Service ■ Single-phase, three-wire, 120/240V AC ■ Three-phase, four-wire, 208Y/120V AC■ Three-phase, three-wire, 240V AC delta
Short Circuit Current Rating ■ 10,000 AIC: All single- and three-phase loadcenters 70 through 225 amperes, 8 to 42 circuits.
■ 22,000 AIC: All convertible loadcenters using 125 amperes rated Type BRH main breakers or selected factory installed 125 ampere rated Type BRH main breaker.
■ 25,000 AIC: All convertible and factory installed single-phase loadcenters rated 150 and 200 amperes using Type BWH main breakers.
Convertible Loadcenters ■ Main Breaker: Single-phase up to 200 amperes and three-phase up to 100 amperes■ Main Lugs: Single-phase up to 200 amperes and three-phase up to 125 amperes
Branch Breakers ■ Types BR, BRH, and BRH: 10 to 125 amperes. One-, two-, and three-pole. Selected amperages available in switching duty, HACR, shunt trip, and high magnetic setting.
■ Type GFCB: 15 to 50 amperes.One- and two-pole ground fault breakers.
■ Types BJ, and BJH: 125 to 225 amperesTwo- and three-pole.
■ Type BD Twin: 10 to 50 amperesTwo of one-pole. Take one 1-inch (25.4 mm) space.
■ Type BQ and BQC Multibreaker: 15 to 30 amperes. Two of two-pole or one two-pole and two one-pole. Takes two 1-inch (25.4 mm) spaces.
■ Type BRW: 15 to 30 amperes.Two-pole water heater breakers.
■ Type BRSN: 15 to 30 amperes.Two-pole switching neutral breakers.
■ Type BR 15 to 100 amperes.Two-pole, 240V AC delta breakers.
Enclosures ■ NEMA Type 1 indoor.■ NEMA Type 3R outdoor.
Meets or exceeds UL requirements for indoor or outdoor applications
Loadcenter and Breaker Accessories ■ Branch Circuit BreakerAuxiliary components.Hold Down Kits.Handle ties.Lockoffs.Lockdogs.
■ Complete Line of Ground Bar Kits5, 10, 14, and 21 circuit, some with additional #2/0 lugs. Each terminal will accommodate: (3) #14-#10 Cu/Al or(1) #14-#4 Cu/Al
■ Main and Sub-feed Lugs125, 150, 225 amperes – two- and three-pole.
■ Shunt Trips
■ Surge ProtectionSingle-phase plug-on surge protector.Single-phase bottle type surge protector.Three-phase bottle type surge protector.Single-phase whole home surge protector.
Group Two: 2, 2-1/2, 3 inches(50.8, 63.5, 76.2 mm)
Adapter plate.
Bussing ■ Tin-plated aluminum as standard.■ Some copper bus panels available.
Type BR LoadcentersSelection Chart
October 1998
CAT.73.01.T.E
Cutler-Hammer C-3
Single-Phase Three-Phase Convertible
Main Circuit Breaker Main Circuit Breaker
Circuit BreakerUnit EnclosuresOutdoor
Main Circuit BreakerCommercial
Main Circuit BreakerCommercial
Main Lugs Main Lugs
Type BR LoadcentersProduct Styles
CAT.73.01.T.E
Cutler-HammerC-4October 1998
Bus
Blank➀ = Aluminum Bus C = Copper Bus
Cutler-Hammer
Type BR Loadcenter
Drywall marking on enclosure
Twin neutral design for easier wiring and balancing of the load, located in wireway, away from circuit breakers
Maximum wiring gutter space for ease of wiring in compliance with NEC requirements
One piece roll formed metal backpan with circuit breaker alignment notches assures accurately aligned breaker and bus stabs
Six mounting holes (three top, three bottom) for ease of installation
Maximum variety of concentric knockouts, at rear and sides
Predrilled mounting holes for ease of installing ground bar kits
Factory pre-attached neutral bonding strap
Commercial grade main breaker designed for straight-in wiring that allows for top or bottom feed
Same size Allen wrench can be used for phase and neutral lugs
Standard 14-3/8 inches (365.1 mm) wide enclosures fit snugly between wall studs
Extra 1-1/2-inch (38.1 mm) knockout for bundling of wires
BR2040B200
Catalog Numbering SystemSingle- and Three-Phase Through 225 Amperes
Tangential main knockout
Combination trim has sliding latch and adjustable deadfront for neat, clean appearance
Example No. 3: 3B4242EFN
3-Phase Cutler-Hammer Type BR Load-center Rated at 600 Amperes with Main Breaker, 42 Spaces Allowing 42 Poles,Indoor Combination Enclosure.
Example No. 2: BR24L70RP
1-Phase Cutler-Hammer Type BR Load-center Rated at 70 Amperes with Main Lugs, 2 Spaces Allowing 4 Poles, Rain-proof Enclosure with Aluminum Bus.
Example No. 1: BR1224L125G
1-Phase Cutler-Hammer Type BR Load-center Rated at 125 Amperes with Main Lugs, 12 Spaces Allowing 24 Poles, Indoor Combination Enclosure, Aluminum Bus, and Ground Bar.
R = NEMA Type 3R Rainproof S = NEMA Type 1 Indoor with
Surface TrimF = NEMA Type 1 Indoor with
Flush Trim Blank➀ = NEMA Type 1 Indoor with
Combination Trim
Maximum
Number
of Poles
Number of 1-inch
(25.4 mm) Spaces
Type BR LoadcentersLoadcenter Features - Catalog Numbering System
Blank➀ = No Feed Thru Lugs
F = Feed Thru Lugs
G = Ground Bar
P = Current Design
B = Main BreakerL = Main LugN = Convertible MainH = Main Breaker High AIC
Single- and Three-Phase 400 Amperes Through 600 Amperes
3 B 30 42 D F N
Phase
Blank➀ = 1-Phase 3 = 3-Phase
Amperes
D = 400 AmperesE = 600 Amperes
Enclosure
F = NEMA Type 1 Indoor with Combination TrimS = NEMA Type 1 Indoor with Surface TrimR1 = NEMA Type 3R Rainproof
Maximum
Number
of Poles
Number of 1-inch
(25.4 mm) Spaces
N = Current Design
Main
Blank➀ = Main Lug B = Main Breaker
October 1998
CAT.73.01.T.E
Cutler-Hammer C-5
Application Information
Loadcenter Construction
Cutler-Hammer Type BR loadcenters have standard tin-plated aluminum bus with a limited availability of copper bus. The sum of the handle ratings connected to any stab is limited to 150 amperes maximum on the 100 and 125 ampere loadcenters, and 200 amperes on load-centers with 150 ampere or higher main bus. NEMA Type 1 boxes or enclosures are manufactured from G60 16-gauge galvanized steel. Raintight boxes are manufactured from G60 16-gauge galva-nized steel, then finished using an elec-trostatic powder coat, baked urethane paint process.
UL Listings
All Cutler-Hammer Type BR loadcenters are listed under UL file E52977 except the 2-8 circuit loadcenters, up through and including 125 amperes, which are listed under UL file E8741.
Neutrals
Cutler-Hammer Type BR loadcenters feature two types of neutrals:Split Neutrals – Single-phase load-centers 12 circuits and above feature a twin neutral (mounted on both sides of the interior assembly) with a cross bus connecting them unless otherwise noted. The neutral is bondable in the field by means of a bonding strap that is supplied with each loadcenter. The cross bus is not removable for separate ground and neutral bars. For sub-feed applications, a separate ground bar must be used. In a service entrance applica-tion, where the neutral is bonded, unused neutral connections may be used for equipment ground conductors.Single Neutral – Single phase 2-8 circuit, three-phase and commercial loadcenters are supplied with a single insulated/bondable neutral. The three-phase load-center neutral is movable to the other side if desired. The neutral is bondable in the field by means of a bonding strap that is supplied with each loadcenter. For sub-feed applications, a separate ground bar must be used. In a service entrance application, where the neutral is bonded, unused neutral connections may be used for equipment ground protectors.
Grounds
Separate ground bars are supplied on those loadcenters having a “G” in the catalog number. For service entrance panels not having a separate ground bar, the extra neutral terminals may be used for equipment ground conductors. When using the loadcenter as a sub-feed, the bonding strap should not be attached, and a separate ground bar must be installed.
Neutral and Ground Terminals
The standard terminals on grounds and neutrals are rated to accept (3) – #14-#10 Cu/Al or (1) – #14-4. For larger cables, add-on neutral lugs may be ordered from the accessories on page C-16.
Bottom Fed Loadcenters
Where power cable is brought into the loadcenter from below the panel, main lug panels, and single-phase, 225 ampere and below loadcenters can be rotated 180 degrees to allow straight-in wiring of power cables to the main ter-minals. Because the main circuit breaker handle operates horizontally, the orien-tation of the main circuit breaker handle is consistent with the requirements of NEC Article 240-81.
Gutter Splicing
Loadcenters are not UL listed as wiring troughs. Therefore, gutter splicing of riser cables to tap off to the main device is not permitted.
Fire Rating
Due to the numerous openings in both loadcenter boxes and trims, they should not be mounted in firewalls. There is no approved method for sealing the enclo-sures for this application.
Date Code
The date of manufacture of each load-center is printed on the outside of the carton as well as inside the loadcenter. On the carton, the date code is printed on the end carton label. In the load-center, the date code is located on the small white label located on the right side wall (with the main device on top).
➀ See Cutler-Hammer Publication Number SA-365 for complete details.
Application Notes and Extended Warranty Highlights
The date code is in the following format:F # # # = . The “F” is the numeric code for the Lincoln, IL plant, and the three numbers are the year and week of manu-facture e.g. 623. The “=” sign at the end signifies the decade of the 1990s. There-fore, the date code F623= would indicate that the product was manufactured in the 23rd week of 1996. The 1980s are represented by a “+” sign at the end of the code.
