1 EE 368 POWER SYSTEMS ANALYSIS (3 0 3) LOAD FLOW ANALYSIS: Formation of a.c. load flow equations. Gauss-Seidel iterative method of solution. Cartesian and polar forms of load flow equations, formation of the jacobian matrix and solution using the Newton-Raphson method. Digital computer study of load flow. FAULT ANALYSIS: Causes of faults, types of faults, 3-phase symmetrical fault calculations, unsymmetrical shunt and series fault calculations. Simultaneous faults. Applications to digital computation. OPERATION AND CONTROL: Characteristics of governors and their operation, speed changer settings, load-sensitive components of a power station, load-frequency characteristics, Exciter characteristics, block diagram representation of voltage control systems, voltage and reactive power control. STABILITY: Equal area criterion and solution of differential equations. Mr. E. A. Frimpong [email protected]0246665284 1. LOAD FLOW STUDIES
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
1
EE 368 POWER SYSTEMS ANALYSIS (3 0 3)
LOAD FLOW ANALYSIS: Formation of a.c. load flow equations. Gauss-Seidel iterative method
of solution. Cartesian and polar forms of load flow equations, formation of the jacobian matrix and
solution using the Newton-Raphson method. Digital computer study of load flow.
FAULT ANALYSIS: Causes of faults, types of faults, 3-phase symmetrical fault calculations,
unsymmetrical shunt and series fault calculations. Simultaneous faults. Applications to digital
computation.
OPERATION AND CONTROL: Characteristics of governors and their operation, speed changer
settings, load-sensitive components of a power station, load-frequency characteristics, Exciter
characteristics, block diagram representation of voltage control systems, voltage and reactive power
control.
STABILITY: Equal area criterion and solution of differential equations.
2. Deduce the sequence network connections for the following system under a resistive „a‟ phase
to earth fault.
A B
fZ
3. Two 11kVA, 20MVA three-phase, star-connected generators operate in parallel. The positive,
negative and zero sequence reactances of each being
18.0j ,
15.0.0j and 1.0j respectively.
The star point of one of the generators is isolated and that of the other is earthed through a 2
resistor. A single-line-earth fault occurs at the terminals of one of the generators. Estimate (i)
the fault current, (ii) current in earthing resistor and (iii) the voltage across earthing resistor.
53
3. Operation and Control
Aims
To know the importance of frequency and voltage control
To understand the control of power system frequency and voltage
To perform simple calculations on frequency
3.1 Introduction
The function of an electric power system is to convert energy from one of the naturally available
forms to the electrical form and to transport it to the points of consumption. Energy is seldom
consumed in the electrical form but is rather converted to other forms such as heat, light and
mechanical energy. The advantage of the electrical form of energy is that it can be transported and
controlled with relative ease and with a high degree of efficiency and reliability. A properly
designed and operated power system should therefore meet the following fundamental
requirements:
(a) The system must be able to meet the continually changing load demand for active and
reactive power. Unlike other types of energy, electricity cannot be conveniently stored in
sufficient quantities. Therefore, an adequate “spinning” reserve of active and reactive power
should be maintained and appropriately controlled at all times.
(b) The system should supply energy at minimum cost and with minimum ecological impact.
(c) The “quality” of power supply must meet certain minimum standards with regard to the
following factors:
i. constancy of frequency
ii. constancy of voltage; and
iii. level of reliability
Several levels of control involving a complex array of devices are used to meet the above
requirements.
In power systems, both active and reactive power demands are never steady. Continuous regulation
of the following is therefore required in the operation of the power system:
(a) Steam input to turbogenerators or water input to hydrogenerators to match the active power
demand. Failing this, the machine‟s speed will vary with consequent change in frequency.
The maximum permissible change in power frequency is Hz5.0 .
(b) Excitation of generators to match the reactive power demand with reactive generation.
Failing this, voltages at various system buses may go lower than or beyond the prescribed
limits.
In modern large interconnected systems, automatic generation and voltage regulation equipment are
installed on each generator. The controllers are set for a particular operating condition and they take
care of small changes in load demand without frequency and voltage exceeding the prescribed
limits. With the passage of time, as the change in load demand becomes large, the controllers must
be reset either manually or automatically.
Load frequency and excitation controls can be modelled and analysed independently for the
following reasons.
(a) Small changes in power depend on the change in the internal angle, , of the machine and is
independent of the machine bus voltage whereas the bus voltage depends on machine
excitation but is independent of machine internal angle.
(b) The load frequency controller is slow acting because of the large time constant contributed
by the turbine and generator moment of inertia, and excitation controller is fast acting
because the time constant of the field winding is relatively smaller.
54
3.2 Load-Frequency control
When a consumer connects a new load to a power system, it is initially supplied by the kinetic
energy stored in the rotating masses of the turbine-generators. As the kinetic energy is released, the
rotational speed of the generators falls and the system frequency throughout the interconnected
network begins to drop.
Because there are many generators supplying power into the system, some means must be provided
to allocate the change in demand to the generators. A speed governor on each generating unit
provides the primary speed control function, while supplementary control originating at a central
control centre allocates generation.
In an interconnected system with two or more independently controlled areas, in addition to the
control of frequency, the generation within each area has to be controlled so as to maintain
scheduled power interchange. The control of generation and frequency is commonly referred to as
load-frequency control (LFC).
Load frequency control is important for the following reasons:
(a) Load-frequency control is required so that the numerous power stations-small and large-
connected to the system will run satisfactorily in parallel.
(b) Considerable drop in frequency could result in high magnetizing currents in induction
motors and transformers.
(c) Constancy of speed of motors is important for satisfactory performance.
(d) Constancy of frequency is important for satisfactory performance of electric clocks and
other electric time keeping instruments.
3.2.1 Governor operation and characteristics
The control of frequency and load depends on the turbine speed governor. The traditional governor
control system uses the watt centrifugal governor as a speed sensing device and a hydraulic servo-
system to operate the main supply valve. Thus the control system has high dead band (or zone), i.e.
the speed must change by a certain amount before the main valve begins to open. Additionally,
such systems have a low speed response (0.2-0.3s). Large modern turbogenerators use electro-
hydraulic governing systems. This governing system has high speed response, low dead band, and
accuracy in speed and load control.
An imbalance in mechanical power into, and electrical power out of, the generator is seen as an
acceleration or deceleration of the shaft and hence as a change in rotor speed from its nominal
value. The turbine governor acts upon this variation in speed to regulate the steam or water flow
into the turbine such that when the rotor speed falls below its nominal value, more steam or water is
admitted to the turbine to increase mechanical power, and vice versa on an increase in rotor speed.
