-
Features• Certified to Current test standards BS EN 1366-2
• Fully tested and CE marked and compliant
• Galvanised or stainless interlocking double skin blades
• Stainless steel frame side seals
• 4 modes of operation
• Connections to suit most proprietary ductwork
• Extensive range of supporting controls
DUCTGARDDuct Mounting Fire and Smoke Dampers
SFB (57.9) X
UDC 697.9
Dampers 1 Sep 2020
-
2
DUCTGARDDuct Mounting Fire and Smoke Dampers
Introduction
Control Mode Options
Gilberts Ductgard presents an ‘engineered’ range of
combined smoke and fire dampers suitable for use in all types of
HVAC ductwork. Benefitting from over 50 years of engineering
experience in the industry considerable
ingenuity has been applied in the design and construction
of this product to produce a damper of high efficiency,
reliability, durability and ease of use.
Ductgard has been tested to the latest BS-EN1366-2 fire test
standard and includes mandatory CE marking.
The Gilbert’s Ductgard presents a re-engineered range of
combined fire and smoke dampers suitable for use in HVAC
ductwork systems.
Developed from a well proven heritage of tried and tested damper
designs, considerable ingenuity and manufacturing expertise has
been applied to produce a robust, effective, competitive unit that
is easy to install and maintain.
The unit is designed to fit within all types of ductwork at its
junction with a fire barrier wall, where it can be fixed directly
in or immediately adjacent to the building structure in both
the horizontal and vertical positions.
With a choice of 4 different modes of operation all units
are fully automatic and motorised. All units comprise of an
air-tight galvanised casing (DW144 Class C Specification) with
stainless steel interlocking blades and frame side seals, which
provides a four-hour fire rated assembly. Sizes range from 200 x
200 upto a maximum of 1000 x 1000 in one unit
Dampers over this size are supplied in multiple units but are
not CE compliant.
Features• Certified to Current test standards BS EN 1366-2
• Fully tested and CE marked and compliant
• Galvanised or stainless interlocking double skin blades
• Stainless steel frame side seals
• 4 modes of operation
• Connections to suit most proprietary ductwork
• Extensive range of supporting controls
Mode Description Page
9A Fully automatic opening operating on 24v with failsafe spring
return closure via 72˚c electro thermal link release
4
9B Fully automatic opening operating on 230v with failsafe
spring return closure via 72˚c electro thermal link release
4
10A Fully automatic closure operating on 24v with failsafe
spring return opening via 72˚c electro thermal link release
4
10B Fully automatic closure operating on 230v with failsafe
spring return opening via 72˚c electro thermal link release
4
-
3
DUCTGARDDuct Mounting Fire and Smoke Dampers
Mode 9
Mode 10
DescriptionMode 9 provides a fully automatic type of smoke and
fire damper that operates on the basis of fail safe closure
with
automatic reset. It has been designed to close in smoke
and fire conditions upon a failure of the supply voltage to the
motor or in the event of an electro thermal fusible link separating
at a pre-determined temperature (72°C
standard). Volt free microswitches are included as standard.
OperationMode 9 is fitted with a spring return square drive
motor which will hold the damper open for as long, as the supply
voltage is available. Interruption of this supply will cause
controlled damper closure by way of the motors spring
return operation. In addition however, the damper is fitted with
an electro thermal fusible link which will fail at a pre-
determined temperature (72°C standard) and close the
damper irrespective of the status of the motor.An integral test
pushbutton on the electro thermal fuse
housing allows for the local testing of the damper
operation.
Motor Voltage Control OptionsMode A: 24V AC or DC supply.
Mode B: 230V AC supply.
Note: All options include position microswitches as
standard.
Re-set ProcedureProvided the fusible link is intact the damper
will automatically reset after an interruption of the supply
voltage to the motor. The motor will take
approximately 80 seconds to open the damper.
The spring return motor and terminal box (if fitted) are mounted
on the ductwork connection sleeve. Fully assembled prior to
despatch they
require only the external electrical connections to be made.
DescriptionMode 10 performs in exactly the same manner as the
Mode
9 except that the operation is reversed and the units are fail
safe open. The motor sets the unit in the full closed position
and the unit will only open in the event of an interruption of
the supply voltage to the motor or separation of the thermal
fusible link.
