8/11/2019 E0878 DC3 --- GS 001.pdf http://slidepdf.com/reader/full/e0878-dc3-gs-001pdf 1/15 REFERENCE NUMBER : GE Energy ECH / SCALE FORMAT / SIZE DATE NOM / NAME VISA TITRE / TITLE REDIGE / MADE APPROUVE / APPROVED VERIFIE / CHECKED REVISION INSTRUCTION DE MODIFICATION Section Doc. N SHEET. N Ce document, propriété exclusive de GE Energy Products France SNC est strictement confidentiel. Il ne peut être communiqué, copié ou reproduit sans son autorisation écrite préalable This document, exclusive property of GE Energy Products France SNC is strictly confidential. It must not be communicated, copied or reproduced without our previous written consent. REVISION : MEGA DEAL PROJECT D GRD none A4 IM-2009009083 20/10/2009 20/10/2009 20/10/2009 91-444756 WEBER DANIEL DENICOURT FRANCK WESTRELIN ARNAUD WESTRELIN ARNAUD DENICOURT FRANCK WEBER DANIEL C H E N U T B R I G I T T E V A L I D E X E0878 DC3 --- GS 001 LV CABLES < 1000 V-STANDARD TECHNICAL SPECIFICATION LV POWER & CTRL CABLES A K 0 4 - N o v - 2 0 1 0 - 1 4 : 0 8 G E O f f i c ial F O R I N F OR M T I O N
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
GE Energy LV POWER, CONTROL & INSTRUMENTATION N° 91 – 444756
Products - Europe NON-ARMOURED CABLES < 1 KV
Sheet : 2/14
Modif. G H J K E F Date : 10/11/98
Date 13/11/06 11/07/07 20/09/07 23/07/09 13/10/03 25/05/04 Name:MICHELOT A. N° 91 – 444756
STATE OF MODIFICATIONS
INDEX DATE DESCRIPTION
A 10 / 11 / 98 First issue
B 25 / 01 / 01Modification of cable protective sheath colours forthermocouples T and K types according to IEC 584.3
C 14 / 02 / 01Standard numbers revision / Reference to IEC 60332-1standard
D 23 / 04 / 02Principal: Added flame retardant & AD7 water-resistant.Control: 500V in place of 0,6 to 1 kV.
E 13 / 10 / 03 Para 2 :- added references to IEC; CUL / CSA; CCC; ANSI / IEEE; CI- light blue outer sheath for intrinsically safety function- cable designed for permanent ambient temperature of 90°C
- fire retardant cables for fire detection / protectionPara 6 :- modified thermocouple TC / KC cable type to TX / KX cabletype- added reference to IEC 60228Para 7 :- Added Twisted Pair Data Cable
F 25 / 05 / 04 Para 2 :- added hydrocarbon resistant- deleted standard cable marking- deleted intrinsically specific requirement- deleted fire detection / protection specific requirementPara 6.2- deleted individual insulation for each pairDocument :- other minor modification
G 13 / 11 / 06 Para 2 :- added Halogen freePower & Control :added class 5, added overall sheath colour Greendeleted PVC referencesPara 5.1 :deleted single quad ( 01IQ ) cable typePara 6 :
-added single pair type E thermocouple extension cableCosmetic modifications
H 11 / 07 / 07Para 2 :- added Fire retardant to IEC 60331Para 6.1 and 6.2 :- added possibility to supply KCB type instead of Kx
J 20 / 09 / 07Para 2 : corrected “Fire retardant to IEC 60331” by “Fireretardant to IEC 60332-3”
K 23 / 07 / 09Please refer to orange parts.Mainly prescription of cores/outer sheaths colours, addition of chapter 11.Cosmetic modifications
GE Energy LV POWER, CONTROL & INSTRUMENTATION N° 91 – 444756
Products - Europe NON-ARMOURED CABLES < 1 KV
Sheet : 3/14
Modif. G H J K E F Date : 10/11/98
Date 13/11/06 11/07/07 20/09/07 23/07/09 13/10/03 25/05/04 Name:MICHELOT A. N° 91 – 444756
1. SUBJECT
Purpose of the present specification is to define LV power, control and instrumentation cables to beused.
All the proposed cables shall comply with IEC standards, latest edition.
2. CABLE GENERAL CONDITIONS
General
· Cables shall be Aliphatic hydrocarbon resistant
· All the cables must be suitable for outdoor use (protective sheath UV stabilised)
·
AD7 water-resistant (temporary submerged - CEI 60529 – 2 months cumulated per year)· Flame retardant to IEC 60332-1, Fire retardant to IEC 60332-3
· All cables subject to present specification shall be designed to withstand a permanenttemperature of 90°C in normal operation (working temperature)
· Low smoke to IEC 61034, Halogen free
· Cables shall be suitable for use in cable trays and PVC ducts
· Manufacturer identity, cable type, temperature class, shall be provided throughout the lengthof the cable
· To avoid any risk of confusion with hypothetic intrinsically safety links, all the cables describedin this specification shall not have the outer sheath blue coloured
GE Energy LV POWER, CONTROL & INSTRUMENTATION N° 91 – 444756
Products - Europe NON-ARMOURED CABLES < 1 KV
Sheet : 14/14
Modif. G H J K E F Date : 10/11/98
9. TESTS
Cables shall be workshop tested in accordance with applicable standards. The minimum scope of tests shall include:
Measurement of insulation resistance Measurement of sheathing and protecting layers thickness (sample only) Continuity test
Moreover, test certificates shall be provided, proving that each cable type to be used hassuccessfully passed all special and type tests as required by the applicable standards during the last12 months before award of contract. Otherwise, these tests have to be repeated on samplesections.
10.DOCUMENTATION
To refer to specification N° 91-463037.
11.NOTE
Before cable shipment, Cable supplier shall inform GE about the cable distribution versus drums(cable type length per drum) for GE to check/confirm the correct distribution with regard to the
project minimum required length.Cable distribution information has to be given in the shortest time after cable order receipt in orderto minimize impact on ex-work date in case of GE comments relating to cable drums organisation.This to avoid having delivered cable drums with unusable cable length.