EE 8602 Protection and switchgear

Page 2: EE 8602 protection and switchgear

Unit 03 Apparatus protection

• Current transformers and Potential transformers and their applications in protection schemes - Protection of transformer, generator, motor, bus bars and transmission line.

Page 3: EE 8602 protection and switchgear

Basic protection circuit

Page 4: EE 8602 protection and switchgear

Instrument transformers.

• For the measurement of large currents and high voltages in AC circuits, specially constructed accurate ratio transformers are used in conjunction with low range AC instruments. These specially constructed transformers are known as instrument transformers.

Page 5: EE 8602 protection and switchgear

Types of instrument transformer.

• There are two types of instrument transformer.

• These are:

• Potential Transformers (PTs)

• Current Transformers (CTs)

Page 6: EE 8602 protection and switchgear

Working & Construction of Current Transformer

Page 7: EE 8602 protection and switchgear

Current transformer

• The current transformer basically consists of an iron core on which a primary and one or two secondary windings are wound.

• The primary winding has one or two turns of thick wire and is connected in series with the load. It carries the actual power system current.

• Primary current ratings vary from 10 A to 3000 A or more.

Page 8: EE 8602 protection and switchgear

Current transformer in substation

Page 9: EE 8602 protection and switchgear

Current transformer

• The secondary winding has a large number of turns of fine wire. It is connected across current coils of indicting and metering instruments and protective relays. The secondary current ratings are of the order of 5 A, 1 A, and 0.1 A. The latter is used for static relay

Page 10: EE 8602 protection and switchgear

Current transformer -terms

• The ratio of primary current to the secondary current is known as the transformation ratio of the CT. The transformation ratio of a CT is usually high.

• The product of voltage and current on the secondary side when it is supplying its maximum rated value of current is known as the rated burden and is measured in volt-amperes (VA).

• The volt-ampere rating of CTs is low (5 – 150 VA) as compared to that of power transformers.

Page 11: EE 8602 protection and switchgear

Potential transformers

• The PTs are highly accurate ratio step down transformers. Its primary winding has a large number of turns and is always connected across the supply system.

• Its secondary winding has few numbers of turns and is connected to the potential coil of indicting and metering instruments and protective relays.

Page 12: EE 8602 protection and switchgear

Potential transformers

• The primaries of PT are rated from 400 V to several thousand volts and secondaries always for 110 V

Page 13: EE 8602 protection and switchgear

Potential transformers used in sub station

Page 14: EE 8602 protection and switchgear

Potential transformers- terms

• The ratio of the rated primary voltage to the rated secondary voltage is known as the turn or transformation ratio of PT.

• The burden is the total external volt-ampere load on the secondary at the rated secondary voltage.

Page 15: EE 8602 protection and switchgear

Advantages of Instrument Transformers

• 1. When instruments are used in conjunction with

instrument transformers, their readings do not depend upon their constants (R, L, C), as is the case with shunts and multipliers.

• 2. We can use moderate size meters for measurements, i.e., 5 A for current and 100 to 120 V for voltage measurements.

• 3. Instruments and meters can be standardized so that there is saving in overall costs. Replacement of damaged instruments becomes easy.

• 4. The metering circuit is isolated from the high voltage circuits. Hence the safety is assured for the operators.

• 5. Power consumption in the metering circuit becomes low.

Page 16: EE 8602 protection and switchgear
Page 17: EE 8602 protection and switchgear

Transmission Line Protection

Distance Protection Over Current Protection

Differential Protection.

Main and Back up Protection

Page 18: EE 8602 protection and switchgear

Distance Relay Protection

• The basic principle is that the apparent impedance seen by the relay reduces drastically in case of line fault.

• If the ratio of apparent impedance to the positive sequence impedance is less than unity, it indicates a fault. This protection scheme is inherently directional.

Impedance relay and Mho relay use this principle.

Page 19: EE 8602 protection and switchgear

Distance Relay Protection

Page 20: EE 8602 protection and switchgear

Over Current Relay Protection Principle of Over current Protection • When the current in a system exceeds a

predetermined value, it indicates the presence of a fault. Relaying decision is based solely on the magnitude of current.

Over current relaying and fuse protection uses this principle

Used in radial distribution systems.