-
4
DUCTGARDDuct Mounting Fire and Smoke Dampers
Dimensional Data Square/Rectangular Spigot Connection
* Allow extra 50mm for cables
Circular Spigot Connection * Allow extra 50mm for cables
B Dimension Up to 350mm dia = 41mm
Over 350mm dia = 55mm
39 120 39
VARYING LENGTHS OF OPTIONAL STUB DUCT AVAILABLE210MM TO 450MM.
PLEASE REFER TO SALES OFFICE
90 40DUCT WIDTH - 4mm
(100 to 1000) 40
40
DU
CT
HE
IGH
T -
4m
m(1
00
to
10
00
)4
0
194
19
8*
19
8*
336*
Dim
en
sio
n ‘A’
Se
e T
ab
le
AL
LO
W F
OR
AC
TU
AT
OR
RE
MO
VA
L
50
25
39
DUCT DIAMETER - 3mm(100 to 1000)B 41 120
194
39
DU
CT
DIA
ME
TE
R -
3m
m(1
00
to
10
00
)3
9
41 B
336*
19
8*
19
8*
Dim
en
sio
n ‘A’
Se
e T
ab
le
1616
38
90 39
AL
LO
W F
OR
AC
TU
AT
OR
RE
MO
VA
L
50
16 16
16
Dimension ADuct Height/Dia. 100 150 200 250 300 350 400 450 500
550 600 650 700 750 800 850 900 950 1000
Dimensio’A’ 84 109 84 159 184 159 184 259 284 259 284 359 384
359 384 459 484 459 484
Damper Handing
Right hand motor
positioning (as shown)
as standard
-
5
DUCTGARDDuct Mounting Fire and Smoke Dampers
Installation Dimensional Data
InstallationFrame(HEVAC)Ref. IF
Sleeve with AngleRef. SF* Suitable for walls
up to 200mm.
Above this thickness refer to our technical
sales office.
Drop RodCleats
Ref. DF
Angle FrameRef. AF
3413134 DUCT WIDTH OR DIA. + 136mm
DU
CT
HE
IGH
T O
R D
IA. +
136m
m
285
DU
CT
HE
IGH
T O
R D
IA. +
81m
m
DU
CT
HE
IGH
T O
R D
IA. +
161m
m
DUCT WIDTH OR DIA. + 189
DUCT WIDTH OR DIA. + 109
DIMENSION = X + 25mm DIMENSION = X
CENTRE LINE OF DUCT
*
CONNECTING DUCTWORK BY OTHERS
CONNECTING
DUCTWORK
BY OTHERS
50 50
50
50
40 40 40O 12mm HOLE FOR DROP RODS
1818
DUCT WIDTH or DIA. + 225
DU
CT
HE
IGH
T O
R D
IA. +
198m
m
35
120
60
60
DIMENSION = X + 25mm DIMENSION = X
CENTRE LINE OF DUCT
6085
-
6
Dry Wall
with sleeve & angles (Ref...SF)Single section sizes
(mm):
100 x 100 to 1000 x 1000
Tested to BS EN 1366-2 for 4 hours
Equivalent to BS EN 13501-3 classification: ES240 (E240S)BS EN
1366-2 test/assessment references: 256538/CC 261450Meets the
requirements of bs 476-20/22 - refer bs 476-10.6.6.3
ALL R
OU
ND
GA
P 5
MM
TYPE 5 PLASTERBOARD
STONE WOOL
SLEEVE
ANGLES
OPENING LINED WITH
TRACK AND BOARD
DUCTGARDDuct Mounting Fire and Smoke Dampers
Installation MethodsDuctgard can be installed in a wide variety
of approved ways using the different installation options detailed
on page 6.
Please remember that only the installation methods detailed
are tested and approved to EN1366-2.
If your installation varies from these options you will need to
confirm approval with Building Control. Manufacturers are not able
to approve alternative installation methods.
