Installation Guide for EdgeBox-RI 4 COMMERCE WAY, ARDEN, NC 28704 USA 800 . 892 . 9173 828 . 676 . 1700 OMGEDGESYSTEMS.COM EdgeBox-RI
Installation Guide for EdgeBox-RI
4 COMMERCE WAY, ARDEN, NC 28704 USA800.892.9173 828.676.1700
OMGEDGESYSTEMS.COM
EdgeBox-RI
G. Finish StripParallel to deck flutes
(required for metal deck)H. Closure Strip
Perpendicular to deck flutes (required for metal deck)
Installation Guide forEdgeBox-RI
FINISH STRIP(TYPE 2 SHOWN)
CORRUGATED ROOFDECK BY OTHERS
#14 HD FASTENER15" F.E. / 45" O.C.
#14 X 1½" UNIVERSAL FASTENER6" F.E. / 12" O.C. (TYP. 4)
TOP SECTION10’ LENGTHS
BOTTOM SECTION 10' LENGTHS
OPTIONAL INSULATIONBY OTHERS
MEMBRANE BY OTHERS
B. Bottom Section10-ft. Lengths
A. Top Section10-ft. Lengths
C. End Cap InsertSlides into exposed end of bottom section
D. #14 X 1½-in. Universal FastenerIncluded and required
F. EdgeBox SpineRequired for face greater than 6-in.
E. #14 HD Roofing Fastener Size varies based on height of EdgeBox min. 1-in. penetration required
A
B
H
OPTIONALINSULATION(BY OTHERS)
ROOF DECK(BY OTHERS)
G
C
E
D
F
CLOSURE STRIPFASTENERPROVIDED
NOTES:#1 - Isolate all metal parts from ACQ treated wood or other galvanically incompatible material with appropriate membrane material. #2 - Appliance attachments, such as lightning rods, signs, or antennae that penetrate the water seal, induce a galvanic reaction, or otherwise compromise the effectiveness of the roof edge system, shall be eliminated or isolated to prevent problems per section 8.0 of ANSI/SPRI/FM4435/ES-1. Appliances shall be isolated from or not attached to the roof edge system. Consult the lightning protection system manufacturer for specific attachment instructions.
ANSI/SPRI/FM4435/ES-1 TESTED
APPROVALS: Contact manufacturer for verification of test report data on your project.
G. Finish StripParallel to deck flutes
(required for metal deck)H. Closure Strip
Perpendicular to deck flutes (required for metal deck)
Installation Guide forEdgeBox-RI
FINISH STRIP(TYPE 2 SHOWN)
CORRUGATED ROOFDECK BY OTHERS
#14 HD FASTENER15" F.E. / 45" O.C.
#14 X 1½" UNIVERSAL FASTENER6" F.E. / 12" O.C. (TYP. 4)
TOP SECTION10’ LENGTHS
BOTTOM SECTION 10' LENGTHS
OPTIONAL INSULATIONBY OTHERS
MEMBRANE BY OTHERS
B. Bottom Section10-ft. Lengths
A. Top Section10-ft. Lengths
C. End Cap InsertSlides into exposed end of bottom section
D. #14 X 1½-in. Universal FastenerIncluded and required
F. EdgeBox SpineRequired for face greater than 6-in.
E. #14 HD Roofing Fastener Size varies based on height of EdgeBox min. 1-in. penetration required
A
B
H
OPTIONALINSULATION(BY OTHERS)
ROOF DECK(BY OTHERS)
G
C
E
D
F
CLOSURE STRIPFASTENERPROVIDED
NOTES:#1 - Isolate all metal parts from ACQ treated wood or other galvanically incompatible material with appropriate membrane material. #2 - Appliance attachments, such as lightning rods, signs, or antennae that penetrate the water seal, induce a galvanic reaction, or otherwise compromise the effectiveness of the roof edge system, shall be eliminated or isolated to prevent problems per section 8.0 of ANSI/SPRI/FM4435/ES-1. Appliances shall be isolated from or not attached to the roof edge system. Consult the lightning protection system manufacturer for specific attachment instructions.
ANSI/SPRI/FM4435/ES-1 TESTED
APPROVALS: Contact manufacturer for verification of test report data on your project.
C. Leveling AngleSets Proper Height for Water Dam
B. Concealed Joint Splice4-in. Lengths
A. Formed Fascia Cover10-ft. Lengths
G. Built-up or Modified Roofing(By Installer)
H. Corner Support (Outside)At All Inside and Outside Corners
D. Formed Galvanized Water-Dam10-ft. Lengths
E. 1½-in. SS Ring Shank Nails (Included & Required)
E
D
A
OUTSIDEMITER
H
C
B
END TERM(LEFT HANDSHOWN)
B
ROOFSIDE
G
FASCIA
FACE
JOINT SPLICECOMPRESSION CLAMP
WATER DAM#12 X 1¼"SELF-DRILLING SCREW
STRIP-IN PLY BY INSTALLERBASE PLYBY OTHERS
1½" SS RING SHANK NAILFOR FACES 6" OR GREATER
1½" SS RING SHANK NAIL
1-in. m
in. Ove
rlap
NOTES:#1 - Isolate all metal parts from ACQ treated wood or other galvanicallyincompatible material with appropriate membrane material.#2 - Appliance attachments, such as lightning rods, signs, or antennaethat penetrate the water seal, induce a galvanic reaction, or otherwisecompromise the effectiveness of the roof edge system, shall beeliminated or isolated to prevent problems per section 8.0 of ANSI/FM4435/SPRI ES -1. Appliances shall be isolated from or not attached to the roof edge system. Consult the lightning protection system manufacturer for specific attachment instructions.
