'E' SERIES GENERAL NOTES A. ALL ELECTRICAL WORK SHALL CONFORM TO THE NATIONAL ELECTRIC CODE 2017 WITH CHICAGO AMENDMENTS. B. FOR EXACT LOCATION AND FINISH SURFACE CONDITIONS OF CEILING, WALL, FLOOR MOUNTED DEVICES, REFER TO ARCHITECTURAL DRAWINGS. C. FOR EXACT LOCATION OF FACILITY EXPANSION JOINTS, FIRE RATED WALLS AND SMOKE WALLS, REFER TO ARCHITECTURAL DRAWINGS. D. FOR EXACT LOCATIONS OF DUCT MOUNTED SMOKE DETECTORS, WATER FLOW SWITCHES AND TAMPER SWITCHES REFER TO HVAC / FP DRAWINGS. E. VERIFY EXACT LOCATION OF CONNECTION POINTS PRIOR TO CONNECTION. F. MOUNTING HEIGHTS ARE TO CENTER OF DEVICE OR EQUIPMENT, UNO. G. PROVIDE RACEWAY, WIRE AND CABLE, ASSOCIATED FITTINGS AND CONNECTORS, AND COMPLETE CONNECTIONS REQUIRED FOR DESIGNATED BRANCH CIRCUITS FROM DEVICE(S) TO FINAL OVERCURRENT DEVICE AND TO LOCAL CONTROL DEVICE(S) PER SPECIFICATIONS. H. MINIMUM BRANCH CIRCUIT WIRE SIZE SHALL BE #12 AWG EXCEPT LIFE SAFETY BRANCH CIRCUIT WIRING WHICH SHALL BE MINIMUM #10 AWG. MAINTAIN MAXIMUM BRANCH CIRCUIT CONDUCTOR LENGTHS AS PER SPECIFICATIONS AND SCHEDULED ON THIS DRAWING. INCLUDE GROUND CONDUCTOR DERATINGS. I. PROVIDE GROUNDING PER NEC. ALSO PROVIDE GREEN GROUND WIRE IN ALL BRANCH AND FEEDER CIRCUITS SIZED PER NEC. J. THE SPACE ABOVE THE CEILING IS LIMITED AND THE INSTALLATION OF WORK WILL BE TIGHT. DUE TO THIS, IT IS IMPORTANT THAT THE TRADE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF THEIR WORK (IE: DUCTWORK, TERMINAL UNITS, PIPING, ETC) WITH THE EXISTING CEILING SYSTEM HEIGHT AND CONSTRUCTION, THE STRUCTURAL SYSTEM, THE LIGHTING FIXTURES, THE SPRINKLER HEADS/MAINS, AND THE PLUMBING PIPES. ROUTE DUCTWORK AND PIPING AS HIGH AS POSSIBLE. LOCATE TERMINAL UNITS BETWEEN STRUCTURAL BEAMS AND MAINTAIN PROPER SERVICE ACCESS CLEARANCES. K. DO NOT INSTALL ANY NEW WORK DIRECTLY ABOVE ANY ELECTRICAL PANELS AND TRANSFORMERS. L. CIRCUIT NUMBERS SHOWN FOR EQUIPMENT WIRED TO EXISTING PANELBOARD(S) IS SHOWN FOR DESIGN INTENT ONLY AND MAY NOT CORRESPOND TO ACTUAL CIRCUIT BREAKER MOUNTING POSITION IN THE PANEL. UPDATE THE AS-BUILT DRAWINGS WITH THE ACTUAL CIRCUIT NUMBERS USED TO CORRESPOND TO THE PANEL DIRECTORY. M. CONFIRM ALL LABELS AND ROOM NUMBERS WITH OWNER PRIOR TO FINALIZING LABELING AND PROGRAMMING. N. COORDINATE FINAL OUTLET LOCATION WITH ALL TRADES AND FURNITURE/MILLWORK PLACEMENT PRIOR TO ROUGH-IN. O. INSTALL DATA OUTLETS 6" AWAY FROM ASSOCIATED ELECTRICAL OUTLET. P. PROVIDE DEDICATED NEUTRAL CONDUCTORS WITH EVERY SINGLE PHASE CIRCUIT. Q. ALL NEW FLOOR PENETRATIONS SHALL BE PROPERLY FIREPROOFED. ALL NEW WALL PENETRATIONS THROUGH FIRE-RATED WALLS (INCLUDING ICRA WALL) SHALL BE FIREPROOFED. R. FIREPROOF ALL PENETRATIONS LEFT BY CONDUITS REMOVED DURING DEMOLITION. ABBREVIATIONS A AMPERE AC ARMOR CLAD CABLE AFCI ARC-FAULT CIRCUIT INTERRUPTING AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AHJ AUTHORITY HAVING JURISDICTION AHU AIR HANDLING UNIT AIC AMPERE INTERRUPTING CAPACITY AL ALUMINUM AM AMMETER ANN ANNUNCIATOR ANSI AMERICAN NATIONAL STANDARDS INSTITUTE ATS AUTOMATIC TRANSFER SWITCH AV AUDIO VISUAL AWG AMERICAN WIRE GAUGE BAS BUILDING AUTOMATION SYSTEM BDF BUILDING DISTRIBUTION FRAME BFC BELOW FINISHED CEILING BFG BELOW FINISHED GRADE BKBD BACKBOARD BKR BREAKER BPS BOLTED PRESSURE SWITCH C CONDUIT CAT CATALOG CATV CABLE ANTENNA TELEVISION CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CEC CHICAGO ELECTRICAL CODE CKT CIRCUIT CLG CEILING CM CONSTRUCTION MANAGER CO COMPANY COAX COAXIAL CT CURRENT TRANSFORMER CTTS CLOSE TRANSITION TRANSFER SWITCH CU COPPER DC DIRECT CURRENT DD DUCT DETECTOR DHCP DYNAMIC HOST CONFIGURATION PROTOCOL DIA DIAMETER DIV DIVISION DN DOWN DO DRAWOUT DPDT DOUBLE POLE DOUBLE THROW DPST DOUBLE POLE SINGLE THROW DS DISCONNECT SWITCH DSP DIGITAL SIGNAL PROCESSOR DVD DIGITAL VERSATILE DISC DVR DIGITAL VIDEO RECORDER DVS DIGITAL VIDEO SURVEILLANCE DWG DRAWING EA EACH EF EXHAUST FAN EGS ENGINE-GENERATOR SET ELEC ELECTRIC ELEV ELEVATOR EMT ELECTRICAL METALLIC TUBING EO EQUIPMENT BY OWNER EOL END OF LINE DEVICE EQUIP EQUIPMENT EWC ELECTRIC WATER COOLER EXH EXHAUST EXP EXPLOSION PROOF FA FIRE ALARM FACU FIRE ALARM CONTROL UNIT FBO FURNISHED BY OWNER FI FILM ILLUMINATOR FLR FLOOR FLUOR FLUORESCENT FPS FRAMES PER SECOND FPU FIELD PROCESSING UNIT FS FUSED SWITCH FTL FEED THRU LUGS GA GAUGE Gb GIGABIT GE GROUNDING EQUALIZER CONDUCTOR GEN GENERATOR GFCI GROUND FAULT CIRCUIT INTERRUPTING GFI GROUND FAULT INTERRUPTING GFR GROUND FAULT RELAY GFRT GROUND FAULT RELAY TEST PANEL GRD GROUND HCT HARMONIC CONDITIONING TRANSFORMER HF HARMONIC FILTER HFT HARMONIC FILTER WITH INTEGRAL TRANSFORMER HID HIGH INTENSITY DISCHARGE HOA HAND OFF AUTO HP HORSEPOWER HST HARMONIC SUPPRESSION TRANSFORMER HSKPG HOUSEKEEPING HTR HEATER HV HIGH VOLTAGE HZ HERTZ (CYCLES/SECOND) ICC INTERMEDIATE CROSS CONNECT ID INSIDE DIAMETER IDF INTERMEDIATE DISTRIBUTION FRAME IMC INTERMEDIATE METAL CONDUIT IP INTERNET PROTOCOL IPS IMAGES PER SECOND iSCSI INTERNET SMALL COMPUTER SYSTEM INTERFACE IR INFRARED JB JUNCTION BOX KO KNOCK OUT KV KILOVOLT KVA KILOVOLT AMPERE KW KILOWATT KWH KILOWATT HOUR LA LIGHTNING ARRESTOR LAN LOCAL AREA NETWORK LCD LIQUID CRYSTAL DISPLAY LED LIGHT EMITTING DIODE LS LIFE SAFETY LTD LONG TIME DELAY LTG LIGHTING LV LOW VOLTAGE MAG MAGNETIC MAN MANUAL MAX MAXIMUM MATV MASTER ANTENNA TELEVISION Mb MEGABIT MC METAL CLAD CABLE MCA MINIMUM CIRCUIT AMPERES MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MCS MOLDED CASE SWITCH MCM THOUSANDS OF CIRCULAR MILS MCP MOTOR CIRCUIT PROTECTOR MDF MAIN DISTRIBUTION FRAME MDP MAIN DISTRIBUTION PANELBOARD MECH MECHANICAL MER MAIN EQUIPMENT ROOM MFGR MANUFACTURER MFS MAIN FUSED SWITCH MGP MEDICAL GAS PANEL MH MANHOLE MI MINERAL INSULATED CABLE MIC MICROPHONE MIN MINIMUM MLO MAIN LUGS ONLY MM MULTIMODE MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED MTS MANUAL TRANSFER SWITCH MV MEDIUM VOLTAGE N NEUTRAL NA NOT APPLICABLE NC NORMALLY CLOSED NEC NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NFPA NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NO NORMALLY OPEN NOC NETWORK OPERATIONS CENTER NTS NOT TO SCALE OA OUTSIDE AIR OC ON CENTER OCPD OVERCURRENT PROTECTIVE DEVICE OD OUTSIDE DIAMETER OH OVERHEAD P POLE PA PUBLIC ANNOUNCEMENT PB PULLBOX/PUSHBUTTON PC PERSONAL COMPUTER PCU PACKAGED CONTROL UNIT P/E PNEUMATIC- ELECTRIC PH PHASE PNL PANELBOARD PLC PROGRAMMABLE LOGIC CONTROLLER PoE POWER OVER ETHERNET PRI PRIMARY PSU PATIENT SERVING UNIT PT POTENTIAL TRANSFORMER PTZ PAN TILT ZOOM PVC POLYVINYL CHLORIDE PWR POWER RAID REDUNDANT ARRAY OF INDEPENDENT DISKS RCP REFLECTED CEILING PLANS RCPT RECEPTACLE RE REFER TO REF REFRIGERATOR RF RADIO FREQUENCY RF RETURN FAN RFID RADIO FREQUENCY IDENTIFICATION DEVICE RGS RIGID GALVANIZED STEEL RM ROOM RTLS REAL TIME LOCATION SYSTEM RUPS ROTARY HYBRID UNINTERRUPTIBLE POWER SUPPLY SCHED SCHEDULE SEC SECONDARY SF SUPPLY FAN SFL SUB FEED LUGS SFP SURGICAL FACILITY PANEL SH SHEET SM SINGLE MODE SP SINGLE POLE SPDT SINGLE POLE DOUBLE THROW SPST SINGLE POLE SINGLE THROW SPC SPACE SPEC SPECIFICATION SPKR SPEAKER SPR SPARE SS STAINLESS STEEL ST SHUNT TRIP STD SHORT TIME DELAY STP SHIELDED TWISTED PAIR STR STARTER SWBD SWITCHBOARD SWGR SWITCHGEAR SYM SYMMETRICAL TB TERRA BYTES TBB TELECOMMUNICATIONS BONDING BACKBONE TC TERMINAL CABINET TERM TERMINAL TEL TELEPHONE TGB TELECOMMUNICATIONS GROUNDING BUSBAR THD TOTAL HARMONIC DISTORTION TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR TR TELECOMMUNICATIONS ROOM TRANS TRANSITION TSER TELECOMMUNICATIONS SERVICE ENTRANCE ROOM TTC TELEPHONE TERMINAL CABINET TV TELEVISION TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION TYP TYPICAL UC UNDER COUNTER UG UNDERGROUND UNO UNLESS NOTED OTHERWISE UPS UNINTERRUPTIBLE POWER SUPPLY USS UNIT SUBSTATION UTP UNSHIELDED TWISTED PAIR V VOLT VAV VARIABLE AIR VOLUME VM VOLTMETER VolP VOICE OVER INTERNET PROTOCOL VPI VACUUM-PRESSURE IMPREGNATED VSD VARIABLE SPEED DRIVE W WATT WAN WIDE AREA NETWORK WAP WIRELESS ACCESS POINT WLAN WIRELESS LOCAL AREA NETWORK WP WEATHERPROOF XFMR TRANSFORMER GENERAL NEW EQUIPMENT EXISTING WORK DEVICE TO BE REMOVED (DEMO PLANS) UNDERFLOOR CONDUIT (NEW PLANS) MATCH LINE REFERENCING CONTINUATION ON OTHER DRAWINGS BRANCH CIRCUIT BOUNDARY WIRE AND/OR CONDUIT RUN CONTINUED ON REFERENCED DETAIL DETAIL AND/OR SECTION REFERENCE FUTURE WORK DRAWING NOTES AND DESIGNATIONS BRANCH VOLTAGE DROP CONDUCTOR AWG #12 #10 #8 MAXIMUM CONDUCTOR LENGTH AT 120V 95 160 245 MAXIMUM CONDUCTOR LENGTH AT 277V 225 375 565 MAXIMUM CONDUCTOR LENGTH AT 208V 1 PH. 170 280 425 MAXIMUM CONDUCTOR LENGTH AT 480V 1 PH. 390 650 985 GROUND CONDUCTOR AWG #12 #10 #8 NOTES: 1. INCREASE BRANCH CIRCUIT CONDUCTOR AS INDICATED. 