (CORRIDOR, STORAGE) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICE 109, 110, 111) 2825 RECEP. (CORRIDOR, STORAGE) 2#12+1#12 G IN 3/4"C 20 A 1 1080 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (FRONT, OFFICE 108, 109) 2623 RECEP (REPTILE/WILDLIFE) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (FRONT, OFFICE 108) 2421 RECEP. (GROOM, REPT, MAMLS) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (FRONT OFFICE 106) 2219 GFI (GROOM, REPT, MAMLS) 2#12+1#12 G IN 3/4"C 20 A 1 540 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (FRONT OFFICE 106) 2017 GFI (CAT ROOM 144, 145, 146) 2#12+1#12 G IN 3/4"C 20 A 1 1080 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (MEETING, FRONT, OBEDI) 1815 GFI (CAT, LAUNDRY) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (ADOPTION, EXAM) 1613 GFI (OBEDIENCE, CAT COMM) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (SURRENDER LOBBY 139) 1411 GFI (DOG ROOM 155, 156) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET GROUP OFFICE) 129 GFI (DOG ROOM 153, 154) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET TECH GROUP 121) 107 GFI (LOUNGE 128) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET TECH GROUP 121) 85 GFI (TOILET 130, 131) 2#12+1#12 G IN 3/4"C 20 A 1 360 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (VET TECH 121, 122) 63 GFI (DOG/CAT KITCHEN 147) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (SURRENDER LOBBY) 41 GFI (TOILET 104, 105, 126, 127) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 300 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (OFFICE 117) 2
CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT
1. SEE ARCHITECTURAL DRAWING A106 FOR EQUIPMENT SCHEDULE.Notes:
Enclosure: NEMA 1 Indoor MCB Rating: 200 AMounting: Surface Wires: 4 Mains Rating: 225 A
Receptacle 83690 VA 55.97% 46845 VAPower 113177 VA 100.00% 113177 VA Total Est. Demand: 871 AOther 56183 VA 100.00% 56183 VA Total Conn.: 908 ALighting 25141 VA 125.00% 31427 VA Total Est. Demand: 724409 VAHVAC 475435 VA 100.00% 475435 VA Total Conn. Load: 754902 VAEquipment 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 908 A
Total Conn. Load: 754902 VA2019181716151413 EQ-38 - X RAY 3 100 A 50 A 46403 VA PROVIDE METER CIRCUIT BREAKER12 SPD 3 -- 30 A 0 VA LOCATED OUTSIDE OF SWITCHBOARD11 TRANSFORMER T1 (BACK-UP POWER VIA ATS-1) 3 200 A 125 A 41653 VA10 DOAS-01 (ON ROOF) 3 100 A 90 A 68506 VA PROVIDE METER CIRCUIT BREAKER9 TRANSFORMER T4 3 200 A 175 A 72130 VA PROVIDE METER CIRCUIT BREAKER8 DOAS-02 (ON ROOF) 3 100 A 80 A 54123 VA PROVIDE METER CIRCUIT BREAKER7 TRANSFORMER T2 3 200 A 125 A 80776 VA PROVIDE METER CIRCUIT BREAKER6 DOAS-03 (ON ROOF) 3 200 A 150 A 123570 VA PROVIDE METER CIRCUIT BREAKER5 TRANSFORMER T3 3 200 A 125 A 17727 VA PROVIDE METER CIRCUIT BREAKER4 PANEL MH1 3 400 A 250 A 140435 VA PROVIDE METER CIRCUIT BREAKER3 DOAS-04 (ON ROOF) 3 200 A 150 A 123570 VA PROVIDE METER CIRCUIT BREAKER2 PANEL LP 3 100 A 100 A 23298 VA PROVIDE METER CIRCUIT BREAKER1 SPARE 3 -- 200 A 0 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
1. SWITCHBOARD TO BE UTILITY SERVICE RATED AND SUITABLE FOR FUTURE RENEWABLE LOCAL POWER SOURCE.Notes:
Enclosure: NEMA 1 INDOOR MCB Rating: 1000 AMounting: FLOOR, FREE STANDING Wires: 4 Mains Rating: 1200 A
Total Est. Demand: 141 AReceptacle 0 VA 0.00% 0 VA Total Conn.: 141 APower 50884 VA 100.00% 50884 VA Total Est. Demand: 50884 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 50884 VAHVAC 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 140 A 144 A 140 ATotal Load: 16840 VA 17264 VA 16780 VA
41 SPARE 20 A 1 0 VA 0 VA -- -- -- SPACE 4239 SPARE 20 A 1 0 VA 0 VA -- -- -- SPACE 4037 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 3835 -- -- -- -- 0 VA 0 VA 1 20 A SPARE 3633 SPARE 20 A 2 0 VA 0 VA 1 20 A SPARE 3431 -- -- -- -- 0 VA 0 VA 1 20 A RESERVED-GATE ENTRAPMENT 3229 SPARE 20 A 2 0 VA 0 VA 1 20 A RESERVED-GATE LOOP... 3027 -- -- -- -- 0 VA 648 VA 1 20 A RESERVED-GATE PEDESTAL 2825 SPARE 20 A 2 0 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-38 ANIMAL SCALE 2623 -- -- -- -- 5452 VA 1700 VA -- -- -- -- 2421 -- -- -- -- 5452 VA 1700 VA 2 35 A 3#10+1#10 G IN 3/4"C EQ-20 STACKED WASHER DRYER 2219 EQ-26 DISHWASHER 2#6+1#10 G IN 1"C 60 A 3 5452 VA 500 VA 1 20 A 2#12+1#12 G IN 3/4"C FLUSH VALVE XFMR (TOILET) 2017 -- -- -- -- 5452 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-8 COFFEE MAKER 1815 -- -- -- -- 5452 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-9 MICROWAVE 1613 EQ-26 DISHWASHER 2#6+1#10 G IN 1"C 60 A 3 5452 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-38 ANIMAL SCALE 1411 EQ-11 WATER COOLER 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-13 COPIER 129 EWC-1 2#12+1#12 G IN 3/4"C 20 A 1 336 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-13 COPIER 107 EQ-21 VENDING MACHINIE 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-13 COPIER 85 EQ-29 INDUSTRIAL WASHER 2#12+1#12 G IN 3/4"C 20 A 1 840 VA 1656 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-28 IN\DUSTRIAL DRYER 63 EQ-29 INDUSTRIAL WASHER 2#12+1#12 G IN 3/4"C 20 A 1 840 VA 1656 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-30 INDUSTRIAL DRYER 41 EQ-27 INDUSTRIAL WASHER 2#12+1#12 G IN 3/4"C 20 A 1 1920 VA 1656 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-30 INDUSTRIAL DRYER 2
CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT
1. SEE ARCHITECTURAL DRAWING A106 FOR EQUIPMENT SCHEDULE.Notes:
Enclosure: NEMA 1 Indoor MCB Rating: 200 AMounting: Surface Wires: 4 Mains Rating: 225 A
1. DOUBLE SECTION PANEL2. CIRCUITS ARE TO BE INDIVIDUALLY METERED. PROVIDE ALL ASSOCIATED EQUIPMENT, ACCESSORIES, SOFTWARE AND TRAINING FOR A COMPLETE AND FULLY FUNCTIONING METERING SYSTEM.