Surge Protectors
The BRSURGE Surge Protector has indi-cating lights that indicate when the units should be replaced. The CHSA01 and CHSA03 Surge Protectors internally short, causing the circuit breaker feeding the surge protector to trip. All but the BRSURGE Surge Protector should be wired to the load side of 15 or 20 ampere feeder circuit breakers mounted adjacent to the main incoming device.
The CHSPCH Clipper Home Surge Protector is an externally mounted TVSS unit that provides industrial level surge protection in a residential design.
Extended Residential Warranty Highlights ➀
■ Five-year branch breaker warranty.■ Five-year loadcenter warranty.■ Both the loadcenter and branch circuit
breaker warranties are extended to 10 years if a functioning surge protector is installed in the loadcenter.
1-Phase – Main Circuit Breaker Loadcenters10,000/22,000 Amperes Interrupting Capacity
➀ All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with a neutral bonding strap preattached. The maximum rating of the panel is the main circuit breaker rating when used as service entrance equipment.
➁ Ground bar kits priced separately. See page C-16.
➂ Refer to page C-25 for dimensions.➃ Includes through-feed lugs for both phase
and neutral conductors.➄ Rainproof panels are furnished with hub
closure plates. For rainproof hubs, refer to page C-16.
➅ Type DK main circuit breaker is rated 65,000 AIC at 240V AC and allows a 22,000 AIC series rating on the panel when Types BR, BD and BJ branch circuit breakers are used.
➆ Type LA main circuit breaker is rated 42,000 AIC at 240V AC. Type LA circuit breaker isnot series rated with Types BR, BD and BJ branch circuit breakers.
➇ Supplied with adapter plate to use DS Group 1 hubs on page C-16. If 2-1/2-inch (63.5 mm) hub is needed, remove adapter and use ARP00007CH25 hub.
➈ Neutral is bonded – suitable for service entrance only – can not be converted for sub-feed application.
➉ The maximum rating of the panel is the main circuit breaker rating when used as service entrance equipment.
� Door lock and key included with loadcenter.� Combination style covers may be used in
surface or flush applications.� Loadcenter has surface cover no flush offer-
ing available.� Wire range size for BR1020B100SP is #6 - #1
Al/Cu.
Type BR Loadcenters1-Phase with Main Circuit Breakers
Discount Symbol 22CD
October 1998
CAT.73.01.T.E
Cutler-Hammer C-7
1-Phase 3-Wire — 120/240V AC — Insulated/Bondable Neutral
➀ All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with neutral bonding strap preattached. The maximum rating of the panel is the main circuit breaker rating when used as service entrance equipment.
➁ Ground bar kits priced separately. See page C-16.
➂ Refer to page C-25 for dimensions.➃ 22,000 AIC series combination rating is
obtained when Types BD, BR, BQ, BQC and GFCB 10,000 AIC branch breakers are used in series with Type BRH main breaker.
➄ 25,000 AIC series combination rating is obtained when Types BD, BR, BQ, BQC and GFCB 10,000 AIC branch circuit breakers are used in series with Type BWH main breaker. Discount Symbol 22CD
1-Phase – Main Circuit Breaker Loadcenters22,000/25,000 Amperes Interrupting Capacity
Type BR Loadcenters1-Phase with High Interrupting Main Circuit Breakers
CAT.73.01.T.E
Cutler-HammerC-8October 1998
1-Phase 3-Wire — 120/240V AC — Insulated/Bondable Neutral
Main AmpereRating
Maximum Number 1-inch (25.4 mm)
Type ofEnclosure
Type ofTrim
Loadcenter Catalog Number
ListPrice
BoxSize➁
WiringDiagramFigureNumber
Wire Size Range for Cu/Al60°C or 75°C for Main Lugs
Flush Surface FlushSurface no Door Flush with Door
ing mains are provided and when not used as a lighting and appliance panelboard (see Article384-14 of the NEC).
� Suitable for use as service equipment when a main breaker is used or when not more than six service disconnecting mains are provided and when not used as a lighting and appliance panelboard(see Article 384-14 of the NEC).
1-Phase – Main Lug Loadcenters
OutdoorOutdoor
October 1998
CAT.73.01.T.E
Cutler-Hammer C-9
1-Phase 3-Wire — 120/240V AC — Insulated/Bondable Neutral
MainAmpereRating
Maximum Number 1-inch (25.4 mm)
EnclosureType
Typeof Trim
LoadcenterCatalogNumber
ListPrice
BoxSize
Wiring DiagramFigure Number
Wire Size Range Cu/Al60°C or 75°C for Main Lugs
Spaces Poles
40➇ � � Indoor Flush No Door TT120FLGNM��
TT120SLGNM��
$ 40.0040.00
22
6565
�
60 22222
44444
IndoorIndoorIndoorIndoor
Outdoor
Flush no DoorSurface no DoorFlush no Door
Surface no Door—
2460FNM2460SNM2460FGNM�
2460SGNM�
2460RNM
44.2544.5046.7547.0085.50
2222
2R
11111
#14 - 2
Type BR Loadcenters1-Phase with Main Lugs
not more than six main disconnecting means are provided and when not used as a lighting and appliance panelboard (see article 384-14 of the NEC.)
➈ Ground bar GBK8 installed.➉ Ground bar GBK10 installed.� Ground bar GBK1220 installed.� Ground bars GBK5 and GBK520 installed.� Includes through-feed lugs for both phase
and neutral conductors. � Refer to page C-25 for dimensions.
➀ Ground bar kits priced separately unless otherwise noted. See page C-16.
➁ Rainproof panels are furnished with hub closure plates. For rainproof hubs refer to page C-16.
➂ Has notch for BREQS125 hold-down kit.➃ Has notch for BRHDK125 hold-down kit.➄ Door lock and key included with loadcenter.➅ Single, movable neutral is provided.➆ Combination cover style.➇ Suitable for use as service equipment when
� This device has no main lugs. A Type BR or BD breaker is required to be backfed to sup-ply power to branch breakers. This device is single phase 120 V AC only. With the use of three Type BR breakers there are two branch circuits available. With the use of three Type BD breakers there are five branch circuits available. See Wiring Diagram 61 onpage C-35.
Type BR Loadcenters3-Phase with Main Circuit Breakers
3-Phase – Main Circuit Breaker Loadcenters10,000/22,000/100,000 Amperes Interrupting Capacity
➀ All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with a neutral bonding strap pre-attached (commercial loadcenters do not have a pre-attached bonding strip). The maxi-mum main rating of the panel is the main circuit breaker rating when used as service entrance equipment.
➁ Ground bar kits priced separately. See page C-16.
➂ Refer to page C-25 for dimensions.➃ Rainproof loadcenters are furnished with
hub closure plates. For rainproof hubs, refer to page C-16.
➄ Door lock and key included with loadcenter.
➅ Type DK main circuit breaker is rated 65,000 AIC at 240V AC and allows a 22,000 AIC series rating on the loadcenter when Types BR, BD and BJ branch circuit breakers are used.
➆ The LD main circuit breaker is rated 65,000 AIC at 240V AC. Type LD circuit breaker isnot series rated with Types BR, BD and BJ branch circuit breakers.
➇ 22,000 AIC series combination rating is obtained when Types BD, BR, BQ, BQC and GFCB branch breakers are used with BRH main.
➈ 100,000 AIC series combination rating is obtained when Types BD, BR, BQ, BQC and GFCB branch breakers are used with CHH main. Discount Symbol 22CD
MainBreakerType
MainAmpereRating
MaximumNumber1-inch (25.4 mm)
EnclosureType
Commercial Loadcenter Catalog Number➀➁➄
List Price BoxSize➂
WiringDiagramFigureNumber
Wire Size Range Cu/Al60°C or 75°Cfor Main Breaker
Spaces Poles With Combination or NEMA Type 3R Cover
➀ Interrupting rating depends on main circuit breaker selected.
➁ The maximum rating of the loadcenter is the main circuit breaker rating when used as service entrance equipment.
➂ 100, 125 and 200 ampere Convertible base unit catalog numbers include interior, box and cover only. Main devices and accessories must be ordered separately for field installa-tion. All Convertible base units are listed as suitable for use as service entrance equip-ment when used per Article 384 of the NEC.
➃ Ground bar kits priced separately, refer to page C-16.
Main Circuit Breaker with Accessory
Example: BW22005R01(Put description with catalog number on order. See page C-24.)
➄ Refer to page C-25 for dimensions.➅ BREQS125 hold-down screw comes with
loadcenter for back-fed Types BR and BRH main circuit breakers.
➆ Rainproof loadcenters are furnished with hub closure plates. For rainproof hubs, refer to page C-16.
➇ Includes through-feed lugs for both phase and neutral conductors.
➈ No hold-down provisions for back-fed Types BR and BRH main circuit breakers.
➉ Convertible to maximum of 100 ampere main circuit breaker and 125 ampere main lug.
� Series combination rating with Types BD, BR, BQ, BQC and GFCB is 22,000 AIC with BRH main and 25,000 AIC with BWH main.
� Suitable for use as service equipment when not more than six main disconnecting means are provided and when not used as a lighting and appliance panelboard (see article 384-14 of the NEC.)
