® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 1 03.06.18
Digital electronic dimming ballasts maximize the benefits of a
lighting management system. EcoSystem Ballasts offer 100% to 10%
dimming; ideal for use where saving energy, increasing flexibility,
and maximizing productivity are the goals of the lighting
design.
Features
•Continuous,flicker-freedimmingfrom100%to10%•Integralsensorconnectionprovidespowerforand
responds to one occupancy sensor, one photo sensor, and one
personal control input (infrared receiver or wallstation)
•CommunicatesstatusandsensorinputsovertheEcoSystemdigitallink
•Programmedrapidstartdesignensuresfullratedlamp life while
dimming and cycling
•Lampsturnontoanydimmedlevelwithoutflashingtofull brightness
•Lowharmonicdistortionthroughouttheentiredimming range
•Frequencyofoperationensuresthatballastdoesnotinterfere with
infrared devices
•End-of-lamp-lifeprotectioncircuitryensuressafeoperation
throughout entire lamp life
•Ultra-quietoperation•Non-volatilememoryrestoresallballastsettingsafter
power
failure•Ballastsmaintainconsistentlightoutputforlinearlamp
lengths (e.g., 4 ft [1.5 m], 3 ft [1 m], 2 ft [0.5 m] have same
relative output)
•Protectedfrommiswiresofanyinputpowertocontrollead, or from lamp
leads to each other and/or ground
•100%performancetestedatfactory•Customballastfactorsavailable.Designtool
and specifications can be found at
www.lutron.com/ballasttool
•BAA-compliant(BuyAmericanAct)modelnumbersavailable.Adda"U"prefixtothemodelnumber
EcoSystem case type G
EcoSystem case type J
EcoSystem Multiple Control Input Ballasts
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 2 03.06.18
Specifications
Regulatory
Approvals•ULRListed(evaluatedtotherequirementsofUL935)•CSAcertified(evaluatedtotherequirementsofC22.2No.74)
•SelectballastsareNOMListed(contactLutronformore
information)
•SMarkCertified•ClassPthermallyprotected•SomemodelsareaffectedbyCaliforniaTitle20regulation.Californiacustomersmayneedtoorderalternativemodelstocomply.SeeCACustomersectionsonfollowingpagesfordetails.Also,seeCECTitle20RegulationAppNote#601(P/N048601)atwww.lutron.com/title20ballasts
for more information
•MeetsANSIC82.11HighFrequencyBallastStandard•ThisdevicecomplieswithPart18(Non-ConsumerLimits)oftheFCCRules.Operationissubjecttothefollowing
conditions:(1)Thisdevicemaycauseinterferencetoradio
equipment.(2)Thisdeviceshouldnotbeinstallednearmaritime
safetycommunicationsequipmentorothercriticalnavigationorcommunicationequipmentoperatingbetween0.45–30MHz.
ModificationnotexpresslyapprovedbyLutronElectronicsCo.,Inc.couldvoidtheusersauthoritytooperatethisequipment.ThisNon-ConsumerRFLDcomplieswiththeCanadianstandardICES-005.
•MeetsANSIC62.41CategoryAsurgeprotectionstandardsuptoandincluding4kV
•ManufacturingfacilitiesemployESDreductionpracticesthatcomplywiththerequirementsofANSI/ESD
S20.20
•LutronQualitySystemsregisteredtoISO 9001:2008
Environment•Minimumlampstartingtemperature:50°F(10°C)•Relativehumidity:lessthan90%non-condensing•SoundRating:ClassA•Maximumballastcasetemperature:167°F(75°C)
Performance•OperatingVoltage:120,220/240,277 V~ at
50or60 Hz
•Grounding:ballastandfixturemustbegroundedforproper dimming
•DimmingRange:100%to10%measuredrelativelightoutput
•LampStarting:programmedrapidstart•LampCurrentCrestFactor:lessthan1.7•LightOutputVariation:Constant±2%lightoutputforlinevoltagevariationsof±10%
•LampLife:Averagelamplifemeetsorexceeds specified lamp
ratings
•PowerFactor:0.95minimum•TotalHarmonicDistortion(THD):Lessthan10%*•MaximumInrushCurrent:3Aperballastat277V~,
7Aperballastat120V~
•Class2Output:+20V-50mAmaximum(onedaylightsensor,onekeypadandoneoccupancysensor
can be connected)
Ballast Wiring &
Mounting•Ballastisgroundedbyamountingscrewtothefixture•Terminalblocksontheballastacceptthefollowing
wire gauges: –PowerWiring,LampWiring,andEcoSystem
digitallink:onlyone16or18AWG(0.75or1.5mm2) solid per
terminal
–Class2Sensors:onlyone22AWG(0.25 mm2) solid per
terminal
•Onlyonewireperterminal•Class2sensorwiringmustbeseparatedfromallpowerandClass1wiring,consultallapplicablelocaland
national codes
•Ballastmountsusingtwoscrews(orsheetmetalfeature and one screw)
within a fluorescent fixture
•Wiringfromtheballasttolampsocketsshouldnotexceed7ft(2m)forT8,T5,andT5HOlamps
•Wiringfromtheballasttolampssocketsshouldnotexceed3ft(1m)forT5TwinTubelamps
Lamp
SeasoningRefertolampmanufacturerforlampseasoningrequirementspriortodimming.
