8/18/2019 Drainage System Project
1/17
Question 1
A)
Determine the total Loading Unit (L.U.) of the system
Given the design flow rate, demand time, frequency of use of each sanitary fitment, demandunit of each fitment can be found.
Usage ratio =
Since the demand of one basin is 1 Loading Unit (L.U.), one basin is our base appliance.
Proportion of base appliance ratio = ( .)
Proportion of base appliance flow rate = (.)
Demand figure = proportion of base appliance ratio x proportion of base appliance flow rate
Demand unit = round up number of the demand figure = loading unit of each fitment
Fitment QuantityDemand
unit
total Loading unit
(L.U.) of each type of
fitment(Quantity x Demand
unit
Basin 10 1 10
Sink 2 5 10
Shower 10 5 50
Clothwasher
2 5 10
Hence, the total Loading Unit (L.U.) of the system = 10 +10 +50+ 10 = 80
Given in the question Calculations
Fitment
Flow
rate(L/s)
Demand
time (s)
Frequency
Of use(s)
Usage
ratio
proportionof base
appliance
ratio
proportionof base
appliance
flow rate
Demand
figure
Demand
unit
Basin 0.12 30 1800 0.017 1.00 1.00 1 1
Sink 0.3 60 1800 0.033 2.00 2.50 5 5
Shower 0.18 300 6000 0.050 3.00 1.50 4.5 5
Cloth
washer 0.2 450 9000 0.050 3.00 1.67 5 5
8/18/2019 Drainage System Project
2/17
Determine the simultaneous demand in L/s of the system
Fitment n
P= Usage
ratio m
Probability of
occurrence Accumulating
Basin 10 0.017 0 P0= 0.845
1 P1= 0.143 0.9892 P2= 0.011 0.999
Sink 2 0.033 0 P0= 0.934
1 P1= 0.064 0.999
Shower 10 0.05 0 P0= 0.599
1 P1= 0.315 0.914
2 P2= 0.075 0.988
3 P3= 0.010 0.999
clothwasher 2 0.05 0 P0= 0.903
1 P1= 0.095 0.998
Based on probability theory, probability of having a sanitary fitment in use at a certain time
can be calculated.
= ( !! ( )!) (1 )− Where n = total number of fittings having the same probability
m= number of fitting in use at any one time
Pm = probability of occurrence
Consider the first case where a group of 10 basins, with a certain design demand time and
frequency of use, the probability factor of a particular number of draw off points occurring at
any one time, P indicated above the chart on the third column from the left, can be computed.
P =
Since the design intent is to serve 99% of all conditions, in the “accumulating” column as
long as shows nearly close to 0.99 meaning with this number of fitments or less in use at one
single time can serve 99% of all times.
For the basin case, 2 basins become the simultaneous demand.
For the sink case, 1 sink becomes the simultaneous demand.
For the shower case, 3 showers become the simultaneous demand.
For the cloth washer case, 1 cloth washer becomes the simultaneous demand.
8/18/2019 Drainage System Project
3/17
Hence, the simultaneous demand of the system, 0.24+0.3+0.54+0.2=1.28 L/s
B) Determine the pump rating and size of the pneumatic tank
The booster system at 20/F serves the toilets three floors above (21/F, 22/F and 23/F) and
three floors below (17/F, 18/F and 19/F). Assume vertical pipe loss=0.1mH/m run.
Technically, the cut- in pressure of the pump only occurs from the booster system at 20/F to
the water point at 23/F since that is the highest water point which has to be satisfied with the
minimum pump pressure need for the entire booster system. In addition, the cut-out pressure
of the pump only occurs at the 17/F since gravity will add up along the pipe going down.
Hence, we only need to consider two conditions: pump cut-in pressure from 20/F to 23/F and
pump cut-out pressure from 20/F to 17/F.
Consider three floors below (17/F, 18/F, and 19/F) and ignore the top three floors for a
moment.
Given maximum residual pressure 4.5bar = 45mH
Head gain from the booster system (20/F) to 17/F = 3.5mH x3=10.5mH
Pump cut-out pressure = 45m-10.5 + 0.1x3.5x3 = 35.55mH
Consider three floors above (21/F, 22/F and 23/F) and ignore the down three floors for a
moment.
Given minimum residual pressure 1.0 bar = 10mH
Head loss from the booster system (20/F) to 23/F = 3.5mH x3=10.5mH
Pump Cut-in pressure= 10mH+10.5+ 0.1x3.5mx3H= 21.55mH
To sum up, pump cut-in pressure is 21.55mH and pump cut-out pressure is 35.55mH in the
booster system which is acceptable since their pressure difference is within the range of 10 -
20 mH.
Fitment Flow rate (L/s) Simultaneous demand
Flow rate x
simultaneous demand(L/s)
Basin 0.12 2 0.24
Sink 0.3 1 0.3
Shower 0.18 3 0.54Cloth
washer0.2 1 0.2
8/18/2019 Drainage System Project
4/17
Each floor has a male, female and disabled toilet: 4 basins for male, 5 basins for female and
1 basin for disabled toilet. Therefore, each floor has 10 basins.
