ECL-PTU Series LonMark ® Certified Powered Terminal Unit Programmable Controllers Overview The ECL-PTU Series controllers are microprocessor-based programmable controllers designed to control powered terminal units such as powered fan coil units, heat pumps units, and chilled beams. Each controller uses the LonTalk ® communication protocol and is LONMARK certified as an SCC Fan Coil Controller. These controllers are optimized for ultra-low power consumption and can be operated as stand-alone units or as part of a networked system to suit any installation requirement Applications These controllers meet the requirements of the following applications: £ Fan Coil Units £ Heat Pumps £ Chilled Beams £ Reversible Ceiling with 6-way valves £ Lighting fixtures and shade / sunblind motors when associated to ECx-Light/Blind Series expansion modules Features & Benefits Preloaded Applications Factory preloaded applications allow these controllers, straight out of the box, to operate standard PTU equipment with a proven energy- efficient sequence of operation thereby eliminating the need for programming. The preloaded application can be selected using an Allure EC-Smart-Vue sensor even before the network has been installed for rapid deployment or through the EC-Net™ solution using Distech Controls’ dcgfxApplications. Datasheet
16

ECL-PTU Series DS 15 EN

Oct 17, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: ECL-PTU Series DS 15 EN

ECL-PTU SeriesLonMark® Certified Powered Terminal Unit Programmable Controllers

OverviewThe ECL-PTU Series controllers aremicroprocessor-based programmablecontrollers designed to control powered terminalunits such as powered fan coil units, heatpumps units, and chilled beams.Each controller uses the LonTalk®

communication protocol and is LONMARK certifiedas an SCC Fan Coil Controller.These controllers are optimized for ultra-lowpower consumption and can be operated asstand-alone units or as part of a networkedsystem to suit any installation requirement

ApplicationsThese controllers meet the requirements of thefollowing applications:£ Fan Coil Units£ Heat Pumps£ Chilled Beams£ Reversible Ceiling with 6-way valves£ Lighting fixtures and shade / sunblind

motors when associated to ECx-Light/BlindSeries expansion modules

Features & BenefitsPreloaded ApplicationsFactory preloaded applications allow thesecontrollers, straight out of the box, to operatestandard PTU equipment with a proven energy-efficient sequence of operation therebyeliminating the need for programming.The preloaded application can be selected usingan Allure EC-Smart-Vue sensor even before thenetwork has been installed for rapid deploymentor through the EC-Net™ solution using DistechControls’ dcgfxApplications.

D a t a s h e e t

Page 2: ECL-PTU Series DS 15 EN

2 / 16 ECL-PTU Series

ProgrammabilitySupports Distech Controls’ EC-gfxProgram,which makes Building Automation System(BAS) programming effortless, by allowing youto visually assemble building blocks to create acustom control sequence for any HVAC ,lighting, or building automation application.

Dedicated Inputs & OutputsEach controller has specific IOs to fulfill any typeof installation:£ Universal inputs for using your preferred or

engineer-specified sensors.£ Sensor inputs to ensure optimal temperature

measurement processing.£ Digital inputs to accelerate the integration of

binary inputs such as window contacts.£ Powered Triac outputs for direct connection

of valves and actuators.£ Powered relay outputs for direct connection

of ventilator fans.£ Relay contact outputs for controlling

externally powered devices such as electricheater, fans, ...

£ Analog outputs to provide control signals forexternal peripherals.

£ Digital / Analog outputs for enhancedflexibility

Depending on the installation configuration andcontrolled equipment (valves, fans…), thesuitable model will allow for simplifiedinstallation and wiring, and eliminate the needfor additional external power supply.

Increased Energy EfficiencyImproves energy efficiency when combinedwith:£ Motion detectors to automatically adjust a

zone’s occupancy mode from standby tooccupied when presence is detected

£ CO2 sensors as part of a demand-controlledventilation strategy that adjusts the amountof fresh air intake according to the numberof building occupants

£ Light switches to control both lighting and aroom’s HVAC occupancy / standby modesetting

Smart Room Control SupportThe Smart Room Control solution is an end-to-end system for the control of HVAC equipment,lighting, and shades/sunblinds, achieving thehighest levels of comfort for occupants whilecutting costs from installation time and wiring/material requirements to energy consumption.This solution combines:£ Lighting and shade/sunblind expansion

modules to control lights (DALI, on/off ordimming) and shades/sunblinds (24 VDC or100-240 VAC, up/down and angle rotation).

£ Multi-sensor combining motion andluminosity (Lux) sensors and equipped withan Infrared receiver that works with aconvenient remote control.

£ Wireless (infrared) personal remote controlfor increased occupant comfort.

£ Allure™ Series Communicating Sensors forincreased occupant comfort settings.