*ModelsEC5T514JUNV1andEC5T817JUNV1havelessthan15%THD
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 3 03.06.18
How to Build a Model Number
Example
E C 5 T 8 3 2 G U N V 2 1 0 L
AB G
HI
CD
E
F
A – Type of Ballast (2 characters)EC=EcoSystemBallast
B – Control Type (1
character)5=5controlinputs:EcoSystemdigitallink,3-wirephasecontrolinput,daylightsensor,
occupancysensor,andpersonalcontrol(IRreceiverorwallstation)
C – Lamp Size (2 characters)T8orT5
D – Lamp Wattage (2
characters)XX=Lampwattage(e.g.54for54Wlamp)
E – Case Type (1 character)GorJ
F – Voltage (3
characters)UNV=Universalvoltage(120 V~,220/240 V~,277 V~)
G – Number of Lamps (1 character)1, 2, or 3
H – Ballast Factor (Blank, 2, or 3
characters)Blank=Default(0.85forT8and1.0forT5)
17=1.17BF
CXX=Customballastfactorof0.XX
I – Optional Power and Lamp Leads (Blank or 1
character)Blank=Noleads
L=Powerandlampleadsincluded(onlyavailableonselectmodelsinGcase)
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 4 03.06.18
How to Build a Model Number (CA Customers only)
Example
E C 5 N S T 8 3 2 C U 2 1 0 R
AB G
HI
CD
E
F
A – Type of Ballast (2 characters)EC=EcoSystemBallast
B – Control Type (3
characters)5NS=EcoSystemdigitallink,3-wirephasecontrolinput,nosensors1
C – Lamp Size (2 characters)T8orT5
D – Lamp Wattage (2
characters)XX=Lampwattage(e.g.54for54Wlamp)
E – Case Type (1 character)C
F – Voltage (1
character)U=Universalvoltage(120 V~,220/240 V~,277 V~)
G – Number of Lamps (1 character)1, 2, or 3
H – Ballast Factor (2 or 3 characters)10=1.0BF
C85=Customballastfactorof0.85
I - Alternative (1 character)R=Replacement
1Forsensorinputs,usewithaC5-BMF-2A
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 5 03.06.18
EcoSystem Ballasts with Integral Sensor Connection for Linear
and U Bend T8 Lamps
Lamp No. ofLamps
Model CaseSize
InputVoltage(V~)
InputCurrent(A)
InputPower(W)
BallastFactor(BF)
SystemLumens(lm)
SystemEfficacy(lm/W)
BallastEfficacyFactor
RelativeEfficacy(RSE)
F32T8(48in [1219mm])
1 EC5T832JUNV11 J 277240120
0.110.130.26
31.631.031.3
0.850.850.85
255025502550
818281
2.692.742.72
0.860.870.87
2 EC5T832GUNV21 G 277240120
0.210.250.49
59.657.658.8
0.850.850.85
510051005100
868987
1.431.481.45
0.910.940.93
EC5T832GUNV2L1 G 277240120
0.210.250.49
59.657.658.8
0.850.850.85
510051005100
868987
1.431.481.45
0.910.940.93
EC5T832JUNV21 J 277240120
0.210.250.49
57.459.059.1
0.850.850.85
510051005100
898686
1.481.441.44
0.950.920.92
3 EC5T832GUNV3L1 G 277240120
0.310.360.72
86.584.085.9
0.850.850.85
765076507650
888989
0.981.010.99
0.940.970.95
EC5T832GUNV317L1 G 277240120
0.410.470.95
105.7106.5106.8
1.171.171.17
10,53010,53010,530
1009999
1.111.101.10
1.061.051.05
F25T8(36in [914mm])
1 EC5T825JUNV1 J 277240120
0.100.110.23
27.627.026.9
0.850.850.85
182818281828
666868
3.083.153.16
0.770.790.79
2 EC5T825JUNV2 J 277240120
0.160.190.38
44.345.645.6
0.850.850.85
366536653665
757575
1.741.731.73
0.870.870.87
F17T8(24 in [610mm])
