ECL-PTU Series LonMark ® Certified Powered Terminal Unit Programmable Controllers Overview The ECL-PTU Series controllers are microprocessor-based programmable controllers designed to control powered terminal units such as powered fan coil units, heat pumps units, and chilled beams. Each controller uses the LonTalk ® communication protocol and is LONMARK certified as an SCC Fan Coil Controller. These controllers are optimized for ultra-low power consumption and can be operated as stand-alone units or as part of a networked system to suit any installation requirement Applications These controllers meet the requirements of the following applications: £ Fan Coil Units £ Heat Pumps £ Chilled Beams £ Reversible Ceiling with 6-way valves £ Lighting fixtures and shade / sunblind motors when associated to ECx-Light/Blind Series expansion modules Features & Benefits Preloaded Applications Factory preloaded applications allow these controllers, straight out of the box, to operate standard PTU equipment with a proven energy- efficient sequence of operation thereby eliminating the need for programming. The preloaded application can be selected using an Allure EC-Smart-Vue sensor even before the network has been installed for rapid deployment or through the EC-Net™ solution using Distech Controls’ dcgfxApplications. Datasheet
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
ECL-PTU SeriesLonMark® Certified Powered Terminal Unit Programmable Controllers
OverviewThe ECL-PTU Series controllers aremicroprocessor-based programmablecontrollers designed to control powered terminalunits such as powered fan coil units, heatpumps units, and chilled beams.Each controller uses the LonTalk®
communication protocol and is LONMARK certifiedas an SCC Fan Coil Controller.These controllers are optimized for ultra-lowpower consumption and can be operated asstand-alone units or as part of a networkedsystem to suit any installation requirement
ApplicationsThese controllers meet the requirements of thefollowing applications:£ Fan Coil Units£ Heat Pumps£ Chilled Beams£ Reversible Ceiling with 6-way valves£ Lighting fixtures and shade / sunblind
motors when associated to ECx-Light/BlindSeries expansion modules
Features & BenefitsPreloaded ApplicationsFactory preloaded applications allow thesecontrollers, straight out of the box, to operatestandard PTU equipment with a proven energy-efficient sequence of operation therebyeliminating the need for programming.The preloaded application can be selected usingan Allure EC-Smart-Vue sensor even before thenetwork has been installed for rapid deploymentor through the EC-Net™ solution using DistechControls’ dcgfxApplications.
D a t a s h e e t
2 / 16 ECL-PTU Series
ProgrammabilitySupports Distech Controls’ EC-gfxProgram,which makes Building Automation System(BAS) programming effortless, by allowing youto visually assemble building blocks to create acustom control sequence for any HVAC ,lighting, or building automation application.
Dedicated Inputs & OutputsEach controller has specific IOs to fulfill any typeof installation:£ Universal inputs for using your preferred or
engineer-specified sensors.£ Sensor inputs to ensure optimal temperature
measurement processing.£ Digital inputs to accelerate the integration of
binary inputs such as window contacts.£ Powered Triac outputs for direct connection
of valves and actuators.£ Powered relay outputs for direct connection
of ventilator fans.£ Relay contact outputs for controlling
externally powered devices such as electricheater, fans, ...
£ Analog outputs to provide control signals forexternal peripherals.
£ Digital / Analog outputs for enhancedflexibility
Depending on the installation configuration andcontrolled equipment (valves, fans…), thesuitable model will allow for simplifiedinstallation and wiring, and eliminate the needfor additional external power supply.
Increased Energy EfficiencyImproves energy efficiency when combinedwith:£ Motion detectors to automatically adjust a
zone’s occupancy mode from standby tooccupied when presence is detected
£ CO2 sensors as part of a demand-controlledventilation strategy that adjusts the amountof fresh air intake according to the numberof building occupants
£ Light switches to control both lighting and aroom’s HVAC occupancy / standby modesetting
Smart Room Control SupportThe Smart Room Control solution is an end-to-end system for the control of HVAC equipment,lighting, and shades/sunblinds, achieving thehighest levels of comfort for occupants whilecutting costs from installation time and wiring/material requirements to energy consumption.This solution combines:£ Lighting and shade/sunblind expansion
modules to control lights (DALI, on/off ordimming) and shades/sunblinds (24 VDC or100-240 VAC, up/down and angle rotation).