Open-to-Wireless™ Solution

The controllers are Open-to-Wireless™ ready,and when paired with the Wireless Receiver,work with a variety of wireless battery-lesssensors and switches, to reduce the cost ofinstallation and minimize the impact on existingpartition walls. For supported frequencies inyour area, refer to the Open-to-WirelessSolution Guide.Available with an optional Wireless Receiverthat supports up to 24 wireless inputs to createwire-free installations.

Allure™ Series Communicating Sensor SupportThese controllers work with a wide range ofsensors, such as the Allure SeriesCommunicating Sensors that are designed toprovide intelligent sensing and control devicesfor increased user experience and energyefficiency.£ Allure EC-Smart-Vue sensors feature a

backlit-display and graphical menus thatprovide precise environmental zone control,with any combination of the following:temperature, humidity, CO2, and motionsensor.

Page 3: ECL-PTU Series DS 15 EN

ECL-PTU Series 3 / 16

£ Allure EC-Smart-Comfort sensors featurecolored LED indicators to provide userfeedback, rotary knobs to adjust the setpointoffset and fan speed, and an occupancyoverride push button. This sensor can alsobe expanded with a combination of up to 4add-on push button modules for lighting andshade/ sunblind control.

£ Allure EC-Smart-Air sensors combineprecise environmental sensing in a discreetand alluring enclosure for temperature,humidity, and CO2.

Supported Platforms

The EC-NetAX multi-protocol integration solutionis web-enabled and powered by the NiagaraAX

Framework, establishing a fully Internet-enabled, distributed architecture for real -timeaccess, automation and control of devices. TheEC- NetAX open framework solution creates acommon development and managementenvironment for integration of LONWORKS®,BACnet ® and other protocols. Regardless ofmanufacturer and protocol, the EC-NetAX systemprovides a unified modeling of diverse systemsand data, providing one common platform fordevelopment, management and enterpriseapplications.

LONWORKS Network Services

The LNS® client-server platform allows multipleusers, running different LNS-compatibleapplications, to access a common source fordirectory, installation, management, monitoringand control services for the network systembeing managed. Distech Controls’ Lonwatcher isan example of a LNS-based networkmanagement tool that can use Plug-Ins toconfigure and monitor controllers and devices inthe control system.

No External TransformerControllers in this series feature a 100-240 VACuniversal power supply input that allows fordirect connection to the mains and do notrequire external transformers, for improvedreliability and reduced installation costs.Some models have a 24 VAC power supplyoutput that can be used to power analogdampers and valve actuators therebyeliminating the need for a transformer.The ECx-Blind-4LV models have an embeddedpower supply that can eliminate the need for anexternal power supply to power the controlleddevice.

Ultra-low Power ConsumptionCareful attention was paid to the design of thesecontrollers as well as to the selection of theircomponents for optimal energy management.This provides ultra-low energy consumptionwhile providing high-level control performance.

Reduced Installation Time & CostOptional strain relief and terminal block coversprovide enhanced electrical protection that canreduce installation costs by eliminating the needfor a protective enclosure (when allowed bylocal regulations).Moreover, powered digital outputs allow fordirect connection of controlled loads to saveinstallation time and wiring costs.

eu.bac Certified Control Efficiency(pending)The eu.bac certification schemes guaranteesthe highest level of performance of the productsand systems, as defined in the EU-Directivesand relevant EN standards. This allows buildingowners to ensure that their building keepsperforming as well, or better than when it wasfirst commissioned.

Page 4: ECL-PTU Series DS 15 EN

4 / 16 ECL-PTU Series

Model Selection

Model ECL-PTU-107

ECL-PTU-207

ECL-PTU-208

ECL-PTU-307

ECL-PTU-308

Points 12 16 14 17 16Universal Inputs 2 2 2 2 2Digital Outputs 3 3 3 2 3Sensor Inputs(NTC 10 kΩ Type II, III)

1 1 1 2 1

Wireless inputs1 24 24 24 24 24Relay Contact Outputs(typ. Electric Heater) 1 x 2 kW 1 x 2 kW 1 x 2 kW 2 x 1 kW 1 x 2 kW

Powered Relay Outputs(typ. Fan Speeds) 3 3 3 3 3

Line-Powered TriacOutputs (typ. Valves) 2 2 0 4 0

24 VAC Triac Outputs(typ. Valves)2 0 0 2 0 4

Analog Outputs 0 4 2 2 224 VAC Power SupplyOutputsSupply Voltage Input 100-240VAC 100-240VAC 100-240VAC 100-240VAC 100-240VACCompatible with Optional Subnet Devices:Allure™ SeriesCommunicating Sensors2

