Top Banner

of 14

EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

Feb 28, 2018

Download

Documents

Limuel Espiritu
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    1/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    ENGINEERING DESIGN STANDARD

    EDS 05-2010

    MAIN SUBSTATION FEEDER AND RING MAIN UNITPROTECTION SETTINGS (LPN)

    Network(s): LPN

    Summary: This standard describes the protection settings for main substation feeders and ringmain units in the LPN area.

    Owner: Kevin Burt Date: 02/12/2015

    Approved By: Barry Hatton Approved Date: 08/01/2015

    This document forms part of the Companys Integrated Business System and its requirements are mandatory throughout UKPower Networks. Departure from these requirements may only be taken with the written approval of the Director of AssetManagement. If you have any queries about this document please contact the author or owner of the current issue.

    Applicable To

    UK Power Networks External

    All UK Power Networks G81 Website

    Asset Management Contractors

    Capital Programme ICPs/IDNOs

    Connections Meter Operators

    HSS&TT

    Network Operations

    UK Power Networks Services

    Other

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    2/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 2 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Revision Record

    Version 4.0 Review Date 08/01/2019

    Date 02/12/2015 Author Kevin Burt

    Why has the document been updatedPeriodic review

    What has changedNo content changes

    Document transferred onto a new template and rules applied

    Version 3.2 Review Date 09/11/2015

    Date 04/09/2012 Author Lee Strachan

    Document reviewed for publishing on G81 website

    Version 3.1 Review Date 09/11/2015

    Date 25/08/2011 Author Chris Anderson

    Reclassified from EI to EDS

    Version 3.0 Review Date 09/11/2015

    Date 19/08/2010 Author David G Edwards

    Rebranded, reviewed and review date extended

    Version 2.0 Review Date

    Date 30/10/2006 Author David G Edwards

    TLF ratings and revised ACB protection settings added Tables (6A and 11A)

    Version 1.0 Review Date

    Date 07/04/2004 Author David G Edwards

    Original, based on Protection Standard Number E 7/6 P 6/1 revision 4. Original no. EI 05-0046

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    3/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 3 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Contents

    1 Introduction ............................................................................................................. 4

    2 Scope ....................................................................................................................... 4

    3 Glossary and Abbreviations ................................................................................... 4

    4 Main Substation Feeder Settings ........................................................................... 4

    5

    Secondary Distribution Transformers ................................................................... 4

    5.1 Transformer Overcurrent Protection .......................................................................... 4

    5.2

    Transformer Earth Fault Protection ............................................................................ 4

    6

    HV Supplies ............................................................................................................. 5

    6.1 HV Supplies to the Customers HV Switchboard........................................................ 5

    6.1.1 Overcurrent Protection .............................................................................................. 5

    6.1.2 Earth Fault Protection ................................................................................................ 5

    Tables

    Table 1Main Substation Feeder Settings ........................................................................... 6

    Table 2Ring Circuit Breaker and Service Circuit BreakerElectromechanical .................. 6

    Table 3Ring Circuit Breaker and Service Circuit BreakerVIP 200/300 ........................... 7

    Table 4SEPAM 1000 ......................................................................................................... 7

    Table 5SEPAM 1000+. ...................................................................................................... 8

    Table 6Overcurrent Protection of Distribution Transformers (Glass Barrel TLF FuseLinks) ................................................................................................................... 9

    Table 7Overcurrent Protection of Distribution Transformers (Tagged TLF Fuse Links) ... 11

    Table 8Settings for Merlin Gerin Masterpact ACB Control Unit STR58U (Glass BarrelTLF Fuse Links) ................................................................................................. 11

    Table 9Masterpact ACB STR 58U - 1200/1600A ACB with MODULE 1600A (GlassBarrel TLF Fuse Links) ...................................................................................... 12

    Table 10Masterpact ACB STR 58U2000A ACB with MODULE 2000A (Glass BarrelTLF Fuse Links) ............................................................................................. 12

    Table 111600A and 2000A Module (Glass Barrel TLF Fuse Links) ................................. 12

    Table 12Micrologic NW16/20 H11600/2000A Module (Glass Barrel TLF Fuse Links) . 13

    Table 13Micrologic NW16/20 H11600/2000A Module (Tagged TLF) ........................... 13

    Table 14Sensitive Earth Fault Settings ............................................................................ 13

    Table 15Overcurrent Protection of HV Supplies (refer to Section 6.1.1) .......................... 14

    Table 16Falcon Alpha RMU Overcurrent Trip Times Versus Fault Current...................... 14

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    4/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 4 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    1 Introduction

    This standard describes protection settings for main substation feeders and ring main unitsin the UK Power Networks (UKPN) LPN region.