1 EC5T817JUNV1 J 277240120
0.070.080.16
19.420.019.2
0.850.850.85
119011901190
686070
4.134.254.23
0.700.720.72
2 EC5T817JUNV2 J 277240120
0.130.150.31
36.237.037.0
0.850.850.85
238023802380
666464
2.352.302.30
0.800.780.78
EcoSystem Ballasts for Linear and U Bend T8 Lamps (CA Customers
only)Lamp No. of
LampsModel Case
SizeInputVoltage(V~)
InputCurrent(A)
InputPower(W)
BallastFactor(BF)
SystemLumens(lm)
SystemEfficacy(lm/W)
BallastEfficacyFactor
RelativeEfficacy(RSE)
F32T8(48in [1219mm])
1 EC5NST832CU1C85R2 C 277240120
0.110.130.26
29.530.631.3
0.850.850.85
255025502550
868381
2.882.782.72
0.920.890.87
2 EC5NST832CU2C85R 2 C 277240120
0.220.250.51
61.060.061.2
0.850.850.85
510051005100
848583
1.391.421.39
0.890.910.89
1
NotforsaleinCalifornia-seeCECTitle20RegulationAppNote#601(P/N048601),forinformationonalternativemodels2
Forsensorinputs,usewithaC5-BMF-2A
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 6 03.06.18
EcoSystem Ballasts for Linear and U Bend T8 Lamps: Reduced
Wattage
Lamp No. ofLamps
Model CaseSize
InputVoltage(V~)
InputCurrent(A)
InputPower(W)
BallastFactor(BF)
SystemLumens(lm)
SystemEfficacy(lm/W)
BallastEfficacyFactor
RelativeEfficacy(RSE)
F32T8(48in [1219mm])
1 EC5T8RWJUNV11
30WJ 277
240120
0.110.120.24
28.928.729.2
0.850.850.85
235023502350
818280
2.942.962.91
0.880.890.87
EC5T8RWJUNV11
28W277240120
0.100.110.22
26.326.226.5
0.850.850.85
220222022202
848483
3.233.243.21
0.900.910.90
2 EC5T8RWJUNV21
30WJ 277
240120
0.190.220.44
52.552.553.4
0.850.850.85
470147014701
909088
1.621.621.59
0.970.970.96
EC5T8RWJUNV21
28W277240120
0.180.200.42
48.948.650.0
0.850.850.85
440344034403
909188
1.741.751.70
0.970.980.95
3 EC5T8RWGUNV3L1
30WG 277
240120
0.280.320.65
76.376.378.1
0.850.850.85
705170517051
929290
1.111.111.09
1.001.000.98
EC5T8RWGUNV3L1
28W277240120
0.260.300.60
71.170.471.6
0.850.850.85
660566056605
939492
1.201.211.19
1.001.011.00
Reducedwattagelampsmayexhibitlighttomoderatestriations(movingbandsofbrightanddarkspots)acrossthelampatcertaindimminglevels.Whilestriationsdonotharmthelamporballast,itcanbedistractinginfixtureswherethelampis
directly visible.
1
NotforsaleinCalifornia-seeCECTitle20RegulationAppNote#601(P/N048601),forinformationonalternativemodels
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 7 03.06.18
EcoSystem Ballasts with Integral Sensor Connection for linear T5
Lamps
Lamp No. ofLamps
Model CaseSize
InputVoltage(V~)
InputCurrent(A)
InputPower(W)
BallastFactor(BF)
SystemLumens(lm)
SystemEfficacy(lm/W)
BallastEfficacyFactor
RelativeEfficacy(RSE)
F35T5(57.1in [1450 mm])
1 EC5T535JUNV1 J 277240120
0.150.180.35
42.042.342.2
1.01.01.0
365036503650
878787
2.382.382.38
0.830.830.83
F28T5(45.2 in [1148mm])
1 EC5T528JUNV11 J 277240120
0.120.140.27
32.632.932.9
1.01.01.0
290029002900
898888
3.073.043.04
0.860.850.85
2 EC5T528JUNV21 J 277240120
0.230.270.54
64.565.065.2
1.01.01.0
580058005800
908989
1.551.541.53
0.870.860.86
F21T5(33.4 in [848mm])
