Load Flow Studies

EEE 103 2nd Exam Review

Page 2: EEE 103 2nd Exam Review

Outline

โ€ข Bus Admittance Matrix

โ€ข Gauss-Seidel Iterative Method

โ€ข Tips for Reliable Solutions

Page 3: EEE 103 2nd Exam Review

The Bus Admittance Matrix

๐‘Œ๐ต๐‘ˆ๐‘† =๐‘Œ11 โ‹ฏ ๐‘Œ1๐‘›โ‹ฎ โ‹ฑ โ‹ฎ๐‘Œ๐‘›1 โ‹ฏ ๐‘Œ๐‘›๐‘›

โ€ข YBUS building rules:

โ€“ Diagonal elements Yii = sum of all admittances connected to bus i

โ€“ Off-diagonal elements Yij = negative of net admittance connected

between bus i and bus j

โ€ข Yii is the self-admittance or driving-point admittance

โ€ข Yij is the mutual admittance or transfer admittance

Page 4: EEE 103 2nd Exam Review

Properties of the YBUS

โ€ข Complex

โ€ข Symmetric

โ€ข Sparse (can have zero elements)

โ€ข Singular if there are no admittances between

any of the buses and the reference bus

Page 5: EEE 103 2nd Exam Review

Example 1: 3-bus system

Page 6: EEE 103 2nd Exam Review

Example 1: 3-bus system

Form the YBUS:

โ€ข Y12 = Y21 = -(1 / (0.02 + j0.04 ฮฉ))= -10 + j20

โ€ข Y13 = Y31 = -(1 / (0.01 + j0.03 ฮฉ)) = -10 + j30

โ€ข Y23 = Y32 = -(1 / (0.0125 + j0.025 ฮฉ)) = -16 + j32

โ€ข Y11 = Y12 + Y13 = (10 โ€“ j20) + (10 โ€“ j30) = 20 โ€“ j50

โ€ข Y22 = Y21 + Y23 = (10 โ€“ j20) + (16 โ€“ j32) = 26 โ€“ j52

โ€ข Y33 = Y31 + Y32 = (10 โ€“ j30) + (16 โ€“ j32) = 26 โ€“ j62

Page 7: EEE 103 2nd Exam Review

Example 1: 3-bus system

๐‘Œ๐ต๐‘ˆ๐‘† =

20 โˆ’ j50 โ€“10 + j20 โˆ’10 + j30โˆ’10 + j20 26 โˆ’ j52 โˆ’16 + j32โˆ’10 + j30 โˆ’16 + j32 26 โˆ’ j62

Page 8: EEE 103 2nd Exam Review

Source Transformation

โ€ข Is = Vs / Zs

โ€ข Ys = 1 / Zs

Page 9: EEE 103 2nd Exam Review

Injected Current

โ€ข The current that flows through a bus

โ€ข Current from sources flow into the bus

โ€ข Current to admittances flow out of the bus

Page 10: EEE 103 2nd Exam Review

Injected Current

KCL equation at bus i:

โ€ข IS = Iij + Iik + Iil

โ€ข IS = Yij(Vi โ€“ Vj) + Yik(Vi โ€“ Vk) + Yil(Vi โ€“ Vl)

โ€ข IS = YijVi โ€“ YijVj + YikVi โ€“ YikVk + YilVi โ€“ YilVl

โ€ข IS = (Yij + Yik + Yil)Vi โ€“ YijVj โ€“ YikVk โ€“ YilVl

Page 11: EEE 103 2nd Exam Review

Injected Current

๐ผ1โ‹ฎ๐ผ๐‘›

=๐‘Œ11 โ‹ฏ ๐‘Œ1๐‘›โ‹ฎ โ‹ฑ โ‹ฎ๐‘Œ๐‘›1 โ‹ฏ ๐‘Œ๐‘›๐‘›

๐‘‰1โ‹ฎ๐‘‰๐‘›

๐ผ๐ต๐‘ˆ๐‘† = ๐‘Œ๐ต๐‘ˆ๐‘† ๐‘‰๐ต๐‘ˆ๐‘†

โ€ข IBUS: Bus current vector (i.e. current sources)