    2 Scope

    This standard only applies to the London Power Network (LPN) area.

    3 Glossary and Abbreviations

    Term Definition

    UK Power Networks UK Power Networks (Operations) Ltd consists of three electricitydistribution networks:

    Eastern Power Networks plc (EPN).

    London Power Network plc (LPN).

    South Eastern Power Networks plc (SPN).

    4 Main Substation Feeder Settings

    The overcurrent and earth fault settings shall be as listed inTable 1 unless otherwise agreedwith UKPN Asset Management.

    5 Secondary Distribution Transformers

    5.1 Transformer Overcurrent Protection

    The rating of the time-limit fuse-links or the type of thermal protection modules forovercurrent protection of secondary distribution transformers applied at ring main units andtheir associated air circuit breakers shall be as listed inTable 6.

    5.2 Transformer Earth Fault Protection

    Instantaneous sensitive earth fault protection with sensitivities as declared in Table 14 isinherent in the design of all but:

    The Falcon Alpha units (original Falcon units) where it is provided, when specified, viadedicated core balanced current transformers; and

    Switch fuses, where it is not good practice to provide it.

    It should be noted that such a provision is not normally present on transformer mountedFalcon Alpha units.

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    5/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 5 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    6 HV Supplies

    Where an HV supply is connected directly to the customers own transformer, of which therating and winding arrangement and impedance are similar to the Companys distributiontransformers, then Section 5 of this document shall apply. For transformers not soidentifiable, advice should be sought from UKPN Asset Management. Where relays are usedto afford protection then the settings shall be as inTable 1, Table 2 andTable 3.

    If Microprocessorrelays are used, reference should be made to UKPN Asset Managementwith full details of the proposed installation so that individual settings can be supplied.

    6.1 HV Supplies to the Customers HV Switchboard

    6.1.1 Overcurrent Protection

    Discrimination with the customers own equipment, other than fuses for HV faults, is notfeasible with ring main units protected by time fuse links. Discrimination with the customersequipment can be afforded by use of protective relays. Relays installed with characteristicsbased on the standard inverse BS 142 curve shall have settings as in Table 2. Relayssupplied with adjustable complex curves, may need special treatment and shall be referredto UKPN Asset Management.

    In some cases the customer will not require discrimination with the service and thus it maybe possible to use time fuses for overcurrent (and instantaneous protection for earth faultswhen applicable). The rating of the time fuse link and thermal modules for these cases shall

    be as listed inTable 15.

    Limited discrimination is possible with units protected by thermal protection modules, andTable 16 relates to Falcon Alpha overcurrent trip times to fault current as an applicationguide. In cases of doubt advice should be sought from UKPN Asset Management. WhereFalcon Alpha units are used to provide such a supply then the module shall be as specifiedinTable 15.

    6.1.2 Earth Fault Protection

    Earth fault protection can be provided by protection relays and for the standard inverse curve

    relay settings refer to Table 2 and Table 3. In the case of Microprocessor relays refer toUKPN Asset Management.

    Instantaneous sensitive earth fault protection with sensitivities as declared in Table 14 isinherent in the design of all but;

    The Falcon Alpha ring main unit, where it is provided, when specified, via a dedicatedcore balance current transformer; and

    Switch fuses, where it is not provided. The switch fuse will, however, discriminate withthe main substation earth fault relay for earth faults exceeding 800A downstream of thering main unit.