Tested to BS EN 1366-2 for 4 hours
Equivalent to BS EN 13501-3 classification: ES240 (E240S)BS EN
1366-2 test/assessment references: 256538/CC 261450Meets the
requirements of bs 476-20/22 - refer bs 476-10.6.6.3
Block/Masonry Wall with sleeve & angles (Ref...SF)Single
section sizes (mm):
100 x 100 to 1000 x 1000
Block/Masonary Wall/Concrete Floorwith HEVAC frame
(Ref...IF)Single section sizes (mm):
100 x 100 to 1000 x 1000
Tested to BS EN 1366-2 for 4 hours
Equivalent to BS EN 13501-3 classification: ES120 (E12 0S)BS EN
1366-2 test/assessment references: 256538/CC 261450Meets the
requirements of bs 476-20/22 - refer bs 476-10.6.6.3
ALL R
OU
ND
GA
P 5
MMBLOCK WALL
BUILDING TIES
MORTAR OR CONCRETE BACK FILL
FRAME POSITIONED CENTRALLY OR
THE CENTRE TO BE AT LEAST
50MM AWAY FROM NEAREST WALL FACE
SLEEVE
ANGLES
MIN.
150MM
Dry Wall
with drop rod cleats (Ref...DF)Single section sizes (mm):
100 x 100 to 1000 x 1000
Tested to BS EN 1366-2 for 4 hours
Equivalent to BS EN 13501-3 classification: ES120 (ES120)BS EN
1366-2 test/assessment references: 256538/CC 261450Meets the
requirements of bs 476-20/22 - refer bs 476-10.6.6.3
M10 DROP RODS
STONE WOOL
TYPE 5 PLASTERBOARD
OPENING LINED WITH
TRACK AND BOARD
-
7
DUCTGARDDuct Mounting Fire and Smoke Dampers
Tested to bs en 1366-2 for 4 hours
Equivalent to bs en 13501-3 classification: es240 (e240s)bs en
1366-2 test/assessment references: 216413/cc 254958/cc 261450Meets
the requirements of bs 476-20/22 - refer bs 476-10.6.6.3
Dry Wall, Masonary or Concrete Floor - with angle frame
(Ref...AF)Single section sizes (mm):-
100 x 100 to 1000 x 1000
MIN. 100MM
MAX. 200MMSTONE WOOL
OPENING LINED WITH TRACK
AND BOARD
TYPE 5 PLASTERBOARD
FLANGE SCREWED
TO TRACK
-
8
CLAMPBRACKET
REVERSE MOUNTEDTRANSFER DRIVE
M6 BOLTS & WASHERS (X4)
ACTUATOR WITH FIXINGBRACKET SUB ASSEMBLY
Reverse Mounted
Actuator Clamping
Kit
439.5
195.5 145
50MM FORCABLE
268
40 DUCT WIDTH - 4MM 40
40
40
DU
CT
HE
IGH
T -
4M
M
25.5
105
565
195.5 270.5
Standard Position
Alternative
Position 1
Alternative
Position 2
145
198
50MM FORCABLE
268
439.5
195.5 145
19
8
50MM FORCABLE
268
19
8
DUCTGARDDuct Mounting Fire and Smoke Dampers
Actuator - Inboard Mounting OptionThe actuator is normally
fitted to the outside face of the motor mounting bracket. Where
limited clearence or other
factors dictate it is posible to move the motor to an inboard
position.
The motor can also be rotated into three alternative positions
either on site or in the factory.
-
9
1 2
- +
M
Control Option A
S1 S2 S3 S4 S5 S6
5° 80°
L N E
M
N L 1 2 3 4 5 6 + + - - S S
1 2 3 4 5 6
2 Core ScreenedCommunication Cable
Belimo Damper Motor
DCM Damper Control Module
240V 50HZFused Spur(option 24V DC)
1 2
- +
M
Control Option B
S1 S2 S3 S4 S5 S6
5° 80°
Control Option A
Control Option B
24 V WIRING DIAGRAM
Power Supply 24V AC +-20%
50/60 Hz 24V DC +-20%
Current Rating 380mA AC max
POWER CONSUMPTION
Opening 5 watts
Holding 2.5 watts
240V WIRING DIAGRAM
Power Supply 240V AC +15% -10%
50/60 Hz 240V AC +10% 50Hz
Current Rating 200mA AC max
POWER CONSUMPTION
Opening approx 6 watts
Holding approx 3 watts
DUCTGARDDuct Mounting Fire and Smoke Dampers
Wiring Diagrams
All ModesAddressable
Mode 9 and 10 Ductgards are normally controlled, by a remote
switch on the Motor Supply.