1 EC5T521JUNV1 J 277240120
0.090.120.22
25.825.825.8
1.01.01.0
210021002100
818181
3.883.883.88
0.810.810.81
2 EC5T521JUNV2 J 277240120
0.170.200.39
46.047.247.2
1.01.01.0
420042004200
918989
2.172.122.12
0.910.890.89
F14T5(21.6in [549mm])
1 EC5T514JUNV1 J 277240120
0.070.080.16
19.019.219.2
1.01.01.0
135013501350
717070
5.265.215.21
0.740.740.74
2 EC5T514JUNV2 J 277240120
0.120.140.28
32.833.333.3
1.01.01.0
270027002700
828181
3.053.003.00
0.850.850.85
EcoSystem Ballasts for Linear T5 Lamps (CA Customers only)Lamp
No. of
LampsModel Case
SizeInputVoltage(V~)
InputCurrent(A)
InputPower(W)
BallastFactor(BF)
SystemLumens(lm)
SystemEfficacy(lm/W)
BallastEfficacyFactor
RelativeEfficacy(RSE)
F28T5(45.2 in [1148mm])
1 EC5NST528CU110R2 C 277240120
0.120.140.28
33.033.633.6
1.01.01.0
290029002900
888686
3.632.982.98
0.850.830.83
2 EC5NST528CU210R2 C 277240120
0.220.260.52
59.862.462.4
1.01.01.0
580058005800
979393
1.671.601.60
0.940.900.90
1
NotforsaleinCalifornia-seeCECTitle20RegulationAppNote#601(P/N048601),forinformationonalternativemodels2
Forsensorinputs,usewithaC5-BMF-2A
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 8 03.06.18
EcoSystem Ballasts with Integral Sensor Connection for Linear T5
HO Lamps
Lamp No. ofLamps
Model CaseSize
InputVoltage(V~)
InputCurrent(A)
InputPower(W)
BallastFactor(BF)
SystemLumens(lm)
SystemEfficacy(lm/W)
BallastEfficacyFactor
RelativeEfficacy(RSE)
F54T5(45.2 in [1148mm])
1 EC5T554JUNV11 J 277240120
0.210.240.48
56.558.057.9
1.01.01.0
500050005000
888686
1.771.731.73
0.960.930.93
2 EC5T554JUNV21 J 277240120
0.400.520.99
110.1119.0119.3
1.01.01.0
10,00010,00010,000
918484
0.910.840.84
0.980.910.91
F39T5(33.4 in [848mm])
1 EC5T539JUNV1 J 277240120
0.160.180.37
43.344.044.0
1.01.01.0
350035003500
818080
2.312.272.27
0.900.890.89
2 EC5T539JUNV2 J 277240120
0.300.350.70
83.084.084.3
1.01.01.0
700070007000
848383
1.201.191.19
0.940.930.93
F24T5(21.6in [549mm])
1 EC5T524JUNV1 J 277240120
0.110.13 0.24
30.028.828.8
1.01.01.0
200020002000
676969
3.333.473.47
0.800.830.83
2 EC5T524JUNV2 J 277240120
0.200.230.45
54.854.053.9
1.01.01.0
400040004000
737474
1.821.851.86
0.890.890.89
EcoSystem Ballasts for Linear T5 HO Lamps (CA Customers
only)Lamp No. of
LampsModel Case
SizeInputVoltage(V~)
InputCurrent(A)
InputPower(W)
BallastFactor(BF)
SystemLumens(lm)
SystemEfficacy(lm/W)
BallastEfficacyFactor
RelativeEfficacy(RSE)
F54T5(45.2 in [1148mm])
1 EC5NST554CU110R2 C 277240120
0.230.260.54
63.762.464.8
1.01.01.0
500050005000
788077
1.571.601.54
0.850.870.83
2 EC5NST554CU210R2 C 277240120
0.430.501.02
119.1120.0122.4
1.01.01.0
10,00010,00010,000
848382
0.840.830.82
0.910.900.88
1
NotforsaleinCalifornia-seeCECTitle20RegulationAppNote#601(P/N048601),forinformationonalternativemodels2
Forsensorinputs,usewithaC5-BMF-2A
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 9 03.06.18
*
Pleaseconsultlampmanufacturersspectodeterminedimmabilityofthereducedwattagelamp.