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    6/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 6 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Where Falcon Alpha ring main units are installed, and there is a requirement by the

    customer for discrimination, no instantaneous earth fault protection is needed and thefollowing applies:

    For applications (seeTable 15)using the D module, no specific earth fault protection isnecessary because the D module discriminates with the main substation earth faultrelay for earth faults downstream of the ring main unit;

    For applications using the F module, a separate IDMT earth fault current relay fed fromthe core balance current transformer and set at 120 primary amperes 0.15 timemultiplier, tripping via the shunt trip coil should be installed. This will prevent the mainsubstation earth fault relay from operating before the ring main unit for earth faultsdownstream of the ring main unit.

    Table 1Main Substation Feeder Settings

    High Set Overcurrentwhen Provided

    IDMT Overcurrent IDMT Earth Fault

    Feeders without HVcustomers or where HVsupplies are afforded tocustomers own distributiontransformers

    2400-3200A 600A 0.2TM 200A 0.2TM

    Feeders from which at leastone HV supply is afforded to

    customers HVswitchboard

    Not deployed 600A 0.35TM 200A 0.35TM

    Table 2Ring Circuit Breaker and Service Circuit BreakerElectromechanical

    Method of Supply Ring CB Service CB

    IDMTOvercurrent

    IDMT EarthFault

    IDMTOvercurrent

    IDMT EarthFault

    Unit protected twofeeders in parallel

    450A 0.15TM 150A 0.15TM

    Unit protected threefeeders in parallel

    600A 0.15TM 200A 0.15TM 450A 0.15TM 150A 0.15TM

    Directionalprotected twofeeders in parallel

    600A 0.15TM 200A 0.15TM 450A 0.15TM 150A 0.15TM

    Radial Feed 450A 0.15TM 150A 0.15TM

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    7/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 7 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Table 3Ring Circuit Breaker and Service Circuit BreakerVIP 200/300

    VIP 200/300

    CTRatio

    200/1 800/1 800/1

    Position Service Service Ring

    O/C SI 200A, t=0.4s

    (equivalent totms=0.135)

    SI 448A, t=0.4s

    (equivalent totms=0.135)

    SI 576A,T=0.4s

    (equivalent to tms=0.135)

    E/F SI 140A, t=0.4s

    (equivalent totms=0.135)

    SI 128A, t=0.4s

    (equivalent totms=0.135)

    SI 196A, t=0.4s

    (equivalent to tms=0.135)

    VIP 300

    CTRatio

    400/1 Not suitable for Ring Busters

    Position Service

    O/C SI 400A, t=0.4s

    (equivalent totms=0.135)

    E/F SI 160A, t=0.4s

    (equivalent to

    tms=0.135)

    Notes:1. VIP Relays are self powered from the CT, the maximum setting is 100% of the CT primary rating.2. As from September 2003 YRM switchgear came with 400/1 CTs.

    Table 4SEPAM 1000

    Position Service Service Ring

    CT Ratio 200/1 600/1 600/1

    Overcurrent SI 440A, t=0.4s

    (equivalent totms=0.135)

    SI 450A, t=0.4s

    (equivalent to tms=0.135)

    SI 600A,T=0.4s

    (equivalent to tms=0.135)

    Earth Fault SI 150A, t=0.4s

    (equivalent totms=0.135)

    SI 150A, t=0.4s

    (equivalent to tms=0.135)

    SI 200A, t=0.4s

    (equivalent to tms=0.135)

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    8/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 8 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Table 5SEPAM 1000+.

    PositionService

    SELECT A+B

    Ring

    SELECT A+B

    CT Ratio 600/1 600/1

    OvercurrentSIT 450, t=0.450s

    (equivalent to tms=0.15)

    SIT 600A,T=0.450s

    (equivalent to tms=0.15)

    E/FSIT 150A, t=0.450s

    (equivalent to tms=0.15)

    SIT 200A, t=0.450s

    (equivalent to tms=0.15)

    Notes:1. For all the above settings refer to Asset Management.2. Special applications will be considered to assist customers with their downstream protection grading. Such

    requests shall be sent to Asset Management and if abnormal settings are to be issued for application tonetwork protection, a note of this abnormality shall be attached in the control graphics system, adjacent tothe substation concerned.