2. TABLE BASED ON 20A CIRCUIT LOADED TO 10A USING SINGLE PHASE, 2 WIRE CIRCUITS. 3. SCHEDULE REPRESENTS MINIMUM CONDUCTOR SIZE BASED ON LENGTH OF BRANCH CIRCUIT CONDUCTOR FROM PANEL TO PHYSICAL CENTER OF LOAD TO OVERCOME VOLTAGE DROP. 3% VOLTAGE DROP ASSUMED. CABLE ROUTING NOTES X DRAWING KEYED NOTES X SYMBOL WITH TAIL INDICATES WALL INSTALLATION, HEIGHT AS INDICATED SYMBOL WITH DASHED OUTLINE INDICATES INSTALLATION AT CEILING EXISTING EQUIPMENT DESIGNATION (E) XXX X NEW EQUIPMENT DESIGNATION EQUIPMENT DESIGNATION NUMBER X WIRE AND CABLE SPLICE NUMBERS INDICATES SOURCE PANELBOARD AND CIRCUIT(S) 1LNL1-12 NEUTRAL WIRE SHOWN AS A LONG LINE, PHASE WIRE SHOWN AS SHORT LINES, AND GROUND WIRE SHOWN AS LONG LINE WITH DOT # # CIRCUIT NUMBER (AND PANELBOARD IF SPECIFICALLY DESIGNATED) POWER BRANCH CIRCUITS XXX # a XXX LUMINAIRE TAG - CORRESPONDS TO LUMINAIRE SCHEDULE # CIRCUIT NUMBER (AND PANELBOARD IF SPECIFICALLY DESIGNATED) a LOWER CASE LETTER(S) INDICATE MULTI-SWITCH CONTROL ARRANGEMENT. LIGHTING BRANCH CIRCUITS RACEWAY AND PATHWAY CONDUIT TURNED UP CONDUIT TURNED DOWN CAPPED CONDUIT CONDUIT STUBBED AND BUSHED INTO ACCESSIBLE CEILING CAVITY SERVICE WEATHERHEAD SINGLE CHANNEL SURFACE RACEWAY DUAL CHANNEL SURFACE RACEWAY TRIPLE CHANNEL SURFACE RACEWAY RACEWAY ROUTED DOWN FROM CEILING TO HORIZONTAL RACEWAY ROUTED UP FROM FLOOR TO HORIZONTAL CABLE TRAY, HUNG ABOVE CEILING OR AS NOTED WIRE BASKET, HUNG ABOVE CEILING OR AS NOTED MULTI-OUTLET ASSEMBLY, 6" ABOVE COUNTER BACKSPLASH OR AS NOTED BOXES AND CABINETS DEVICE BOX WITH BLANK COVER PLATE, HEIGHT AS INDICATED ON DWG B JUNCTION BOX J PULL BOX PB CABINET, TOP OF TRIM 6'-2" AFF POWER DISTRIBUTION METER SOCKET M PROTECTIVE RELAY (*INDICATES ANSI FUNCTION, NUMBER INDICATES QUANTITY) * MEDIUM VOLTAGE DRAWOUT POWER CIRCUIT BREAKER LOW VOLTAGE INTERRUPTER SWITCH MEDIUM VOLTAGE INTERRUPTER SWITCH POTENTIAL TRANSFORMER (NUMBER INDICATES QUANTITY) CURRENT TRANSFORMER (NUMBER INDICATES QUANTITY) LIGHTNING ARRESTOR NETWORK PROTECTOR CABLE LUGS PROVISIONS FOR FUTURE EXPANSIONS TRANSFORMER (SINGLE LINE DENOTATION) TRANSFORMERS T TRANSFORMER (PLAN DENOTATION) WIRING DEVICES SINGLE POLE SWITCH, 3'-8" AFF 2 2-POLE SWITCH, 3'-8" AFF 3 3-WAY SWITCH, 3'-8" M MOMENTARY CONTACT SWITCH, 3'-8" AFF NEMA 5-20R DUPLEX RECEPTACLE, 1'-6" AFF TWO (2) NEMA 5-20R DUPLEX RECEPTACLES INSTALLED UNDER COMMON COVERPLATE, 1'-6" AFF UNFUSED DISCONNECT SWITCH, SURFACE 3'-8" AFF, (5-0" AFF IN EQ ROOMS) XXAS/XXAF FUSED DISCONNECT SWITCH, SURFACE MOUNTED 3'-8" AFF, (5'-0" AFF IN EQ ROOMS). FUSED DISCONNECT SWITCH, "AS" INDICATES AMPERE RATING OF SWITCH AND "AF" INDICATES AMPERE RATING OF FUSE. BOLTED PRESSURE CONTACT SWITCH BPS XXAS XXAT # POLES CIRCUIT BREAKER (SINGLE LINE DENOTATION) XXAF FUSE (SINGLE LINE DENOTATION) LOW VOLTAGE DRAWOUT POWER CIRCUIT BREAKER PROTECTIVE DEVICES MOTOR CONNECTION. REFER TO EQUIPMENT CONNECTION MOTOR CONTROLLER SCHEDULE FOR SPECIFIC REQUIREMENTS T FRACTIONAL HORSEPOWER MOTOR CONTROLLER, RECESSED 3'-8" AFF OR ABOVE CEILING (MANUAL THERMAL SWITCH) MOTOR CONTROLLERS MOTOR CONTROLLER/DISCONNECT, 3'-8" AFF (5'-0" AFF IN EQ ROOMS) VARIABLE SPEED DRIVE VSD PANELBOARDS SHADING INDICATES BRANCH TYPE TEXT INDICATES LUG / BREAKER TYPE PANELBOARD (SINGLE LINE DENOTATION) NORMAL BRANCH PANELBOARD (LIFE SAFETY / NEC 517) - (EMERGENCY/ NEC 700) BRANCH PANELBOARD INTERIOR LIGHTING INDUSTRIAL STRIP LUMINAIRE GEOMETRIC SHAPE LUMINAIRE, RECESSED OR SURFACE (T) INDICATES WALL MOUNT STYLE LUMINAIRE INDICATES PENDANT HUNG STYLE LUMINAIRE DOWNLIGHT, ROUND OR SQUARE, RECESSED OR SURFACE LIGHTING TRACK WITH TRACK MOUNTED LUMINARIES SELF CONTAINED BATTERY LIGHTING UNIT REMOTE LIGHTING LAMP HEAD(S) LOW VOLTAGE CONTROL UNIT, RACK MOUNTED BATT LUMINAIRE CONNECTED TO LIFE SAFETY / NEC 517 EMERGENCY / NEC 700 BRANCH SINGLE LINE - SINGLE FACE (DIRECTION OF ARROWS AS INDICATED) DOUBLE LINE - DOUBLE FACE (DIRECTION OF ARROWS AS INDICATED) #XX - CORRESPONDS TO TABLE BELOW. #XX #XX #1 SINGLE FACE DOUBLE FACE TAG NO. SYMBOL FIRE ESCAPE DESCRIPTION TAG NO. SYMBOL DESCRIPTION #2 STAIRS/STAIRWAY #3 EXIT #4 FIRE ESCAPE #5 STAIR(S) #6 EXIT #7 FIRE ESCAPE #8 STAIR(S) #9 EXIT #10 FIRE ESCAPE #11 STAIR(S) #12 EXIT #14 14-1 FIRE ESCAPE 14-2 STAIR 14-3 EXIT #16 FIRE ESCAPE #17 STAIRS #18 EXIT #19 FIRE ESCAPE #20 STAIR(S) #21 EXIT #22 FIRE ESCAPE #23 STAIR(S) #24 EXIT ILLUMINATED "EXIT" SIGNAGE (CHICAGO) FIRE ALARM SYSTEMS DOOR HOLDER H STROBE LIGHT, 80" AFF V CITY STROBE LIGHT, MOUNT PER ARCHITECT RB HORN, 18" BELOW CEILING A FIRE ALARM SPEAKER S MANUAL PULL STATION, 3'-8" AFF S FIRE PHONE [JACK STATION], 3'-8" AFF FJ REMOTE TEST STATION RTS HEAT DETECTOR, RATING AS INDICATED ON PLANS, CEILING MOUNT D SMOKE DETECTOR, SURFACE CEILING MOUNTED SD DUCT SMOKE DETECTOR, DUCT INSTALLED DD SMOKE DETECTOR INDICATOR LIGHT, TOP EVEN WITH TOP OF DOOR FRAME RA BAS INTERFACE PANEL, TOP OF TRIM 6'-2" AFF BASP FIRE ALARM CONTROL PANEL, TOP OF TRIM 6'-2" AFF FACP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL, TOP OF TRIM 6'-2" AFF FAA VOICE CONTROL PANEL VCP SUPERVISORY ANNUNCIATOR PANEL SAA FIRE COMMAND CENTER, 5'-6" AFF,UNO FCC NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL, TOP OF TRIM 6'-2" AFF NAC PRE-SIGNAL CHIME PS CARBON MONOXIDE DETECTOR CO SUPERVISORY TAMPER SWITCH VSS WATERFLOW SWITCH WF ALARM CHECK VALVE (WATER FLOW SWITCH) AC DRY PIPE PRESSURE SWITCH DP ADDRESSABLE MONITOR MODULE DTU ADDRESSABLE RELAY MODULE DTU-R ADDRESSABLE CONTROL MODULE DTU-C FIRE PUMP PHASE REVERSAL FPPR FIRE PUMP RUN FPR FIRE PUMP CONTROLLER FPC DUCT DETECTOR TROUBLE BELL TB DD DATA GATHERING PANEL DGP SUPERVISORY CONTROL PANEL SCP CITY TIE TROUBLE BELL TB CT SUPERVISORY TROUBLE BELL TB VSS FIRE ALARM TROUBLE BELL TB FA POINT OF CONNECTION POINT OF DISCONNECTION SECURITY SYSTEMS VIDEO SURVEILLANCE CAMER - INTERIOR C1 CREDENTIAL READER CR ELECTROMAGNETIC DOOR LATCH RETRACTION ELR PANIC ALARM SWITCH/BOTTON - UNDER OF DESK MOUNTING PAS1 COMMUNICATIONS TELECOMMUNICATIONS OUTLET WITH BACKBOX AND CONDUIT, 1'-6" AFF TV, POWER AND COAXIAL CABLE WITH 2 VOICE DATA OUTLETS TV NURSE CALL SYSTEM SINGLE PATIENT STATION WITH STAFF EMERGENCY & PILLOW SPEAKER 1A DUAL PATIENT STATION 1B CODE BLUE 2A STAFF EMERGENCY STATION 2B TOILET EMERGENCY STATION 3A CORRIDOR DOME LIGHT - 1 LAMP 4A MASTER STATION DESK MOUNTED 5A CENTRAL EQUIPMENT. PROVIDE 120V CONNECTION 6A RELAY INTEFACE MODULE 6B Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing. This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled. Not published - All rights reserved. No. Date Issue Sheet Name Drawing No. Project Number Drawn Checked Proj. Arch./Eng. Project Name Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part. Department of Capital Planning & Policy Bureau of Asset Management AG TL Approver NOTES, LEGENDS, SYMBOLS AND ABBREVIATIONS E0001 Provident Hospital - Renal Dialysis Center 430 East 51st Place Chicago, Illinois 60615 15849 1 09/07/2018 ISSUED FOR BID
12
Embed
E0001 - Cook County Health...BKR BREAKER BPS BOLTED PRESSURE SWITCH C CONDUIT CAT CATALOG CATV CABLE ANTENNA TELEVISION CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CEC CHICAGO
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
'E' SERIES GENERAL NOTESA. ALL ELECTRICAL WORK SHALL CONFORM TO THE NATIONAL ELECTRIC CODE 2017 WITH CHICAGO
AMENDMENTS.
