-
21Transformers
At the end of this chapter you should be able to:
understand the principle of operation of a transformer
understand the term rating of a transformer use V1/V2 D N1/N2 D
I2/I1 in calculations on transformers construct a transformer
no-load phasor diagram and calculate magnetising and core
loss components of the no-load current state the e.m.f. equation
for a transformer E D 4.44f8mN and use it in calculations construct
a transformer on-load phasor diagram for an inductive circuit
assuming
the volt drop in the windings is negligible describe transformer
construction derive the equivalent resistance, reactance and
impedance referred to the primary of
a transformer
understand voltage regulation describe losses in transformers
and calculate efciency appreciate the concept of resistance
matching and how it may be achieved perform calculations using R1 D
N1/N22RL describe an auto transformer, its advantages/disadvantages
and uses describe an isolating transformer, stating uses describe a
three-phase transformer describe current and voltage
transformers
21.1 Introduction
A transformer is a device which uses the phe-nomenon of mutual
induction (see Chapter 9) tochange the values of alternating
voltages and cur-rents. In fact, one of the main advantages of
a.c.transmission and distribution is the ease with whichan
alternating voltage can be increased or decreasedby
transformers.
Losses in transformers are generally low and thusefciency is
high. Being static they have a long lifeand are very stable.
Transformers range in size from the miniatureunits used in
electronic applications to the largepower transformers used in
power stations; the prin-ciple of operation is the same for
each.
A transformer is represented in Fig. 21.1(a) asconsisting of two
electrical circuits linked by acommon ferromagnetic core. One coil
is termed the
TLFeBOOK
-
304 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
Figure 21.1
primary winding which is connected to the supplyof electricity,
and the other the secondary winding,which may be connected to a
load. A circuit diagramsymbol for a transformer is shown in Fig.
21.1(b)
21.2 Transformer principle ofoperation
When the secondary is an open-circuit and an alter-nating
voltage V1 is applied to the primary wind-ing, a small current
called the no-load currentI0 ows, which sets up a magnetic ux in
thecore. This alternating ux links with both primaryand secondary
coils and induces in them e.m.f.s ofE1 and E2 respectively by
mutual induction.
The induced e.m.f. E in a coil of N turns is givenby E D Nd8/dt
volts, where d8dt is the rateof change of ux. In an ideal
transformer, the rateof change of ux is the same for both
primaryand secondary and thus E1/N1 D E2/N2 i.e. theinduced e.m.f.
per turn is constant.
Assuming no losses, E1 D V1 and E2 D V2
HenceV1N1
D V2N2
orV1V2
D N1N2
1
V1/V2 is called the voltage ratio and N1/N2the turns ratio, or
the transformation ratio ofthe transformer. If N2 is less than N1
then V2 isless than V1 and the device is termed a
step-downtransformer. If N2 is greater then N1 then V2 isgreater
than V1 and the device is termed a step-uptransformer.
When a load is connected across the secondarywinding, a current
I2 ows. In an ideal transformerlosses are neglected and a
transformer is consideredto be 100 per cent efcient. Hence input
power Doutput power, or V1I1 D V2I2 i.e. in an ideal
transformer, the primary and secondary ampere-turns are
equal
ThusV1V2
D I2I1
2
Combining equations (1) and (2) gives:
V1V2
=N1N2
=I2I1
3
The rating of a transformer is stated in terms of
thevolt-amperes that it can transform without overheat-ing. With
reference to Fig. 21.1(a), the transformerrating is either V1I1 or
V2I2, where I2 is the full-loadsecondary current.
Problem 1. A transformer has 500 primaryturns and 3000 secondary
turns. If theprimary voltage is 240V, determine thesecondary
voltage, assuming an idealtransformer.
For an ideal transformer, voltage ratio D turns ratioi.e.
V1V2
D N1N2
hence240V2
D 5003000
Thus secondary voltage
V2 D 2403000500 D 1440V or 1.44 kV
Problem 2. An ideal transformer with aturns ratio of 2:7 is fed
from a 240V supply.Determine its output voltage.
TLFeBOOK
-
TRANSFORMERS 305
A turns ratio of 2:7 means that the transformerhas 2 turns on
the primary for every 7 turns onthe secondary (i.e. a step-up
transformer); thusN1/N2 D 2/7.
For an ideal transformer, N1/N2 D V1/V2hence 2/7 D 240/V2 Thus
the secondary voltage
V2 D 24072 D 840V
Problem 3. An ideal transformer has aturns ratio of 8:1 and the
primary current is3A when it is supplied at 240V. Calculatethe
secondary voltage and current.
A turns ratio of 8:1 means N1/N2 D 1/8 i.e. astep-down
transformer.(
N1N2
)D(
V1V2
)or secondary voltage
V2 D V1(
N1N2
)D 240
(18
)D 30 volts
Also,(
N1N2
)D(
I2I1
)hence secondary current
I2 D I1(
N1N2
)D 3
(81
)D 24A
Problem 4. An ideal transformer, connectedto a 240V mains,
supplies a 12V, 150Wlamp. Calculate the transformer turns ratioand
the current taken from the supply.
V1 D 240V, V2 D 12V, I2 D P/V2 D150/12 D 12.5A.
Turns ratio D N1N2
D V1V2
D 24012
D 20(
V1V2
)D(
I2I1
), from which,
I1 D I2(
V2V1
)D 12.5
(12240
)
Hence current taken from the supply,
I1 D 12.520 D 0.625A
Problem 5. A 12 resistor is connectedacross the secondary
winding of an idealtransformer whose secondary voltage is120V.
Determine the primary voltage if thesupply current is 4A.
Secondary current I2 D V2/R2 D 120/12 D10A.
V1/V2 D I2/I1, from which the primaryvoltage
V1 D V2(
I2I1
)D 120
(104
)D 300 volts
Problem 6. A 5 kVA single-phasetransformer has a turns ratio of
10 : 1 and isfed from a 2.5 kV supply. Neglecting losses,determine
(a) the full-load secondary current,(b) the minimum load resistance
which canbe connected across the secondary windingto give full load
kVA, (c) the primary currentat full load kVA.
(a) N1/N2 D 10/1 and V1 D 2.5 kV D 2500V.Since
(N1N2
)D(
V1V2
), secondary voltage
V2 D V1(
N2N1
)D 2500
(110
)D 250V
The transformer rating in volt-amperes D V2I2(at full load) i.e.
5000 D 250I2Hence full load secondary current I2 D5000/250 D
20A.
(b) Minimum value of load resistance,RL D
(V2V1
)D(25020
)D 12.5Z.