EcoSystem Ballasts with Integral Sensor Connection for T5 Twin
Tube Lamps
Lamp No. ofLamps
Model CaseSize
InputVoltage(V~)
InputCurrent(A)
InputPower(W)
BallastFactor(BF)
SystemLumens(lm)
SystemEfficacy(lm/W)
BallastEfficacyFactor
RelativeEfficacy(RSE)
FT55(20.7in [526mm])
1 EC5T555JUNV1 J 277240120
0.200.230.46
55.455.255.2
0.90.90.9
432043204320
707070
1.621.631.63
0.890.900.90
2 EC5T555JUNV2 J 277240120
0.400.460.92
110.8110.4110.4
0.90.90.9
864086408640
787878
0.810.820.82
0.990.900.90
FT50(22.5 in [572mm])
1 EC5T550JUNV1 J 277240120
0.200.230.45
55.454.054.0
1.01.01.0
400040004000
727274
1.811.851.85
0.900.930.93
2 EC5T550JUNV2 J 277240120
0.360.420.84
99.7100.8100.8
1.01.01.0
800080008000
807979
1.000.990.99
1.000.990.99
FT40(22.5 in [572mm])
1 EC5T540JUNV1 J 277240120
0.160.180.36
44.343.243.2
1.01.01.0
310031003100
707272
2.262.312.31
0.900.930.93
2 EC5T540JUNV2 J 277240120
0.270.320.64
74.876.876.8
1.01.01.0
620062006200
838181
1.341.301.30
1.071.041.04
3 EC5T540GUNV3L G 277240120
0.400.470.95
111.3112.4113.2
1.01.01.0
930093009300
848382
0.900.890.88
1.081.071.06
FT39FT36(15.5 in [394mm])
1 EC5T536JUNV1 J 277240120
0.140.170.33
38.839.639.6
1.01.01.0
285028502850
747272
2.572.532.53
0.930.910.91
2 EC5T536JUNV2 J 277240120
0.260.310.61
72.073.273.2
1.01.01.0
570057005700
797878
1.391.371.37
1.000.980.98
FT25*(22.5 in [572mm])
1 EC5T540RWJUNV1 J 277240120
0.120.140.28
34.334.534.1
1.01.01.0
260026002600
767576
2.912.892.93
0.730.720.73
2 EC5T540RWJUNV2 J 277240120
0.210.250.49
59.361.059.3
1.01.01.0
520052005200
888588
1.681.641.68
0.840.820.84
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 10 03.06.18
G Case Dimensions
A=9.5 in(241 mm)
B=8.9 in(226 mm)
C=7.1 in(180 mm)
D=1.0 in(25 mm)
E=2.38 in(60 mm)
G Case
EcoSystem Ballast Case Dimensions
Gcaseballastswithleadsshipwith36 in(914 mm)leadsforlampconnectionsand18 in(457 mm)leadsforLine/Hot,Neutral,E1andE2connections
J Case / C Case
ABC D
E
AB
C D
E
F
J Case / C Case Dimensions
A=18.0 in(457 mm)
B=17.68 in(449 mm)
C=6.82 in(173 mm)-JCaseonly
D=0.394 in(10 mm)-JCaseonly
E=1.0 in(25 mm)
F=1.18 in(30 mm)
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 11 03.06.18
EcoSystem Ballast Wiring Diagrams — T8, T5, T5 HO
Wiring to One Lamp (J case shown)
Wiring to Two Lamps (G case shown)
Blue
Red
Yellow
Wiring to Three Lamps (G case shown)
Blue
Red
Yellow
Striped
NOTICE
•Maximumballasttolampsocketleadlengthis7ft(2m)•Wirecolorsshownarelabeledontheballast,butmayvarydependinguponfixtureconstruction
Wiring to Two Lamps (J case shown)
Blue
Red
Yellow
Blue
Red
BLU
BLU
RED
RED
BLU
BLU
RED
RED
YEL
YEL
BLUBLU
REDRED
YEL
N/C
YEL
N/C
BLUBLU
REDRED
YEL
B/W
YEL
B/W
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 12 03.06.18
EcoSystem Ballast Wiring Diagrams — T5 Twin-Tube
Wiring to One Lamp
Wiring to Two Lamps
NOTICE
•Maximumballasttolampsocketleadlengthis3 ft(1 m)•Wirecolorsshownarelabeledontheballast,butmayvarydependinguponfixtureconstruction
EcoSystem Ballast Wiring: Power Wiring for EcoSystem Digital
Link
1 Ballast is grounded via the case2
WirecolorsshownareforLutroncontrolsandballastsonly.Dimmingcontrolwiresmaynotmatchballastwirecolors3
TheHotmustnotbewiredtoaswitchingdeviceorsystemfunctionalitywillbelost
NEU
DH
HOT
LINE
Class 2 Bus
E1
E2
EcoSystem Ballast
Ground1
Neutral
Line/Hot 2,3
E1
E2
Blue
Red
Yellow
Blue
Red
BLU
BLU
RED
RED
BLU
BLU
RED
RED
YEL
YEL
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 13 03.06.18
To the EcoSystem digital link & up to 64 total ballasts,
drivers, or modules
EcoSystem Ballast Wiring: EcoSystem Digital LinkEcoSystem
Digital Link Overview
•TheEcoSystemdigitallinkwiring(E1andE2)connects the ballasts
together to form a lighting control system
•EachEcoSystemdigitallinksupportsupto64digitalballasts,64occupantsensors,16daylightsensors,and64wallstationsorIRreceivers
•E1andE2(EcoSystemdigitallinkwires)arepolarity insensitive and