The control characteristics of governors are set so that a given change in speed results in a specific
change in turbine power, as described by equation 3.1
fR
1PP refm Eqn 3.1
where mP Change in mechanical power
refP Change to power reference setting, refP
f Change in speed expressed in Hz or per unit
R The „regulation constant‟ or „droop‟
55
With the reference speed constant, so that 0Pref , the change in mechanical power is directly
proportional to the change in speed i.e.
fR
1Pm Eqn 3.2
This characteristic is shown graphically in figure 3.1 for .u.p04.0R (i.e. 4% droop) with refP set
to give .u.p0.1Pm at .u.p0.1f i.e. full load at nominal frequency.
0.2 0.4 0.6 0.8 1.0 1.21.00
O.99
0.98
1.01
1.02
1.03
1.04
Power Output (p.u.)
Sp
eed/f
req
uen
cy (
p.u
.)
mP
f
Fig 3.1 Governor characteristic for pu.R 040
The reference value refP is set via equipment called the speed changer motor, or speeder gear, which
acts upon the governor valves to change the operating point (i.e. valve opening) about which the
governor effects the changes mP in response to frequency deviation f . The effect of changing the
speed gear setting (i.e. refP ) upon the governor characteristic is illustrated in figure 3.2. Effectively,
a family of characteristics is achieved, on any one of which the turbine may be set to operate, by
altering the setting of the speeder gear. In figure 3.2, 1P , 2P and 3P represent different outputs at
various speeder gear settings but for the same speed.
0.2 0.4 0.6 0.8 1.0 1.21.00
O.99
0.98
1.01
1.02
1.03
1.04
Power Output (p.u.)
Sp
eed
/fre
qu
ency
(p
.u.)
1P 2P 3PAlternative speeder
settings
Fig 3.2 Governor characteristic showing effect of speeder motor settings
56
The governor characteristics only completely decide the outputs of the machines when a sudden
change in load occurs or when machines are allowed to vary their outputs according to speed within
a prescribed range in order to keep the frequency constant. This latter mode of operation is known
as free-governor-error action.
The basic concepts of speed governing are best illustrated by considering an isolated generating
unit supplying a local load as shown in figure 3.3. When there is a load change, it is reflected
instantaneously as a change in the electrical torque eT output of the generator. This causes a
mismatch between the mechanical torque mT and the electrical torque eT which in turn results in
speed variations. The governor senses the speed variations and sends actuating signals to the valve
or gate to regulate the steam or water flow into the turbine.
Governor
Turbine G
Load PL
GeneratorValve/gate
Steam or water
Speed
Pe
Pm
Tm
Te
Fig 3.3 Generator supplying isolated load
Tm = mechanical torque Te = electrical torque PL = load power
Pm = mechanical power Pe = electrical power
Example 3.1
A MW500 generator supplies an isolated load of 450MW at a nominal frequency of 50Hz. The
governor operates with a 4% droop. If the load falls to 350MW, what is the new frequency?
Solution
On a base of 500MW, the load of 450MW is .u.p9.0500
450
On the same base, the load of 350MW is .u.p7.0500
350
.u.p2.09.07.0Pm
From Equation 3.2,
mPRf
Hz4.0
Hz50008.0
.u.p008.0
2.004.0
Hence, the new frequency Hzfffnew 4.504.050 Hz4.504.050
57
Example 3.2
Two generators operate in parallel to supply a common load of 750MW. The first has a full load
capacity of 600MW, a governor droop of 5% and is currently generating 450MW. The second has a
full load capacity of 500MW, a governor droop of 4% and is currently generating 300MW. The
initial frequency is 50Hz. What is the new frequency immediately following a load rise of 100MW
and what is the load distribution before supplementary control is applied?
Solution
On a common base of 1100MW
Ignoring losses in the transmission system and assuming that the system load is independent of
frequency, the total load change will be met by the changes in generation of the individual
machines, that is:
.u.p091.01100
100
MW100
PPP 2m1mL
With no change in refP for either machine,
21
2m1mLR
f
R
fPPP
21 R
1
R
1f
Hz204.0
Hz500041.0
.u.p0041.0
088.01
0917.01
091.0
R
1
R
1
Pf
21
L
Hence the new frequency is Hz796.49204.050 .
MW.
MW.
.u.p.
.
.
R
fPm
9548
110004450
04450
09170
00410
1
1
088.01100500
04.0R
0917.01100600
05.0R
2
1
58
MW.
MW.
.u.p.
.
.
R
fPm
2651
110004660
04660
0880
00410
2
2
Note: MW...PP mm 211002651954821 is not exactly 100MW due to approximations
made during calculation.
Example 3.3
Two synchronous generators operate in parallel and supply a total load of 200MW. The ratings of
the machines are 100MW and 200MW and both have governor droop characteristics of 4% from no
load to full load. Calculate the load taken by each machine, assuming free governor action.
Solution
Load supplied by machine A, MWx 10004.0
Load supplied by machine B is MWMWx 20004.0
200
From the above equations,
xx
xx
2002
200
200
10004.0
MWx 67.663
200
Hence load on machine B MW33.13367.66200
3.2.2 Generator-Load model
The increment in power input to a generator-load system is DG PP where tG PP is the
incremental turbine power output, assuming generator incremental loss to be negligible. DP is the
increment in load.
The increment in power input to the system is accounted for in two ways:
(a) Rate of increase of stored KE in the rotating mass of the generator. At scheduled frequency
f 0
, the stored energy is
rke PHW 0 kW-sec.
Where rP is the KVA rating of the generator and H is its inertia constant. Kinetic energy is
proportional to the square of speed (frequency). Therefore, the kinetic energy at frequency
fff 0is given by:
020
20200
2
0
00 2
1Pr)(
)(2)(
f
fH
f
ffffW
f
ffWW kekeke
The rate of change of kinetic energy is
fdt
d
f
HPW
dt
d rke
0
2
(b) As frequency changes, load that is frequency sensitive (motor load) changes. The rate of
change of load with respect to frequency can be regarded as constant for small changes in
frequency. Hence, change in load with frequency can be expressed as
59
fBff
PD
B is positive for a predominantly motor load. Writing a power balance equation, we have
fBfdt
d
f
HPPP r
DG 0
2
Dividing throughout by rP , we obtain
fpuBfdt
d
f
HpuPpuP DG )(
2)()(
0
Taking, the Laplace transform, we obtain
sf
HB
sPsPsF DG
0
2
)()()(
sT
KsPsP
Bs
Bf
H
sPsP
ps
ps
DG
DG
1)()(
1.