Page 21: EE 8602 protection and switchgear

Over Current Relay Protection

Page 22: EE 8602 protection and switchgear

Directional Over Relay Protection

• Directional Over current Protection Uses both magnitude of current and phase angle information for decision making. Used in radial distribution systems with source at both ends

Page 23: EE 8602 protection and switchgear

Directional Over Relay Protection

Page 24: EE 8602 protection and switchgear

Differential Relay Protection for Transmission Line

By comparing the two currents either in magnitude or in phase or in both, fault can be determined.

Its implementation requires a communication channel.

It is extremely accurate.

Its zone is demarkated by CTs

Page 25: EE 8602 protection and switchgear

Differential Relay Protection for Transmission Line

Page 26: EE 8602 protection and switchgear

Bus bar Protection

Page 27: EE 8602 protection and switchgear
Page 28: EE 8602 protection and switchgear
Page 29: EE 8602 protection and switchgear
Page 30: EE 8602 protection and switchgear
Page 31: EE 8602 protection and switchgear
Page 32: EE 8602 protection and switchgear
Page 33: EE 8602 protection and switchgear
Page 34: EE 8602 protection and switchgear

NPR COLLEGE OF ENGINEERING AND TECHNOLOGY Natham, Dindigul-624401

UNIT -III

APPARATUS PROTECTION

(PART II)

Presented by,

M.Edwinlawrance, Assistant Professor

Department of Electrical and Electronics Engineering

Page 35: EE 8602 protection and switchgear

Syllabus

Current transformers and Potential transformers and their applications in protection schemes - Protection of transformer, generator, motor, bus bars and transmission line

Department of Electrical and Electronics Engineering

Page 36: EE 8602 protection and switchgear

Transformer Protection

• The power transformer is a major and very important equipment in a power system.

• It requires highly reliable protective devices.

• The protective scheme depends on the size of the transformer.

• The rating of transformers used in transmission and distribution systems range from a few kVA

to several hundred MVA.

• Bus zone protection includes, besides the busbar itself, all the apparatus connected to the busbars

such as circuit breakers, disconnecting switches, instrument transformers and bus sectionalizing

reactors etc.

Department of Electrical and Electronics Engineering

Page 37: EE 8602 protection and switchgear

Transformer Protection

1. Types of Faults Encountered in Transformers

The faults encountered in transformer can be placed in two main groups. (a) External faults (or through faults)

(b) Internal faults

(a) External Faults • In case of external faults, the transformer must be disconnected if other

to operate for such faults, fail to operate within a predetermined time.

protective devices meant

• For external faults, time graded overcurrent relays are employed as back-up protection.

Department of Electrical and Electronics Engineering

Page 38: EE 8602 protection and switchgear

r Transformer Protection

(b) Internal Faults The primary protection of transformers is meant for internal faults. Internal faults are classified into

two groups.

(i) Short circuits in the transformer winding and connections These are electrical faults of serious nature and are likely to cause immediate damage.

(ii) Incipient faults Initially, such faults are of minor nature but slowly might develop into major faults.

Department of Electrical and Electronics Engineering

Page 39: EE 8602 protection and switchgear

2. Percentage Differential Protection • Percentage

protection is

differential used for the

protection of large power transformers having ratings above.

of 5 MVA and

• This scheme is employed for the protection of transformers against internal short circuits.

• It is not capable of detecting incipient faults.

Fig. 1 Percentage differential protection for star-delta connected transformer

Department of Electrical and Electronics Engineering

Page 40: EE 8602 protection and switchgear

Percentage Differential Protection • The direction of current and the polarity of the CT voltage shown in the figure

instant.

The convention for marking the polarity for upper and lower CTs is the same.

The current entering end has been marked as positive.

The end at which current is leaving has been marked negative.

are for a particular

The relay settings for transformer protection are kept higher than those for alternators. The typical value of alternator is 10% for operating coil and 5% for bias. The corresponding values for transformer may be

40% and 10% respectively. The reasons for a higher setting in the case of transformer protection are.

(i) A transformer is provided with on-load tap changing gear. The CT ratio cannot be changed with

varying transformation ratio of the power transformer. The CT ratio is fi xed and it is kept to suit the

nominal ratio of the power transformer.

(ii) When a transformer is on no-load, there is no-load current in the relay.

Department of Electrical and Electronics Engineering

Page 41: EE 8602 protection and switchgear

3. Overheating Protection • The rating of a transformer depends on the temperature rise above an assumed maximum

ambient temperature.

