Top Banner

of 20

Dynamics of Hydronic Systems - JCI

Feb 21, 2018

Download

Documents

Antonio Lebrun
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    1/20

    Valve and Actuator Manual 977

    Hydronic System Basics Section

    Engineering Bulletin H112

    Issue Date 0989

    1989 Johnson Controls, Inc. 1Code No. LIT-351H112

    A hydronic system can be configured in many different ways. This report

    will discuss the following types:

    1. Reverse Return

    2. Direct Return

    3. Primary/Secondary

    The variant configurations of the hydronic systems noted above will be

    analyzed as well as the relative advantages and disadvantages of each.

    Part-load characteristics will also be considered.

    Any of the three types of hydronic systems could be utilized in either a

    heating or cooling system. To simplify the remainder of this report only

    the case of a cooling system will be considered. Most of the concepts

    covered however, would be applicable for either heating or cooling

    systems.

    It is strongly recommended that the concepts discussed in Engineering

    Reports H111 and H110 be understood before preceding with this report.

    Engineering Report H111 includes a detailed discussion of the

    performance of control valves. Engineering Report H110 discusses the

    relationship between fluid flow and pressure drop as it pertains to typicalhydronic systems.

    Accurate, stable control is dependent upon two factors. The first is the

    ability of the controller and control valve to compensate for process

    nonlinearites. A coil is a good example of a nonlinear process. If the

    capacity of a coil is plotted for each flow rate through the coil, the result is

    a logarithmic relationship. Secondly, the physical limitations of the

    control valve must be considered. As discussed in Engineering Report

    H111, all control valves have some amount of uncontrollable flow when

    the valve plug is initially lifted form its seat. The magnitude of this

    uncontrollable flow is related to the valve rangeability and the pressure

    differential across the valve. Rangeability values are limited by machining

    process tolerances. Therefore, it becomes important to minimize the

    variation in pressure differential across the valve to minimize the

    uncontrollable flow through it.

    Dynamics of Hydronic Systems

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    2/20

    2 H112 Engineering Bulletin

    Even small amounts of uncontrollable flow can compromise the ability of

    a hydronic system to be properly controlled. This is the result of the

    extremely high coil gain at low flow rates. It is important to properly size

    the control valves. It is also necessary for the consultant to design a

    hydronic system which is able to maintain a relatively constant branch

    differential pressure, Pb, regardless of building load. This reportdiscusses how well the standard types of distribution systems are able to

    maintain a constant Pb.

    In a reverse return system the pressure drops in the distribution

    piping between the circulating pump and each air handling unit are

    equal. This is true because the system is designed so that the

    length of the water circuit is the same for each air handling unit

    regardless of its location with respect to the circulating pump. As

    a result the Pbfor every branch is equal regardless of the

    magnitude of the building cooling load. If the air handling unit

    cooling coils are all selected for the same pressure drop this type

    of system is self-balancing. Unfortunately the installed cost of a

    reverse return piping system is higher than that of the other types

    of hydronic systems. This is due primarily to the cost of the

    additional chilled water return piping (See Figure 1).

    Reverse ReturnDistributionSystems

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    3/20

    H112 Engineering Bulletin 3

    When 3-way valves are installed in a reverse return system, each valve can

    be optimally selected based upon the same criteria. Changes in the

    magnitude of the cooling load will have little effect on the chilled water

    flow rate. As a result, the value of Pbfor every branch will remain

    constant regardless of changes in the magnitude of the building cooling

    load.In the case of the reverse return system shown in Figure 1 the Pbfor

    every branch will alwaysbe 50ft H2O. Since Pbis always

    50ft H2O, every control valve can be optimally selected, based upon the

    above criterion. If a valve authority of 50% is desired, all of the control

    valves can be selected for a 25ft H2O pressure drop at design flow. Since

    the branch pressure drop does not deviate from 50ft H2O, there should be

    no increase in uncontrollable flow nor will there be any loss in effective

    valve travel as the building cooling load decreases.

    As with any system which utilizes 3-way valves, the flow rate through the

    chiller(s) can always be maintained at a constant level without therequirement for a large central plant bypass with its associated controls.

    Because the 3-way control valves shown in Figure 1 are mixing valves

    piped in a bypass configuration, problems associated with control valve

    actuator spring range shift or the inability to shut off flow through the

    cooling coil will be minimized.