B. FOR EXACT LOCATION AND FINISH SURFACE CONDITIONS OF CEILING, WALL, FLOOR MOUNTED DEVICES, REFER TO ARCHITECTURAL DRAWINGS.
C. FOR EXACT LOCATION OF FACILITY EXPANSION JOINTS, FIRE RATED WALLS AND SMOKE WALLS, REFER TO ARCHITECTURAL DRAWINGS.
D. FOR EXACT LOCATIONS OF DUCT MOUNTED SMOKE DETECTORS, WATER FLOW SWITCHES AND TAMPER SWITCHES REFER TO HVAC / FP DRAWINGS.
E. VERIFY EXACT LOCATION OF CONNECTION POINTS PRIOR TO CONNECTION.
F. MOUNTING HEIGHTS ARE TO CENTER OF DEVICE OR EQUIPMENT, UNO.
G. PROVIDE RACEWAY, WIRE AND CABLE, ASSOCIATED FITTINGS AND CONNECTORS, AND COMPLETE CONNECTIONS REQUIRED FOR DESIGNATED BRANCH CIRCUITS FROM DEVICE(S) TO FINAL OVERCURRENT DEVICE AND TO LOCAL CONTROL DEVICE(S) PER SPECIFICATIONS.
H. MINIMUM BRANCH CIRCUIT WIRE SIZE SHALL BE #12 AWG EXCEPT LIFE SAFETY BRANCH CIRCUIT WIRING WHICH SHALL BE MINIMUM #10 AWG. MAINTAIN MAXIMUM BRANCH CIRCUIT CONDUCTOR LENGTHS AS PER SPECIFICATIONS AND SCHEDULED ON THIS DRAWING. INCLUDE GROUND CONDUCTOR DERATINGS.
I. PROVIDE GROUNDING PER NEC. ALSO PROVIDE GREEN GROUND WIRE IN ALL BRANCH AND FEEDER CIRCUITS SIZED PER NEC.
J. THE SPACE ABOVE THE CEILING IS LIMITED AND THE INSTALLATION OF WORK WILL BE TIGHT. DUE TO THIS, IT IS IMPORTANT THAT THE TRADE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF THEIR WORK (IE: DUCTWORK, TERMINAL UNITS, PIPING, ETC) WITH THE EXISTING CEILING SYSTEM HEIGHT AND CONSTRUCTION, THE STRUCTURAL SYSTEM, THE LIGHTING FIXTURES, THE SPRINKLER HEADS/MAINS, AND THE PLUMBING PIPES. ROUTE DUCTWORK AND PIPING AS HIGH AS POSSIBLE. LOCATE TERMINAL UNITS BETWEEN STRUCTURAL BEAMS AND MAINTAIN PROPER SERVICE ACCESS CLEARANCES.
K. DO NOT INSTALL ANY NEW WORK DIRECTLY ABOVE ANY ELECTRICAL PANELS AND TRANSFORMERS.
L. CIRCUIT NUMBERS SHOWN FOR EQUIPMENT WIRED TO EXISTING PANELBOARD(S) IS SHOWN FOR DESIGN INTENT ONLY AND MAY NOT CORRESPOND TO ACTUAL CIRCUIT BREAKER MOUNTING POSITION IN THE PANEL. UPDATE THE AS-BUILT DRAWINGS WITH THE ACTUAL CIRCUIT NUMBERS USED TO CORRESPOND TO THE PANEL DIRECTORY.
M. CONFIRM ALL LABELS AND ROOM NUMBERS WITH OWNER PRIOR TO FINALIZING LABELING AND PROGRAMMING.
N. COORDINATE FINAL OUTLET LOCATION WITH ALL TRADES AND FURNITURE/MILLWORK PLACEMENT PRIOR TO ROUGH-IN.
O. INSTALL DATA OUTLETS 6" AWAY FROM ASSOCIATED ELECTRICAL OUTLET.
P. PROVIDE DEDICATED NEUTRAL CONDUCTORS WITH EVERY SINGLE PHASE CIRCUIT.
Q. ALL NEW FLOOR PENETRATIONS SHALL BE PROPERLY FIREPROOFED. ALL NEW WALL PENETRATIONS THROUGH FIRE-RATED WALLS (INCLUDING ICRA WALL) SHALL BE FIREPROOFED.
R. FIREPROOF ALL PENETRATIONS LEFT BY CONDUITS REMOVED DURING DEMOLITION.
ABBREVIATIONSA AMPEREAC ARMOR CLAD CABLEAFCI ARC-FAULT CIRCUIT INTERRUPTINGAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHJ AUTHORITY HAVING JURISDICTIONAHU AIR HANDLING UNITAIC AMPERE INTERRUPTING CAPACITYAL ALUMINUMAM AMMETERANN ANNUNCIATORANSI AMERICAN NATIONAL STANDARDS INSTITUTEATS AUTOMATIC TRANSFER SWITCHAV AUDIO VISUALAWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEMBDF BUILDING DISTRIBUTION FRAMEBFC BELOW FINISHED CEILINGBFG BELOW FINISHED GRADEBKBD BACKBOARDBKR BREAKERBPS BOLTED PRESSURE SWITCH
C CONDUITCAT CATALOGCATV CABLE ANTENNA TELEVISIONCB CIRCUIT BREAKERCCTV CLOSED CIRCUIT TELEVISIONCEC CHICAGO ELECTRICAL CODECKT CIRCUITCLG CEILINGCM CONSTRUCTION MANAGERCO COMPANYCOAX COAXIALCT CURRENT TRANSFORMERCTTS CLOSE TRANSITION TRANSFER SWITCHCU COPPER
DC DIRECT CURRENTDD DUCT DETECTORDHCP DYNAMIC HOST CONFIGURATION PROTOCOLDIA DIAMETERDIV DIVISIONDN DOWNDO DRAWOUTDPDT DOUBLE POLE DOUBLE THROWDPST DOUBLE POLE SINGLE THROWDS DISCONNECT SWITCHDSP DIGITAL SIGNAL PROCESSORDVD DIGITAL VERSATILE DISCDVR DIGITAL VIDEO RECORDERDVS DIGITAL VIDEO SURVEILLANCEDWG DRAWING
EA EACHEF EXHAUST FANEGS ENGINE-GENERATOR SETELEC ELECTRICELEV ELEVATOREMT ELECTRICAL METALLIC TUBINGEO EQUIPMENT BY OWNEREOL END OF LINE DEVICEEQUIP EQUIPMENTEWC ELECTRIC WATER COOLEREXH EXHAUSTEXP EXPLOSION PROOF
FA FIRE ALARMFACU FIRE ALARM CONTROL UNITFBO FURNISHED BY OWNERFI FILM ILLUMINATORFLR FLOORFLUOR FLUORESCENTFPS FRAMES PER SECONDFPU FIELD PROCESSING UNITFS FUSED SWITCHFTL FEED THRU LUGS
HCT HARMONIC CONDITIONING TRANSFORMERHF HARMONIC FILTER HFT HARMONIC FILTER WITH INTEGRAL
TRANSFORMERHID HIGH INTENSITY DISCHARGEHOA HAND OFF AUTOHP HORSEPOWERHST HARMONIC SUPPRESSION TRANSFORMERHSKPG HOUSEKEEPINGHTR HEATERHV HIGH VOLTAGEHZ HERTZ (CYCLES/SECOND)
ICC INTERMEDIATE CROSS CONNECTID INSIDE DIAMETERIDF INTERMEDIATE DISTRIBUTION FRAMEIMC INTERMEDIATE METAL CONDUITIP INTERNET PROTOCOLIPS IMAGES PER SECONDiSCSI INTERNET SMALL COMPUTER SYSTEM
INTERFACEIR INFRARED
JB JUNCTION BOX
KO KNOCK OUTKV KILOVOLTKVA KILOVOLT AMPEREKW KILOWATTKWH KILOWATT HOUR
LA LIGHTNING ARRESTORLAN LOCAL AREA NETWORKLCD LIQUID CRYSTAL DISPLAYLED LIGHT EMITTING DIODELS LIFE SAFETYLTD LONG TIME DELAYLTG LIGHTING LV LOW VOLTAGE
MCA MINIMUM CIRCUIT AMPERESMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMCS MOLDED CASE SWITCHMCM THOUSANDS OF CIRCULAR MILSMCP MOTOR CIRCUIT PROTECTORMDF MAIN DISTRIBUTION FRAMEMDP MAIN DISTRIBUTION PANELBOARDMECH MECHANICALMER MAIN EQUIPMENT ROOMMFGR MANUFACTURERMFS MAIN FUSED SWITCHMGP MEDICAL GAS PANELMH MANHOLEMI MINERAL INSULATED CABLEMIC MICROPHONEMIN MINIMUMMLO MAIN LUGS ONLYMM MULTIMODEMOCP MAXIMUM OVERCURRENT PROTECTIONMTD MOUNTEDMTS MANUAL TRANSFER SWITCHMV MEDIUM VOLTAGE
N NEUTRALNA NOT APPLICABLENC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATIONNFPA NATIONAL FIRE PROTECTION ASSOCIATIONNIC NOT IN CONTRACTNO NORMALLY OPENNOC NETWORK OPERATIONS CENTERNTS NOT TO SCALE
OA OUTSIDE AIROC ON CENTEROCPD OVERCURRENT PROTECTIVE DEVICEOD OUTSIDE DIAMETEROH OVERHEAD
P POLEPA PUBLIC ANNOUNCEMENTPB PULLBOX/PUSHBUTTONPC PERSONAL COMPUTERPCU PACKAGED CONTROL UNITP/E PNEUMATIC- ELECTRICPH PHASEPNL PANELBOARDPLC PROGRAMMABLE LOGIC CONTROLLERPoE POWER OVER ETHERNETPRI PRIMARYPSU PATIENT SERVING UNITPT POTENTIAL TRANSFORMERPTZ PAN TILT ZOOMPVC POLYVINYL CHLORIDEPWR POWER
RAID REDUNDANT ARRAY OF INDEPENDENT DISKSRCP REFLECTED CEILING PLANSRCPT RECEPTACLERE REFER TOREF REFRIGERATORRF RADIO FREQUENCYRF RETURN FANRFID RADIO FREQUENCY IDENTIFICATION DEVICERGS RIGID GALVANIZED STEELRM ROOMRTLS REAL TIME LOCATION SYSTEMRUPS ROTARY HYBRID UNINTERRUPTIBLE POWER
SUPPLYSCHED SCHEDULESEC SECONDARYSF SUPPLY FANSFL SUB FEED LUGSSFP SURGICAL FACILITY PANELSH SHEETSM SINGLE MODESP SINGLE POLESPDT SINGLE POLE DOUBLE THROWSPST SINGLE POLE SINGLE THROWSPC SPACESPEC SPECIFICATIONSPKR SPEAKERSPR SPARESS STAINLESS STEELST SHUNT TRIPSTD SHORT TIME DELAYSTP SHIELDED TWISTED PAIRSTR STARTERSWBD SWITCHBOARDSWGR SWITCHGEARSYM SYMMETRICAL
TB TERRA BYTESTBB TELECOMMUNICATIONS BONDING BACKBONETC TERMINAL CABINETTERM TERMINALTEL TELEPHONETGB TELECOMMUNICATIONS GROUNDING BUSBARTHD TOTAL HARMONIC DISTORTIONTMGB TELECOMMUNICATIONS MAIN GROUNDING
BUSBARTR TELECOMMUNICATIONS ROOMTRANS TRANSITIONTSER TELECOMMUNICATIONS SERVICE ENTRANCE
ROOMTTC TELEPHONE TERMINAL CABINETTV TELEVISIONTVSS TRANSIENT VOLTAGE SURGE SUPPRESSIONTYP TYPICAL
UC UNDER COUNTERUG UNDERGROUNDUNO UNLESS NOTED OTHERWISEUPS UNINTERRUPTIBLE POWER SUPPLYUSS UNIT SUBSTATIONUTP UNSHIELDED TWISTED PAIR
V VOLTVAV VARIABLE AIR VOLUMEVM VOLTMETERVolP VOICE OVER INTERNET PROTOCOLVPI VACUUM-PRESSURE IMPREGNATEDVSD VARIABLE SPEED DRIVE
W WATTWAN WIDE AREA NETWORKWAP WIRELESS ACCESS POINTWLAN WIRELESS LOCAL AREA NETWORKWP WEATHERPROOF
XFMR TRANSFORMER
GENERALNEW EQUIPMENT
EXISTING WORK
DEVICE TO BE REMOVED (DEMO PLANS) UNDERFLOOR CONDUIT (NEW PLANS)
MATCH LINE REFERENCING CONTINUATION ON OTHER DRAWINGS
BRANCH CIRCUIT BOUNDARY
WIRE AND/OR CONDUIT RUN CONTINUED ON REFERENCED DETAIL
DETAIL AND/OR SECTION REFERENCE
FUTURE WORK
DRAWING NOTES AND DESIGNATIONS
BRANCH VOLTAGE DROP
CONDUCTOR AWG #12 #10 #8
MAXIMUM CONDUCTOR LENGTH AT 120V 95 160 245MAXIMUM CONDUCTOR LENGTH AT 277V 225 375 565MAXIMUM CONDUCTOR LENGTH AT 208V 1 PH. 170 280 425MAXIMUM CONDUCTOR LENGTH AT 480V 1 PH. 390 650 985GROUND CONDUCTOR AWG #12 #10 #8
NOTES:
