NYC Department of Education Building Condition Assessment Survey 2019-2020 M506 Architectural Inspection Inspection Type Last Edited Time In InspectionId EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 STREET, MANHATTAN, NY, 10025 School: 253 2019-10-04 07:24AM 2020-08-24 10:00AM ARCHITECTURAL - SENIOR 276 2019-10-04 08:02AM 2019-10-07 08:08AM ARCHITECTURAL - ASSOCIATE Asset Data Question Answer Was the Building Fully Accessible for Inspection? No Science lab room 202, (no key) Comments on Inaccessible Inspection Shower Rooms Principal(s) Information Principal Name Lilit Suffet Principal Organization Edward A. Rey Meeting with Principal? Yes Principal Feedback The Principal has following comments 1. Plaza deck, Exterior Stair and Ramp is deteriorated and needs to be repaired. 2. There are Roof leaks and the Roofing needs to be repaired. 3. Air conditioner/ heater is not working properly and needs to be updated. Custodian Alejo Harmandez Fireman Ali Tarat Building Square Footage 85,000 Comments on the Area (Square Feet) None Comments on the Stories (Floors) plus Basements 3+B Comments on the Year Built 1999 Comments on the Student Population 342 Comments on the Staff Population 88 Comments on the Number of Classrooms 30 Weather Fair Facade Photo Corner of West 102nd Street and Amsterdam Avenue - West view Page 1 of 33 Print Date: 9/11/2020 Mobile Validity Version 2.0 (P)
33

EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

Feb 28, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Inspection Type Last EditedTime InInspectionId

EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 STREET, MANHATTAN, NY, 10025School:

253 2019-10-04 07:24AM 2020-08-24 10:00AMARCHITECTURAL - SENIOR

276 2019-10-04 08:02AM 2019-10-07 08:08AMARCHITECTURAL - ASSOCIATE

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? No

Science lab room 202, (no key)Comments on Inaccessible Inspection

Shower Rooms

Principal(s) Information

Principal Name Lilit Suffet

Principal Organization Edward A. Rey

Meeting with Principal? Yes

Principal Feedback The Principal has following comments

1. Plaza deck, Exterior Stair and Ramp is deteriorated and needs

to be repaired.

2. There are Roof leaks and the Roofing needs to be repaired.

3. Air conditioner/ heater is not working properly and needs to be

updated.

Custodian Alejo Harmandez

Fireman Ali Tarat

Building Square Footage 85,000

Comments on the Area (Square Feet) None

Comments on the Stories (Floors) plus Basements 3+B

Comments on the Year Built 1999

Comments on the Student Population 342

Comments on the Staff Population 88

Comments on the Number of Classrooms 30

Weather Fair

Facade Photo

Corner of West 102nd Street and Amsterdam Avenue - West view

Page 1 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 2: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural InspectionMain Entrance Photo

Facade A - West 102nd Street

Roof Photo

Roof 1 - East view

Have any Systems/Major Building Components been upgraded? Systems: Library Flooring refinished

Years: 2007

Systems: Gymnasium Flooring refinished

Years: 2008

Systems: Exterior Soffit, Parapet repairs

Years: 2013

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Leased Space? No

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Page 2 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 3: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Accessibility

Accessibility Status Question Response

Is the Primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are All floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,

Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Complies Required DeficiencyAudio

Induction

System

Fire

Alarm

Strobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

YesExterior Entrances & Exits

NoNoExterior H/C Lifts

YesYesExterior Ramps and Railings

Interior Routes

NoNoCorridor and Lobby H/C Lifts

YesYesInterior Corridor Doors And

Hardware

YesInterior Corridors & Lobbies

YesYesInterior Elevators

YesInterior Lobby Doors And Hardware

NoInterior Ramps

Rooms & Spaces

Art Rooms

Yes YesRoom 222

NoAuditorium

Cafeteria

Yes YesBasement Yes Yes

Classrooms

Yes Yes2nd and 3rd Floor

Computer Rooms

Yes YesRooms 203, 227 and 327

Gymnasium

Yes YesBasement No Yes

Library

Yes YesRoom 100

Main Office

Yes YesRoom 130

NoMulti-purpose Room

Nurse's Office

Yes YesRoom B8

NoPool

Science Lab

Yes YesRooms 202, 210

Toilet Rooms (boys)

