Top Banner

of 7

Earthing & Lightning Protection Guide

Jul 07, 2018

Download

Documents

Sofyan Shah
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/18/2019 Earthing & Lightning Protection Guide

    1/7

    EARTHING & LIGHTNING PROTECTION

    www.dongabestech.comJ2

    CODES OF PROTECTION OF STRUCTURES AGAINST LIGHTNING.BS 6651 : Protection of structures against lightning.

    BSEN 62305 : Embrace the whole concept of lightning protection from design to installation.

    IEC 61024-1 : Protection of structures against lightning.IEC 60364-5-54 : Earthing arrangements and protective conductors.

    KS C 9609 : Lightning rod.

    UL96 : Lightning Protection Components.

    EARTH RODS.When earth rods are used, they should be driven into the ground beneath, or as close as practicable to,

    the structure and down conductor. The practice of siting terminations away from the building is normally

    unnecessary and uneconomical.

    Where ground conditions are favourable for the use of rods in parallel, the reduction in earth resistance

    is small when the separation between the rods becomes less than their driven length.

    Lightning protection system for tall buildings(over 20m high) showing air terminations, down

    conductors, bonds to projections above roof.

    Earth terminations : arrangement of earth electrodes.

    Air termination mesh should be not greater than 10m X 20m. Down conductor should be not more than 10m apart.

    Air termination bondedto steel reinforcing orsteel frame of buliding.

    Earth electrode

  • 8/18/2019 Earthing & Lightning Protection Guide

    2/7

    EARTHING & LIGHTNING PROTECTION

    www.dongabestech.com J3

    AIR TERMINATIONS.Air termination networks may consist of vertical or horizontal conductors or combinations of both.

    For large flat roofs, this is achived typically by use of an air termination network mesh of approximately 10m x 20m.

    On multiple ridge roofs, additional conductors are necessary if the separation, S(in metres), of the ridgesis greater than 10 +2H, where H is the height of the ridge (in metres). See Fig.5

    On a reinforced concrete structure, the air termination should be connected to the reinforcing bars in the number

    of positions needed for down conductors.

    Air terminations for a flat roof

  • 8/18/2019 Earthing & Lightning Protection Guide

    3/7

    EARTHING & LIGHTNING PROTECTION

    www.dongabestech.comJ4

    Air terminations for flat roofs at different levels

    Air terminations for large areas of roof of various profiles.

    Perimeter = 24 + 24+ 12+ 12 = 72mNumber of down conductoors required= 72/20 = 4.

    NOTE 1 If S > 10 +2H, additional longitudinal conductors are needed so that the distance between conductorsNOTE 1does not exceed 10m.NOTE 2 If the length of the roof exceeds 20m. additional transverse conductors are necessary.NOTE 3 Down conductors are omitted for clarity.

  • 8/18/2019 Earthing & Lightning Protection Guide

    4/7

    EARTHING & LIGHTNING PROTECTION

    www.dongabestech.com J5

    Air terminations for tall conducting structures.

    Example of lightning protection system for brick chimneys.

    The air termination network for a tall reinforced concreteor steel structure should be as follows:a) horizontal conductors on roofs from a 10m X 20m network;b) bonds to steelwork at comers, at 20m intervals around theb) periphery and on the tower 0.5m above the lower roof level;c) key bonding to the building steelwork.

  • 8/18/2019 Earthing & Lightning Protection Guide

    5/7

    EARTHING & LIGHTNING PROTECTION

    www.dongabestech.comJ6

    DOWN CONDUCTORS.The function of a down conductor is to provide a low impedance path from the air termination to the earth

    electrode so that the lightning current can be safely conducted to earth.

    Depending upon the form of the building, it is often necessary to have multiple down conductors in parallel,some or all of which may be part of the building structure itself. For example, a steel framed or reinforced concrete

    structure might need no added down conductors as the framework itself provides an efficiant natual network

    of many paths to earth ; conversely a structure made entirely from non-conducting materials would need

    down conductors deployed according to the size and form of the structure.

    Patterns of down conductors(natural or not) for various forms of tall building.