21
)()(
0
Where0
2
Bf
HTps i.e. power system time constant.
B
K ps
1 i.e. power system gain.
The figure below shows a complete block diagram of load frequency control of an isolated area.
ST
K
sg
sg
1 ST
K
t
t
1 ST
K
ps
ps
1
R
1
)()( sPsP Gt )(sPD
)(sPc
Speed changer
commandGenerator load
Speed governor system
Turbine
)(sF
Fig 3.4: Block diagram of load frequency control of an isolated area
60
Example 3.4
A 100MVA synchronous generator operates on full load at a frequency of 50Hz. The load is
suddenly reduced by 50MW. Due to time lag in governor system, the main supply valve begins to
close after 0.4s. Determine the change in frequency that occurs in this time. kVAkWH sec/5 of
generator capacity. Neglect change in load due to change in frequency, i.e. .0B
Solution
)(2
0puPf
dt
d
f
HD or
H
fpuPf
dt
d D
2
).( 0
5.0100
50)(
MVA
MWpuPD
5.252
505.0
fdt
d
Hzdtf 10)4.0(5.25.25.24.0
0
4.0
0 and
Hzfff 511500
3.2.3 Control area
It is possible to divide an extended power system into sub-areas in which the generators are tightly
coupled together so as to form a coherent group, i.e. all generators respond in unison to changes in
load or speed changer settings. Such a coherent area is called a control area. In a control area, the
frequency is assumed to be the same throughout, in static as well as dynamic conditions.
In practice, a control area may consist of a single large private company, a government-operated
system such as VRA, or several investor-owned companies bonded together in a power pool. A
control area has a single control centre which operates it.
For purposes of developing a control strategy, a control area can be reduced to a single speed
governor, turbo-generator and load system.
Example 3.5
Determine the drop in the frequency of an unregulated isolated control area because of sudden
increase in load demand. The control area has no inter-ties and no automatic regulation. The
dispatcher is absent. The kinetic energy of the rotating mass before the disturbances is 25,000MWs.
The load demand increases from 5000MW to 5200MW. Assume that ./3.83 HzMWB System
frequency = 60Hz.
Solution
fBfdt
d
f
HPP DG
0
2
ffdt
d
3.83
60
2500022000
024.01.0 ffdt
d
By using one of the methods of solving differential equations:
14.2 1.0 tef
61
The time constant, st 101.0
1 . Therefore in about 5 times the time constant, st 50 .
38.299.04.214.2 5 ef
Hence, the final value of the frequency
Hzfff 62.5738.2600
Self Assessment 3.1
Repeat example 3.5 if by inter-ties, kinetic energy available is MW000,2510 and load before the
disturbance is MW500010 . Note that B was estimated as 1% load reduction per 1% frequency
reduction HzMWHz
MW/33.83
%)1(60
%)1(5000
. Thus, with a load of MW500010 the new
HzMWB /3.833 . Comment on your answer.
Self Assessment 3.2
Obtain the transfer function (figure 3.4)DP
F
for 0)( sPC , 1tsg KK , 100psK , 3R ,
sTsg 4.0 , sTt 5.0 and sTps 20 . DP is in per unit. (a) Use the final value theorem to obtain the
final value of f when puPD 01.0 . (b) Determine the dynamic response of F to a step change
in load puPD 01.0 .
3.2.4 Proportional load frequency control
The use of a regulating factor, or gain, in the feedback branch, here known as R
1is called
proportional-feedback control. It does not completely restore the frequency to 50Hz, but does
reduce the deviation.
The steady state load-frequency characteristic of a speed governor system is obtained from the
transfer function in self assessment 3.2 for the free governor action. The droop of the characteristic
curves
RB 1
1
, i.e.
PKP
Bf D
R
1
1[see figure 3.1]. When
R
1represents the total
regulation factor for a system and B represents the system (control area) load change with
frequency, then R
B1
is known as the area frequency response characteristic(AFRC). AFRC of a
system is determined experimentally.
Example 3.6
Two power systems, A and B, are interconnected through a tie-line and are initially at 60Hz. If there
is a 100MW load change in system A, calculate the change in the steady-state values of frequency
and power transfer. The parameters of the system are as follows:
System A: Stiffness HzMWB /1500
Regulation MWHzR /1500
6
System B: Stiffness HzMWB /1000
62
Regulation MWHzR /1000
6
Solution
BBB PPf
7000
6
1000
1
61000
BBA PPf
100
500,10
6100
1500
1
61500
the changes in frequency in each system must be equal as they are electrically connected. Hence,
BB PP 100500,10
6
7000
6
BP
7000
6
500,10
6
500,10
600
BP
7000
500,101100
MWPB 40500,17
7000100
407000
6 Bf
Hz034.0
3.2.5 Proportional plus integral control
To restore a system completely to its normal frequency, the speed changer setting is adjusted
automatically by feeding a signal from f through an integrator to the speed changer. A block
diagram of integral controller has been shown in figure 3.5.
S
K1 )(sPc)(sF
Fig 3.5 Integral controller
3.3 Reactive power and voltage control
For efficient and reliable operation of power systems, the control of voltage and reactive power
should satisfy the following objectives:
(a) Voltages at the terminals of all equipment in the system are within acceptable limits. Both
utility equipment and consumer equipment are designed to operate certain voltage ratings.
Prolonged operation of an equipment at voltages outside the allowable range could
adversely affect their performance and possibly damage them.
(b) System stability is enhanced to maximize utilization of the transmission system. Voltage
and reactive power control have a significant impact on system stability.
(c) The reactive power flow is minimized so as to reduce RI2 and XI2 losses to a practical
minimum. This ensures that the transmission system operates efficiently, i.e., mainly for
active power transfer.
63
The problem of maintaining voltages within the required limits is complicated by the fact that the
power system supplies power to a vast number of loads and is fed from several generating units. As
loads vary, the reactive power requirements of the transmission system vary. Since reactive power
cannot be transmitted over long distances, voltage control has to be effected by using special
devices dispersed throughout the system. This is in contrast to the control of frequency which
depends on the overall system active power balance. The proper selection and coordination of
equipment for controlling reactive power and voltage are among the major challenges of power
system engineering.
3.3.1 Production and absorption of reactive power
(a) Synchronous generators can generate or absorb reactive power depending on the excitation.