    3. Settings and logic for all microprocessor relays are the responsibility of Programme Delivery, ProtectionApplications.

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    9/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 9 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Table 6Overcurrent Protection of Distribution Transformers (Glass Barrel TLF Fuse Links)

    Equipment CTRatio

    Voltage Transformer Ratings

    500kVA 750/800kVA 1000kVA 2x500kVA 2 x750/800kVA

    BrushFalcon

    ALPHARMU

    8/1 6.6kV D D (*3) - - -

    (*1) 11kV C D D D (*2) -

    19/1 6.6kV - - F E (*2) -

    (*1) 11kV - - - - E (*2)

    BrushFalconBETA RMU

    50/5 6.6kV 10A - - - -

    11kV7.5A - seetable 8

    10A - - -

    100/5 6.6kV - 7.5A 10A 10A -

    11kV - - 7.5A 7.5A 10A

    Yorkshire(*6)SwitchgearRingmasterRMU MK1.5

    75/5 6.6kV7.5A (*4) -see table8

    10A (*4) 10A (*4) 10 (*2) -

    11kV 5A 7.5A 10A 7.5 (*2)

    YorkshireSwitchgearRingmasterRMU MK 2

    50/5 6.6kV 10A - - - -

    11kV7.5A - seetable 8

    10A - - -

    100/5 6.6kV - 7.5A 10A 10A -

    11kV - - 7.5 7.5A 10A

    Long & (*7)Crawford(*8) LCGTRMU(Switchfuse)

    - 6.6kV 100(80)A 140(100)A140(100)

    A- -

    11kV 63(50)A 80(63)A 100(80)A - -

    Lucy (*8)

    SFRMU CF1Switchfuse

    - 6.6kV 80A 125A - - -

    - 11kV 50A 80A 100A - -

    LucySCRMU

    70/5 6.6kV 10A - - - -

    11kV7.5A - seetable 8

    10A - - -

    100/5 6.6kV - 7.5A 10A 10A -

    11kV - - 7.5A 7.5 10A

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    10/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 10 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Equipment CTRatio

    Voltage Transformer Ratings

    500kVA 750/800kVA 1000kVA 2x500kVA 2 x750/800kVA

    ABBSentinelRMU

    50/5 6.6kV 10A - - - -

    11kV7.5A - seetable 8

    10A - - -

    100/5 6.6kV - 7.5A 10A 10A -

    11kV - - 7.5A 7.5A 10A

    All OtherRMUs

    50/5 6.6kV 10A - - - -

    11kV7.5A - seetable 8

    10A - - -

    80/5 6.6kV7.5A - seetable 8

    10A - - -

    11kV 5A 7.5A 10A 10A 10A

    100/5 6.6kV - 7.5A (*4) 10A 10A -

    11kV - - 7.5A 7.5A 10A

    MasterpackACB

    Standard settings set at factory for 1200 & 1600 amp units see Table 9. Any other unitsneed to be referred to System Development Protection

    ACB

    800/5 0.433kV 7.5A - - 7.5A -

    1200/5 0.433kV 5A 7.5A - 5A 7.5A

    1600/5 0.433kV - - 7.5A - -

    Notes:1. On the Falcon Alpha RMU, current transformers are matched to particular types of protection modules.

    Unless specifically agreed with the MPL Protection Section, module types must not be interchanged betweenthe two CT types. The CTs are mounted inside the SF6chamber which must be returned to the manufacturerif a change is necessary.

    2. In the interests of faster fault clearance, discrimination across the distribution transformer is sacrificed if theLV windings are paralleled.

