e....,.1111•- BUSINESS OFFICE AND CUSTOMER SERVICE TELEPHONE NUMBERS Customer Service Phone Number. 570-819-4844 or Toll-Free 1-800-962-1212. Staff is availableMonday through Fridayfrom 7:30 a.m. to 4:00 p.m. Customer Service Office. One UGI Center {Bldg. A-2) Wilkes-Barre, PA 18711-0600 Open Mon. through Fri., 7:30 a.m.- 4:00 p.m. Table of Contents.htm U G I Th is page last modffied: 07 August 2009 (individual sectionsindicate last date modified)
75
Embed
Electric Meter and Service Installations - UGI · Single-Phase Multi-Meter Trough, Center Wire Compartment Single-Phase, All-in-One Multi-Meter Trough Single-Phase, Stacked (Gangable)
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
e....,.1111•-
BUSINESS OFFICE AND CUSTOMER SERVICE TELEPHONE NUMBERS
Customer Service Phone Number.
570-819-4844 or Toll-Free 1-800-962-1212. Staff is available Monday through Friday from 7:30 a.m. to 4:00 p.m.
Customer Service Office.
One UGI Center {Bldg. A-2) Wilkes-Barre, PA 18711-0600 Open Mon. through Fri., 7:30 a.m.- 4:00 p.m.
Table of Contents.htm
U G I Th is page last modffied: 07 August 2009 (individual sections indicate last date modified)
FORWABD
This manual covers the general conditions that apply to the
furnishing of electricity on the UGI Corporation system, and must
be adhered to in all respects by those customers receiving electric
service from the Company,
Changes and additions to these rules will be required from
time to time, Revisions will be mailed to those persons on record
as having a copy of this manual.
Section 1
Section 2
TABLE OF CON'IEm.'S
Introductory Information
Business Office and Customer Service Phone Numbers •••••••••• •• • • • • • • • •
This manual presents the electric service requirements of the Company
relative to service entrances. metering, and the installation of certain
utilization equipment. The information given is not a complete set of rules
governing the installation of electric wiring or apparatus. It covers only
those points in which the customer, the architect, the engineer, the
electrical contractor, and the Company are mutually interested, and the
knowledge of which will serve to prevent unnecessary delays or expense in
furnishing service. Nothing contained herein is intended in any way to
conflict with the requirements of the National Electric Code or with any
municipal ordinance applying to electrical installations,
Special conditions may arise which would be impracticable to cover in
a book of this type, and to such cases the Company will be pleased to give
attention on request.
The information herein must not be construed to conflict, in any·way,
with the "Electric Service Tariff," issued by the Company,
1')/~1/i:1!1
DEFINITIONS
COMPANY--UGI Corporation, Electric Utility Division.
CUSTOMER--The corporation, municipality, governmental agency, association, partnership or individual served by or using electric service supplied by the Company.
VOLTAGE--Nwnerical voltages mentioned are to be construed as nominal values.
SERVICE--As used herein refers to the supply of the Company's product "electric energy" to the customer.
COMPANY POLE--A Company-owned pole or a pole owned by another utility company with whom the company has an agreement or understanding for joint use of poles.
SERVICE INSTALLATION--The connection between the Company's distribution system and the customer's service equipment is a service installation and is commonly referred to as "a service." This generally consists of:
Service Drop or Service Wires--That portion of an overhead service. installation supplied by the Company between.its pole or aerial support and the point of connection to the customer's service entrance conductors.
Service Lateral--That portion of an underground service installation supplied by the Company between its overhead or underground distribution mains and the point of connection to the customer's service equipment.
Service Entrance Conductors--That portion of an overhead or underground service installation supplied by the customer between the Company's service drop or service lateral and the customer's service equipment.
POINT OF DELIVERY--The point in or on a premises where the Company's overhead service drop or underground service lateral connects to the customer's service entrance conductors. The location is designated by the Company.
PREMISES--A building, group of buildings And/or contiguous parcels of land under the control of a customer-and devoted to the conduct of a single business. A building is one premises even though occupied by two or more customers. Adjoining buildings under one roof but separated completely from each other by vertical fire walls are considered as separate premises.
NATIONAL ELECTRICAL CODE--The standard as recommended by the National Fire Protection Association and adopted by the American National Standards Institute in effect at any given time for electrical wiring and apparatus.
NATIONAL ELECTRICAL SAFETY CODE--The rules published by the Institute of Electrical and Electronics Engineers applying to grounding, installation, maintenance and operation of electric supply, communication, utilization equipment, lines and facilities which have been adopted as standard by the American National Standards Institute.
COMPANY OFFICE-·The Business Office at 247 WYoming Avenue, Kingston, Pennsylvania.
SECTION 2 - GENERAL
A. Initial Inquiry - In order to avoid additional expense and minimize
delays, UGI should be contacted before work has started on any electric ser
vice installation. An authorized Company representative will specify the -service location and obtain information necessary to properly supply the
service and apply the provisions of the Collipany's tariff. The Company may
refuse to comnence service when, in the Company's opinion, the customer's
installation does not conform to UGI' s tariff. Furthemoie, the customer
is responsible for changes in the service installation required by the Com
pany before service is supplied.
B. Services Available - The Company supplies alternating current only,
at a llOlllinal frequency of 60 hertz. The min:lmm service size normally
accepted by the Company is 100 amp, single-phase, three wire. (Single
phase, two wire service is available for limited loads, such as, traffic
signals, small signs, telephone booths, etc.) Available voltages are as
specified in the Company's tariff. However, not all service voltages are
available in all areas. Before purchasing electrical equipment or proceeding
with any wiring, information regarding the type of service available should
be obtained from the Company.
c. customer Responsibility
1. Application for Service - The CUstoiaer must notify the Company
well in advance of the date service is desired. It may be necessary to
complete an application for service at the Company office and in some cases
deposits are required. (Note: The receipt of a Fire Underwriter's inspection
at the Company office does !!2! constitute an application for service.) The
following information must be supplied before service will be rendered:
customer account number (if not a new installation), Customer name, customer
12/3l/81 Page 2-1
phone number(s), service and mailing address, nearest UGI pole number
(10-digit), load data, and type of dwelling or business.
Z, Right-of-Way - Where necessary, the customer shall provide
an adequate right-of-way for UGI to supply service to bis premises. An
adequate right-of-way will consist of a strip of land as specified by the
Company which must remain open and accessible so that the Company can per
form line improvements, clearance, and maintenance as may be from time tQ
time required.
3. Tree Trimming - If tree tr1lDIDing is required to accOt11110date
the installation of any power lines on private property, it will be the
customer's responsibility to provide the initial trfaming as directed by
the Company. 'l'he Company will perform subsequent trinming as it considers
necessary to maintain adequate clearance to its facilities.
4. Inspections - The wiring and appliances on the premises of
the customer must be installed in accordance with and ,conform to the latest
rules and requirements of the National Electrical Code, and other such state
or municipal regulations as may be applicable. It will be the Customer's
responsibility to obtain all necessary electrical inspections prior to con--= nection by the Company. Furthermore, the Company shall have the right, but
shall not be obligated, to exsrn1ne the Customer's installation at the t:lme
service is first supplied or at a later time. If at any time, the Company
finds the wiring, fixtures, or appliances of the customer to be defective
or dangerous, the customer will be informed and service may be refused or
discontinued unless the condition is corrected. The Company's responsibility
extends only to the supply of service at the point of delivery.
5. Metering Devices and Equipment - The Customer shall provide,
without charge, a suitable location for the meter or rneters, transformer or
transformers, or other equipment of the Company along with an adequate point
lZ/31/81 Page Z-2
of attachment for the service drop. The location of these items will be
specified by the Company and must be of convenient access to meter readers
or inspectors. Meters must be located between four (4-) and six (6) feet
above final grade.