When overexcited, they supply reactive power, and when underexcited, they absorb reactive
power. The capability to continuously supply or absorb reactive power is however limited
by the field current, armature current, and end-region heating limits. Synchronous
generators are normally equipped with automatic voltage regulators which continually
adjust the excitation so as to control the armature voltage.
(b) Overhead lines, depending on the load current, either absorb or supply reactive power. At
loads below the natural load (surge impedance), the lines produce net reactive power; at
loads above the natural load, the lines absorb reactive power.
(c) Underground cables, owing to their high capacitance, have high natural loads. They are
always loaded below their natural loads, and hence generate reactive power under all
operating conditions.
(d) Transformers always absorb reactive power regardless of their loading; at no load, the shunt
magnetizing reactance effects predominate; and at full load, the series leakage inductance
effects predominate.
(e) Loads normally absorb reactive power. A typical load bus supplied by a power system is
composed of a large number of devices. The composition changes depending on the day,
season, and weather conditions. The composite characteristics are normally such that a load
bus absorbs reactive power. Both reactive power and active power of the composite loads
vary as a function of voltage magnitudes. Loads at low-lagging power factors cause
excessive voltage drops in the transmission network uneconomical to supply. Industrial
consumers are normally charged for reactive as well as active power; this gives them an
incentive to improve the load power factor by using shunt capacitors.
(f) Compensating devices are usually added to supply or absorb reactive power and thereby
control the reactive power balance in a desired manner.
3.3.2 Methods of voltage control
The control of voltage levels is accomplished by controlling the production, absorption, and flow of
reactive power at all levels in the system. The generating units provide the basic means of voltage
control; the automatic voltage regulators control field excitation to maintain a scheduled voltage
level at the terminals of the generators. Additional means are usually required to control voltage
throughout the system. The devices used for this purpose may be classified as follows:
(a) Sources or sinks of reactive power, such as shunt capacitors, shunt reactors, synchronous
condensers, and static var compensators(SVCs)
(b) Line reactance compensators, such as series capacitors
(c) Regulating transformers, such as tap-changing transformers and boosters.
3.3.2.1 Shunt capacitors
Shunt capacitors supply reactive power and boost local voltages. They are used throughout the
system and are supplied in a wide range of sizes. The principal advantages of shunt capacitors are
their low cost and their flexibility of installation and operation. The principal disadvantage
64
associated with shunt capacitors is that their reactive power output is proportional to the square of
the voltage. Consequently, the reactive power output is reduced at low voltages when it is likely to
be needed most.
3.3.2.2 Shunt reactors
Shunt reactors are used to compensate for the effects of line capacitance particularly to lime voltage
rise on pen circuit or light load. During heavy loading conditions, some of the reactors may have to
be disconnected. They are usually required for EHV overhead lines longer than 200km.
3.3.2.3 Series capacitors
Series capacitors are connected in series with the line conductors to compensate for the inductive
reactance of the line. This reduces the transfer reactance between buses to which the line is
connected, increases maximum power that can be transmitted, and reduces the effective reactive
power ( XI2 ) loss. Although series capacitors are not usually installed for voltage control as such,
they do contribute to improved voltage control and reactive power balance. The reactive power
produced by a series capacitor increases with increasing power transfer; a series capacitor is self-
regulating in this regard.
3.3.2.4 Synchronous condensers
A synchronous condenser is a synchronous machine running without a prime mover or a
mechanical load. By controlling the field excitation, it can be made to either generate or absorb
reactive power. With a voltage regulator, it can automatically adjust the reactive power output to
maintain constant terminal voltage. It draws a small amount of active power from the power system
to supply losses.
3.3.2.5 Static var compensators
Static var compensators are shunt-connected static generators and/or absorbers whose outputs are
varied so as to control specific parameters of the electric power system. The term “static” is used to
indicate that SVCs, unlike synchronous compensators, have no moving or rotating main
components.
3.3.2.6 Tap-changing transformers
Transformers with tap-changing facilities constitute an important means of controlling voltage
throughout the system at all voltage levels. The taps on these transformers provide a convenient
means of controlling reactive power flow between subsystems. This in turn can be used to control
the voltage profiles, and minimize active and reactive power losses.
The table below summarizes the various voltage control devices and their control action.
Table 3.1 Control action of voltage control devices
Voltage control device Control action
1 Shunt capacitors Generate reactive power
2 Shunt reactors Absorb reactive power
3 Synchronous condensers Generate or absorb reactive power
4 Static var compensators Generate or absorb reactive power
5 Series capacitors Reduce reactive power consumption in lines
6 Tap-changing transformers Raise or lower voltage levels
65
3.4 Excitation systems
The basic function of an excitation system is to provide direct current to the synchronous machine
field winding. In addition, the excitation system performs control and protective functions essential
to the satisfactory performance of the power system by controlling the field voltage and thereby the
field current. Excitation systems have taken many forms over the years of their evolution. They
may be classified into the following three broad categories based on the excitation power source
used: DC excitation systems, AC excitation systems and Static excitation systems.
The control functions include the control of voltage and reactive power flow, and the enhancement
of system stability. The protective functions ensure that the capability limits of the synchronous
machine, excitation system, and other equipment are not exceeded.
3.4.1 Excitation system requirements
The performance requirements of excitation systems are determined by considerations of the
synchronous generator as well as the power system.
The basic requirement is that the excitation system supply and automatically adjust the field current
of the synchronous generator to maintain the terminal voltage as the output varies within the
continuous capability of the generator. In addition, the excitation system must be able to respond to
transient disturbances with field forcing consistent with the generator instantaneous and short-term
capabilities. The generator capabilities in this regard are limited by several factors: rotor insulation
failure due to high field voltage, rotor heating due to high field current, stator heating due to
excessive flux (volts/Hz). The thermal limits have time-dependent characteristics, and the short-
term overload capability of the generators may extend from 15 to 60 seconds. To ensure the best
utilization of the excitation system, it should be capable of meeting the system needs by taking full
advantage of the generator‟s short-term capabilities without exceeding their limits.
From the power system viewpoint, the excitation system should contribute to effective control of
voltage and enhancement of system stability. It should be capable of responding rapidly to a
disturbance so as to enhance transient stability, and of modulating the generator field so as to
enhance small-signal stability (explained in chapter 4).
To fulfil the above roles satisfactorily, the excitation system must meet the following requirements:
Meet specified response criteria.
Provide limiting and protective functions as required to prevent damage to itself, the
generator, and other equipment.
Meet specified requirements for operating flexibility.
Meet the desired reliability and availability, by incorporating the necessary level of
redundancy and internal fault detection and isolation capability.