Yes YesBasement, 1st - 3rd

Floors

Toilet Rooms (girls)

Page 3 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 4: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Physical Breakdown Structure Exists Complies Required DeficiencyAudio

Induction

System

Fire

Alarm

Strobe

Yes YesBasement, 1st - 3rd

Floors

Toilet Rooms (staff)

Yes YesBasement, 1st - 3rd

Floors

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

Does not existAREAWAY

Does not existAWNINGS AND CANOPIES

Does not existCHIMNEY

InspectedCOPING

Condition 3- Fair

CAST STONE:DISINTEGRATING / FREEZE THAWDeficiency

Deficiency Location/Instance

40Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE-IN-KIND

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Page 4 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 5: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

COPING

Deficiency Photo 1

Facade A

Violations No violations recorded

CAST STONE:OPEN TRANSVERSE JOINTS WITH

DAMAGED CAULKING

Deficiency

Deficiency Location/Instance

80Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade D

Violations No violations recorded

Does not existCORNICE

InspectedDOORS

InspectedDOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 3- Fair

METAL CLAD:DETERIORATED DOOR AND FRAME -

MINOR DETERIORATION

Deficiency

Deficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

Page 5 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 6: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

LEVEL 2Purpose of Action

Deficiency Photo 1

Office door

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTRANSOM/SIDE LIGHT

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR SOFFITS

Condition 2- Between Good and Fair

STUCCO/PLASTER:MINOR CRACKS/SPALLINGDeficiency

Roof Plan Reference

Elevation

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

InspectedEXTERIOR WALLS

MasonryMaterial Type(s)

25,000Replacement Quantity

Replacement Uom S.F.

Page 6 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 7: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Instance on All Facades Inspected

3- FairInstance Condition

Instance Quantity 25,000

Instance Quantity Uom S.F.

BRICK:MAJOR / THRU CRACKSDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facade A

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Main entrance

Violations No violations recorded

BRICK:DETERIORATED MASONRY SILLSDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facades A, B, D

15Deficiency Quantity

Quantity Uom L.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

Page 7 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 8: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade B

Violations No violations recorded

BRICK:DETERIORATED CONTROL/EXPANSION JOINTS

WITH DAMAGED CAULKING

Deficiency

Roof Plan Reference

Elevation

Elevation Reference All Facades

25Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade B

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Roof Plan Reference

Page 8 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 9: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Elevation Reference All Facades

800Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

Does not existLOADING DOCK

InspectedLOUVER

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedPARAPETS

MasonryMaterial Type(s)

8,000Replacement Quantity

Replacement Uom C.F.

Instance on All Facades Inspected

2- Between Good and FairInstance Condition

Instance Quantity 8,000

Instance Quantity Uom CF

No deficiencies recordedDeficiency

InspectedPLAZA DECK

Instance on Concrete:Roof 3 Inspected

3- FairInstance Condition

Instance Quantity 4,000

Instance Quantity Uom S.F.

Installation Year 1999

Source of Installation Year Custodial Staff

CONCRETE:OPEN JOINTSDeficiency

Deficiency Location/Instance

100Deficiency Quantity

Quantity Uom L.F.

Potential Action REPOINT

Page 9 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 10: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

PLAZA DECK

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Plaza Deck

Violations No violations recorded

CONCRETE:MAJOR CRACKSDeficiency

Deficiency Location/Instance

70Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Plaza Deck

Violations No violations recorded

InspectedROOF

InspectedROOFING

Replacement Quantity 26,000

Replacement Uom S.F.

InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOF BARRIER

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existROOF CAGE

Does not existROOF FENCE

InspectedROOF HATCH/SMOKE HATCH

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOFING

Instance on Single Ply, Fully Adhered Roof:Roof 1 and 2 Inspected

4- Between Fair and PoorInstance Condition

Page 10 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 11: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

Instance Quantity 26,000

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

Yes

Installation Year 1999

Source of Installation Year Custodial Staff

SINGLE PLY, FULLY ADHERED ROOF:ROOFING:MAJOR

ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE

Deficiency

Deficiency Location/Instance

300Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT

REMOVAL

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 310 shown, similar condition at rooms 226, 300, 302, 303,

312, 314, 317, 318, 322, 326, 327, 328, Stair A/3, Stair C/3,

Corridor near Rooms 305, 311, 313, Gymnasium

Violations No violations recorded

SINGLE PLY, FULLY ADHERED ROOF:ROOFING:MAJOR

ACTIVE ROOF LEAKS IN ELECTRICAL PANEL ROOM

Deficiency

Deficiency Location/Instance

60Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT

REMOVAL

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Page 11 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 12: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

Deficiency Photo 1

Room 310 shown, similar condition at rooms 318, Stair C/3

Violations No violations recorded

InspectedROOFING DRAINS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedSPECIALTIES

InspectedBULKHEAD/PENTHOUSE

2- Between Good and FairCondition

BULKHEAD/PENTHOUSE WALLS/EXTERIOR:OPEN

JOINTS

Deficiency

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

BH

Violations No violations recorded

Does not existCUPOLA/ SPIRES/ TOWERS

Does not existDORMER

InspectedDUNNAGE STEEL

3- FairCondition

HEIGHT LESS THAN 18"Deficiency

Deficiency Location/Instance

Page 12 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 13: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

ROOF

SPECIALTIES

DUNNAGE STEEL

20Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 1Urgency of Action

LEVEL 1Purpose of Action

Deficiency Photo 1

Roof 1

Violations No violations recorded

MINOR RUSTINGDeficiency

Deficiency Location/Instance

40Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 2

Violations No violations recorded

Does not existROOF/GRAVITY TANK

Does not existSKYLIGHT/ROOF VENT

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedBUILDING CHEEK/FLANK WALLS

Condition 4- Between Fair and Poor

MASONRY UNIT:CRACKS/SPALLING - MAJORDeficiency

Deficiency Location/Instance

50Deficiency Quantity

Page 13 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 14: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A - Main entrance

Violations No violations recorded

MASONRY UNIT:OPEN JOINTSDeficiency

Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 4Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

Facade A - Main entrance

Violations 35402274R

InspectedRAILINGS

Condition 3- Fair

RUST - MINORDeficiency

Deficiency Location/Instance

12Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 14 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 15: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS

Deficiency Photo 1

Facade A

Violations No violations recorded

InspectedSTAIRS/RAMPS

Condition 4- Between Fair and Poor

STONE:WORN-OUT TREAD/RISER/NOSINGDeficiency

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

Facade A

Violations 35207298H

CONCRETE:CRACKS/SPALLING - MINORDeficiency

Deficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 15 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 16: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo 1

Ramp

Violations No violations recorded

STONE:CRACKS, SPALLINGDeficiency

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

Facade A

Violations 35207298H

InspectedWINDOWS

8,000Replacement Quantity

Replacement Uom S.F.

InspectedEXTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLINTELS

Condition 3- Fair

STONE:CHIPPED/SPALLED/BROKEN PIECESDeficiency

Roof Plan Reference

Page 16 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 17: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

WINDOWS

LINTELS

Elevation

125Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade C (roof 1 )

Violations No violations recorded

InspectedWINDOWS

Material Type(s) Aluminum

Instance on Aluminum - Double Hung:All Facades Inspected

3- FairInstance Condition

Instance Quantity 8,000

Instance Quantity Uom S.F.

Installation Year 1999

Source of Installation Year Custodial Staff

ALUMINUM - DOUBLE HUNG:INOPERABLE BALANCEDeficiency

Roof Plan Reference

Elevation

Elevation Reference All Facades

90Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE BALANCES

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

ALUMINUM - DOUBLE HUNG:HARDWARE POOR

CONDITION/MISSING

Deficiency

Page 17 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 18: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

EXTERIOR

WINDOWS

WINDOWS

Roof Plan Reference

Elevation

Elevation Reference All Facades

100Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

INTERIOR Inspected

Does not existAUDITORIUM

CAFETERIA

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on Basement Does not exist

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Center of RoomDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Page 18 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 19: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

CAFETERIA

Floor Finish

Center of Room

Violations No violations recorded

Sliding-folding Partition

Instance on Basement Does not exist

Stage

Instance on Basement Does not exist

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on Basement Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