Tampering, interferring with, or breaking of seals on meters,
switches, or other equipment of the Company installed on the Customer's
premises is prohibited. Offenders will be prosecuted to the full extent of
the law.
6. Connection of Multiple Conductors - When a customer installs
a service entrance consisting of two or more conductors per phase, it is
the customer's responsibility to install, own, and maintain the necessary
equipment to bring all conductors for each phase and the neutral to a
coamon single connection. For specific information regarding situations
of this nature the Company should be contacted.
7. Change of Connected Load - When a customer's service is con
nected to the Company's system, arrangements are made for meters, trans
formers, and other equipment to supply the load at that time. It is
essential that customers notify the Company of any material increase or
decrease in load. It is also advisable that the customer consult .the
Company regarding equipment so that the proper type will be obtained. The
Company will hold the customer liable for any damages caused by increases
in load added to its system without permission.
8. Change or Relocation of Company Facilities - Any alterations
or changes in service connections, or relocation of service connections, or
Company's facilities supplying individual customers shall be at the expense
of the Customer when any of said contingencies are requested by the Customer
(and are for the customers benefit).
12/31/81 Page 2-l
.. 9. Upgrading or Replacement of Service - If existing service
entrance equipment is upgraded or replaced, the customer shall provide a
safe means of maintaining electrical service until the required inspections
are obtained and the Company permanently connects the new entrance equip
ment to its lines. Under no circumstances will the Company allow two
meters to be installed for the purpose of allowing the customer to trans
fer load from one panel to another. The Company will make only one (l)
trip to a premises for upgrading or replacing of service equipment.
10. Uability for Damages~ The Company assumes no responsibility
for any damage done by, or resulting from any defect in the wiring, fixtures,
or appliances of the customer, In the event that any loss or damage to
property of the Company, or any accident or injury to persons is caused
by or results from the negligence or wrongful set of the customer, bis
agents or employees,the cost of the necessary repairs or replacement or
injury shall be paid by the Customer to the Company; and, any liability
othet:Wise resulting shall be the responsibility of the Customer.
D, Company Responsibility - The COmpany will supply electric service
of the highest quality consistent with reasonable cost. However, the Com
pany cannot guarantee continuous uninterrupted service to any customer
and will not assume responsibility for damages resulting from its inter-
ruption,
l. Company Installation - The Company will provide the necessary
equipment for service up to the point of delivery along with necessary
metering devices, after the customer's responsibilities have been met,
only one source of supply to a premises at a single point of delivery will
be allowed in most cases, The point of deiivery on overhead service is the
point of connection to the customer's service entrance conductors. On
12/31/81 Page 2-4
underground residential service, installed by UGI, the point of delivery
is normally the line side of the Customer's meter trough. (UGI will not
install underground services to coamercial or industrial Customers.) The
point of delivery for any customer installed underground is at the point
of connection to the Company's supply system.
overhead service is normally supplied at no charge to cus
tomers within 100 feet of existing Company facilities. If the customer
requires an unusually long service, more than 100 feet from Company facil
ities, or desires undergrOllDd service, minimum monthly bills and/or aid
to construction charges -y apply. The Company should be contacted for
information regarding these situations.
Connection of Company facilities and customer equipment shall
be made only by authorized UGI employees. Every reasonable effort will be
made to coordinate work with the Customer on both new and upgraded instal
lations.
2. Company OWned Services - In the late 1960's and early 1970's
the Company purchased new service installations from many customers. The
Company agreed to maintain the following equipment on 'these installations:
westherhead, service cable and/or conduit, meter trough, grounding, main
panel box, and the main circuit breaker. The Customer is responsible for
all branch breakers and the wire fed from them.
These installations are identified by a sticker, which reads
"Property of UGI Corporation," placed on the main panel box or the meter
trough. A record is also kept by UGI, at the Kingston office, of all
"Company OWned Services."
The Customer forfeits all maintenance privileges when he
alters, relocates, or upgrades one of these services.
12/31/81 Page 2-5
3. Service to Motors • The Company reserves the right to
dete1'mine the method of supply and/or to prescribe restrictions on the
method of operation, when necessary, of loads which may cause flicker
on the service of its customers. Anyone intending to install such a
load must notify the Company prior to its proposed adaition. Service
will not be supplied to fluctuating loads of appreciable size without
a comprehensive review by the Company.
4. Customer Information • The Company does not accept respon·
sibility for any information given to a customer or applicant for service
unless such information is furnished by the assigned authorized repre
sentative and, when requested, confirmed in writing.
5. Identification - Employees of the Company are furnished
I.D. cards SZJ.d/or badges. All custOCD.ers should refuse admission to their
property of any persons not having the proper identification.
E. Rate Information· All rate schedules are available at the UGI
office. For information regarding rates, available voltages, and any
other rules covered in the Electric Service Tariff, the UGI consumer
II.elations Department should be contacted.
12/31/81 Page 2-6
S!:CTIOB 3 - TEMPORARY SERVICE The lnetallation of Coape.ny equipment firr any Custoaer service of
liaited duration, is considered teaporary. T&11porary services are available
for both overhead and underground inatallations.
'lbe Cuatoaer 11USt secant froll an authorized Coapany representatiTe0
a location for an7 tnporarf sernce structure, (If applicable, the
peruuent service location will also be given at this the,)
'lbe Collpany will connect the temporary senice only after the CuatOll8r
hu provided the following1
l. Pa1aent for the 1.nataUation and reJIOval of all teaporcy equipment.
(In the case of special. inat•JJ•tiona requirtng poles, transrm, and
other Coapany equi:pMDt the •tia&ted cost of lnatallation end reaoval will
be utilized.)
2. An electrical 1n.spection froa a qualified Fire Underwriter's
NOTE: 5th Terminal -- Devices for use on 120/208, 3-wire u GI EIJ!cn,IC U11LITI' DMSl()f,I ~ices must have 5th terminal installed. Specify when 2<17 -og Ave. P.Q !lox 1389: l(Jogs,on. Po. 1870, ordering. COl!l'OlAIION
NOTE: Only the bade catalog references shown in these columns are necessary for acceptance. Alphabetical and/or APPROVED METER SEl\VICE DEVICES numerical suff:lxes denote hub size or other featur~e. SINGLE-PHASE OVEl\HEAD SINGLE POSITION When aluminum conductors are usedt the electrical contractor shall apply the ~ori:osion inhtbtt1ng compound recommended· by and 1n the manner prescribed by the cable OAAWN •v r..ia·t~l,,l~, Due ~-z4-.eet, manufacturer, "'""""''" .... /, :";: ;(:
4 300 U 44542 44704-82 1004984 Sl-797-X RPU557SA/ and MS8807 400
NOTE: 5th Tei:111inal -- Devices for use on 120/208, 3~wire u GI EI.ECTRIC UTILITY PMIION iierii'ices must have 5th terminal installed, Specify when 2,1 w,,,m;ng Ave, P.O. Box 1389: Kingston. Pa. 16704 ordering. CORl'OIIATION
NOTE: Only . the basic catalog references shown in these ~mns are necessary for acceptance .. Alphabetical and/or APPROVED METER SERVICE DEVICES numerical suffixes denote hub size or other features, When SlNGLE-PHASE UNDERGROUND SINGLE POSITION aluminum conductors are used. the electrical contractor shall apply the corrosion inhibiting compound recommended I
by and in the manner prescribed by the cable manufacturer. DIIIIAWN 11V Joio"'....t..""\~t,...I~, ., .. .,. c. Z4.,&!:', ~- .,. re..-:;-. n.- • . .,.. .. /-_, __ .,,.,
Rev. 3-17-92 0111.Ailll'IH:e NO. . ..,..._.