66
3.4.2 Elements of an excitation system
Figure 3.6 shows the functional block diagram of a typical excitation control system for a large
synchronous generator. The following is a brief description of the various subsystems identified in
the figure.
Limiters and
protective circuits
Generator
Power system
stabilizer
Terminal voltage
transducer and
load compensators
Regulator ExciterRef. To power
system
5
4
3
21
Fig 3.6 Functional block diagram of a synchronous generator excitation control system
(1) Exciter. Provides dc power to the synchronous machine field winding, constituting the
power system stage of the excitation system.
(2) Regulator. Process and amplifies input control signals to a level and form appropriate for
control of the exciter. This includes both regulating and excitation system stabilizing
functions.
(3) Terminal voltage transducer and load compensator. Senses generator terminal voltage,
rectifiers and filters it to dc quantity, and compares it with a reference which represents the
desired terminal voltage. In addition, load (or line-drop or reactive) compensation may be
provided, if it is desired to hold constant voltage at some point electrically remote from the
generator terminal (for example, partway through the step-up transformer).
(4) Power system stabiliser. Provides an additional input signal to the regulator to damp power
system oscillations. Some commonly used input signals are rotor speed deviation,
accelerating power, and frequency deviations.
(5) Limiters and protective circuits. These include a wide array of control and protective
functions which ensure that the capability limits of the exciter and synchronous generator
are not exceeded. Some of the commonly used functions are the field-current limiter,
maximum excitation limiter, terminal voltage limiter, volts-per-Hertz regular and
protection, and underexcitation applied to the excitation system at various locations as a
summing input or a gated input.
67
Assignments
1. Two synchronous generators operate in parallel and supply a total load of 240MW. The ratings
of the machines are 150MW and 200MW and both have governor droop characteristics of 5%
from no load to full load. Calculate the load taken by each machine, assuming free governor
action.
2. A 200MW generator supplies an isolated load of 120MW at a nominal frequency of 50Hz. The
governor operates with a 5% droop. If the load drops by 25%, what is the new frequency?
3. Two generators operate in parallel to supply a common load of 850MW. The first has a full
load capacity of 600MW, a governor droop of 5% and is currently generating 500MW. The
second has a full load capacity of 500MW, a governor droop of 4% and is currently generating
350MW. The initial frequency is 50Hz. What is the new frequency immediately following a
load rise of 100MW and what is the load distribution before supplementary control is applied?
68
4. Stability
Aims
To gain understanding of the types of rotor angle stability
To know the conditions for transient and steady state stability
To perform simple calculations on transient and steady state stability.
4.1 Introduction
All power systems, small or large, have synchronous generators, motors and condensers. A power
system in steady state has frequency 0 and machine rotor angle 0 with respect to a synchronous
rotating axis. After having been subjected to a random disturbance, it is required that it remains in a
state of operating equilibrium. Power system stability may be broadly defined as that property of a
power system that enables it to remain in a state of operating equilibrium under normal operating
conditions and to regain an acceptable state of equilibrium after being subjected to a disturbance.
Instability in a power system may be manifested in many different ways depending on the system
configuration and operating mode. Traditionally, the stability problem has been one of maintaining
synchronous operation. Since power systems rely on synchronous machines for generation of
electrical power, a necessary condition for satisfactory operation is that all synchronous machines
remain in synchronism or, colloquially, “in step”. This aspect of stability is influenced by the
dynamics of generator rotor angles and power-angle relationships.
Instability may also be encountered without loss of synchronism. For example, a system consisting
of synchronous generator feeding an induction motor load through a transmission line can become
unstable because of the collapse of load voltage. Maintenance of synchronism is not an issue in this
instance; instead, the concern is stability and control of voltage.
Power system stability problems may therefore be classified into rotor angle stability and voltage
stability. Only rotor angle stability is studied in this course.
4.2 Rotor angle stability
Rotor angle stability is the ability of interconnected synchronous machines of a power system to
remain in synchronism. Rotor angle stability may be categorized into Steady state(small-
disturbance) stability and Transient stability
4.2.1 Steady state stability
Steady state (small-disturbance) stability is the ability of a power system to maintain synchronism
when subjected to small disturbances as occur continually in normal operation due to small
variations in consumption and generation. Instability that may result can be of two forms: (i) steady
increase in rotor angle due to the lack of sufficient synchronizing torque, or (ii) rotor oscillations of
increasing amplitude due to lack of sufficient damping torque.
In steady state stability problem, we are basically concerned with the determination of upper limits
of machine loadings under condition of gradual changes in load.
4.2.1.1 The swing equation
Assuming that windage (effect of damper windings) and frictional torque is negligible, the motion
of the rotor of a synchronous generator is described by the equation:
ei2
m
2
TTdt
dJ
Where J is rotor moment of inertia
69
iT is shaft torque developed by turbine.
eT is electromagnetic torque developed by synchronous machine.
m is angular displacement of rotor in mechanical radians.
We can derive from the above equation the following equivalent equation called the swing
equation.
ei2
2
0
PPdt
dH2
Where iP is shaft input power in per unit.
eP is electromagnetic power in per unit.
H is inertia constant defined as the stored kinetic energy at synchronous speed in MJ or
MW-sec per unit MVA of machine rating.
MVAMJ
P
JH
r
60 102
radiansinspeedssynchronourotorormechanical
MVAinmechaniceofratingPr
0
is the load angle, power angle, torque angle or internal angle.
4.2.1.2 Power transfer
Consider a single synchronous machine connected to an infinite bus through an external impedance
or reactance. Infinite bus is a system assumed to have large generating capacity so that change in
shaft power of the single machine operating to it does not affect its frequency and change in the
excitation of the single machine does not affect its voltage.
Eeee jXRZ
RI
oV 0
Infinite busSynchronous
machine Fig 4.1 A simple power system
The complex power injected into the infinite bus(or the complex power at its receiving end) if
0R e is given by:
*
RR I0VS
ee
*
ee
*
e
X
90V
X
)90(EV
X
90V
X
)90(EV
90X
VEV
and the active power injected is
e
RX
sinVEP
70
4.2.1.3 Steady state stability limit
The steady state stability limit of the simplest electrical system is defined as the greatest possible
power at its receiving end under a given condition of operation and excitation in the presence of
small disturbances.
We consider the stability limit of the system without excitation control i.e. the excitation is
constant. In this case, the synchronous machine is represented by a constant voltage behind its
synchronous reactance. For a salient machine, it is assumed that dq XX .