    3. Some loss of discrimination across the distribution transformer results from avoiding a CT change on

    uprating to 11kV operation.4. Discrimination across the transformer is sacrificed in the interest of faster fault clearance.5. This ratio is not available on Yorkshire Ringmaster, Lucy SCRMU, or Falcon BETA RMUs.6. Yorkshire Ringmasters, pre-MK 2 on the LPN network, are referred to as MK 1.5.7. Figures quoted are fuse rating in oil. Ratings in air are shown in brackets.8. Discrimination with LV ACBs is not guaranteed and should not be used with solidly interconnected LV

    systems.9. Discrimination between Falcon ALPHA RMUs and MSS is not guaranteed for faults between the RMU and

    its transformer.10. There is no overload factor on this application.11. For applications other than the above, advice should be sought from Asset Management

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    11/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 11 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Table 7Overcurrent Protection of Distribution Transformers (Tagged TLF Fuse Links)

    Voltage Transformer rating CT ratio TLF rating SAP code

    11 kV

    500 kVA 40/5 N/A N/A

    50/5 N/A N/A

    800 kVA 80/5 15 A 11947C

    100/5 15 A 11947C

    1000 kVA 80/5 15 A 11947C

    100/5 15 A 11947C

    Note: For existing distribution substations with a 500kVA transformer where HV switchgearis to be changed and the 500kVA transformer is to be retained, it is not possible to gradetag-type TLFs with the LV fuses. Therefore, when replacement of the HV equipment isnecessary, complete the following:

    Install a Lucy Sabre VRN2A RMU.

    Retro fit clips for glass barrel-type TLFs.

    Install 10A glass barrel-type TLFs.

    Table 8Settings for Merlin Gerin Masterpact ACB Control Unit STR58U (Glass Barrel TLF FuseLinks)

    Characteristics Setting Value Dial Position Dial Position

    Long Time Pick Up LT 1600A IO= 1 Ir=1

    Long Time Time Delay LT 15 s tr= 15 -

    Short Time Pick Up ST 2400A Im=1.5 -

    Short Time Time DelayST

    0.2 s tm= 0.2 -

    I2t ON tmDial Set Clockwise to 0.2

    Instantaneous Pick Up 12800A I = 8 -

    Notes:

    1. For transformers of all sizes associated with 1200A and 1600A ACBs using 1600A sensors.2. These settings grade with downstream J400A fuses. They will not grade with J-type distribution fuses of

    higher rating.3. Upstream RMU 7.5A TLFs with 50/5, 70/5, 75/5 and 80/5 CTs must be changed to 10A TLFs (Glass Barrel

    TLF Fuse Links).

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    12/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 12 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Table 9Masterpact ACB STR 58U - 1200/1600A ACB with MODULE 1600A (Glass Barrel TLF

    Fuse Links)

    1200/1600amp ACB with MODULE 1600A

    TransformerSize

    TLFMin CTratio

    Io Ir tr Im tm I2t I

    500kVA 50/5 1 1 15 1.5 0.2 on 12

    800kVA 80/5 1 1 15 1.5 0.2 on 14

    800kVA 75/5 1 1 15 1.5 0.2 on 14

    1000kVA 100/5 1 1 15 1.5 0.2 0n 22

    Notes:1. Settings to apply for transformers with services having 630A or 800A fuses and on interconnected areas

    using 500A fuses.2. Always use 10A TLFs (Glass Barrel TLF Fuse Links).

    Table 10Masterpact ACB STR 58U2000A ACB with MODULE 2000A (Glass Barrel TLF FuseLinks)

    TransformerSize

    CTRatio

    Io Ir tr Im tm I2t I

    1000kVA 100/5 1 1 15 1.5 0.2 0n 17

    Notes:1. Where two transformers are connected in parallel at LV from different feeders, in the event of an earth fault

    on one feeder, there is the possibility of the feeder being back fed by the other transformer.2. This will occur with radial LV networks, where hold-up performance is poor in fully interconnected LV

    networks.3. This arrangement is to coordinate with reverse power relays and parasitic trip units.