    The down conductors may be natural (parts of the building framework) or added strips or rods on external faces.On structures exceeding 20m in height, down conductors should be spaced not more than 10m apart.

  • 8/18/2019 Earthing & Lightning Protection Guide

    6/7

    EARTHING & LIGHTNING PROTECTION

    www.dongabestech.com J7

    Air termination and zone of protection for simple structure with explosive or

    highly flammable contents.

    CORROSION.Electrolytic corrosion between dissimilar metals :

    The contact of dissimilar metals, unless the contact surfaces are kept completely dry and protected

    against the ingress of moisture, is likely to initiate and accelerate corrosion.

    Chemical corrosion of copper :

    Although copper is highly resistant to many types of chemical attack, lead coating is recommended where

    it is subject to serve corrosion due to the presence of sulphur compounds.

    INSPECTION.All lightning protection systems should be visually inspected by a competent person during installation,

    after completetion and after alteration or extension, in order to verify that they conform to the recommendations in

    BS6651, Visual inspections should be repeated at fixed intervals, preferably not exceeding 12 months.

    To prevent flashover between mast/conductor and protected building, the minimum clearance distance has to be 2m,whichever is the greater.

    This clearance has to under maximum sag conditions, i.e. snow ice on the aerial conductor.

  • 8/18/2019 Earthing & Lightning Protection Guide

    7/7

    COPPER CONDUCTOR & COPPER TAPE

    www dongabestech comJ8

    ANNEALED STRANDED COPPER CONDUCTOR

    COPPER CONDUCTOR PVC INSULATED GROUNDING WIRE

    Stranded constructionNumber/diameter

    No./mm

    ConductorSize(mm

    2

    )

    ElectricResistance max.

     /mm2

    10

    16

    25

    35

    50

    70

    95

    120

    150

    185

    240

    300

    -

    1.15

    0.727

    0.524

    0.387

    0.268

    0.193

    0.153

    0.124

    0.0991

    0.0754

    0.0601

    -

    4.7

    5.9

    7

    8.1

    9.6

    11.4

    13

    14.4

    16

    18.3

    20.5

    -

    142

    225

    312

    427

    617

    854

    1034

    1280

    1600

    2064

    2641

    7/1.35

    Compact

    Stranded

    C.C

    Reference

    Overall Diametermm(approx.)

    Approximately Weightkg/km

    PART NO

    CT - 2003

    CT - 2503CT - 3003

    CT - 3806

    CT - 5003

    CT - 5006

    20

    2530

    38

    50

    50

    3

    3

    3

    6

    3

    6

    50M

    50M

    50M

    25M

    40M

    20M

    0.27kg

    0.67kg

    0.80kg

    1.45kg

    1.33kg

    2.68kg

    W TQ’ty per coil

    Dimensions(mm)Weight per m

    ConductNominal sectional area

    mm2

    ConstructionNo./mm

    610162535507095

    120150185240300

    7/1.047/1.35C.C.C.C.C.C.C.C.C.C.C.C.

    C.C.C.C.C.C.C.C.C.C.

    2.42.42.42.62.62.82.83.1

    3.13.43.64.04.5

    --

    0.190.290.410.530.731.00

    1.161.542.012.493.05

    Nominal thicknessof insulation

    mm

    IEC Standard Designation : IEC60228

    Soft drawn stranded copper : BS6360

    HIGH CONDUCTIVITY COPPER TAPE (BS EN13601)

    *C.C. : Circular Compact stranded shape

    Remarks : The numerical values in this table are taken at 20

    **Tinned Copper Tape : 30M*Steel Tape(H.D.G) is available.

    •High conductivity copper

    •Insulation : Green Color (UV stability)

    PART NO

    IBCB - 253

    IBCB - 256

    IBCB - 506

    25

    25

    50

    3

    6

    6

    5M

    5M

    5M

    0.77kg

    1.53kg

    2.95kg

    W TQ’ty per coil

    Dimensions(mm)Weight per m

    PVC COVERED COPPER TAPE

    T

    T

    W

    W

    Approx. weight of cable

    kg/m

    Green/Yellow PVC Covered Soft drawn stranded copper : BS 6004 / PVC Green or Green/Yellow insulation : IEC60502