can be wired in any topology
•AnEcoSystemEnergiSavrNodedevice,
GRAFIKEyeQSwithEcoSystemconnection,orQuantumsystemprovidespowerfortheEcoSystemdigitallinkandsupportssystemprogramming
•AllEcoSystemdigitallinkprogrammingiscompletedbyusingtheEcoSystemProgrammer,
GRAFIKEyeQSwithEcoSystemconnection,orQuantumsystem
EcoSystem Digital Link Wiring
•DriverEcoSystemdigitallinkterminalsonlyaccept
onesolidwireperterminalfrom18AWGto16AWG (0.75mm2 to 1.5 mm2)
•Makesurethatthesupplybreakertotheballastand
EcoSystemdigitallinksupplyisOFFwhenwiring
•Connectthetwoconductorstothetwodriverterminals E1 and E2
•UsingtwodifferentcolorsforE1andE2willreduceconfusion when
wiring several ballasts together
•TheEcoSystemdigitallinkmaybewiredClass1orClass2.Consultapplicableelectricalcodesforproperwiring
practices
Notes
•TheEcoSystemdigitallinksupplydoesnothave
tobelocatedattheendofthedigitallink
•E1andE2wiresarenotpolaritysensitive
•EcoSystemdigitallinklengthislimitedbythewiregauge used for E1
and E2 as follows:
Wire Gauge Digital Link Length (max)
12 AWG 2200 ft
14 AWG 1400 ft
16 AWG 900 ft
18 AWG 550 ft
Wire Size Digital Link Length (max)
4.0 mm2 828 m
2.5 mm2 517 m
1.5 mm2 310 m
1.0 mm2 207 m
0.75 mm2 155 m
BallastTerminals
BallastTerminals
NEUDH
HOT
LINE
Class 2 BusE1
E2
NEUDH
HOT
LINE
Class 2 BusE1
E2
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 14 03.06.18
EcoSystem Ballast Wiring: Class 2 SensorsElectrical Contractors
and Engineers:
•AlwaysfollowapplicablenationalandlocalelectricalcoderequirementswhenconnectingcircuitstoEcoSystem
devices
•AllfieldinstalledClass2wiringmustbeseparatedfromlinevoltagewiringbyatleast0.25in(6.4mm)
•SomelocalelectricalcodesrequireClass2wiringtobe separately
routed in a metal conduit
•BallastClass2Sensorterminalsonlyaccept 22AWG(0.25 mm2)
solid conductors; all other terminalsaccept18AWGto16AWG(0.75mm2 to
1.5 mm2) solid conductors
Lutron Requires:
•KeepClass1andClass2wiringseparate
•Whereseparationisnotpossible,usea600Vinsulatedcablewithaninternalshield.Connecttheshield
to ground to provide better noise immunity for low voltage
circuits
•RefertoApplicationNote#142foradditionalinformationonEcoSystemdigitallinkClass1andClass2wiring
Fixture Manufacturers:
•ULR15986.17.1allows:
Factoryinstalledpowerlimitedwiringandbranchcircuit wiring that come
in random contact within the luminaire shall have insulation rated
for the maximum voltage that exists in any of the circuits.
(EcoSystem ballastcircuitsrequireminimum600Vinsulatedwire)
•ULR15986.17.2.1requires:
Luminairesdesignedforthefieldinstallationofpower limited circuits
shall be provided with a means
ofsegregatingorseparatingthefield-installedpowerlimited circuit
wiring from the branch circuit wiring
withintheluminaire(seeULR15986.17fordetails)
Lutron Requires:
•KeepClass1andClass2wiringseparate
•Whereseparationisnotpossible,usea600Vinsulatedcablewithaninternalshield.Connecttheshield
to ground to provide better noise immunity for low voltage
circuits
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 15 03.06.18
EcoSystem Ballast Wiring: Daylight SensorWiring to a Daylight
Sensor
•Sensorwiringsummary:
Sensor Wire Ballast Terminal Terminal ColorRed +20V- Red
Black Common Black
White IR White
Yellow Daylight Yellow
•MakesurethatthesupplybreakertotheDigital
BallastisOFFwhenwiring
•ConnectthefourconductorstothefourDigital Ballast terminals as
shown
•Themaximumwirelengthfromtheballasttothesensor is 50 ft (15
m)
•BallastClass2terminalsonlyacceptone 22AWG(0.25 mm2) solid
wire
Notes
•Consultthedaylightsensorspecificationsheettoproperly position
the sensor
•Donotplacethesensorabovependantfixtures,directlybelowlightingfixtures,orwithinskylightwells
•Whenwiringbothawallstationanddaylightsensortooneballast,onlyconnecttheIRwire(white)
fromthekeypad.Capoffthewhitewirefromthedaylight sensor
•AllsensorandwallstationwiringisClass2.Followallapplicable