    The disadvantages of utilizing 3-way valves are increased installation and

    operating costs; specifically, a more complex (costly) coil piping

    arrangement, a high continuous building flow requirement and a lower

    overall chiller coefficient of performance (C.O.P). When 3-way control

    valves are installed, the building demand for chilled water does not vary

    with diversity in the building thermal load. Remember, the flow rate

    through each branch does not change with the cooling load requirements

    of the space served by the air handling unit. Only the chilled water flow

    rate through the cooling coil changes with the load. Consequently, chilled

    water pumps must often be operated without their associated chiller to

    insure each branch will have chilled water available to meet the space

    cooling load. Otherwise the branches nearest the chilled water pumps will

    consume all of the available chilled water.

    In the case of a chilled water system the operation of extra chilled water

    pumps not only increases pumping horsepower requirements but also

    reduces the overall chiller plant C.O.P. The lower overall chiller plantC.O.P. is the result of mixing relatively warm water passing through a

    nonoperating chiller with exceptionally cold water leaving a operating

    chiller. This is required to meet both the building flow and chilled water

    supply temperature requirements. The C.O.P. of the operating chiller

    decreases since it is forced to provide a lower chilled water supply

    temperature for a given building thermal load.

    This problem is illustrated in Example 1.

    Reverse ReturnSystem with3-way Valves

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    4/20

    4 H112 Engineering Bulletin

    Refer to Figure 1. This distribution system was designed for a total

    cooling capacity of 400 tons. There are four air handling units (AHU),

    each with a design capacity of 100 tons. Each AHU requires 150 gpm of

    chilled water at a 16F rise (45-61F) when fully loaded.

    Assume that the AHU is Branch #4 serves a computer facility and has a

    constant cooling load of 100 tons regardless of outdoor conditions. Alsoassume the AHUs in branches #1 through #3 serve exterior zones in the

    building. Finally, assume it is a temperate spring day, such that the

    cooling load on the AHUs located in branches #1 through #3 is 20 tons per

    AHU.

    The total building cooling load is 160 tons. It would seem, since each

    chiller has a capacity of 200 tons only one chiller will need to operate.

    Unfortunately things arent that simple. Because this distribution system

    has 3-way control valves, both chilled water pumps must operate to

    maintain flow in all branches.

    The cooling coil in branch #4 is fully loaded. Therefore 150 gpm ispassing through this coil and is being heated from 45F to 61F.

    Meanwhile in branches #1 though #3 only 30 gpm of the chilled water

    actually passes through the cooling coil. The other 120 gpm of 45F

    chilled water bypasses the coil. These two streams then mix resulting in a

    branch chilled water return temperature of 48.2F. The temperature of the

    chilled water returning to the central plant will be 51.4F after the water

    returning from all four branches is mixed.

    Here is the problem. A single operating chiller must produce 38.6F

    chilled water if 45F water is to be supplied to the building. This

    extremely low chilled water temperature requirement is dictated by thefact an equal volume of 51.4F water is simply passing through the

    nonoperating chiller and the AHU in branch #4 requires 45F to meet its

    cooling load.

    When a chiller designed to produce 45F chilled water is forced to produce

    lower temperature chilled water its C.O.P. drops in a nonlinear manner.

    For each additional degree drop in chilled water supply temperature

    increasing amounts of compressor power is required. In this case it is

    unlikely that the one operating chiller could even provide 38.6F chilled

    water. In this extreme case both chillers would be required to operate even

    though the actual cooling load is less than the capacity of one chiller. Thisis very inefficient.

    Example 1

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    5/20

    H112 Engineering Bulletin 5

    When 2-way valves are installed in a reverse return system the Pbfor

    every branch will the same regardless of load, but the magnitude of the

    Pbwill vary with changes in the building cooling load. This occurs

    because the pipe-friction factor changes with the variable chilled water

    flow rate (See Figure 2).

    A reduction in cooling load will cause one or more of the 2-way control

    valves to reduce the system chilled water flow rate. The hydronic system

    depicted in Figure 2 does not have a central plant bypass. Without a

    bypass the pressure developed by the chilled water pump(s) will increase

    with the reduction in the cooling load. The pumps operating point will

    ride up its pump curve as the chilled water flow rate decreases. Thisincrease in pressure developed by the pump, as well as the reduced pipe-

    friction factor, will increase the differential pressure across the branches.

    This is undesirable. The numbers shown in Figure 2 without parenthesis

    represent the system pressures at maximum design cooling load. The

    numbers shown in parenthesis represent system pressures when each

    branch is at (1/2) of its design load. Notice how each Pbincreased from

    50ft to 120ft H2O.

    Reverse ReturnSystems With2-way Valves

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    6/20

    6 H112 Engineering Bulletin

    If the distribution system had a central plant bypass, the magnitude of the

    Pbcould have been held constant (See

    Figure 3).