Up to 43,4 Up to 43,4 Up to 43,4 Up to 43,4 Up to 43,4

EC-Multi-Sensor series Up to 44 Up to 44 Up to 44 Up to 44 Up to 44

ECx-Light-4 / ECx-Light-4D / 2 2 2 2 2

ECx-Blind-4 / ECx-Blind-4LV 2 2 2 2 21. All controllers are Open-to-Wireless ready. Available when an optional Wireless Receiver is connected to the controller. Some wireless sensors may use more

than one wireless input from the controller.2. Can be used to power certain types of valves and air dampers, thereby eliminating the need for a transformer.3. A controller can support a maximum of two Allure Series Communicating Sensor models equipped with a CO2 sensor. The remaining connected Allure Series

Communicating Sensor models must be without a CO2sensor.4. A controller can support four sensors among Allure EC-Smart-Vue and EC-Multi-Sensor.

Page 5: ECL-PTU Series DS 15 EN

ECL-PTU Series 5 / 16

Terminal SelectionInput Terminal SelectionModel ECB-PTU-107 ECB-PTU-207 ECB-PTU-208 ECB-PTU-307 ECB-PTU-308Universal Inputs(UI)1

UI1UI2

UI1UI2

UI1UI2

UI1UI2

UI1UI2

Sensor Inputs (SI) 1 SI3 SI3 SI3 SI3SI4 SI3

Digital Inputs (DI) 1DI4DI5DI6

DI4DI5DI6

DI4DI5DI6

DI5DI6

DI4DI5DI6

Power Supply1 Vref Vref Vref Vref VrefUI = Universal Input

SI = Sensor Input

DI = Digital Input

Output Terminal SelectionModel ECB-PTU-107 ECB-PTU-207 ECB-PTU-208 ECB-PTU-307 ECB-PTU-308

Triac Outputs DO5DO6

DO5DO6

DO51

DO61

DO5DO6DO9

DO10

DO51

DO61

DO91

DO101

Powered RelayOutputs

DO1DO2DO3

DO1DO2DO3

DO1DO2DO3

DO1DO2DO3

DO1DO2DO3

Digital RelayContact Outputs

DO4C4

DO4C4

DO4C4

DO4C4

DO11C11

DO4C4

Analog Outputs1

AO7AO8AO9

AO10

AO7AO8

AO7AO8

AO7AO8

24 VAC Outputs1 24V~ 24V~DO = Digital Output

AO = Analog Output

C = Contact1. SELV (Safety Extra Low Voltage) inputs/outputs.

Page 6: ECL-PTU Series DS 15 EN

6 / 16 ECL-PTU Series

Recommended ApplicationsModel ECB-

PTU-107ECB-

PTU-207ECB-

PTU-208ECB-

PTU-307ECB-

PTU-308Fan Coil Unit:£ 2/4 pipes - 3 speed fan - On/Off / thermal

valves£ 2/4 pipes - Variable / 3-speed fan - On/off /

thermal valves£ 2/4 pipes - Variable / 3-speed fan - Analog

actuator£ 2 pipes - Variable / 3-speed fan - Floating

actuator£ 4 pipes - Variable / 3-speed fan - Floating

actuator£ Two Room: 2/4 pipes - Variable speed fan -

On/Off / thermal valvesHeat Pump Unit:£ 3-speed fan£ Variable speed fanChilled Beam:£ On/Off / thermal valves£ 2 pipes - Floating actuator£ 4 pipes - Floating actuator£ Two Room: 2/4 pipes - On/Off / thermal /

analog valvesReversible Ceiling with 6-way valvesUnit Ventilator

Page 7: ECL-PTU Series DS 15 EN

ECL-PTU Series 7 / 16

Objects ListModel ECL-

PTU-107ECL-

PTU-207ECL-

PTU-208ECL-

PTU-307ECL-

PTU-308Calendar Objects 1 1 1 1 1£ Events per calendar 25 25 25 25 25Schedule Objects 2 2 2 2 2£ Special events per schedule 5 5 5 5 5Lamp Actuator Objects 8 8 8 8 8Sunblind Actuator Objects 8 8 8 8 8PID Loop Objects 8 8 8 8 8Constants:£ Boolean 124 124 124 124 124£ Enumeration 62 62 62 62 62£ Numeric 56 56 56 56 56Variables:£ Boolean 124 124 124 124 124£ Enumeration 54 54 54 54 54£ Numeric 56 56 56 56 56nciSetpointTotal Network Variables 236 244 240 246 244Network Variable Input (General Usage):£ NVI Changeable Type, Up to 31

Bytes 50 50 50 50 50

Network Variable Output (General Usage):£ NVO Changeable Type, Up to 31

Bytes 50 50 50 50 50

Hardware Input Network Variable:£ nvoHwInput per Hardware InputHardware Output Network Variable:£ nviHwInput per Hardware Output£ nvoHwInput per Hardware Output