(c)(
N1N2
)D(
I2I1
)from which primary current
I1 D I2(
N1N2
)D 20
(110
)D 2A
Now try the following exercise
Exercise 114 Further problems on thetransformer principle of
operation1 A transformer has 600 primary turns
connected to a 1.5 kV supply. Determine thenumber of secondary
turns for a 240V outputvoltage, assuming no losses. [96]
TLFeBOOK
-
306 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
2 An ideal transformer with a turns ratio of 2:9is fed from a
220V supply. Determine itsoutput voltage. [990V]
3 A transformer has 800 primary turns and2000 secondary turns.
If the primary voltageis 160V, determine the secondary
voltageassuming an ideal transformer. [400V]
4 An ideal transformer with a turns ratio of 3:8is fed from a
240V supply. Determine itsoutput voltage. [640V]
5 An ideal transformer has a turns ratio of12:1 and is supplied
at 192V. Calculate thesecondary voltage. [16V]
6 A transformer primary winding connectedacross a 415V supply
has 750 turns.Determine how many turns must be woundon the
secondary side if an output of 1.66 kVis required. [3000 turns]
7 An ideal transformer has a turns ratio of 12:1and is supplied
at 180V when the primarycurrent is 4A. Calculate the
secondaryvoltage and current. [15V, 48A]
8 A step-down transformer having a turns ratioof 20:1 has a
primary voltage of 4 kV anda load of 10 kW. Neglecting losses,
calculatethe value of the secondary current. [50A]
9 A transformer has a primary to secondaryturns ratio of 1:15.
Calculate the primaryvoltage necessary to supply a 240V load. Ifthe
load current is 3A determine the primarycurrent. Neglect any
losses. [16V, 45A]
10 A 10 kVA, single-phase transformer has aturns ratio of 12:1
and is supplied from a2.4 kV supply. Neglecting losses,
determine(a) the full load secondary current, (b) theminimum value
of load resistance which canbe connected across the secondary
windingwithout the kVA rating being exceeded, and(c) the primary
current.
[(a) 50A (b) 4 (c) 4.17A]11 A 20 resistance is connected across
the
secondary winding of a single-phase powertransformer whose
secondary voltage is150V. Calculate the primary voltage andthe
turns ratio if the supply current is 5A,neglecting losses. [225V,
3:2]
21.3 Transformer no-load phasordiagram
The core ux is common to both primary andsecondary windings in a
transformer and is thustaken as the reference phasor in a phasor
diagram.On no-load the primary winding takes a small no-load
current I0 and since, with losses neglected, theprimary winding is
a pure inductor, this current lagsthe applied voltage V1 by 90. In
the phasor diagramassuming no losses, shown in Fig. 21.2(a),
currentI0 produces the ux and is drawn in phase withthe ux. The
primary induced e.m.f. E1 is in phaseopposition to V1 (by Lenzs
law) and is shown 180out of phase with V1 and equal in magnitude.
Thesecondary induced e.m.f. is shown for a 2:1 turnsratio
transformer.
A no-load phasor diagram for a practical trans-former is shown
in Fig. 21.2(b). If current owsthen losses will occur. When losses
are consideredthen the no-load current I0 is the phasor sum oftwo
components (i) IM, the magnetising compo-nent, in phase with the
ux, and (ii) IC, the coreloss component (supplying the hysteresis
and eddycurrent losses). From Fig. 21.2(b):
No-load current, I0 D
I 2M C I 2C whereIM D I0 sinf0 and IC D I0cosf0.
Power factor on no-load D cos0 D IC/I0.The total core losses
(i.e. iron losses)
D V1I0 cos0
Problem 7. A 2400V/400V single-phasetransformer takes a no-load
current of 0.5Aand the core loss is 400W. Determine thevalues of
the magnetising and core losscomponents of the no-load current.
Draw toscale the no-load phasor diagram for thetransformer.
V1 D 2400V,V2 D 400V and I0 D 0.5A Core loss(i.e. iron loss) D
400 D V1I0 cos0.i.e. 400 D 24000.5 cos0Hence cos0 D 400
24000.5D 0.3333
0 D cos1 0.3333 D 70.53The no-load phasor diagram is shown in
Fig. 21.3
Magnetising component,IM D I0 sin0 D 0.5 sin 70.53 D 0.471A.Core
loss component, IC DI0 cos0 D0.5 cos 70.53D 0.167A
TLFeBOOK
-
TRANSFORMERS 307
Figure 21.2
Figure 21.3
Problem 8. A transformer takes a current of0.8A when its primary
is connected to a 240volt, 50Hz supply, the secondary being onopen
circuit. If the power absorbed is72 watts, determine (a) the iron
loss current,(b) the power factor on no-load, and (c)
themagnetising current.
I0 D 0.8A and V D 240V(a) Power absorbed D total core loss D 72
D
V1I0 cos0. Hence 72 D 240I0 cos0 and ironloss current, Ic D I0
cos0 D 72/240 D 0.30A
(b) Power factor at no load,
cos0 D ICI0
D 0.30.8
D 0.375
(c) From the right-angled triangle in Fig. 21.2(b)and using
Pythagoras theorem, I20 D I2C C I2Mfrom which, magnetising
current,
IM D
I20 I2C Dp
0.82 0.32 D 0.74A
Now try the following exercise
Exercise 115 Further problems on theno-load phasor diagram1 A
500V/100V, single-phase transformer takes
a full load primary current of 4A. Neglectinglosses, determine
(a) the full load secondarycurrent, and (b) the rating of the
transformer.
[(a) 20A (b) 2 kVA]2 A 3300V/440V, single-phase transformer
takes a no-load current of 0.8A and theiron loss is 500W. Draw
the no-load phasordiagram and determine the values of
themagnetising and core loss components of theno-load current.
[0.786A, 0.152A]3 A transformer takes a current of 1A when
its primary is connected to a 300V, 50Hzsupply, the secondary
being on open-circuit.
TLFeBOOK
-
308 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
If the power absorbed is 120 watts, calculate(a) the iron loss
current, (b) the power factoron no-load, and (c) the magnetising
current.
[(a) 0.4A (b) 0.4 (c) 0.92A]
21.4 E.m.f. equation of a transformer
The magnetic ux 8 set up in the core of a trans-former when an
alternating voltage is applied to itsprimary winding is also
alternating and is sinusoidal.
Let 8m be the maximum value of the ux and fbe the frequency of
the supply. The time for 1 cycleof the alternating ux is the
periodic time T, whereT D 1/fseconds
The ux rises sinusoidally from zero to its max-imum value in
(1/4) cycle, and the time for (1/4)cycle is 1/4f seconds. Hence the
average rate ofchange of ux D 8m/1/4f D 4f8m Wb/s, andsince 1Wb/s D
1 volt, the average e.m.f. induced ineach turn D 4f8m volts. As the
ux 8 varies sinu-soidally, then a sinusoidal e.m.f. will be induced
ineach turn of both primary and secondary windings.
For a sine wave,
form factor D r.m.s. valueaverage value
D 1.11 (see Chapter 14)Hence r.m.s. value D form factoraverage
value D1.11 average value Thus r.m.s. e.m.f. induced ineach
turn
D 1.11 4f8m voltsD 4.44f8m volts
Therefore, r.m.s. value of e.m.f. induced in primary,
E1 = 4.44 f8mN1 volts 4
and r.m.s. value of e.m.f. induced in secondary,
E2 = 4.44 f8mN2 volts 5
Dividing equation (4) by equation (5) gives:(
E1E2
)D(
N1N2
),
as previously obtained in Section 21.2
Problem 9. A 100 kVA, 4000V/200V,50Hz single-phase transformer
has 100secondary turns. Determine (a) the primaryand secondary
current, (b) the number ofprimary turns, and (c) the maximum value
ofthe ux.