£ Multi-sensor combining motion andluminosity (Lux) sensors and equipped withan Infrared receiver that works with aconvenient remote control.
£ Wireless (infrared) personal remote controlfor increased occupant comfort.
£ Allure™ Series Communicating Sensors forincreased occupant comfort settings.
Open-to-Wireless™ Solution
The controllers are Open-to-Wireless™ ready,and when paired with the Wireless Receiver,work with a variety of wireless battery-lesssensors and switches, to reduce the cost ofinstallation and minimize the impact on existingpartition walls. For supported frequencies inyour area, refer to the Open-to-WirelessSolution Guide.Available with an optional Wireless Receiverthat supports up to 24 wireless inputs to createwire-free installations.
Allure™ Series Communicating Sensor SupportThese controllers work with a wide range ofsensors, such as the Allure SeriesCommunicating Sensors that are designed toprovide intelligent sensing and control devicesfor increased user experience and energyefficiency.£ Allure EC-Smart-Vue sensors feature a
backlit-display and graphical menus thatprovide precise environmental zone control,with any combination of the following:temperature, humidity, CO2, and motionsensor.
ECL-PTU Series 3 / 16
£ Allure EC-Smart-Comfort sensors featurecolored LED indicators to provide userfeedback, rotary knobs to adjust the setpointoffset and fan speed, and an occupancyoverride push button. This sensor can alsobe expanded with a combination of up to 4add-on push button modules for lighting andshade/ sunblind control.
£ Allure EC-Smart-Air sensors combineprecise environmental sensing in a discreetand alluring enclosure for temperature,humidity, and CO2.
Supported Platforms
The EC-NetAX multi-protocol integration solutionis web-enabled and powered by the NiagaraAX
Framework, establishing a fully Internet-enabled, distributed architecture for real -timeaccess, automation and control of devices. TheEC- NetAX open framework solution creates acommon development and managementenvironment for integration of LONWORKS®,BACnet ® and other protocols. Regardless ofmanufacturer and protocol, the EC-NetAX systemprovides a unified modeling of diverse systemsand data, providing one common platform fordevelopment, management and enterpriseapplications.
LONWORKS Network Services
The LNS® client-server platform allows multipleusers, running different LNS-compatibleapplications, to access a common source fordirectory, installation, management, monitoringand control services for the network systembeing managed. Distech Controls’ Lonwatcher isan example of a LNS-based networkmanagement tool that can use Plug-Ins toconfigure and monitor controllers and devices inthe control system.
No External TransformerControllers in this series feature a 100-240 VACuniversal power supply input that allows fordirect connection to the mains and do notrequire external transformers, for improvedreliability and reduced installation costs.Some models have a 24 VAC power supplyoutput that can be used to power analogdampers and valve actuators therebyeliminating the need for a transformer.The ECx-Blind-4LV models have an embeddedpower supply that can eliminate the need for anexternal power supply to power the controlleddevice.
Ultra-low Power ConsumptionCareful attention was paid to the design of thesecontrollers as well as to the selection of theircomponents for optimal energy management.This provides ultra-low energy consumptionwhile providing high-level control performance.
Reduced Installation Time & CostOptional strain relief and terminal block coversprovide enhanced electrical protection that canreduce installation costs by eliminating the needfor a protective enclosure (when allowed bylocal regulations).Moreover, powered digital outputs allow fordirect connection of controlled loads to saveinstallation time and wiring costs.
eu.bac Certified Control Efficiency(pending)The eu.bac certification schemes guaranteesthe highest level of performance of the productsand systems, as defined in the EU-Directivesand relevant EN standards. This allows buildingowners to ensure that their building keepsperforming as well, or better than when it wasfirst commissioned.