Sustained overload is not allowed if the ambient temperature is equal to the assumed ambient

temperature.

At lower ambient temperature, some overloading is permissible.

The overloading will depend on the ambient temperature prevailing at the time of operation.

The maximum safe overloading is that which does not overheat the winding.

The maximum allowed temperature is about 95°C.

Thus the protection against overload depends on the winding temperature which is usually

measured by thermal image technique.

In the thermal image technique, a temperature sensing device is placed in the transformer oil near

the top of the transformer tank.

Department of Electrical and Electronics Engineering

Page 42: EE 8602 protection and switchgear

4. Protection against Magnetising Inrush Current

• When an unloaded transformer is switched on, it draws a large initial magnetizing current

which may be several times the rated current

of the transformer.

This initial magnetising current is called the

magnetising inrush current.

• As the inrush current flows only in the primary winding, the differential protection will see this inrush current as an internal fault.

The harmonic contents in the inrush current

are different than those in usual fault current.

Fig. 2 Harmonic restraint relay

Department of Electrical and Electronics Engineering

Page 43: EE 8602 protection and switchgear

4. Protection against Magnetising Inrush Current

• Figure 2 shows a high speed biased differential scheme incorporating a harmonic restraint feature.

The relay of this scheme is made insensitive to magnetic inrush current. •

• The operating principle is to filter out the and add them to the percentage restraint.

harmonics from the differential current, rectify them

Department of Electrical and Electronics Engineering

Page 44: EE 8602 protection and switchgear

5. Buchholz Relay •

It is a gas actuated relay. It is used to detect incipient

faults which are initially minor

faults but may cause major faults in due course of time. The Buchholz relay is used to

supplement biased differential

protection of the transformer

Fig. 3 (a) Transformer tank, Buchholz relay and conservator (b) Buchholz relay because the Buchholz relay • When a fault develops slowly, it produces heat, thereby cannot necessarily

circuits within the

or at the terminals.

detect short transformer

decomposing transform.

solid or liquid insulating material in the

• The decomposition of the insulating material produces inflammable gases.

Department of Electrical and Electronics Engineering

Page 45: EE 8602 protection and switchgear

6. Oil Pressure Relief Devices

• An oil pressure relief device is fitted at the top of the transformer tank.

• In its simplest form, it is a frangible disc located at the end of an oil relief pipe protruding from the

top of the transformer tank.

• In case of a serious fault, a surge in the oil is developed, which bursts the disc, thereby allowing

the oil to discharge rapidly.

• This avoids the explosive rupture of the tank and the risk of fire.

Department of Electrical and Electronics Engineering

Page 46: EE 8602 protection and switchgear

7. Rate of Rise of Pressure Relay • This device is capable of detecting a rapid rise of

pressure, rather than absolute pressure.

Its operation is quicker than the pressure relief

valve.

It is employed in transformers which are provided

with gas cushions instead of conservators.

The bellows is placed in the transformer oil. The

relay is placed at the bottom of the tank where

maintenance jobs can be performed conveniently.

It operates on the principle of rate or increase of

pressure.

It is usually designed to trip the transformer.

Fig. 4 Sudden pressure relay

Department of Electrical and Electronics Engineering

Page 47: EE 8602 protection and switchgear

8. Overcurrent Relays

• Overcurrent relays are used for the protection of transformers of rating 100 kVA and below 5

MVA.

• An earth fault tripping element is also provided in addition to the overcurrent feature.

• Such relays are used as primary protection for transformers which are not provided with

differential protection.

• Overcurrent relays are also used as back-up protection where differential protection is used as

primary protection.

Department of Electrical and Electronics Engineering

Page 48: EE 8602 protection and switchgear

9. Earth Fault Relays • A simple overcurrent and earth fault relay does not

provide good protection for a star connected winding,

particularly when the neutral point is earthed through

an impedance.

Restricted earth fault protection, as shown in Fig. 5

provides better protection.

• This scheme is used for the winding of the

transformer connected in star where the neutral point

through an is either solidly earthed or earthed

impedance.

The relay used is

Fig. 5. Earth fault protection of a power transformer • of high impedance type to make the

scheme stable for external faults.

Department of Electrical and Electronics Engineering

Page 49: EE 8602 protection and switchgear

10. Overfluxing Protection •

The magnetic flux increases when voltage increases.

