Installation Guide for EdgeBox-RI 4 COMMERCE WAY, ARDEN, NC 28704 USA 800 . 892 . 9173 828 . 676 . 1700 OMGEDGESYSTEMS.COM EdgeBox-RI
3

EdgeBox-RI...1½" S RI NG SHANK AIL FOR FACES 6" OR GREATER 1½" SS RING SHANK NAIL 1-in. min. Overlap NOTES: #1 - Is ola te all m al pa rs f om ACQ ad w d her galv nic lly incompatible

Feb 15, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • Installation Guide for EdgeBox-RI

    4 COMMERCE WAY, ARDEN, NC 28704 USA800.892.9173 828.676.1700

    OMGEDGESYSTEMS.COM

    EdgeBox-RI

  • G. Finish StripParallel to deck flutes

    (required for metal deck)H. Closure Strip

    Perpendicular to deck flutes (required for metal deck)

    Installation Guide forEdgeBox-RI

    FINISH STRIP(TYPE 2 SHOWN)

    CORRUGATED ROOFDECK BY OTHERS

    #14 HD FASTENER15" F.E. / 45" O.C.

    #14 X 1½" UNIVERSAL FASTENER6" F.E. / 12" O.C. (TYP. 4)

    TOP SECTION10’ LENGTHS

    BOTTOM SECTION 10' LENGTHS

    OPTIONAL INSULATIONBY OTHERS

    MEMBRANE BY OTHERS

    B. Bottom Section10-ft. Lengths

    A. Top Section10-ft. Lengths

    C. End Cap InsertSlides into exposed end of bottom section

    D. #14 X 1½-in. Universal FastenerIncluded and required

    F. EdgeBox SpineRequired for face greater than 6-in.

    E. #14 HD Roofing Fastener Size varies based on height of EdgeBox min. 1-in. penetration required

    A

    B

    H

    OPTIONALINSULATION(BY OTHERS)

    ROOF DECK(BY OTHERS)

    G

    C

    E

    D

    F

    CLOSURE STRIPFASTENERPROVIDED

    NOTES:#1 - Isolate all metal parts from ACQ treated wood or other galvanically incompatible material with appropriate membrane material. #2 - Appliance attachments, such as lightning rods, signs, or antennae that penetrate the water seal, induce a galvanic reaction, or otherwise compromise the effectiveness of the roof edge system, shall be eliminated or isolated to prevent problems per section 8.0 of ANSI/SPRI/FM4435/ES-1. Appliances shall be isolated from or not attached to the roof edge system. Consult the lightning protection system manufacturer for specific attachment instructions.

    ANSI/SPRI/FM4435/ES-1 TESTED

    APPROVALS: Contact manufacturer for verification of test report data on your project.

    G. Finish StripParallel to deck flutes

    (required for metal deck)H. Closure Strip

    Perpendicular to deck flutes (required for metal deck)

    Installation Guide forEdgeBox-RI

    FINISH STRIP(TYPE 2 SHOWN)

    CORRUGATED ROOFDECK BY OTHERS

    #14 HD FASTENER15" F.E. / 45" O.C.

    #14 X 1½" UNIVERSAL FASTENER6" F.E. / 12" O.C. (TYP. 4)

    TOP SECTION10’ LENGTHS

    BOTTOM SECTION 10' LENGTHS

    OPTIONAL INSULATIONBY OTHERS

    MEMBRANE BY OTHERS

    B. Bottom Section10-ft. Lengths

    A. Top Section10-ft. Lengths

    C. End Cap InsertSlides into exposed end of bottom section

    D. #14 X 1½-in. Universal FastenerIncluded and required

    F. EdgeBox SpineRequired for face greater than 6-in.

    E. #14 HD Roofing Fastener Size varies based on height of EdgeBox min. 1-in. penetration required

    A

    B

    H

    OPTIONALINSULATION(BY OTHERS)

    ROOF DECK(BY OTHERS)

    G

    C

    E

    D

    F

    CLOSURE STRIPFASTENERPROVIDED

    NOTES:#1 - Isolate all metal parts from ACQ treated wood or other galvanically incompatible material with appropriate membrane material. #2 - Appliance attachments, such as lightning rods, signs, or antennae that penetrate the water seal, induce a galvanic reaction, or otherwise compromise the effectiveness of the roof edge system, shall be eliminated or isolated to prevent problems per section 8.0 of ANSI/SPRI/FM4435/ES-1. Appliances shall be isolated from or not attached to the roof edge system. Consult the lightning protection system manufacturer for specific attachment instructions.