โ€ข YBUS: Bus admittance matrix

โ€ข VBUS: Bus voltage vector

Page 12: EEE 103 2nd Exam Review

Injected Power

๐‘†1โ‹ฎ๐‘†๐‘›

=๐‘‰1 โ‹ฏ 0โ‹ฎ โ‹ฑ โ‹ฎ0 โ‹ฏ ๐‘‰๐‘›

๐‘Œ11 โ‹ฏ ๐‘Œ1๐‘›โ‹ฎ โ‹ฑ โ‹ฎ๐‘Œ๐‘›1 โ‹ฏ ๐‘Œ๐‘›๐‘›

๐‘‰1โ‹ฎ๐‘‰๐‘›

โˆ—

๐‘†๐‘— = ๐‘‰๐‘— ๐‘Œ๐‘—๐‘–๐‘‰๐‘—โˆ—

๐‘›

๐‘–=1

โ€ข The complex power that flows through a bus

Page 13: EEE 103 2nd Exam Review

Example 2: 4-bus system

Page 14: EEE 103 2nd Exam Review

Example 2: 4-bus system

Page 15: EEE 103 2nd Exam Review

Example 2: 4-bus system

Page 16: EEE 103 2nd Exam Review

The Gauss-Seidel (G/S) Iterative Method

โ€ข A solution to a non-linear equation with the form f(x) = 0

โ€ข Steps:

1. Rewrite function into x = g(x)

2. Initialize x(k), k = 0

3. Approximate x(k+1) with g(x(k))

4. Stop approximations when |x(k+1) โ€“ x(k)|< ฮต, where ฮต is the desired accuracy

Page 17: EEE 103 2nd Exam Review

Example 3: G/S solution

Find a root of f(x) = x3 โ€“ 6x2 + 9x โ€“ 4 = 0

Desired accuracy is 0.01

1. x = -(1/9)x3 + (6/9)x2 + (4/9) = g(x)

2. Let x(0) = 3.5

Page 18: EEE 103 2nd Exam Review

Example 3: G/S solution

Find a root of f(x) = x3 โ€“ 6x2 + 9x โ€“ 4 = 0

3. First iteration, x(1) = g(3.5) = -(1/9)(3.5)3 + (6/9)(3.5)2 + (4/9) = 3.8472

4. Check convergence |x(0) โ€“ x(1)| = 0.3472

5. Second iteration, x(2) = g(3.8472) = 3.9848

6. Check convergence |x(1) โ€“ x(2)| = 0.1376

7. Third iteration, x(3) = g(3.9848) = 3.9998

Page 19: EEE 103 2nd Exam Review

Example 3: G/S solution

Find a root of f(x) = x3 โ€“ 6x2 + 9x โ€“ 4 = 0

8. Check convergence |x(3) โ€“ x(2)| = 0.015

9. Fourth iteration, x(4) = g(3.9998) = 4.0

10. Check convergence |x(4) โ€“ x(3)| = 0.0002

11. Stop iterations, x = 4.0

Page 20: EEE 103 2nd Exam Review

The Load Flow Problem

โ€ข The ff. information are available

โ€“ Source (Generator) โ€ข Voltage and real power

delivered

โ€“ Line (Transmission) โ€ข Impedance

โ€“ Load โ€ข Complex power

consumed V, P

Z

P, Q

โ€ข The ff. are unknown

โ€“ Bus voltages

โ€“ Bus currents

โ€“ Line power flows

Page 21: EEE 103 2nd Exam Review

The Load Flow Problem

โ€ข We need the equation f(x) to solve for x

โ€ข f(x) is the complex injected power

โ€ข x is the bus voltage

โ€ข G/S will be extended to a linear system

Page 22: EEE 103 2nd Exam Review

The Load Flow Problem

For a bus i, ๐‘“ ๐‘‰๐‘– = ๐‘†โˆ—

๐‘ƒ๐‘– โˆ’ j๐‘„๐‘– = ๐‘‰๐‘–โˆ— ๐‘Œ๐‘–1๐‘‰1 +โ‹ฏ๐‘Œ๐‘–๐‘–๐‘‰๐‘– +โ‹ฏ๐‘Œ๐‘–๐‘›๐‘‰๐‘›