V1 D 4000V, V2 D 200V, f D 50Hz, N2 D 100turns
(a) Transformer ratingDV1I1 DV2I2 D1 00 000VAHence primary
current,
I1 D 1 00 000V1
D 1 00 0004 000
D 25A
and secondary current,
I2 D 1 00 000V2
D 1 00 000200
D 500A
(b) From equation (3), V1V2
D N1N2
from which, pri-mary turns,
N1 D(
V1V2
)N2D
(4000200
)100D2000 turns
(c) From equation (5), E2 D 4.44f8mN2 fromwhich, maximum ux,
8m D E4.44fN2D 200
4.4450100(assuming E2 D V2
D 9.01 103 Wb or 9.01mWb
[Alternatively, equation (4) could have been used,where
E1 D 4.44f8mN1from which,
8m D 40004.44502000
(assuming E1 D V1
D 9.01mWb as above]
TLFeBOOK
-
TRANSFORMERS 309
Problem 10. A single-phase, 50Hztransformer has 25 primary turns
and 300secondary turns. The cross-sectional area ofthe core is 300
cm2. When the primarywinding is connected to a 250V
supply,determine (a) the maximum value of the uxdensity in the
core, and (b) the voltageinduced in the secondary winding.
(a) From equation (4),e.m.f. E1 D 4.44f8mN1 voltsi.e. 250 D
4.44508m(25) from which, maxi-mum ux density,
8m D 2504.445025
Wb D 0.04505Wb
However, 8m D BmA,where Bm D maximumux density in the core and A
D cross-sectionalarea of the core (see Chapter 7). HenceBm 300 104
D 0.04505 from which,
maximum ux density, Bm D 0.04505300 104D 1.50T
(b) V1V2
D N1N2
from which, V2 D V1(
N2N1
)i.e.
voltage induced in the secondary winding,
V2 D 250(300
25
)D 3000V or 3 kV
Problem 11. A single-phase 500V/100V,50Hz transformer has a
maximum core uxdensity of 1.5 T and an effective
corecross-sectional area of 50 cm2. Determine thenumber of primary
and secondary turns.
The e.m.f. equation for a transformer is E D4.44f8mN and maximum
ux, 8m D B A D1.550 104 D 75 104 Wb
Since E1 D 4.44f8mN1 then primary turns,N1 D E14.44f8m D
5004.445075 104
D 300 turnsSince E2 D 4.4f8mN2 then secondary turns,
N2 D E24.44f8m D100
4.445075 104D 60 turns
Problem 12. A 4500V/225V, 50Hzsingle-phase transformer is to
have anapproximate e.m.f. per turn of 15V andoperate with a maximum
ux of 1.4 T.Calculate (a) the number of primary andsecondary turns
and (b) the cross-sectionalarea of the core.
(a) E.m.f. per turn D E1N1
D E2N2
D 15
Hence primary turns, N1 D E115 D450015
D 300
and secondary turns, N2 D E215 D25515
D 15
(b) E.m.f. E1 D 4.44f8mN1 from which,
8mE1
4.44fN1D 4500
4.4450300D 0.0676Wb
Now ux, 8m D Bm A, where A is the cross-sectional area of the
core,
hence area, A D(
8mBm
)D(0.0676
1.4
)
D 0.0483m2 or 483 cm2
Now try the following exercise
Exercise 116 Further problems on thetransformer e.m.f. equation1
A 60 kVA, 1600V/100V, 50Hz, single-phase
transformer has 50 secondary windings. Cal-culate (a) the
primary and secondary current,(b) the number of primary turns, and
(c) themaximum value of the ux
[(a) 37.5A, 600A (b) 800 (c) 9.0mWb]2 A single-phase, 50Hz
transformer has 40 pri-
mary turns and 520 secondary turns. Thecross-sectional area of
the core is 270 cm2.When the primary winding is connected to a300
volt supply, determine (a) the maximumvalue of ux density in the
core, and (b) thevoltage induced in the secondary winding
[(a) 1.25 T (b) 3.90 kV]
TLFeBOOK
-
310 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
3 A single-phase 800V/100V, 50Hz trans-former has a maximum core
ux density of1.294 T and an effective cross-sectional areaof 60
cm2. Calculate the number of turns onthe primary and secondary
windings.
[464, 58]4 A 3.3 kV/110V, 50Hz, single-phase trans-
former is to have an approximate e.m.f. perturn of 22V and
operate with a maximumux of 1.25 T. Calculate (a) the number
ofprimary and secondary turns, and (b) the cross-sectional area of
the core
[(a) 150, 5 (b) 792.8 cm2]
21.5 Transformer on-load phasordiagram
If the voltage drop in the windings of a transformerare assumed
negligible, then the terminal voltage V2is the same as the induced
e.m.f. E2 in the secondary.Similarly, V1 D E1. Assuming an equal
numberof turns on primary and secondary windings, thenE1 D E2, and
let the load have a lagging phaseangle 2
Figure 21.4
In the phasor diagram of Fig. 21.4, current I2lags V2 by angle
2. When a load is connectedacross the secondary winding a current
I2 owsin the secondary winding. The resulting secondarye.m.f. acts
so as to tend to reduce the core ux.
However this does not happen since reduction of thecore ux
reduces E1, hence a reected increase inprimary current I01 occurs
which provides a restoringm.m.f. Hence at all loads, primary and
secondarym.m.f.s are equal, but in opposition, and the coreux
remains constant. I01 is sometimes called thebalancing current and
is equal, but in the oppositedirection, to current I2 as shown in
Fig. 21.4. I0,shown at a phase angle 0 to V1, is the no-loadcurrent
of the transformer (see Section 21.3)
The phasor sum of I01 and I0 gives the supplycurrent I1 and the
phase angle between V1 and I1 isshown as 1
Problem 13. A single-phase transformer has2000 turns on the
primary and 800 turns onthe secondary. Its no-load current is 5A at
apower factor of 0.20 lagging. Assuming thevolt drop in the
windings is negligible,determine the primary current and
powerfactor when the secondary current is 100A ata power factor of
0.85 lagging.
Let I01 be the component of the primary currentwhich provides
the restoring m.m.f. Then
I01N1 D I2N2i.e. I012000 D 100800
from which, I01 D100800
2000D 40A
If the power factor of the secondary is 0.85, thencos2 D 0.85,
from which, 2 D cos1 0.85 D 31.8If the power factor on no-load is
0.20, thencos0 D 0.2 and 0 D cos1 0.2 D 78.5
In the phasor diagram shown in Fig. 21.5, I2 D100A is shown at
an angle of D 31.8 to V2 andI01 D 40A is shown in anti-phase to
I2
The no-load current I0 D 5A is shown at an angleof 0 D 78.5 to
V1. Current I1 is the phasor sumof I01 and I0, and by drawing to
scale, I1 D 44Aand angle 1 D 37.
By calculation,
I1 cos1 D 0a C 0bD I0 cos0 C I01 cos2D 50.2 C 400.85D 35.0A
TLFeBOOK
-
TRANSFORMERS 311
Figure 21.5
and I1 sin1 D 0c C 0dD I0 sin0 C I01 sin2D 5 sin 78.5 C 40 sin
31.8D 25.98A
Hence the magnitude of I1 Dp
35.02 C 25.982 D43.59A and tan 1 D 25.98/35.0 from which,f1 D
tan1 25.98/35.0 D 36.59 Hence thepower factor of the primary D cos1
D cos 36.59 D0.80
Now try the following exercise
Exercise 117 A further problem on thetransformer on-load1 A
single-phase transformer has 2400 turns on
the primary and 600 turns on the secondary.Its no-load current
is 4A at a power factor of0.25 lagging. Assuming the volt drop in
thewindings is negligible, calculate the primarycurrent and power
factor when the secondarycurrent is 80A at a power factor of 0.8
lagging.