Note: To interface with Gilberts remote indicators it is
easier
to switch the negative rather than the positive.
Mode 9 and 10 Ductgards in this option are interfaced with
our Gardex Controller as described on Page 11. Motorised
dampers are fitted with the Belimo BLF-T range as standard.
Other actuators are available upon request.
-
10
DUCTGARDDuct Mounting Fire and Smoke Dampers
Control Systems
Bespoke Control Panels
Gilberts offer a wide choice of hard wired and multiplex
controlled systems to meet the challenge of effective fire and
smoke control monitoring.
Available as stand alone, or suitable for interfacing or
incorporating with building management or fire/smoke control
systems designs, the range includes four simple off the shelf
packages through to bespoke designs to satisfy the most
demanding criteria.
The Gardex system has been designed to reduce the cost of
electrical wiring installations and satisfy the most complex
of
control changes. Up to 126 dampers can share the same 2
wire communication line to transmit information to and from
the central controller.
Features
Housing - Metal wall mounted enclosure complete with a
clear hinged lockable front cover and lower cabling chamber.
Protection rating IP55
Keyboard and Display - Directory command programming
via arrow keys and 2 line x 40 character LCD display are
provided as an operator interface.
Fault reporting - Faults are identified on the LCD display and
the controller can be interrogated to determine the
nature of the fault and its location.
Gardex (Modes 9/10 Options Only) Multiplex System
GardexController
DamperIndicator
DamperIndicatorExpander
400mm
500m
m
Bottom Entry GlandPlate 300x90mm (approx)
CENTRAL CONTROLLER
PROGRAMRESET
ACKNOWLEDGE
POWER ON
SYSTEM FAULT
LAMP TEST
FIRE COMMAND
FAULTACKNOWLEDGED
SMOKE DAMPER STATUS INDICATION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
SMOKE DAMPER STATUS INDICATION
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
SMOKE DAMPER STATUS INDICATION
41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
SMOKE DAMPER STATUS INDICATION
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80
TYPICAL OPTIONAL FEATURES• MIMIC AND DAMPER STATUS INDICATOR
LIGHTS• INTEGRAL FIREMANS INTERFACE SWITCH• MECHANICAL FAN CONTROL•
LINE ISOLATION• REMOTE ALARM INTERFACE
Field Stations (DCM)
Available as an integral part of the damper, or as a separate
enclosure, the addressable module has been designed to provide
independent operation of individual or groups of dampers in
accordance with a pre-programmed logic
sequence of events.
Individual dampers are controlled and have there status
constantly monitored by the module in response to signals
from the pre-programmed controller. Maximum length of
communications 2km. In the event of communications failure
dampers assume failsafe position.
These are available in a number of configurations and are
designed and manufactured to suit individual specific requirements.
The electro-mechanical control/monitoring panels are based on IP55
wall mounting enclosures, which can be provided to include such
features as:
• FIREMANS/BMS INTERFACE• MULTI ZONE CONTROL & DAMPER
STATUS
INDICATIONS
• UPS• VOLT FREE CONTROLS FOR REMOTE INDICATION
OR ALARM
Please contact Head Office to discuss specific requirements.
-
11
DUCTGARDDuct Mounting Fire and Smoke Dampers
Ancillary Items
Gilberts range of ancillary Items have been designed for use in
conjunction with both the Ductgard and Smokegard models. Purpose
built for straightforward connection and compatibility they offer a
number of useful services.
Remote Indicators/Master Monitors
Gilberts remote indicator panels can be
linked to damper Modes 5 and 6 and
will provide remote indication of the status of one or more
dampers.
Ref:
• RT1 (1 damper)• MM1-12 (upto 12 dampers)
Larger Panels available upon request
Master Monitor
A more advanced form of remote indication is available with a
master monitor. This unit provides remote indication for the status
of up to 12
individual dampers.
Ref:
• MM1-12*
* dependant on number of dampers on
the system
Standard Power Supply
Standard power supplies are available in two sizes to suit up to
6 or up to 12
dampers. They provide conversion from 240v AC input to a smooth
and stabilised 24v DC output.