TABLE 3
II OF # OF SUPERIOR , ' o, O AM1>1'RES POSITIONS ANCHOR DURHAM MILBANK SWITCHBOARD
5 ---- 9955-2 9959 X ----NOTE: 5th Te=inal: Devices for use on 120-208, 3-wire service u GI l!U!CTNC UTIUTV DMIION lllUSt have 5th terminal installed, Specify when ordering, i,r w,.,m;ng -· P.O. ea. 1389; l(Jngttoo. Pl. 18104 NOTE: Only the basic catalog references sho,rn in these eolur,ns C(Nll'OU.nCIN
are necessary for aeeep.tance, Alphah<!!tical and/or numerical suffixes denote hub size or other features. APPROVED METER SERVICES DEVICES When aluminum conductors are used, the electrical eon- SINGLE-PHASE OVERHEAD AND UNDERGROUND tractor shall apply the corrosion inhibiting compound MULTI-POSITION WITH ENU WIRING COMPARTMENT recommended by and in the manner prescribed by the cable manufacturer.
* Left position 200 Amp; Right position LOO Amp. DtlAWN ff 1"""~·)P70~, DAft &•Z4•A'!o ** Vertical trough--overhesd only, Al IIIIIIIOI\IIO .,, /"c!., . .,, , .,("7.,. • DAft /-,;- ... 1>q
Rev, 3-17-92 ~WINNO, . -
TABLE 4
II OF II OF SUPERIOR TERMINAL AMPCRES POSITIO! ANCHOR OURHAM MILBANK SWITCHBOARD LA.'lDlS & GYR
NOTE: 5th Terminal: Devices for use on 120-208, 3-wire s,ervicru UGI ELECTR1c unutY DIVISION must have 5th terminal installed. Specify when ordering. 2<17 Wyoming Ave. P.0 8oK 1389: K,ng•too, Pa. 1e104 NOTE: Only the basic c~talog references shown in these columns COll'OUTIQH
are necessary for acceptance, Alphabetical and/or numerical suffixes denote hub size or other features. APPROVED METER SERVICES DEVICES When aluminum conductors are used, the electrical con- 10 OVERHEAD AND UNDERGROUND tractor shall apply the corrosion inhibiting compound MULTIPOSITION WITH CENTER WIRING COMPARTMENT reconunended by and in the manner prescribed by the cable manufacturer. •
* Left position 200 Amp; Right position 100 Amp DflAWN rt ....... I ....t.M-, DA111 & "~4, •.!>O Nr•av• n n.: :::;:: fl ,
DAn J-,-J?9,--.- · Rev. 3~17-92 DAAWtM• NO.
. .......
'IAIILE 5
CROUSE:- CUTLER- GENERAL :HALL£NGllR TERMINALS ANC!!Oll HINDS HAMMER ELECTRIC IT£ SQUARED (SYLVANIA) llRYANT MIDWEST
4 M-2llR UM Series CG-4 trMM Series PAK MP Series ·MP Series QP-2 MM Series Or and and to
5 M-411RB AM $er:l.u CG-5 WPAK QP-6 Sedu Seriea
SPECIFICATIONS: 1. The catalog number must be stamped on the outside of .the device so that it will be visible after
the device is installed. 2. MATERIAL: Aluminum, galvannealed steel or equivalent. 3. MOUNTING: Horizontal or vertical.
(a) The center of the bottom meter must be a minimum of 30" above the floor. (b) The center of the top meter must not be more than 84" above the floor or ground. (c) There shall be a clearance of 4 foot free space in front of the meter. (d) On outdoor installations, if the center line of the bottom meter is 60'' above ground,
no barriers are required. If the center line of the bottom meter is between 60'1 and no less than 44" above ground, barrier$ are required around the meters - for example, a fence, shrubbery, etc,
4. BY-PASSES: Ringless - manual type required; ring M none permitted. 5. METER GUIDES: Required on ringless devices, 6. BARRIERS: Required between (1) compartments, (2) metered and unmetered cables. 7. BUSSING: Factory bussing required.
UGI 8. 5TH TERMINAL: Devices for use on 120/208 volt, 3-wire. IU!CTIIIC unun DM1110H Network services must have 5th terminal instal~ed. 2'17 Wyoming """' P,0, 11oo< 1389; King_, Po. 18704 Specify when ordering. --NOTE: Only the basic catalog references shown in these columns
APPROVED METER SERVICE DEVICES are necessary for acceptance. Alphabetical and/or numerical suffixes denote hub size or other features. When aluminum
SINGLE-PHASE ALL IN ONE conductors are used, the electrical contractor shall apply the MULTIPLE METER TROUGHS corrosion inhibiting compound recollllll8nded by and in the manner
prescribed by the cable manufacturer. (8¼,u, 911 or 10" center I
spacings are acceptable.) INAW1ill rt ' .u•A• • D•ft 6 •Z4 ·88 Arr•olltWO.., ,_,,, • u .......
, . .,,. .. !-.,-Rev. 3-17-92 0.AWt ... NIii. -
TABLE 6
CROUSE-CUTLER- SQUARE: CHALLENG R Tl!RMlNALS ANCHOR BRYANT HlNOS HAMMtR GE ITE SUPERIO! D SYLVANIA
4 VMS; QS-2 to UA CG-2 TMP MM u EZM MM Or Ml2 to Ml5 QS-6 UE Series Series and and Seri•n and
5 and and RY CG-3 WMM CCU M3M M32 to M35 QS-2R to AG Series Series Sertea Series Series QS-SR Series M35M
Series Series
SPECIFICATIONS: 1. The catalog number must be stamped on the outside of the device so that it will be visible after
the device is installed. 2. MATERIAL: Aluminum, galvannealed steel or equivalent. 3. MOUNTING: Horizontal or vertical.
(a) The center of the bottom meter must bes minimum of 30" above the floor. (b) The center of the top meter must not be more than 84" above the floor or ground, (c) There sha11 be a clea~ance of 4 foot free $pace in front of th• meter. (d) On outdoor installations. if the center line of the bottom meter is 60 11 above ground,
no barriers are required, If the center line of the bottom meter is between 60" and no less than 44" above ground, barriers are required around the meters - for example, a fence, shrubbery, etc,
4, BY-PASSES: Ringless - manual type required, ring - none permitted, 5. METER GUIDES: Required on ringless devices, · 6. BARRIERS: Required between (1) Compartments, (2) Metered and unmctarcd c3blcs. 7. BUSSING: Factory bussing required. u G I EU!CTl'IIC UTILITY OMS40t, 8. 5TH TERMINAL: Devices for use on 120/208 volt 3-wire. 2'17 W/<lffllng /\w:. P,0 8ol< 138ll; King'1on. Po. 18704
Network services must have 5th terminal installed. COlll'Ol!AtlON
Specify when ordering. NOTE: Only the basic catalog references shown in the columns APPROVED Ml!TER SERVICE DEVICES ~necessary for acceptance. Alphabetical and/or numerical SINGLE-PHASE Ml!TER STACKS (GANGABLE) suffixes denote hub size or other features. When aluminum MULTI•Ml!TER TROUGHS conductors are used, the electrical contractor shall apply the corrosion inhibiting compound recommended by and in the • manner prescribed by the cable manufacturer. (8½", 9" or 10" DIii.AWN av ,. - DATIi .e, · Z:4 ,61',
center spacings are acceptable.) ..__ ... rt o:. ~. " . DATIi /-,-=
Rev. 3~17-92 o .. ,.,., .... .... . ., ..... '
TABLE 7
NUMBER OF MIDWEST SUPERIOR TERMINALS ANCHOR MFG. COMPAN SQUARED SWITCHBOARD
tht c•nt•r line ot the low••t ••t•r •hall b• ••H· (.) Naxi•u• Dl•tanc• ~ Hi1h••t ••t•r: Th• •••1•~• diatanQt tro•
th• 1rou.nd Une to the c«ntu Un• at th ht,hHt H_t·•.r it;hdl UGI IL.!eTIIIC U'l1UlY DMIION b• '"'". 247 w,,,,,,;"11 Avo, P.O. 8"" 1J89: Ki"!l'm, Pa. 18704
8. STABlLlZl~G POOT: R•qulud. on all. pl4utai.. --· 9. CONDUIT .SUPPOll:TI WhftH (!Otklli,t!t h HiJU.lHd hf' 'th• Ul'Viu
htud. • ondut't •up,O,t •HHd•atitl)' 3' bU(p~ th• .. tu bau APPROVED MEIER SERVICt DEVICES •h,-11 ·t:t, provl4,4 to •o.t .,11:e ttquh••ut.