[23.26A, 0.73]
21.6 Transformer construction(i) There are broadly two types of
single-phase
double-wound transformer constructions thecore type and the
shell type, as shown in
Fig. 21.6. The low and high voltage windingsare wound as shown
to reduce leakage ux.
Figure 21.6
(ii) For power transformers, rated possibly atseveral MVA and
operating at a frequency of50Hz in Great Britain, the core material
usedis usually laminated silicon steel or stalloy,the laminations
reducing eddy currents andthe silicon steel keeping hysteresis loss
to aminimum.
Large power transformers are used in themain distribution system
and in industrialsupply circuits. Small power transformers havemany
applications, examples including weldingand rectier supplies,
domestic bell circuits,imported washing machines, and so on.
(iii) For audio frequency (a.f.) transformers, ratedfrom a few
mVA to no more than 20VA, andoperating at frequencies up to about
15 kHz, thesmall core is also made of laminated siliconsteel. A
typical application of a.f. transformersis in an audio amplier
system.
(iv) Radio frequency (r.f.) transformers, operat-ing in the MHz
frequency region have eitheran air core, a ferrite core or a dust
core. Ferriteis a ceramic material having magnetic proper-ties
similar to silicon steel, but having a highresistivity. Dust cores
consist of ne particlesof carbonyl iron or permalloy (i.e. nickel
andiron), each particle of which is insulated fromits neighbour.
Applications of r.f. transformersare found in radio and television
receivers.
TLFeBOOK
-
312 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
(v) Transformer windings are usually of enamel-insulated copper
or aluminium.
(vi) Cooling is achieved by air in small transform-ers and oil
in large transformers.
21.7 Equivalent circuit of atransformer
Figure 21.7 shows an equivalent circuit of a trans-former. R1
and R2 represent the resistances of theprimary and secondary
windings and X1 and X2 rep-resent the reactances of the primary and
secondarywindings, due to leakage ux.
The core losses due to hysteresis and eddy cur-rents are allowed
for by resistance R which takes acurrent IC, the core loss
component of the primarycurrent. Reactance X takes the magnetising
compo-nent Im. In a simplied equivalent circuit shown inFig. 21.8,
R and X are omitted since the no-loadcurrent I0 is normally only
about 35 per cent ofthe full load primary current.
It is often convenient to assume that all of theresistance and
reactance as being on one side of
the transformer. Resistance R2 in Fig. 21.8 can bereplaced by
inserting an additional resistance R02 inthe primary circuit such
that the power absorbed inR02 when carrying the primary current is
equal to thatin R2 due to the secondary current, i.e.
I21R02 D I22R2
from which, R02 D R2(
I2I1
)2D R2
(V1V2
)2
Then the total equivalent resistance in the primarycircuit Re is
equal to the primary and secondaryresistances of the actual
transformer.
Hence Re D R1 C R02
i.e. Re = R1 + R2(V1
V2
)26
By similar reasoning, the equivalent reactance in theprimary
circuit is given by Xe D X1 C X02
i.e. Xe = X1 + X2(V1
V2
)27
Figure 21.7
Figure 21.8
TLFeBOOK
-
TRANSFORMERS 313
The equivalent impedance Ze of the primary andsecondary windings
referred to the primary isgiven by
Ze =
R2e + X 2e 8
If e is the phase angle between I1 and the volt dropI1Ze
then
cosfe =ReZe
9
The simplied equivalent circuit of a transformer isshown in Fig.
21.9
Problem 14. A transformer has 600 primaryturns and 150 secondary
turns. The primaryand secondary resistances are 0.25 and0.01
respectively and the correspondingleakage reactances are 1.0 and
0.04respectively. Determine (a) the equivalentresistance referred
to the primary winding,(b) the equivalent reactance referred to
theprimary winding, (c) the equivalentimpedance referred to the
primary winding,and (d) the phase angle of the impedance.
(a) From equation (6), equivalent resistance
Re D R1 C R2(
V1V2
)2
i.e. Re D 0.25 C 0.01(600150
)2
D 0.41Z since N1N2
D V1V2
(b) From equation (7), equivalent reactance,
Xe D X1 C X2(
V1V2
)2
i.e. Xe D 1.0 C 0.04(600150
)2D 1.64Z
(c) From equation (8), equivalent impedance,Ze D
R2e C X2e D
p0.412 C 1.642 D 1.69Z
(d) From equation (9),cose D Re
ZeD 0.41
1.69
Hence fe D cos1 0.411.69 D 75.96
Now try the following exercise
Exercise 118 A further problem on theequivalent circuit of a
transformer1 A transformer has 1200 primary turns and 200
secondary turns. The primary and secondaryresistances are 0.2
and 0.02 respectivelyand the corresponding leakage reactancesare
1.2 and 0.05 respectively. Calculate(a) the equivalent resistance,
reactance andimpedance referred to the primary winding,and (b) the
phase angle of the impedance.
[(a) 0.92, 3.0, 3.14 (b) 72.95]
21.8 Regulation of a transformerWhen the secondary of a
transformer is loaded,the secondary terminal voltage, V2, falls. As
the
Figure 21.9
TLFeBOOK
-
314 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
power factor decreases, this voltage drop increases.This is
called the regulation of the transformerand it is usually expressed
as a percentage ofthe secondary no-load voltage, E2. For
full-loadconditions:
Regulation =(
E2 V2E2
) 100% 10
The fall in voltage, (E2 V2), is caused by theresistance and
reactance of the windings. Typicalvalues of voltage regulation are
about 3% in smalltransformers and about 1% in large
transformers.
Problem 15. A 5 kVA, 200V/400V,single-phase transformer has a
secondaryterminal voltage of 387.6 volts when loaded.Determine the
regulation of the transformer.
From equation (10):
regulationD
No load secondary voltage terminal voltage on loadno load
secondary voltage
100%
D(400 387.6
400
) 100%
D(12.4400
) 100%
D 3.1%
Problem 16. The open circuit voltage of atransformer is 240V. A
tap changing deviceis set to operate when the percentageregulation
drops below 2.5%. Determine theload voltage at which the
mechanismoperates.
RegulationD
No load secondary voltageterminal voltage on loadno load
secondary voltage
100%
Hence 2.5 D(240 V2
240
) 100%
2.5240
100D 240 V2
i.e. 6 D 240 V2from which, load voltage, V2 D 2406 D 234
volts
Now try the following exercise
Exercise 119 Further problems onregulation1 A 6 kVA, 100V/500V,
single-phase trans-
former has a secondary terminal voltage of487.5 volts when
loaded. Determine the reg-ulation of the transformer. [2.5%]
2 A transformer has an open circuit voltageof 110 volts. A
tap-changing device operateswhen the regulation falls below 3%.
Calculatethe load voltage at which the tap-changer oper-ates.
[106.7 volts]
21.9 Transformer losses and efciencyThere are broadly two
sources of losses in trans-formers on load, these being copper
losses and ironlosses.