Notes:
Total Est. Demand: 115 AReceptacle 11880 VA 92.09% 10940 VA Total Conn.: 116 APower 21496 VA 100.00% 21496 VA Total Est. Demand: 41544 VAMotor 0 VA 0.00% 0 VA Total Conn. Load: 41653 VAHVAC 4956 VA 100.00% 4956 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 137 A 125 A 93 ATotal Load: 15941 VA 14501 VA 11210 VA
83 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 8481 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 8279 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 8077 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7875 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7673 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7471 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 7269 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 7067 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6865 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6663 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6461 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 6259 EQ-31 HEAT TRACE 2#12+1#12 G IN 3/4"C 20 A 1 100 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP ( UNDER (COUNTER... 6057 -- -- -- -- 1560 VA 1560 VA -- -- -- -- 5855 L6-20R (SERVER 125) 2#12+1#12 G IN 3/4"C 20 A 2 1560 VA 1560 VA 2 20 A 2#12+1#12 G IN 3/4"C L6-20R (SERVER 125) 5653 -- -- -- -- 4080 VA 0 VA 1 20 A SPARE 5451 -- -- -- -- 4080 VA 0 VA 1 20 A SPARE 5249 EQ-31-CU 3#4+1#8 G IN 3/4"C 45 A 3 4080 VA 0 VA 1 20 A GENERATOR RECEPTACLE 5047 EQ-31 - WALK-IN FREEZER LTG 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 0 VA 1 20 A GENERATOR BATTERY CHARGER 4845 -- -- -- -- 770 VA 0 VA 1 20 A GENERATOR BLOCK HEATER 4643 EQ-31-EC - WALKIN FREEZER... 2#12+1#12 G IN 3/4"C 20 A 2 770 VA 500 VA 1 20 A 2#12+1#12 G IN 3/4"C EXTERIOR SIGNAGE 4441 SPARE 20 A 1 0 VA 500 VA 1 20 A 2#12+1#12 G IN 3/4"C EXTERIOR SIGNAGE 4239 -- -- -- -- 1144 VA 45 VA 1 20 A 2#12+1#12 G IN 3/4"C LTG. LOBBY TRACK LIGHTING 4037 ACU-1 2#10+1#10 G IN 3/4"C 15 A 2 1144 VA 580 VA 1 20 A RECEP ( UNDER (COUNTER... 3835 EF-3 2#12+1#12 G IN 3/4"C 15 A 1 528 VA 448 VA 1 20 A 2#12+1#12 G IN 3/4"C LTG. (SURGERY, HOLDING) 3633 SPARE 20 A 1 0 VA 800 VA 1 20 A 2#12+1#12 G IN 3/4"C LTG. (DOG AND CAT HOLDING) 3431 EQ-51 - SCAVENGE ALARM PANEL 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 512 VA 1 20 A 2#12+1#12 G IN 3/4"C LTG. (SURGERY PREP 168) 3229 EQ-48 AUTOCLAVE 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 600 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-50 - SURGICAL LIGHT 3027 EQ-48 AUTOCLAVE 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 0 VA 1 20 A SPARE 2825 EQ-42 BLOOD ANALYZER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 180 VA 1 20 A GFI (LAB 177) 2623 EQ-42 BLOOD ANALYZER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C GFI (CAT HOLDING) 2421 EQ-42 BLOOD ANALYZER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C GFI (DOG HOLDING 161, 162) 2219 EQ-42 BLOOD ANALYZER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 540 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SURGERY 170) 2017 FRIDGE (OFFICE 186, 187, 188, 189) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 0 VA 1 20 A SPARE 1815 FRIDGE (AC BREAK 190) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (CAT, SURGERY) 1613 FRIDGE (LOUNGE 128) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 1260 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SURGERY SUITE) 1411 2 DOOR FREEZER (KITCHEN 147) 2#12+1#12 G IN 3/4"C 20 A 1 1416 VA 540 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SURGERY 170) 129 FRIDGE (KITCHEN 147) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SURGERY PREP 168) 107 FRIDGE (KITCHEN 147) 2#12+1#12 G IN 3/4"C 20 A 1 400 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (SURGERY PREP 168) 85 FRIDGE (MED STORAGE 180) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SERVER 125) 63 FRIDGE (LAB 177) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SERVER 125) 41 FRIDGE (SURGERY PREP 168) 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C RECEP. (SERVER 125) 2
CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT
Notes:
Enclosure: NEMA 1 Indoor MCB Rating: 300 AMounting: Surface Wires: 4 Mains Rating: 400 A
Total Est. Demand: 115 AReceptacle 71630 VA 56.98% 40815 VA Total Conn.: 200 APower 0 VA 0.00% 0 VA Total Est. Demand: 41315 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 72130 VAHVAC 500 VA 100.00% 500 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 209 A 194 A 200 ATotal Load: 24980 VA 23220 VA 23930 VA
41 - -- -- -- 0 VA 17090 VA -- -- -- -- 4239 - -- -- -- 0 VA 17100... -- -- -- -- 4037 RESERVED FOR RP2 BREAKER -- -- -- 0 VA 17780... 3 200 A PANEL RP2 3835 SPARE 20 A 1 0 VA 0 VA -- -- -- -- 3633 SPARE 20 A 1 0 VA 0 VA -- -- -- -- 3431 0 VA 3 30 A SPD 3229 GFI (ROOF) 20 A 1 720 VA 3027 RECEP. (ELECTRICAL 202) 2#12+1#12 G IN 3/4"C 20 A 1 360 VA 2825 RECEP. (CORRIDOR) 2#12+1#12 G IN 3/4"C 20 A 1 1080 VA 2623 RECEP. (CORRIDOR 160) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (LAB, X-RAY, EUTHANASIA) 2421 RECEP. (CORRIDOR 159) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (X-RAY) 2219 RECEP. (DOG, CAT EXAM) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (CAT INTAKE 175, OFFICE... 2017 RECEP. (SURRENDER 139, 140) 2#12+1#12 G IN 3/4"C 20 A 1 540 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET OFFICE, EXAM) 1815 RECEP. (BREAK, OFFICES) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (VET OFFICE, DOG INTAKE) 1613 GFI (OBSERV, QUARAN) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 720 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (SURRENDER, LAB 177) 1411 GFI (LAUNDRY 179) 2#12+1#12 G IN 3/4"C 20 A 1 360 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (OFFICES 186, 188, 189) 129 GFI (INTAKE, STOR, EUTHAN) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (WORKSTATIONS 185) 107 GFI (INTAKE, TOILETS) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 1080 VA 1 20 A 2#12+1#12 G IN 3/4"C CPU (WORKSTATIONS 185) 85 GFI (GARAGE, AC STORAGE) 2#12+1#12 G IN 3/4"C 20 A 1 900 VA 360 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (WORKSTATION 185) 63 GFI (LOCKER ROOMS, TRAP) 2#12+1#12 G IN 3/4"C 20 A 1 540 VA 180 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (VET OFFICE 172) 41 GFI (TOILET & SHOWERS) 2#12+1#12 G IN 3/4"C 20 A 1 720 VA 540 VA 1 20 A 2#12+1#12 G IN 3/4"C PRINTER (OFFICES 187, 188, 189) 2
CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT
Notes:
Enclosure: NEMA 1 Indoor MCB Rating: 300 AMounting: Surface Wires: 4 Mains Rating: 400 A
Total Est. Demand: 224 AReceptacle 180 VA 100.00% 180 VA Total Conn.: 224 APower 80596 VA 100.00% 80596 VA Total Est. Demand: 80776 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 80776 VAHVAC 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 211 A 235 A 234 ATotal Load: 25304 VA 27776 VA 27696 VA