Wireless inputs1 24 24 24 24 24Relay Contact Outputs(typ. Electric Heater) 1 x 2 kW 1 x 2 kW 1 x 2 kW 2 x 1 kW 1 x 2 kW
Powered Relay Outputs(typ. Fan Speeds) 3 3 3 3 3
Line-Powered TriacOutputs (typ. Valves) 2 2 0 4 0
24 VAC Triac Outputs(typ. Valves)2 0 0 2 0 4
Analog Outputs 0 4 2 2 224 VAC Power SupplyOutputsSupply Voltage Input 100-240VAC 100-240VAC 100-240VAC 100-240VAC 100-240VACCompatible with Optional Subnet Devices:Allure™ SeriesCommunicating Sensors2
Up to 43,4 Up to 43,4 Up to 43,4 Up to 43,4 Up to 43,4
EC-Multi-Sensor series Up to 44 Up to 44 Up to 44 Up to 44 Up to 44
ECx-Light-4 / ECx-Light-4D / 2 2 2 2 2
ECx-Blind-4 / ECx-Blind-4LV 2 2 2 2 21. All controllers are Open-to-Wireless ready. Available when an optional Wireless Receiver is connected to the controller. Some wireless sensors may use more
than one wireless input from the controller.2. Can be used to power certain types of valves and air dampers, thereby eliminating the need for a transformer.3. A controller can support a maximum of two Allure Series Communicating Sensor models equipped with a CO2 sensor. The remaining connected Allure Series
Communicating Sensor models must be without a CO2sensor.4. A controller can support four sensors among Allure EC-Smart-Vue and EC-Multi-Sensor.
Real Time Keeper Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)
)
Calendar
Object Type #20030
Manufacturer Network Variables
Optional Configuration Properties
nvoCalendar Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)Default Output Value (SCPTdefOutput)
Manufacturer Configuration Properties:
1 x
nvoCalendar_1SNVT_tod_event(changeable type)
Object Major Version (SCPTobjMajVerObject Minor Version (SCPTobjMinVer)
Scheduler
Object Type #20020
Manufacturer Network Variables
Optional Configuration Properties
nviSchedule Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumReceive Time (SCPTmaxRcvTime)
nvoSchedule Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)Default Output Value (SCPTdefOutput)
Scheduler Object Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)
2 x
nvoSchedule_# (# = 1 to 2)SNVT_tod_event(changeable type)
nvoHwInput Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)Send Delta (SCPTsndDelta)
Open-Loop SensorObject Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)
nvoHwInput_# (# = 1 to 6)SNVT_count_inc_f(changeable type)
#6110
:)
:))
nvoSblndStatusSNVT_sblnd_state
nvoSblndSetFwdSNVT_setting
:)
Configuration Properties))
Sunblind
Actuator Object Type
nviSblndSetSNVT_setting
Mandatory Network Variables
Optional Configuration Properties
nvoSbldStatusConfiguration PropertiesMaximumSend Time (SCPTMaxSendTime
SunblindObject Configuration PropertiesObject Major Version (SCPTobjMajVerObject Minor Version (SCPTobjMinVer
OptionalNetwork Variables
8 x
nviSblndSetConfiguration PropertiesMaximumReceive Time (SCPTmaxRcvTime
nvoSbldStatus& nvoSblndSetFwdMaximumSend Time (SCPTMaxSendTimeMinimumSend Time (SCPTMinSendTime
Manufacturer Configuration Properties
Lamp Actuator
Object Type #3040
nviLampValueSNVT_switch
Mandatory Network Variables
Optional Configuration Properties
nvoLampValueFbSNVT_switch