(a) Copper losses are variable and result in a heat-ing of the
conductors, due to the fact that theypossess resistance. If R1 and
R2 are the primaryand secondary winding resistances then the
totalcopper loss is I21R1 C I22R2
(b) Iron losses are constant for a given value offrequency and
ux density and are of twotypes hysteresis loss and eddy current
loss.(i) Hysteresis loss is the heating of the core as
a result of the internal molecular structurereversals which
occur as the magnetic uxalternates. The loss is proportional to
thearea of the hysteresis loop and thus low lossnickel iron alloys
are used for the core sincetheir hysteresis loops have small
areas.(SeeChapters 7)
(ii) Eddy current loss is the heating of thecore due to e.m.f.s
being induced not onlyin the transformer windings but also in
thecore. These induced e.m.f.s set up circulat-ing currents, called
eddy currents. Owing tothe low resistance of the core, eddy
currentscan be quite considerable and can cause a
TLFeBOOK
-
TRANSFORMERS 315
large power loss and excessive heating of thecore. Eddy current
losses can be reduced byincreasing the resistivity of the core
mate-rial or, more usually, by laminating the core(i.e. splitting
it into layers or leaves) whenvery thin layers of insulating
material canbe inserted between each pair of laminations.This
increases the resistance of the eddy cur-rent path, and reduces the
value of the eddycurrent.
Transformer efciency,
D output powerinput power
D input power - lossesinput power
i.e. h = 1 lossesinput power
11
and is usually expressed as a percentage. It is notuncommon for
power transformers to have efcien-cies of between 95% and 98%
Output power D V2I2 cos2.Total losses D copper loss C iron
losses,and input power D output power C losses
Problem 17. A 200 kVA rated transformerhas a full-load copper
loss of 1.5 kW and aniron loss of 1 kW. Determine the
transformerefciency at full load and 0.85 power factor.
Efciency, D output powerinput power
D input power lossesinput power
D 1 lossesinput power
Full-load output power D VI cos D 200 0.85D 170 kW.
Total losses D 1.5 C 1.0 D 2.5 kWInput power D output power C
lossesD 170 C 2.5 D 172.5 kW.
Hence efciency D(1 2.5
172.5
)D 1 0.01449
D 0.9855 or 98.55%
Problem 18. Determine the efciency ofthe transformer in Problem
17 at halffull-load and 0.85 power factor.
Half full-load power output D 1/22000.85D 85 kW.
Copper loss (or I2R loss) is proportional to cur-rent squared.
Hence the copper loss at half full-loadis:( 12)2
1500 D 375WIron loss D 1000W (constant)Total losses D
375C1000D1375W or 1.375 kW.Input power at half full-loadD output
power at half full-load C lossesD 85 C 1.375 D 86.375 kW. Hence
efciency D 1 lossesinput power
D(1 1.375
86.375
)
D 1 0.01592D 0.9841 or 98.41%
Problem 19. A 400 kVA transformer hasa primary winding
resistance of 0.5 anda secondary winding resistance of 0.001.The
iron loss is 2.5 kW and the primary andsecondary voltages are 5 kV
and 320V respec-tively. If the power factor of the load is
0.85,determine the efciency of the transformer(a) on full load, and
(b) on half load.
(a) Rating D 400 kVA D V1I1 D V2I2. Henceprimary current,
I1 D 400 103
V1D 400 10
3
5000D 80A
and secondary current,
I2 D 400 103
V2D 400 10
3
320D 1250A
Total copper loss D I21R1 C I22R2, (whereR1 D 0.5 and R2 D
0.001
D 8020.5 C 125020.001D 3200 C 1562.5 D 4762.5 wattsOn full load,
total loss D copper lossC iron loss
D 4762.5 C 2500 D 7262.5W D 7.2625 kWTotal output power on full
load
D V2I2 cos2 D 400 1030.85 D 340 kW
TLFeBOOK
-
316 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
Input power D output power C lossesD 340 kW C 7.2625 kW D
347.2625 kW
Efciency, D(1 losses
input power
) 100%
D(1 7.2625
347.2625
) 100%
D 97.91%(b) Since the copper loss varies as the square of
the
current, then total copper loss on half loadD 4762.5 ( 12
)2 D 1190.625W. Hence totalloss on half load D 1190.625 C 2500
D3690.625W or 3.691 kW.Output power on half full load D ( 12
)340
D 170 kW.Input power on half full loadD output power C
losses
D 170 kW C 3.691 kWD 173.691 kWHence efciency at half full
load,
D(1 losses
input power
) 100%
D(1 3.691
173.691
) 100% D 97.87%
Maximum efciencyIt may be shown that the efciency of a
transformeris a maximum when the variable copper loss (i.e.I21R1 C
I22R2) is equal to the constant iron losses.
Problem 20. A 500 kVA transformer has afull load copper loss of
4 kW and an ironloss of 2.5 kW. Determine (a) the output kVAat
which the efciency of the transformer is amaximum, and (b) the
maximum efciency,assuming the power factor of the load is 0.75
(a) Let x be the fraction of full load kVA at whichthe efciency
is a maximum. The correspond-ing total copper loss D 4 kWx2. At
maxi-mum efciency, copper loss D iron loss. Hence4x2 D 2.5 from
which x2 D 2.5/4 andx D p2.5/4 D 0.791.Hence the output kVA at
maximumefciency D 0.791 500 D 395.5 kVA.
(b) Total loss at maximum efciencyD2 2.5D5 kWOutput power D
395.5 kVA p.f.D 395.5 0.75 D 296.625 kWInput power D output power C
lossesD 296.625 C 5 D 301.625 kWMaximum efciency,
D(1 losses
input power
) 100%
D(1 5
301.625
) 100% D 98.34%
Now try the following exercise
Exercise 120 Further problems on lossesand efciency1 A
single-phase transformer has a voltage ratio
of 6:1 and the h.v. winding is supplied at540V. The secondary
winding provides a fullload current of 30A at a power factor of
0.8lagging. Neglecting losses, nd (a) the ratingof the transformer,
(b) the power supplied tothe load, (c) the primary current
[(a) 2.7 kVA (b) 2.16 kW (c) 5A]2 A single-phase transformer is
rated at 40 kVA.
The transformer has full-load copper losses of800W and iron
losses of 500W. Determinethe transformer efciency at full load and
0.8power factor [96.10%]
3 Determine the efciency of the transformerin problem 2 at half
full-load and 0.8 powerfactor [95.81%]
4 A 100 kVA, 2000V/400V, 50Hz, single-phasetransformer has an
iron loss of 600W and afull-load copper loss of 1600W. Calculate
itsefciency for a load of 60 kW at 0.8 powerfactor. [97.56%]
5 Determine the efciency of a 15 kVA trans-former for the
following conditions:(i) full-load, unity power factor(ii) 0.8
full-load, unity power factor(iii) half full-load, 0.8 power
factorAssume that iron losses are 200W and the full-load copper
loss is 300W
[(a) 96.77% (ii) 96.84% (iii) 95.62%]
TLFeBOOK
-
TRANSFORMERS 317
6 A 300 kVA transformer has a primary wind-ing resistance of 0.4
and a secondarywinding resistance of 0.0015. The ironloss is 2 kW
and the primary and secondaryvoltages are 4 kV and 200V
respectively. Ifthe power factor of the load is 0.78, determinethe
efciency of the transformer (a) on fullload, and (b) on half
load.
[(a) 96.84% (b) 97.17%]7 A 250 kVA transformer has a full load
copper
loss of 3 kW and an iron loss of 2 kW. Calcu-late (a) the output
kVA at which the efciencyof the transformer is a maximum, and (b)
themaximum efciency, assuming the power fac-tor of the load is
0.80
[(a) 204.1 kVA (b) 97.61%]
21.10 Resistance matchingVarying a load resistance to be equal,
or almostequal, to the source internal resistance is
calledmatching. Examples where resistance matching isimportant
include coupling an aerial to a transmitteror receiver, or in
coupling a loudspeaker to anamplier, where coupling transformers
may be usedto give maximum power transfer.