Page 8: ECL-PTU Series DS 15 EN

8 / 16 ECL-PTU Series

Functional Profile

Node

Object Type #0

Device Major Version (SCPTdevMajVer)Device Minor Version (SCPTdevMinVer)

Location (SCPTlocation)

Mandatory Network Variables

Optional Configuration Properties

Manufacturer Configuration Properties

Firmware Version(UCPTfirmwareVersion)UCPTvendorId

UCPTvendorName

nviRequestSNVT_obj_request

nvoStatusSNVT_obj_status

Optional Network Variables

nviFileReqSNVT_file_req

nvoFileStatSNVT_file_status

nviFilePosSNVT_file_pos

Real Time Keeper

Object Type #3300

nvoTimeDateSNVT_time_stamp

Mandatory Network Variables

Optional Configuration Properties

Manufacturer Configuration Properties

Daylight Saving Time (UCPTdst)

nviTimeSetSNVT_time_stamp

Optional Network Variables

nvoTimeDate Configuration Properties:MaximumSend Time(SCPTMaxSendTime)MinimumSend Time(SCPTMinSendTime)

Real Time Keeper Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)

)

Calendar

Object Type #20030

Manufacturer Network Variables

Optional Configuration Properties

nvoCalendar Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)Default Output Value (SCPTdefOutput)

Manufacturer Configuration Properties:

1 x

nvoCalendar_1SNVT_tod_event(changeable type)

Object Major Version (SCPTobjMajVerObject Minor Version (SCPTobjMinVer)

Scheduler

Object Type #20020

Manufacturer Network Variables

Optional Configuration Properties

nviSchedule Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumReceive Time (SCPTmaxRcvTime)

nvoSchedule Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)Default Output Value (SCPTdefOutput)

Scheduler Object Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)

2 x

nvoSchedule_# (# = 1 to 2)SNVT_tod_event(changeable type)

nviSchedule_# (#= 1 to2)SNVT_tod_event(changeable type)

Hardware Input

Open-Loop Sensor Object Type #1

Mandatory Network Variables

Optional Configuration Properties

6 x

nvoHwInput Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)Send Delta (SCPTsndDelta)

Open-Loop SensorObject Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)

nvoHwInput_# (# = 1 to 6)SNVT_count_inc_f(changeable type)

#6110

:)

:))

nvoSblndStatusSNVT_sblnd_state

nvoSblndSetFwdSNVT_setting

:)

Configuration Properties))

Sunblind

Actuator Object Type

nviSblndSetSNVT_setting

Mandatory Network Variables

Optional Configuration Properties

nvoSbldStatusConfiguration PropertiesMaximumSend Time (SCPTMaxSendTime

SunblindObject Configuration PropertiesObject Major Version (SCPTobjMajVerObject Minor Version (SCPTobjMinVer

OptionalNetwork Variables

8 x

nviSblndSetConfiguration PropertiesMaximumReceive Time (SCPTmaxRcvTime

nvoSbldStatus& nvoSblndSetFwdMaximumSend Time (SCPTMaxSendTimeMinimumSend Time (SCPTMinSendTime

Manufacturer Configuration Properties

Lamp Actuator

Object Type #3040

nviLampValueSNVT_switch

Mandatory Network Variables

Optional Configuration Properties

nvoLampValueFbSNVT_switch

LampActuator Object Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)

Manufacturer Network Variables

nvoRunHoursSNVT_elapsed_tm

8 x

nviRunHoursSNVT_elapsed_tm

OptionalNetwork Variables

nvoLampValueSNVT_switch

nviLampValue& nviRunHoursConfiguration PropertiesMaximumReceive Time (SCPTmaxRcvTime)

nvoLampValueFb, nvoRunHours, nvoLampValueConfiguration Properties:MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)

Manufacturer Configuration Properties

SCC-FCU Object Type #8501

Mandatory Network Variables

nviSpaceTempSNVT_temp_p

Configuration Properties

Manufacturer Network Variables

nviLightSet_# (#=1 to 4)