41 - -- -- -- 0 VA 16780 VA -- -- -- -- 4239 - -- -- -- 0 VA 17264... -- -- -- -- 4037 RESERVED - PP2 BREAKER -- -- -- 0 VA 16840... 3 200 A 4#1 + 1#6G IN 2"C PANEL PP2 3835 SPARE 20 A 1 0 VA 3633 EQ-22 MICROSCOPES 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 3431 EQ-13 COPIER (WORKSTATION... 2#12+1#12 G IN 3/4"C 20 A 1 1000 VA 3229 EQ-11 WATER COOLER 2#12+1#12 G IN 3/4"C 20 A 1 500 VA 3027 EQ-9 MICROWAVE 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 2825 EQ-8 COFFEE MAKER 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 552 VA -- -- -- -- 2623 EQ-52 SCAVENGE VAC PUMP 2#12+1#12 G IN 3/4"C 20 A 1 504 VA 552 VA 2 20 A 2#12+1#12 G IN 3/4"C OVERHEAD DOOR OPENER 2421 EQ-3 CHEST FREEZER 2#12+1#12 G IN 3/4"C 20 A 1 240 VA 552 VA -- -- -- -- 2219 EQ-48 AUTOCLAVE 2#12+1#12 G IN 3/4"C 20 A 1 180 VA 552 VA 2 20 A 2#12+1#12 G IN 3/4"C OVERHEAD DOOR OPENER 2017 -- -- -- -- 1560 VA 1560 VA -- -- -- -- 1815 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 15 A 2 1560 VA 1560 VA 2 15 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 1613 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 20 A 1 1000 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 1411 -- -- -- -- 1560 VA 1560 VA -- -- -- -- 129 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 15 A 2 1560 VA 1560 VA 2 15 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 107 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 20 A 1 1000 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 85 -- -- -- -- 1560 VA 1560 VA -- -- -- -- 63 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 15 A 2 1560 VA 1560 VA 2 15 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 41 EQ-58 POWER WASH 2#12+1#12 G IN 3/4"C 20 A 1 1000 VA 1000 VA 1 20 A 2#12+1#12 G IN 3/4"C EQ-58 POWER WASH 2
CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT
Notes:
Enclosure: NEMA 1 Indoor MCB Rating: 400 AMounting: Surface Wires: 4 Mains Rating: 400 A
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
X LITHONIA LIGHTING LRP 1/2 GMR 120/277 EL N80 LED 0 lm/W 12 W 120V (277V) VARIES
XWL LITHONIA LIGHTING WLTE W 1 LED 0 lm/W 12 W 120V (277V) VARIES No STANDARD TEMP RATING -4° TO122°F (-20°C TO 50°C)
Notes:
Total Est. Demand: 34 AReceptacle 0 VA 0.00% 0 VA Total Conn.: 27 APower 0 VA 0.00% 0 VA Total Est. Demand: 28451 VALighting 22760 VA 125.00% 28451 VA Total Conn. Load: 22760 VAHVAC 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 29 A 27 A 29 ATotal Load: 7912 VA 7520 VA 7898 VA
41 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 4239 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 4037 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3835 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3633 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3431 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3229 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 3027 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 2825 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 2623 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 2421 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 2219 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 2365 VA 104 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING (CANOPY) 2017 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 1610 VA 2115 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING 1815 CORRIDOR LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 1605 VA 2493 VA 1 20 A 2#6+1#6 G IN 1"C SITE LIGHTING 1613 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 1732 VA 2306 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING 1411 SITE LIGHTING 2#10+1#10 G IN 1"C 20 A 1 1400 VA 1610 VA 1 20 A 2#12+1#12 G IN 3/4"C DOG ROOM LIGHTING 129 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 1290 VA 1541 VA 1 20 A 2#12+1#12 G IN 3/4"C CORRIDOR LIGHTING 107 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 380 VA 1021 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING 85 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 278 VA 952 VA 1 20 A 2#12+1#12 G IN 3/4"C LIGHTING 63 LIGHTING 2#12+1#12 G IN 3/4"C 20 A 1 111 VA 570 VA 1 20 A 2#12+1#12 G IN 3/4"C LOBBY/OBEDIENCE LTG 41 TIME-CLOCK 2#12+1#12 G IN 3/4"C 20 A 1 0 VA 10 VA 1 20 A 2#12+1#12 G IN 3/4"C EMERGENCY LIGHTING 2
CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT
Notes:
Enclosure: NEMA 1 Indoor MCB Rating: 100 AMounting: Surface Wires: 4 Mains Rating: 125 A
LIGHTING FIXTURE SCHEDULE NOTES:1. LISTED CATALOG NUMBER AND MANUFACTURER CONSTITUTES "BASIS OF DESIGN". LISTING OF ALTERNATE MANUFACTURER'S NAMES DOES NOT IMPLY ACCEPTANCE OF THEIR STANDARD PRODUCT. MANUFACTURERS ARE
RESPONSIBLE FOR PROVIDING FIXTURES THAT ARE EQUAL IN ALL RESPECTS TO THE "BASIS OF DESIGN" FIXTURES. "INTENT IS TO ALLOW FOR COMPETITIVELY BID LIGHTING PACKAGE, FOR FIXTURES WITH MULTIPLE NAMED MANUFACTURERS."
2. SUBSTITUTIONS OF FIXTURES ONLY ALLOWED WHEN APPROVED IN ADVANCE BEFORE SHOP DRAWINGS SUBMITTAL AND REQUEST FOR SUBSTITUTION IS SUBMITTED IN ACCORDANCE WITH SPECIFICATION REQUIREMENTS.
3. LIGHTING FIXTURES SUBMITTALS SHALL INCLUDE, AS A MINIMUM: A) FIXTURE TYPE (TO MATCH WITH SCHEDULE), DIMENSIONS AND FINISH. B) LAMP DATA/LED DATA FOR EACH TYPE OF FIXTURE INCLUDING: TYPE, QUANTITY, WATTAGE, AND PHOSPHOR COLOR. C) DRIVER FOR EACH FIXTURE TYPE AND FIXTURE VOLTAGE.
4. PROVIDE UNIVERSAL 120/277 VOLT, 0-10V DIMMING DRIVER FOR DIMMING TO 1% UNLESS OTHERWISE INDICATED.
5. VERIFY CEILING/WALL TRIM COMPATIBILITY PRIOR TO SUBMITTING THE FIXTURES. COLOR AND FIXTURE FINISHES AS SELECTED BY ARCHITECT WHETHER SHOWN OR NOT. PROVIDE ADAPTER AND ADDITIONAL MOUNTING EQUIPMENT AS REQUIRED TO MOUNT FIXTURE TO SURFACE.
6. PROVIDE LABOR AND EQUIPMENT FOR FOCUSING OF ADJUSTABLE FIXTURES AND PRESETTING OF LIGHTING CONTROL SYSTEMS. FOCUSING AND PRESETTING SHALL BE DONE IN THE PRESENCE OF THE OWNER AND ARCHITECT/ENGINEER.
7. PROVIDE ALL CONTROL WIRES FOR 0-10V DIMMING.
8. IF THE CONTRACTOR OPTS TO USE THE FIXTURE OF ALTERNATE MANUFACTURER (WHERE ACCEPTABLE), THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE POINT-TO-POINT CALCULATIONS FOR ALL AREAS AS DIRECTED BY THE ENGINEER AT THE TIME OF SUBSTITUTION REQUEST.
9. PROVIDE ALL CHANNELS, HANGERS, CABLES, SUPPORTS AND OTHER ACCESSORIES AS REQUIRED FOR SUSPENDED FIXTURES FOR COMPLETE WORKING SYSTEM WITHOUT ADDITIONAL COST TO OWNER.
10. ALL LIGHT FIXTURES ANNOTATION WITH A SUFFIX OF 1 SHALL BE HAVE INTEGRAL EMERGENCY BATTERY BALLAST AND CONNECT TO CIRCUIT AS INDICATED, UPSTREAM OF ASSOCIATED CONTROL SWITCH TO SERVE AS A NIGHT LIGHT. PROVIDE ALL WIRING/RACEWAY AS REQUIRED FOR COMPLETE WORKING SYSTEM.
11. IF MULTIPLE VOLTAGES ARE INDICATED, FIXTURE IS COMPATIBLE WITH MULTIPLE VOLTAGES. FIXTURE TO BE WIRED TO VOLTAGE INDICATED IN PARENTHESES ().