With d.c. generators or secondary cells, the inter-nal
resistance is usually very small. In such cases,if an attempt is
made to make the load resistance assmall as the source internal
resistance, overloadingof the source results.
A method of achieving maximum power trans-fer between a source
and a load (see section 13.9,page 179), is to adjust the value of
the load resis-tance to match the source internal resistance.
Atransformer may be used as a resistance matchingdevice by
connecting it between the load and thesource.
The reason why a transformer can be used for thisis shown below.
With reference to Fig. 21.10:
RL D V2I2
and R1 D V1I1
For an ideal transformer,
V1 D(
N1N2
)V2
and I1 D(
N2N1
)I2
Figure 21.10
Thus the equivalent input resistance R1 of thetransformer is
given by:
R1 D V1I1
D
(N1N2
)V2
(N2N1
)I2
D(
N1N2
)2 (V2I2
)D(
N1N2
)2RL
i.e. R1 =(N1
N2
)2RL
Hence by varying the value of the turns ratio,the equivalent
input resistance of a transformer canbe matched to the internal
resistance of a load toachieve maximum power transfer.
Problem 21. A transformer having a turnsratio of 4:1 supplies a
load of resistance100. Determine the equivalent inputresistance of
the transformer.
From above, the equivalent input resistance,
R1 D(
N1N2
)2RL
D(41
)2100 D 1600Z
Problem 22. The output stage of anamplier has an output
resistance of 112.Calculate the optimum turns ratio of atransformer
which would match a loadresistance of 7 to the output resistance
ofthe amplier.
TLFeBOOK
-
318 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
Figure 21.11
The circuit is shown in Fig. 21.11The equivalent input
resistance, R1 of the trans-
former needs to be 112 for maximum powertransfer.
R1 D(
N1N2
)2RL
Hence(
N1N2
)2D R1
RLD 112
7D 16
i.e.N1N2
Dp
16 D 4
Hence the optimum turns ratio is 4:1
Problem 23. Determine the optimum valueof load resistance for
maximum powertransfer if the load is connected to anamplier of
output resistance 150 througha transformer with a turns ratio of
5:1
The equivalent input resistance R1 of the transformerneeds to be
150 for maximum power transfer.
R1 D(
N1N2
)2RL
from which, RL D R1(
N2N1
)2
D 150 ( 15)2 D 6Z
Problem 24. A single-phase, 220V/1760Videal transformer is
supplied from a 220Vsource through a cable of resistance 2. Ifthe
load across the secondary winding is1.28 k determine (a) the
primary currentowing and (b) the power dissipated in theload
resistor.
The circuit diagram is shown in Fig. 21.12
Figure 21.12
(a) Turns ratio(
N1N2
)D(
V1V2
)D( 2201760
)D(18
)
Equivalent input resistance of the transformer.
R1 D(
N1N2
)2RL D
(18
)21.28 103 D 20
Total input resistance,RIN D R C R1 D 2 C 20 D 22Primary
current,
I1 D V1RIN
D 22022
D 10A
(b) For an ideal transformerV1V2
D I2I1
from which,
I2 D I1(
V1V2
)D 10
(2201760
)D 1.25A
Power dissipated in load resistor RL,
P D I22RL D 1.2521.28 103D 2000 watts or 2 kW
Problem 25. An a.c. source of 24V andinternal resistance 15 k is
matched to aload by a 25:1 ideal transformer. Determine(a) the
value of the load resistance and(b) the power dissipated in the
load.
The circuit diagram is shown in Fig. 21.13
(a) For maximum power transfer R1 needs to beequal to 15 k.
R1 D(
N1N2
)2RL
from which, load resistance,
TLFeBOOK
-
TRANSFORMERS 319
Figure 21.13
RL D R1(
N2N1
)2D 15 000
(125
)2D 24Z
(b) The total input resistance when the source isconnected to
the matching transformer is RIN CR1 i.e. 15 k C 15 k D 30 k.Primary
current,
I1 D V30000 D24
30000D 0.8mA
N1/N2 D I2/I1 from which, I2 D I1N1/N2 D0.8 10325/1 D 20 103
A.Power dissipated in the load RL,
P D I22RL D 20 103224D 9600 106 W D 9.6mW
Now try the following exercise
Exercise 121 Further problems onresistance matching1 A
transformer having a turns ratio of
8:1 supplies a load of resistance 50.Determine the equivalent
input resistance ofthe transformer. [3.2 k]
2 What ratio of transformer is required to makea load of
resistance 30 appear to have aresistance of 270? [3:1]
3 Determine the optimum value of loadresistance for maximum
power transfer if theload is connected to an amplier of
outputresistance 147 through a transformer witha turns ratio of 7:2
[12]
4 A single-phase, 240V/2880V ideal trans-former is supplied from
a 240V sourcethrough a cable of resistance 3. If theload across the
secondary winding is 720determine (a) the primary current owing
and
(b) the power dissipated in the load resistance.[(a) 30A (b) 4.5
kW]
5 A load of resistance 768 is to be matchedto an amplier which
has an effective outputresistance of 12. Determine the turns
ratioof the coupling transformer. [1:8]
6 An a.c. source of 20V and internal resistance20 k is matched
to a load by a 16:1 single-phase transformer. Determine (a) the
value ofthe load resistance and (b) the power dissi-pated in the
load.
[(a) 78.13 (b) 5mW]
21.11 Auto transformersAn auto transformer is a transformer
which haspart of its winding common to the primary andsecondary
circuits. Fig. 21.14(a) shows the circuitfor a double-wound
transformer and Fig. 21.14(b)that for an auto transformer. The
latter shows thatthe secondary is actually part of the primary,
thecurrent in the secondary being (I2 I1). Sincethe current is less
in this section, the cross-sectionalarea of the winding can be
reduced, which reducesthe amount of material necessary.
Figure 21.14
Figure 21.15 shows the circuit diagram symbolfor an auto
transformer.
Figure 21.15
Problem 26. A single-phase autotransformer has a voltage ratio
320V:250Vand supplies a load of 20 kVA at 250V.Assuming an ideal
transformer, determinethe current in each section of the
winding.
Rating D 20 kVA D V1I1 D V2I2.
TLFeBOOK
-
320 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
Hence primary current,
I1 D 20 103
V1D 20 10
3
320D 62.5A
and secondary current,
I2 D 20 103
V2D 20 10
3
250D 80A
Hence current in common part of the windingD 80 62.5 D 17.5A
The current owing in each section of thetransformer is shown in
Fig. 21.16
Figure 21.16
Saving of copper in an auto transformerFor the same output and
voltage ratio, the autotransformer requires less copper than an
ordinarydouble-wound transformer. This is explained below.
The volume, and hence weight, of copper requiredin a winding is
proportional to the number of turnsand to the cross-sectional area
of the wire. In turnthis is proportional to the current to be
carried, i.e.volume of copper is proportional to NI.