    Table 111600A and 2000A Module (Glass Barrel TLF Fuse Links)

    Module TransformerSize

    CT ratio Io Ir tr Im tm I2t I

    1600A 2 x 1000kVA 100/5 1 1 15 3 0.2 on 22

    2000A 2 x 1000kVA 100/5 1 1 15 3 0.2 on 17

    Notes:1. Masterpact NM ACB.2. Micrologic 5.0A.3. Settings to apply for transformers with services having 630A or 800A fuses and on interconnected areas

    using 500A fuses.4. Always use 10A TLFs (Glass Barrel TLF Fuse Links)

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    13/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    UK Power Networks 2016 All rights reserved 13 of 14

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Table 12Micrologic NW16/20 H11600/2000A Module (Glass Barrel TLF Fuse Links)

    Protection settings to be applied when grading with a glass barreled TLF fuse link. Refer to Table 6 Over-current protection of distribution transformers (Glass Barrel TLF)

    ModuleTransformerSize

    TLF MinCT Ratio

    Ir tr Isd tsd Iinst

    Micrologic NW16 H1- 1600A

    All 100/5 1.00 4.0 8.00 0.1+I2t 15

    Micrologic NW20 H1- 2000A

    All 100/5 1.00 4.0 6.00 0.1+I2t 15

    Note: For all Micrologic these settings are factory set. They will need to be checked at the time of commissioning.

    Table 13Micrologic NW16/20 H11600/2000A Module (Tagged TLF)

    Protection settings to be applied when grading with a Tagged TLF fuse link. Refer to Table 7 Over-current protection of distribution transformers (Tagged TLF).

    ModuleTransformerSize

    TLF MinCT Ratio

    Ir tr Isd tsd Iinst

    Micrologic NW16 H1- 1600A

    All 100/5 1.00 12 6.00 0.1+I2t 15

    Micrologic NW20 H1- 2000A All 100/5 1.00 4.0 4.00 0.1+I

    2

    t 15

    Note: For all Micrologic these settings are factory set. They will need to be checked at the time of commissioning.

    Table 14Sensitive Earth Fault Settings

    Equipment CT Ratio Sensitive Earth Fault Setting

    Brush ALPHA RMU Core balance

    400/5 30 A

    Brush BETA RMU 50/5

    100/5

    30 A

    40 A

    Yorkshire Ringmaster MK1.5 75/5 20A

    Yorkshire Ringmaster MK2 50/5

    100/5

    20 A

    25 A

    Lucy SCRMU 70/5

    100/5

    20 A

    25 A

    ABB

    Sentinel RMU

    50/5

    100/5

    20 A - 27 A

    28 A - 35 A

    All RMUs except Switch Fusesand the above

    50/5

    80/5

    100/5

    20 A

    20 A

    25 A

  • 7/25/2019 EDS+05-2010+Main+Substation+Feeder+and+Ring+Main+Unit+Protection+Settings+(LPN).pdf

    14/14

    Document Number: EDS 05-2010

    Version: 4.0

    Date: 02/12/2015

    THISISAN

    UNCONTROLLED

    DOCUMENT,THE

    READER

    MUSTCONFIRMI

    TSVALIDITYBEF

    OREUSE

    Table 15Overcurrent Protection of HV Supplies (refer to Section 6.1.1)

    Equipment Load MVA at 6.6kV MVA at 11kV Module/fuse CT

    Brush FalconALPHA

    0-100A 0-1.1 0-1.9 d (1) 8/1

    100-180A 1.1-2.0 1.9-3.4 F (1) 19/1

    >180A >2.0 >3.4 Use extensible switchgear

    YorkshireSwitchgearRingmaster

    0-150A 0-1.7 0-2.85 10A 75/5 MK1

    0-200A 0-2.28 0-3.8 10A 100/5 MK2

    MK2 only for downstream discrimination using relays

    Long &

    CrawfordLCGT Sw/fuse

    0-80A 0.9 1.5 100(80)A(7)

    -

    Lucy SFRMU-CF1 Sw/fuse

    0-83A 0.95 1.58 125A -

    All RMUsexcept asabove

    0-100A 0-1.1 0-1.9 10A 100/5

    Notes:1. For downstream discrimination a relay should be used. Refer to Asset Management for VIP200 Settings.2. Refer to Section6.1.2 for earth fault protection requirements.

    Table 16Falcon Alpha RMU Overcurrent Trip Times Versus Fault Current

    Fault Current (A) D Module (s) F Module (s)

    1000 0.8 1.0

    2000 0.45 0.4

    4000 0.3 0.22

    6000 0.25 0.17

    8000 0.22 0.15

    10000 0.2 0.13