EC centrifugal module - RadiPac backward curved, single inlet in cube design K3G800-AS07-01 ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 · D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 [email protected]www.ebmpapst.com Limited partnership · Headquarters Mulfingen County court Stuttgart · HRA 590344 General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen County court Stuttgart · HRB 590142 Nominal data Type K3G800-AS07-01 Motor M3G200-QA Phase 3~ Nominal voltage VAC 400 Nominal voltage range VAC 380 .. 480 Frequency Hz 50/60 Type of data definition ml State prelim. Speed min -1 1370 Power input W 11600 Current draw A 17.8 Min. ambient temperature °C -40 Max. ambient temperature °C +40 ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit Subject to alterations Data according to ErP directive Installation category A Efficiency category Static Variable speed drive Yes Specific ratio * 1.01 * Specific ratio = 1 + p fs / 100 000 Pa Actual Request 2013 Request 2015 Overall efficiency η es 66.7 58.1 62.1 Efficiency grade N 66 58 62 Power input P ed kW 11.54 Air flow q v m³/h 22900 Pressure increase p fs Pa 1164 Speed n min -1 1365 Data definition with optimum efficiency. Item no. 51809-5-9980 · Revision 79796 · Release 2013-03-27 · Page 1 / 5 ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com
5
Embed
EC centrifugal module - RadiPac€¦ · Air flow qv m³/h 22900 ... Approval GOST Item no. 51809-5 ... EC centrifugal module - RadiPac backward curved, single inlet in cube design
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
EC centrifugal module - RadiPacbackward curved, single inlet
General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen
County court Stuttgart · HRB 590142
Nominal data
Type K3G800-AS07-01
Motor M3G200-QA
Phase 3~
Nominal voltage VAC 400
Nominal voltage range VAC 380 .. 480
Frequency Hz 50/60
Type of data definition ml
State prelim.
Speed min-1 1370
Power input W 11600
Current draw A 17.8
Min. ambient temperature °C -40
Max. ambient temperature °C +40ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unitSubject to alterations
Data according to ErP directive
Installation category A
Efficiency category Static
Variable speed drive Yes
Specific ratio* 1.01* Specific ratio = 1 + pfs / 100 000 Pa
Actual Request 2013 Request 2015
Overall efficiency ηes 66.7 58.1 62.1
Efficiency grade N 66 58 62
Power input Ped kW 11.54
Air flow qv m³/h 22900
Pressure increase pfs Pa 1164
Speed n min-1 1365Data definition with optimum efficiency.
KL 2 1 NO Status relay, floating status contact; normally open; make for failure
KL2 2 COM Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / 2A (AC1)
KL2 3 NC Status relay, floating status contact; break for failure
KL 3 1 RSA Bus connection RS485; RSA; MODBUS RTU
KL 3 2 RSB Bus connection RS485; RSB; MODBUS RTU
KL 3 3 / 10 GND Reference ground for control interface
KL 3 4 Ain1 U Analogue input 1 (set value); 0-10 V; Ri= 100 kΩ; parametrisable curves; only usable as alternative toinput Ain1 I
KL 3 5 + 10 V Fixed voltage output 10 VDC; + 10 V +/-3%; max. 10 mA; short circuit proof; power supply for ext.devices (e.g. potentiometer)
KL 3 6 Ain1 I Analogue input 1 (set value); 4-20 mA; Ri= 100 Ω; parametrisable curves; only usable as alternative toinput Ain1 U
KL 3 7 Din1 Digital input 1: enabling of electronics; enabling: open pin or applied voltage 5 to 50 VDC; disabling: bridgeto GND or applied voltage < 1 VDC; reset function: triggers software reset after a level change to <1 V
KL 3 8 Din2 Digital input 2: parameter set switch 1/2; according to EEPROM setting, the valid/used parameter set isselectable per BUS or per digital input DIN2. Parameter set 1: open pin or applied voltage 5 to 50 VDC;parameter set 2: bridge to GND or applied voltage < 1 VDC
KL 3 9 Din3 Digital input 3: Control characteristic of the integrated controller; according to EEPROM setting, the controlcharacteristic of the integrated controller is normally/inversely selectable per BUS or per digital input;normal: open pin or applied voltage 5 to 50 VDC (control deviation = actual sensor value - set value)inverse: bridge to GND or applied voltage < 1 VDC (control deviation = set value - actual sensor value)
KL 3 11 Ain2 U Analogue input 2; actual sensor value 0-10 V; Ri= 100 kΩ; parametrisable curve; only usable asalternative to input Ain2 I
KL 3 12 + 20 V Fixed voltage output 20 VDC; + 20V +25/-10%; max. 50 mA; short circuit proof; supply voltage for ext.devices (e.g. sensors)
KL 3 13 Ain2 I Analogue input 2; actual sensor value 4-20 mA; Ri= 100 Ω; parametrisable curve; only usable asalternative to input Ain2 U
KL 3 14 Aout Analogue output 0-10 V; max. 5 mA; output of the actual motor control factor (output voltage of electronics)/of the actual motor speed. Parametrisable curve.
Air performance measured as per ISO 5801Installation category A. For detailedinformation on the measuring set-up, pleasecontact ebm-papst. Suction-side noiselevels: LwA measured as per ISO 13347 /LpA measured with 1m distance to fan axis.The values given are valid under themeasuring conditions mentioned above andmay vary according to the actual installationsituation. With any deviation from thestandard set-up, the specific values have tobe checked and reviewed with the unitinstalled.
Measured values
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
U
V
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
400
f
Hz
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
n
min-1
1370
1370
1370
1370
1200
1200
1200
1200
1000
1000
1000
1000
800
800
800
800
Ped
W
6755
9619
11600
10690
4510
6456
7812
7120
2610
3736
4521
4120
1336
1913
2315
2110
I
A
10.53
14.77
17.80
16.37
7.03
9.92
11.95
10.90
4.07
5.74
6.92
6.31
2.08
2.94
3.54
3.23
LpAin
dB(A)
94
91
82
86
90
87
79
83
86
83
74
78
80
77
69
73
LwAin
dB(A)
106
98
90
93
102
94
87
90
98
90
83
85
92
84
77
79
LwAout
dB(A)
108
101
94
96
105
98
91
92
100
93
86
88
95
87
81
82
qv
m3/h
35375
30510
23040
13335
30920
26710
20240
11650
25765
22260
16865
9710
20610
17810
13495
7765
pfs
Pa
0
600
1200
1600
0
460
933
1220
0
319
648
847
0
204
415
542
U = Supply voltage · f = Frequency · n = Speed · Ped = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet side · LwAout = Sound power level outlet side