~ \li,'h•n alU•tnu• condu.etor• at• Ultd.·tht •l•~ttlt•l contractor •h•li MOBILE HOME MEIER PEDESTALS FOR 3-WIRE, •PP.l)' th, c-orro•ion inhibl tln1 eo•povn4 .nco11111111nd•d b,- •nd in tb• ••nn•t l~. 120/208 OR 120/240 VOLT, 200A, UNDERGROUND pr~acribtd ., the cabli ••n\liact.1,1.r•r. Th•.br••k•r at th1 Pldtat•l •u•t ' hi YI •n interi:'u.'pttn, capacity whhh 11ut•· coll.• n4\linM1nh, the• \Ht Of DtlA- IIY .!-:::'.....::>. ~ ... 4,.-- DAft & .z4-,,o...,
'"' p,4c•t11l ..... t •• r..ctory co•t•d on ... in1id• end o\lt•i4, or th• "-D IIY r.J "'f, f/ A _ I . DATIi f-5"~8"y pcdc•t1l ~o 2".abov• gro\lnd tcvel With b1t1,t•e•tt~ or •quiv11~nt,
DRAWi ... Nct, -ll(l\'. 8-21,-88
TABLE 8 Lnndis &
Crouse- Gyr UJaws Amperes Entry Anchor Hinda Durham Milbank Superior
NOTE: I/hen aluminum conductors are used, the u GI ,~CTl'IIC UTILITY DIVISION ~tr1cal contractor shall apply corrosion 2-47 Wyo'nlng Aw,.. P.O. SOI< 1389: K1ngs1on. Pi. 11.\704 inhibiting compound as reco,mnended by and in COlll'OMTION the manner prescribed by the cable manufacturer.
APPROVED METER SERVICE DEVICES . POLYPHASE 208 VOLT WYE OR 240 VOLT DELTA
Cutler General Challenger Terminals Br;i:ant Crouse-Hinds Halll!l!er Electric Square D (Sylvania)
7 QS-3CL1BR RY cc-7 TMP EZM SC~ QS~3CL211R Series Series TMPR Series Series & QS-3CL3BR Series M37M
SPECIJ.'ICATIONS: Series
1. The cata1og number must be stamped on the outside of the device so that it will be visible after the device is installed.
2. 3.
MATERIAL: Galvannealed Steel of Equivalent MOUNTING: Horizontal or Vertical
BY-PASSES: 4. 5. METER GUIDES: 6, BARRIERS: 7. BUSSING:
NOTES:
(a} The center of the bottom meter must be a minimum of 30 inches above the floor for indoor installations and 44 inches above the ground for outdoor installations.
(b) The center of the top metet must not be more than 72 inches above the floor
(c) (d)
or ground. There shall be a clearance of 3 feet free space in front of the meter. On outdoor installations, if the center line of the bottom meter is 60 inches above ground, no barries are required. If the center line of the bottom meter is between 60 inches and 44 inches above ground, barriers are required around the meters - for example, a fence, shrubbery, etc. Ringless-Lever type requires, Ring-None permitted. Required on ringless devices, Required between (1) compartments (2) metered and unmetered cables, Factory bussing required.
1, When aluminum conductors are used, the electrical contractor shall apply the corrosion inhibiting compound n,commended by and in the manner prescribed by the cable manufacturer. i-------------------1
2, 8.5 inch, 9 inch or 10 inch center spacings are acceptable.
Rev, 3-17-92
UGI £1.l!CffllC U11UTV D1V1$10N
247 Wyoming A~. F'.O, 8oJ: 1389, K1ngstoo. Pa 18704 (Oll'OIIATION
Approved Meter Service Davices 30 Meter Stacks (Gsngsble) Mv.lti-Meter Troughs
STRUCTURE OF 2-2"x4" TIMBERS SET 2' IN GROUND, FIRMLY SET AND BRACED, OR CLASS 5 POLE, MIN Ill!JM, SET 5' IN THE GROOND OF SUFFICIENT HE IGl!T TO PROVIDE SERVICE DROP C LF.ARANCE OF 18' OVER ROAO OR 14' OVER DRIVE.
2 "x4" TIMBERS SHA LL BE SOUND · AND FREE OF KNOTS.
SPLICING OF TIMBERS IS NOi' PERMITTED.
SKETCH NO. 1
TOP VIEW
SIDE VIEW
. ~ :,:
0 00
0 N ...
!Qlli:
THE LOCATION OF THE TEMPORARY STRUCIDRE WILL RE DETERMINED BY AN AUTHORIZED COMPANY REPRESENTATIVE.
REFER TO TABLE# l FOR ACCEPIABLll METER TROUGHS.
DIMENSION "L" SHALL NOT RE LESS THAN 1/2 OF DDIENSION '
1H11 00:R GR.E6.TER THAN "Hn.
NAllS USl!D IN MAKING TEMPORARY STRIJCn!RES Sl!AL1 BE 20d OR LARGER.
SPACE MUST l!E PROVIDl!D FOR SERVICEMEII TO PIACE IADDl!R ON SIDE OF Tl!MPORARY SUPPORT SO THAT HE FACES SERVICE POLE WHEN INSTALLING OR REMOVING SERVICE DROP ATTACHMEHT.
CUSTOMER FU!UUSHES, INSTALLS AND MUNTAINS SERVICE E!l'IRANCE CONDUCTORS, HETER TROUGH, GROOND FAULT SERVICE DISCONNECT DEVICE AllD SERVICE GROUND. COMPANY FUIUIISHl!S AND INSTALLS METER •
CUSTOMER'S GROUNDROO LUZERNE ELECTRIC DIVISION - UGI CORPORATION 247 WYOMING AVENUE
{FULLY DRIVEN) KINGSTON, PA
TYPICAL 3-WIRE
REVlSIOH9 TEMPORARY
No. DATI OVERllEAD SERVICE STRUCnJRE
:DIIIAWN ay DAff
APPIIOYED aY- D"tt
O!IIIA.Wlfot& NO. SeM.E None
STRUCnJRE OF 2"x4" TIMBERS, SET 2'0" IN GROOND, MUST BE OF SUFFICIENT HEIGHT TO ALLOW METER TROOGH TO BE PU.CED 4 ' 0" TO 6' 0" AllOVE GROUND •
CUSTOMER'S SERVICE DISCONNECT DEVICE AND RECEPTACLE MOONTl!D ON FRONT OR REAR OF STRUCnJRE.
CUSTOMER FURNISHES, INSTALLS AND MAINTAINS HETER TROUGH, GROOND FAULT SJ!llVICE DISCONNECT DEVICE, AND SERVICE CONDUCTORS SUITAIILE FOR DIRECT BURIAL AIID SERVICE GROOND. COMPANY FURNISHES AND INSTALLS METER.