This results in increased iron loss and magnetising current.

The core and core bolts get heated and the lamination insulation is affected.

Protection against overfluxing is required where overfluxing due to sustained

occur.

overvoltage can

• The reduction in frequency also increases the flux

as those due to overvoltage.

The expression of flux in a transformer is given by

density and consequently, it has similar effects

where, phi = flux, f = frequency, E = applied voltage and K = constant.

Department of Electrical and Electronics Engineering

Page 50: EE 8602 protection and switchgear

11. Protection of Earthing Transformer • The function of an earthing transformer is to provide a

grounding point for the power system where machines

have delta connection.

An earthing transformer is connected either in star-

delta or zig-zag fashion.

When a fault occurs only zero sequence current flows

from the earthing transformer to the grounding point.

Positive or negative sequence currents can flow only

towards the earthing transformer and not away from it.

An earthing transformer can be protected by IDMT

Fig. 6. Protection of earthing transformer

overcurrent relays fed by delta connected CTs, as shown in Fig. 6.

Department of Electrical and Electronics Engineering

Page 51: EE 8602 protection and switchgear

12. Protection of Three-Winding Transformer •

In a three-winding transformer, one of the three windings is connected to the source of supply. The other two windings feed loads at different voltages.

When a three-winding transformer is connected to the source of supply at both primary and

secondary side, the distribution of current cannot readily be predicted and there is a possibility of

current circulation between two sets of paralleled CTs without producing any bias.

Fig. 7 Protection of three-winding transformer with power source at one end

Department of Electrical and Electronics Engineering

Page 52: EE 8602 protection and switchgear

12. Protection of Three-Winding Transformer •

Figure .8 shows protective scheme for such a situation. In this case, the restraint depends on the scalar sum of the currents in the various windings.

Fig. 10.8 Protection of three-winding transformer with power source at both ends

Department of Electrical and Electronics Engineering

Page 53: EE 8602 protection and switchgear

13. Generator-Transformer Unit Protection • In a modern system, each generator is directly connected to the delta connected primary winding of

the power transformer.

The star connected secondary winding is HV winding and it is connected to the HV bus through a

circuit breaker.

• In addition, to normal protection of the generator and transformer, an overall protection is provided to protect both the generator and transformer as one unit.

biased differential

• Usually harmonic restraint is not provided because the transformer is only connected to the busbar at full voltage.

Fig. 9 Differential protection of generator transformer unit

Department of Electrical and Electronics Engineering

Page 54: EE 8602 protection and switchgear

14. Miscellaneous 14.1 Tank-earth Protection • If the transformer tank is nominally insulated from earth (an insulation resistance

being sufficient), the primary of a CT is connected between the tank and earth.

A relay is connected to the secondary of the CT.

This protection is similar to the frame earth scheme of protection for busbar.

This is also called Harward protection.

of 10 ohms

14.2 Neutral Displacement • In case of unearthed transformer, an earth fault elsewhere in the system

may result in the displacement of the neutral.

The secondary of the potential transformer is connected in open delta.

Its output which is applied to the relay is proportional to the zero sequence

voltage of the line, i.e. any displacement of the neutral point.

• Fig. 10. Neutral displacement detection

Department of Electrical and Electronics Engineering

Page 55: EE 8602 protection and switchgear

Bus zone protection

BUSZONE PROTECTION 1. Differential Current Protection

The operating principle is based on Kirchhoff ’s law. The algebraic sum of all the currents entering and

leaving the busbar zone must be zero, unless there is a

fault therein.

The relay is connected to trip all the circuit breakers. In •

case of a bus fault the algebraic sum of not be zero and relay will operate.

currents will Fig. 11 Differential current protection of bus-zone

Department of Electrical and Electronics Engineering

Page 56: EE 8602 protection and switchgear

BUSZONE PROTECTION

2. High Impedance Relay Scheme

• A sensitive dc polarised relay is used in series with a tuning circuit which makes the relay responsive only to the fundamental component of the differential (spill) current of the CTs.

• The tuning circuit makes the relay insensitive to dc and harmonics, thereby making it more stable on heavy external faults.

Fig. 12 Differential protection using high impedance relay • To prevent excessive voltages on internal faults, a non-linear resistance (thyrite) and a high set overcurrent relay, connected in series with the non-linear resistance are employed.

The high set relay provides fast operation on heavy faults. Its

pick-up is kept high to prevent operation on external faults.