1. INCREASE BRANCH CIRCUIT CONDUCTOR AS INDICATED.
2. TABLE BASED ON 20A CIRCUIT LOADED TO 10A USING SINGLE PHASE, 2 WIRE CIRCUITS.
3. SCHEDULE REPRESENTS MINIMUM CONDUCTOR SIZE BASED ON LENGTH OF BRANCH CIRCUIT CONDUCTOR FROM PANEL TO PHYSICAL CENTER OF LOAD TO OVERCOME VOLTAGE DROP. 3% VOLTAGE DROP ASSUMED.
CABLE ROUTING NOTESX
DRAWING KEYED NOTESX
SYMBOL WITH TAIL INDICATES WALL INSTALLATION, HEIGHT AS INDICATED
SYMBOL WITH DASHED OUTLINE INDICATES INSTALLATION AT CEILING
EXISTING EQUIPMENT DESIGNATION(E) XXX
X
NEW EQUIPMENT DESIGNATION
EQUIPMENT DESIGNATION NUMBER
X
WIRE AND CABLE
SPLICE
NUMBERS INDICATES SOURCE PANELBOARD AND CIRCUIT(S)1LNL1-12
NEUTRAL WIRE SHOWN AS A LONG LINE, PHASE WIRE SHOWN AS SHORT LINES, ANDGROUND WIRE SHOWN AS LONG LINE WITH DOT
# # CIRCUIT NUMBER (AND PANELBOARD IF SPECIFICALLY DESIGNATED)
POWER BRANCH CIRCUITS
XXX#
a
XXX LUMINAIRE TAG - CORRESPONDS TO LUMINAIRE SCHEDULE # CIRCUIT NUMBER (AND PANELBOARD IF SPECIFICALLY DESIGNATED) a LOWER CASE LETTER(S) INDICATE MULTI-SWITCH CONTROL ARRANGEMENT.
LIGHTING BRANCH CIRCUITS
RACEWAY AND PATHWAYCONDUIT TURNED UP
CONDUIT TURNED DOWN
CAPPED CONDUIT
CONDUIT STUBBED AND BUSHED INTO ACCESSIBLE CEILING CAVITY
SERVICE WEATHERHEAD
SINGLE CHANNEL SURFACE RACEWAY
DUAL CHANNEL SURFACE RACEWAY
TRIPLE CHANNEL SURFACE RACEWAY
RACEWAY ROUTED DOWN FROM CEILING TO HORIZONTAL
RACEWAY ROUTED UP FROM FLOOR TO HORIZONTAL
CABLE TRAY, HUNG ABOVE CEILING OR AS NOTED
WIRE BASKET, HUNG ABOVE CEILING OR AS NOTED
MULTI-OUTLET ASSEMBLY, 6" ABOVE COUNTER BACKSPLASH OR AS NOTED
BOXES AND CABINETSDEVICE BOX WITH BLANK COVER PLATE, HEIGHT AS INDICATED ON DWGB
JUNCTION BOXJ
PULL BOXPB
CABINET, TOP OF TRIM 6'-2" AFF
POWER DISTRIBUTION
METER SOCKETM
PROTECTIVE RELAY (*INDICATES ANSI FUNCTION, NUMBER INDICATES QUANTITY)*
MEDIUM VOLTAGE DRAWOUT POWER CIRCUIT BREAKER
LOW VOLTAGE INTERRUPTER SWITCH
MEDIUM VOLTAGE INTERRUPTER SWITCH
POTENTIAL TRANSFORMER (NUMBER INDICATES QUANTITY)
CURRENT TRANSFORMER (NUMBER INDICATES QUANTITY)
LIGHTNING ARRESTOR
NETWORK PROTECTOR
CABLE LUGS
PROVISIONS FOR FUTURE EXPANSIONS
TRANSFORMER (SINGLE LINE DENOTATION)
TRANSFORMERST TRANSFORMER (PLAN DENOTATION)
WIRING DEVICESSINGLE POLE SWITCH, 3'-8" AFF
2 2-POLE SWITCH, 3'-8" AFF
3 3-WAY SWITCH, 3'-8"
M MOMENTARY CONTACT SWITCH, 3'-8" AFF
NEMA 5-20R DUPLEX RECEPTACLE, 1'-6" AFF
TWO (2) NEMA 5-20R DUPLEX RECEPTACLES INSTALLED UNDER COMMON COVERPLATE, 1'-6" AFF
PANIC ALARM SWITCH/BOTTON - UNDER OF DESK MOUNTINGPAS1
COMMUNICATIONSTELECOMMUNICATIONS OUTLET WITH BACKBOX AND CONDUIT, 1'-6" AFF
TV, POWER AND COAXIAL CABLE WITH 2 VOICE DATA OUTLETSTV
NURSE CALL SYSTEMSINGLE PATIENT STATION WITH STAFF EMERGENCY & PILLOW SPEAKER1A
DUAL PATIENT STATION1B
CODE BLUE2A
STAFF EMERGENCY STATION2B
TOILET EMERGENCY STATION3A
CORRIDOR DOME LIGHT - 1 LAMP4A
MASTER STATION DESK MOUNTED5A
CENTRAL EQUIPMENT. PROVIDE 120V CONNECTION6A
RELAY INTEFACE MODULE6B
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
Department of Capital Planning & Policy
Bureau of Asset Management
AG
TL
Approver
NOTES, LEGENDS, SYMBOLS
AND ABBREVIATIONS
E0001
Provident Hospital - Renal
Dialysis Center
430 East 51st PlaceChicago, Illinois 60615
15849
1 09/07/2018 ISSUED FOR BID
OS
VS
OS
VS
OS
VS VS
VS VS
VS
OS
OS
VS
PC
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS OS
RACK
RACK
OS
321
5
A
B
C
D
E1F1B
E1F1B
E1F1B
E1F1B
E1F1A
E1F1A
E1F1B
E1F1A
E1F1A
1F1A
1F1A
E1F1B
E1F1B
E1F1A
E5F9
5F92
F5
E5F2
E5F2
E7F3
E7F3
E7F3
1F3
1F3
1F3
1F3
5F4
5F4
E5F4
5F4
E5F4
5F4
5F4
E7F4
5F4
E7F4
5F4
5F4
E7F4
5F4
E7F4
5F4
E3F7
E3F7
E3F7
E7F3
E7F3
E7F3
1F1A
1F1A
1F2
1F2
1F10
1F10
1F12
SOILEDSTORAGE
118
CLEANSUPPLY
119
EQUIP.REPAIR
120
STORAGE
122
LAB
121
ELECTRICAL
123 MECHANICAL
124
W.C.
117A
NURSESTATION
116A
TREATMENTAREA
116
SOCIALWORKER
104
DIETITIAN
103
VESTIBULE
100A
RECEPTION
105
EXAM
106
PAT. TOILET
114
MED. PREP.
115
CONFERENCE
102
WAITINGROOM
101
WOMENS
107
MENS
108
OFFICE
109DIRECTOR
OFFICE
110
TELECOM
111 STAFFTOILET
113B
JANITOR'SCLOSET
112
CHANGINGROOM
113A
STAFF
113
CORRIDOR
100D
OS
VS
OS
D
OS
#3
#3
#3
#3
OS
WATERTREATMENT
125
#21
#21
#6
#3
VS VS
VS VSOS
OS
E9X
E9X
E9
E9X
E9X
E9X
E9X
E9X
1F3
1F3
LP
3F2
3F2
3F2
3F9
3F9
3F3
3F3
3F2
3F2
3F7
3F2
3F7
3F7
3F2
3F7
EP
2F2
2F2
2F2
2F1
2F1
2F2
2F2
2F2
2F9
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F1B
E1F9
E1F8
3F8
E1F1B
2F4
2F6
3F7
E1F7
2F8
2F8
1F8
1F8
1F8
1F8
E1F7
E1F7
ALL EXTERIOR LIGHTS TO REMAIN
EXTERIOR LIGHT POLE WITH CAMERAS TO REMAIN
EXISTING PHOTOCELL
#21
E9X
a
E1a
a
a
a a
a
a
E1a
D
b
E1b
D
c
E1c
D
d
E1d
D
e
E1e
D
f
E1f
g
D
E1g
h
D
E1h
j
D
E1j
D
D
E1k
k
D
E1m
m
D
E1n
n
D
E1p
p
a
a
a
a a
a
E9X
#3
3W
3Wa
a
a
1a1b
bb
bb
a
1cc
c d1d
1fff
1h
h
h
1g
g
g
a
a
5a3W
5a3W
aa
3a
aaa
a
3dd
c
3c
b
3b
f
3f
f
g
3g3h
h
j
j
j
k
3k 3j
k
k
1
1
1
1
1
1
E7a
aa
a a
a a
2a
a
2b
b
2c
c
E1c
c
c
c
m
2m
m
n
n
2n
p
E1p
E1c
q q
E1q
s
s
ss
s
s
r
r
r
rr
a
a
a
2s
r rr
5r
s
r
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
Department of Capital Planning & Policy
Bureau of Asset Management
AG
TL
Approver
LEVEL 01 LIGHTING PLAN
E0101
Provident Hospital - Renal
Dialysis Center
430 East 51st PlaceChicago, Illinois 60615
15849
SHEET NOTES:
1/4" = 1'-0"E0101
1 LEVEL 01 LIGHTING PLAN
A. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR ADDITIONAL INFORMATION AND EXACT LOCATION OF LUMINARIES.