national and local codes for proper circuit separation and
protection
G Case Terminals
J Case Terminals
Daylight Sensor 22AWG(0.25 mm2) solid only
22AWG(0.25 mm2) solid onlyDaylight Sensor
NEUDHSH
LINE
+20V
Common
IROcc
Daylight
Class 2 (22 AWG Solid)
Class 2 BusE1
E2
+20
VCo
mm
onIR Occ
Day
light
Class 2 (22 AWG Solid)
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 16 03.06.18
EcoSystem Ballast Wiring: Occupancy Sensor
Wiring to a Lutron Occupancy Sensor
(LOS-XX)•Sensorwiringsummary:
Sensor Wire Ballast Terminal Terminal ColorRed +20V- Red
Black Common Black
Blue Occ Blue
•MakesurethatthesupplybreakertotheDigital
BallastisOFFwhenwiring
•Connectthethreeconductorstothethreeballastterminals as
shown
•Themaximumwirelengthfromtheballasttothesensor is 50 ft (15
m)
•BallastClass2terminalsonlyacceptone 22AWG(0.25 mm2) solid
wire
Notes
•Occupancysensorsfromothermanufacturersmaybeused with EcoSystem
ballasts if the sensor meets the following criteria:
Vin=+20V-currentdrawlessthan35mA
•Ifothermanufacturer’soccupantsensorsareusedterminal colors and
sensor wire colors may not match
•AllsensorandwallstationwiringisClass2.Followallapplicable
national and local codes for proper circuit separation and
protection
J Case Terminals
22AWG(0.25 mm2) solid only
OccupancySensor 22AWG(0.25 mm2) solid only
G Case Terminals
OccupancySensor
NEUDHSH
LINE
+20V
Common
IROcc
Daylight
Class 2 (22 AWG Solid)
Class 2 BusE1
E2
+20
VCo
mm
onIR Occ
Day
light
Class 2 (22 AWG Solid)
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 17 03.06.18
Wiring to an IR Receiver and Wallstation
•Wiringsummary:
Sensor Wire Ballast Terminal Terminal ColorRed +20V- Red
Black Common Black
White IR White
•MakesurethatthesupplybreakertotheDigital
BallastisOFFwhenwiring
•ConnectthethreeconductorstothethreeDigital Ballast terminals as
shown
•Themaximumwirelengthfromtheballasttothesensor is 50 ft (15
m)
•BallastClass2terminalsonlyacceptone 22AWG(0.25 mm2) solid
wire
Notes
•OnlyonewallstationorIRreceivercanbewiredtoadigital ballast
•Ifadaylightsensorandwallstation/IRreceiverareconnected to one
ballast, do not connect the daylightsensor’sIRoutput
•AllsensorandwallstationwiringisClass2.Followallapplicable
national and local codes for proper circuit separation and
protection
22AWG(0.25 mm2) solid only
G Case Terminals
IRReceiver
J Case Terminals
22AWG(0.25 mm2) solid only
IRReceiver
Wallstation
WirestoDigitalBallast
NEUDHSH
LINE
+20V
Common
IROcc
Daylight
Class 2 (22 AWG Solid)
Class 2 BusE1
E2
+20
VCo
mm
onIR Occ
Day
light
Class 2 (22 AWG Solid)
EcoSystem Ballast Wiring: IR Receiver and Wallstation
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 18 03.06.18
EcoSystem Ballast Wiring: Multiple DevicesMultiple Sensors with
One Ballast
•EcoSystemballastsacceptwiringforonedaylight
sensorinput,oneoccupantsensorinputandoneIRinput(wallstationorIRreceiver)
•EcoSystemdaylightsensorshaveIRoutputsthat allow the device to
operate as a programming port.
Inapplicationswhereadaylightsensorand wallstation are wired to the
same ballast, do not connect the white wire of the daylight sensor
to theballast.Thewallstationoperatesasthe
programmingportthroughitsintegralIRreceiver
•Usethechartbelowasaguideforwiringmultipledevices to a
ballast
How to Use the Chart
Connectasensortoaballastfromthe“Devices”column(inbold).Alongtheselecteddevicerow,are“Y’s”and“N’s”.Wherea“Y”isplaced,thedevice
at the top of that column can also be connected to the same
ballast.An“N”indicatesnoconnectionallowed.
Devices Daylight Sensor (with IR)
Occupant Sensor
Wallstation or
IR receiver
Daylight Sensor (no IR)
Daylight Sensor(with IR) Y N N
OccupantSensor Y Y Y
Wallstation orIR Receiver N Y Y
Daylight sensor(no IR) N Y Y
Example: When a Daylight Sensor with IR is connected to a
ballast, then only an occupancy sensor can be added for the system
to properly function.