๐‘Œ๐‘–๐‘–๐‘‰๐‘– =๐‘ƒ๐‘– โˆ’ j๐‘„๐‘–๐‘‰๐‘–โˆ— โˆ’ ๐‘Œ๐‘–1๐‘‰1 +โ‹ฏ๐‘Œ๐‘– ๐‘–โˆ’1 ๐‘‰๐‘– ๐‘–โˆ’1 + ๐‘Œ๐‘–(๐‘–+1)๐‘‰๐‘–(๐‘–+1) +โ‹ฏ๐‘Œ๐‘–๐‘›๐‘‰๐‘›

The (k+1)th approximation to the voltage Vi is

๐‘‰๐‘–(๐‘˜+1)=1

๐‘Œ๐‘–๐‘–

๐‘ƒ๐‘– โˆ’ j๐‘„๐‘–

๐‘‰๐‘–(๐‘˜)โˆ—โˆ’ ๐‘Œ๐‘–1๐‘‰1

(๐‘˜)+โ‹ฏ+ ๐‘Œ๐‘–(๐‘–โˆ’1)๐‘‰(๐‘–โˆ’1)

(๐‘˜)+ ๐‘Œ๐‘–(๐‘–+1)๐‘‰(๐‘–+1)

(๐‘˜)+โ‹ฏ+ ๐‘Œ๐‘–๐‘›๐‘‰๐‘›

(๐‘˜)

Page 23: EEE 103 2nd Exam Review

System Representation

Page 24: EEE 103 2nd Exam Review

Step-by-step G/S Formulation

1. Build the [YBUS]

2. Initialize voltages (Viโˆ ฮด) and power (Psch,Qsch)

A. PV bus: use given V, set ฮด = 0.0ยฐ, and Psch = Pg โ€“ Pl

B. PQ bus: set V = 1.0, ฮด = 0.0ยฐ, Psch = Pg โ€“ Pl, and Qsch = Qg โ€“ Ql

3. Approximate voltages (except slack bus). Use the latest approximations.

A. PQ bus: ๐‘‰๐‘–(๐‘˜+1)=1

๐‘Œ๐‘–๐‘–

๐‘ƒ๐‘–๐‘ ๐‘โ„Žโˆ’j๐‘„๐‘–

๐‘ ๐‘โ„Ž

๐‘‰๐‘–(๐‘˜)โˆ— โˆ’ ๐‘Œ๐‘–1๐‘‰1

(๐‘˜)+โ‹ฏ+ ๐‘Œ๐‘–(๐‘–โˆ’1)๐‘‰(๐‘–โˆ’1)

(๐‘˜)+ ๐‘Œ๐‘–(๐‘–+1)๐‘‰(๐‘–+1)

(๐‘˜)+โ‹ฏ+ ๐‘Œ๐‘–๐‘›๐‘‰๐‘›

(๐‘˜)

Page 25: EEE 103 2nd Exam Review

Step-by-step G/S Formulation

3. Approximate voltages (except slack bus). Use the latest approximations.

B. PV bus: i. Approximate Qsch

using ๐‘„ = โˆ’Im ๐‘‰๐‘–

โˆ— ๐‘Œ๐‘–1๐‘‰1 +โ‹ฏ๐‘Œ๐‘–๐‘–๐‘‰๐‘– +โ‹ฏ๐‘Œ๐‘–๐‘›๐‘‰๐‘›

ii. If there are MVAR limits, Qsch = Qmin if Q โ‰ค Qmin and Qsch = Qmax if Q โ‰ฅ Qmax; otherwise Qsch = Q

iii. Approximate Vโ€™ as if it were a PQ bus

iv. V = |V(0)|โˆ (angle of Vโ€™)