B. CONFIRM EXACT LOCATION OF ALL LIGHT SWITCHES AND CONTROLS DEVICES WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN.
C. ALL NORMAL LUMINARIES SHALL BE CONNECTED TO BRANCH PANELBOARD "LP" U.N.O.
D. ALL EMERGENCY LUMINAIRES SHALL BE CONNECTED TO NEW BRANCH PANELBOARD "EP" U.N.O.
E. WHERE MULTIPLE SWITCHES ARE GROUP TOGETHER AT A SINGLE LOCATION, ALL SWITCHES SHALL BE INSTALLED UNDER A COMMON FACEPLATE.
F. REFER TO DRAWING E0601 FOR LUMINAIRE SCHEDULE AND NOTES.
G. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL OCCUPANCY AND VACANCY SENSORS.
H. CONFIRM EXACT MOUNTING OF EXIT SIGNS WITH ARCHITECT PRIOR TO ORDERING.
1 09/07/2018 ISSUED FOR BID
2 09/13/2018 ADDENDUM #1
1. PROVIDE EMERGENCY BALLAST IN THIS LIGHT FIXTURE.
KEYED NOTES:
HNL2442LPHONHCG10 HNL2442RPHONHCG10
HN
L231628PBBF
HO
N
HCG10
HNL231628PBBFHONHCG10
0.0000001HUMHUMEC
0.0000001HUMHUMEC
0.0000001HUMHUMEC
W
EST
0.0000001HUMHUMEC
S
taff 113
Staff 113
S
taff 113
S
taff 113
Staff 113
S
taff 113
J JJ J
JJ
JJ
321
5
A
B
C
D
WATERTREATMENT
125
CABINET CABINET
WOMENS
107 MENS
108
OFFICE
109
STAFF
113
STAFFTOILET
113B
TELECOM
111
JANITOR'SCLOSET
112
CORRIDOR
100B
SOILEDSTORAGE
118
STORAGE
122
LAB
121
MECHANICAL
124
ELECTRICAL
123
W.C.
117A
CLEANSUPPLY
119
8
CONFERENCE
102
SOCIALWORKER
104
DIRECTOROFFICE
110
EXAM
106
EQUIP.REPAIR
120
1
2
3
4
5
6 7
9
10
11
12MED. PREP.
115
PAT. TOILET
114
RECEPTION
105
DIETITIAN
103
WAITINGROOM
101
NURSESTATION
116A
TREATMENTAREA
116
CHANGINGROOM
113A
CORRIDOR
100C
CORRIDOR
100D
PRIVATEPAT./ISOLATION
117
VESTIBULE
100A
1LP
PP3
PP2PP1
MDP
U/CREF
U/CREF
U/CREF
GFI
GFI
GFIGFI
GFI
GFI
EP
DIALYSISMACH.
DIALYSISMACH.
DIALYSISMACH.
DIALYSISMACH.
DIALYSISMACH.
DIALYSISMACH.
DIALYSISMACH.
DIALYSISMACH.
DIALYSISMACH.
DIALYSISMACH.
DIALYSISMACH.
E19
1'-6"AFF
E19
1'-6"AFF
E19
1'-6"AFF
E18
1'-6"AFF
E18
1'-6"AFF
E18
1'-6"AFF
E21
1'-6"AFF
6" ABOVECOUNTER
E21
GFI
1
PP2
3
PP2
1
PP2
3
PP2
3
PP2
5
PP2
7
PP2
5
PP2
7
PP2
5
PP2
7
PP29
PP2
9
PP2
9
PP2
19
PP2 19
PP2
19
PP2
19
PP2
4
PP2
21
PP2
4
PP2
21
PP2
4
PP2
21
PP2
4
PP3
17
PP3
6
PP3
9
PP2
1
PP2
15
PP2
15
PP2
15
PP2
15
PP2
15
PP2
6
PP2
10
PP22
PP2
POWEREXAMTABLE
17
PP2
6
PP2
6
PP2
17
PP2
17
PP2
8
PP2
8
PP2
11
PP2
11
PP2
E21
1'-6"AFF
11
PP2 31
PP2 13
PP2
31
PP2
31
PP2
11
PP2
12
PP3
14
PP3
14
PP3
9
PP3
1
PP3
7
PP3
2
PP3
15
PP3
15
PP3
15
PP3
15
PP3
11
PP3
13
PP3
25
PP2
2
PP3
2
PP3
2
PP3
2
PP3
10
PP3
2
PP3
19
PP3
10
PP3
10
PP3
COPIER, PRINTERMULT.
MICROWAVE
REFRIGERATOR, FREEZER
2
PP3
E20
SCALE,INTEGRATED
GFI, 6" ABOVECOUNTER
8
PP3
GFI, 6" ABOVECOUNTER
GFI, 6" ABOVECOUNTER
DIALYSISMACH.
E23 E23E21
17
PP2
17
PP2
8
PP2
7
PP1
10
PP3
10
PP3
ATS-1
8
PP3GFI, 6" ABOVECOUNTER
11
PP2
23
PP2
E15
EP
E14
EP
E17
EP
E16
EP
E12
EPE13
EP
E10
EPE11
EP
E8
EP
E6
EP
E2
EP
E4
EP
AV
5
PP3
10
PP3
GFI
VAV-8
CUH-3
H-1
34
PP2
11
PP2
E25
EP
3
PP3
2
PP2
3
14
PP2
VAV-16
16,18
PP2VAV-15
28,30
PP2
VAV-9
1
PP1
VAV-7
38,40,42
PP2VAV-1
2
PP1
VAV-10
32
PP2
VAV-11
33
PP2VAV-12
13,15,17
PP1
VAV-13
19,21,23
PP1
VAV-4
4,6
PP1
VAV-6
29,31
PP1
VAV-5
32
PP1
VAV-2
33
PP1
VAV-14
15
PP3
EF-6
2
PP3
GFI
20
PP3
18
PP3
16
PP3
8
PP2
9
PP2
GFI
LCP
15
PP3
GFI
1
PP2 GFI
19
PP2GFI
15
PP2
11
PP2
E0401
1
E0401
3
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
Department of Capital Planning & Policy
Bureau of Asset Management
AG
TL
WH
LEVEL 01 POWER PLAN
E0201
Provident Hospital - Renal
Dialysis Center
430 East 51st PlaceChicago, Illinois 60615
15849
A. ALL CIRCUIT SHOWN SHALL BE WIRED TO BRANCH PANELBOARDS INDICATED ON PLAN.
B. SEE ARCHITECTURAL DRAWINGS FOR MOUNTING TYPE OF DEVICES, HEIGHT AND DETAILS. ALL LOCATIONS SHALL BE CONFIRMED WITH ARCHITEC PRIOR TO ROUGH-IN.
C. PROVIDE FIRE STOPPING AT ALL FIRE RATED WALLS AND PARTITIONS.
D. SEE HVAC AND PLUMBING DRAWINGS FOR EXACT LOCATION OF HVAC AND PLUMBING EQUIPMENT.
E. ALL RECEPTACLES SHALL BE MOUTED VERTICALLY EXCEPT ABOVE CONTERTOPS WHERE THEY SHALL BE MOUNTED HORIZONTALLY.
F. SEE FURNISHINGS, FITTINGS AND REQUIREMENT PLAN FFE 2-1 AND OWNER REQUIREMENT SCHEDULE Q1-1 FOR EXACT REQUIREMENT FOR TREATMENT AREA.
SHEET NOTES:
1/4" = 1'-0"E0201
1 LEVEL 01 POWER PLAN
1. PROVIDE NEW TWO SECTIONS PANEL.
2. INTERCEPT (4) 4" INCOMING TELECOME FIBER CONDUITS AND EXTEND ABOVE CEILING TO NEW 24"X24"x8" JUNCTION BOX. EXTEND CONDUITS FROM NEW JUNCTIONBOX TO NEW IT ROOM LOCATION AS INDICATED ON DRAWINGS. TERMINATE NEWCONDUITS 82" AFF. PROVIDE GROUND BUSHING ON EACH CONDUIT.
3. PROVIDE NEW ATS. SEE ONE-LINE DIAGRAM FOR MORE INFOMATION.
KEYED NOTES :
1 09/07/2018 ISSUED FOR BID
2 09/13/2018 ADDENDUM #1
HNL2442LPHONHCG10 HNL2442RPHONHCG10
HN
L231628PBBF
HO
N
HCG10
HNL231628PBBFHONHCG10
0.0000001HUMHUMEC
0.0000001HUMHUMEC
0.0000001HUMHUMEC
W
EST
0.0000001HUMHUMEC
S
taff 113
Staff 113
S
taff 113
S
taff 113
Staff 113
S
taff 113
V V
VSS
J
PP
PP
PP
J
FA
CP
CR
C1
C1
CR
C1
C1
PAS1
C1
PAS1
ELR
PAS1
ELR
PAS1
ELR
CR
C1
CR
EL
C1
CR
TV
TV
TV
TV
TV
TVTVTV
TV
TV
TV
TV
TV
TV
TV
TV
TV
V A
V A
V A
V
V
V
V
A
V
V
J
180180
180
180
180
180
180
180
180 J
180180
180180 180180
180
18
0
180
3A
3A
4A
4A
5A
FAA
V A
A
V
A
V
V
V
V
A
V
A
VA
V A
DR
ML
WAP
WAP WAP
WAP WAP
WAP
WAP
V
EL
EL
PP
A
321
5
A
B
C
D
AV
WOMENS
107
MENS
108OFFICE
109
STAFF
113STAFFTOILET
113B
TELECOM
111
JANITOR'SCLOSET
112
CORRIDOR
100B
SOILEDSTORAGE
118
STORAGE
122
LAB
121
MECHANICAL
124
ELECTRICAL
123
W.C.
117A
WATERTREATMENT
125
CLEANSUPPLY
119
8
CONFERENCE
102
SOCIALWORKER
104
DIRECTOROFFICE
110
EXAM
106
EQUIP.REPAIR
120
1
2
3
4
5
6 7
9
10
11
12
MED. PREP.
115
PAT. TOILET
114
RECEPTION
105
DIETITIAN
103
WAITINGROOM
101
NURSESTATION
116A
TREATMENTAREA
116
CHANGINGROOM
113A
CORRIDOR
100C
CORRIDOR
100D
PRIVATEPAT./ISOLATION
117
VESTIBULE
100A
LP EP
TIME CLOCKFIRE ALARM DOOR CONTROL RELAY
PROVIDE (4) 3" DIAMETER FIRE RATED SLEEVES THROUGH WALL
W
W
W
12"x4" 12"x4"12"x4"
12"x4"
12"x4"
12"x4"
1
E0401
2
2
W
W
W
W
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
Department of Capital Planning & Policy
Bureau of Asset Management
AG
TL
Approver
LEVEL 01 SYSTEMS PLAN
E0301
Provident Hospital - Renal
Dialysis Center
430 East 51st PlaceChicago, Illinois 60615
158491/4" = 1'-0"
1LEVEL 01 SYSTEMS PLAN
SHEET NOTES:
A. SEE ARCHITECTURAL DRAWINGS FOR MOUNTING OF ELECTRICAL DEVICES. ALL LOCATIONS SHALL BE CONFIRM WITH ARCHITECT PRIOR TO ROUGH-IN.
B. ALL FIRE ALARM SYSTEM WIRING SHALL BE IN CONDUIT.
C. ALL TELECOMMUNICATION WORK SHALL CONFIRM WITH UCM INFORMATION TECHNOLOGY SERVICE (ITS) CABLING GUIDELINES AND SPECIFICATIONS.
D. ALL DATA/VOICE CABLES SHALL BE INSTALLED IN CONDUIT TO BASKET TRAY. CONDUITS SHALL SERVICE ONLY (1) INFORMATION OUTLET. NO DAISY CHANGING OR LOOPING BETWEEN INFORMATION OUTLETS IS ALLOWED. 4-11/16 INCH X 4-11/16 INCH ELECTRICAL BOX SHALL BE INSTALLED WITH A SINGLE GANG TRIM RING.