Volume of copper in an auto transformer/ N1 N2I1 C N2I2 I1
see Fig. 21.14(b)/ N1I1 N2I1 C N2I2 N2I1/ N1I1 C N2I2 2N2I1/
2N1I1 2N2I1 (since N2I2 D N1I1
Volume of copper in a double-wound transformer/ N1I1 C N2I2 /
2N1I1
(again, since N2I2 D N1I1). Hencevolume of copper inan auto
transformer
volume of copper in adouble-wound transformer
D 2N1I1 2N2I12N1I1
D 2N1I12N1I1
2N2I12N1I1
D 1 N2N1
If N2/N1 D x then
(volume of copper in an auto transformer)= .1 x/ (volume of
copper in a double-
wound transformer) .12/
If, say, x D 4/5 then (volume of copper in autotransformer)
D (1 45) (volume of copper in a
double-wound transformer)D 15 (volume in double-wound
transformer)
i.e. a saving of 80%.Similarly, if x D 1/4, the saving is 25 per
cent,
and so on. The closer N2 is to N1, the greater thesaving in
copper.
Problem 27. Determine the saving in thevolume of copper used in
an auto transformercompared with a double-wound transformerfor (a)
a 200V:150V transformer, and (b) a500V:100V transformer.
(a) For a 200V:150V transformer,
x D V2V1
D 150200
D 0.75Hence from equation (12), (volume of copper inauto
transformer)
D 1 0.75 (volume of copper indouble-wound transformer)D 0.25
(volume of copper indouble-wound transformer)D 25% (of copper in
adouble-wound transformer)Hence the saving is 75%
(b) For a 500V:100V transformer,
x D V2V1
D 100500
D 0.2
TLFeBOOK
-
TRANSFORMERS 321
Hence, (volume of copper in auto transformer)
D 1 0.2 (volume of copper indouble-wound transformer)D 0.8
(volume in double-wound transformer)D 80% of copper in a
double-wound transformerHence the saving is 20%.
Now try the following exercise
Exercise 122 Further problems on theauto-transformer1 A
single-phase auto transformer has a volt-
age ratio of 480V:300V and supplies a loadof 30 kVA at 300V.
Assuming an ideal trans-former, calculate the current in each
section ofthe winding.[I1 D 62.5A, I2 D 100A, (I2 I1 D 37.5A]
2 Calculate the saving in the volume ofcopper used in an auto
transformer comparedwith a double-wound transformer for (a)a
300V:240V transformer, and (b) a400V:100V transformer [(a) 80% (b)
25%]
Advantages of auto transformersThe advantages of auto
transformers over double-wound transformers include:
1 a saving in cost since less copper is needed (seeabove)
2 less volume, hence less weight3 a higher efciency, resulting
from lower I2R
losses4 a continuously variable output voltage is achiev-
able if a sliding contact is used5 a smaller percentage voltage
regulation.
Disadvantages of auto transformersThe primary and secondary
windings are not electri-cally separate, hence if an open-circuit
occurs in thesecondary winding the full primary voltage
appearsacross the secondary.
Uses of auto transformersAuto transformers are used for reducing
the voltagewhen starting induction motors (see Chapter 23) and
for interconnecting systems that are operating atapproximately
the same voltage.
21.12 Isolating transformersTransformers not only enable current
or voltageto be transformed to some different magnitudebut provide
a means of isolating electrically onepart of a circuit from another
when there isno electrical connection between primary andsecondary
windings. An isolating transformer isa 1:1 ratio transformer with
several importantapplications, including bathroom
shaver-sockets,portable electric tools, model railways, and so
on.
21.13 Three-phase transformersThree-phase double-wound
transformers are mainlyused in power transmission and are usually
of thecore type. They basically consist of three pairsof
single-phase windings mounted on one core, asshown in Fig. 21.17,
which gives a considerablesaving in the amount of iron used. The
primary andsecondary windings in Fig. 21.17 are wound on topof each
other in the form of concentric cylinders,similar to that shown in
Fig. 21.6(a). The windingsmay be with the primary delta-connected
and thesecondary star-connected, or star-delta, star-star
ordelta-delta, depending on its use.
A delta-connection is shown in Fig. 21.18(a) anda
star-connection in Fig. 21.18(b).
Problem 28. A three-phase transformer has500 primary turns and
50 secondary turns. Ifthe supply voltage is 2.4 kV nd thesecondary
line voltage on no-load when thewindings are connected (a)
star-delta, (b)delta-star.
(a) For a star-connection, VL Dp
3Vp (see Chap-ter 20). Primary phase voltage,
Vp D VL1p3 D2400p
3D 1385.64 volts.
For a delta-connection, VL D Vp. N1/N2 DV1/V2 from which,
secondary phase voltage,
Vp2 D Vp1(
N2N1
)D 1385.64
( 50500
)
D 138.6 volts
TLFeBOOK
-
322 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
Figure 21.17
Figure 21.18
(b) For a delta-connection, VL D Vp hence, primaryphase voltage
Vp1 D 2.4 kV D 2400 volts.Secondary phase voltage,
Vp2 D Vp1(
N2N1
)D 2400
( 50500
)D 240 volts
For a star-connection, VL Dp
3Vp hence, thesecondary line voltage, VL2 D
p3240
D 416 volts.
Now try the following exercise
Exercise 123 A further problem on thethree-phase transformer1 A
three-phase transformer has 600 primary
turns and 150 secondary turns. If the supplyvoltage is 1.5 kV
determine the secondary linevoltage on no-load when the windings
areconnected (a) delta-star (b) star-delta
[(a) 649.5V (b) 216.5V]
TLFeBOOK
-
TRANSFORMERS 323
21.14 Current transformersFor measuring currents in excess of
about 100Aa current transformer is normally used. With ad.c.
moving-coil ammeter the current required togive full scale deection
is very small typicallya few milliamperes. When larger currents are
to bemeasured a shunt resistor is added to the circuit (seeChapter
10). However, even with shunt resistorsadded it is not possible to
measure very largecurrents. When a.c. is being measured a shunt
cannotbe used since the proportion of the current whichows in the
meter will depend on its impedance,which varies with frequency.
In a double-wound transformer:I1I2
D N2N1
from which,
secondary current I2 = I1(N2
N1
)
In current transformers the primary usually consistsof one or
two turns whilst the secondary can haveseveral hundred turns. A
typical arrangement isshown in Fig. 21.19
Figure 21.19
If, for example, the primary has 2 turns and thesecondary 200
turns, then if the primary current is500A,
secondary current, I2 D I1(
N2N1
)D 500
(2
200
)
D 5ACurrent transformers isolate the ammeter from the
main circuit and allow the use of a standard range
of ammeters giving full-scale deections of 1A, 2Aor 5A.
For very large currents the transformer core canbe mounted
around the conductor or bus-bar. Thusthe primary then has just one
turn.
It is very important to short-circuit the secondarywinding
before removing the ammeter. This isbecause if current is owing in
the primary,dangerously high voltages could be induced in
thesecondary should it be open-circuited.
Current transformer circuit diagram symbols areshown in Fig.
21.20
Figure 21.20
Problem 29. A current transformer has asingle turn on the
primary winding and asecondary winding of 60 turns. Thesecondary
winding is connected to anammeter with a resistance of 0.15.
Theresistance of the secondary winding is0.25. If the current in
the primary windingis 300A, determine (a) the reading on
theammeter, (b) the potential difference acrossthe ammeter and (c)
the total load (in VA) onthe secondary.
(a) Reading on the ammeter,
I2 D I1(
N1N2
)D 300
(160
)D 5A.