EdX eX
oV 0
The electromagnetic power is given as
sinXX
EVP
ed
e
Suppose a small disturbance causes the rotor angle to vary by , i.e. changes from
00 to , the subscript „0‟ denoting steady state condition. Then the change in the
electromagnetic power will be
c
PP
0
e
e
We suppose iP is constant because the governor is slow to act compared to the speed of energy
dynamics. Substituting the above equation into the swing equation we obtain
e0ei2
0
2
0
PPPdt
)(dH2
i0ee2
2
0
PPforPdt
dH2
0
2
2 H2MwhereC
dt
dM
0Cdt
dM
2
2
The characteristic equation is
0CMp2 and its roots areM
Cp
If 0C , the roots are pure imaginary and any small disturbance appearing in the system will result
in continuous oscillations. Line resistance and damper windings of machines ignored in the analysis
cause the system oscillations to decay. The system is therefore stable for a small disturbance so
long as 0P
0
e
.
If 0C both roots are real and one of them is positive. In this case, any small disturbance results
in a periodic rise of the torque angle, and synchronism is soon lost. Thus the system is unstable if
0P
0
e
.
71
At 0cosX
EVC,90 0
o
0 . The angle o
0 90 therefore determines the steady state stability
limit mP , i.e.X
EV90sin
X
EVP o
m .
Example 3.1
For the system where .u.p20.1E.,u.p60.0X.,u.p0.1V.,u.p20.1X ed ,
MVAMWH sec4 and the system frequency Hz50 , calculate the frequency of natural
oscillations if the generator is loaded to (a) 50% and (b) 80% of its maximum power limit.
Solution
(a) For 50% loading,o
0
m
0e
0 305.0P
Psin
radelectrical/pu577.030cos8.1
12.1cos
X
EVC o
0
radelectrical/.u.p0255.0502
42
f2
H2H2M
00
757.40255.0
577.0jj
M
Cp
Natural frequency of oscillations Hz757.02
757.4sec/rad757.4
(b) For 80% loading,o
0
m
0e
0 1.538.0P
Psin
radelectrical/pu4.01.53cos8.1
12.1C o
radelectrical/.u.p0255.0M as before
961.3j0255.0
4.0j
M
Cp
(c) Natural frequency of oscillations Hz637.02
961.3sec/rad961.3
Example 3.2
For the system shown in the figure below, chalculate the limit of steady state power with and
without reactor switch closed.
Mpu.X t 10 puX t 1.0
puX dg 1
1 2gE . pu puEm 0.1
1mgX pu
puX c 1
puX L 25.0
Solution
It can be shown that the system is equivalent to the simplest electrical system.
Case A: Reactor switch is open
Total reactance between generator and motor, dg t L t mgX X X X X X
72
.u.p.... 452110250101
.u.p49.045.2
12.1
X
EEP
mg
m
Case B: Reactor switch is closed. The equivalent circuit is as follows
puEg 2.1 puEm 0.1
puj1 puj 1.0 puj 25.0 puj 1.0 puj1
puj1
a b
c
M
This can be reduced to (by star-to-delta conversion)
puEg 2.1 puEm 0.1
X
M
This gives c
ba
baX
XXXXX
where 35.1j)25.01.01(jXa
1.1j)1.01(jXb
and 1jXc
Therefore
.u.p965.0j485.1j45.2j1j
1.1j35.1j1.1j35.1jX
Steady state power limit, .u.p..
.Pm 2441
9650
121
Self Assessment 3.1
Recalculate the power limit with the capacitive reactor replaced by an inductive reactor of the same
value.
In a generator with controlled field current, the emf, E remains constant for slow increases in the
load. This leads to a fall in the machine terminal voltage. In practice, the field current is controlled
so that the magnitude of the machine terminal voltage remains constant. Under this condition of
excitation, the maximum power is 50-80% higher (depending on the parameters of the generator
and transmission line) than in the case of a constant excitation.
We consider the steady state stability limit of the system where the excitation is controlled by a
regulator with a dead zone (i.e. with a delayed excitation control). Such a regulator acts only after
the voltage drop has exceeded a value called its dead zone. Both andE change under this
condition but since the change in excitation takes place after the change in load, the stability limit is
73
determined from the condition E Constant, i.e.,
0
e
e
PP and the limiting value of the
torque angle is o90 . Note that if the excitation is controlled with a fast-acting regulator then
EE
PPP
0
e
0
e
e
.
Example 3.3
For the system given below, determine the steady state power limit if the terminal voltage of the
generator is held constant at 1.2p.u. by an automatic voltage regulator which does not act fast
enough (i.e. it has sufficient dead zone).
pujX d 5.0
puj 0.1 oV 00.1
Infinite bus
Solution
E 001V
5.0jX d 0.1jX e
02.1 tV
Current injected into the infinite bus1j
0.12.1
jX
VVI
e
t
The machine internal voltage
1j
0.12.15.0j2.1IjXVE dt or
sin8.1j5.0cos8.15.08.1E
Steady state power limit is reached when o90 , i.e., the real part of E is zero, thus o87.7305.0cos8.1 and
o90729.1729.1j87.73sin8.1jsin8.1jE
Steady state power limit .u.p152.15.1
1728.1
XX
EVP
ed
m
4.2.2 Transient stability
Transient stability is the ability the power system to maintain synchronism when subjected to a
severe disturbance such as short-circuit, the tripping of a heavily loaded line, the tripping of a
loaded generator and sudden drop of a large load. A system which is transiently stable may recover
to its original frequency or settle down to a new frequency. Among the problems of transient
stability is the determination of critical clearing time of circuit breakers which isolate the faulty
portion from the system. Knowledge of the critical clearing time helps system planner to coordinate
the relay system so that a given fault is cleared in time. A fault cleared before the critical clearing
time will result in a stable system and a fault cleared after the critical clearing time will result in the
loss of synchronism.
74
The behaviour of the rotor angle in the presence of large disturbance can be determined by solving
the swing equation.
4.2.2.1 Definition of eP in the swing equation
A generator is represented by a constant voltage 'E behind its transient reactance 'Xd . The power
eP in this case for the simplest system is given by
sinX'X
V'EP
ed
e
EdX
eXoV 0
Note that the internal angle of E is not the same as that of E. Thus the angle in the above
equation is an approximation of the torque or load angle.