3.9 W
15 W
25 W22 lm/W
Notes:
Total Est. Demand: 49 AReceptacle 0 VA 0.00% 0 VA Total Conn.: 49 APower 0 VA 0.00% 0 VA Total Est. Demand: 17727 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 17727 VAHVAC 14619 VA 100.00% 14619 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 52 A 48 A 48 ATotal Load: 6264 VA 5715 VA 5748 VA
41 SPARE 20 A 1 0 VA 0 VA -- -- -- SPACE 4239 VAV CONTROL(S) 2#12+1#12 G IN 3/4"C 15 A 1 350 VA 0 VA -- -- -- SPACE 4037 DWH-1 2#12+1#12 G IN 3/4"C 15 A 1 600 VA 0 VA -- -- -- SPACE 3835 CP-2 2#10+1#10 G IN 3/4"C 15 A 1 1012 VA 0 VA 1 20 A SPARE 3633 CP-1 2#10+1#10 G IN 3/4"C 15 A 1 1012 VA 0 VA 1 20 A SPARE 3431 -- -- -- -- 435 VA 237 VA -- -- -- -- 3229 DOAS-06 2#12+1#12 G IN 3/4"C 15 A 2 435 VA 237 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-2-08, 2-09 3027 -- -- -- -- 435 VA 375 VA -- -- -- -- 2825 DOAS-05 2#12+1#12 G IN 3/4"C 15 A 2 435 VA 375 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-2-07, 2-10 2623 SPARE 20 A 1 0 VA 588 VA -- -- -- -- 2421 SPARE 20 A 1 0 VA 588 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-2-02, 2-04 ,2-06 2219 -- -- -- -- 232 VA 588 VA -- -- -- -- 2017 BCU-02, 04 2#12+1#12 G IN 3/4"C 15 A 2 232 VA 588 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-2-01, 2-03, 2-05 1815 -- -- -- -- 232 VA 0 VA 1 20 A SPARE 1613 BCU-01, 03 2#12+1#12 G IN 3/4"C 15 A 2 232 VA 0 VA 1 20 A SPARE 1411 EF-7 2#12+1#12 G IN 3/4"C 20 A 1 528 VA 798 VA -- -- -- -- 129 EF-6 2#12+1#12 G IN 3/4"C 15 A 1 360 VA 798 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-1-05, 1-07, 1-09 107 EF-4 2#12+1#12 G IN 3/4"C 15 A 1 528 VA 802 VA -- -- -- -- 85 EF-5 2#12+1#12 G IN 3/4"C 15 A 1 528 VA 802 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-1-04, 1-06 ,1-08 63 EF-2 2#12+1#12 G IN 3/4"C 15 A 1 125 VA 1440 VA -- -- -- -- 41 EF-1 2#12+1#12 G IN 3/4"C 15 A 1 360 VA 1440 VA 2 15 A 2#12+1#12 G IN 3/4"C SSU-1-01, 1-03, 1-10 2
CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT
Notes:
Enclosure: NEMA 1 Indoor MCB Rating: 100 AMounting: Surface Wires: 4 Mains Rating: 125 A
Total Est. Demand: 168 AReceptacle 0 VA 0.00% 0 VA Total Conn.: 168 APower 0 VA 0.00% 0 VA Total Est. Demand: 139715 VALighting 0 VA 0.00% 0 VA Total Conn. Load: 139715 VAHVAC 139715 VA 100.00% 139715 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 176 A 176 A 159 ATotal Load: 48212 VA 48212 VA 44012 VA
41 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 4239 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 4037 SPACE -- -- -- 0 VA 0 VA -- -- -- SPACE 3835 -- -- -- -- 5272 VA 0 VA -- -- -- SPACE 3633 -- -- -- -- 5272 VA 0 VA -- -- -- SPACE 3431 HPU-04 3#10+1#10 G IN 3/4"C 30 A 3 5272 VA 0 VA -- -- -- SPACE 3229 -- -- -- -- 5272 VA 0 VA 1 20 A SPARE 3027 -- -- -- -- 5272 VA 0 VA 1 20 A SPARE 2825 HPU-03 3#10+1#10 G IN 3/4"C 30 A 3 5272 VA 0 VA 1 20 A SPARE 2623 -- -- -- -- 2742 VA 5155 VA -- -- -- -- 2421 -- -- -- -- 2742 VA 5155 VA -- -- -- -- 2219 HPU-02 (MODULE 2) 3#12+1#12 G IN 3/4"C 20 A 3 2742 VA 5155 VA 3 25 A 2#12+1#12 G IN 3/4"C DAC-1 AIR CURTAIN 2017 -- -- -- -- 3740 VA 3300 VA 1 20 A 2#12+1#12 G IN 3/4"C EHUH-2 (ELECTRICAL 202) 1815 -- -- -- -- 3740 VA 7500 VA 1 35 A 2#8+1#10 G IN 3/4"C EHUH-1 (AC GARAGE 193) 1613 HPU-02 (MODULE 1) 3#10+1#10 G IN 3/4"C 25 A 3 3740 VA 7500 VA 1 35 A 2#8+1#10 G IN 3/4"C EHUH-1 (AC GARAGE 193) 1411 -- -- -- -- 5983 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (TRAP STORAGE 194) 129 -- -- -- -- 5983 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (TOILET 184) 107 HPU-01 (MODULE 2) 3#8+1#10 G IN 3/4"C 35 A 3 5983 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (CORRIDOR 160) 85 -- -- -- -- 7730 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (CORRIDOR 160) 63 -- -- -- -- 7730 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (WORKSTATIONS 118) 41 HPU-01 (MODULE 1) 3#8+1#10 G IN 3/4"C 50 A 3 7730 VA 2409 VA 1 15 A 2#12+1#12 G IN 3/4"C EWH-1 (WORKSTATIONS 185) 2
CKT Circuit Description Wire Size Trip Poles A B C Poles Trip Wire Size Circuit Description CKT
Notes:
Enclosure: NEMA 1 Indoor MCB Rating: 250 AMounting: Surface Wires: 4 Mains Rating: 400 A
Driving Area 2.3 fc 4.6 fc 0.3 fc 15.3:1 7.7:1Parking One 2.2 fc 4.5 fc 0.2 fc 22.5:1 11.0:1Parking Two 2.2 fc 5.3 fc 0.1 fc 53.0:1 22.0:1Rear Biulding 2.2 fc 5.5 fc 0.1 fc 55.0:1 22.0:1
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.
S T U D I O S10839-D PHILADELPHIA RDWHITE MARSH, MD 21162
ARCHITECTURE + MASTER PLANNING
Eng
inee
ring
Infra
stru
ctur
e S
olut
ions
C.C
. Joh
nson
& M
alho
tra,
P.C
.
400
Eas
t Pra
tt S
treet
, Sui
te 6
04B
altim
ore,
MD
212
02(P
) 410
-461
-992
0 | (
F) (
667)
239-
3534
| (E
) BA
LTIM
OR
E@
CC
JM.C
OM
CC
JM
3/15
/201
9 6:
04:5
4 PM
E700
BALT
IMO
RE C
ITY
ANIM
AL S
ERVI
CES
BUIL
DING
2490
GIL
ES R
OAD
, BAL
TIM
ORE
, 212
25
ELECTRICAL - SITEPHOTOMETRICS PLAN
03-15-2019
17-023
100% CD
