ELECTRIC POWER SYSTEM GROUNDING By Steve Blume [email protected] (760) 612-8488
29

ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Mar 18, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

ELECTRIC POWER SYSTEM GROUNDING

BySteve [email protected](760) 612-8488

GND1

Page 2: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Presentation Outline

Electric Power System Grounding

▪ 3-Phase Power Systems▪ Reasons for Grounding and Bonding▪ Substation, Transmission, and Distribution Grounding▪ Power Faults and Lightning Strikes▪ Fault current distribution▪ Ground Potential Rise (GPR)▪ Touch and Step Potentials▪ Safety

2

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 3: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Single Phase Generation

3-Phase Power Systems

N

S

+ Volts

- Volts

Faraday’s Law:

Voltage is produced on any conductor in

a changing magnetic field!

3

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 4: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

N

S

+ Volts

- Volts

Three Phase Generation

3-Phase Power Systems

4

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 5: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

3-Phase AC Generator

3-Phase Generator

N

S

Exciter

ControlsAC Voltage Out

Field/Rotor

Stator

Slip Rings

5

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 6: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

ToLoad

Winding 2

Winding 3 Winding 1

Delta

Winding 3

Winding 1

Winding 2

WYE

Neutral

ToLoad

Symmetrical Connections

3-Phase Power Systems

6

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 7: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Neutral vs. Ground vs. Bond

3-Phase Power Systems

Neutral

Ground

BondNeutral

Winding 2

Winding 1

Winding 3

To the loadWYE

L

L

L

N

▪ Grounding: the neutral is connected to earth via ground rods, grids, or conductors. Unbalanced neutral currents flow through the earth connection.

▪ Bonding: electrical connections between equipment and grounded conductors to provide equipotential during faults.

7

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 8: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

3-Phase Power Systems

▪ Control power fault and Lightning strike currents▪ Protect equipment and trip energizing equipment▪ Equipotential Grounding▪ Effects of Ground Potential Rise▪ Touch and Step Potentials▪ Detect and minimize unbalanced currents

8

Reasons for Grounding and Bonding

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 9: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

System Grounding

3-Phase Power Systems

9

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 10: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Substation Grounding

3-Phase Power Systems

Ground grids

FenceStructures

Equipment

10

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 11: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Rod Line

60º

60º

60º shield angle is typical

Shield Wires andOptical Ground Wires

Lightning Protection through Grounding

Transmission Line Shielding and Grounding

3-Phase Power Systems

11

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 12: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Distribution Lines: Wye Configuration

3-Phase Power Systems

A

B

C

N

A

N

Multi-GroundedNeutral

Grounded neutral

Multi-grounded Neutral: At least four times per mile per the National Electric Safety Code

12

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 13: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Distribution Lines: Delta Configuration

3-Phase Power Systems

A

B

C

A

B

Delta three-phase distribution lines use three wires, no neutral. Transformer tanks and lightning arresters are connected to ground rods at each pole.

No grounded neutral!

13

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 14: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Source Balanced 3-Phase Currents

NO Earth Return Current!

GridGrid

Load

Generator Transformer

Balanced Conditions

3-Phase Power Systems

14

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 15: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Ground Grid Wires Ground Rods

Lightning RodsPower Fault

or Lightning Strike

Substation Fault

Power System Fault

15

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 16: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

G

Phase Currents

Earth Return Current

XFMRGPRs

GridGrid

Assumptions• Homogenous Soil (i.e., round contours)• Power Fault at substation transformer bushing

Ground Potential Rise (GPR) – unbalanced current

Power System Fault

16

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 17: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

G

Un-Balanced 3-Phase Current

Grid

XFMR

Neutral Currents

Shield Wire Currents

GPRs

Grid

Earth Return Current

Multiple Ground Paths and GPR’s

Power System Fault

17

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 18: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

NO Earth Return Currents!!!

NO GPR!!!

Current flow through grid: YES

Voltage drop on grid: YES

G

Un-Balanced 3-Phase Current

XFMR

Metropolitan Grids

Power System Fault

18

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 19: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Homogeneous Soil

300 volt point

GPR“Zone of Influence”

x

SubstationGnd Grid

GPR - Zone of Influence

Power System Fault

19

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 20: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

SubstationsStructures

Distance From Fault

Touch StepGround Potential Rise

Ground Grid

Touch & Step Potentials

Electrical Grounding Safety

20

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 21: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Human Characteristics

Electrical Grounding Safety

The average 155-lb man takes the following currents:▪ 1.2ma to produce a slight tingling feeling, called perception threshold▪ 9ma can produce a painful shock, but still below lock-on conditions▪ 16ma can cause the loss of muscle control▪ 23ma can cause difficulty breathing▪ 50ma approximately can cause burning▪ 100ma for 3 seconds can cause heart fibrillation▪ 1 amp for 30ms can cause heart fibrillation

21

NOTE: Current path through body is a critical factor!

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 22: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

2-Ways to be Safe!

Electrical Grounding Safety

CONDUCTION – Equipotential GroundingThe use of materials in situations where good conduction (low resistance) will result in small potential differences and high current flow. (Ground Jumpers)

ISOLATION – Personal Protective EquipmentThe use of materials in situations where good insulation (high resistance) will result in large voltage differences and low current flow. (Rubber Insulation)

22

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 23: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Conduction - Ground Source Preferences

Electrical Grounding Safety

1. Substation Ground Grid2. Multi-Grounded Neutral (MGN)3. Steel Tower or Steel Pole4. Driven or Screw-in Ground Rods5. Anchor Rods

23

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 24: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

YOUYOUR

JUMPERS

FAULT CURRENT

Earth

"TRUE" GROUND

Conduction - Jumper Voltage Drop Protection

Electrical Grounding Safety

24

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 25: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Example:

Single Point

Grounding a

metal lattice

tower

Electrical Grounding SafetyConduction - Transmission Structure Safety

Example: Single Point Grounding for one worker

on a wooden “H” frame structure with overhead

ground wiresSteel Towers Wood Structures 25

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 26: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Conduction - Distribution Structure Safety

Electrical Grounding Safety

Single Point Grounding

Example: Worker minimizing

exposure to touch potential by

operating equipment controls

from a conductive mat

Vehicle Arrangement26

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 27: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Neutrals and Lightning Arresters are Grounded.

Conduction - Underground Equipment

Electrical Grounding Safety

27

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 28: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Isolation - Personal Protective Equipment (PPE)

Electrical Grounding Safety

28

Co

pyr

igh

t P

rote

cted

–B

lum

e C

on

sult

ing

Page 29: ELECTRIC POWER SYSTEM GROUNDING · 2018-11-20 · Presentation Outline Electric Power System Grounding 3-Phase Power Systems Reasons for Grounding and Bonding Substation, Transmission,

Electric Power System Grounding

Any Questions?

Thank you!

BySteve [email protected](760) 612-8488