4.2.2.2 The swing equation
Solution depends on the type of disturbance and also its location in the power system. The practical
approach to the transient stability problem is to simulate a disturbance in the system, obtain a
numerical solution of the swing equation (or equations for a multi-machine case) and then plot
delta against time curve called the swing curve. If delta starts to decrease after reaching a maximum
value, it is normally assumed that the system is stable and the oscillations of delta around the
equilibrium will decay and finally die out. If it is unstable, delta continues to increase.
In the simplest electrical system, large disturbance are generally reflected as the changes in the
transfer reactance. In the study of transient stability, the mechanical input power of the synchronous
generator is assumed to be constant.
4.2.2.3 Equal area criterion
In a system where one machine is swinging with respect to an infinite bus, we can study transient
stability without finding the function )t(f . The general stability criterion is that the system is
stable if at some time t, 0dt
d
and is unstable if 0
dt
d
for a sufficiently long time (more than 1sec
will generally do)
0dt
d
stable
time
0
max
0
Fig 4.2 A stable system
75
This stability criterion can be converted into a simple and easily applicable form for the simplest
electrical system. The swing equation can be restated as:
eiaa
0
2
2
PPPwherePH2dt
d
Multiplying both sides of the swing equation by
dt
d2 , we get
dt
dP
Hdt
d
dt
d2 a
0
2
2
2
0a
d d dP
dt dt H dt
2
0a
dd P d
dt H
Integrating, we obtain
0
2
0a
dd P d
dt H
0
dPHdt
da
0
2
2
1
0
dPHdt
da
0
where 0 is the initial rotor angle before it begins to swing due to disturbance.
From the stability condition, 0dt
d, the condition for stability can be written as:
000
2
1
0
0
dPdP
Hdt
daa . From the figure below,
a
b
c
d e
iP
eIIP
2A
1A
eIP
P
0 c 2
Fig 4.3 Equal area criterion
0000
dPPdP ia This leads to:
76
2121 000
AAAAdPPdPPc
c
eIieIIi
The condition of stability can therefore be stated as: the system is stable if the area under aP
curve reduces to zero at some value of . In other words, a power system will be stable in terms of
transient stability IF AND ONLY IF the accelerating area equals the decelerating area. Hence, the
name equal area criterion of stability.
Consider the figure below.
a
bc
d e
,faultduring
,postfaultandprefault
P
0 c 2
f
PPm
AD
t
. .
.g
eIIP
eIP
Fig 4.4 Pre-fault, during fault and post fault P and the movement of system operating
point when the system is stable
We assume that the fault is cleared with the faulty transmission line back in service. Hence the pre-
fault P also represents the post-fault P curve. Transient stability of the power system can
be analysed by discussing the movement of the system operating point on the P curve, as
follows:
Point a is the initial operating point of the power system where PPm when the generator rotates
at a synchronous speed 0 and the rotor angle is 0 . At the moment when the fault occurs, the
operating point drops from a to b, where eIIm PP . Therefore, the generator starts to accelerate and
the operating point moves along the during-fault P curve. At ctt , the fault is cleared at
operating point c with c . The operating point on the post-fault P curve jumps to point d.
due to the acceleration from point b to c, at this moment, the generator rotates faster than the
reference axis at speed c .
77
At point d, eIm PP . The generator starts to decelerate from speed c . However, because 0 c ,
the rotor angle continues to increase. As a result, the operating point moves along the post-fault
P curve towards point g until it arrives at point e. at point e, the rotor has decelerated to the
synchronous speed 0 from 0 c . However, at point e, eIm PP and the generator continues to
decelerate from the synchronous speed. This results in a decrease in rotor angle and the operating
point moves back along the P curve towards the initial operating point a until it arrives at point
f. finally, the operating point comes back to its initial operating point a. The system is stable in
terms of transient stability.
a
bc
d
e
,faultduring
,postfaultandprefault
P
0 c 2
f
PPm
AD
t
. .eIIP
eIP
.h
bP .
AP
g
Fig 4.5 The case in which the system is unstable in terms of transient stability
The analysis of the unstable condition is similar to that of the stable condition. At point d, (in figure
4.5) the generator starts to decelerate from speed( c corresponding to c ). If c is so great that
generator takes a longer time to reduce its speed back to the synchronous speed, then the operating
point travels along the post-fault P curve and does not stop until it passes point h, as shown in
figure 4.5. At any point under point h – for example, at point e, eIIm PP - the generator starts to
accelerate again from a speed greater than the synchronous speed. Hence, the rotor angle continues to increase and the operating point moves towards point f and g in figure 4.5. The system
loses stability.
From the above analysis, if the system is unstable in terms of transient stability, then it loses
stability in the first swing of rotor angle. Hence, power system transient stability is also called first-
swing stability.
78
The following factors influence system transient stability:
(a) How heavily the generator is loaded
(b) The generator output during the fault. This depends on the fault location and type.
(c) The fault clearance time. The more slowly the fault is cleared, the closer point d is to point h
and the higher the chance that the system will lose transient stability, because the distance for
the operating point to decelerate from point d to h is shorter.
(d) The post-fault transmission reactance.
(e) The generator reactance. A lower reactance increases peak power and reduces initial rotor
angle.
(f) The generator inertia. The higher the inertia, the slower the rate of change in angle. This
reduces the kinetic energy gained during fault; i.e. area accelerating area is reduced.
(g) The generator internal voltage magnitude. This depends on the field excitation.
(h) The infinite bus voltage magnitude.
4.2.2.4 Application of equal area criterion
CASE 1: Sudden loss of one of two parallel lines.
EdX
oV 0
X
XS
Before switch off sinsin mI
ed
eI PXX
VEP
where
2
XX e
Immediately after switching off line,
sinsin mII
d
eII PXX
VEP
mI
i
mIiP
PPP 1
00 sinsin
The P curves are shown below.
79
iP 2A
1A
eIPeP
0 21
eIIP
m
Accelerating area 1
01
dPPA eIIi
Decelerating area 2
12
dPPA ieII
For the system to be stable, it should be possible to find angle 2 such that 21 AA . A limiting
condition is reached when 1
0
2 180 m where
IIm
i
P
P1
1 sin
CASE 2: A 3-phase short-circuit fault occurs at one end of a line, say at point S.