    ANSI/SPRI/FM4435/ES-1 TESTED

    APPROVALS: Contact manufacturer for verification of test report data on your project.

    C. Leveling AngleSets Proper Height for Water Dam

    B. Concealed Joint Splice4-in. Lengths

    A. Formed Fascia Cover10-ft. Lengths

    G. Built-up or Modified Roofing(By Installer)

    H. Corner Support (Outside)At All Inside and Outside Corners

    D. Formed Galvanized Water-Dam10-ft. Lengths

    E. 1½-in. SS Ring Shank Nails (Included & Required)

    E

    D

    A

    OUTSIDEMITER

    H

    C

    B

    END TERM(LEFT HANDSHOWN)

    B

    ROOFSIDE

    G

    FASCIA

    FACE

    JOINT SPLICECOMPRESSION CLAMP

    WATER DAM#12 X 1¼"SELF-DRILLING SCREW

    STRIP-IN PLY BY INSTALLERBASE PLYBY OTHERS

    1½" SS RING SHANK NAILFOR FACES 6" OR GREATER

    1½" SS RING SHANK NAIL

    1-in. m

    in. Ove

    rlap

    NOTES:#1 - Isolate all metal parts from ACQ treated wood or other galvanicallyincompatible material with appropriate membrane material.#2 - Appliance attachments, such as lightning rods, signs, or antennaethat penetrate the water seal, induce a galvanic reaction, or otherwisecompromise the effectiveness of the roof edge system, shall beeliminated or isolated to prevent problems per section 8.0 of ANSI/FM4435/SPRI ES -1. Appliances shall be isolated from or not attached to the roof edge system. Consult the lightning protection system manufacturer for specific attachment instructions.

    G. Finish StripParallel to deck flutes

    (required for metal deck)H. Closure Strip

    Perpendicular to deck flutes (required for metal deck)

    Installation Guide forEdgeBox-RI

    FINISH STRIP(TYPE 2 SHOWN)

    CORRUGATED ROOFDECK BY OTHERS

    #14 HD FASTENER15" F.E. / 45" O.C.

    #14 X 1½" UNIVERSAL FASTENER6" F.E. / 12" O.C. (TYP. 4)

    TOP SECTION10’ LENGTHS

    BOTTOM SECTION 10' LENGTHS

    OPTIONAL INSULATIONBY OTHERS

    MEMBRANE BY OTHERS

    B. Bottom Section10-ft. Lengths

    A. Top Section10-ft. Lengths

    C. End Cap InsertSlides into exposed end of bottom section

    D. #14 X 1½-in. Universal FastenerIncluded and required

    F. EdgeBox SpineRequired for face greater than 6-in.

    E. #14 HD Roofing Fastener Size varies based on height of EdgeBox min. 1-in. penetration required

    A

    B

    H

    OPTIONALINSULATION(BY OTHERS)

    ROOF DECK(BY OTHERS)

    G

    C

    E

    D

    F

    CLOSURE STRIPFASTENERPROVIDED

    NOTES:#1 - Isolate all metal parts from ACQ treated wood or other galvanically incompatible material with appropriate membrane material. #2 - Appliance attachments, such as lightning rods, signs, or antennae that penetrate the water seal, induce a galvanic reaction, or otherwise compromise the effectiveness of the roof edge system, shall be eliminated or isolated to prevent problems per section 8.0 of ANSI/SPRI/FM4435/ES-1. Appliances shall be isolated from or not attached to the roof edge system. Consult the lightning protection system manufacturer for specific attachment instructions.