4. If max(|V(k+1) โ€“ V(k)|) โ‰ค ฮต then stop iteration, otherwise repeat steps 3 and 4.

Page 26: EEE 103 2nd Exam Review

Example 4: 3-bus Load Flow

โ€ข Use 100 MVA base and ฮต = 0.01

Line R (pu) X (pu)

1-2 0.02 0.04

1-3 0.01 0.03

2-3 0.0125 0.025

Bus Type V (pu) ฮด (deg) PGEN

(MW)

QGEN

(MVAR) PLOAD

(MW)

QLOAD

(MVAR)

1 SLACK 1.05 0 - - - -

2 LOAD - - 0 0 400 250

3 GEN 1.04 - 200 - - -

Page 27: EEE 103 2nd Exam Review

Example 4: 3-bus Load Flow

โ€ข The [YBUS] was solved earlier in Ex. 1

๐‘Œ๐ต๐‘ˆ๐‘† =

20 โˆ’ j50 โ€“10 + j20 โˆ’10 + j30โˆ’10 + j20 26 โˆ’ j52 โˆ’16 + j32โˆ’10 + j30 โˆ’16 + j32 26 โˆ’ j62

โ€ข The initial voltage vector [VBUS] is [1.0500โˆ 0.00ยฐ 1.0000โˆ 0.00ยฐ 1.0400โˆ 0.00ยฐ]

โ€ข The scheduled complex powers in per-unit are P2

sch = โˆ’4.0, Q2sch = โˆ’2.5, and P3

sch = 2.0

Page 28: EEE 103 2nd Exam Review

Example 4: 3-bus Load Flow

โ€ข First iteration V2

(1) = [1/(26โˆ’j52)+ * ,*(โˆ’4.0+j2.5) / (1.0โˆ 0)+ โˆ’ [(โˆ’10+j20) * (1.05โˆ 0) + (โˆ’16+j32) * (1.04โˆ 0)]}]

= 0.9755โˆ โˆ’2.49

Q3(1) = โˆ’ Im{[1.04โˆ 0] * [(โˆ’10+j30) * (1.05โˆ 0) +

(โˆ’16+j32) * (0.9755โˆ โˆ’2.49) + (26โˆ’j62) * (1.04โˆ 0)]}

= 1.16

V3(1) = *1/(26โˆ’j62)] * {[(2.0-j 1.16) / (1.04โˆ 0)+ โˆ’

[(โˆ’10+j30) * (1.05โˆ 0ยฐ) + (โˆ’16+j32) * (0.9755โˆ โˆ’2.49)]}] = 1.04โˆ โˆ’0.29

Page 29: EEE 103 2nd Exam Review

Example 4: 3-bus Load Flow

โ€ข Second iteration V2

(2) = 0.9708โˆ โˆ’2.56

Q3(2) = 1.2911

V3(2) = 1.04โˆ โˆ’0.36

โ€ข Third iteration V2

(3) = 0. 9720โˆ โˆ’2.56

Q3(3) = 0.8605

V3(3) = 1.04โˆ โˆ’0.36

Max. voltage mismatch: 0.0037, stop iterations.

Page 30: EEE 103 2nd Exam Review

Example 5: 4-bus Load Flow Line R (pu) X (pu)

1-2 0.01008 0.05040

1-3 0.00744 0.03720

2-4 0.00744 0.03720

3-4 0.01272 0.06360

Bus Type V (pu) ฮด (deg) PGEN

(MW)

QGEN

(MVAR) PLOAD

(MW)

QLOAD

(MVAR)