NO. DESCRIPTION DATE
ELECTRICAL - SITE LIGHTING PHOTOMETRICS PLANSCALE: NONE
1
20.7
27.6 34.2
32.3
30.2
24.2
36.9
29.3
33.2 57.8 55.7
15.3
40.9
0.0 0.0 0.0 0.0 0.0
46.8 55.5
49.1
37.6
59.3
51.4
28.9
34.8
29.7 29.7
32.8 32.8
38.5
59.5
59.5
48.0
15.2
15.1
48.0
59.4
57.8 58.2 58.2
58.8
79.5
47.2
60.4
75.2
56.8
56.8
102.8 101.9
29.3
29.3
29.3
51.4
51.4
42.9
42.9
82.0
134.3
134.3
79.4
70.6
117.8
108.5
56.8
57.7
56.6
58.0
48.6
59.7
59.7
130.3
23.8
29.4 29.4
106.2
21.3
28.1
36.6
44.9
49.6
48.9
45.8
44.3
46.6
51.7
55.3
55.1
51.6
49.8
51.3
51.8
54.0
52.1
48.0
45.4
46.7
49.8
50.5
46.1
38.2
29.9
21.4
28.6
37.6
46.4
51.3
50.6
47.2
45.6
47.9
52.8
57.8
55.8
54.0
53.3
53.7
56.2
54.3
49.8
47.0
48.4
51.9
52.6
48.1
39.5
30.8
26.5
33.8
40.9
44.9
44.7
42.3
41.2
43.3
46.7
50.6
57.9
56.0
54.8
45.5
48.7
50.7
49.0
45.5
43.5
44.5
46.8
47.2
43.5
36.5
29.4
37.0
49.6
50.6
42.8
36.8
49.7
47.1
41.4
52.4
52.2
45.6
51.3
53.6
47.3
48.4
50.4
45.5
44.8
46.0
42.8
44.1
44.7
41.5
47.4
47.8
43.4
51.9
52.1
46.6
52.8
53.1
47.3
50.5
50.7
45.5
46.4
46.6
42.7
45.1
45.3
41.3
47.7
47.8
41.9
52.1
52.3
52.9
53.0
44.0
49.8
49.8
43.9
45.4
45.5
41.1
43.6
43.6
39.8
45.8
45.8
33.9
48.9
48.9
37.8
48.3
48.2
41.6
42.8
42.7
37.9
34.0
33.8
30.9
25.9
25.6
23.4
27.7
28.6
35.5
37.3
35.0
43.6
46.4
42.8
48.9
52.2
47.8
49.3
52.8
48.3
47.1
49.4
46.3
44.7
47.2
44.1
46.0
48.7
45.4
49.7
52.9
48.7
51.8
55.2
50.7
49.9
53.1
48.9
45.5
48.0
44.8
40.7
42.7
40.3
40.4
42.3
40.0
43.7
46.0
43.1
49.1
52.2
48.2
52.6
56.1
51.6
52.1
55.5
51.1
48.8
51.7
48.1
46.6
49.2
46.0
48.0
50.7
47.4
51.7
55.0
50.8
54.1
53.1
52.9
56.3
51.9
48.4
51.3
47.8
46.2
48.7
45.7
47.0
49.8
46.5
51.2
54.7
50.6
53.2
57.0
52.5
52.5
56.1
51.8
47.9
50.8
47.4
45.4
48.0
45.0
45.8
48.6
45.3
49.0
52.3
48.3
49.7
53.3
49.1
46.2
49.4
45.5
38.8
40.8
38.4
30.7
32.0
30.6
44.8
47.8
44.3
50.3
53.7
49.6
51.8
55.1
50.9
49.3
52.1
48.5
46.5
48.8
46.0
47.1
49.4
46.5
50.6
53.3
49.7
54.5
57.9
53.5
54.0
57.3
53.0
50.6
53.4
49.9
48.3
50.6
47.7
48.0
50.8
47.4
51.6
54.4
50.8
54.2
57.4
53.2
54.7
58.1
53.7
51.2
54.0
50.4
48.2
50.5
47.6
47.2
49.5
46.7
50.5
53.3
49.8
54.9
53.9
54.7
58.1
53.7
51.3
54.1
50.5
48.3
50.7
47.8
48.5
50.8
47.9
51.8
54.6
51.0
54.9
53.9
54.7
58.0
53.6
51.3
54.1
50.5
47.5
49.8
46.9
48.1
49.6
47.4
50.6
53.3
49.8
54.5
57.8
53.5
53.8
57.0
52.7
50.7
53.5
49.9
46.8
49.1
46.3
46.4
48.6
45.8
48.8
51.5
48.0
51.0
54.2
49.9
49.4
52.2
48.4
42.6
45.0
42.0
34.5
35.9
45.9
49.5
45.8
50.6
54.8
50.5
51.6
55.2
51.5
49.1
52.2
48.8
46.7
49.2
46.3
47.7
50.1
47.0
51.3
54.4
50.5
54.4
57.9
53.5
54.3
57.8
53.4
50.4
53.3
49.6
47.8
50.2
47.1
48.5
50.9
47.8
52.2
54.6
51.5
55.1
54.5
53.9
57.5
53.2
50.4
53.4
49.8
47.5
49.9
47.0
48.1
50.6
47.6
51.6
54.7
51.0
54.6
58.3
54.0
54.1
57.7
53.6
50.7
53.7
50.2
47.7
50.3
47.2
48.3
50.9
47.8
51.9
54.9
51.4
54.7
58.4
54.2
54.2
57.8
53.7
50.8
53.9
50.2
48.0
50.4
47.5
48.4
50.9
47.8
51.5
55.0
51.1
54.5
58.3
54.1
53.9
57.6
53.5
50.3
53.3
49.9
47.4
49.9
47.0
47.9
50.5
47.5
51.3
54.5
51.0
54.0
57.9
53.8
53.5
57.3
53.3
50.0
53.0
49.6
47.7
49.9
47.3
47.9
50.5
47.5
51.4
54.6
50.9
53.8
57.6
53.3
53.1
56.8
52.7
49.5
52.5
49.0
46.3
48.8
45.8
46.3
48.8
45.8
48.6
51.7
48.1
50.5
54.1
50.0
47.6
50.9
47.1
40.7
43.1
40.4
32.7
33.7 31.4
30.5
37.6
40.3
38.6
44.8
48.8
46.4
48.7
53.5
50.8
48.8
53.2
50.7
46.1
49.7
47.6
45.3
48.5
46.6
46.9
51.1
48.9
50.6
55.1
52.4
53.1
58.0
55.2
51.3
55.9
53.2
47.5
51.0
48.9
45.6
48.7
46.8
48.5
52.2
50.0
51.9
56.6
53.9
52.4
57.2
54.4
51.5
56.1
53.4
47.6
51.2
49.0
46.4
49.6
47.6
48.3
51.9
49.7
51.8
56.5
53.7
52.1
56.8
54.1
50.5
54.8
52.2
47.3
50.8
50.2
46.9
54.0
53.5
45.0
53.2
64.8
67.2
69.5
66.1
58.7
49.4
60.4
69.4
72.2
78.7
73.1
63.7
47.8
58.1
67.9
73.3
74.5
65.3
52.7
68.5
62.0
48.7
53.2
53.8
46.3
49.5
48.1
48.5
52.1
49.8
52.1
56.7
53.9
53.8
58.7
55.7
51.7
56.2
53.5
48.4
52.0
49.8
47.0
50.2
48.2
48.4
52.0
49.8
52.3
56.9
54.1
52.7
57.4
54.6
51.7
56.2
53.5
48.2
51.7
49.5
46.2
49.4
47.4
47.9
51.5
49.2
51.8
56.4
53.6
53.2
58.3
55.3
51.1
54.9
52.2
46.6
50.0
47.9
45.1
48.0
46.1
46.3
49.8
47.6
49.1
53.5
50.8
49.4
54.1
51.3
42.8
48.6
51.6
50.1
47.0
46.1
49.1
52.9
54.2
51.9
48.4
47.0
50.0
53.1
54.9
51.9
48.8
46.9
49.2
52.9
54.2
51.8
48.1
46.6
48.3
50.9
49.9
45.1
37.3
45.4
50.2
47.6
45.6
52.2
55.1
53.4
49.6
48.8
52.0
56.5
58.1
55.4
51.1
49.5
52.9
56.7
58.7
55.3
51.5
49.4
52.1
56.5
57.9
55.3
50.9
49.2
51.3
54.4
53.5
48.1
39.2
39.1
42.2
40.4
42.8
48.6
51.6
50.0
47.0
46.1
49.0
52.8
54.2
51.9
48.4
47.0
49.9
53.0
54.8
51.9
48.7
46.9
49.2
52.9
54.2
51.7
48.1
46.6
48.3
50.7
49.9
45.0
37.2
29.2
32.2
33.3
33.0
32.4
32.6
34.0
35.6
35.7
34.3
33.5
33.6
34.4
35.6
35.6
34.4
33.6
33.5
34.2
35.3
35.2
33.8
32.4
32.4
32.9
33.2
31.7
28.5
24.3
32.3
35.9
37.0
36.7
35.9
36.2
37.9
39.5
39.6
38.2
36.9
37.0
38.4
39.7
39.8
38.3
36.9
36.8
38.1
39.5
39.3
37.7
36.0
35.5
36.1
36.6
34.9
31.0
26.2
34.2
38.1
39.4
39.0
38.1
38.5
40.2
41.8
42.0
40.6
39.4
39.1
40.6
42.1
42.2
40.9
39.3
39.2
40.4
41.8
41.9
40.2
38.3
37.7