nvoSpaceTempSNVT_temp_p

nvoUnitStatusSNVT_hvac_status

nvoEffectSpSNVT_temp_p

nvoEffectOccupSNVT_occupancy

nvoHeatCoolSNVT_hvac_mode

nvoFanSpeedSNVT_switch

nvoDischAirTempSNVT_temp_p

nvoTerminalLoadSNVT_lev_percent

nvoSpaceRHSNVT_lev_percent

nvoOutdoorTempSNVT_temp_p

nvoEnergyHoldOffSNVT_switch

nvoSpaceCO2SNVT_ppm

nvoLocalSpaceTmpSNVT_temp_p

nvoReturnAirTempSNVT_temp_p

nvoFanSpeedCmdSNVT_switch

nvoSourceTempSNVT_temp_p

nvoEffectCoolSpSNVT_temp_p

nvoEffectHeatSpSNVT_temp_p

nvoSetPtOffsetSNVT_temp_p

nvoTempErrSNVT_temp_diff_p

nvoCO2LoadSNVT_lev_percent

nvoPresenceSNVT_occupancy

nvoChgOverSNVT_switch

nvoDewPtSensorSNVT_switch

nvoFlowStatusSNVT_switch

nvoWindowContactSNVT_switch

nvoAuxContactSNVT_switch

nvoEcoVueUNVT_energy_efficient

nvoSlaveInfoUNVT_Slave_Info

nvoLightLevelSNVT_lux

nvoLightSet_# (#=1 to 4)SNVT_setting

nvoSblndSet_# (#=1 to 4)SNVT_setting

nvoSystemInfoUNVT_system_info

nviFP_x (x = 1 to 50)*SNVT_Count_Inc_F(changeable type, up to 31 bytes)

nvoFP_x (x = 1 to 50)SNVT_Count_Inc_F(changeable type, up to 31 bytes)

*These NVIs support fan-in binding that increases the level of your building'sintelligence by making it easy to analyze multiple values from terminal and

application systems to determine the optimal operating point.

MandatoryConfiguration PropertiesnciSetPoints (CSPTserPnts#SI)Send Heartbeat (SCPTmaxSendTime)Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)

OptionalConfiguration PropertiesSCPTmaxRcvTime (SNVT_time_sec)SCPTminSendTime (SNVT_time_sec)

nviFP Configuration PropertiesNetwork Variable Type (SCPTnvType)Max Network Variable Length (SCPTmaxNVLength)Maximum Receive Time (SCPTmaxRcvTime)Default Output Value (SCPTdefOutput)

SCPTnvUsage

nvoFP Configuration PropertiesNetwork Variable Type (SCPTnvType)Max Network Variable Length (SCPTmaxNVLength)Maximum Send Time (SCPTMaxSendTime)Minimum Send Time (SCPTMinSendTime)Send Delta (SCPTsndDelta)SCPTnvUsage

Static Programmable Device

Object Type #410

nvoHwIn01_06UNVT_hardware_inputf_1to6

nvoVb01_124UNVT_variable_bool_1to124

nviModifyUNVT_modify_val2

Manufacturer Network Variables

nvoProgramStatusSNVT_prog_status

nvoVe01_27UNVT_variable_enum_1to27

nvoVe28_54UNVT_variable_enum_28to54

nvoVn01_07UNVT_variable_numf_1to7

nvoVn08_14UNVT_variable_numf_8to14

nvoVn15_21UNVT_variable_numf_15to21

nvoStatusxx (12x)SNVT_string(changeable type)

nvoVn22_28UNVT_variable_numf_22to28

nvoVn29_35UNVT_variable_numf_29to35

nvoVn36_42UNVT_variable_numf_36to42

nvoVn50_56UNVT_variable_numf_50to56

nvoVn43_49UNVT_variable_numf_43to49

Optional Configuration Properties

Manufacturer Configuration Properties

Manufacturer Configuration Properties:nciSetPoint (SCPTsetPnts#SI)nciCb01_124 (UCPT_constant_bool_1to124)nciCe01_31 (UCPT_constant_enum_1to31)nciCe32_62 (UCPT_constant_enum_32to62)nciCn01_07 (UCPT_constant_numf_1to7)nciCn08_14 (UCPT_constant_numf_8to14)nciCn15_21 (UCPT_constant_numf_15to21)nciCn22_28 (UCPT_constant_numf_22to28)nciCn29_35 (UCPT_constant_numf_29to35)nciCn36_42 (UCPT_constant_numf_36to42)nciCn43_49 (UCPT_constant_numf_43to49)nciCn50_56 (UCPT_constant_numf_50to56)UCPT_reason_for_haltUCPT_Loop# (# = 1 to 8)

Mandatory Network Variables

nvoHwOut01_10UNVT_hardware_output_1to6

ECL-PTU-208

nvoHwOut01_10UNVT_hardware_output_1to8

Static Programmable Device Object ConfigurationProperties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)MinimumSend Time (SCPTminSendTime)MaximumSend Time (SCPTmaxSendTime)SCPTprogCmdHistorySCPTprogStateHistorySCPTprogErrorHistorySCPTprogFileIndexesSCPTprogNameSCPTprogRevision

ECL-PTU-107

ECL-PTU-207 & ECL-PTU-308

nvoHwOut01_10UNVT_hardware_output_1to10

ECL-PTU-307

nvoHwOut01_10UNVT_hardware_output_1to11

Hardware Output

Open -Loop Actuator Object Type #3

nviHwOutput_# (# = 1 to 10)SNVT_switch(changeable type)