ACOUSTIC TILES:DAMAGED/MISSINGDeficiency

Room 226Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 226

Violations No violations recorded

GYPSUM BOARD:DAMAGED/DETERIORATED - ACTIVE

LEAK

Deficiency

Room 312Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 312

Violations No violations recorded

TECTUM:DAMAGED/MISSING - ACTIVE LEAKDeficiency

Room 310, 312, 327. Corridor near Room 310Deficiency Location/Instance

Page 19 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 20: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 310

Deficiency Photo 2

Room 327

Violations No violations recorded

InspectedDoor(s)

Condition 2- Between Good and Fair

WOOD:DETERIORATED DOORDeficiency

Room 210Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 210

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

EPOXY FLOORING:CRACKS/SPALLINGDeficiency

Room 202, 206, 210, 214, 216, and othersDeficiency Location/Instance

800Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 20 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 21: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo 1

Room 206

Deficiency Photo 2

Room 210

Violations No violations recorded

VINYL TILES:TRIPPING HAZARD - ELECTRICAL OUTLETDeficiency

Room 203, 222, 227Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Room 203

Violations No violations recorded

VINYL TILES:DETERIORATED SUBSTRATEDeficiency

Room 122, 126, Main Entrance LobbyDeficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 126

Violations No violations recorded

Page 21 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 22: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedSpecialties

InspectedClassroom Locker(s)

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existFixed Seating

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

GYMNASIUM

Instance on Basement Inspected

Ceiling

Instance on Basement Does not exist

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Seating

Instance on Basement Inspected

2- Between Good and FairInstance Condition

DAMAGED BLEACHERSDeficiency

Near the EntranceDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near the Entrance

Violations No violations recorded

Sliding-folding Partition

Instance on Basement Does not exist

Stage

Instance on Basement Does not exist

Walls

Instance on Basement Inspected

4- Between Fair and PoorInstance Condition

GYPSUM BOARD:DETERIORATEDDeficiency

Page 22 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 23: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

GYMNASIUM

Walls

Rear of RoomDeficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Rear of Room

Violations No violations recorded

WALL PADDING:DETERIORATEDDeficiency

Rear of RoomDeficiency Location/Instance

400Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Rear of Room

Violations No violations recorded

Window Curtains/Shades/Blinds

Instance on Basement Does not exist

InspectedINTERIOR DOOR HARDWARE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedINTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

KITCHEN

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Page 23 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 24: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

KITCHEN

Floor Finish

Instance on Basement Inspected

3- FairInstance Condition

QUARRY TILE:BROKEN/MISSING TILESDeficiency

Serving Areas, Storage Room, Corridor near Room B25BDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Serving Area

Violations No violations recorded

VINYL TILES:DETERIORATED SUBSTRATEDeficiency

Room B25CDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room B25C

Violations No violations recorded

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

LIBRARY

Instance on Room 100 Inspected

Built-in Furnishing

Instance on Room 100 Does not exist

Ceiling

Instance on Room 100 Inspected

2- Between Good and FairInstance Condition

TECTUM:DAMAGED/MISSINGDeficiency

Rear of RoomDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

Page 24 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 25: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

LIBRARY

Ceiling

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Rear of Room

Violations No violations recorded

Door(s)

Instance on Room 100 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Room 100 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on Room 100 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

LOCKER ROOM

Instance on Basement - Girls (408 lockers) Inspected

NoAlternative Use

Instance on Basement - Boys (396 lockers) Inspected

NoAlternative Use

Ceiling

Instance on Basement - Girls (408 lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Basement - Boys (396 lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement - Girls (408 lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Basement - Boys (396 lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Basement - Girls (408 lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Basement - Boys (396 lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Page 25 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 26: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

LOCKER ROOM

Locker Room Lockers

Instance on Basement - Girls (408 lockers) Inspected

2- Between Good and FairInstance Condition

DAMAGED UNITSDeficiency

Locker 362Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Locker 362

Violations No violations recorded

Instance on Basement - Boys (396 lockers) Inspected

3- FairInstance Condition

DAMAGED UNITSDeficiency

Lockers 4, 18, 280, 303, 322, and othersDeficiency Location/Instance

12Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Locker 280

Violations No violations recorded

Walls

Instance on Basement - Girls (408 lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Basement - Boys (396 lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Does not existMULTI-PURPOSE ROOM