CUSTOMER FURNISHES, INSTALLS, AND MAINTAINS THREADED GALV. RIGID OR INTERMEDIATE STEEL COIIDU IT AND BU SH ING OR PVC SCHEDULE 40 CONDUIT EXTENDING 12" BELOW GRADE.
SKETCH NO. 2
NOTES,
THE LOCI. TION OF THE TE!!i'ORA!lY STRUCTIJRF. WIU BE DETERMINED EY AN AUTHORIZED COHPAN!'. Ri!PRESDITATIVE.
THE TEMl'ORARY STRUCTURE DESCRIBED IN THIS SKETCH IS SUITAllLll FOR UNDERGROUND TEl!PORARY SERVICE IF T!!E METER JASE AND SERVICE COtiDUCTORS ARE INSTALLED IN ACCORDANCE WITH THE DETAILS ON TRIS SKETCH,
L-J
q : CONDUIT r ( L-5 0
OPTION TO LOCATING DISCONNECT AND RECEPTACLE ON OPPOSITE SIDE
~ OH ;r- z I "' ... ..a..:,:--
"' 0 ... OF METER •
CUSTOMER'S .,,->..,_---SERVICE GROOND
IL.---V'
~TOMER' S GROUND ROD ~(FULLY DRIVEN}
GROOND LEVEL
" .'k... ___ ~ BUSKING (WIIEN STE.EL
CUSTOMER SUPPLIED CONDUCTORS ~CONDUIT IS USED).
MUST EXTEND A MINIMUM OF 2 '0" BEYOND END OF CONDUIT.
No. DATE
LUZERNE ELECTRIC DIVISION - UGI CORPORATION 241 WYOMING AVENUE
LUZERNE ELECTRIC DIVISION - UGI CORPORATION 247 WYOMING AVENUE
KINGSTON. PA.
TYl'ICAL OVERHEAD SERVICE 300 AMP & 400 AMP
Dl!tAWN ·" ·J-. c .. HAUCK ~vso av ~-- f.l DIIU.W.NG 110. V
D4TS 12/1/80 D4TE /:J 3,l-'61 Sc::Au None
NOTES:
ALL METER LOCATIONS MUST BE DESIGNATED BY AN AUTIIOR.IZED COMPANY REPRESENTATIVE.
REFER TO TABLE #1 FOR ACCEPTABLE METER TJ.OIJG!!S.
COMPANY SUPPLIES METER, ATIACIIMENT SUPPORT AND SERVICE DROP.
SEllVICB CONDUIT ABOVE THE ROOF LINE CANNOT HAVE ANY COUPLIHGS.
MAST HEIGHT OVER 48" ABOVE ROOP LINE REQUIRES A GUY WIRE PIRMLY SECURl!D TO THE ROOF.
LOAD SIDE OF Ml!TEll SOCKET MAY ALSO BE . SKltVICE CABLE.
GALVANIZED RIGID STEEL
SICET<:H NO. S
CUSTOMER 111ST PROVIDE A 3' MINIMUM TAI
12"
MINUi.-1-- ...........
48" MAX
ATEACHMENT SUPPORT SUPPLIED AND l!ISTALLED BY COMPANY
CONDUIT !l!ST BE SECUlll!LY ANCHORED AT THE ROOF TO PREVENT POSS IBLE ROOF DAMA.GE DUE TO VIBRATION
CONDUIT SIZE PER SERVICE SIZE:
2½:" _ 100 AMP 200 AMP
3" 300 AMP
3½;" - 400 AMP
P IIUSl!!D GRADE
LINE SIDE
l LOAD SIDE
CUSTONER.'S GROOHD WIRE
CUSTOl!Ell'S GR.OOHI)
ROD PULLY DRIVEHV
No. DATE
1 -21-82
LUZERNE ELECTRIC DIVISION - U G I CORPORA TJON 247 WYOMING AVENUE
KINGSTON, PA
TYPICAL MAST SERVICE
DIIAWH aY OATII
APPIIOYID SY
0RAWING NO. SCALI: None
COl'ANY FURNISHES, INSTALLS z AND MAIN1'Ail6 SERVICE IECP !./ AND MAJ::ES CONNl:Cl'ION TO ~·s SERVICE mmm:: •
t:: OOND!.C'IDRS. ~-----,(,._
ClB'lUIER FOR.NISHES, INSTALLS AND MAIN1'AIN3 A iOJD POLE (CLASS 5 MIN.) FOLL LENGTil OF POLI! :IIIST RE
TREATED BY A PRESSDRF. I PROCESS TO PREVENT PREMATURE DE'rERIOl!ATION.
• t: .,, ..
....
CU3'IU(ER FllR!USHES, I!mJ AND MAil,ll'AOO METER TRO SEE TABLES FOR LIST OF APPROVED DEVICES. CXJ!PANY FllRNISHE3 AND I.NS'.l'ALLS _..µ,., KEI'ER.
• ~
SKETCH !IO. 6
CW'l'CtiER FURIHSHES, IlfflALLS AND MAINI'AINS SERVICE EN'fflA!CE COllll£'l"ORS.
r NEUrRAL
--- ClB'.OCMER'S OVERHEAD DIS'l'RIWJ:ION, SINGLE CO~, TRIPLEX, QUAJ:im'LEX OR CAILE CPTIONAL.
ROTE: WHl!II POLE HIJST BE GUYED TO OFFSET PULL OF Cl»IPANY' S SERVICE DROP OR CUSTCl'IER'S OVERJ!EAD DISTRI· BUTION WIRES, CUSTOMER FURNISHES, INSTALLS AND MAINTAINS THE GUY {S} •
CIBTClml'S SERVICE GROUND.
<( CUSTC»IEI!.' S GROUND ROD V (FULLY DRIVEN).
DJ;P'll! 5 ' MIJUMUM
LUZERNE ELECTRIC DIVISION - UGI CORPORATION 247 WYOMING AVENUE
KINGSTON. PA.
I I I J r I , ___ .,__._I
No. DATIi:
SERVICE Il1CP ATT.nmtmrr TO CW'l'CHER-CMNED SERVICE AND ME.TER POLE OVERHEAD SER'IICE TO
OVERHEAD DIS'l'RifmION
0JIAWH •'t
APPltOVED •Y- Du• 011tAW1NG NO~ Sc,a,u None.
SKETCH NO. 7
r---_~ --.L-E-I z «.H
~ H :0:
CCH'ANY FURNISHES, IKSTAl.lS AND MAINI'AINS SERVICE tRCI' AND MAKES CONIIOCTIOH TO CU3'IOMER'S SERVICE ENTRANCE
CIBI'CMER FURNISHES, INSTALIB AND MAINl' Allfl SERVICE ENTRA!C ~ 1-o CONDOC'IQRS. 1 l
CUSTCMER FURNISHES, I NSTAL!.'3 AND MAI NI' Allfl A w::xJD POLE ( CLAS.S 5 MIN.) FULL LENGTH~ • OF POLI, · HUST BE TREATED BY A PRES SURE PROCESS TO PREVENT PREMATURE DETERIORATION.
I >
. .., <v
C::::::CONDU:'ro~.
NOTE: WHEN POLE WST BE GUYED TO OFFSET PULL OF COMPANY'S SERVICE DROP, CUSTO!l!R FURNISHES, INSTALLS, AND MAINTAINS THE GIIY(S) •
ClBIUMER FURIUSl!ES, IN3'I'ALIB AND l..l . I,,/" MAIIII'AINS HE:l'ER TROUGH, SEE TAB.ES
Q)- - V'- FOR LIST OF JIPPROVED DEVICES, CClfPANY . T ...,,,,, .... .,., ,,.,,.,..., ,,.., .
'Il!READED GALVANIZED RIGID OR INr EEiME DIA'.I'E STEEL CONDUIT OR PVC s:::HEDULE 40 CCNDUIT, _ ___,.___µ.