Mandatory Network Variables

Optional Configuration Properties

ECL-PTU-107: 6 xECL-PTU-207: 8 xECL-PTU-208: 10 xECL-PTU-307: 11 xECL-PTU-308: 10 x

nvoHwOutput_# (# = 1 to 10)SNVT_switch(changeable type)

nviHwOutput Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumReceive Time (SCPTmaxRcvTime)

nvoHwOutput Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)Send Delta (SCPTsndDelta)

Open-Loop Actuator Object Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)

nviSetpointSNVT_temp_p

nviSetptOffsetSNVT_temp_p

nviOccManCmdSNVT_occupancy

nviOccSensorSNVT_occupancy

nviApplicModeSNVT_hvac_mode

nviFanSpeedCmdSNVT_switch

nviComprEnableSNVT_switch

nviAuxHeatEnableSNVT_switch

nviEnergyHoldOffSNVT_switch

nviSourceTempSNVT_temp_p

nviOutdoorTempSNVT_temp_p

nviSpaceRHSNVT_lev_percent

nviSpaceCO2SNVT_ppm

nviTerminalLoadSNVT_lev_percent

nviChgOverSNVT_switch

nviSpaceTempAvgSNVT_temp_p

nviOutdoorCO2SNVT_ppm

nviDewPtSensorSNVT_switch

nviFlowStatusSNVT_switch

nviWindowContactSNVT_switch

nviSheddingSNVT_lev_percent

nviUnitStatusSNVT_hvac_status

nviWindSpeedSNVT_Speed

nviSlaveInfoUNVT_Slave_Info

nviLightLevelSVNT_lux

nviLightCmd_# (#=1 to 2)SNVT_switch

SNVT_setting

nviSblndSet_# (#=1 to 4)SNVT_setting

nviSunblindCmdSNVT_setting

nciSpaceCO2LimSNVT_ppm

nciFanSettingsUNVT_fan_setting

nciSpaceRHSetptSNVT_lev_percent

nciDamperSettingsUNVT_damper_settings

nciLightBlndCfgUNVT_light_blind

nciHVACScalingUNVT_hvac_scaling

nciLightLoopCfgUNVT_lightCtrlLoop

nciComSensorConfigUNVT_comsensor_1to2_Config

nciMiscConfigUNVT_mIsc_config

Page 9: ECL-PTU Series DS 15 EN

ECL-PTU Series 9 / 16

Product SpecificationsPower Supply (ECL-PTU-107 / 207 / 307)Voltage Range 100-240 VAC; -15%/+10%;Frequency Range 50/60HzOvercurrent Protection 4.0A external circuit breaker type C or

4.0A fast acting high breaking external fuse (250 VAC min)Device Insulation Type Double Insulation

Overvoltage Category II - 2.5 kVPower Consumption 0.9 W plus all external loads1

Maximum Consumption 4.0 A1. External loads must include the power consumption of any connected modules such as subnet devices, wireless module (1VA) and triac outputs.. Refer to the

respective module’s datasheet for related power consumption information.

Power Supply (ECL-PTU-208 / 308)Voltage Range 100-240 VAC; -15%/+10%;Frequency Range 50/60HzOvercurrent Protection 4.0A external circuit breaker type C or

4.0A fast acting high breaking external fuse (250 VAC min)Device Insulation Type Double Insulation

Overvoltage Category II - 2.5 kVPower Consumption < 2.7 W plus all external loads1

Maximum Consumption 3.5 A1. External loads must include the power consumption of any connected modules such as subnet devices, wireless module (1VA) and triac outputs.. Refer to the

respective module’s datasheet for related power consumption information.

CommunicationsCommunication LonTalk ProtocolTransceiver FT 5000 Free Topology Smart TransceiverChannel TP/FT-10; 78KbpsLonMark Interoperability Guidelines Version 3.4Device Class SCC Fan CoilLonMark Functional Profile :£ Input Objects Open-Loop Sensor #1£ Output Objects Open-Loop Actuator #3£ Node Object Node Object #0£ Real Time Clock Real Time Keeper #3300£ Scheduler Scheduler #20020£ Calendar Calendar #20030£ Programmable Device Static Programmable Device #410£ Lamp Objects Lamp Actuator #3040£ Sunblind Objects Sunblind Actuator #6110£ SCC Object SCC Fan Coil #8501

Page 10: ECL-PTU Series DS 15 EN

10 / 16 ECL-PTU Series

HardwareProcessor STM32 (ARM Cortex™ M3) MCU, 32 bitCPU Speed 68 MHzMemory 384 kB Non-volatile Flash (applications)