E. ALL WALL PHONE LOCATION SHALL MEET ALL ADA HEIGHT REQUIREMENTS.
F. ITS STANDARD STYLE IS BASKET TRAY WITH A MINIMUM DIMENSIONS OF 12 INCH WIDE AND 4 INCH DEEP.
G. THE BASKET TRAY SHALL HAVE A MINIMUM SIX (6) INCHES OF CLEARANCE ON ALL SIDES.
H. COMMUNICATION CONDUIT SHALL NOT RUN CONTINUOUSLY OF MORE THAN 100 FEET BEFORE INSTALLING A PULL BOX.
I. COMMUNICATION CONDUITS SHALL NOT EXCEED MORE THAN THREE (3) 90-DEGREE BENDS WITHOUT A PULL BOX.
J. ELECTRICAL CONTRACTOR SHALL PROVIDE PULL STRING ON ALL EMPTY CONDUITS.
K. CONTRACTOR SHALL PROVIDE ALL CONDUIT BACKBOXES FOR ALL LOW-VOLTAGE SYSTEMS.
L. PROVIDE CONDUIT PROVISIONS FOR ALL SECURITY DEVICES.
M. CABLE TRAY SHALL HAVE 12 INCHES ON CLEARENCE ON ALL SIDES.
N. FIELD COORDINATE EXACT ROUTE OF CABLETRAY WITH MECHANICAL DUCTS, PLUMBING SYSTEM, LIGHTING FIXTURES AND OTHER TRADES PRIOR TO ANY INSTALLATION.
KEYED NOTES :
1. INTERCEPT (4) 4" INCOMING CONDUITS AND EXTEND ABOVE CEILING TO NEW 24"X24"X8" JUNCTION BOX. EXTEND CONDUITS FROM NEW JUNCTION BOX TO NEW IT ROOM LOCATION AS INDICATED ON DRAWINGS. TERMINATE NEW CONDUITS 82" AFF. PROVIDE GROUND BUSHING ON EACH CONDUIT.
2. PROPOSED LOCATION OF (4) 4" CONDUIT. FIELD COORDINATE EXACT ROUTE OF CONDUIT WITH MECHANICAL DUCTS. PLUMBING SYSTEMS, LIGHTING FIXTURES
1 09/07/2018 ISSUED FOR BID
2 09/13/2018 ADDENDUM #1
LEGEND:
WALL PHONEW
321
5
A
B
C
D
TE-5
TE-2
TE-4
23
PP3
EF-2
21
PP3
EF-5
23
PP3
EF-4
23
PP3
EF-3
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
1" GRS CONDUIT CONCRETE ENCASED FOR BATTERY CHARGER.
1" GRS CONDUIT CONCRETE ENCASED FOR JACKET HEATER.
1" GRS GENERATOR START SIGNAL
1" GRS CONDUIT CONCRETE ENCASED FOR REMOTE FIRE ALARM ANNUN.
GENERATOR STUB-UP CONDUITS
2
3
LCP
B
C
AUTO CW BY-PASS
WATER LEAK CONTROL PANEL
TWIST LOCK, HUBBELL 2320 FOR THE FEED WATER BOOSTER PUMP
WATER SOFTENER
CARBON FILTER
DISCONNECT SWITCH FOR CWP-104H
OVER TEMPERATURE ALARM
CWP-PT
E38
EP
WH-1A
E38
EP
E38
EPE35,37,39
EP
TWRP-1
HWRP-1CWP-104H
E45
EP
EF-2
ACID CONCENTRATE DELIVERY SYSTEM
BICARBONATE MIX AND DISTRIBUTION SYSTEM
JUNCTION BOX FOR REMOTE
22,24,26
PP2
E44
EPE40
EPE33
EPE28
EPE30
EP
E43
EP
E22
EP
E41
EP
E26
EP
E24
EP
CUH-1
6'-8
"2
'-7
"4
'-5
"2
'-10
"2
'-6
"
6'-9"10'-11 3/8"
WATERTREATMENT
125
3'-9
"8
"3
'-2
"
1
GFI GFI GFI GFI GFI GFI
GFI
GFI
GFI
GFI
GFI
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
Department of Capital Planning & Policy
Bureau of Asset Management
Checker
Author
Approver
ELECTRICAL ENLARGED PLANS
E0401
Provident Hospital - Renal
Dialysis Center
430 East 51st PlaceChicago, Illinois 60615
15849
2 09/13/2018 ADDENDUM #1
1/2" = 1'-0"E0401
2 ENLARGED TELECOM ROOM 111
TELECOM ROOM 111 - KEYED NOTES :
1. TELECOMMUNICATION GROUND BUS.
2. 7'H X 19"W COMMUNICATION RACK, REFER TO UCM TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS.
3. PROVIDE 8'W X 8'H X 3/4" FIRE RETARDANT TREATED PLYWOOD. INSTALL AS TO SHOW THE FIRE RATING OF BACKBOARD, DO NOT PAINT OVER FIRE-RATING STAMP.
4. CONTRACTOR SHALL PROVIDE VERTICAL AND HORIZONTAL CABLE MANAGEMENT AS REQUIRED.
5. MINIMUM CEILING HEIGHT SHALL BE 8 FEET 6 INCHES AND NOT CEILING IS TO BE INSTALLED.
6. CABLE TRAY, LADDER RACK EQUIPMENT RACK AND CABINETS SHALL BE GROUNDED/BOUNDED TO THE TELECOMMUNICATION GROUND BUS (TGB). MINIMUM SIZE BC ( BONDING CONDUCTOR) OF 6 AWG SHALL BE USED.
7. PROVIDE AND INSTALL HORIZONTAL CONDUIT PENETRATIONS UTILIZE "EZ-PATH CONDUIT ROUTING OF WIRE THRU FIRE-RATED WALL.
TELECOM ROOM 111- NOTES:
A. ALL MATERIALS AND INSTALLATION SHALL COMPLY WITH UCM TELECOMMUNICATION STRUCTURAL CABLING GUIDELINES AND SPECIFICATIONS.
B. CONTRACTOR TO PROVIDE CONDUIT BUSHINGS AND FIRESTOP AT ALL INCOMING TELECOMMUNICATION AND PHONE CONDUITS.REFER TO E0301 FOR PROPOSED CONDUIT ROUTE.
1/4" = 1'-0"E0401
3 ENLARGED ELECTRICAL ROOM 123 & GENERATOR
ELECTRICAL ROOM 123 & GENERATOR KEYED NOTES :
1. CONTRACTOR TO FURNISH AND PROVIDE 6" CONCRETE PAD GENERATOR, COORDINATE WITH GENERATOR MANUFACTURER FOR EXACT DIMENSIONS, TOTAL WEIGHT & LOCATION OF STUB-UPS CONDUIT PRIOR TO ANY INSTALLATION.
2. ALL BURIED INCOMING CONDUITS SHALL BE INSTALL WITH REQUIRED CONDUIT SLOPE OUT OF BUILDING. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH ALL EXISTING UNDERGROUND UTILITIES.
3. PROPOSED LOCATION OF STUB-UPS CONDUITS.
1/2" = 1'-0"1
ENLARGED WATER TREATMENT ROOM 125
1'-11"11"2'-10" 6" 4'-3"3'-6"3'-9"
WATER TREATMENT ROOM 125 - NOTE:
A. WATER TREATMENT EQUIPMENT LAYOUT AND FINAL CONFIGURATION PENDING SELECTION OF WATER TREATMENT SYSTEM.
B. ALL ELECTRICAL OUTLETS, SWITCHED OUTLETS, SAFETY DISCONNECTS, JUNCTION BOXES, AND POWER SUPPLIED TO EQUIPMENT IS SUPPLIED AND INSTALLED BY E.C UNLESS NOTED OTHERWISE. INSTALL ALL AFOREMENTIONED ITEMS 6'-6" A.F.F. UNLESS NOTED OTHERWISE.
WATER TREATMENT ROOM 125 - KEYED NOTES :
1. THE TWIST LOCK REQUIRES 208/230V, 1PH, 60 HZ POWER. THE TWIST LOCK IS TO BELOCATED 6'-0" A.F.F.
Stephanie_D
Rectangle
Stephanie_D
Snapshot
EXISTING MAIN DISTRIBUTION BOARD "MDP" 800A, 208/120V, 3 PH, 4W + GROUND, 60 MHZ, COOPER BUS
COMED SERVICE 4 KV,
3 PH, 3W
M
100A/3P 400A/3P
800AF/800AT
100A/3P 225A/3P225A/3P
CP
RTU-1
LP PP1 PP2 PP3
CT'S
EXISTING COMED PAD MOUNTED TRANSFORMER
4160V-208/120V
M
FCP
20 HPFIRE
PUMP
EXISTING (2) SETS OF 4#500 KCMIL, 1#2/0 GRD IN 3 1/2"C
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
GN
EXISTING #2/0 IN 1" RGSC
EXISTING GROUND ROD
EXISTING #2/0 IN 1" RGSCCONNECTION TO WATER MAIN
EXISTING
SPACE
FACP
G
150AT150AF
3P
EP150A MB
208/120V
3PH, 4W.
ATS-1
N E
L
NEW STANDBY 45 KVA, 208/120V, 3PH NATURAL GASGENERATOR
1" GRS CONDUIT CONCRETE ENCASED FOR REMOTE FIRE ALARM ANNUN.
1#6 GRD 3/4" GRSC.
FACP(ROOM P116)
FPC
FAA
4 PAIR #22 AWG, 3/4"CTO TELEPHONE TERMNALBOARD IN ROOM P117
V
A
V
A
VSSVSSVSSVSSVSSVSSVSSVSS
AAVVVVVVV
AA
B
3/4"C - 4#10 TO RYAN BOXDD
WF
VVV
A
VV
A
VVV
A
VV
A
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
Department of Capital Planning & Policy
Bureau of Asset Management
AG
TL
Approver
POWER RISER DIAGRAMS
E0521
Provident Hospital - Renal
Dialysis Center
430 East 51st PlaceChicago, Illinois 60615
15849
NTS1
ELECTRICAL ONE LINE RISER DIAGRAM
NTS2
FIRE ALARM RISER DIAGRAM (EXISTING)
1 09/07/2018 ISSUED FOR BID
2 09/13/2018 ADDENDUM #1
KEYED NOTES :
1. PROVIDED CIRCUIT BREAKER AS INDICATED. NEW CIRCUIT BREAKER TYPE SHALL MATCH EXISTING MANUFACTURER.
2. PROVIDE NATURAL GAS GENERATOR TO SUPPLY ELECTRICAL POWER AT 208Y/120V, 60HZ, 3-PHASE.
3. PROVIDE 150A, 4P, 208V CLOSED TRANSITION, AUTOMATIC TRANSFER SWITCH. REFER TO ELECTRICAL FLOOR PLAN FOR EXACT LOCATION
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
Department of Capital Planning & Policy
Bureau of Asset Management
AG
TL
Approver
LIGHTING SCHEDULES
E0601
Provident Hospital - Renal
Dialysis Center
430 East 51st PlaceChicago, Illinois 60615
15849
3. ALL EMERGENCY FIXTURES SHALL BE PROVIDED WITH INTEGRAL BATTERY UNIT. REFER TO ELECTRICAL LIGHTING PLAN.
2. THE FINAL FIXTURE HOUSING AND REFLECTOR FINISH SHALL BE SELECTED BY ARCHITECT.
1. REFER TO ARCHITERUAL PLANS FOR ADDITIONAL INFORMATION, MOUNTING HEIGHT/ORIENTATION AND CONSTRUCTION MATERIAL.
TROFFER LED LUMINAIREDRIVER LED LED 120V 38W RECESSED 1,2,3
FAIL-SAFE ENC-24-2-LD2-39-35K-CA125-UNVF1B
RECESSED WAVESTREAM 2X2 LED
LUMINAIRE WITH HOUSING /GRID
GASKET AND ACRYLIC LENSESDRIVER LED LED 120V 42W RECESSED 1,3
FAIL-SAFE ENC-24-4-LD2-45-35K-CA125-UNVF1A
RECESSED WAVESTREAM 2X4 LED
LUMINAIRE WITH HOUSING /GRID
GASKET AND ACRYLIC LENSESDRIVER LED LED 120V 47W RECESSED 1,3
FAIL-SAFE MAE-G-2-LD4-120V-2-LOW/LOW-35-ED1D-1F1
RECESSED 2X4 LED LUMINAIRE WITH
EXAM AND AMBIENT LIGHTINGDRIVER LED LED 120V 53W RECESSED 1,2,3
TYPE QTY. TYPE WATTSTAG DESCRIPTION MANUFACTURER MODEL
BALLAST LAMP LAMPVOLTAGE
FIXTUREMOUNTING NOTES
LUMINAIRE FIXTURE SCHEDULE
1 09/07/2018 ISSUED FOR BID
2 09/13/2018 ADDENDUM #1
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
Department of Capital Planning & Policy
Bureau of Asset Management
AG
TL
Approver
POWER SCHEDULES
E0621
Provident Hospital - Renal
Dialysis Center
430 East 51st PlaceChicago, Illinois 60615
15849
Remarks:
*Demand factor applied as outlined in Articles 220, 430, and 440 of the National Electrical Code
Total Demand (A): 12
Total Connected (A): 10
LITES 222 VA 125.00% 278 VA Total Demand Load (VA): 4,271
Spare 1596 VA 100.00% 1596 VA Total Connected Load (VA): 3,734
D. ENCLOSURE SELECTION FOR STARTERS AND DISCONNECT SWITCH TO BE AS FOLLOW:
AC POWER. COORDINATE EXACT LABELING REQUIREMENTS WITH OWNER AND DIVISION 23.