38.4
38.9
36.9
32.8
27.5
35.3
39.5
40.9
40.6
39.8
40.3
42.0
43.5
43.7
42.3
41.0
41.1
42.3
43.8
44.0
42.4
41.0
41.0
42.3
43.7
43.5
41.8
39.7
39.4
40.0
40.3
38.2
34.0
28.5
36.2
40.5
42.0
41.7
40.9
41.3
43.1
45.0
45.1
43.5
42.0
42.3
43.8
45.3
45.4
43.8
42.0
42.2
43.6
45.0
44.8
43.0
41.0
40.6
41.2
41.4
39.3
34.9
29.2
36.9
41.3
42.8
42.4
41.7
42.1
44.0
45.9
46.0
44.5
43.1
43.1
44.7
46.2
46.3
44.7
43.1
43.0
44.4
45.8
45.7
43.8
41.8
41.2
41.8
42.1
39.9
35.5
29.7
37.1
41.6
43.1
42.8
42.2
42.6
44.5
46.2
46.3
44.9
43.4
43.4
44.9
46.5
46.6
45.0
43.5
43.3
44.7
46.2
45.9
44.1
42.1
41.5
42.0
42.5
40.1
35.6
29.9
37.2
41.6
43.1
42.9
42.2
42.7
44.5
46.2
46.5
45.1
43.7
43.7
45.2
46.8
46.8
45.3
43.4
43.6
45.0
46.4
46.2
44.4
42.4
41.9
42.4
42.5
40.3
35.8
29.9
37.5
41.9
43.6
43.4
42.7
43.2
45.0
46.6
46.8
45.3
43.8
43.8
45.3
46.9
47.0
45.4
43.8
43.7
45.0
46.5
46.5
44.7
42.6
42.1
42.6
42.7
40.6
36.0
30.2
37.6
42.1
43.8
43.5
42.8
43.3
45.1
46.8
47.0
45.5
44.0
44.0
45.5
47.1
45.6
44.0
43.8
45.2
46.7
46.5
44.7
42.6
41.9
42.5
42.8
40.7
36.1
30.2
37.5
42.0
43.6
43.4
42.7
43.2
45.1
46.6
46.8
45.3
43.9
43.9
45.4
47.0
47.0
45.5
44.0
44.0
45.4
46.8
46.5
44.7
42.5
42.1
42.6
42.8
40.6
36.1
30.2
37.3
41.7
43.2
43.0
42.2
42.8
44.6
46.2
46.6
45.1
43.6
43.6
45.1
46.8
46.8
45.3
43.8
43.7
45.0
46.4
46.2
44.4
42.4
41.8
42.3
42.4
40.4
35.9
30.1
37.2
41.6
43.2
42.9
42.5
42.7
44.6
46.4
46.5
45.0
43.6
43.6
45.1
46.6
46.7
45.1
43.6
43.5
44.9
46.3
46.0
44.2
42.2
41.6
42.1
42.3
40.3
35.7
30.0
36.9
41.3
42.9
42.8
41.8
42.3
44.2
45.8
46.1
44.6
43.0
43.0
44.6
46.3
46.3
44.7
42.9
43.1
44.5
45.9
45.7
43.9
41.9
41.3
41.9
42.1
40.0
35.5
29.7
36.3
40.6
42.2
41.9
41.1
41.6
43.4
45.0
45.1
43.7
42.3
42.4
43.7
45.3
45.4
43.8
42.3
42.2
43.6
45.1
44.9
43.1
41.1
40.5
41.1
41.4
39.4
34.9
29.3
35.4
39.5
41.0
40.7
39.9
40.4
42.1
43.8
43.8
42.5
41.0
41.1
42.6
43.9
44.1
42.4
40.8
40.7
42.4
43.8
43.5
41.8
39.9
39.4
39.9
40.2
38.3
34.0
28.5
34.2
38.2
39.6
39.2
38.4
38.8
40.5
42.1
42.3
40.9
39.5
39.4
40.9
42.2
42.3
40.8
39.2
39.1
40.4
41.8
41.8
40.1
38.2
37.6
38.4
38.8
37.1
33.0
27.7
32.3
36.0
37.6
37.1
36.3
36.7
38.0
39.5
39.7
38.1
36.7
36.7
38.4
39.9
39.9
38.5
36.6
36.9
38.2
39.6
39.4
37.8
36.0
35.6
36.2
36.6
35.0
31.2
26.2
29.4
32.5
33.9
33.6
32.9
33.2
34.4
35.7
35.8
34.8
33.6
33.6
34.8
35.7
35.7
34.6
33.4
33.2
34.3
35.4
35.3
34.0
32.5
32.0
32.5
32.8
31.8
28.6
37.3
42.7
45.0
42.6
43.0
50.7
54.1
50.9
43.2
46.6
55.9
60.1
56.3
47.1
46.8
56.2
56.5
47.3
43.4
51.3
54.8
51.5
43.7
37.9
43.5
45.9
43.4
37.5
56.4
61.0
62.3
57.1
50.7
49.5
47.4
45.7
45.5
47.0
49.4
50.6
49.2
47.8
47.0
48.1
50.1
51.1
50.1
48.2
47.0
47.7
49.4
50.1
48.8
46.5
45.2
45.4
46.2
45.5
42.0
36.4
60.7
63.0
68.4
63.7
55.9
53.9
51.1
49.5
49.3
50.6
53.3
55.1
54.0
51.9
50.5
52.2
54.6
54.9
53.8
51.6
50.5
51.6
54.1
55.0
53.5
51.0
49.4
49.6
50.5
49.7
45.5
39.3
62.7
71.1
69.7
63.3
58.1
56.9
54.2
51.7
51.5
53.6
56.2
57.6
56.3
54.1
53.1
54.6
56.9
58.5
57.3
55.0
53.8
55.0
57.0
57.9
56.4
53.6
51.7
51.9
52.9
52.4
48.0
41.3
63.9
72.5
70.9
63.1
59.0
58.4
55.6
53.1
52.9
54.8
57.7
59.1
58.3
56.1
54.7
56.0
58.9
59.7
58.6
56.2
55.1
56.1
58.6
59.5
58.0
55.2
53.6
53.8
54.7
53.7
49.2
42.3
64.2
72.0
72.2
67.0
60.6
59.2
56.2
54.2
54.1
56.0
59.0
60.5
59.2
56.9
55.9
57.5
59.8
61.3
60.1
57.7
56.5
57.6
59.5
60.4
58.8
55.9
54.3
54.9
55.8
54.8
49.6
42.6
64.1
67.1
73.6
69.3
60.9
59.2
56.3
54.3
54.2
56.1
59.0
60.5
59.2
57.0
56.0
57.3
59.9
60.9
60.1
57.7
56.2
57.9
59.7
60.6
59.1
56.4
54.8
54.4
55.3
54.7
50.1
42.7
65.4
74.3
72.9
66.3
60.2
58.6
55.9
54.0
53.8
55.8
58.7
60.1
58.9
56.7
55.6
57.0
59.4
60.6
59.4
57.0
55.8
56.9
58.6
59.5
57.9
55.1
53.6
53.6
54.6
53.5
49.1
42.5
66.3
73.1
64.1
58.7
57.2
54.3
52.3
52.2
54.1
56.9
58.3
57.2
54.9
53.9
55.2
57.6
58.8
57.6
55.3
54.1
55.2
57.1
57.9
56.2
53.5
51.9
52.3
53.3
52.3
48.0
41.1
64.1
71.7
71.1
64.6
57.3
54.7
51.9
49.9
49.7
51.5
54.3
55.7
54.5
52.4
51.4
52.7
55.0
56.2
55.0
52.7
51.6
52.7
54.5
55.4
53.9
51.2
49.7
50.0
51.1
50.3
46.1
39.7
62.3
64.5
69.7
63.8
53.9
50.6
48.0
46.2
46.0
47.7
50.1
51.4
50.4
48.5
47.6
48.7
50.9
51.6
50.5
48.5
47.5
48.8
50.4
51.2
49.8
47.2
46.0
46.0
47.1
46.4
42.8
36.9
62.2
69.7
66.1
57.0
46.1
44.0
42.3
40.9
40.8
42.2
44.2
45.2
44.5
43.0
42.3
43.2
44.9
45.4
44.6
43.0
42.2
43.3
44.5
45.1
44.0
42.0
40.7
41.1
41.7
41.1
38.1
33.3
61.7
68.4
63.5
38.7
36.7
36.6
35.6
35.1
35.3
36.3
37.5
38.2
37.9
37.0
36.6
37.2
38.2
38.7
38.2
37.3
36.8
37.2
38.1
38.4
37.7
36.4
35.5
35.2
35.4
34.6
32.3
57.8
62.2
51.2
52.6
49.2
47.2
45.4
47.3
40.6
41.6
47.4
50.5
50.4
47.2
41.4
34.0
47.0
53.3
52.9
45.8
36.9
46.3
52.6
56.0
55.9
52.1
45.2
36.6
40.1
45.7
48.6
48.5
45.5
40.0
67.8
75.8
80.0
80.1
75.8
68.0
58.2
80.7
90.3
95.8
95.7
89.9
79.1
65.9
86.0
96.7
102.6
96.1
84.0
69.1
81.3
90.9
96.5
96.3
90.4
79.3
65.7
68.6
76.7
81.0
80.9
76.4
68.3
68.8
75.9
79.7
79.2
74.4
66.0
80.4
90.2
95.3
94.7
88.2
76.9
63.3
85.3
96.3
101.3
94.2
81.6
66.8
80.5
90.3
95.3
94.7
88.3
77.1
63.8
68.9
75.9
79.7