LampActuator Object Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)
Manufacturer Network Variables
nvoRunHoursSNVT_elapsed_tm
8 x
nviRunHoursSNVT_elapsed_tm
OptionalNetwork Variables
nvoLampValueSNVT_switch
nviLampValue& nviRunHoursConfiguration PropertiesMaximumReceive Time (SCPTmaxRcvTime)
nvoLampValueFb, nvoRunHours, nvoLampValueConfiguration Properties:MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)
Manufacturer Configuration Properties
SCC-FCU Object Type #8501
Mandatory Network Variables
nviSpaceTempSNVT_temp_p
Configuration Properties
Manufacturer Network Variables
nviLightSet_# (#=1 to 4)
nvoSpaceTempSNVT_temp_p
nvoUnitStatusSNVT_hvac_status
nvoEffectSpSNVT_temp_p
nvoEffectOccupSNVT_occupancy
nvoHeatCoolSNVT_hvac_mode
nvoFanSpeedSNVT_switch
nvoDischAirTempSNVT_temp_p
nvoTerminalLoadSNVT_lev_percent
nvoSpaceRHSNVT_lev_percent
nvoOutdoorTempSNVT_temp_p
nvoEnergyHoldOffSNVT_switch
nvoSpaceCO2SNVT_ppm
nvoLocalSpaceTmpSNVT_temp_p
nvoReturnAirTempSNVT_temp_p
nvoFanSpeedCmdSNVT_switch
nvoSourceTempSNVT_temp_p
nvoEffectCoolSpSNVT_temp_p
nvoEffectHeatSpSNVT_temp_p
nvoSetPtOffsetSNVT_temp_p
nvoTempErrSNVT_temp_diff_p
nvoCO2LoadSNVT_lev_percent
nvoPresenceSNVT_occupancy
nvoChgOverSNVT_switch
nvoDewPtSensorSNVT_switch
nvoFlowStatusSNVT_switch
nvoWindowContactSNVT_switch
nvoAuxContactSNVT_switch
nvoEcoVueUNVT_energy_efficient
nvoSlaveInfoUNVT_Slave_Info
nvoLightLevelSNVT_lux
nvoLightSet_# (#=1 to 4)SNVT_setting
nvoSblndSet_# (#=1 to 4)SNVT_setting
nvoSystemInfoUNVT_system_info
nviFP_x (x = 1 to 50)*SNVT_Count_Inc_F(changeable type, up to 31 bytes)
nvoFP_x (x = 1 to 50)SNVT_Count_Inc_F(changeable type, up to 31 bytes)
*These NVIs support fan-in binding that increases the level of your building'sintelligence by making it easy to analyze multiple values from terminal and
application systems to determine the optimal operating point.
MandatoryConfiguration PropertiesnciSetPoints (CSPTserPnts#SI)Send Heartbeat (SCPTmaxSendTime)Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)
Static Programmable Device Object ConfigurationProperties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)MinimumSend Time (SCPTminSendTime)MaximumSend Time (SCPTmaxSendTime)SCPTprogCmdHistorySCPTprogStateHistorySCPTprogErrorHistorySCPTprogFileIndexesSCPTprogNameSCPTprogRevision
ECL-PTU-107
ECL-PTU-207 & ECL-PTU-308
nvoHwOut01_10UNVT_hardware_output_1to10
ECL-PTU-307
nvoHwOut01_10UNVT_hardware_output_1to11
Hardware Output
Open -Loop Actuator Object Type #3
nviHwOutput_# (# = 1 to 10)SNVT_switch(changeable type)
nvoHwOutput_# (# = 1 to 10)SNVT_switch(changeable type)
nviHwOutput Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumReceive Time (SCPTmaxRcvTime)
nvoHwOutput Configuration Properties:Network Variable Type(SCPTnvType)Max Network Variable Length(SCPTmaxNVLength)MaximumSend Time (SCPTMaxSendTime)MinimumSend Time (SCPTMinSendTime)Send Delta (SCPTsndDelta)
Open-Loop Actuator Object Configuration Properties:Object Major Version (SCPTobjMajVer)Object Minor Version (SCPTobjMinVer)
nviSetpointSNVT_temp_p
nviSetptOffsetSNVT_temp_p
nviOccManCmdSNVT_occupancy
nviOccSensorSNVT_occupancy