J Case Terminals
+20
VCo
mm
onIR Occ
Day
light
Class 2 (22 AWG Solid)
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 19 03.06.18
EcoSystem Ballast Wiring: Line Voltage DimmersEcoSystem Ballasts
and 3-wire dimmers
•Lutron3-wiredimmersonlycontroltheballasttheyare wired to;
EcoSystem ballasts do not support groupingof3-wirecontrolinput
3-Wire Control Wiring
•MakesurethatthesupplybreakertotheDigital
BallastisOFFwhenwiring
•Wireasshown
Line input Connects toHot DimmerBlackWire
Neutral DimmerWhiteWire
Dimmer wire Connects toYellow BallastOrange(DH)
Red BallastBlack(HOT)
White BallastWhite(NEU)
Green EarthGround
•EcoSystemballastlinevoltageand3-wireinput
terminalsonlyacceptone18to16AWG (0.75to1.5mm2) solid wire
Emergency and 3-wire
•EcoSystemballastscontrolledbyawallboxdimmershould not be used
for emergency/egress lighting unless an external emergency ballast
is used in the fixture.SeeLutronApplicationNote#50at
www.lutron.com
•EcoSystemballastsmaybeusedforemergency/egresslightingwhencontrolledbyaLutrondimmingpanel(GP);wherethepanelisadedicated
emergency panel
Notice
3-Wirecontrolturnsoffdigitalballastswhenthecontrolisintheoffposition.Thedigitalballastinputs(daylight
sensor, wallstation, occupant sensor, and
IRreceiver)willnotfunctionwhenthedigitalballastis turned off.
LUTRON
3-WireDimmer Green
Ground
Red
Yellow
White
Neutral
Line/Hot
White
Orang
e
Black
NEUDH
HOT
LINE
Class 2 Bus
E1E2
LINE
Class 2 BusE1
E2
NEUDH
HOT
-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem Five Control Input Digital Dimming Ballasts
369454m 20 03.06.18
ATTENTION ELECTRICIANS AND CONTRACTORSBallast/Socket Leads
Leadlengthsfromballasttosocketmustnotexceed7ft(2m)forlinearlamps(T5,T5HO,T8).Leadlengthsmustnotexceed3ft(1m)forT5twintubelamps.
Lamp Sockets
LampsocketsasperIEC 60400arerequiredtoensurepositivelamp-pintosocketcontact.
Lamp Mounting
Manyfluorescentlampsocketsareavailablewithmounting slots to vary
the height of the lamp away
fromthegroundedmetalsurface.Havingafluorescent lamp too close to
the grounded metal will
reducelamplife.Havingafluorescentlamptoofarawayfromthegroundedmetalwillmakethelampflickerornotturnonatall.Pleasenotethatallofthelamp
heights are measured between the grounded metal surface and the
glass wall of the lamp.
Mounting for T8 Lamps
Mountlamps1/8to3/4in(3.2to19mm)awayfromthe grounded metal
surface.
Mounting for T5 and T5HO Lamps
Mountlamps1/16into3/8in(1.6mmto9.5mm)away from the grounded
metal surface.
Mounting for T5 Twin Tube Lamps
Mountlamps1/16into1/2in(1.6mmto13mm)awayfrom the grounded metal
surface.
Ballast Operating Temperature
Ballastcasetemperaturemustnotexceed167°F
(75°C)atanypointonballast.
Cold Air Flow
Ensurethatnocoldair(fromHVACsystem,etc)isblowingacrossthelamps.CoolingthelampwillcauseperformanceissuesasnotedinNEMALSD-34.
ATTENTION FACILITIES MANAGERS
Lamp Seasoning Requirements
Some fluorescent lamp manufacturers recommend that new
fluorescent lamps be operated at full output
(“seasoned”)beforetheycanbedimmed, to render lamp impurities inert,
ensuring proper dimming performance and average rated lamp life.
Pleasecontactyourlampmanufacturerforseasoningrequirements.
SERVICE
Replacement Parts
UsereplacementpartswithexactLutronmodelnumbers.ConsultLutronifyouhaveanyquestions.
Further Information
Forfurtherinformation,pleasevisitusat
www.lutron.com/ballastsorcontactLutron
CustomerAssistanceat1.844.LUTRON1
IMPORTANT: Lamps must never touch ground plane and should be
placed without obstruction.
Lamp Lamp Socket(side view)Mounting height
Grounded metalBallast
LutronandGRAFIKEyeQSaretrademarksLutronElectronicsCo.,Inc.registeredintheU.S.andothercountries.EnergiSavrNodeisatrademarkofLutronElectronicsCo.,Inc.ULisatrademarkofULLLC.
pdfformfields_file_11pages.pdfpdfformfields_file_11pages.pdf