(a) Before occurrence of fault
sinsin mI
ed
eI PXX
EVP
where2
XX e
(b) Upon occurrence of fault: 0eIIP
(c) Circuit breakers at the two ends of the faulted line open at a time 1t (corresponding to angle
1 ), called the clearing time to isolate the faulted line.
iP
eIIP
2A
1A
eIP
0 1 2 m
IIIeP
eP
Fig 4.6 P curves for normal operation and during a 3-phase short-circuit fault at one
end of a line.
dPdPPA ieIIi
1
0
1
01
80
2
1
2
dPPA ieIII sinsin mIII
d
eIII PXX
EVP
Area 1A depends upon the clearing time 1t . This must be less than a certain value called critical
clearing time ct , for the system to be stable. The angle 1 corresponding to ct denoted c is called the
critical clearing angle. It is determined as follows:
m
c
cc
mIII
i
mieIIIieIIiP
PdPPdPdPP
1sin,
00
m
c
c
dPPdP ieIIIi
0
0
m
c
c
dPPdP eIIIii
0
0
m
c
m
c
c
eIIIii PdPdP
0
0
cmmIII
mcmIII
mIII
mIII
mIIIeIII
P
P
P
dP
dPdP
c
m
c
m
c
m
c
m
coscos
coscos
sin
sin
]cos[
00
c
m
m
cmmIIIcmieIIIi coscosPPdPdP
mIII
mmIIIomic
P
cosPPcos
Im
i
P
P1
0 sin and
mIII
i
mP
P1sin
CASE 3: 3-phase short-circuit occurs in the middle of a line.
EdX
oV 0X
2
X
2
X
This is equivalent to the circuit below (using a star-to-delta conversion)
EXXX dII
3
oV 0
2
X
The circuit model of the system during fault is:
(a) Before occurrence of fault: As in case 2
(b) Upon occurrence of fault sinsin mI
II
eII PX
VEP
57
(c) Post-fault eIIIP as in case 2.
iP
eIIP
2A
1A
eIPeP
0 21
eIIIP
m
Fig 4.7 P curves for normal operation, during a 3-phase short-circuit fault at the
middle of a line and after fault clearing
1
01
dPPA eIIi
2
12
dPPA ieIII , for critical clearing angle, we have
m
c
c
dPPdPP ieIIIeIIi
0
00
m
c
c
dPPdPP eIIIieIIi
000 cmIIImmIIImIIcmIImi cosPcosPcosPcosPP
mIImIII
mmIIImIImi
cPP
PPP
coscoscos 00
Where
Im
i
P
P1
0 sin and
mIII
i
mP
P1sin
CASE 4: The circuit breakers of line 2 are reclosed successfully because the fault was
transient and so vanished.
iP
eIIP
aA2
1A
eIVeI PP
eP
0 21
eIIIP
mrc
bA2
58
Fig 4.8 P curves for normal operation, during a 3-phase short-circuit fault at the
middle of a line and after a successful reclosure
We have sinmIeIeIV PPP
mI
i
mP
P1sin
1
0 1
rc m
rci mII mIII i mI iP P sin d P sin P d P sin P d
Example 3.4
A Hz50 generator is delivering 50% of the power that it is capable of delivering
through a transmission line to an infinite bus. A fault occurs that increases the
reactance between the generator and the infinite bus to 500% of the value before the
fault. When the fault is isolated, the maximum power that can be delivered is 75% of
the original maximum value. Determine the critical clearing angel for the condition
described.
Solution
Curves are as shown in figure 4.7
mIImIII
mmIIImIImi
cPP
PPP
coscoscos 00
Dividing the top and bottom by mIP , we obtain
23
30201 coscoscos
rr
rrr mm
c
wheremI
i
P
Pr 1 ,
mI
mII
P
Pr 2 and
mI
mIII
P
Pr 3
X
EVPmI ,
X
EVPmII
5 , mImIII PP 75.0
From the data 75.0,2.05
1,5.0 321 rrr
Also o
IIm
i
P
P305.0sinsin 11
0
o
mIII
mI
mI
i
IIIm
i
P
P
P
P
P
P8.41
75.0
5.0sin1sinsin 11
1
oooo
m 2.1388.41180180 1
Therefore,
o
c
c
34.67
3853.0
2.075.0
2.138cos75.030cos2.0180
302.1385.0
cos
4.2.2.5 Methods of improving system transient stability
The following methods are often employed in practice
(a) Increasing system voltage during disturbance using modern high-speed
excitation systems.
(b) Reducing transfer reactance by reducing conductor spacing, by using series
capacitors(for lines 350km) and increasing the number of parallel lines
between transmission points.
(c) Using high-speed circuit breakers and reclosing breakers.
(d) Fast valving: This measure reduces the mechanical input to the generator after
the occurrence of a fault through fast action from the side of the prime mover.
The result is that the accelerating area is reduced and the decelerating area is
increased.
4.3 Dynamic stability
Dynamic stability has also been widely used as a class of rotor angle stability.
However, it has been used to denote different aspects of the phenomenon in different
literatures. In North American literature, it has been used mostly to denoted small-
signal stability in the presence of automatic control devices(primarily generator
voltage regulators) as distinct from the classical steady-state stability without
automatic controls. In the French and German literature, it has been used to denote
what is termed transient stability. Since much confusion has resulted from use of the
term dynamic stability, both CIGRE and IEEE have recommended that it is not used.
Assignments
1. A synchronous generator represented by a voltage of ..15.1 up in series with a
transient reactance is connected to a large power system with a voltage of ..0.1 up
through a power network. The equivalent transient transfer reactance X between
voltage sources in ..50.0 upj . After the occurrence of a three-phase-to-earth fault
on one of the lines of the power network, two of the line circuit breakers A and B
operate sequentially as follows with corresponding transient transfer reactance
given therein.
(a) Short-circuit occurs at o300 , A operates instantaneously to make
.u.p.X 03
(b) Ato601 , A recloses, ..0.6 upX
(c) Ato752 , A reopens
(d) At o903 , B also opens to clear the fault making ..60.0 upX
Check if the system will operate stably.
2. Calculate the limit of steady state power for the system below
Mpu.X t 10 puX t 1.0
puX dg 1
1 2gE . pu puEm 0.1
1mgX pu
puX c 1
puX L 25.0
puX c 1
3. For the system given below, determine the steady state power limit if the terminal
voltage of the generator is held constant at 1.1p.u. by an automatic voltage
regulator which does not act fast enough(i.e. it has sufficient dead zone).
pujX d 4.0
pujX e 0.1 oV 00.1
Infinite bus
4. A Hz50 generator is delivering 40% of the power that it is capable of delivering
through a double-circuit transmission line to an infinite bus. A three-phase short-
circuit occurs at the generator terminal end of one feeder. Circuit breakers at the
ends of the faulted line trip, and the maximum power that can be transferred is
65% of the original maximum value.
(i) Determine the critical clearing angel for the condition described.
(ii) Find the accelerating and decelerating areas at this angle.