Type BR LoadcentersConvertible, Base Units and Main Devices
Discount Symbol 22CD
October 1998
CAT.73.01.T.E
Cutler-Hammer C-13
Main Lug — 1-Phase 3-Wire —120/240V AC — Single Neutral
Main Ampere
Rating
Maximum Number
1-inch (25.4 mm)
Enclosure
Type
Type
of Trim
Loadcenter
Catalog Number
List
Price
Box
Size➂Wiring Diagram
Figure Number
Wire Size Range
Cu/Al 60°C or 75°C
for Main LugsSpaces Poles
125 88
1616
IndoorIndoor
Surface w/doorFlush w/door
BR816LC1255DP
BR816LC1255PDP
$140.00
140.00
77
77
#14 - 1
Convertible — 1-Phase 3-Wire — 120/240V AC — Insulated/Bondable Neutral
Main Circuit Breaker/Main Lug/Convertible Loadcenters – With Copper Bus10,000/22,000/25,000 Amperes Interrupting Capacity
Type BR LoadcentersCopper Bus Main Circuit Breaker, Main Lug, Convertible
Discount Symbol 22CD
Main Lug — 3-Phase 4-Wire — 208Y/120V AC or 240V AC — Insulated/Bondable Neutral
Main Ampere
Rating
Maximum Number
1-inch (25.4 mm)
Enclosure
Type
Loadcenter Catalog Number
With Combination or
NEMA Type 3R Cover➁
List
Price
Box
Size➂Wiring Diagram
Figure Number
Wire Size Range
Cu/Al 60°C or 75°C
for Main LugsSpaces Poles
200 304242
424242
IndoorIndoor
Outdoor
3BR3042LC200
3BR4242LC200
3BR4242LC200R➃
$434.00
620.00
705.00
G1L1
L1R
333737
#1/0 - 300 kcmil
Convertible — 3-Phase 4-Wire — 208Y/120V AC or 240V AC — Insulated/Bondable Neutral
Main Ampere
Rating
Maximum Number
1-inch (25.4 mm)
Enclosure Type Loadcenter Catalog Number
With Combination or
NEMA Type 3R Cover➀➁➄
List
Price
Box
Size➂Wiring Diagram
Figure Number
Wire Size Range
Cu/Al 60°C or 75°C
for MainSpaces Poles
10010/22 kAIC➇
3030
3030
IndoorOutdoor
3BR3030NC100➅3BR3030NC100R➃➅
$358.00
446.00
D1D1R
4848
See main breaker and main lug kit tables
on page C-12.12510/22 kAIC➇
1212
2424
IndoorOutdoor
3BR1224NC125➅➆➈3BR1224NC125R➃➅➆➈
225.00
309.00
C1C1R
5151
➀ All main circuit breaker loadcenters are listed for use as service entrance equipment and are shipped with a neutral bonding strap pre-attached. The maximum main rating of the loadcenter is the main breaker rating when used as service entrance equipment.
➁ Ground bar kits priced separately. See page C-16.
➂ Refer to page C-25 for dimensions.➃ Rainproof loadcenters are furnished with
hub closure plates. For rainproof hubs, refer to page C-16.
➄ 100, 125 and 200 ampere Convertible base unit catalog numbers include interior, box and cover only. Main devices must be ordered separately from page 12. Accessories must also be ordered separately for field installa-tion. All Convertible base units are listed as suitable for use as service entrance equipment when used per article 384 of the NEC.
➅ Hold-down screw BREQS125 comes with loadcenter for back-fed Types BR and BRH main circuit breakers.
➆ Convertible to maximum of 100 ampere main breaker and 125 ampere main lug.
➇ Interrupting rating depends on main circuit breaker selected. See page C-12 for mains.
➈ Suitable for use as service equipment when not more than six main disconnecting means are provided and when not used as a lighting and appliance panelboard (see arti-cle 384-14 of the NEC.)
➉ 22,000 AIC series combination rating is obtained when BD, BR, BQ, BQC and GFCB 10,000 AIC branch circuit breakers are used with a BRH main.
Main Circuit Breaker — 1-Phase 3-Wire — 120/240V AC — Insulated/Bondable Neutral
Ground Bar Legend�(3) #14 - #10 Cu/Al or (1) #14 - #4 Cu/Al�(1) #6 - 2/0 Cu/Al�(1) #14 - #6 Cu/Al or (2) #14 - #12 Cu/Al�(1) 1/8 - 14 or (3) #10 - 12 Cu/Al�(1) #14 - 1/0 Cu/Al or (3) #14 - #10 Cu/Al�(1) #6 - 14 or (2) #10 - 14 Cu/Al�Mounting Hole
Field Installation Rainproof Conduit Hubs
Description Conduit Size
Inches (mm)
Catalog
Number
List Price
Each
Ordering
Quantity➀
Group 1 – For use with 70, 100 and 125 Ampere MLO and MCB Loadcenters and Circuit Breaker Enclosures
3/4 (19.1)1 (25.4)
1-1/4 (31.8)1-1/2 (38.1)
2 (50.8)
DS075H1
DS100H1
DS125H1
DS150H1
DS200H1
$22.30
22.30
22.30
22.30
36.40
11111
Group 2 – For use with 150, 200 and 225 Ampere MLO and MCB Loadcenters and Circuit Breaker Enclosures
2 (50.8)2-1/2 (63.5)
3 (76.2)
DS200H2
DS250H2
DS300H2
36.40
64.50
76.00
111
Type R1H Conduit Hubs for 400 and 600 Ampere Loadcenters and New York City Loadcenters
2 (50.8)2-1/2 (63.5)
3 (76.2)
R1H200
R1H250
R1H300
34.70
56.50
75.50
111
Type H Conduit Hubs for Loadcenters PL0724R and S3100RN
3/4 (19.1)1 (25.4)
1-1/4 (31.8)1-1/2 (38.1)
RH75
RH100
RH125
RH150
20.90
20.90
20.90
20.90
1111
Adapter Kit – Allows Installing a Group 1 Hub on Devices Arranged for Group 2 HubsGroup 1 Small Blank Hub Plate with BumpGroup 2 Large Blank Hub Plate with Bump
➀ Must be purchased in multiples of ordering quantities indicated.
➁ Distance between mounting holes is 1-3/4 inches (44.5 mm).
BRL200
BRSF125
3BRS225
GBK14
DS100H1
Discount Symbol 22CD
TDL
➂ For 1- and 3-phase 400 and 600 ampere applications.
➃ Distance between mounting holes is 2-11/32 inches (59.5 mm).
➄ For non-metallic enclosures. Snaps into molded base.
Type BR LoadcentersAccessories
� � � � � � � � � � � � � � �
��
October 1998
CAT.73.01.T.E
Cutler-Hammer C-17
Description CatalogNumber
ListPrice
Discharge Voltage, V AC Lead LengthInches (mm)1.5 kA 3 kA 5 kA 10 kA
Surge Protector Plug-On Type BR, Single-Phase, 120/240V AC
BRSURGE $100.00 345 370 500 545 8 (203.2)
Surge Protector, 2-PoleSingle-Phase, 3-Wire, 120/240V AC
CHSA01 47.80 490 640 980 1410 15 (381.0)
Surge Protector, 3-PoleThree-Phase, 4-Wire, 600V AC
CHSA03 96.50 1700 2100 2510 3800 15 (381.0)
BRSURGESurge
Protector
CHSP (Clipper Home Surge Protector)
Surge Protectors
Clipper Home Surge Protector
CHSP – This surge protector is an exter-nally mounted TVSS unit that provides industrial level surge protection in a residential design. It is available in two versions, available in both indoor and outdoor enclosures. The first provides AC power line protection only. The second provides complete surge protection for your electrical, telephone, and coaxial cable lines in one convenient unit. Both CHSP models are UL1449 (2nd edition) and 497A listed.
CatalogNumber
ListPrice
CHSPCHARBCHSPCHARPCHSPCHAOBCHSPCHAOP
$325.00325.00395.00395.00
CHSPCHSRBCHSPCHSRPCHSPCHSOBCHSPCHSOP
400.00400.00470.00470.00
The CHSP is backed by a 5-year product warranty and provides a $10,000 warranty for properly connected equipment.➀
Protection Specifications
AC Power Protection
■ 120/240V (3-wire + Ground) ■ 39 kA surge current per phase■ All modes protected ■ Nanosecond response time ■ 24-inch (609.6 mm) leads included for
installation■ Two status indicator lights
Telephone Protection
■ Two incoming lines■ 10 kA per pair surge protection■ PTC polyswitch resetting fuses■ 230V DC gas tube protection
Coaxial Cable Protection
■ Two Cable Type F connectors (input and output)
■ Line-to-shield (ground) protection■ 90V DC gas tube protection
Clipper Home Surge Protector Catalog Numbering System
CHSPCH A R B
ProtectionPosition 1A = AC
ProtectionOnly
S = AC,Telephoneand Cable
EnclosurePosition 2R = Surface/
FlushO = Outdoor
Enclosure
PackagingPosition 3B = Box P = Blister
Pack
Surge Protector
BRSURGE – For use on single-phase, 120/240V AC systems. This easily plugs into a single-phase Type BR loadcenter and occupies two 1-inch (25.4 mm) pole spaces similar to a 2-pole Type BR breaker. When plugged into the first two stabs at the top of the loadcenter just below the main breaker or main lug, it provides surge protection for the entire loadcenter. If internal components are damaged, the BRSURGE LED visual indi-cators will signal the need for replace-ment. This device is suitable for service entry locations installed in accordance with NEC Article 280. The BRSURGE is ideal for protecting sensitive appliances and electronics, such as refrigerators, microwave ovens, and home computers.
CHSA01 – For use on single-phase, 120/240V AC systems. This surge protector can be easily installed in the enclosure of indoor or outdoor loadcenters by using the 1/2-inch (12.7 mm) threaded nipple. It is ideal for protecting outdoor lighting, garages, sump and irrigation pumps, etc.
Surge Protector
CHSA03 – For use on three-phase, 600V AC systems. This surge protector is installed in the enclosure of indoor and outdoor loadcenters by using the 1/2-inch (12.7 mm) threaded nipple. It provides protection for commercial electrical ser-vices especially those using electric motors.