    ANSI/SPRI/FM4435/ES-1 TESTED

    APPROVALS: Contact manufacturer for verification of test report data on your project.

    OPTIONAL FINISH STRIP (TYPE 2 SHOWN)

    CORRUGATED ROOF DECK BY OTHERSACCESSORY

    HIEGHT

    BOX WIDTHMIN: 3-1/2-IN.MAX: 16-IN.

    SPINES, 1-IN. WIDE, 2-FT. O.C. REQ'D FOR BOX HEIGHT AND/OR BOX WIDTH > 6-IN.

    #14 HD FASTENER PROVIDED @ 15-IN. F.E. AND 45-IN. O.C.

    #14 X 1-1/2-IN. UNIVERSAL FASTENER PROVIDED @ 12-IN. O.C.

    TOP SECTION FORMED IN 10-FT. LENGTHS

    BOTTOM SECTION 10-FT. LENGTHS

    OPTIONAL INSULATION BY OTHERS

    MEMBRANEBOX HEIGHTMIN: 1-1/4-IN.MAX: 16-IN.

    OPTIONAL INSULATION BY OTHERS #14 X 1-1/2-IN. UNIVERSAL FASTENER

    PROVIDED @ 12-IN. O.C.

    #14 X 1-1/2-IN. UNIVERSAL FASTENER PROVIDED @ 24-IN. O.C. WHEN SPINES USED

    PRE-DRILL WITH 3/16-IN. DRILL BIT FOR MASONRY CONDITIONS.CONTACT OMG FOR APPROPRIATE RECOMMENDATIONS NEEDED TO MEET/EXCEED

    ANSI/SPRI/FM4435/ES-1 DESIGN CRITERIA

    ANSI/SPRI/FM4435/ES-1 TEST PRESSURES UP TO 911 PSF (VERTICAL) AND 526 PSF (HORIZONTAL)

  • 4 COMMERCE WAY, ARDEN, NC 28704 USA800.892.9173 828.676.1700 OMGEDGESYSTEMS.COMCopyright © 2020 OMG, Inc. All rights reserved. EM

    1067

    Re

    v. 10

    2120

    20Superior productivity. Superior performance.

    STEP 1: Installing Closure Strip & Finish StripRequired for metal deck only. Place appropriate strips on the edgeof the metal deck. Secure in place with #14 x 1½-in. universalfastener (5 per 10-ft. section). Fastener heads not to interfere withbottom sections.

    FINISHSTRIP

    CLOSURESTRIP

    METAL DECKBY OTHERS

    #14 x 1½" UNIVERSALFASTENER @ 24" O.C.

    FIGURE 1

    STEP 4: Installing End CapsPlace end cap in exposed end of bottom section, secure withprovided #14 x 1½-in. universal fastener (2 per end cap).

    END CAP

    FIGURE 4

    STEP 2: Installing Bottom SectionStarting at the corners, place bottom sections as shown aboveworking from the corners to the center. Secure in place usingprovided #14 x 1½-in. universal fasteners through pre-punchedholes (10 per 10-ft. section). Butt adjacent sections.

    BOTTOMSECTIONS

    #14 X 1½"UNIVERSALFASTENER@ 12" O.C.

    FIGURE 2

    FIGURE 3

    STEP 5: Installing Top SectionStarting at the corners, place top sections as shown in FIGURE 5.Working from the corners to the center, consider lengths of middlepieces prior to cutting to avoid creating relatively short sections (lessthan 5-ft.). Secure top to bottom using # 14 X 1½-in. universalfastener through pre-punched holes in the face (10 per 10-ft.section), and through pre-punched holes in the back (10 per 10-ft.section).Install the #14 HD Roofing Fasteners through the

    required for 10-ft. section. Butt adjacent sections.

    FIGURE 5

    TOPSECTIONS

    FIGURE 6

    #14 HDROOFINGFASTENER,MIN. 3 PER 10'SECTION

    pre-punched holes and into the substrate. Minimum 3 HD fasteners