    The control valve located in the central plant bypass will be controlled by

    a differential pressure controller. The high and low reference sensing lines

    for the controller will be connected across one of the branches in the

    distribution system. If the sensed differential pressure deviates from the

    controller set-point, the control valve in the bypass piping will modulate as

    required to maintain the desired Pb.

    Since each branch has the same Pbin a reverse return system, common

    sense would dictate that the sensing location for the differential pressure

    controller would be across the branch closest to the bypass. This would

    reduce the length of the controller sensing and/or output lines, thereforereducing installation costs. This system has all of the advantages of a

    reverse return system with 3-way valves, but does not have its

    disadvantages.

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    7/20

    H112 Engineering Bulletin 7

    As an alternative to using a central plant bypass to maintain a constant

    Pb, a variable frequency drive could be installed on the chilled water

    pump motor. The differential pressure controller would then vary the

    speed of the chilled water pump to maintain the desired Pb. The main

    problem with using a variable speed drive in lieu of a central plant bypass

    is that the flow through the chiller(s) will now vary with changes in thecooling load. This potential problem must be carefully considered, and it

    would be wise to consult the chiller manufacturer to obtain acceptable

    guidelines.

    The major advantage in using a variable speed drive in lieu of a central

    plant bypass is the potential for energy savings. The variable speed drive

    will save energy in two areas. First, any energy losses which normally

    occur within the bypass valve will be avoided. In addition, the reduction

    in the chilled water flow rate will proportionally decrease the chilled water

    pump brake-horsepower requirement. Remember, in a system with a

    central plant bypass the flow rate to the building is directly proportional to

    the cooling load, but the flow rate through the chilled water pumps

    actually increases with reductions in the cooling load. In a system

    utilizing variable speed drives the flow rate through the pumps will vary

    directly with the cooling load.

    Keep in mind however, that in a properly sequenced multiple chiller

    central plant the flow rate through the bypass line will be less than the

    water flow rate associated with only one chiller. In other words, the

    excess amount of chilled water produced in the central plant above and

    beyond the demand required by the building would be less than the

    amount of water provided by one chilled water pump. This assumes there

    is one chilled water pump for each chiller. Therefore, the savingsprovided by using a variable speed drive compared to a central plant

    bypass is not a function of the total plant chilled water pumping capacity.

    Instead the potential savings is a function of the capacity of only one, not

    all, of the chilled water pumps. If the central plant has a large number

    (greater than four) of chillers and chilled water pumps, variable speed

    drives will save very little energy over a properly operated constant speed

    system utilizing a bypass valve.

    In a direct return distribution system the length of the distribution piping

    between the chilled water pump and each air handling unit will vary (See

    Figure 4). As result the Pbfor every branch will be different. The closer

    an air handling unit is located to the chilled water pump, the larger the

    Pb. The magnitude of the Pbwill also be affected by the chilled water

    flow rate. Remember the pipe friction-factor changes with the square of

    the flow rate through the pipe.

    DirectReturnDistributionSystems

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    8/20

    8 H112 Engineering Bulletin

    The following four items can be utilized to minimize the variation in Pb:

    1. Properly sizing the distribution piping can help to maintain a

    constant Pb. This piping should be sized for small (less than 4 ft

    head loss per 100 ft of pipe) friction-factors. The change in

    pressure drop of the distribution piping, as flow is varied from

    maximum to minimum, then should not exceed the design pressuredrop across a properly sized control valve. This is true for all but

    the largest systems. Some central campus systems, and the like,

    would require booster pumps in remote locations.

    2. Utilize a central plant bypass or variable speed pump. The Pb

    across one of the branches can then be maintained at a constant

    level. This will prevent unwanted changes in the pressure

    developed by the chilled water pump from being shifted out to the

    branches.

    3. Utilize control valves with large design pressure drops.

    4. In some cases, utilize balancing valves.

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    9/20

    H112 Engineering Bulletin 9

    When 3-way valves are installed in a direct return hydronic system the

    magnitude of the Pbfor each branch will be constant. This is true

    because the chilled water flow rate is always constant and is not affected

    by the load. However the magnitude of the Pbwill be different for each

    branch. This occurs because the length of water circuit between the

    branch and chilled water pump is different for each branch (See Figure 4).The control valves for each branch can, therefore, be optimally sized for

    any cooling load condition. Unfortunately each branch will have a

    different sizing criterion since the Pbis different for each branch. In

    comparison, the 3-way valves in the reverse return systemcan all be

    sized for the same pressure drop.