CHSA01Surge
Protector
CHSA03Surge
Protector
➀ Refer to Cutler-Hammer CHSP warranty for complete details. Discount Symbol 22CD
Type BR LoadcentersSurge Protection
CAT.73.01.T.E
Cutler-HammerC-18October 1998
Type BR Breakers, 1-Inch (25.4 mm) per Pole 240V AC, 10,000, 22,000 and 42,000 AIC➀➁
Amperes 3-Pole 240V AC
Common Trip
Requires Three 1-Inch Spaces
Wire Size
Range
Cu/Al
60°C or
75°C5 per Shelf Carton
10 kAIC 22 kAIC
Catalog
Number
List
Price
Catalog
Number
List
Price
10 15➂➃ 20➂➃ 25 30
—
BR315➅BR320➅BR325➅BR330➅
$143.00
143.00
143.00
143.00
—
BRH315➅BRH320➅—
BRH330➅
$219.00
219.00
219.00
#14-4
35 40 45 50
BR335➅BR340➅BR345➅BR350➅
143.00
143.00
143.00
143.00
—
BRH340➅—
BRH350➅
219.00
219.00
#14-4
55 BR355➅ 137.00 — #14-3
60 70 80 90100110
BR360➅BR370➅BR380➅BR390➅BR3100➅—
143.00
143.00
143.00
143.00
213.00
BRH360➅BRH370➅—
BRH390➅BRH3100➅—
219.00
275.00
307.00
307.00
#4-1/0
125150
—
—
—
—
#4-2/0
Plug-On Circuit Breakers, Types BR10,000/22,000/42,000/65,000 Amperes Interrupting Capacity 120V AC, 120/240V AC and 240V AC
BR120 BR215 BR320
Discount Symbol 22CD
➀ All Type BR 1-, 2-, and 3-pole circuit breakers carry listing for HACR application.
➁ For circuit breakers with a shunt trip, add ST suffix and obtain pricing from table on page C-24.
➂ One pole, 1-inch (25.4 mm) per pole circuit breakers are available with high magnetic setting for switching large tungsten lamp loads. Add suffix H to catalog number.
➃ Switching duty rated.
➄ For use as a branch circuit breaker in 400 and 600 ampere panels only.
➅ On the new black handle breaker add suffix B to the catalog number and $4 to the list price to obtain a tapped molded opening for proper use with hold-down kits.
Type BR LoadcentersPlug-On Circuit Breakers
Type BR Breakers, 1-Inch (25.4 mm) per Pole 120/240, 10,000, 22,000 and 42,000 AIC➀➁
Type BR Arc Fault Circuit Breakers1-Inch (25.4 mm) per Pole 120V AC or 120/240V ACAFCI technology recognizes the unique characteristics of an arcing fault to trip the breaker and interrupt the circuit.
Amperes 1-Pole
120V AC
Requires One 1-Inch Space
2-Pole➀120/240V AC
Common Trip
Requires Two 1-Inch Spaces
Wire Size
Range Cu/Al
60°C or 70°C
1 per Shelf Carton 1 per Shelf Carton
10,000 AIC 10,000 AIC
Configuration Catalog
Number
List
Price
Configuration Catalog
Number
List
Price
15 AFCIAFCI w/GFCI
BR115AF
BR115GFAF
$146.00
➁AFCI
AFCI w/GFCIBR215AF
BR215GFAF
➁➁
#14-4
20 AFCIAFCI w/GFCI
BR120AF
BR120GFAF
$146.00
➁AFCI
AFCI w/GFCIBR220AF
BR220GFAF
➁➁
Discount Symbol 22CD
➀ Two-pole AFCI breakers are designed for use in 3-Wire, 120/240V AC circuits, multiwire circuits utilizing a shared neutral (often referred to as a ”home run” circuit), and 240V AC circuits obtained from 120/240V AC source.
➁ Availability to be announced.
Plug-On Arc Fault Circuit Breakers, Type BR10,000 Amperes Interrupting Capacity120V AC and 120/240V AC
Type BR 1- and 2-PoleAFCI Circuit Breakers
The NEC will mandate the use of AFCI Protection for 15 and 20 ampere bedroom outlet circuits in the year 2002. Informa-tion will be published in the 1999 National Electrical Code.
CAT.73.01.T.E
Cutler-HammerC-20October 1998
Type GFCBH Ground Fault Breakers (5 Milliampere), 1-Inch (25.4 mm) per Pole 120V AC or 120/240V AC, 22,000 AIC
Amp-
eres
1-Pole
120V AC
Requires One 1-Inch Space
2-Pole
120/240V AC
Common Trip
Requires Two 1-Inch Space
Wire
Size
Range
Cu/Al
60°C or
75°C1 per Shelf Carton 1 per Shelf Carton
22,000 AIC 22,000 AIC
Catalog Number List Price Catalog Number List Price
15202530
HAGFH15
HAGFH20
HAGFH25
HAGFH30
$347.00
347.00
347.00
347.00
GFCBH215
GFCBH220
GFCBH225
GFCBH230
$472.00
472.00
472.00
472.00
#14-4
Type GFCB Ground Fault Circuit Breakers (5 Milliampere), 1-Inch (25.4 mm) per Pole 120V AC or 120/240V AC, 10,000 AIC
Amp-
eres
1-Pole
120V AC
Requires One 1-Inch Space
2-Pole
120/240V AC
Common Trip
Requires Two 1-Inch Space
Wire
Size
Range
Cu/Al
60°C or
75°C1 per Shelf Carton 1 per Shelf Carton
10,000 AIC 10,000 AIC
Catalog Number➀ List Price Catalog Number List Price
152025304050
GFCB115
GFCB120
GFCB125
GFCB130
GFCB140
—
$136.00
136.00
136.00
136.00
136.00
—
GFCB215
GFCB220
GFCB225
GFCB230
GFCB240➁GFCB250➁
$241.00
241.00
241.00
241.00
241.00
241.00
#14-4
Type GFEP Ground Fault Equipment Protectors (30 Milliampere), 1-Inch (25.4 mm) per Pole 120V AC or 120/240V AC, 10,000 AIC.
Amp-
eres
1-Pole
120V AC
Requires One 1-Inch Space
2-Pole
120/240V AC
Common Trip
Requires Two 1-Inch Space
Wire
Size
Range
Cu/Al
60°C or
75°C1 per Shelf Carton 1 per Shelf Carton
10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price
152025304050
GFEP115
GFEP120
GFEP125
GFEP130
GFEP140
GFEP150
$223.00
223.00
223.00
223.00
223.00
223.00
GFEP215
GFEP220
GFEP225
GFEP230
GFEP240
GFEP250
$395.00
395.00
395.00
395.00
395.00
395.00
#14-4
Plug-On Ground Fault Circuit Breakers, Type GFCB and GFEP10,000/22,000 Amperes Interrupting Capacity120V AC and 120/240V AC
➀ Available with bell alarm or auxiliary switch. See circuit breaker accessories on page C-24. Discount Symbol 22CD
Type GFCB2-Pole
Ground Fault Application Notes
Single-pole GFCBs are designed for use in 2-wire, 120V AC circuits. Figure 1 shows a typical wiring configuration.
Two-pole GFCBs are designed for use in 3-wire, 120/240V AC circuits, 120V AC multi-wire circuits employing common, neutral and 2-wire, 240V AC circuits obtained from a 120/240V AC source.
Figures 2 and 3 illustrate typical wiring config-urations for a 120/240V AC multiwire circuits.
Figure 4 depicts a 240V AC, 2-wire circuit. Note the “panel neutral” conductor connects to the neutral bar, even though the neutral is not included in the load circuit. This connection is necessary to supply a 120V AC power source to the ground fault sensing circuit.
The figures are shown with a 120/240V AC, single-phase, 3-wire power source, but are also applicable to a 120/208V AC, 3-phase, 4-wire power supply. For all figures the electrical opera-tion of the GFCB is not affected by the equip-ment ground.
Figure 11-Pole
Figure 32-Pole
Figure 22-Pole
Figure 42-Pole
Type GFCB1-Pole
➁ For use with copper wire only.
Type BR LoadcentersPlug-On Ground Fault Circuit Breakers
October 1998
CAT.73.01.T.E
Cutler-Hammer C-21
Duplex and Independent Trip Quadplex Breakers
Class CTL 10,000 AIC — All circuit breakers have rejection tab feature.
Type BD Duplex (UL Type BRD) Type BQ Quadplex Independent Trip (UL Type BRD) Type BQ Quadplex Independent Trip (UL Type BRD) Wire Size
Range
Cu/Al
65°C or
75°C
1-Pole➁
Requires One 1-Inch Space
2-Pole➀ and 1-Pole➁
Requires Two 1-Inch Spaces
2-Pole
Requires Two 1-Inch Spaces
10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton
Ampere
Rating
10,000 AIC 10,000 AIC 10,000 AIC
120V AC 120V AC 120/240V AC 120V AC Catalog
Number
List
Price
120/240V AC Catalog
Number
List
PriceCatalog
Number
List
Price
Ampere Rating Ampere Rating
Outer Left
1-Pole
Center
2-Poles
Independent
Trip
Outer Right
1-Pole
Outer
2-Poles
Independent
Trip
Center
2-Poles
Independent
Trip
15-1515-2020-2030-20
BD1515
BD1520
BD2020
BD3020
$35.20
35.20
35.20
35.20
1520152015201520
2020303040405050
1520152015201520
BQ2202115
BQ2202120
BQ2302115
BQ2302120
BQ2402115
BQ2402120
BQ2502115
BQ2502120
$68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
152020202025303030404050
152030405025304050405050
BQ215215
BQ220220
BQ220230
BQ220240
BQ220250
BQ225225
BQ230230
BQ230240
BQ230250
BQ240240
BQ240250
BQ250250
$68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
68.50
CTL Plug-On Circuit Breakers, Type BD Duplex, BQ and BQC Quadplex10,000 Amperes Interrupting Capacity120/240V AC
BD2020 BQ2302115 BQC230230
120V AC120V AC
120V AC
120V AC120/240V AC
120/240V AC
120/240V AC
Type BR LoadcentersCTL Plug-On Circuit Breakers, BD Duplex, BQ and BQC Quadplex
Common Trip Quadplex Breakers
Class CTL 10,000 AIC — All circuit breakers have rejection tab feature.