Ref:-
• G6 = 6 UNIT OUTPUT• G12 = 12 UNIT OUTPUT• G6R = 6 UNIT OUTPUT
+ RELAY• G12R = 12 UNIT OUTPUT + RELAY
Uninterruptible Power Supply
Uninterruptible power supplies
operating on a 240v AC input provide a smooth 24v DC output to
power up to 12 dampers. Unlike standard
power supplies however, in the event of a power failure, there
will be an automatic changeover to in-built batteries without
tripping the dampers
providing continued power for a period of up to 1 hour.
Ref:-
• UPS6 = 6 UNIT OUTPUT• UPS12 = 12 UNIT OUTPUT• UPS6R = 6 UNIT
OUTPUT + RELAY• UPS12R = 12 UNIT OUTPUT + RELAY
RED LIGHT
SYSTEM TRIPPED
GREEN LIGHT
SYSTEM SET
UNIT No.
AIIFA No.
OUTLINE OF PCB
NOTE: When damper is open yellow is +VE
When damper is closed blue is +VE
O
R
G
YE
LL
OW
BL
UE -V
E D
C
FROM
DUCTGARD
10
0m
m
76mm 35mm
Master Monitor
UP TO 12 PCBs IN 1
MASTER MONITOR
NOTE: When damper is open yellow is +VE
When damper is closed blue is +VE
FROM
DUCTGARD
YE
LL
OW
BL
UE -V
E D
C
O
R
G
O
R
G
240mm
24
0m
m
87mm
240mm
24
0m
m
87mm
POWER SUPPLY
UNITTYPE G12
MAINS INPUT 240 V.A.C.l
OUTPUT TO DAMPER 24 V.A.C.l
WARNING - ISOLATE
MAINS SUPPLY BEFORE
ENTERING
E
N
L
MAIN POWER SUPPLY
240v AC
24v DC POWER OUT
240mm
35
0m
m
87mm
UNINTERUPTABLE
POWER SUPPLY
CELLS:- 27.6v DC MAX: TEST YEARLY
MAINS INPUT: 240v AC
OUTPUT TO DAMPERS 24v DC
ON
ON
THIS UNIT IS DESIGNED TO SUPPLY UP
TO 12 DAMPERS FOR UP TO 1 HOUR
THE INTERNAL DRY-FIT CELLS DO NOT REQUIRE SERVICE OR
ELECTROLYTE LEVEL TOPPING-UP. WARNING: TAKE CARE WHEN
INSIDE THIS UNIT CELLS GIVE 100+ AMPS IF SHORTED OUT
E
N
L
MAIN POWER SUPPLY
240v AC
24v DC POWER OUT
Smoke Detectors
Smoke Detectors are available for in duct or ceiling mounting
and can link directly into Modes 5 & 6 or the output relay of
the Power Supply units. Detectors are 24v DC Ionisation type
Ref:
• In-duct 4 wire - SD3• 4 wire - SD2
-
12
DUCTGARDDuct Mounting Fire and Smoke Dampers
Test Data
Pressure Drop BSRIA Report 15633/1Calculated performance at
various damper settingsSize tested: 500mm x 600mm
Blade Leakage
------- 100mm x 100mm (smallest) unit as tested to BS EN
1366-2
------- 1000mm x 1000mm (largest) unit as tested to BS EN
1366-2
Casing Leakage
Ductgard was tested and found to meet Class ‘C’
Classification BS EN 1751:1999. Leakage recorded at less than
0.1l/s/m² at 2000 Pa
Blade Leakage for a 500mm square Damper------- 500mm x 500mm
unit as tested to BS EN 1366-2
Width (mm)
Height (mm) 100 200 300 400 500 600 700 800 900 1000
100 7.8 9.0 9.8 10.8 11.9 13.2 14.3 15.4 16.5 17.7
200 9.0 10.5 11.3 12.4 13.6 15.4 16.7 18.1 19.4 20.7
300 10.3 11.9 12.8 14.1 15.4 17.7 19.3 20.8 22.4 23.9
400 11.6 13.4 14.4 15.8 17.3 20.0 21.8 23.6 25.4 27.2
500 12.9 14.9 16.0 17.6 19.1 22.3 24.3 26.4 28.4 30.4
600 14.2 16.3 17.6 19.3 21.0 24.6 26.9 29.1 31.4 33.6
700 15.5 17.8 19.1 21.0 22.8 26.9 29.4 31.9 34.3 36.8
800 16.8 19.3 20.7 22.7 24.6 29.3 31.9 34.6 37.3 40.0
900 18.1 20.8 22.3 24.4 26.5 31.6 34.5 37.4 40.3 43.2
1000 19.4 22.3 23.9 26.1 28.3 33.9 37.0 40.2 43.3 46.4
Pre
ssure
Dro
p (
Pa)
Pre
ssure
Dro
p (
Pa)
Pre
ssure
Dro
p (
Pa)
1000
25%
OP
EN
75%
OP
EN
50%
OP
EN
100%
OP
EN
100
500 1000
10
300 100
10
1
100 0
Class C
(BS EN
1751)
0.01100
10 5 50
0.1
50
1
100
Velocity (m/s)
Leakage (m3/hr/m2) Leakage (l/s/m2)
10
10 1000200
EN17
51 C
lass 3
EN17
51 C
lass 2
EN17
51 C
lass 1
Teste
d Res
ult
Weight Chart (kg approx.)Square/Rectangular Spigot
Weight Chart (kg approx.)Circular Spigot
To include a HEVAC/ HVCA Installation Frame, apply the following
multiplier: 1.4
Dia.(mm) Weight (kg)
100 8.4