    As discussed earlier, the 3-way valves will insure a constant flow rate

    through the chiller(s). Problems with actuator spring range shift, and

    cooling coil shutoff will also be minimal. Unfortunately, the same

    disadvantages are still apparent. The installed cost of a system with 3-way

    valves is higher due to more complex coil piping arrangements. Also asdiscussed previously the chiller plant C.O.P. will be lower when compared

    to a system with 2-way valves. This results from the high continuous

    building demand for chilled water dictating operation of chilled water

    pumps without their associated chiller.

    When 2-way valves are installed in a direct return system, the Pbwill be

    dependent upon the location of the branch relative to the chilled water

    pump and the magnitude of the cooling load (See Figure 5). The numbers

    in parenthesis indicate the system pressures when each branch is at (1/2) of

    its design cooling load. The numbers without parenthesis indicate the

    system pressures when the system is at maximum design cooling load.

    If the system does not have a central plant bypass the value of Pbwill be

    extremely dynamic. These extreme changes in differential pressure occur

    for three reasons: the chilled water pump will ride up its curve, the pipe-

    friction factor in the distribution piping will change with load, and the

    length of the water circuit is different for each branch. This system is as

    far from optimal as any can get.

    Direct ReturnSystem with3-way Valves

    Direct ReturnSystems with2-way Valves

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    10/20

    10 H112 Engineering Bulletin

    If the system does have a central plant bypass, the pressure fluctuations

    across each branch are reduced (See Figure 6). The numbers in

    parenthesis indicate the system pressures when each branch is at (1/2) of

    design cooling load.

    Adding the central plant bypass keeps changes in the pressure developed

    by the chilled water pump from being shifted out to the branches.

    However, since the pipe-friction factor in the distribution piping will

    change with load, the value of the Pbwill be affected.

    Whenever the load in the building decreases and the bypass valve

    opens, the flow rate in the central plant will increase. This occurs

    because the pressure drop across the bypass will decrease as it is

    opened. In turn the pressure developed by the pump will decrease.

    As the pump operating point moves further out on its pump curve,

    its flow rate will increase. This increased flow rate will, in turn,

    increase the pipe-friction factor of the central plant piping.Eventually a balance point between the increased central plant

    piping friction losses and the decreased pressure across the bypass

    will be found. This is graphically shown in Figures 7, 8 and 9.

    Notice how the slope (pipe-friction factor) of the line representing

    1/2 design load changes within the central plant portion of the

    graph.

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    11/20

    H112 Engineering Bulletin 11

    Assuming the branches are uniformly spaced in a distribution

    system, the best differential pressure sensing location for the

    bypass controller is in the middle of the system. Figure 7 relates

    the change in Pbwith location as a function of cooling load. The

    graph illustrates the possible variation in Pbas the building load

    changes from no load to maximum design load. The slope of each

    of the different load lines is equal to the negative of the respective

    piping friction factors. The area underneath the lowest load line

    represents the pressure available for the branch piping, coil and

    control valve. Depending on the location of the branch in the

    system the lowest load line could be either the design or no loadline. In this case the control valves in the first half of the branches

    which are closest to the pump should be selected for a higher

    design pressure drop than those in the second half of the system.

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    12/20

    12 H112 Engineering Bulletin

    By sensing differential pressure in the middle of the distribution system

    the magnitude of the maximum variation in branch differential pressure is

    minimized when compared to other sensing locations. Compare the

    maximum variation of Pbin the building portion of Figure 7 to that

    shown in Figures 8 or 9.

    The bypass control scheme shown in Figure 8 will provide good pressure

    control at the end of the system. Unfortunately the variation in Pbat thebeginning of the system may be excessive.

    The bypass control scheme shown in Figure 9 can provide good pressure

    control at the beginning of the system. Unfortunately the variation in Pb

    at the end of the system may be excessive.

    In spite of some inherent problems, direct return hydronic systems with 2-

    way control valves are very popular. This is likely due to the fact it has a

    lower initial cost relative to other types of hydronic systems and it is a

    very energy efficient pumping system. Lastly, a direct return system

    incorporating either a central plant bypass or variable speed pumping can

    provide acceptable pressure control when distribution piping is properlysized. Proper distribution pipe sizing is critical to insure trouble free

    control. If the distribution piping is undersized the Pbcan vary

    significantly with the load.

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    13/20

    H112 Engineering Bulletin 13

    As a rule, the potential changein Pbmust be less than the designpressure drop of the control valve, or problems can occur. These problems

    can manifest themselves in the following ways: unacceptable

    uncontrollable valve flow, problems with valve shutoff and spring range

    shift, valve cavitation, and overflowing marginally sized cooling coils.