Department of Electrical and Electronics Engineering

Page 57: EE 8602 protection and switchgear

FRAME LEAKAGE PROTECTION • This is more favoured for indoor than

outdoor installations. • This is applicable to metal clad type

switchgear installations. •

• The frame work is insulated form the ground. The insulation is light, anything over 10 ohms is acceptable. This scheme is most effective in case of isolated-phase construction type switchgear

installations ground.

in which all faults involve

• To avoid the undesired operation of the Fig. 13 Frame leakage protection relay due to spurious currents, a check relay energised from a CT connected in the neutral of the system is employed.

Department of Electrical and Electronics Engineering

Page 58: EE 8602 protection and switchgear

NPR COLLEGE OF ENGINEERING AND TECHNOLOGY Natham, Dindigul-624401

UNIT -III

APPARATUS PROTECTION

(PART III)

Presented by,

M.Edwinlawrance, Assitant Professor

Department of Electrical and Electronics Engineering

Page 59: EE 8602 protection and switchgear

Syllabus

Current transformers and Potential transformers and their applications in protection schemes - Protection of transformer, generator, motor, bus bars and transmission line

Department of Electrical and Electronics Engineering

Page 60: EE 8602 protection and switchgear

Part 1. Generator Protection

― Protection of generators against stator faults

― Rotor faults and abnormal conditions

― Restricted earth fault and inter turn fault protection

Department of Electrical and Electronics Engineering

Page 61: EE 8602 protection and switchgear

Generator Protection A modern generating set is generally provided with the following protective schemes. (i) Stator protection

(a) Percentage differential protection (b) Protection against stator inter-turn faults (c) Stator-overheating protection

(ii) Rotor protection (a) Field ground-fault protection (b) Loss of excitation protection (c) Protection against rotor overheating because of unbalanced three-phase stator currents

(iii) Miscellaneous (a) Overvoltage protection (b) Overspeed protection (c) Protection against motoring (d) Protection against vibration (e) Bearing-overheating protection (f) Protection against auxiliary failure (g) Protection against voltage regulator failure

Department of Electrical and Electronics Engineering

Page 62: EE 8602 protection and switchgear

Stator Protection (A) Percentage Differential Protection • It is used for the protection of generators above 1

MW.

It protects against winding faults, i.e. phase to phase

and phase to ground faults.

This is also called biased differential protection or

longitudinal differential protection.

The polarity of the secondary voltage of CTs at a

particular moment for an external fault has been

shown in the figure.

In the operating coil, the current sent by the upper

CT is cancelled by the current sent by the lower CT

and the relay does not operate.

Fig. 1 Percentage differential protection for external fault condition (instantaneous current directions shown for external fault condition)

Department of Electrical and Electronics Engineering

Page 63: EE 8602 protection and switchgear

Stator Protection • For an internal fault, the polarity of the secondary

voltage of the upper CT is reversed, as shown in Fig. 2.

The operating coil carries the sum of the currents sent

by the upper CT and the lower CT and it operates and

trips the circuit breaker.

• The percentage differential protection does not respond to external faults and overloads. It provides complete protection against phase to phase

faults.

It provides protection against ground faults to about 80

to 85 per cent of the generator windings.

Fig. 2 Percentage differential protection of generator (instantaneous current directions shown for internal fault condition)

Department of Electrical and Electronics Engineering

Page 64: EE 8602 protection and switchgear

Stator Protection • It does not provide protection to 100 per cent of the winding because it is influenced by the

magnitude of the earth fault current which depends upon the method of neutral grounding.

Due to the difference in the magnetizing currents of the upper and the lower CTs, the current

through the operating coil will not be zero even under normal loading conditions or during

external fault conditions.

• In case of stator faults, the tripping of circuit breaker to isolate the faulty generator is not sufficient to prevent further damage as the fault until its field excitation is suppressed.

generator will still continue to supply power to the

Department of Electrical and Electronics Engineering

Page 65: EE 8602 protection and switchgear

Stator Protection Restricted earth-fault protection by differential system • When the neutral is solidly grounded, it is possible to

provide protection to complete winding of the generator

against ground faults.

However, the neutral is grounded through resistance to

limit ground fault currents.

With resistance grounding it is not possible to protect the

complete winding against ground faults.