150 9.8
200 11.8
250 13.4
300 15.1
350 17.2
400 19.1
450 21.3
500 23.4
550 25.8
Dia.(mm) Weight (kg)
600 30.0
650 33.2
700 36.0
750 39.5
800 42.5
850 46.3
900 49.6
950 53.6
1000 57.1
-
13
DUCTGARDDuct Mounting Fire and Smoke Dampers
Operation & MaintenanceInstructions
Trouble-Shooting
Gilberts Damper, Smoke and Fire Control Range
Operating and Maintenance Instructions
All Ductgard units are tested before leaving the factory but
should be test operated prior to commissioning to
ensure correct operation. Quick and easy testing and reset
procedures for each operational mode are detailed on their
respective data pages in this brochure. In addition to their
initial test however, being a fire safety product, it is also
recommended that the units are test operated regularly
thereafter . Test frequency will depend upon the damper
environment but, in the absence of any other information, a maximum
interval of 6 months is recommended. In addition an annual visual
inspection is also advisable to permit cleaning and removal of any
airborne contaminants which may affect the dampers operation.
Note
For safety the damper blades should be closed on modes 9
and open on modes 10, before personally approaching them for
inspection/cleaning.
Since the drive, linkage, motors and electronic components on
the ductgard units are ‘sealed for life’ there should be
no requirement for periodic maintenance and spares are not
normally required. Items such as reset levers and test keys however
can be misplaced over time. In this event replacements are readily
available from Head Office.
All Ductgard units are both inspected and tested before
leaving our premises. Manufactured using maintenance free
‘sealed for life’ components there is no reason why they
should not reach site in full working order and continue to
function when installed providing that our fitting and wiring
instructions have been adhered to.
In the event of operational difficulties please contact our Head
Office for on-line guidance and advice.
Telephone: (01253) 766911
Ductgard units carry a full 1 year warranty from the date of
delivery for all parts and labour.
Series 60
Smoke Evacuation DamperFiregard
Curtain Fire Dampers
Airgard
Volume Control Dampers
-
14
DUCTGARDDuct Mounting Fire and Smoke Dampers
Declaration of Performance: Ductgard Range
1. Unique identification code of the product-type:
DUCTGARD fire damper (see table below for specific damper
installation type) To be used in conjunction with
walls/partitions/floors to maintain fire compartments in heating,
ventilating and air conditioning Installations
2. Name, registered trade name or registered trade mark and
contact address of the manufacturer as required under Article
11(5):
Gilberts (Blackpool) Ltd, Clifton Road, Blackpool, FY4 4QT
3. System or systems of assessment and verification of constancy
of performance of the construction product as set out in CPR, Annex
V:
System 1
4. In case of the declaration of performance concerning a
construction product covered by a harmonized standard:
BRE Global Ltd (notified body 2831) performed the determination
of the product type on the basis of type testing (including
sampling), type calculation, tabulated values or descriptive
documentation of the product, the initial inspection of the
manufacturing plant and of factory production control and
continuous surveillance, assessment and evaluation of factory
production control under system 1 and issued the certificate of
constancy of performance of the factory production control (no.