C. CONTRACTOR SHALL PROVIDE A LABEL ON ALL MECHANICAL EQUIPMENT DISCONNECT DEVICES INDICATING EQUIPMENT NAME, VOLTAGE, CIRCUIT NUMBER AND SOURCE OF
B. PROVIDE ALL 24 VOLT CONTROL WIRING IN CONDUIT PER MANUFACTURER'S WIRING DIAGRAMS AND RECOMMENDATIONS.
AND 2 SETS OF NORMALLY OPEN AND 2 SETS OF NORMALLY CLOSED CONTACTS TO ALLOW CONTROL OF EQUIPMENT BY LOW VOLTAGE SIGNAL FROM TEMPERATURE CONTROL CONTRACTOR U.O.N.
A. ALL 3-PHASE STARTERS THAT ARE TO BE PROVIDED BY DIVISION 16 SHALL BE FULL VOLTAGE, NON-REVERSING TYPE AND H-O-A (HAND-OFF-AUTO) SWITCH WITH LED INDICATING LIGHTS, 120V CONTROL TRANSFORMER
GENERAL NOTES:
FEED WATER BOOSTER PUMP WATER TREATMENT ROOM 208/3 3#12, 1 #12 GND IN 3/4" C EP (SEC 2) 2.0 1.5 6
CWP-104H PUMP WATER TREATMENT ROOM 208/3 4#6, 1 #10 GND IN 1" C EP (SEC 2) - - - 60 - E.C.
CUH-1 CABINET UNIT HEATER WATER TREATMENT ROOM 208/3 3#12, 1 #12 GND IN 3/4" C PP-1 5.7 - - - - - MC
VAV-16 VARIABLE AIR VOLUME SEE MECH PLANS 120/1 2#12, 1 #12 GND IN 3/4" C PP-2 2.0 - - M.C. - - M.C.
VAV-15 VARIABLE AIR VOLUME SEE MECH PLANS 208/1 2#12, 1 #12 GND IN 3/4" C PP-2 3.0 - - M.C. - - M.C.
VAV-14 VARIABLE AIR VOLUME SEE MECH PLANS 120/1 2#12, 1 #12 GND IN 3/4" C PP-2 2.0 - - M.C. - - M.C.
VAV-13 VARIABLE AIR VOLUME SEE MECH PLANS 208/3 3#12, 1 #12 GND IN 3/4" C PP-2 5.5 - - M.C. - - M.C.
VAV-12 VARIABLE AIR VOLUME SEE MECH PLANS 120/1 2#12, 1 #12 GND IN 3/4" C PP-2 1.0 - - M.C. - - M.C.
VAV-11 VARIABLE AIR VOLUME SEE MECH PLANS 120/1 2#12, 1 #12 GND IN 3/4" C PP-2 1.5 - - M.C. - - M.C.
VAV-10 VARIABLE AIR VOLUME SEE MECH PLANS 120/1 2#10, 1 #10 GND IN 3/4" C PP-1 2.5 - - M.C. - - M.C.
VAV-9 VARIABLE AIR VOLUME SEE MECH PLANS 208/1 2#12, 1 #12 GND IN 3/4" C PP-1 4.0 - - M.C. - - M.C.
VAV-7 VARIABLE AIR VOLUME SEE MECH PLANS 120/1 2#12, 1 #12 GND IN 3/4" C PP-1 2.0 - - M.C. - - M.C.
VAV-6 VARIABLE AIR VOLUME SEE MECH PLANS 208/1 2#12, 1 #12 GND IN 3/4" C PP-1 3.5 - - M.C. - - M.C.
VAV-5 VARIABLE AIR VOLUME SEE MECH PLANS 208/1 2#12, 1 #12 GND IN 3/4" C PP-1 3.5 - - M.C. - - M.C.
VAV-4 VARIABLE AIR VOLUME SEE MECH PLANS 208/3 3#12, 1 #12 GND IN 3/4" C PP-1 5.5 - - M.C. - - M.C.
VAV-2 VARIABLE AIR VOLUME SEE MECH PLANS 120/1 2#10, 1 #10 GND IN 3/4" C PP-1 2.5 - - M.C. - - M.C.
VAV-1 VARIABLE AIR VOLUME SEE MECH PLANS 208/3 3#12, 1 #12 GND IN 3/4" C PP-1 6.0 - - M.C. - - M.C.
EF-6 EXHAUST FAN ROOF 120/1 2#12, 1 #12 GND IN 3/4" C PP-3 1/8 FVNR - E.C. - - E.C. PROVIDE WALL SWITCH
EF-5 EXHAUST FAN ROOF 120/1 2#12, 1 #12 GND IN 3/4" C PP-3 1/8 FVNR - E.C. - - M.C.
EF-4 EXHAUST FAN ROOF 120/1 2#12, 1 #12 GND IN 3/4" C PP-3 1/15 FVNR - E.C. - - M.C.
EF-3 EXHAUST FAN ROOF 120/1 2#12, 1 #12 GND IN 3/4" C PP-3 1/20 FVNR - E.C. - - M.C.
EF-2 EXHAUST FAN ROOF 120/1 2#12, 1 #12 GND IN 3/4" C PP-3 1/15 FVNR - E.C. - - M.C.
TAG PHASE BRANCH CCT. FROM KVA HP FLA TYPE NEMA SIZE PROVIDED BY SIZE FUSE PROV. BY
1. PROVIDE 3" PREMANUFACTURED FIRE-RATED ASSEMBLY, OF QUANTITIES PER SPECIFICATIONS, AT ALL FIRE-RATED WALLS FOR PASSING CABLING ABOVE. ACCESSIBLE CEILING.
2. FIRE-RATED WALL. CONTINUES TO DECK ABOVE. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS.
3. ACCESSIBLE CEILING.
3
1
2
BONDING (GROUND) CONDUCTOR
FIRE STOP GANG PLATE ATTACH TO STUDS WITH MOUNTING SCREWS
CABLE
CABLE TRAY
WALL ASSEMBLY
FIRE RATED ASSEMBLY SPARES FOR FUTURE CABLE. MINIMUM TWO SPARES
FIRE RATED ASSEMBLIES QUANTITY AS REQUIRED FOR 40% OF CABLE FILL
KEYED NOTES :
1. VARY LENGTH TO MEET APPLICATION REQUIREMENTS OF LISTED COMPRESSIONS TWO-HOLE LUGS.
ELECTRO-TIN PLATED COPPER
7/16" DIA INSULATION MOUNTING HOLES
PREDRILLED 5/16" DIA (TYP)
SUPPORT
INSULATOR
ELECTRO-TIN PLATED COPPER
2"
MIN
.
SUPPORT
Ø0.44"
INSULATOR
5.8
".
6.7
5".
SUPPORT
12" MIN.2
" M
IN.
.25".
1".
1
.
1.125" (TYP)
.
PREDRILLED 7/16" DIA (TYP)
. .
1.125" (TYP)
. . . .
1.125" (TYP)
. ..
2".
.625
" (T
YP
)
.
1".
1".
1/2
".
RGS OR IMC
PVC CONDUIT
PVC TO RIGID ADAPTER
WRAP ALL JOINTS 100% WATERTIGHT
FINISHED FLOOR
THREADED CAP ON ALL SPARESTO COUPLING, PULLBOX, PANELBOX, ETC. AS SHOWN OR REQUIRED
TYPICAL-SEAL VAPOR BARRIER TO CONDUIT
TYPICAL-TIE REBARS WITH #3 BARS
RGS OR IMC
TYPICAL #4 REBARS 6" O.C. ALL AROUND
TYPICAL-CONCRETE BLOCKS. LENGTH AS REQUIRED
KEYED NOTES :
1. AT EACH CONDUIT STUB-UP, AFFIX ENGRAVED PLASTIC NAMEPLATE INDICATING CONDUIT NO. OR CIRCUIT IDENTIFICATION. ATTACH WITH NYLON CABLE TIE.
1
SECTION TYPE LABEL
1LNL2
FED FROM: XXXXXXXXX ROOM # XXXXXXX
5C
FED FROM: XXXXXXXXX ROOM # XXXXXXX
B-SWBDN-1
1LNL1
208/120 VOLT SYSTEMPHASE A - BLACKPHASE B - REDPHASE C - BLUE
7"
1"
1 1/2"
RESERVED FOR(FUTURE) BARCODING
EQUIPMENT IDENTIFICATION LABEL
(1/2" & 1/8" TEXT)
1"
3"
CUBICLE LABEL(1/2" & 1/4" TEXT)
PROTECTIVE DEVICELOAD LABEL SAMPLE
(1/4" TEXT)
3/4"
2"
VOLTAGE LABEL SAMPLE(1/4" BLACK TEXT ON ORANGE)
3"
4"
2"
AS REQUIRED
ASSEMBLY NAMEPLATE SAMPLE(1/2" & 1/8" TEXT)
FED FROM TEXT FOR ELECTRICALDISTRIBUTION EQUIPMENT ONLY
EMERGENCY
ILSLI-3
3-ILSLI
"RED" RECEPTACLE (ON GENERATOR) (FRONT VIEW)NORMAL POWER RECEPTACLE(FRONT
VIEW)
KEYED NOTES :
1. LASER OR MECHANICALLY ENGRAVED ONTO WALL PLATE.
2. METAL TAG ON DEVICE SCREW.
3. SELF-ADHESIVE LABEL ON BACK OF WALL PLATE COVER.
PNLBD : ILNLI
CKT # : 3
1
1
2
3
FOR FLUSH MOUNTED PANELBOARDS IN FINISHED SPACES (INCLUDING ISOLATED POWER PANELBOARDS)
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
MOUNT TO WALL. OFFSET FROM WALL TO AS REQUIREDTO SUPPORT CONDUITS ADJACENT TO BEAM AND CONDUIT PENETRATIONS IN FLOOR.
No. OF
DUCTS
DUCT
SIZE A B
2 4" 17" 10"
12"19"5"2
17"17"4"4
19"19"5"4
17"24"4"6
19"27"5"6
17"31"4"8
19"35"5"8
9 4" 24" 24"
27"27"4"9 3A/3B
3A/3B
4A/2B
4A/2B
3A/2B
3A/2B
2A/2B
2A/2B
2A/1B
2A/1B
(A/B DUCTS)
CONFIG.
ELEVATION
FINISHED GRADE
CONCRETE
SPACERS
4" OR 5" CONDUITS
BEDDING
NOTE:
USE SIMILAR SPACINGS FOR CONFIGURATIONS NOT IDENTIFIED.
3". 3". 3".
±A
3".
6".