79.2
74.4
66.3
56.5
15.5
17.9
19.9
21.4
22.3
22.9
23.2
23.2
23.0
22.5
21.6
20.1
18.4
17.0
20.1
22.7
24.4
25.7
26.3
26.7
26.8
26.4
25.7
24.6
23.1
20.7
17.9
21.2
24.1
26.2
27.6
28.4
28.7
28.7
28.5
27.7
26.5
24.6
22.0
18.2
21.5
24.6
26.8
28.1
29.0
29.0
28.3
27.0
25.0
22.3
18.1
21.6
24.6
26.7
28.0
28.9
29.2
29.0
28.3
27.0
25.0
22.3
17.8
21.2
24.1
26.1
27.4
28.2
28.6
28.7
28.3
27.7
26.5
24.6
22.0
16.8
19.8
22.4
24.3
25.4
26.1
26.5
26.5
26.3
25.7
24.6
23.0
20.6
17.6
19.6
21.0
22.1
22.7
22.9
23.0
22.8
22.3
21.5
20.1
18.4
45.4
51.0
46.3
46.3
51.0
45.3
45.2
50.9
51.2
46.1
46.2
51.3
50.9
45.1
41.0
45.2
45.5
41.6
41.7
45.6
45.3
34.7
36.4
34.8
35.0
36.5
34.5
38.4
40.8
38.7
38.9
40.8
38.2
40.2
40.5
40.8
40.0
38.9
41.4
39.1
39.4
41.3
38.6
35.4
37.3
35.5
35.7
37.2
35.2
51.7
57.2
59.7
61.8
63.3
64.0
63.2
61.8
60.1
57.1
51.0
59.0
66.1
69.7
71.4
73.4
74.4
73.3
71.5
69.6
65.9
58.5
63.4
71.5
75.5
77.6
79.7
80.3
79.6
77.6
75.4
71.3
62.4
63.8
71.9
75.9
78.8
80.9
80.4
78.2
76.0
72.2
63.2
62.5
70.3
73.8
76.5
78.5
79.0
78.4
76.4
74.2
69.3
61.3
59.4
66.1
70.0
71.6
73.9
74.8
73.7
71.3
69.2
65.3
58.0
54.2
60.6
63.3
65.4
66.5
67.9
66.3
64.5
62.7
59.3
53.3
48.1
52.9
55.4
56.5
58.2
58.8
57.6
56.7
54.8
51.8
61.9
65.0
66.3
64.4
59.7
74.4
78.8
80.1
77.3
70.9
83.4
90.6
92.9
89.8
80.8
89.6
100.6
104.9
102.4
89.9
101.6
116.6
117.5
115.4
109.3
71.6
83.0
92.3
98.8
103.1
105.9
107.6
108.6
109.6
112.8
124.5
125.7
125.7
124.2
121.5
117.8
104.3
99.8
95.5
88.8
79.7
68.1
56.1
77.1
90.6
101.7
109.2
114.3
117.4
119.3
121.1
122.8
127.0
131.7
132.2
131.7
130.6
128.9
125.7
118.1
112.5
106.5
98.3
86.9
73.3
59.4
80.0
94.3
106.3
114.3
119.9
123.3
125.6
127.4
128.8
132.2
134.0
132.2
131.5
128.9
124.9
118.2
112.0
103.0
90.8
76.1
61.0
79.5
93.7
105.7
113.6
119.3
122.7
124.9
126.4
128.1
130.0
131.4
130.9
130.7
129.1
128.6
126.3
123.4
117.9
111.5
102.6
90.6
75.9
60.9
76.0
89.0
99.8
107.0
112.2
115.3
117.3
118.7
120.2
122.0
122.0
121.9
121.4
120.9
119.9
117.8
115.3
111.0
105.2
96.8
86.0
72.6
58.8
69.8
80.5
89.1
95.4
99.8
102.4
104.1
105.6
107.2
107.8
107.9
107.8
107.3
106.8
106.1
104.4
102.1
98.8
93.9
86.9
77.9
67.2
56.5
60.8
60.8
56.3
56.8
67.3
73.7
73.4
66.6
60.2
72.2
79.1
71.4
57.3
68.0
74.5
74.3
67.5
49.8
57.6
62.1
62.0
57.4
40.1
40.4
38.1
45.9
50.7
51.3
47.1
53.7
60.6
61.5
55.5
58.8
67.2
68.3
61.0
60.6
69.5
62.9
59.2
67.5
68.5
61.3
54.2
61.3
62.1
55.9
46.6
51.5
52.0
47.7
38.1
40.7
41.0
38.6
68.3
75.4
80.9
84.5
86.4
87.1
86.8
85.3
82.1
77.6
70.9
62.5
66.7
78.3
87.6
94.6
99.0
101.4
102.2
101.8
100.1
96.3
90.5
81.8
70.8
71.8
85.5
96.7
104.5
109.8
112.3
113.2
112.7
110.8
106.6
99.8
89.6
76.7
74.1
88.7
100.4
108.7
114.4
116.9
117.3
115.2
110.8
103.7
92.8
79.1
73.1
87.7
98.8
107.1
112.0
114.8
115.8
115.2
113.5
109.0
102.0
91.4
77.9
69.0
81.6
91.8
99.1
103.8
106.1
107.0
106.5
104.6
100.8
94.4
85.1
72.9
62.5
72.8
80.7
86.6
90.3
92.4
93.1
92.8
91.2
87.9
82.7
75.2
65.7
63.1
68.1
71.8
74.4
76.0
77.0
77.4
77.2
76.5
75.5
73.7
70.5
66.0
59.9
52.1
73.3
79.8
84.4
87.6
89.6
90.8
91.2
91.0
90.1
89.1
86.9
82.9
77.1
69.0
58.6
80.7
88.6
93.9
97.5
99.8
101.1
101.6
101.3
100.5
99.3
96.9
92.3
85.4
75.9
63.7
84.4
92.9
98.8
102.7
105.1
106.5
107.1
106.8
105.9
104.6
101.9
96.9
89.6
79.3
66.3
85.3
93.9
99.9
103.9
106.4
107.9
108.2
107.2
105.8
103.1
97.9
90.5
80.1
66.9
84.3
92.8
98.6
102.5
104.9
106.4
106.9
106.6
105.7
104.4
101.7
96.7
89.4
79.2
66.2
80.4
88.2
93.5
97.1
99.4
100.7
101.2
100.9
100.1
98.9
96.4
91.8
85.0
75.5
63.4
72.7
79.1
83.6
86.5
88.6
89.8
90.1
90.0
89.3
88.2
86.0
82.1
76.3
68.3
57.9
62.5
67.3
70.8
73.4
74.8
75.8
76.3
76.1
75.5
74.6
72.7
69.5
65.1
58.9
32.4
32.2
39.5
45.7
47.6
46.2
43.7
44.2
47.1
49.9
48.1
45.6
45.7
46.0
48.9
51.7
51.9
48.9
45.9
45.4
47.3
49.6
48.0
43.0
34.5
43.4
50.8
52.9
50.7
47.5
47.7
51.2
54.8
54.5
51.1
48.3
48.7
52.6
56.6
53.1
49.2
48.5
51.5
54.5
53.1
47.1
33.8
42.1
49.1
51.1
49.1
46.1
46.3
49.6
53.1
53.1
50.0
47.0
47.1
50.7
54.4
54.7
51.3
47.6
47.0
49.7
52.4
51.0
45.3
42.7
48.8
50.6
48.7
46.4
46.8
50.2
53.8
53.7
50.5
47.4
47.9
50.8
53.9
53.6
50.1
46.7
46.5
49.1
51.5
49.6
44.1
36.4
45.6
52.5
54.2
51.9
48.9
49.6
53.4
57.6
57.5
53.7
49.9
50.5
54.1
57.4
53.3
49.2
49.1
52.4
55.3
53.5
47.2
34.9
42.9
48.9
50.6
48.7
46.4
46.7
50.1
53.7
53.7
50.5
47.4
47.8
50.8
53.8
53.5
50.1
46.7
46.6
49.2
51.6
49.8
44.1
29.8
37.7
45.2
49.5
49.1
46.4
45.3
47.4
51.2
52.8
51.1
47.2
45.2
46.3
49.1
49.5
45.2
37.6
30.9
39.7
48.4
53.2
52.7
49.2
47.8
50.2
54.8
54.6
50.0
47.7
49.1
52.6
53.2
48.3
39.5
30.8
29.8
37.6
45.2
49.5
49.1
46.3
45.2
47.2
51.1
52.7
51.0
47.2
45.1
46.2
49.1
49.4
45.1
37.5
40.6
47.7
50.4
49.2
46.5
46.4
49.3
53.0
53.8
51.6
47.7
47.0
49.6
53.2
54.1
51.3
47.5
46.5
48.6
51.3
51.0
46.8
34.0
43.0
51.0
54.2
52.5
49.1
48.9
52.4
56.8
57.7
55.0
50.4
49.6
52.7
57.0
54.7
50.2
49.0
51.7
55.1
55.1
50.2
40.7
47.7
50.5
49.3
46.5
46.4
49.3
53.0
53.9
51.6
47.8
47.1
49.7
53.3
54.2
51.4
47.5
46.5
48.7
51.4
51.1
46.8
43.2
43.4
39.5
43.2
48.5
43.5
43.0