nviApplicModeSNVT_hvac_mode
nviFanSpeedCmdSNVT_switch
nviComprEnableSNVT_switch
nviAuxHeatEnableSNVT_switch
nviEnergyHoldOffSNVT_switch
nviSourceTempSNVT_temp_p
nviOutdoorTempSNVT_temp_p
nviSpaceRHSNVT_lev_percent
nviSpaceCO2SNVT_ppm
nviTerminalLoadSNVT_lev_percent
nviChgOverSNVT_switch
nviSpaceTempAvgSNVT_temp_p
nviOutdoorCO2SNVT_ppm
nviDewPtSensorSNVT_switch
nviFlowStatusSNVT_switch
nviWindowContactSNVT_switch
nviSheddingSNVT_lev_percent
nviUnitStatusSNVT_hvac_status
nviWindSpeedSNVT_Speed
nviSlaveInfoUNVT_Slave_Info
nviLightLevelSVNT_lux
nviLightCmd_# (#=1 to 2)SNVT_switch
SNVT_setting
nviSblndSet_# (#=1 to 4)SNVT_setting
nviSunblindCmdSNVT_setting
nciSpaceCO2LimSNVT_ppm
nciFanSettingsUNVT_fan_setting
nciSpaceRHSetptSNVT_lev_percent
nciDamperSettingsUNVT_damper_settings
nciLightBlndCfgUNVT_light_blind
nciHVACScalingUNVT_hvac_scaling
nciLightLoopCfgUNVT_lightCtrlLoop
nciComSensorConfigUNVT_comsensor_1to2_Config
nciMiscConfigUNVT_mIsc_config
ECL-PTU Series 9 / 16
Product SpecificationsPower Supply (ECL-PTU-107 / 207 / 307)Voltage Range 100-240 VAC; -15%/+10%;Frequency Range 50/60HzOvercurrent Protection 4.0A external circuit breaker type C or
4.0A fast acting high breaking external fuse (250 VAC min)Device Insulation Type Double Insulation
Overvoltage Category II - 2.5 kVPower Consumption 0.9 W plus all external loads1
Maximum Consumption 4.0 A1. External loads must include the power consumption of any connected modules such as subnet devices, wireless module (1VA) and triac outputs.. Refer to the
respective module’s datasheet for related power consumption information.
Power Supply (ECL-PTU-208 / 308)Voltage Range 100-240 VAC; -15%/+10%;Frequency Range 50/60HzOvercurrent Protection 4.0A external circuit breaker type C or
4.0A fast acting high breaking external fuse (250 VAC min)Device Insulation Type Double Insulation
Overvoltage Category II - 2.5 kVPower Consumption < 2.7 W plus all external loads1
Maximum Consumption 3.5 A1. External loads must include the power consumption of any connected modules such as subnet devices, wireless module (1VA) and triac outputs.. Refer to the
respective module’s datasheet for related power consumption information.
CommunicationsCommunication LonTalk ProtocolTransceiver FT 5000 Free Topology Smart TransceiverChannel TP/FT-10; 78KbpsLonMark Interoperability Guidelines Version 3.4Device Class SCC Fan CoilLonMark Functional Profile :£ Input Objects Open-Loop Sensor #1£ Output Objects Open-Loop Actuator #3£ Node Object Node Object #0£ Real Time Clock Real Time Keeper #3300£ Scheduler Scheduler #20020£ Calendar Calendar #20030£ Programmable Device Static Programmable Device #410£ Lamp Objects Lamp Actuator #3040£ Sunblind Objects Sunblind Actuator #6110£ SCC Object SCC Fan Coil #8501
£ EC-Multi-Sensor SeriesSupported expansion modules per controller:£ ECx-Light-4 / ECx-Light-4D / ECx-Light-4DALI 2£ ECx-Blind-4 / ECx-Blind-4LV 21. A controller can support a maximum of two Allure Series Communicating Sensor models equipped with a CO2 sensor. The remaining connected Allure Series
Communicating Sensor models must be without a CO2 sensor.