CPR-P0007-certificate number-CPR-P0010).
5. Declared performance according to:
EN 15650 (Ventilation for Buildings — Fire Dampers)
Fire resistance according to EN 1366-2 and Classification
according to EN 13501.3 and Harmonised Technical specification to
EN 15650:2010:
Range Type Supporting Construction Document Ref
Classification
100x100mm - 1000x1000mm DUC/IF Concrete Floor P100960 - 1006B/4
E120 (ho i 70) S
100x100mm - 1000x1000mm DUC/IF Blockwork Wall 287719F/2 E120 (ve
i o) S
100x100mm - 1000x1000mm DUC/SF Dry Wall & Blockwork
287719A/1 E120 (ve i o) S
100x100mm - 1000x1000mm DUC/DF Dry Wall 287719B/2 E120 (ve i o)
S
100x100mm - 1000x1000mm DUC/AF Dry Wall 287719C/2 E120 (ve i o)
S
100x100mm - 1000x1000mm DUC (No Frame) Dry Wall & Blockwork
287719E/2 E120 (ve i o) S
100x100mm - 1000x1000mm DUC/AF Blockwork 287719B/2 E120 (ve i o)
S
100x100mm - 1000x1000mm DUC/AF Concrete Floor 287719G/2 E120 (ho
i 70) S
Nominal activation conditions/sensitivity according to ISO
10294-4:
• sensing element load bearing capacity• sensing element
response temperature
Pass
Pass
Response delay (response time)
• closure time Pass
Operational reliability
• cycling 50 cycles
Durability of response delay according to EN 1366-2:
• sensing element response to temperature and load bearing
capacity Pass
Durability of operational reliability according to EN 15650:
• open and closing cycle 10.000 cycles Pass
-
OrderingSpecification
GILBERTSHead Office and WorksGILBERTS (BLACKPOOL) LTD
Gilair Works, Clifton Road,Blackpool, Lancashire FY4 4QT.
Telephone: (01253) 766911
Fax: (01253) 767941
e-mail: [email protected]
Web: www.gilbertsblackpool.com
Specification Fire and smoke dampers shall be LPCB certificated
and pass the test requirements stated in EN 1366-2 with an ES
classi-fication to EN 13501-3. Dampers to be fitted with an
actuator that can respond to a smoke alarm signal to ensure
closure
at the first sign of smoke.
Motors Dampers to be motor operated with a failsafe thermal
fuse
set to operate at 72°C. The damper will close (or open) in
less than 30 seconds.
Damper Blades & Linkage Dampers to have opposed blade
operation with interlocking double skinned blades on robust 19mm
spindles for both re-
sistance to fire and daily airflow exposure. The drive linkage
shall be fully enclosed and set outside of the air stream for
protection against damage and air contamination.
Casing Stainless steel gaskets shall be provided at the top,
bottom and sides to reduce casing leakage to below the levels
stated in EN 1366-2. Damper casings shall be fully welded to
meet
the air tightness test requirements of HVCA specification DW144
to classes A, B and C at up to 1500Pa.
Approvals The fire and smoke damper shall have a tested or
assessed installation method that matches the requirement of the
sup-porting construction into which it is built.
Gilberts (Blackpool) Ltd reserve the right to alter the
specification without notice. For our latest product data please
visit www.gilbertsblackpool.com. All images and drawings are for
illustrational purposes only and are not intended to deliver an
exact visual representation. Minor variations can be expected due
to the different manufacturing processes The information contained
in this brochure is correct at time of going to press © 2019.
SERIES:
SIZE (mm width x Height or Dia)
FIXING OPTION
Installation Frame (HEVAC)....IF
Sleeve and Angle...SF
Drop Rod...DF
Angle Frame...AF
Frameless ... NF
TYPE:
Square/Rectangular:..............S
Circular...................................C
CONTROL OPTION
A or B
MODE
9 or 10
NUMBER REQUIRED
DUC 450 x 200 A 159 FC/NCS
DUCTGARDDuct Mounting Fire and Smoke Dampers