CWT(!,!ER'S WDERGROUND SERVICE EN'rn!\H:::E CONIXCI'ORS IN RIGID OR INI' ERMEDIATE
t
' CUSTOMER'S SERVICE GROUND
GALVAN I ZED STEEL CONDUIT, PVC s:::HElJULE 40 CONDUIT, OR 1 ~
,;- FINISHED GRADE
.L~l-t-¼---'--J.
DIRECTLY BURIED !BING CABLE - LI 1 :.,..--'-7...J I I SUIT ABLE FOR THAT P URPOO E • - - .., , ---t-
i
I k-1------i CUSTOMl!R 'S GROUND ROD (FULLY DRIVEN)
c--DfPIB 5 fT. MINIMIM I I ! -
I r I LUZERNE ELECTRIC 0/VISIOIII - UGI CORPORATION I _j 247 WYOMING AVENUE __ ---'-1--------~K~IN~~~TO~N~,~P~A;..... ______ -1
No.
SERVICE IRCP ATr/CHMEm' TO ClBIOIER-OWNED SERVICE AND METER POLE
NOTE: ALL METEI! LOCATIONS KIST BE DESIGNATED l!Y AN AUTHORIZED COMPANY REPRESENTATIVE.
REFER TO TABLE NO. _2_ FOR ACCEPTABLE H!TER TROUGHS.
UlIDEl!Gl!OUIID SECTION FROM POLE TO _BOOSE SERVICE CAN BE DIRECT BURIAL CABLE OR IN COffllUIT AS SPECIFIED BY THE NATIONAL ELECTRICAL CODE.
If CUSTOMER" PROVIDES POLE, IT KIST BE A MHH!IIJM CLASS 5 AND TREATED ruu Li!.lfGTH BY A PRESSURE PROCESS TO PREVENT PREMATURE DETERIORATION.
liHBN REQUIRED, THE CUSTOMER WILL ALSO FUIUUSH, INSTALL AIID MAINTAIN GUYING TO OFFSET THE PULL OF THE COMPANY'S SERVICE DROP.
CUSTQIER 111ST INSTALL SERVICE HEAD, GALVANIZED RIGID ST1!EL CONDUIT (Sl!CllltELY FASTBlil!D TO COMPANY Olt CUS'l'Ct!ER POLE), AND SERVICE COOIJUCTORS.
-.,.,;.....J_CUST(JIEll.'S Gl!OOliD WillE
r---_ - CUST<lll!l!'S GROOND 1!00 (nJLLY DRIVEN)
. '
Gl!Clll!D LEVEL I I BUSHING ---------------:, l_J __ 5_•_1_N. BUSHING SHOULD BE_/ USED IIITII STEEL COffllllIT.
SEE SECTION 6-D FOR llECOMH£NDED DEPTHS.
lln11fONI
No. DAn
LUZERNE E LE CTR IC DIVISION - U G I CORPORATION 247 WYOMING AVENUE
DUWN e¥
D•AWI .... MO.
KINGSTON. PA.
TYPICAL CUSTCIID. INSTALLED UllDEl!GllOUND
DATE
OATS
SCALE None
SKETCH NO. I l
NEUTRALHOT -=*===/· HOT-
CT CAIHNET NOTES:
ALL HETER LOCATIONS !IUST BE DESIGNATED BY AN AUTIE)RlZEI> COMPANY REPRESl!NTATIVE.
THIS IHSTALLAITON TO J!.I! USED FOR RESIDENTIAL SERVICE EXCEEDING 400 AMPS AND IIHEN RESIDENTIAL WSTctlER IS BILLED UNDER RATE RTII AND THE SERVICE EXCEEDS 200 AMPS.
CUSTOMER'S GROUND WIRE
~ ...... s (
lo 1.1;" RIGID STEEL
COODUIT_}
r
IF SERVICE IS TO Bl! SUPPLIED UNDERGROUND, THE CUSTOMER SU!'PLlES AND INSTALLS A 36"X36"X10" C. T. CABINET AND A 1½;" RIGID CONDUIT FROM THE C.T. CA.J!.INET TO THE METER TII.OUG!!.
GROUHD ROD \
(FuLLY DRIVE!f)2-..
,'.;L~::==1 ,_, /, .,, .,
UNDERG:~ND)
Rcv.t•IONII
No. DATIi
IF SERVICE IS TO l!E SIJPPLIED OVERHEAD, THE CUSTOMER MAY UTILIZE A C,T, CABDIET AS ABOVE OR THE C.T. MAY llE RACK KXJNTED AT THE CUSTOMl!R' s Wl!ATIIEIU!EAD.
THE CCl!PANr SUPPLIES TO THE CUSTOHEII. FOR INSTALLATIOII THE METER TROUGH, CURRENT TRANSFORMER, AND RACK, IF REQUIRED.
SERVICE PANELS
LUZERNE ELECTRIC DIVISION - UGI CORPORATION 247 WYOMING AVENUE
KINGSTON. PA.
WIii.ING D lAGRAM FOIi. SINGLE PHASE TRANSFOl!MEJ. RATED METER,
OVERHEA!) OR UNDERGROUND SERVICE
DATC 1 22 81 DATE /.;l.-;l /- 'J;j
OllAWINQ NO. Scau: Hone
FINAL GRADE
I/ARNING TAPE SlPPUED BY UGI.
SAND BACD'ILL
EIB:.l'RIC CABLE
~=
/
SKE'l'CH NO. 12
30"
12"
w ~EE NCII'E 4.
1, Cable or oondult depth shall be 30" below fi,..l grade as shown above.
2. Sand bacl::fill will be required on all .sides of electrio cable e.nd. facllit iaa •s ah.own above... (Th.e CompanJ' may prefer to utilize, conduit as &n alternate to sand bool:fl 11. )
3. '!he remainder of the trench may be bool:fllled with the excanted eorth exoept that no frozen lmip,s, large stones, rubbish, debris,- ash-es, coal .refuse or -cinders- ma.y be used.
•t. All trenches shall be at lefl.at •ix inches wide. Elowever, joint use of s.
trench by the Tel.ephone ~Y or other po.rtiea uy ch,mge the spec! fi. oat ions of the t renchinge and bacl:fi lling. Mutual ai;ireement between puties -oooq:,ying a trench must be obtain-::d before any wo.ri: ia started.
s. m trenches shall be bacl:filled tha - day that they are -Md .... r. procticablo. 4'en trenches a hall be praperly guarded to preftltt iajury to per80llS or doll>oge ti> property. ibri:: ,,hloh ohould nomdly be done ill ,advance of the oable instsl.lat:lon date, auch •• at.rut conduit oroa•lns1, pipe pushing or a,~arinl)' shall be scheduled and -1atad. Powr equipoant sho.11 not be ""8d within H inches of any existirq hurled oahlo.
6. 1ha c""1:,_r end{ or contrsot<>r 1B responsible for any and all liebility ruu.lting· fraa the trenching and bocl::flllirlQ' oponti<>n and ahal.l ... .,. UGI O:,rporation hanll.ess from any and all cl&lms. ·
No. DATI:
I
LUZERNE ELECTRIC DIVISION - UGI CORPORATION 247 WYOMING AVENUE
KINGSTON, PA.
DU" 4/16181 D,uc -~ -Ir Sc.AL-IE lJOO.e
~:
THE RECEP'rACLE CORD CONNECTION BETWEEN DISCOIINllCT BOX AND SERVICE PANEL MUST REMAIN ABOVE GROOND. WHEN DIRECT BURIAL CABLE IS USED AS AN UNDERGROUND FEED IT MUST BE DIRECTLY WIRED AT THE DIS CONNECT BOX.