(b) P.d. across the ammeter D I2RA, (where RA is theammeter
resistance D 50.15 D 0.75 volts.(c) Total resistance of secondary
circuit D
0.15 C 0.25 D 0.40.Induced e.m.f. in secondaryD 50.40D2.0V.Total
load on secondary D 2.05 D 10VA.
Now try the following exercise
Exercise 124 A further problem on thecurrent transformer1 A
current transformer has two turns on the
primary winding and a secondary winding of
TLFeBOOK
-
324 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
260 turns. The secondary winding is connectedto an ammeter with
a resistance of 0.2.The resistance of the secondary winding is0.3.
If the current in the primary windingis 650A, determine (a) the
reading on theammeter, (b) the potential difference acrossthe
ammeter, and (c) the total load in VA onthe secondary [(a) 5A (b)
1V (c) 7.5VA]
21.15 Voltage transformers
For measuring voltages in excess of about 500V itis often safer
to use a voltage transformer. Theseare normal double-wound
transformers with a largenumber of turns on the primary, which is
connectedto a high voltage supply, and a small number of turnson
the secondary. A typical arrangement is shownin Fig. 21.21
Figure 21.21
SinceV1V2
D N1N2
the secondary voltage,
V2 D V1N2V1
Thus if the arrangement in Fig. 21.21 has 4000primary turns and
20 secondary turns then for avoltage of 22 kV on the primary, the
voltage on thesecondary,
V2 D V1(
N2N1
)D 22 000
( 204000
)D 110 volts
Now try the following exercises
Exercise 125 Short answer questions ontransformers1 What is a
transformer?2 Explain briey how a voltage is induced in
the secondary winding of a transformer3 Draw the circuit diagram
symbol for a
transformer4 State the relationship between turns and volt-
age ratios for a transformer5 How is a transformer rated?6 Briey
describe the principle of operation of
a transformer7 Draw a phasor diagram for an ideal trans-
former on no-load8 State the e.m.f. equation for a transformer9
Draw an on-load phasor diagram for an ideal
transformer with an inductive load10 Name two types of
transformer construction11 What core material is normally used
for
power transformers12 Name three core materials used in r.f.
trans-
formers13 State a typical application for (a) a.f. trans-
formers (b) r.f. transformers14 How is cooling achieved in
transformers?15 State the expressions for equivalent resis-
tance and reactance of a transformer, referredto the primary
16 Dene regulation of a transformer17 Name two sources of loss
in a transformer18 What is hysteresis loss? How is it minimised
in a transformer?19 What are eddy currents? How may they be
reduced in transformers?20 How is efciency of a transformer
calcu-
lated?21 What is the condition for maximum ef-
ciency of a transformer?22 What does resistance matching
mean?
TLFeBOOK
-
TRANSFORMERS 325
23 State a practical application where matchingwould be used
24 Derive a formula for the equivalent resistanceof a
transformer having a turns ratio ofN1 : N2 and load resistance
RL
25 What is an auto transformer?
26 State three advantages and one disadvantageof an auto
transformer compared with adouble-wound transformer
27 In what applications are auto transformersused?
28 What is an isolating transformer? Give twoapplications
29 Describe briey the construction of a three-phase
transformer
30 For what reason are current transformersused?
31 Describe how a current transformer operates
32 For what reason are voltage transformersused?
33 Describe how a voltage transformer operates
Exercise 126 Multi-choice questions ontransformers (Answers on
page 376)1 The e.m.f. equation of a transformer of
secondary turns N2, magnetic ux densityBm, magnetic area of core
a, and operatingat frequency f is given by:(a) E2 D 4.44N2Bmaf
volts
(b) E2 D 4.44N2Bmfa
volts
(c) E2 D N2Bmfa
volts
(d) E2 D 1.11N2Bm a f volts2 In the auto-transformer shown in
Fig. 21.22,
the current in section PQ is:(a) 3.3A (b) 1.7A (c) 5A (d)
1.6A
3 A step-up transformer has a turns ratio of10. If the output
current is 5A, the inputcurrent is:(a) 50A (b) 5A (c) 2.5A (d)
0.5A
V1
V2
1.7A
3.3A
Q
p
Figure 21.22
4 A 440V/110V transformer has 1000 turns onthe primary winding.
The number of turns onthe secondary is:(a) 550 (b) 250 (c) 4000 (d)
25
5 An advantage of an auto-transformer is that:(a) it gives a
high step-up ratio(b) iron losses are reduced(c) copper loss is
reduced(d) it reduces capacitance between turns6 A 1 kV/250V
transformer has 500 turns on
the secondary winding. The number of turnson the primary is:(a)
2000 (b) 125 (c) 1000 (d) 250
7 The core of a transformer is laminated to:(a) limit hysteresis
loss(b) reduce the inductance of the windings(c) reduce the effects
of eddy current loss(d) prevent eddy currents from occurring
8 The power input to a mains transformer is200W. If the primary
current is 2.5A, thesecondary voltage is 2V and assuming nolosses
in the transformer, the turns ratio is:(a) 40:1 step down (b) 40:1
step up(c) 80:1 step down (d) 80:1 step up
9 A transformer has 800 primary turns and 100secondary turns. To
obtain 40 V from thesecondary winding the voltage applied to
theprimary winding must be:(a) 5V (b) 320V(c) 2.5V (d) 20VA 100
kVA, 250V/10 kV, single-phase trans-former has a full-load copper
loss of 800Wand an iron loss of 500W. The primary wind-ing contains
120 turns. For the statements in
TLFeBOOK
-
326 ELECTRICAL AND ELECTRONIC PRINCIPLES AND TECHNOLOGY
questions 10 to 16, select the correct answerfrom the following
list:(a) 81.3 kW (b) 800W (c) 97.32%(d) 80 kW (e) 3 (f) 4800(g) 1.3
kW (h) 98.40% (i) 100 kW(j) 98.28% (k) 200W (l) 101.3 kW(m) 96.38%
(n) 400W
10 The total full-load losses11 The full-load output power at
0.8 power factor12 The full-load input power at 0.8 power factor13
The full-load efciency at 0.8 power factor14 The half full-load
copper loss15 The transformer efciency at half full-load,
0.8 power factor16 The number of secondary winding turns17 Which
of the following statements is false?
(a) In an ideal transformer, the volts per turnare constant for
a given value of primaryvoltage
(b) In a single-phase transformer, the hystere-sis loss is
proportional to frequency
(c) A transformer whose secondary current isgreater than the
primary current is a step-up transformer
(d) In transformers, eddy current loss isreduced by laminating
the core
18 An ideal transformer has a turns ratio of 1:5and is supplied
at 200V when the primarycurrent is 3 A. Which of the following
state-ments is false?
(a) The turns ratio indicates a step-up trans-former
(b) The secondary voltage is 40V(c) The secondary current is
15A(d) The transformer rating is 0.6 kVA(e) The secondary voltage
is 1 kV(f) The secondary current is 0.6A
19 Iron losses in a transformer are due to:(a) eddy currents
only(b) ux leakage(c) both eddy current and hysteresis losses(d)
the resistance of the primary and secondary
windings
20 A load is to be matched to an amplierhaving an effective
internal resistance of 10via a coupling transformer having a
turnsratio of 1:10. The value of the load resistancefor maximum
power transfer is:(a) 100 (b) 1 k(c) 100m (d) 1m
TLFeBOOK