Wireless Receiver1
Communication Protocol EnOcean wireless standardNumber of Wireless Inputs2 24Supported Wireless Receivers Refer to the Open-to-Wireless Solution GuideCable Telephone cord£ Connector 4P4C modular jack£ Length (maximum) 6.5ft (2m)
1. Available when an optional external Wireless Receiver module is connected to the controller. Refer to the Open-to-Wireless Solution Guide for a list of supportedEnOcean wireless modules.
2. Some wireless modules may use more than one wireless input from the controller.
ECL-PTU Series 11 / 16
MechanicalDimensions£ without terminal block covers 132 × 132 × 44 mm (5.2 x 5.2 x 44”)
132 (5.2)
132
(5.2)
44 (1.7)
mm (inches)
£ with terminal block covers 182 × 132 × 44 mm (7.2 x 5.2 x 44”)
Enclosure Material ABSEnclosure Rating Plastic housing, UL94-5VB flammability ratingColor Blue casing & grey connectorsInstallation Direct DIN-rail mounting or wall mounting
EnvironmentalOperating Temperature 41°F to 104°F (+5°C to +40°C) Storage Temperature -4°F to 158°F (-20°C to +70°C) Relative Humidity 0 to 90% Non-condensingIngress Protection Rating IP30 (with terminal block cover and strain relief)Altitude < 6561ft (2000m)Pollution Degree 2
Certified PerformancesChilled Ceiling Systems£ Cooling Control Accuracy 0.36°F (0.2°C)Fan Coil Systems (2 pipes + electric heater)£ Heating Control Accuracy 0.18°F (0.1°C)£ Cooling Control Accuracy 0.18°F (0.1°C)Fan Coil Systems (4 pipes)£ Heating Control Accuracy 0.18°F (0.1°C)£ Cooling Control Accuracy 0.18°F (0.1°C)
Standards and Regulation1
CE:Emission EN61000-6-3: 2006; A1:2010; Generic standards for residential,
commercial and light-industrial environmentsImmunity EN61000-6-1: 2005; Generic standards for residential,
commercial and light-industrial environmentsFCC This device complies with FCC rules part 15, subpart B, class BUL Listed (CDN & US) UL 61010-1 Safety Requirements for Electrical Equipment For
Measurement, Control, And Laboratory Use - Part 1: General Requirements - Edition 2 - Revision Date 2008/10/28
CSA C22.2 NO. 61010-1 Safety Requirements For Electrical Equipment For Measurement, Control, And Laboratory Use - Part 1: General
1. Must be mounted with strain reliefs and terminal block covers or in a junction box to comply with CE and UL regulations.