CUSTOMER FURNISHES, INSTALLS AND Mi\INTAINS A WOOD POLE (MINI1'1JM CLASS 5) TREATED FULL LENGTH BY A PRESSURE PROCESS TO PREVENT PREMATURE DBTERIORATION.
lll!EN REQUIRED, GUY WIRE WILL BE INSTALLED 011 POLE IN OPPOSITE DIRECTION OF INCOMING
SKETCH NO. 13
WEATl!f;RPROOF BOX CONTAINING DISCONNECT AND MOBILE HOKE OUTLET OR DIRECT CONNECTION POINT, 7'"--
SERVICE DROP. THIS ( WILL BE FURNISHED, INSTALLED AND Mil.IN- '----~" TAINEO BY THE CIJSTOH&R.
GROUND LEVEL __ _
CUSTOMER'S CONDUIT (OR SERVICE COID)
CUSTOMER'S C-GROIJIID ROD __J {FULLY DRIVEN)
5/8"x6'0" ANCHOR ROD MINIMUM SIZE
I 0
z ... H
;,:
12°
-·----~~ 0
"'
LUZERNE ELECTRIC DIVISION - VG I CORPORATION 247 WYOMING AVENUE
Rn-1•10N•
No. CATIE
D1tAWN aY
OIi.AWi l'tG NO.
KINGSTON. PA
1YPICAL IIIDIVIDIJAL OVERHEAD MOBILE HOME.POLE SERVICE
DAYS
DAff
SCALE Hone
SKETCH NO. 14
WEAT!WU'ROOF BOX CONTAINS DISCONNECT AlllJ K>BILE HOME OUTLET OR DIRECT CONNBCTION POUIT.
LOAD SIDE CONDUIT (OR SERVICE CORD)
ND.
NOTES:
THE RECEPTACLE CORD CONNECTION BETWEEN DISCONNECT BOX AND SERVIC PANEL MUST REW.. Ill ABOVE GROOND. WHEN DIRECT BURIAL CABLE IS USED AS Ali UllDERGROOIID FEED IT MIJST BE DIRECTLY WIRED AT THE DISCONNECT BOX.
THE SKETCH BELOW CAN BE REPLACED WITH A STANDARD P1!EFAB "UllDERGROUND MOBILE HO!IE PEDESTAL." (SEE TABLE 7.)
CUSTOMER FIJRHISHES, INSTALLS AHO MA.INTAINS THREADED GALVANIZED RIGID OR INTEl!MEDIATE STEEL COIIDUIT AND BUSHING OR PVC SCHEDULE 40 CONDUIT EXT!!NDllfG 12" BELOW GRADE.
LIHE SIDE COffllUIT SIZE:
. ~n,~t ( 2~" FO..R 100 OR 200 AMP Si!RVICE.
~ AIJJMIIIJM CONDUIT IS NOT
DATIi:
0 ACCEPTABLE.
CUSTOMER'S SERVICE GR.OU!ID
CIJSTOMl!R' S GROUllD RciJ>.'-.-JiFULLY DRIVD}
(WHEN PVC IS HOT USED)
LUZERNE ELECTRIC DIVISION - UGI CORPORATION 247 WYOMING AVENUE
Dt1AWN 9T
KINGSTON. PA.
TYPICAL INDIVIDUAL UNDERGllOONll !«)BILE HOME POLE Sl!RVICI!
DATIi
A-PPlllOYaO aY O&n
SCALI:
SKETCH NO. 15
) OVEIU!FAD SUPPLY ~:
ALL METER LOCATIONS !IJBT BE DESIGNATED BY Ali AUTHORIZED COMPANY UPIIESENTATIVE • . -,--~
l I
0 0 O:O: REFE!l TO TABLE # 3 Alm 4 FOR ACCEPTABLE Ml!TER TROOGHS.
..,....,~-- ,-,-4-,;.,r'-c, ~ r:u rr ~ u LINE SIDE SUPPLY MA.Y BE CONDUIT OR SERVICE CAJLE. SERVIC!! CABLE US!I> AS THE SUPPLY, WILL BE LIMITED, BASED ON HUMBER 01' SOCKETS.
Ll '----- .... ----) UNDERGRDU~ SUPPLY ~
IF A !IJLTI-Ml!TER INSTALLATION IS TD BE SUPPLIED BY COMPANY INSTALLl!D lllillERGROOND FACILITIES, SUPPLY SIDI! L
r-
SECOHDAilY ~ SIDE MAY BE CONDUIT OR SERVICE CABLE.
cotlDUIT(S) 111ST BE MIHIMUM 3" 11.IGID STl!EL OR APPROVED SCIIEOULE 40 PVC. l'AIALLEL CONDUITS MAY BE RJ!SiUillID IF Tl!E lMD, AS OETERMI!lEI) BY THE COMPANY, IS OF SUFFICIENT SIZE.
0\1E~-+ SUPP~Y)
lO O O 000 [ L'a 11 11 1T l ll ~ =~ ~ u~ T ~ ~ ~... L UNDERGROUND SUPPLY ) t Z:,· ~ ~ SECOHDAilY LOAD SIDE _J :0. ~ <> MAY BE CONDUIT OR SERVIC!! GAJILE
'
RIIY .. fON•
No. DATIi
1 9-21-82
LUZERNE ELECTRIC DIVISION - UGI CORPORATION 247 WYOMING AVENUE
KINGSTON. PA.
!t!LTI-METER INSTALLATIOlf
DttAwN ev J.C. HAUCK DAT& 12/ 1/80
DIIU,WING- ttO. f ( J
SKETCH HO. 16
LINE
LOAD
2 WIRE, l PHASE 120 VOLTS • LIii
LOAD 3 'WIRE, 1 PHASE U0/208 VOLTS
LOAD
4 WIRE, 3 PIIASE 208Y/120 VOLTS
No. DATI
LINE
LOAD
3 WIRE, 1 PHASE 120/240 VOLTS LiliE
t-:::1::f=l~::=+---IDENTIFY HIGH
LOAD
LEG AT SERVICE El!TlilfCE AND AT HETER SOCKET
4 WllE, 3 PHASE 120 /2'40 VOLTS
LUZERNE El ECT RIC DIVISION - U G I CORPORATION 247 WYOMING AVENUE
0#1.AWN .,..
KINGSTON. PA.
METER TROUGH CONNECTIONS FOR SELF-COIITAINED METERS
ill,~ovt:D aY
• .,.. - .,l ·,--r I ' I ' I ' I ' ' . l I
.I''.,!./ .. , .... .I
' 1 t ' . ' 1 ' . ' I ! I ' . -' I
' I
SKETCH NO. 17
NOTE l
NOTE 2
__)
NOTE 1
0 _.)
I ,4 ·- 6'
l FINAL GRADE
llll"WlalON•
No. 0.ATI(
NOTES:
1. METER TROUGH AIID FIVE POSITIOlf RACK SUPPLIED BY COMPANY AND INS'l'ALLED BY CUSTOl!El!.,
2:. Iii;" RIGID STEEL METERING CONDUIT SUPPLIED AND INSTALLED BY C!ISTOl!ER.
3. COMPMlY F!llt!USBES AIID INSTALLS INS'l'1UJMEIIT TIWISFOI!HERS AND WIRING BETIIEEN INSTRUMENT Tl!ANSFOBMEltS AIID METER •
4. CUSTOMER MUST PROVIDE 3' MINIMlJM TAILS - COLOR CODED PER NATIONAL ELECTRIC CODE.
5. CLEARANCES PER MINIMUM NATIOIIAL ELECTRIC SAFETY CODE REQUIREMENTS •
LUZf.R!\!f flECTAIC OIVISIOl\l UGI CORPORATION :t,41 WYOMING AVENU( •
KINGSTON. PA.