Type BQC Quadplex Common Trip Center Poles (UL Type BRD) Type BQC Quadplex Common Trip Center and Outer Poles (UL Type BRD) Wire
Size
Range
Cu/Al
65°C or
75°C
2-Pole➀ and 1-Pole➁
Requires Two 1-Inch Spaces
2-Pole➀
Requires Two 1-Inch Spaces
5 per Shelf Carton 5 per Shelf Carton
10,000 AIC 10,000 AIC
120V AC 120/240V AC 120V AC Catalog
Number
List
Price
120/240V AC Catalog
Number
List
PriceAmpere Rating Ampere Rating
Outer Left
1-Pole
Center 2-Poles
Common Trip
Outer Right
1-Pole
Outer 2-Poles
Common Trip
Center 2-Poles
Common Trip
1515151515
2025304050
1515151515
BQC2202115
BQC2252115
BQC2302115
BQC2402115
BQC2502115
$72.50
72.50
72.50
72.50
72.50
1520202020
1520304050
BQC215215
BQC220220
BQC220230
BQC220240
BQC220250
$79.00
79.00
79.00
79.00
79.00
#14-4
202020202020
152025304050
202020202020
BQC2152120
BQC2202120
BQC2252120
BQC2302120
BQC2402120
BQC2502120
72.50
72.50
72.50
72.50
72.50
72.50
2525303030
2530304050
BQC225225
BQC225230
BQC230230
BQC230240
BQC230250
79.00
79.00
79.00
79.00
79.00
#14-4
30 50 20 BQC2502030 74.50 404050
405050
BQC240240
BQC240250
BQC250250
79.00
79.00
79.00
#14-4
120V AC
120V AC120/240V AC
120/240V AC
120/240V AC
Discount Symbol 22CD
➀ All Type BD Duplex, BQ and BQC Quadplex circuit breakers carry listing for HACR applications.
➁ All 15 and 20 ampere single poles are switch-duty rated.
CAT.73.01.T.E
Cutler-HammerC-22October 1998
Non-CTL Plug-On Replacement Circuit Breakers, Type BRD10,000 Amperes Interrupting Capacity120/240V ACNon-CTL 10,000 AIC for Replacement Purposes OnlyFor replacement in enclosures manufac-tured prior to 1968 with unnotched stabs. Circuit breakers do not have rejection tab.
Type BR LoadcentersNon-CTL Plug-On Circuit Breakers, BR Duplex, BR and BRD Quadplex
Discount Symbol 22CD
BD1515
Important Note:Type BD Duplex, BQ and BQC Quadplex (CTL) circuit breakers conform to Section 384-15 of the latest National Electrical Code. Install breaker only in panel posi-tions that have notched bus stabs.
NotchedBus Stab
UnnotchedBus Stab
Type BR orType BD Duplex, (CTL),Type BQ and BQC Quadplex
Type BR NotchedStab Non-CTL
Non-CircuitLimiting Type BR
Type BDDuplex
CTL CircuitLimitingFeature
RejectionTab
Type BR Duplex Type Brand BRD Quadplex Independent Trip Type BRD Quadplex Common Trip center and Outer Poles Wire Size
Range
Cu/Al
65°C or
75°C
1-Pole
Requires One 1-Inch Space
2-Pole
Requires Two 1-Inch Spaces
2-Pole
Requires Two 1-Inch Spaces
10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton
Ampere
Rating
10,000 AIC 10,000 AIC 10,000 AIC
120V AC 120/240V AC 120/240V AC Catalog
Number
List
Price
120/240V AC Catalog
Number
List
PriceCatalog
Number
List
Price
Ampere Rating Ampere Rating
Outer 2-Poles
Independent Trip
Center 2-Poles
Independent Trip
Outer 2-Poles
Common Trip
Center 2-Poles
Common Trip
15-1515-2020-1520-2030-30
BR1515
BR1520
BR2015
BR2020
BR3030
$48.90
48.90
48.90
48.90
48.90
152030203030
152030304050
BR415
BR420
BR430
BRD220230
BRD230240
BRD230250
$87.00
87.00
87.00
87.00
87.00
87.00
15303030
15304050
BRDC215215
BRDC230230
BRDC230240
BRDC230250
$97.50
97.50
97.50
97.50
#14-4
120V AC120V AC
120/240V AC
120/240V AC
120/240V AC
120/240V AC
October 1998
CAT.73.01.T.E
Cutler-Hammer C-23
Plug-On Circuit Breakers, Types BJ and BJH10,000/22,000 Amperes Interrupting Capacity120/240V AC and 240V AC
For Use in 1-Phase and 3-Phase Loadcenters150 Amperes and Above
Type BJ
Types BJ and BJH Breakers, 120/240 or 240V AC, 10,000, 22,000 AIC➀
Amperes 2-Pole
120/240V AC
Common Trip
Requires Four 1-Inch Spaces➁
3-Pole
240V AC
Common Trip
Requires Six 1-Inch Spaces➂
Wire Size
Range
Cu/Al
60°C or 75°C
10 per Shelf Carton 5 per Shelf Carton
10,000 AIC 22,000 AIC 10,000 AIC 22,000 AIC
Catalog
Number
List
Price
Catalog
Number
List
Price
Catalog
Number
List
Price
Catalog
Number
List
Price
125150175200225
BJ2125
BJ2150
BJ2175
BJ2200
BJ2225
$264.00
264.00
264.00
264.00
264.00
BJH2125
BJH2150
BJH2175
BJH2200
BJH2225
$620.00
620.00
620.00
620.00
620.00
BJ3125
BJ3150
BJ3175
BJ3200
BJ3225
$745.00
745.00
745.00
745.00
745.00
BJH3125
BJH3150
BJH3175
BJH3200
BJH3225
$1,045.00
1,045.00
1,045.00
1,045.00
1,045.00
#2-300 kcmil
Type BR LoadcentersSpecial Applications Plug-On Circuit Breakers
Plug-On Special Application Circuit Breakers10,000 Amperes Interrupting Capacity120V AC, 120/240V AC and 240V AC
LINE
LOADOUTIN
NEUTRAL
BRWH215Water Heater Breaker
BRSN220Switching Neutral Breaker
➀ If BJ or BJH breakers are used as a main or a back feed device, a hold-down kit is required. See page C-24.
➁ Breaker uses two 1-Inch (25.4 mm) pole spaces on left side and two 1-Inch (25.4 mm) pole spaces on right side of loadcenter.
➂ Breaker uses three 1-Inch (25.4 mm) pole spaces on left side and three 1-Inch (25.4 mm) pole spaces on right side of loadcenter.
➃ On the new black handle breaker add suffix "B" to the catalog number and $4 to the list price to obtain a tapped molded opening for proper use with hold-down kits. Discount Symbol 22CD
Special Application Circuit Breakers
Water Heater Breakers Switching Neutral Breakers 240V Breakers➃ Non-Automatic Molded Case Switches Wire Size
Range
Cu/Al
60°C or
75°C
2-Pole
120/240V AC
Common Trip
Requires Two 1-Inch Spaces
2-Pole
120V AC
Common Trip
Requires Two 1-Inch Spaces
2-Pole
240V AC
Common Trip
Requires Two 1-Inch Spaces
2-Pole
240V AC
Requires Two 1-Inch Spaces
With Isolated Line Terminals for
Separately Metered Water Heaters
With Switching Neutral
Pole for Gasoline Pump Applications
Where Voltage to
Ground is 240V AC
For Use as Disconnect Contains No
Magnetic or Thermal Trip Properties
5 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton
➀ Handle Ties: Typically used to join two simi-lar independent single-pole breakers to form a 2-pole noncommon trip breaker.
➁ Handle Lockoffs: Devices that use a padlock to lock the circuit breaker’s handle in the “On” or “Off” position.
➂ Handle Lockdogs: Devices that are used to secure a circuit breaker’s handle in the “On” or “Off” position. Handle Lockdogs are not padlockable devices.
➃ Hold-Down Kits: Devices used to secure the circuit breaker to the loadcenter for back-feed main application. See NEC Article 384-16(f). Discount Symbol 22CD
Circuit Breaker Accessories
Field Installation Kits and Parts
Description Catalog
Number
List Price
Each
Ordering
Quantity➇
Handle Ties➀Handle tie bar for physically joining the handles of two adjacent 1-pole Type BR Circuit Breakers. (Metal Cylinder Pin Type) . . . . . . .
Handle tie bar for joining two independent outside poles of Types BQ and BQC Quadplex and outside poles of two Type BD Duplex Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Handle tie bar for joining two adjacent outside poles of Types BQ and BQC Quadplex and outside poles of two Type BD Duplex Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BHT
THOW
THS1
$ 3.30
3.10
2.10
10
10
10
Handle Lockoffs➁�
Padlockable device for locking the handle of 1-, 2-, or 3-poleType BR Circuit Breakers and 1-pole of a Type BD Duplex or one independent outside pole of a Type BQ or BQC QuadplexCircuit Breakers. (Escutcheon Mounted)➄ . . . . . . . . . . . . . . . . . . . . . .