The percentage of winding protected depends on the

value of the neutral grounding resistor setting. The usual practice is to protect 80 to 85% from neutral end is left unprotected.

and the relay Fig. 3 Percentage of unprotected winding against phase to ground fault

of the generator winding against ground fault. The remaining 15-20% •

• In Fig. 3 for phase to ground fault, it can be seen that the relay setting for the differential protection is determined by the value of the neutral grounding resistor and the percentage of winding to be protected.

Department of Electrical and Electronics Engineering

Page 66: EE 8602 protection and switchgear

Stator Protection In Fig. 3, let p% of the winding from the neutral remains unprotected. Then (100 – p)% of the winding is protected. The ground fault current If is given by

where, V is the line to neutral voltage and Rn is the neutral grounding resistance. For the operation of the relay, the fault current must be greater than the relay pick-up current.

Department of Electrical and Electronics Engineering

Page 67: EE 8602 protection and switchgear

Stator Protection Percentage differential protection for a Y-connected generator

with only four leads brought out

When the neutral connection is made within the generator and only the neutral terminal is brought

out, the percentage differential protection can be

provided, as shown in Fig. 4.

• This scheme protects the generator winding against ground faults.

It does not protect it against phase faults.

only

Generator-transformer unit protection

Fig. 4 Percentage differential protection for Y connected generator with only four leads brought out

Department of Electrical and Electronics Engineering

Page 68: EE 8602 protection and switchgear

Stator Protection

(B) Protection against Stator Interturn Faults

• Longitudinal percentage differential protection does not detect stator interturn faults.

• A transverse percentage differential protection, as the shown in Fig. 5 is employed for the protection

generator against stator interturn faults.

of

Fig. 5 Transverse percentage differential protection for multi- winding generators

Department of Electrical and Electronics Engineering

Page 69: EE 8602 protection and switchgear

Stator Protection

• A faster and more sensitive split-phase protection as shown in Fig. 6 can be employed.

• In this scheme, a single CT having double primary is used. No bias is necessary because a common CT is •

employed so do not occur.

that errors due to CT differences

Fig. 6 Split-phase protection of generator using double primary CTs

Department of Electrical and Electronics Engineering

Page 70: EE 8602 protection and switchgear

Stator Protection Interturn protection based on zero-sequence component

• If generators do not have windings, a method based

voltage measurement can

access to parallel on zero-sequence

be employed for

the protection against stator interturn faults. This type of scheme will also be applicable to

single winding generators having multi-turn

per phase per slot to protect against interturn

faults.

Figure 7 shows the schematic diagram of

interturn protection by zero-sequence

voltage measurement across the machine.

Fig. 7 Interturn protection of generator using zero-sequence voltage •

Department of Electrical and Electronics Engineering

Page 71: EE 8602 protection and switchgear

Stator Protection (C) Stator-overheating Protection

Modern generators employ two methods to detect overheating both being used in large generators

(above 2 MW).

First Method, the inlet and outlet temperatures of the cooling medium which may be hydrogen/

water are compared for detecting overheating.

Second Method, the temperature sensing elements are embedded in the stator slots to sense the

temperature.

Department of Electrical and Electronics Engineering

Page 72: EE 8602 protection and switchgear

Stator Protection • When the temperature exceeds a certain preset maximum

temperature limit, the relay sounds an alarm.

The scheme employs a temperature detector unit, relay

and Wheatstone-bridge for the purpose.

• The temperature sensing elements may either be thermistors, indicators.

thermocouples or resistance temperature

• They are embedded in the stator slots at different locations. These elements are connected to a multi-way selector

switch which checks each one in turn for a period long

enough to operate an alarm relay.

Fig. 8 Stator-overheating protection

Department of Electrical and Electronics Engineering

Page 73: EE 8602 protection and switchgear

Rotor Protection (A) Field Ground-fault Protection

As the field circuit is operated ungrounded, a single ground fault does not

affect the operation of the generator or cause any damage.

• A dc voltage is impressed between the field circuit and earth through a polarised moving iron relay.

It is not necessary to trip the machine when a single field earth fault occurs.

Usually an alarm is sounded. Then immediate steps are taken to transfer

the load from the faulty generator and to shut it down as quickly.

In case of brushless machines, the main field circuit is not accessible.

Fig. 9 Earth fault protection If there is a partial field failure due to short-circuiting of turns in the main field winding, it is detected by the increase in level of the field current.