WIRING DIAGRAM FOR THREE-PHASE SERVICE, 120/240 VOLT, INSTRUMENT
Tl!AIISFORMER METERING A!ID QUADRAPLEX SERVICE WIRE
0A.TC -/.
.. ' , I i'.,
• • ,...._.,
' }
SKETCH NO. 18
~
1.2"
NOTES: ----1. HETER TROUGH AND SEVEII POSITION l!ACKS Slll'PLIED BY OOMP.MIY AND INSTALLED BY CUSTO!IEll •.
4. CUSTOHD. MUST PROVIDE 3' HIIII.Kl.JH TAILS - COLOR CODED PER NATIONAL ELECTUC CODE.
5. CLEARANCES PER: MIIIIHIIM NATIONAL ELECTJUC SAFETY CODE REQUIREHEll7S.
WIRING DIAGRAM FOR THREE-PHASE SERVICE, 120 /208 VOLT, IHSTR!JMEliT TRAHSFOBMER METERI!iG
AHD OPEii WIRE SERVICE
k i AUii .. aY
NOTE 4
18" 12"
NOTE 2
~.LL-NOTE l
01-
FINAL GRADE
SKETCH NO. 22
1 NOTES:
1. METER TROUGH AND SEVEN POSITION RACK SUPPLIED RY COMPANY AND IHSTALI.ED BY CUSTOMER.
2. llr:" RIGIO STEEL !IETERIIIC CONOUIT SUPPLlEI> AND ll!STALLE!) BY CUSTOHER.
51:i' IIINIMUM
l. COKP AN1 Fllltlll SHES AND INSTALLS UISTRI.NEIIT TIWIS.fORHD.S AND WlRIIIG B&nlEDI IMSTRIIIEIIT TRA.~SFOltltERS AJIO HETER.
4. CIJSTOHER MUST PROVlllE )' KINIHUH TAll.S - COLOR COD£1> PER NATIONAL ELECTRIC CODE.
5. CUARAIICES ru HIN lHUH NA TlON AL ELECTR{C SAFETY COllE REQUlREHEHTS.
UGI COltl'OUIION
ELECTRIC untnY DM-2«1 Wyornit'Q Ave. P.O b 1389." KingSllon Pa 18704
11.nalC:ffS
lflll!IG DIAGRAM FOR THREE-PHASE MAST SERVICE, 120/208 VOLT, INSTRUMENT
TRANSFORMER HE1'EIUNC ANO QUADRAPLEll SERVICE WIRE
No. DAff
.,,~:: -\ f{-: 1:~t I~..\-'. I -~"'i'"" \ I "\
i I I'\ I
NOTE 4
I I'' I I
I I I
L-~ 'r·r I I I : I • ,,.. ... 1~
....... < I r I I I I
I_J •
' I '-·
GROUIII} CLAMP BY CUSTOMER
SKETCH NO. 23
NOTE 1
12"
NOTE 2
/ NOTE 1
4' - 6 1
NOTES:
l. METER TlOUGR MID SEVEN POSITION BACKS SUPPLIED BY COMPANY AND INSTALLBD BY CIJSTOIIER.
2. l\" IUGIO STEEL METERING CONDUIT Slll'PLIEO ANO IIISTALJ.EI) BY CUSTOIIER.
J. COl1PANY FUltl!ISHES ANO IIISTALLS IIISTRlR!EliT TRAJISFOl!MUS ANO li'IIUIIC BETIIEEli lllSTlUJMENT TRAJISFOl!IIEJ1.S Allll HETER.
4. CUSTONElt MUST PROVIDE 3' MINIMUM TAILS - COUll!. CODED PER NATIONAL ELECTUC COOE •
S. CLEABAIICES PER MINI.MU!{ NATIOIIAL ELECTRIC SAFETY CODE REQUIRE!IEIITS.
FINAL CRADE
No. D,1,n
LUZERNE ELECTRIC DIVISION - UGI CORPORATION 247 WYOMtNG AVENUE
KINGSTON. PA.
WIRING DIAGRAM FOR THREE-PHASE, THREE-WIRE SERVICE, 480 VOLT, IIISTRIJMElIT
TRANSFORMER METERING AND OPEN WIRE SERVICE
0.AWN 8Y
SKETCH NO. 24
CURRENT TIWISFORMER WTI'!I THE LOWER RATIO
NEUTRAL
NOTES:
1. METER TROUGH AND IlfSTIWMEIIT TIWISFOl!MERS SUP1'LIED BY COMPANY AND INSTALLED BY CUSTOMER.
2 • 1~' RIG ID STEEL COR!lUIT AIID ·er CABINET SUPPLIED AllD IlfSTALLED BY CUSTOMER.
3. COMPANY FURNISHES AND INSTALLS WIRING BETWEEN INSTRUMl!IIT TIWISFORMERS A11D METER.
•ns11a11a - .......
/
ll,;" RIGID STEEL CO!IDllIT TO METER TROUGH LOCATED OUTSIDE 4' - 6' Al!OVF. FINAL GRADE. 50' MAXIMUM L&l!GTH
ClllffiENT TRANSFORMER WITH THE RICHER RATIO
TO CUSTOMER'S SERVICE EQUIPMENT
WIRIIIG DIAGRAM FOR THREE-PHASE SERVICE, 120/240 VOLT, INSTRU!!EIIT TRANSFORMER
METERING, IJHOERGROOIID SERVICE __ ..,
CUSTOMER'S UNDERGROUND SEIi.VICE EN'I'RMICE
~· 1, METER l'ROUGH AND IIISTRUMEIIT
Tlil!SF01\MERS SUPPLIED l!Y CQ!l>ANY AllD IlfSTALLE!> BY CUSTOMER.
2. 11(' RIGID STEEL CONDUIT AND CT CABINET SUPPLIED AllD INSTALLEO BY CUS'l'OMER.
3. COMP ANY FURNIS!li!S AND INSTALLS WIRING BETWEEN llfSTRUMEIIT TRANSFORMEl!S MID METER.
....... NidJI
No.
SKETCH NO. 25
lli;" RIGID STEEL CONDUIT TO METER TROUGH LOCATED OUTSIDE 4' - 6' A!IOVl'. :Fil!AL GRADE - 50' MilillllM LEIIG'fB
-=====D~ro CUSTOMEJt's - SERVICE EQUIPMEll'f
CT CABlllET 36" X 36" X 10" - HDIIl!llM SEE SECTION ll-C FOR SPECIFICATIOlfS
WIRil!G DIAGRAM FOR TIIREE-Pl!ASE SERVICE, 120/208 VOLT,
INSTRUMEHT TRANSFORMER METERING, UNDERGROUND SERVICE
DIIAWN ff
.Auraoua ff
SKETCH NO. 26
NOTE: ALL METER LOCATIONS AND TERMINAL POLES MUST BE DESIGNATED BY AN AUTIIORIZED
~ COMPA~'Y REPRESENTATIVE.
REFER TO TABLE NO. 2 FOR ACCEPTABLE METER _.../COMPAflY OWNED POLE. TROUGllS. CONDUIT SHALL BE INSTALLED BY TIIE ~
CUSTOMER IN ACCORDANCE WITH COMPANY SPECIFICATIONS. CONDUIT MAY BE ELECTRICAL GRADE PVC SCHEDULE /jO 00 THREADED GALV.o.NIZED RIGID STEEL. WHEN PVC IS !Tl'ILIZED ALL JOINTS MUST. BE SECURELY GLUED WITH AN APPROPRIATE.PVC CEMEHT.
-;f<51 1 PULL LINE. INSTALLED BY CUSTOMER. END OF CONDUIT
-· .._ - MUST BE COVllllED to PREVENT 4' TO 6' ENTRANCE OF MOISTURE. ,_