www.tridonic.com 1 Subject to change without notice. Data sheet 02/13-881-3 FL ballasts Electronic dimming Product description • Processor-controlled ballast with y inside • Highest possible energy class CELMA EEI = A1 BAT 1 • Noise-free precise control via DALI or DSI signal, switchDIM or corridorFUNCTION • OEM-specific reserved memory areas • Extended DALI commands • 5-year guarantee Interfaces • DALI • DSI • switchDIM (with memory function + selectable dimming rate) • corridorFUNCTION (individually programmable) Functions • Intelligent Temperature Guard (overtemperature protection) • Intelligent Voltage Guard (overvoltage indication and undervoltage shutdown) • Optimum filament heating in any dimmer setting • Disconnection of filament heating from a dimming level of approx. 90 % for maximum energy efficiency (SMART-Heating concept) • Fade rates between 50 ms and 90 s (min. – max.) • Automatically triggered emergency lighting value in DC mode, can be set between 1 and 100 % • For emergency lighting systems as per EN 50172 • Automatic start after replacement of defective lamps • Automatic shutdown if the lamp is faulty • Dimming possible in DC mode • Backwards compatible È Standards, page 3 Wiring diagrams and installation examples, page 6 PCA T8 EXCEL one4all lp Y, 36 – 58 W EXCEL T8 T8 side fixing features Technical data Mains voltage range 220 – 240 V AC voltage range 198 – 264 V DC voltage range 176 – 280 V (lamp start ≥ 198 V DC) Mains frequency 0 / 50 / 60 Hz Overvoltage protection 320 V AC, 1 h Typ. power input on standby < 0.5 W Protective hot restart 0.5 s for AC / 0.2 s for DC Dimming range 1 – 100 % Lamp start possible from 1% Operating frequency ~ 40 – 100 kHz Type of protection IP20 Ordering data Type Article number Packaging, carton Packaging, pallet Weight per pcs. For luminaires with 1 lamp PCA 1x36 T8 EXCEL one4all lp Y 22176239 10 pc./pcs. 760 pc./pcs. 0.244 kg PCA 1x58 T8 EXCEL one4all lp Y 22176235 10 pc./pcs. 760 pc./pcs. 0.263 kg For luminaires with 2 lamps PCA 2x36 T8 EXCEL one4all lp Y 22176240 10 pc./pcs. 760 pc./pcs. 0.277 kg PCA 2x58 T8 EXCEL one4all lp Y 22176237 10 pc./pcs. 640 pc./pcs. 0.333 kg PHASED OUT
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
www.tridonic.com 1Subject to change without notice.
AC operationMainsvoltage220–240V50/60Hz198–264V50/60Hzincludingsafetytolerance(±10%)202–254V50/60Hzincludingperformancetolerance(+6%/-8%)
DC operation220–240V0Hz198–280V0Hzcertainlampstart176–280V0HzoperatingrangeUseinemergencylightinginstallationsaccordingtoEN50172orforemergencyluminairesaccordingtoEN61347-2-3appendixJ.
Light output level in DC operationProgrammablefrom0%to100%ProgrammingbyextendedDSIorDALIsignal(16bit).Defaultvalueis70%InDCoperationdimmingmodecanbeactivated.
Temperature rangeUnlimiteddimmingrangefrom0°Ctotamax.-25°Cto0°C:dimmingoperationfrom100%to30%.Ifdimmlevelgoesbelow30%malfunctionpossible,butnoelectronicballastdamage.ThisappliestoACandDCoperation.
Mains currents in DC operation (at 70 % light output)
TypeWattage Mainscurrentat
Un=220VDCMainscurrentatUn=240VDC
PCA 1x36 T8 EXCEL one4all lp X 1x36W 0.13A 0.12APCA 2x36 T8 EXCEL one4all lp X 2x36W 0.26A 0.24APCA 1x58 T8 EXCEL one4all lp X 1x58W 0.19A 0.18APCA 2x58 T8 EXCEL one4all lp X 2x58W 0.40A 0.36A
Harmonic distortion in the mains supply (at 230 V / 50 Hz)Type Wattage THD 3 5 7 9 11
Control input (DA/D1, DA/D2)DigitalDALI/DSIsignalorapush-to-makeswitch(switchDIM)canbewiredonthesameterminals(DAandDA).