Does not existPOOLS

SCIENCE DEMO ROOM

Instance on Room 214, 216, 218 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 214, 216, 218 Inspected

Page 26 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 27: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

SCIENCE DEMO ROOM

Fixed Equipment

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

SCIENCE LAB

Instance on Room 202 Inaccessible

Instance on Room 210 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 210 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

SCIENCE PREP ROOM

Instance on Room 206 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 206 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

SHOWER ROOM

Instance on Basement - Boys Inaccessible

Instance on Basement - Girls Inaccessible

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? Yes

InspectedCeiling

Condition 2- Between Good and Fair

GYPSUM BOARD:DAMAGED/DETERIORATED - ACTIVE

LEAK

Deficiency

Stair A/3, C/3Deficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair C/3

Deficiency Photo 2

Stair A/3

Violations No violations recorded

InspectedDoor(s)

Page 27 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 28: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existPartition

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 2- Between Good and Fair

STEEL COLUMNS/BEAMS:MINOR RUSTINGDeficiency

Facade ADeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR AND REPAINT

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Facade A (near ramp landing)

Violations No violations recorded

InspectedFLOOR STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFOUNDATION WALLS

Material Type(s) Concrete

Condition 3- Fair

CONCRETE:WATER INFILTRATION IN NON-

INSTRUCTIONAL SPACE

Deficiency

BasementDeficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

PRIORITY 5Urgency of Action

LEVEL 5Purpose of Action

Page 28 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 29: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Deficiency Photo 1

Gas meter -Room 3C shown, similar condition at room B3D (Acid

Tank Diesel ), Room B25H ( Sprinkler)

Violations No violations recorded

CONCRETE:WATER INFILTRATION IN ELECTRICAL

PANEL ROOM

Deficiency

BasementDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Electrical Room B2A

Violations No violations recorded

InspectedROOF STRUCTURE

Condition 2- Between Good and Fair

METAL DECK:MINOR RUSTINGDeficiency

BasementDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Electrical Room B2A

Violations No violations recorded

Does not existVAULTS-BUNKERS

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

Page 29 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 30: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STAFF

Ceiling

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 4- Between Fair and Poor

WOOD:DETERIORATED DOORDeficiency

Room 307Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 307

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTOILET ROOMS - STUDENTS

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

BROKEN/MISSINGDeficiency

Room 305Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 30 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 31: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Stalls

Deficiency Photo 1

Room 305

Violations No violations recorded

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

Does not existCONTAINERIZATION

Does not existDRAINAGE SYSTEM FOR ASPHALT

InspectedDRAINAGE SYSTEM FOR CONCRETE

InspectedCatch Basins/Manhole - Surrounded by Concrete

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Concrete Covering

Does not existDRAINAGE SYSTEM FOR SOIL

Does not existDRINKING FOUNTAINS

InspectedFENCES

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

3- FairCondition

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

West 102nd StreetDeficiency Location/Instance

150Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

West 102nd Street

Page 31 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 32: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Violations 21295

HEAVINGDeficiency

West 102nd StreetDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

West 102nd Street

Violations 21295

DAMAGED CURBSDeficiency

West 102nd StreetDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

West 102nd Street

Violations 21295

Does not existPavers

InspectedSite Sidewalks & Walkways

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedStudent Non-Use

Gravel Exists? No

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

East sideDeficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

Page 32 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 33: EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 …NYC Department of Education Building Condition Assessment Survey 2019-2020 Architectural Inspection M506 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

M506Architectural Inspection

Question Response

SITE

PAVING

Student Non-Use

Concrete

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

East side

Violations No violations recorded

Does not existPavers

Does not existStudent Use

Does not existPLAYGROUNDS

Does not existPLAYING SURFACE

Does not existRETAINING WALLS

Does not existSEATING

Does not existSITE WALLS (NOT RETAINING WALLS)

Does not existSTAIRS/RAMPS: EXTERIOR

Page 33 of 33 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)