ECL-PTU Series 13 / 16
Specifications – InputsUniversal Inputs (UI)GeneralInput Type Universal; software configurable
ContactType dry contact (0 - 3.3VDC)
CounterType dry contact (0 - 3.3VDC)Maximum Frequency 1Hz maximumMinimum Duty Cycle 500milliseconds On / 500milliseconds Off
0 to 10VDCRange 0 to 10VDC
Resistance/ThermistorType 10 kΩ Type II, III (10 kΩ @ 77°F; 25°C)Sensor Inputs (SI)GeneralInput Type Sensor; software configurableAccuracy ± 32.18°F; 0.1°C @ 77°F; 25°C (controller only)
ContactType dry contact (0 - 3.3VDC)
CounterType dry contact (0 - 3.3VDC)Maximum Frequency 1Hz maximumMinimum Duty Cycle 500milliseconds On / 500milliseconds Off
ResistanceResistor 10 kΩ Type II, III (10 kΩ @ 77°F; 25°C)Digital Inputs (DI)GeneralInput Type Digital; software configurable
ContactType dry contact (0 - 3.3VDC)
CounterType dry contact (0 - 3.3VDC)Maximum Frequency 20Hz maximumMinimum Duty Cycle 20milliseconds On / 20milliseconds OffPower Supply (Vref)Output (Vref) 5VDC for polarization (I < 1mA)
14 / 16 ECL-PTU Series
Specifications – OutputsTriac OutputsGeneral
ECL-PTU-107, ECL-PTU-207, and ECL-PTU-307Output Type TriacVoltage Range 100-240 VAC (same as device power supply)Maximum Current per Output 0.5A continuous
1 A @15% duty cycle for a 10-minute periodInrush Current 3.0 A maximum (<20 milliseconds)Common Terminal 1 per pair of outputs
General
For ECL-PTU-208 and ECL-PTU-308Output Type TriacVoltage See on-board 24 VAC power supplyCurrent See on-board 24 VAC power supplyPower Source Internal on-board 24 VAC power supplyCommon Terminal 1 per pair of outputs
Digital (On/Off)Voltage Range for Models:£ ECL-PTU-107 / ECL-PTU-207 / ECL-PTU-307 0 or 100-240 VAC
(Same as device power supply)£ ECL-PTU-208 / ECL-PTU-308 0 or 24 VAC
PWMApplication Typically Thermal Valve ControlRange Adjustable period from 2 to 65 seconds
FloatingMinimum Outputs 2 consecutive outputsMinimum Pulse On/Off Time 500 millisecondsDrive Time Period Adjustable from 10 to 600 seconds
Powered Relay OutputsGeneralOutput Type DigitalApplication Typically Fan SpeedsCurrent 3.0 A max. (inductive or resistive load) for the total sum of the 3 outputsResting State Normally openCommon Terminal Shared
Digital (On/Off)Voltage Range 0 or 100-240 VAC (Same as device power supply)
ECL-PTU Series 15 / 16
Digital Relay ContactGeneralOutput Type DigitalApplication Typically Electric HeaterOutput Protection Must be protected with a 10.0 A external circuit breaker or a
10.0 A external fast acting, high breaking fuse (250 VAC min.)
ContactType Dry contactVoltage Range 100 to 255 VACCurrent for models:£ ECL-PTU-107 / ECL-PTU-207 / ECL-PTU-208 / ECL-PTU-308 9.0 A max. on a resistive load (2
kW @ 230 VAC)£ ECL-PTU-307 6.0 A max. on a resistive load (1.4 kW @ 230 VAC)Resting State Normally OpenCommon Terminal Dedicated digital
AnalogECL-PTU-207 / ECL-PTU-208 / ECL-PTU-307 / ECL-PTU-308 models only
GeneralOutput Type AnalogVoltage Range 0 to 10VDC linearCurrent 5 mA maximum
24 VAC OutputsECL-PTU-208 / ECL-PTU-308 models onlyVoltage See on-board 24 VAC power supplyCurrent See on-board 24 VAC power supplyPower Source Internal on-board 24 VAC power supply
On-board 24 VAC power supplyECL-PTU-208 / ECL-PTU-308 models onlyVoltage Range 24 VAC; ± 10%Frequency Range 50 HzCurrent 500 mA max. on a resistive load (12 VA @ 24 VAC)Peak current 0.8 A max.Protection Short-circuit protected
Overload protected
16 / 16 ECL-PTU Series_DS_15_EN
Specifications subject to change without notice.Distech Controls, the Distech Controls logo, Innovative Solutions for Greener Buildings, EC-Net, ECO-Vue, Allure, and Open-To-Wireless are trademarks of DistechControls Inc.; LonWorks, LON, and LNS are registered trademarks of Echelon Corporation; BACnet is a registered trademark of ASHRAE; BTL is a registered trade-