• A severe fault or short-circuiting of the diode is detected by a relay monitoring the current in the exciter control circuit.

Department of Electrical and Electronics Engineering

Page 74: EE 8602 protection and switchgear

Rotor Protection (B) Loss of Excitation

When the excitation of a generator is lost, it speeds up slightly and

operates as an induction generator.

Round-rotor generators do not have damper windings and hence they

are not suitable for such an operation.

The rotor is overheated quickly due to heavy induced currents in the

rotor iron.

The rotors of salient pole generators are not overheated because they

have damper windings which carry induced currents.

• The stators of both salient and non-salient pole generators are overheated due to wattless current drawn by the machines as

Fig. 10 Loss of excitation relay characteristic magnetising current from the system. The stator overheating does not occur as quickly as rotor overheating. •

Department of Electrical and Electronics Engineering

Page 75: EE 8602 protection and switchgear

Rotor Protection (c) Protection against Rotor Overheating because of Unbalanced Three-phase Stator Currents

The overcurrent relay used in the negative phase sequence protection

has a long operating time

A typical time range of the relay is 0.2 to 2000 s.

It has a typical construction with a special electromagnet.

It has shaded pole construction with a Mu-metal shunt.

The negative sequence filter gives an output proportional to I2. It actuates an alarm as well as the time-current relay which has a very

inverse characteristic.

The alarm unit also starts a timer which is adjustable from 8% to 40% of

• Fig. 11 Protection against unbalanced stator currents

negative sequence component. The timer makes a delay in the alarm to prevent the alarm from

sounding unnecessarily on unbalanced loads of short duration.

Department of Electrical and Electronics Engineering

Page 76: EE 8602 protection and switchgear

Miscellaneous A. Overvoltage Protection- • Overvoltage may be caused by a defective voltage regulator

electrical load on generators.

Overvoltage relays are provided with hydro and gas-turbine

or it may occur due to sudden loss of

sets. Overvoltage relays are not commonly used with turbo-alternators.

B. •

Overspeed Protection- A turbo-generator is provided with a mechanical overspeed device.

The speed governor normally controls its speed.

It is designed to prevent any speed rise even with a 100 per cent load rejection.

An emergency centrifugal overspeed device is also incorporated to trip emergency steam

when the speed exceeds 110 percent.

valves

Department of Electrical and Electronics Engineering

Page 77: EE 8602 protection and switchgear

Miscellaneous C. •

Protection against Motoring- When the steam supply is cut off, the generator runs as a motor.

The steam turbine gets overheated because insufficient steam passes

away the heat generated by windage loss.

through the turbine to carry

Therefore, a protective relay is required for the protection of the steam turbine. Generally, the relay operates when power output falls below 3%.

A sensitive reverse power relay is available which has an operating setting of about 0.5%

generator ’s output.

of the

D. Protection against Vibration and Distortion of Rotor- • Vibration is caused by overheating of the rotor or some mechanical failure or abnormality.

Department of Electrical and Electronics Engineering

Page 78: EE 8602 protection and switchgear

Miscellaneous E. •

Bearing Overheating Protection- Temperature of the bearing is detected by inserting a temperature sensing device in a hole in the

bearing.

For large machines where lubricating oil is circulated through the bearing, an oil flow device is

used to detect the failure of oil cooling equipment.

F. •

Protection against Auxiliary Failure- The power plant auxiliaries are very important for the running of the generating sets.

High grade protective equipment is employed for their reliable operation.

For large generating sets, protection against loss of vacuum and loss of boiler pressure are

provided. Such failures are due to the failure of the associated auxiliaries.

Department of Electrical and Electronics Engineering

Page 79: EE 8602 protection and switchgear

Miscellaneous

G. Protection against Voltage Regulator Failure- •

Modern quick response automatic voltage regulators are very complex. They are subject to component failures.

Suitable protective devices are provided against their failure.

A definite time dc overcurrent relay is provided which operates when there is overcurrent in the

rotor circuit for a period longer than a prescribed limit.

In such a situation, the excitation is switched to a predetermined value for manual control. •

Department of Electrical and Electronics Engineering

Page 80: EE 8602 protection and switchgear

Miscellaneous H. Protection against Pole Slipping • In case of system disturbances after the operation of circuit breaker or when heavy load is thrown or

switched on, the generator rotor may oscillate.