3".
CO
VE
R
30"
MIN
IUM
±B
KEYED NOTES :
1. CEILING MOUNTED WIRELESS ACCESS POINT. SECURE TO CEILING AND TILE SUPPORT BRACKET.
2. UTP PATCH CABLE.
3. ROUTE CABLING IN J-HOOKS IN OPEN ACCESSIBLE CEILINGS OR IN EMT CONDUIT IN INACCESSIBLE AREAS.
ACCESSIBLE CEILING
1
2
3
W1
EMERGENCY
ENGRAVED LAMACOID PLATE
WALL MOUNT MUSHROOM PUSH-BUTTON WITH KEY RESET SWITCH.
KEYED NOTES :
1. PROVIDE CONNECTION TO STRUCTURED CABLING SYSTEM FOR OPERATION OVER VolP TELEPHONE SYSTEM.
2. COORDINATE INSTALLATION AND OPERATION WITH TELEPHONE SYSTEM INSTALLER AND OWNER.
1
2
SECURED SIDE
CEILING
HINGES (TYP)
NOTE:COORDINATE WORK WITH DIVISION 8 AND DIVISION 28
KEYED NOTES :
1. 3/4" FLEXIBLE CONDUIT WITH PULL STRING.
2. HOLE (CENTERED IN BOX).
3. SECURITY OVERRIDE DEVICE LOCATED IN PANIC BAR. (PROVIDED BY DIV. 8, CONNECTED BY DIV. 26.) OPTIONAL
4. 1-GANG HINGE MORTAR GUARD BOX WELDED TO FRAME AT HEIGHT OF ELECTRIC POWER TRANSFER HINGE.
5. CARD READER 2-GANG JUNCTION BOX. LOCATED ON EXTERIOR SIDE OF DOOR AS SHOWN ON DRAWINGS. CUT AND MOUNT CARD READER FLUSH IN EXTERIOR WALL. COORDINATE INSTALLATION OF MULLION MOUNTED DEVICE WITH DIVISION 8 AS SHOWN ON FLOOR PLANS.
6. MORTAR GUARD BOX FOR FLUSH MAGNETIC DOOR CONTACT BY DIV. 26. 3/4" HOLE IN DOOR FRAME AND TOP OF DOOR BUCK BY DIVISION 8.
7. ROUTE THROUGH ALUMINUM FRAME AT STOREFRONT/CURTAIN WALL LOCATIONS AS REQUIRED.
8. MOUNT DEVICES ON SECURE SIDE OF DOOR.
9. ENCLOSURE SHALL CONTAIN READER INTERFACE MODULE AND POWER SUPPLY FOR DOOR DEVICES.
10. INTERCOM 2-GANG JUNCTION BOX LOCATED ON EXTERIOR SIDE OF DOOR AS SHOWN ON DRAWINGS. CUT AND MOUNT INTERCOM FLUSH IN EXTERIOR WALL. PATCH BRICK AS REQUIRED.
11. BUSHED 3/4"C TO CABLE TRAY SYSTEM WITH PULL STRING.
12. SECURE J-HOOK TO STRUCTURE. SUPPORT CABLING IN J-HOOKS ABOVE SUSPENDED CEILING TO NETWORK CONTROLLER.
1211
9
8
7
3
4 4 5
1
2
1 E
J
DC 6
SOD
10
44
" A
FF
6".
CONCEAL AND SUPPORT 12" O.C. FLEXIBLE METAL CONDUIT. ROUTE IN MILLWORK. COORDINATE ROUTING WITH FURNITURE/ MILLWORK PROVIDER.
INSTALL DURESS BUTTON ON DESK [SIDE OR BOTTOM] AS REQUIRED.COORDINATE WITHFURNITURE PROVIDERAND OWNER.
KEYED NOTES :
1. COORDINATE OPERATION WITH SECURITY SYSTEM INSTALLER AND OWNER.
2. LATCH HOLD-UP SWITCH.
3. EXTEND PLENUM RATED CABLE TO SECURITY SYSTEM.
2
1
3
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
SINGLE DOOR WITH CARD READER AND INTERCOM1/8" = 1'-0"
6TYPICAL DURESS BUTTON - DESK MOUNTED
ISP
V V V
V
V
VSS
WF
VSS
FPFFPR
FPPR
A
V
A
V
AV
A
V
J
PP
J
PP
PP
J
J
PP
PP
PP
J
PP
PP
J
J
JJ
C1
C1
C1C1
J
J
S S
SS
SS
C1
C1
CR
CR
EL
C1
KP
CR
EL
C1
C1
S
C1
C1
C1
FA
CP
WAPWAP
V
A
J
J
J
J
J
180180
180
180
180
180
180
180
180 J
180180
180180 180180
180
18
0
180
J
ML
PC
J J
AV
1
J
J
J
JJ
JJ
321
A
B
C
D
321
5
A
B
C
D
LP
PP3
PP2PP1
EMERGENCYDURESS BUTTON
EMERGENCYDURESS BUTTON
EMERGENCYDURESS BUTTON
EMERGENCYDURESS BUTTON
MDP
WOMENS
107
MENS
108
OFFICE
109
STAFF
113
JANITOR'SCLOSET
112
MECHANICAL
124
ELECTRICAL
123
MOTORFOR
COUNTERDOOR
MOTORFOR
COUNTERDOOR
MOTORFOR
COUNTERDOOR
MOTORFOR
COUNTERDOOR
MOTORFOR
COUNTERDOOR
MOTORFOR
COUNTERDOOR
CUH-1
BP-1
DWH-1
2
1 1
3
3
3
3
3
3
3
3
3
4
EXISTING TO REMAIN EMERGENCY DURESS CALL STATION
EXISTING TO REMAIN EMERGENCY DURESS CALL STATION
EXIST. WP, GFI, RECEPTACLE ALL EXTERIOR LIGHTS TO REMAIN
ALL EXTERIOR LIGHTS TO REMAIN
ALL EXTERIOR CAMERAS TO REMAIN
EXTERIOR LIGHT POLE WITH CAMERAS TO REMAIN
EXISTING COMED METER FOR FIRE PUMP
EXISTING COMED METER CABINET
EXISTING PHOTOCELL
LCP
LPA
EWC-1
FP-1
CUH-2
VAV-1
H-2
VAV-3
VAV-4
VAV-5
VAV-6
VAV-7
H-1
VAV-8
VAV-2-EXIST
5
5
5 5
AC-1
CUH-3
JOCKEYPUMP
FIRE PUMPCONTROL
PANEL
AIR DRYER
BALL VALVE
AC-1
EWC-2
6
RACK
W
7
8
GFI
3
3
3
3
3
EF
EF
EF
25,27PP1
9,11PP1
26,28,30PP1
8,10,12PP1
14,16,18PP1
Holabird & Root, LLC expressly disclaims any responsibility arising from any unauthorized use of these plans, drawings and notes. Any authorization must be in writing.
This drawing copy may have been reproduced at a size different than originally drawn. The Owner and Architect assume no responsibility for use of incorrect scale. Drawings are not to be scaled.
Not published - All rights reserved.
No. Date Issue
Sheet Name
Drawing No.
Project Number
Drawn
Checked
Proj. Arch./Eng.
Project Name
Notice: This drawing has not been published and is the sole property of Cook County. It is loaned to the borrower for their confidential use only. In consideration of the loan of this drawing, the borrower promises and agrees to return it upon request and agrees that it shall not be reproduced, copied, loaned, or otherwise disposed of directly or indirectly, nor used for any purpose other than for which it is furnished, in whole or part.
Department of Capital Planning & Policy
Bureau of Asset Management
Checker
TL
Approver
LEVEL 01 DEMOLITION PLAN
ED101
Provident Hospital - Renal
Dialysis Center
430 East 51st PlaceChicago, Illinois 60615
15849
1. EXISTING ELECTRICAL EQUIPMENT IN THIS ROOM TO REMAIN UNLESS NOTED OTHERWISE.
2. REMOVE ALL TECHNOLOGY INFRUSTRUCTURE FROM THIS AREA AND RETURN TO OWNER FOR OWNER'S DISPENSATION. NOTIFY OWNER OF SCHEDULED DEMOLITION OF THIS SPACE TO ALLOW ADEQUATE TIME FOR CCHS TECHNOLOGY DIVISION TO REMOVE SENSITIVE EQUIPMENT PRIOR TO COMMENCEMENT.
3. DISCONNECT EXISTING MECHANICAL EQUIPMENT AND REMOVE ALL ASSOCIATED CONDUIT AND CONDUCTORS. SEE MECHANICAL DEMOLITION DRAWINGS FOR ADDITIONAL INFORMATION.
4. DISCONNECT AND REMOVE ALL LIGHT FIXTURES, LIGHTING CONTROL SWITCHES, EMERGENCY BATTERY UNITS INCLUDING REMOTE HEADS & EXIT SIGNS. UNLESS NOTED OTHERWISE.
5. ALL EXISTING EXTERIOR CAMERAS TO BE REMAIN.
6. EXISTING INCOMMING TELECOMMUNICATION AND TELEPHONE CABLING IN (4) 4" RGSC. REFER TO E0301 FOR FURTHER INFORMATION.
7. CONTRACTOR SHALL CUT FLUSH AND CAPPED ALL STUB-UP CONDUITS, REMOVE ALL LOV-VOLTAGE CABLING.
8. ELECTRICAL CONTRACTOR SHALL TRACE AND LOCATE DIRECT BURIED CONDUIT EMININATING FROM EXTERIOR POLE WITH CAMERAS ATTACHED. CONTRACTOR SHALL INTERCEPT CONDUIT DEDICATED FOR LOW-VOLTAGE CABLING AND PROVIDE A PULL BOX AND CONDUIT SHALL BE EXTEND TO CABLE TRAY. REFER TO E0301 FOR EXACT LOCATION OF CABLE TRAY.
KEYED NOTES :
A. ELECTRICAL CONTRACTOR SHALL REVIEW ALL PERTINENT DOCUMENTS AND DRAWINGS TO VERIFY THE EXTENT OF THE DEMOLITION WORK. ELECTRICAL CONTRACTOR SHALL SURVEY EXISTING SITE TO DETERMINE THE EXTENT OF THE NECESSARY REMOVALS, REPAIRS AND RELOCATIONS TO AVOID CONFLICTS WITH NEW CONSTRUCTION. DISCUSS ANY DISCREPANCIES WITH THE OWNER.
B. FOR ALL ELECTRICAL EQUIPMENT AND DEVICES TO BE REMOVED, ALL CONDUIT, CONDUCTOR AND CABLE SHALL BE REMOVED COMPLETELY BACK TO THE SOURCE. EXISTING CONDUITS SHALL BE REMOVED,
C. THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL EXISTING HANGERS AND SUPPORTS ASSOCIATED WITH EXISTING RACEWAYS TO BE REMOVED.
D. COORDINATE SEQUENCING AND EXECUTION OF DEMOLITION WORK WITH THE OWNER AND OTHER TRADES.
E. THE ELECTRICAL CONTRACTOR SHALL BECOME FAMILIAR WITH THE STAGING OF THE WORK. PROVIDE TEMPORARY LIGHTING AND POWER (IF REQUIRED) FOR ALL TRADES DURING ALL STAGES OF THE CONSTRUCTION.
F. REMOVE ALL ELECTRICAL DEVICES ON OR IN EXISTING WALLS, CEILINGS AND PARTITIONS WHICH ARE TO BE DEMOLISHED. REMOVE ALL EXPOSED PORTIONS OF BRANCH CIRCUIT AND CONTROL VOLTAGE WIRING AND CONDUITS BACK TO SOURCE.
G. EXISTING BUILDING EXTERIOR LIGHT FIXTURES SHALL REMAIN IN CONTINUOUS AND UNINTERRUPTED OPERATION DURING THIS RENOVATION WORK, INCLUDING EXISTING ASSOCIATED HELD CONTACTOR AND EXTERIOR PHOTOCELL.
GENERAL DEMOLITION NOTES:
1/4" = 1'-0"ED101
1 LEVEL 01 DEMOLITION - LIGHTING, POWER & SPECIAL SYSTEMS