1 MB Non-volatile Flash (storage) 64 kB RAM

Status Indicator Green LEDs: Controller & Power Status LAN Tx & Rx

SubnetworkCommunication RS-485Cable Cat 5e, 8 conductor twisted pairConnector RJ-45Connection Topology Daisy-chainMaximum number of supported room devices per controller combined 4Supported room devices:£ Allure EC-Smart-Vue Series1

£ Allure EC-Smart-Comfort Series£ Allure EC-Smart-Air Series1

£ EC-Multi-Sensor SeriesSupported expansion modules per controller:£ ECx-Light-4 / ECx-Light-4D / ECx-Light-4DALI 2£ ECx-Blind-4 / ECx-Blind-4LV 21. A controller can support a maximum of two Allure Series Communicating Sensor models equipped with a CO2 sensor. The remaining connected Allure Series

Communicating Sensor models must be without a CO2 sensor.

Wireless Receiver1

Communication Protocol EnOcean wireless standardNumber of Wireless Inputs2 24Supported Wireless Receivers Refer to the Open-to-Wireless Solution GuideCable Telephone cord£ Connector 4P4C modular jack£ Length (maximum) 6.5ft (2m)

1. Available when an optional external Wireless Receiver module is connected to the controller. Refer to the Open-to-Wireless Solution Guide for a list of supportedEnOcean wireless modules.

2. Some wireless modules may use more than one wireless input from the controller.

Page 11: ECL-PTU Series DS 15 EN

ECL-PTU Series 11 / 16

MechanicalDimensions£ without terminal block covers 132 × 132 × 44 mm (5.2 x 5.2 x 44”)

132 (5.2)

132

(5.2)

44 (1.7)

mm (inches)

£ with terminal block covers 182 × 132 × 44 mm (7.2 x 5.2 x 44”)

mm (inches)

132 (5.2) 44 (1.7)

182

(7.2)

Shipping Weight:£ ECL-PTU-107 / ECL-PTU-207 0.82lbs (0.37 kg)£ ECB-PTU-307 0.86lbs (0.39 kg)£ ECB-PTU-208 / ECB-PTU-308 0.93lbs (0.42 kg)

Page 12: ECL-PTU Series DS 15 EN

12 / 16 ECL-PTU Series

Enclosure Material ABSEnclosure Rating Plastic housing, UL94-5VB flammability ratingColor Blue casing & grey connectorsInstallation Direct DIN-rail mounting or wall mounting

EnvironmentalOperating Temperature 41°F to 104°F (+5°C to +40°C) Storage Temperature -4°F to 158°F (-20°C to +70°C) Relative Humidity 0 to 90% Non-condensingIngress Protection Rating IP30 (with terminal block cover and strain relief)Altitude < 6561ft (2000m)Pollution Degree 2

Certified PerformancesChilled Ceiling Systems£ Cooling Control Accuracy 0.36°F (0.2°C)Fan Coil Systems (2 pipes + electric heater)£ Heating Control Accuracy 0.18°F (0.1°C)£ Cooling Control Accuracy 0.18°F (0.1°C)Fan Coil Systems (4 pipes)£ Heating Control Accuracy 0.18°F (0.1°C)£ Cooling Control Accuracy 0.18°F (0.1°C)

Standards and Regulation1

CE:Emission EN61000-6-3: 2006; A1:2010; Generic standards for residential,

commercial and light-industrial environmentsImmunity EN61000-6-1: 2005; Generic standards for residential,

commercial and light-industrial environmentsFCC This device complies with FCC rules part 15, subpart B, class BUL Listed (CDN & US) UL 61010-1 Safety Requirements for Electrical Equipment For

Measurement, Control, And Laboratory Use - Part 1: General Requirements - Edition 2 - Revision Date 2008/10/28

CSA C22.2 NO. 61010-1 Safety Requirements For Electrical Equipment For Measurement, Control, And Laboratory Use - Part 1: General

Requirements - Edition 2 - Revision Date 2008/10/01 File number: E352591

             1. Must be mounted with strain reliefs and terminal block covers or in a junction box to comply with CE and UL regulations.