G. Finish StripParallel to deck flutes
(required for metal deck)H. Closure Strip
Perpendicular to deck flutes (required for metal deck)
Installation Guide forEdgeBox-RI
FINISH STRIP(TYPE 2 SHOWN)
CORRUGATED ROOFDECK BY OTHERS
#14 HD FASTENER15" F.E. / 45" O.C.
#14 X 1½" UNIVERSAL FASTENER6" F.E. / 12" O.C. (TYP. 4)
TOP SECTION10’ LENGTHS
BOTTOM SECTION 10' LENGTHS
OPTIONAL INSULATIONBY OTHERS
MEMBRANE BY OTHERS
B. Bottom Section10-ft. Lengths
A. Top Section10-ft. Lengths
C. End Cap InsertSlides into exposed end of bottom section
D. #14 X 1½-in. Universal FastenerIncluded and required
F. EdgeBox SpineRequired for face greater than 6-in.
E. #14 HD Roofing Fastener Size varies based on height of EdgeBox min. 1-in. penetration required
A
B
H
OPTIONALINSULATION(BY OTHERS)
ROOF DECK(BY OTHERS)
G
C
E
D
F
CLOSURE STRIPFASTENERPROVIDED
NOTES:#1 - Isolate all metal parts from ACQ treated wood or other galvanically incompatible material with appropriate membrane material. #2 - Appliance attachments, such as lightning rods, signs, or antennae that penetrate the water seal, induce a galvanic reaction, or otherwise compromise the effectiveness of the roof edge system, shall be eliminated or isolated to prevent problems per section 8.0 of ANSI/SPRI/FM4435/ES-1. Appliances shall be isolated from or not attached to the roof edge system. Consult the lightning protection system manufacturer for specific attachment instructions.
ANSI/SPRI/FM4435/ES-1 TESTED
APPROVALS: Contact manufacturer for verification of test report data on your project.
OPTIONAL FINISH STRIP (TYPE 2 SHOWN)
CORRUGATED ROOF DECK BY OTHERSACCESSORY
HIEGHT
BOX WIDTHMIN: 3-1/2-IN.MAX: 16-IN.
SPINES, 1-IN. WIDE, 2-FT. O.C. REQ'D FOR BOX HEIGHT AND/OR BOX WIDTH > 6-IN.
#14 HD FASTENER PROVIDED @ 15-IN. F.E. AND 45-IN. O.C.
#14 X 1-1/2-IN. UNIVERSAL FASTENER PROVIDED @ 12-IN. O.C.
TOP SECTION FORMED IN 10-FT. LENGTHS
BOTTOM SECTION 10-FT. LENGTHS
OPTIONAL INSULATION BY OTHERS
MEMBRANEBOX HEIGHTMIN: 1-1/4-IN.MAX: 16-IN.
OPTIONAL INSULATION BY OTHERS #14 X 1-1/2-IN. UNIVERSAL FASTENER
PROVIDED @ 12-IN. O.C.
#14 X 1-1/2-IN. UNIVERSAL FASTENER PROVIDED @ 24-IN. O.C. WHEN SPINES USED
PRE-DRILL WITH 3/16-IN. DRILL BIT FOR MASONRY CONDITIONS.CONTACT OMG FOR APPROPRIATE RECOMMENDATIONS NEEDED TO MEET/EXCEED
ANSI/SPRI/FM4435/ES-1 DESIGN CRITERIA
ANSI/SPRI/FM4435/ES-1 TEST PRESSURES UP TO 911 PSF (VERTICAL) AND 526 PSF (HORIZONTAL)
4 COMMERCE WAY, ARDEN, NC 28704 USA800.892.9173 828.676.1700 OMGEDGESYSTEMS.COMCopyright © 2020 OMG, Inc. All rights reserved. EM
1067
Re
v. 10
2120
20Superior productivity. Superior performance.
STEP 1: Installing Closure Strip & Finish StripRequired for metal deck only. Place appropriate strips on the edgeof the metal deck. Secure in place with #14 x 1½-in. universalfastener (5 per 10-ft. section). Fastener heads not to interfere withbottom sections.
FINISHSTRIP
CLOSURESTRIP
METAL DECKBY OTHERS
#14 x 1½" UNIVERSALFASTENER @ 24" O.C.
FIGURE 1
STEP 4: Installing End CapsPlace end cap in exposed end of bottom section, secure withprovided #14 x 1½-in. universal fastener (2 per end cap).
END CAP
FIGURE 4
STEP 2: Installing Bottom SectionStarting at the corners, place bottom sections as shown aboveworking from the corners to the center. Secure in place usingprovided #14 x 1½-in. universal fasteners through pre-punchedholes (10 per 10-ft. section). Butt adjacent sections.
BOTTOMSECTIONS
#14 X 1½"UNIVERSALFASTENER@ 12" O.C.
FIGURE 2
FIGURE 3
STEP 5: Installing Top SectionStarting at the corners, place top sections as shown in FIGURE 5.Working from the corners to the center, consider lengths of middlepieces prior to cutting to avoid creating relatively short sections (lessthan 5-ft.). Secure top to bottom using # 14 X 1½-in. universalfastener through pre-punched holes in the face (10 per 10-ft.section), and through pre-punched holes in the back (10 per 10-ft.section).Install the #14 HD Roofing Fasteners through the
required for 10-ft. section. Butt adjacent sections.
FIGURE 5
TOPSECTIONS
FIGURE 6
#14 HDROOFINGFASTENER,MIN. 3 PER 10'SECTION
pre-punched holes and into the substrate. Minimum 3 HD fasteners