Digital signal DALI/DSIThecontrolinputisnon-polarandprotectedagainstaccidentalconnectionwithamainsvoltageupto264V.ThecontrolsignalisnotSELV.Controlcablehastobeinstalledinaccordancetotherequirementsoflowvoltageinstallations.Differentfunctionsdependingoneachmodule.
Wiring type and cross sectionThewiringcanbesolidcablewithacrosssectionof0.5to0.75mm²forpushterminaland0.5mm²forIDCterminal.Forthepush-wireconnectionyouhavetostriptheinsulation(8–9mm).
Loosenwirethroughtwistingandpulling
Intelligent Temperature GuardTheintelligenttemperatureguardprotectsthePCAT8EXCELone4alllpxfromthermalover-heatingbyreducingtheoutputpowerorswitchingoffincaseofoperationabovethethermallimitsoftheluminaireorballast.Dependingontheluminairedesign,theITGoperatesatabout5to10°CaboveTctemperature.
Intelligent Voltage GuardIntelligentVoltageGuardisthenameofthenewelec-tronicmonitorfromTridonic.ThisinnovativefeatureofthePCAfamilyofcontrolgearfromTridonicimmediatelyshowsifthemainsvoltagerisesabovecertainthresholds.Measurescanthenbetakenquicklytopreventdamagetothecontrolgear.• Ifthemainsvoltagerisesaboveapprox.305V(volt-agedependsontheballasttype),thelampstartsflashingonandoff.
and wiringThenewplug&playsolutionsimplifieshandling.ByattachingdifferentcoloredmarkedplugstotheSMART-Interface,groupaddressesareassignedtothePCAT8EXCELone4alllpx.Thissupersedesasingleaddressingandthedevicescanbeputintooperationwithoutanyadditionalprogramming.Anothersignificantadvantageofthisconceptisincaseofexchangeandnolimitsto64DALIaddresses.IdealforRGBapplicationsandcost-effectivesystemsolutionswithsimplecontrollers.Simple–Quick–Plug&Play!
General adviseElectronicballastsarevirtuallynoisefree.Magneticfieldsgeneratedduringtheignitioncyclecancausesomebackgroundnoisebutonlyforafewmilliseconds.
For further technical information please visit www.tridonic.com
PCA T8 EXCEL one4all lp X 1x36–58 W PCA T8 EXCEL one4all lp X 2x36–58 W
* * control signal
* leads 9, 10: keep wires short, max. 1.0 m leads 11, 12: max. 2.0 m; ballast must be earthed* * digital signal (DSI), DALI or switchDIM
DA/D2
DA/D1
234
67
1211109
LN
PC and the“configTOOL”
USBSCI
DALIPS
1211109
16151413
DADA
PELN
234
67
PELN
1211109
16151413
DADA
PELN
234
67
max. 64 ECGs (DALI)
1211109
16151413
DADA
PELN
234
67
* * control signal
* leads 9, 10, 15, 16: keep wires short, max. 1.0 m leads 11, 12, 13, 14: max. 2.0 m; ballast must be earthed* * digital signal (DSI), DALI or switchDIM
DA/D2
DA/D1
234
67
141516
131211109
DimmableballastsfromTridonichavetobeearthed.
Operation on DC voltageOurballastsareconstruedtooperateDCvoltageandpulsedDCvoltage.TooperateballastswithpulsedDCvoltagethepolarityisabsolutemandatory.
234
67
D1
D2
+–
Isolation and electric strength testing of luminairesElectronicdevicescanbedamagedbyhighvoltage.Thishastobeconsideredduringtheroutinetestingoftheluminairesinproduction.