48.3
48.4
43.3
38.9
42.9
42.9
39.0
52.3
57.1
58.7
57.6
54.4
68.5
76.2
78.9
78.2
73.5
84.7
96.4
100.3
99.7
92.9
79.6
63.2
96.0
110.1
115.3
114.2
106.3
89.9
70.4
103.1
118.3
123.9
122.8
114.4
96.7
74.7
107.0
121.8
128.0
127.3
118.5
99.2
76.9
108.5
123.6
129.7
119.4
100.7
78.0
107.7
123.6
129.8
128.6
119.1
100.5
77.9
106.1
121.6
127.6
126.4
117.2
98.7
76.6
101.1
115.2
120.8
119.7
111.3
93.9
73.2
90.4
102.5
107.1
106.3
99.1
84.3
66.9
74.3
82.7
86.4
85.7
80.2
69.9
57.5
57.6
63.0
65.3
64.8
61.3
55.7
16.8
18.3
18.9
19.5
19.6
19.0
18.2
17.0
15.3
18.1
19.7
20.4
21.1
21.1
20.5
19.8
18.7
16.3
19.1
20.8
21.5
22.5
22.5
21.8
20.9
19.7
17.3
19.9
21.6
22.3
23.4
23.5
22.7
21.8
20.4
17.6
20.1
21.8
22.7
23.7
23.2
22.1
20.7
17.6
19.9
21.6
22.4
23.4
23.5
22.8
21.8
20.4
17.6
19.2
20.9
21.6
22.6
22.7
22.0
20.9
19.7
17.3
18.2
19.8
20.5
21.3
21.3
20.7
19.9
18.7
16.4
16.9
18.4
19.0
19.6
19.6
19.1
18.3
17.0
16.8
17.9
18.2
19.1
20.7
20.6
20.4
21.1
20.8
20.7
20.6
19.3
18.7
18.0
16.8
15.4
15.9
18.3
19.6
19.7
21.0
22.9
22.8
22.4
23.5
22.8
22.9
22.9
21.0
20.4
19.7
18.2
16.2
16.8
19.7
21.1
21.3
22.8
24.9
24.9
24.5
26.0
24.8
24.9
24.8
22.6
21.8
21.1
19.5
17.0
17.7
20.9
22.5
22.6
24.4
26.6
26.5
26.2
28.0
26.6
26.3
26.4
24.0
23.0
22.3
20.7
17.8
18.2
21.4
23.2
23.4
25.2
27.8
27.5
27.1
29.0
27.7
27.3
27.5
25.1
23.8
23.0
21.2
18.4
18.3
21.8
23.5
23.7
25.5
28.3
28.0
27.6
28.0
28.0
28.1
25.3
24.3
23.5
21.6
18.5
18.3
21.8
23.5
23.7
25.5
28.3
27.9
27.6
28.0
27.9
28.0
25.3
24.3
23.5
21.4
18.4
18.2
21.4
23.2
23.4
25.2
27.7
27.4
27.1
28.9
27.7
27.3
27.5
25.0
23.9
22.9
21.1
18.3
17.7
20.8
22.4
22.5
24.2
26.5
26.4
26.1
27.9
26.5
26.2
26.3
23.9
22.9
22.2
20.6
17.8
16.8
19.7
21.1
21.3
22.7
24.8
24.8
24.3
25.8
24.5
24.7
24.7
22.5
21.6
21.1
19.5
16.9
16.1
18.3
19.6
19.8
21.0
22.7
22.7
22.4
23.3
22.6
22.8
22.6
21.0
20.2
19.6
18.1
16.1
55.1
60.1
64.0
66.5
68.1
68.6
68.8
68.9
68.2
67.5
67.1
65.9
64.8
63.5
61.2
58.1
54.0
48.4
66.7
74.3
79.7
82.9
84.7
85.0
85.0
84.5
83.3
82.4
81.5
80.3
79.0
77.3
74.5
70.7
65.0
57.1
76.7
86.7
93.5
97.2
98.7
98.6
97.8
96.4
94.7
93.2
92.2
90.5
89.0
86.9
84.0
79.5
72.5
62.9
82.5
93.8
101.1
104.8
105.8
104.3
102.0
99.3
96.6
94.4
93.0
90.9
89.1
87.1
84.0
79.4
72.5
62.8
84.2
95.8
102.8
106.0
102.2
97.5
92.9
88.6
85.7
82.9
80.8
79.2
77.2
74.4
70.5
64.6
56.6
84.1
95.5
102.1
104.4
102.8
96.6
88.9
82.1
74.2
68.6
66.8
65.6
64.4
62.8
60.6
57.6
53.5
82.5
93.4
99.5
100.9
97.7
89.7
78.4
77.1
86.5
91.8
92.5
88.1
79.0
65.0
67.2
74.5
78.3
78.3
74.5
66.0
56.7
Description Symbol Avg Max Min Max/Min Avg/Min
AC Garage 193 22.8 fc 29.4 fc 15.1 fc 1.9:1 1.5:1Calc Zone #21 47.9 fc 56.8 fc 28.9 fc 2.0:1 1.7:1Calc Zone #22 49.7 fc 57.7 fc 34.8 fc 1.7:1 1.4:1Calc Zone #23 45.9 fc 56.6 fc 29.7 fc 1.9:1 1.5:1Calc Zone #24 49.6 fc 58.0 fc 32.8 fc 1.8:1 1.5:1Cat Holding 163,164 32.9 fc 42.9 fc 0.0 fc N/A N/AClassroom 137 81.4 fc 102.8 fc 57.8 fc 1.8:1 1.4:1Corridor 107 45.3 fc 59.4 fc 20.7 fc 2.9:1 2.2:1Corridor 132 (North) 50.9 fc 58.8 fc 32.3 fc 1.8:1 1.6:1Corridor 132 (South) 47.4 fc 57.8 fc 27.6 fc 2.1:1 1.7:1Corridor 159 50.6 fc 58.2 fc 34.2 fc 1.7:1 1.5:1Corridor 160 51.5 fc 79.5 fc 30.2 fc 2.6:1 1.7:1Dog Holding 161,162 66.8 fc 82.0 fc 46.8 fc 1.8:1 1.4:1Dog Intake 175 86.6 fc 108.5 fc 51.4 fc 2.1:1 1.7:1Dog Room 153,154,155,157,158 40.5 fc 47.2 fc 24.2 fc 2.0:1 1.7:1
Statistics
Description Symbol Avg Max Min Max/Min Avg/Min
Electrical Closet 202 20.2 fc 23.8 fc 15.2 fc 1.6:1 1.3:1Foster Exam 138,140 80.2 fc 101.9 fc 55.7 fc 1.8:1 1.4:1Front Office 106 80.7 fc 106.2 fc 48.0 fc 2.2:1 1.7:1Locker Room 197,198 54.1 fc 70.6 fc 37.6 fc 1.9:1 1.4:1Meeting Room 103 94.3 fc 130.3 fc 48.0 fc 2.7:1 2.0:1Open Workstation 118 52.8 fc 75.2 fc 29.3 fc 2.6:1 1.8:1Sugery 170 92.6 fc 117.8 fc 59.3 fc 2.0:1 1.6:1Surgery Prep 168 103.8 fc 134.3 fc 55.5 fc 2.4:1 1.9:1T&S 199 43.4 fc 48.6 fc 38.5 fc 1.3:1 1.1:1T&S 199 (Shower) 59.6 fc 59.7 fc 59.5 fc 1.0:1 1.0:1Typical Cat Comm 133,134,135,136 46.7 fc 56.8 fc 33.2 fc 1.7:1 1.4:1Typical Cat Room 144,145,146 24.0 fc 29.3 fc 15.3 fc 1.9:1 1.6:1Typical Office 115,114,113,112,111,110,109,108 47.8 fc 60.4 fc 36.9 fc 1.6:1 1.3:1Typical Office 189,188,187 64.6 fc 79.4 fc 49.1 fc 1.6:1 1.3:1Typical Toilet Rooms 131,130,126,127,104,105,183,184,195,196,199,201 46.7 fc 51.4 fc 40.9 fc 1.3:1 1.1:1
Statistics
SHEET NUMBER:
DRAWING TITLE:
DATE ISSUED:
PROJECT NUMBER:
PROJECT SET:
I HEREBY CERTIFY THAT THESE DOCUMENTS WERE PREPARED OR APPROVED BY ME, AND THAT I AM A
DULY LICENSED PROFESSIONAL ENGINEER UNDER THE LAWS OF THE
STATE OF MARYLAND. LICENSE NUMBER: #xxxxx
EXPIRATION DATE: mm-dd-yyyy
CO
NSU
LTAN
T:SE
AL
ALL DRAWINGS ARE PROTECTED BY FEDERAL COPYRIGHT BY MANNS WOODWARD STUDIOS, INC. AND CAN NOT BE REPRODUCED OR MODIFIED IN ANY MANNER WITHOUT WRITTEN PERMISSION. DOCUMENTS MAY NOT BE USED IN PART OR WHOLE TO DEVELOP THE DESIGN OF ANOTHER BUILDING WITHOUT EXPRESS WRITTEN PERMISSION BY MANNS WOODWARD STUDIOS.