Padlockable device for locking the handle of a 1-pole Type BRCircuit Breaker. (Handle Mounted)➅ . . . . . . . . . . . . . . . . . . . . . . . . . .
Padlockable device for locking the handle of a 2- and 3-pole Type BR Circuit Breaker. (Handle Mounted)➅ . . . . . . . . . . . . . . . . . .
Padlockable device for locking the handle of a 1-pole Type BD Duplex, BQ or BQC Quadplex Breaker. (Handle Mounted)➅ . . . . . .
Padlockable device for locking the handle of the two centerpoles of Type BQ and BQC Quadplex Circuit Breakers. (Escutcheon Mounted)➄ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Padlockable device for locking the handle of main circuit breaker Types CC and CHH into the “On” or “Off” position.(Screw Mounted)➆ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Padlockable device for locking the handle of main breaker TypesBW and BWH into the “On” or “Off” position. (EscutcheonMounted)➄ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
BRLW
BRLW1
BRLW2
BRDL1
BRQLW
CCPL
MCBPL
8.70
14.00
14.00
13.30
11.90
20.30
23.80
10
10
10
10
10
1
1
Handle Lockdogs➂�
Device used to secure handle in “On” or “Off” position for 1-, 2-, or 3-pole Type BR Circuit Breakers and 1-pole of Type BD Duplex and one independent outside pole of Type BQ or BQC QuadplexCircuit Breakers. (Escutcheon Mounted)➄ . . . . . . . . . . . . . . . . . . . . . .
Device used to secure handle in “On” or “Off” position for 1-pole Type BR Circuit Breakers. (Handle Mounted)➅ . . . . . . . . . . . . . . . . . .
Device used to secure handle in “On” or “Off” position for 2- and 3-pole Type BR Circuit Breakers. (Handle Mounted)➅ . . . . .
Device used to secure handle in “On” or “Off” position for 1-pole Type GFCB Ground Fault Circuit Breakers. (Handle Mounted)➅ . . .
Device used to secure handle in “On” or “Off” position for one independent outside pole of Types BQ and BQC Quadplex or 1-pole Type BD Duplex Circuit Breakers. (Handle Mounted)➅ . . . . .
BHLW
BHLW1
BHLW2
BHGW
HLW1
8.00
8.00
8.00
7.70
12.20
10
10
10
10
10
Hold-Down Kits➃Hold-down retainer kit for 3-pole Type BR Circuit Breakers in S3100SLN and S3100RN Loadcenters only. . . . . . . . . . . . . . . . . . . . .
Hold-down screw kit for 2- and 3-pole Type BR Circuit Breakers in MLO Loadcenters through 125 amperes.. . . . . . . . . . . . . . . . . . . . .
Hold-down screw kit for 2- and 3-pole Type BR Circuit Breakers in MLO Loadcenters 150 through 225 amperes. . . . . . . . . . . . . . . . . .
Hold-down screw kit for 2-pole Types BJ and BJH Circuit Breakers in MLO Loadcenters 125 through 225 amperes.. . . . . . . . .
Hold-down screw kit for 3-pole Types BJ and BJH Circuit Breakers in MLO Loadcenters 125 through 225 amperes.. . . . . . . . .
BRHDB
BREQS125
BRHDK125
BJHDS
BJHDS3P
1.40
3.40
7.90
10.90
13.20
1
1
1
1
1
Main Breaker Lug Kits
Types CC and CHH Main Breaker Lug Kit (2) 300 kcmil.. . . . . . . . . . .
Unit Enclosure Knockouts, Types CCM and CCB Knockouts
NEMA Type 1 – Indoor NEMA Type 3R – Outdoor
AH
EFA
B B BB B
C
D D D D
E
CB
BB
BB
AH
B B BB B
C
E E E E
E
EFA CB
BB
BB
G F
E E ED D
C BB
BB
B
A
HUB HUB
G F
F F FD D
C BB
BB
B
A
HUB HUB
Type BR LoadcentersKnockouts
CAT.73.01.T.E
Cutler-HammerC-28October 1998
Symbol Key TYPE C, 1-POLE ORTYPE A, 2-POLES
NOTCHED BUS STAB
SOLID BUS STAB
TYPE C, 1-POLE
Figure 2
13
57
24
A
B
68
N
InsulatedNeutral
Figure 3
1012
BA
13
911
24
57
68
N
InsulatedNeutral
EQUIP.GND
(WhenInstalled)
MAIN LUGS
Figure 4
1315
1416
BA
1012
13
911
24
57
68
N
InsulatedNeutral
EQUIP.GND
(WhenInstalled)
MAIN LUGS
Figure 8
MAIN LUGS
A B
1
3
5
7
9
11
13
15
2
4
6
8
10
12
14
16
1719
2123
1820
2224
BONDINGSTRAP
INSULATED NEUTRAL
N
Figure 7
MAIN LUGS
A B
1
3
5
7
2
4
6
8
911
1315
1719
2123
1012
1416
1820
2224
BONDINGSTRAP
N
INSULATED NEUTRAL
EQUIP. GND(When Installed)
EQUIP.GND
(WhenInstalled)
Figure 6
MAIN LUGS
13
57
911
1315
1719
2123
24
1012
1416
1820
2224
A B
68
N
BONDINGSTRAP
INSULATED NEUTRAL
2424
4040
Figure 5
MAIN LUGS
A B
1
3
5
7
2
4
6
8
9
11
13
15
10
12
14
16
17
19
21
23
18
20
22
24
25
27
29
31
26
28
30
32
33
35
37
39
34
36
38
40
1616
N
BONDINGSTRAP
2020
EQUIP.GND
(WhenInstalled)
INSULATED NEUTRAL
Figure 9
A B
1
3
5
7
9
11
2
4
6
8
10
12
BONDINGSTRAP
INSULATED NEUTRAL
N
Figure 10
INSULATED NEUTRAL
1
3
5
7
9
11
13
15
2
4
6
8
10
12
14
16
1719
2123
1820
2224
N
MAIN CIRCUIT BREAKER
A
B
BONDINGSTRAP
Figure 11
MAIN LUGS
1
3
5
7
9
2
4
6
8
10
1113
1517
1921
2325
2729
1214
1618
2022
2426
2830
N
A B
BONDINGSTRAP
INSULATED NEUTRAL
Figure 1
A B
N
InsulatedNeutral
1 2 3 4
EQUIPGND
(WhenInstalled)
Wiring Diagrams
Type BR LoadcentersWiring Diagrams
October 1998
CAT.73.01.T.E
Cutler-Hammer C-29
Figure 12
13
57
911
1315
1719
2123
2527
2931
3335
3739
24
68
1012
1416
1820
2224
2628
3032
3436
3840
1224
2040
A B
N
INSULATED NEUTRAL
BONDINGSTRAP
MAIN LUGS
EQUIP.GND
(WhenInstalled)
Figure 13
13
57
911
1315
1719
2123
2527
2931
3335
3739
24
68
1012
1416
1820
2224
2628
3032
3436
3840
1224
1632
2040
A B
N
BONDINGSTRAP
Figure 14
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
N
INSULATED NEUTRAL
MAIN LUGSA B
MAIN LUGS
1
3
5
7
9
11
13
15
17
19
2
4
6
8
10
12
14
16
18
20
2123
2527
2931
3335
3739
2224
2628
3032
3436
3840
Figure 15
A B
N
INSULATED NEUTRAL
BONDINGSTRAP
EQUIP.GND
(WhenInstalled)
Figure 16
1
3
5
7
9
2
4
6
8
MAIN CIRCUIT BREAKER
B
N
BONDINGSTRAP
11
13
15
17
19
21
23
25
27
29
10
12
14
16
18
20
22
24
26
28
30
A
Figure 17
MAIN CIRCUIT BREAKER
13
57
911
1315
24
68
1012
1416
BONDINGSTRAP
N
INSULATEDNEUTRAL
A
B
Figure 18
13
57
911
1315
24
68
1012
1416
MAIN CIRCUIT BREAKERBA
BONDINGSTRAP
N
FEED THRU LUGS
INSULATEDNEUTRAL
Figure 19
MAIN CIRCUIT BREAKER
68
1012
1416
1820
1
3
A
B
57
911
1315
1719
2
4
BONDINGSTRAP
N
INSULATEDNEUTRAL
MAIN CIRCUIT BREAKER
A B
MAIN LUGSOR
1719
2123
1820
2224 1224
816
Wiring Diagrams
Symbol Key TYPE C, 1-POLE ORTYPE A, 2-POLES
NOTCHED BUS STAB
SOLID BUS STAB
TYPE C, 1-POLE
Type BR LoadcentersWiring Diagrams
CAT.73.01.T.E
Cutler-HammerC-30October 1998
Figure 20
MAIN LUGS
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
41
42
A B
N
BONDINGSTRAP
INSULATED NEUTRAL
5
1113
1517
1921
2325
2729
3133
3537
3941
6
810
1214
1618
2022
2426
2830
3234
3638
1
3
2
4
Figure 21
MAIN LUGSA B
N
INSULATED NEUTRAL
79
4042
1212
1616
2020
Figure 22
MAIN CIRCUIT BREAKER
1
3
5
7
9
11
13
15
17
19
2
4
6
8
10
12
14
16
18
20
B
A
BONDINGSTRAP
N
INSULATED NEUTRAL
Figure 23
MAIN CIRCUIT BREAKER
1
3
5
7
9
A
B
BONDINGSTRAP
N
INSULATEDNEUTRAL
2
4
6
8
10
1211
Figure 24
MAIN CIRCUIT BREAKER
911
1315
1719
2123
1012
1416
1820
2224
1
3
5
7
2
4
6
8
B
A
BONDINGSTRAP
N
INSULATED NEUTRALFigure 25
35
79
1113
1517
1921
2325
2729
46
810
1214
1618
2022
2426
2930
1 2
MAIN CIRCUIT BREAKER
A B
BONDINGSTRAP
N
INSULATED NEUTRAL
Figure 26
1113
1517
1921
2325
2729
1214
1618
2022
2426
2830
1
3
5
7
9
2
4
6
8
10
MAIN CIRCUIT BREAKER
A B
N
BONDINGSTRAP
INSULATED NEUTRAL
Figure 27
1921
2325
2729
2022
2426
2830
1
3
5
7
9
11
13
15
17
2
4
6
8
10
12
14
16