1 SLACK 1.0 0 - - - -

2 LOAD - - - - 170 105.35

3 LOAD - - - - 200 123.94

4 GEN 1.02 - 318 - 80 49.58

Page 31: EEE 103 2nd Exam Review

Example 5: 4-bus Load Flow

โ€ข Build the bus impedance matrix

โ€ข Solve for the bus voltages using G/S. Use 100 MVA base and ฮต = 0.01

Page 32: EEE 103 2nd Exam Review

Example 5: 4-bus Load Flow

โ€ข [YBUS]

8.9852โ€“j44.9260 โ€“3.8156 +j19.0781 โ€“5.1696 +j25.8478 0

โ€“3.8156+j19.0781 8.9852โ€“j44.9260 0 โ€“5.1696+j25.8478

โ€“5.1696+j25.8478 0 8.1933โ€“j40.9663 โ€“3.0237+j15.1185

0 โ€“5.1696+j25.8478 โ€“3.0237+j15.1185 8.1933โ€“j40.9663

Page 33: EEE 103 2nd Exam Review

Example 5: 4-bus Load Flow

โ€ข First iteration

V2 = 1.0034โˆ โˆ’1.82ยฐ

V3 = 1.0013โˆ โˆ’2.34ยฐ

V4 = 1.0200โˆ โˆ’4.28ยฐ

Q4 = 1.0468

Max mismatch = 0.0762

Page 34: EEE 103 2nd Exam Review

Example 5: 4-bus Load Flow

โ€ข Second iteration

V2 = 1.0032โˆ โˆ’4.26ยฐ

V3 = 1.0001โˆ โˆ’3.87ยฐ

V4 = 1.0200โˆ 6.45ยฐ

Q4 = 1.5222

Max mismatch = 0.0428

Page 35: EEE 103 2nd Exam Review

Example 5: 4-bus Load Flow

โ€ข Third iteration

V2 = 1.0016โˆ โˆ’5.47ยฐ

V3 = 0.9986โˆ โˆ’4.64ยฐ

V4 = 1.0200โˆ 7.53ยฐ

Q4 = 1.4658

Max mismatch = 0.0211

Page 36: EEE 103 2nd Exam Review

Example 5: 4-bus Load Flow

โ€ข Fourth iteration

V2 = 1.0006โˆ โˆ’6.07ยฐ

V3 = 0.9978โˆ โˆ’5.02ยฐ

V4 = 1.0200โˆ 8.07ยฐ

Q4 = 1.3588

Max mismatch = 0.0105

Page 37: EEE 103 2nd Exam Review

Example 5: 4-bus Load Flow

โ€ข Fifth iteration

V2 = 1.0001โˆ โˆ’6.37ยฐ

V3 = 0.9973โˆ โˆ’5.21ยฐ

V4 = 1.0200โˆ 8.34ยฐ

Q4 = 1.2858

Max mismatch = 0.0053, stop iterations

Page 38: EEE 103 2nd Exam Review

Example 6: 3-bus Load Flow

Line R (pu) X (pu)

1-2 0.02 0.10

1-3 0.04 0.15

2-3 0.07 0.25

Bus Type V (pu) ฮด (deg) PGEN

(MW)

QGEN

(MVAR) PLOAD

(MW)

QLOAD

(MVAR)

1 SLACK 1.0 0 - - 0 0

2 GEN 1.0 - 44.1 - 0 0

3 LOAD - - - - 100 66.67

Page 39: EEE 103 2nd Exam Review

Tips for Reliable Solutions

1. Remember these equations: [I] = [YBUS][V] and [P-jQ] = diag([V*])[YBUS][V]

2. Report per-unit quantities in four (4.0000) decimal places and angles in two (2.00) decimal places

3. YBUS

A. Complete the upper-diagonal only. Remember that the matrix is symmetric

B. Start with off-diagonal elems.

C. The diagonal elems. have positive real terms

Page 40: EEE 103 2nd Exam Review

Tips for Reliable Solutions

4. System Modelling

A. Positive power flows from generators

B. Negative power flows into load

5. G/S Iterative Method

A. Write the voltages in tabular form

B. Setup all equations first

C. Use the latest information available

D. All quantities are in per-unit