    A primary secondary distribution system utilizes two sets of pumps. The

    first set is used to pump water through the chillers. These pumps are

    called the primary pumps. The second set of pumps are used to pump

    water through the building. These pumps are called the secondary pumps.

    The primary and secondary pumps are hydraulically isolated from oneanother. This isolation is accomplished by installing a bypass line

    between the primary and secondary pumping systems as shown in

    Figure 10.

    Primary/SecondaryDistributionSystems

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    14/20

    14 H112 Engineering Bulletin

    The bypass line is also often called a decoupler line since it isolates or

    decouples the primary and secondary systems. The direction of flow in

    the decoupler piping can be in either direction. The direction of flow will

    depend upon the amount of chilled water produced in the central plant

    (primary flow) and the amount consumed by the building (secondary

    flow). If the primary loop produces a greater volume of chilled water than

    the secondary system consumes, flow in the decoupler will be from supply

    to return. If then secondary system consumes a greater volume of water

    than the primary system produces the water in the decoupler will flow

    from return to supply. Normally flow within the decoupler should be from

    supply to return. Otherwise the chilled water supply temperature in the

    secondary loop will rise to unacceptable levels.

    The hydraulic isolation allows both the primary and secondary pumping

    systems to function as if the other was not present. The primary pumpsare, therefore, able to maintain a constant flow rate through the chiller

    regardless of the building load.

    The secondary system can be configured as either a direct or

    reverse return distribution system. The same advantages and

    disadvantages discussed earlier will still apply. However, in

    either case only two-way control valves should be installed.

    The chilled water flow rate in the secondary system will then

    vary in relation to the building load. This is desirable for two

    reasons.

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    15/20

    H112 Engineering Bulletin 15

    First, a variable flow secondary system will require less pumping energy

    than other types of systems. The secondary flow rate, in a primary

    secondary system, can be reduced to extremely low flow rates. The

    minimum secondary flow rate is not fixed by flow limitations imposed on

    the system by the chillers. If a variable speed secondary chilled water

    pumps is installed, the amount of pumping power required will beminimized. In a variable speed pumping system, the pumping power

    requirement will vary with the cube of the flow rate as dictated by the

    pump affinity laws. The sensing location for the differential pressure

    transmitter should be near the middle of the secondary system. Once

    again, this location is the best compromise for minimizing the variation in

    the magnitude of the Pb.

    Secondly, if both the magnitude and direction of the flow rate in the

    decoupler are known, this information can be utilized in various building

    automation schemes. Particularly for chiller sequencing. Chiller

    sequencing is discussed in Engineering Report H324.

    It is important for the decoupler line which separates the primary and

    secondary systems to be properly sized. It must be sized so that its

    pressure drop at full flow is kept very small (i.e., less than 1 psig).

    Normally full flow is about 115% of the flow rate associated with the

    largest chiller. Flow rates in excess of this value would indicate an

    operating chiller should be stopped. The decoupler should be a straight

    length of pipe with no restrictions. It is very important for the pressure

    drop in the decoupler to be kept very small to provide the hydraulic

    isolation between the primary and secondary systems. If the size of the

    decoupler is too small, pressure changes in the secondary system will betransmitted into the primary system. This interaction can cause stability

    problems and undesired flow variations through the chillers.

    Occasionally, a primary secondary distribution system with a check valve

    installed in the decoupler line is encountered (See Figure 11).

    Decoupler LineSizingConsiderations

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    16/20

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    17/20

    H112 Engineering Bulletin 17

    Note: Do not use square law type flow meters to measure the flow rate in

    a decoupler line. Square law type flow meters include annubars,

    orifice plates, flow nozzles, and venturi tubes. The output signal

    cannot be accurately measured with these flow meters at

    turndowns greater than 3:1. A bidirectional turbine flow meter

    should be utilized because it can indicate both direction and

    amount of flow accurately at much lower flow rates. Turbine

    meters with turndown ratios of 10:1 are typical, but are available

    with ratios up to 30:1. Remember water must be able to flow bothways through the decoupler line.

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    18/20

    18 H112 Engineering Bulletin

    Notes

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    19/20

    H112 Engineering Bulletin 19

    Notes

  • 7/24/2019 Dynamics of Hydronic Systems - JCI

    20/20

    20 H112 Engineering Bulletin

    Notes

    Controls Group

    507 E. Michigan Street

    P.O. Box 423

    Milwaukee, WI 53201 Printed in U.S.A.