18
MAIN CIRCUIT BREAKER
A B
N
BONDINGSTRAP
INSULATED NEUTRAL
Wiring Diagrams
Symbol Key TYPE C, 1-POLE ORTYPE A, 2-POLES
NOTCHED BUS STAB
SOLID BUS STAB
TYPE C, 1-POLE
Type BR LoadcentersWiring Diagrams
October 1998
CAT.73.01.T.E
Cutler-Hammer C-31
30
32
34
36
38
40
3030
4040
Figure 28
1
3
5
7
9
11
13
15
17
19
21
23
25
2
4
6
8
10
12
14
16
18
20
22
24
26
2827
29
31
33
35
37
39
MAIN CIRCUIT BREAKER
A B
N
BONDINGSTRAP
INSULATED NEUTRAL
Figure 30
1
3
5
7
9
11
13
15
17
19
2
4
6
8
10
12
14
16
18
20
2123
2527
2931
3335
3739
2224
2628
3032
3436
3840
MAIN CIRCUIT BREAKER
A B
N
BONDINGSTRAP
INSULATED NEUTRAL1
3
5
7
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
Figure 31
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
MAIN CIRCUIT BREAKER
A B
9
41
N
BONDINGSTRAP
INSULATED NEUTRAL
Figure 35
MAIN LUGS
13
57
911
1315
1719
2123
2527
2931
3335
24
68
1012
1416
1820
2224
2628
3032
3436
A B C
BONDINGSTRAP
INSULATED NEUTRAL
N
Figure 32
NA B C INSULATED NEUTRAL
Figure 33
MAIN LUGS
1
3
5
911
1315
1719
2123
2527
2931
33
35
37
39
41
2
4
6
1012
1416
1820
2224
2628
3032
34
36
38
40
42
A B C
7 8
BONDINGSTRAP
INSULATED NEUTRAL
N
Figure 34
MAIN LUGS
35
79
1113
1517
1921
2325
2729
3133
3738
39
41
46
810
1214
1618
2022
2426
2830
3234
3840
41
42
A B C
1 2
BONDINGSTRAP
INSULATED NEUTRAL
N
Figure 29
911
1315
1719
2123
2527
2931
3335
3739
24
68
1012
1416
1820
2224
2628
3032
3436
3840
13
57
MAIN CIRCUIT BREAKER
A B
N
BONDINGSTRAP
INSULATED NEUTRAL
1632
2040
1224
1836
Wiring Diagrams
Symbol Key TYPE C, 1-POLE ORTYPE A, 2-POLES
NOTCHED BUS STAB
SOLID BUS STAB
TYPE C, 1-POLE
Type BR LoadcentersWiring Diagrams
CAT.73.01.T.E
Cutler-HammerC-32October 1998
Figure 36
MAIN CIRCUIT BREAKER
A B
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
N
INSULATED NEUTRAL
Figure 37
MAIN LUGS
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
A B C
BONDINGSTRAPS
➀
INSULATED NEUTRAL
N
Figure 38
MAIN LUGS
79
1113
1517
1921
2325
2729
3133
3537
3941
2
4
6
10
1214
1618
2022
2426
2830
3234
3638
4042
A CB N
INSULATED NEUTRAL
Figure 39
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
N
MAIN LUGS
A CB
INSULATED NEUTRAL
1
3
5
8
Figure 40
MAIN LUGS
13
57
911
1315
1719
2123
2527
2931
3335
24
68
1012
1416
1820
2224
2628
3032
3436
A CBN
INSULATED NEUTRAL
Wiring Diagrams
Symbol Key TYPE C, 1-POLE ORTYPE A, 2-POLES
NOTCHED BUS STAB
SOLID BUS STAB
TYPE C, 1-POLE
➀ Two bonding straps provided on 225 ampere loadcenters only.
Type BR LoadcentersWiring Diagrams
October 1998
CAT.73.01.T.E
Cutler-Hammer C-33
N
Figure 42
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
MAIN BREAKER
A CB
INSULATED NEUTRAL
Figure 43
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
MAIN BREAKER
A CB
BONDINGSTRAPS
➀
INSULATED NEUTRAL
N
MAIN LUGS
13
57
911
1315
1719
2123
24
68
1012
1416
1820
2224
A B N
Figure 44
INSULATED NEUTRAL
Figure 45
1
3
5
7
2
4
6
8
911
1315
1719
2123
1012
1416
1820
2224
MAIN CIRCUIT BREAKER OR MAIN LUG BLOCK
N
BONDINGSTRAP
INSU
LATED N
EUTR
AL
A
B
A
B
Figure 46
12
34
56
78
BONDEDNEUTRAL
MAIN CIRCUIT BREAKER
FEED THRU LUGS
A B
MAIN BREAKER
Figure 41
1
3
5
7
911
1315
1719
2123
2527
33
35
37
39
41
2
4
6
8
1012
1416
1820
2224
2628
34
36
38
40
42
A CB
BONDINGSTRAP
INSULATED NEUTRAL
2931
3032
N
Wiring Diagrams
Symbol Key TYPE C, 1-POLE ORTYPE A, 2-POLES
NOTCHED BUS STAB
SOLID BUS STAB
TYPE C, 1-POLE
➀ Two bonding straps provided on 225 ampere loadcenters only.
Type BR LoadcentersWiring Diagrams
CAT.73.01.T.E
Cutler-HammerC-34October 1998
Figure 49
13
911
1315
1719
2123
24
1012
1416
1820
2224
68
57
N
BONDINGSTRAP
INSU
LATED N
EUTR
AL
A
B
A
B
Figure 50
1
3
5
7
9
11
13
15
2
4
6
8
10
12
14
16
1719
2123
1820
2224
N
BONDINGSTRAP
INSU
LATED N
EUTR
AL
A
B
A
B
Figure 51
13
57
911
1315
1719
2123
24
68
1012
1416
1820
2224
BONDINGSTRAP
INSULATED NEUTRAL
OR
A
B
C
A
B
C
MAINCIRCUIT
BREAKER
MAINLUG
BLOCK
N
Figure 53
MAIN CIRCUIT BREAKER
A B
A BMAIN LUGS
OR
2123
2527
2931
1
3
5
7
9
11
13
15
17
19
2
4
6
8
10
12
14
16
18
20
3335
3739
2224
2628
3032
3436
3840
N
BONDINGSTRAP
INSULATED NEUTRAL
Figure 52
13
57
911
1315
24
68
1012
1416
MAIN CIRCUIT BREAKER
A B
BONDINGSTRAP
N
INSULATED NEUTRAL
A BMAIN LUGS
OR
FEED THRU LUGS
Figure 54
1
3
5
7
2
4
6
8
N
INSULATED NEUTRAL
MAIN CIRCUIT BREAKER
A B C
911
1315
1719
2123
2527
2931
33
35
37
39
41
1012
1416
1820
2224
2628
3032
34
36
38
40
42
Figure 48
OR
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
A
B
C
BONDINGSTRAP
INSU
LATED N
EUTR
AL
A
B
C
MAINCIRCUIT
BREAKER
MAINLUG
BLOCK
N
Figure 47
MAIN CIRCUIT BREAKER
A B
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
N
BONDINGSTRAP
INSULATED NEUTRAL
A B
MAIN LUGSOR
ORMAIN
CIRCUITBREAKER
MAINLUG
BLOCKOR
MAINCIRCUIT
BREAKER
MAINLUG
BLOCK
Symbol Key TYPE C, 1-POLE ORTYPE A, 2-POLES
NOTCHED BUS STAB
SOLID BUS STAB
TYPE C, 1-POLE
Wiring Diagrams
Type BR LoadcentersWiring Diagrams
October 1998
CAT.73.01.T.E
Cutler-Hammer C-35
Figure 56
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
N
INSULATED NEUTRAL
MAIN CIRCUIT BREAKER
A
B
Figure 57
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
N
INSULATED NEUTRAL
MAIN CIRCUIT BREAKER
A B C
Figure 58
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
N
INSULATED NEUTRAL
MAIN CIRCUIT BREAKER
A B C
Figure 55
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
A B
N
INSULATED NEUTRAL
Figure 59
MAIN CIRCUIT BREAKER
BONDINGSTRAP
N
INSULATEDNEUTRAL
1719
1820
FEED THRU LUGS
A
B
13
57
24
68
911
1315
1012
1416
Figure 60
MAIN CIRCUIT BREAKER
BONDINGSTRAP
N
INSULATEDNEUTRAL
1315
1719
1416
1820
A
B
1
3
2
4
1
3
2
4
5
7
6
8
9
11
10
12
Symbol Key TYPE C, 1-POLE ORTYPE A, 2-POLES
NOTCHED BUS STAB
SOLID BUS STAB
TYPE C, 1-POLE
Wiring Diagrams
Type BR LoadcentersWiring Diagrams
CAT.73.01.T.E
Cutler-HammerC-36October 1998
Figure 65
13
57
911
1315
1719
2123
24
68
1012
1416
1820
2224
BONDINGSTRAP
INSULATED NEUTRAL
A
B
C
MAIN CIRCUIT BREAKER
N
Figure 63
MAIN LUGS
BONDINGSTRAP
N
INSULATEDNEUTRAL
FEED THRU LUGS
13
57
24
68
911
1315
1012
1416
A B
Figure 62
35
79
1113
1517
1921
2325
2729
46
810
1214
1618
2022
2426
2830
A B
N
INSULATED NEUTRAL
BONDINGSTRAP
MAIN LUGS
1 2
Figure 64
911
1315
1719
2123
2527
2931
3335
1012
1416
1820
2224
2628
3032
3436
A B
N
INSULATED NEUTRAL
BONDINGSTRAP
MAIN LUGS
1 2
3 4
5 6
7 8
3739
3840
Figure 61
MAIN CIRCUIT BREAKERA B
N
BONDINGSTRAP
INSULATED NEUTRAL
1
3
5
7
2
4
6
8
911
1315
1719
2123
2527
2931
1012
1416
1820
2224
2628
3032
3335
3739
3436
3840
Figure 66
GROUND
111
1 2 3 4 5
NEUTRAL
MAIN
Figure 67
12
34
56
78
910
1112
1314
1516
1718
1920
INSULATED NEUTRAL
A
B
MAINCIRCUIT
BREAKERN
Wiring Diagrams
Type BR LoadcentersWiring Diagrams
Symbol Key TYPE C, 1-POLE ORTYPE A, 2-POLES
NOTCHED BUS STAB
SOLID BUS STAB
TYPE C, 1-POLE
October 1998
CAT.73.01.T.E
Cutler-Hammer C-37
General
A. The Contractor shall furnish and install deadfront loadcenters incorpo-rating circuit breakers of the number, rating and type as specified herein and as shown on the contract drawings.