Page 13: ECL-PTU Series DS 15 EN

ECL-PTU Series 13 / 16

Specifications – InputsUniversal Inputs (UI)GeneralInput Type Universal; software configurable

ContactType dry contact (0 - 3.3VDC)

CounterType dry contact (0 - 3.3VDC)Maximum Frequency 1Hz maximumMinimum Duty Cycle 500milliseconds On / 500milliseconds Off

0 to 10VDCRange 0 to 10VDC

Resistance/ThermistorType 10 kΩ Type II, III (10 kΩ @ 77°F; 25°C)Sensor Inputs (SI)GeneralInput Type Sensor; software configurableAccuracy ± 32.18°F; 0.1°C @ 77°F; 25°C (controller only)

ContactType dry contact (0 - 3.3VDC)

CounterType dry contact (0 - 3.3VDC)Maximum Frequency 1Hz maximumMinimum Duty Cycle 500milliseconds On / 500milliseconds Off

ResistanceResistor 10 kΩ Type II, III (10 kΩ @ 77°F; 25°C)Digital Inputs (DI)GeneralInput Type Digital; software configurable

ContactType dry contact (0 - 3.3VDC)

CounterType dry contact (0 - 3.3VDC)Maximum Frequency 20Hz maximumMinimum Duty Cycle 20milliseconds On / 20milliseconds OffPower Supply (Vref)Output (Vref) 5VDC for polarization (I < 1mA)

Page 14: ECL-PTU Series DS 15 EN

14 / 16 ECL-PTU Series

Specifications – OutputsTriac OutputsGeneral

ECL-PTU-107, ECL-PTU-207, and ECL-PTU-307Output Type TriacVoltage Range 100-240 VAC (same as device power supply)Maximum Current per Output 0.5A continuous

1 A @15% duty cycle for a 10-minute periodInrush Current 3.0 A maximum (<20 milliseconds)Common Terminal 1 per pair of outputs

General

For ECL-PTU-208 and ECL-PTU-308Output Type TriacVoltage See on-board 24 VAC power supplyCurrent See on-board 24 VAC power supplyPower Source Internal on-board 24 VAC power supplyCommon Terminal 1 per pair of outputs

Digital (On/Off)Voltage Range for Models:£ ECL-PTU-107 / ECL-PTU-207 / ECL-PTU-307 0 or 100-240 VAC

(Same as device power supply)£ ECL-PTU-208 / ECL-PTU-308 0 or 24 VAC

PWMApplication Typically Thermal Valve ControlRange Adjustable period from 2 to 65 seconds

FloatingMinimum Outputs 2 consecutive outputsMinimum Pulse On/Off Time 500 millisecondsDrive Time Period Adjustable from 10 to 600 seconds

Powered Relay OutputsGeneralOutput Type DigitalApplication Typically Fan SpeedsCurrent 3.0 A max. (inductive or resistive load) for the total sum of the 3 outputsResting State Normally openCommon Terminal Shared

Digital (On/Off)Voltage Range 0 or 100-240 VAC (Same as device power supply)

Page 15: ECL-PTU Series DS 15 EN

ECL-PTU Series 15 / 16

Digital Relay ContactGeneralOutput Type DigitalApplication Typically Electric HeaterOutput Protection Must be protected with a 10.0 A external circuit breaker or a

10.0 A external fast acting, high breaking fuse (250 VAC min.)

ContactType Dry contactVoltage Range 100 to 255 VACCurrent for models:£ ECL-PTU-107 / ECL-PTU-207 / ECL-PTU-208 / ECL-PTU-308 9.0 A max. on a resistive load (2

kW @ 230 VAC)£ ECL-PTU-307 6.0 A max. on a resistive load (1.4 kW @ 230 VAC)Resting State Normally OpenCommon Terminal Dedicated digital

AnalogECL-PTU-207 / ECL-PTU-208 / ECL-PTU-307 / ECL-PTU-308 models only

GeneralOutput Type AnalogVoltage Range 0 to 10VDC linearCurrent 5 mA maximum

24 VAC OutputsECL-PTU-208 / ECL-PTU-308 models onlyVoltage See on-board 24 VAC power supplyCurrent See on-board 24 VAC power supplyPower Source Internal on-board 24 VAC power supply

On-board 24 VAC power supplyECL-PTU-208 / ECL-PTU-308 models onlyVoltage Range 24 VAC; ± 10%Frequency Range 50 HzCurrent 500 mA max. on a resistive load (12 VA @ 24 VAC)Peak current 0.8 A max.Protection Short-circuit protected

Overload protected

Page 16: ECL-PTU Series DS 15 EN

16 / 16 ECL-PTU Series_DS_15_EN

Specifications subject to change without notice.Distech Controls, the Distech Controls logo, Innovative Solutions for Greener Buildings, EC-Net, ECO-Vue, Allure, and Open-To-Wireless are trademarks of DistechControls Inc.; LonWorks, LON, and LNS are registered trademarks of Echelon Corporation; BACnet is a registered trademark of ASHRAE; BTL is a registered trade-

mark of the BACnet Manufacturers Association; NiagaraAX Framework is a registered trademark of Tridium, Inc.; EnOcean is a registered trademark of EnOceanGmbH. All other trademarks are property of their respective owners.

©, Distech Controls Inc., 2013 - 2017. All rights reserved.