Consequently, variations in current, voltage and power factor may take place.

Such oscillations may disappear in a few seconds.

Therefore, in such a situation, tripping is not desired. In some cases, angular displacement of the rotor exceeds the stability limit and the rotor slips a pole

pitch.

If the disturbance is over, the generator may regain synchronism.

If it does not, it should be tripped.

Department of Electrical and Electronics Engineering

Page 81: EE 8602 protection and switchgear

Miscellaneous I. •

Field Suppression When a fault occurs in the generator winding, the circuit breaker trips and the generator is

isolated from the system.

However, the generator still continues to feed the fault as long as the excitation is maintained, and

the damage increases.

Therefore, it is desirable to suppress the field as quickly as possible. Back-up Protection

Overcurrent relays are used as back-up protection.

As the synchronous impedance of a turbo-generator is more than 100%, the fault current,

may fall below the normal load current.

Therefore, standard time-overcurrent relays cannot be employed for back-up protection.

A voltage controlled overcurrent can be employed for such a purpose.

A better alternative is to use reactance or impedance type distance relays.

J.

Department of Electrical and Electronics Engineering

Page 82: EE 8602 protection and switchgear

Presented by

Edwinlawrance.M

AP/EEE,NPRCET

EE 8602 Protection and switchgear

Page 83: EE 8602 protection and switchgear

Unit 03 Apparatus protection

• Current transformers and Potential transformers and their applications in protection schemes - Protection of transformer, generator, motor, bus bars and transmission line.

Page 84: EE 8602 protection and switchgear

Contents

• Protection of motors

Page 85: EE 8602 protection and switchgear

AC Motor Protection

• HRC or rewirable fuse is normally used as protective device for motors. Rewirable fuse is used for motors ranging from FHP to 5 HP. •

HRC fuses are used for motors But HRC fuse cannot provide phasing and earth faults.

ranging above protection for

5 HP. overloading, single

• Thermal overloading relays are used for protection against overloading.

• For high capacity induction motors, a comprehensive motor protection is used.

Page 86: EE 8602 protection and switchgear

Fuse & HRC fuse

Page 87: EE 8602 protection and switchgear

Thermal overload relay

Page 88: EE 8602 protection and switchgear

Protection Scheme for Motors

Page 89: EE 8602 protection and switchgear

Short Circuit Protection

Attracted armature type relay is connected in each phase. Starting current.

current during DOL starting may be 4-5 times full load

Normally the fault current will be 7 times the full load current. Hence the relays are set to operate for currents of current.

5-7 times full load

Page 90: EE 8602 protection and switchgear

Earth Fault Protection

• Earth fault relays (IDMT type) with a setting the rated current is used.

• This is a single relay for all the 3 phases.

of 10% to 40% of

Earth Fault Protection

type overcurrent relays are connected • IDMT setting

in each phase with of 110% - 125% of rated current.

Page 91: EE 8602 protection and switchgear

Stalling Protection

• Due to some mechanical problem or overload, the motors may refuse to start. Motor will draw a heavy current for an indefinite period. This is really dangerous and undesirable.

Definite time relays with a current setting equal to the starting current at stall are used to protect the motors for this case.

Page 92: EE 8602 protection and switchgear

Single Phasing Protection • It is undesirable to run the motor when one of the phases is

disconnected. It is called single phasing and it needs to be identified so that the motor should be disconnected from supply. It is done by single phasing preventer circuits.

Page 93: EE 8602 protection and switchgear

Undervoltage Protection

• Operation of be

motor on undervoltage generally cause overcurrent

which can sensed by overload devices or temperature sensitive devices.

• But still a separate undervoltage relay is used to protect against a 3

phase voltage drop.

• A time delay is given for the relay operation to prevent tripping by transient voltage drop.

a

Page 94: EE 8602 protection and switchgear

Phase Reversal Relay • Phase reversal occurs when the supply connections

repairs. The motor will run in wrong direction.

In applications like elevators, cranes & hoists, the dangerous.

are changed after

• phase reversal is

• A phase reversal relay working based on the electromagnetic principle is used.

• For a correct phase sequence (RYB), the disc present in the relay produces a positive torque so that its contacts are closed. Hence motor runs. When phase reversal happens (RBY), the disc present in the relay produces an opposite torque so that its contacts are opened.

• Hence the magnetic coil of the started is de-energized or circuit breaker can be tripped.