B. The loadcenter and all components shall be designed, manufactured and tested in accordance with the latest applicable standards of UL, NEMA and NEC including:
1. UL 67 — Standards for Panelboards.
2. UL 50 — Standards for Cabinets and Boxes.
3. UL 489 — Standards for Molded Case Circuit Breakers.
4. UL 869 — Standards for Service Equipment.
5. Federal Specification W-C 375B — Circuit Breakers.
6. Federal Specification W-C P115b — Panel Power Distribution Type 1, Class 2.
Qualifications
A. The manufacturer of the loadcenter shall be the manufacturer of the circuit breaker within the loadcenter.
B. For the equipment specified herein, the manufacturer shall be ISO 9000 certified.
C. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of seven (7) years.
Manufacturers
A. Cutler-Hammer.
Ratings
A. Loadcenters shall be rated for 120/240V AC and shall have short circuit ratings as shown on the drawings or as herein scheduled, but not less than 10,000 amperes RMS symmetrical.
B. Circuit breakers shall be a minimum of 125 ampere frame. Circuit breakers 15 through 125 amperes trip size shall take up the same pole spacing.
C. Loadcenters shall be labeled with a UL short circuit rating. When series combination ratings are applied with integral or remote upstream devices, a label shall be provided. Series com-bination ratings shall cover all trip ratings of installed frames. It shall
state the conditions of the UL series ratings including:
1. Size and type of upstream device.
2. Branch devices that can be used.
3. UL series short circuit rating.
Construction
A. All interiors, with the exception of the branch circuit breakers, shall be com-pletely factory assembled with main breakers, main lugs, or no main device.
B. Interiors shall be designed so that cir-cuit breakers can be replaced without disturbing adjacent units and without removing the main bus connectors and shall be designed so that circuits may be changed without machining, drilling, or tapping.
C. Physical means shall be provided to prevent the installation of more over-current devices than that number for which the enclosure was designed, rated, and approved. Half-size break-ers shall have a UL listed rejection tab over the line terminals. Loadcenter interiors must have notched stabs to accept these rejection tab class CTL breakers, if required and approved.
Bus
A. Bus bars for the main and cross con-nectors shall be➀ [tin-plated alumi-num] [copper] in accordance with Underwriters Laboratories stan-dards. Bussing shall be braced throughout to conform to industry standard practice governing short circuit stresses in loadcenters.
B. Neutral bussing shall have a suitable lug for each outgoing feeder requir-ing a neutral connection of same ampacity as branch.
Wiring/Termination
A. All wire connectors and terminals shall be of the anti-turn solderless type and shall be suitable for copper or alumi-num wire of the sizes indicated. All connectors must meet the “Require-ments for Wire Connectors and Solder-ing Lugs” as stated in UL 486B.
B. All loadcenters where marked shall be suitable for use with 60°C or 75°C rated wire.
Circuit Breakers
A. Circuit breakers shall be molded case type. Circuit breakers shall have four-rivet construction (GFI Type – 5 rivets). Multipole circuit breakers shall be of a stack pole design to provide electrical phase isolation.
Typical SpecificationsB. Each pole of the circuit breaker will
provide inverse time delay overload and instantaneous short circuit pro-tection by means of both thermal and magnetic sensors.
C. The circuit breaker calibration shall not be affected by environmental changes in relative humidity. The ther-mal bimetal element shall be welded to the steel frame and calibration shall be set independent of the molded case by computer controlled equipment.
D. All circuit breakers shall be operated by a toggle-type handle and multipole circuit breakers shall have an internal common trip mechanism. The circuit breakers shall incorporate trip mecha-nisms that are mechanically trip-free from the handle. The handle position shall provide visual trip indication.
E. Contacts shall be of non-welding silver alloy.
F. All circuit breakers shall have the trip rating inscribed on the handle on each circuit breaker pole. Also, unique color-coded cases that indicate the UL listed 10 kA or 22 kA interrupting rat-ings. Breakers shall be able to be used as main or branch disconnect devices.
G. Branch circuit breakers may also be used in the 1/2-inch (12.7 mm) per pole ratings that include 2-pole 1-inch (25.4 mm) wide modules and 4-pole 2-inch (50.8 mm) wide modules. 2-pole circuit breakers must incorporate a common trip mechanism. The exclu-sive CTL rejection tab feature shall be provided to limit the number of branch devices for a loadcenter to 42, in com-pliance with NEC Article 384-15.
H. Circuit breakers shall be completely enclosed in a molded case of thermoset material. No internal aluminum parts shall be used. All internal ferrous parts shall be plated to prevent corrosion.
I. All terminals shall be listed for use with copper or aluminum conductors. Terminals shall be of the box lug or clamp type design. The terminals shall meet UL 486B requirements and shall be suitable for use with either 60°C or 75°C wire.
J. The calibrated bimetal assembly shall be mechanically isolated from the load terminal using a flexible braided copper shunt wire, such that move-ment of the terminals due to twisting and overtorquing does not affect breaker calibration.
K. Breakers shall be SWD rated and/or HACR rated as required.
➀ Note to spec writer – select one (copper available in limited ratings)
Type BR LoadcentersTypical Specifications
CAT.73.01.T.E
Cutler-HammerC-38October 1998
L. Arc Fault Interrupting circuit breakers, (AFI), shall be provided on all 15 and 20 ampere single-phase 120/240V AC circuits except those indicated as remote controlled breakers. AFI breakers shall be ”Classified for miti-gating the effects of arcing faults,” or conforming to UL Standard 1699 and as defined by Article 210-12 Section A of the 1999 NEC Code.
Surge Protection Devices
All 120/240V AC single-phase load-centers shall have surge protection provided by a [Clipper Home Surge Protector device] [plug-in surge protection device].
A. The Clipper Home Surge Protector shall be supplied in its own rugged steel enclosure and must be suitable for flush or surface mounting exter-nal of the loadcenter. The device shall provide surge protection for the load-center as well as protection for: two incoming telephone lines and one incoming coaxial cable. The surge protector shall be installed in accor-dance to NEC Article 280 and be listed under UL1449, (2nd Edition), and UL497A. The units shall be CSA certified and be tested to meet ANSI/IEEE Category B3 and C3 levels. The surge protector shall incorporate a surge plane design to facilitate a
common point of grounding for all connected power, telephone, and coaxial incoming conductors. The device shall provide, as a minimum, the following protection:
1. Up to 39 kA surge current protec-tion per phase for transients on the incoming AC line
2. Up to 10 kA surge protection per pair for telephone lines
3. Up to 5 kA line to shield (ground) protection for coaxial conductors
– OR –
A. The surge protection device shall be capable of plugging onto a maximum of two adjacent spaces in a single-phase loadcenter. The device shall pro-vide, as a minimum, up to 10 kA surge current protection per phase for tran-sients on the incoming AC line.
B. Surge protection devices must be equipped with LEDs to indicate proper functioning of the internal electronics.
Enclosures
A. Loadcenter shall have NEMA Type 1 general purpose or NEMA Type 3R rainproof enclosures as indicated on the drawings and shall be surface or combination flush/surface mounted except where noted.
B. Boxes shall be made from galvanized sheet steel having multiple knockouts. Rainproof boxes shall use galvanized steel or an approved coating system which meets or exceeds standards for
Typical Specifications, Continued
outdoor NEMA Type 3R enclosures. Boxes shall be of sufficient size to pro-vide at least a minimum code gutter space on all sides.
C. The deadfront shall have an easy adjustment feature for flush applications.
D. Boxes shall be factory assembled into a single rigid structure.
E. Unless otherwise noted on drawings, hinged doors covering all circuit breaker handles shall be included in all trims. Trim doors shall not uncover any live parts in making the circuit breaker handles accessible. If key locks are required, all locks shall be keyed alike.
F. Combination trims for flush and surface panels shall be flat and shall overlap the box by at least 5/8-inch (15.9 mm) all around. Trims shall be mounted by a screwdriver without the need for special tools.
Finish
A. Trims shall be bonderized and finished with a light gray ANSI-61 enamel. The paint finish shall be of a type to which field applied paint will adhere.
Factory Testing
A. The standard factory tests shall be performed on the equipment provided under this section. All tests shall be in accordance with the latest version of UL and NEMA.