Since the booster system serves the basins in toilets three floors above and three floors below,
The simultaneous demand for 6 floors = 1 LU x 6 floors x 10 basins = 60 LU
Flow rate based on 60LU (See Pipe sizing Chart on the next page, graph 3)
For a 10 minute cut-out cycle, this ‘effective volume’ = 0.9 L/s x 10min x 60sec =540 L
P1 V1 = pressure and volume at initial conditions
(P1 =100kPa (abs) for normal atm. Condition)
P2V2 = pressure volume at ‘Pump Cut-in’
P3V3 = pressure volume at ‘Pump Cut-out’
V2 – V3 = effective capacity of tank = 540L = 0.54m3
P2 = 21.55mH (gauge) = 100 + 215.5 = 315.5kPa (abs) (lower limit)P3 = 35.55mH (gauge) = 100 +355.5 = 455.5kPa (abs) (upper limit)
According to Ideal gas law = 315500 ( +0.54) =455500 = 1.22 = 100000 =455500∗1.22 =5.54 The actual size of the pneumatic tank = 5.54m
3
Pump rating: Pump Cut-in pressure= 21.55mH; Pump Cut-out pressure = 35.55mH
8/18/2019 Drainage System Project
5/17
Pipe Sizing Chart
Source: Plumbing Engineering Services Design Guide (2002)
0.9 L/s
8/18/2019 Drainage System Project
6/17
Question 2
A) Determine whether the existing hot water system is sufficient for the present demand
and give recommendations if the analysis shows dissatisfaction of the system
Hour
Consumption
(L )
0:00 16801:00 1260
2:00 590
3:00 170
4:00 160
5:00 250
6:00 170
7:00 840
8:00 1680
9:00 2015
10:00 67011:00 250
Hour
Consumption
(L )
12:00 8013:00 85
14:00 505
15:00 1090
16:00 1085
17:00 2100
18:00 2770
19:00 3360
20:00 4200
21:00 4620
22:00 378023:00 2100
Table A: Peak hourly loads (above)
Table B: Peak hourly loads
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
0 : 0 0
1 : 0 0
2 : 0 0
3 : 0 0
4 : 0 0
5 : 0 0
6 : 0 0
7 : 0 0
8 : 0 0
9 : 0 0
1 0 : 0 0
1 1 : 0 0
1 2 : 0 0
1 3 : 0 0
1 4 : 0 0
1 5 : 0 0
1 6 : 0 0
1 7 : 0 0
1 8 : 0 0
1 9 : 0 0
2 0 : 0 0
2 1 : 0 0
2 2 : 0 0
2 3 : 0 0
C o n s u m p t i o n ( L )
Hour (hr)
Demand Profile of a Hot Water
8/18/2019 Drainage System Project
7/17
Peak
hours
litres
used
litres per
hour
1 4620 4620
2 8820 4410
3 12600 4200
4 15960 39905 18730 3746
6 20830 3472
7 22930 3276
8 24015 3002
9 25105 2789
10 25610 2561
11 25695 2336
12 25775 2148
13 26025 2002
Peak
hours
litres
used
litres per
hour
14 26695 1907
15 28710 1914
16 30390 1899
17 31230 183718 31400 1744
19 31650 1666
20 31810 1591
21 31980 1523
22 32570 1480
23 33830 1471
24 35510 1480
24hr average:
35510/24 = 1479.6 =1480 L/hrTable B: Peak hourly loads (above)
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
0 5000 10000 15000 20000 25000 30000 35000 40000
R e c o v e r y ( L / h r )
Storage-litres (L)
Storage make-up ratio curve peak hour 1peak hour 2
peak hour 3
peak hour 4
peak hour 5
peak hour 6
peak hour 7
peak hour 8
peak hour 9
peak hour 10
peak hour 11
peak hour 12
peak hour 13
peak hour 14
peak hour 15
peak hour 16
peak hour 17
peak hour 18
peak hour 19
peak hour 20
peak hour 21
peak hour 22
peak hour 23
peak hour 24
Min recovery rate =1480 L/hr
Recovery/storage curve
8/18/2019 Drainage System Project
8/17
Given that
-Existing hot water tank = 8000 L
-Existing hot water heater Q= 120kW
-Design cold and hot water temperature = Tw=10°C & Th= 65°C
-Heat capacity of water, cp= 4.2 kJ/kgK
Assume water density as 1kg/L = ∆120= 4.2 (6 5 1 0) = 0.52 /
= 0.52 1 / 3600 /ℎ
= 1872ℎ In the existing system, the 8000L hot water tank is at a recovery rate of 1872L/hr. However, in
the storage make-up ratio curve, under the condition of a 8000L hot water demand, the required
recovery rate is at least roughly 2300L/hr. Hence, the existing system is not sufficient for the
present hot water demand.
Recommendations:
If the hot water tank storage to 8000L is kept,
= ∆ = 80001ℎ 1ℎ3600 11 4.2 (6 5 1 0) =147.6 The power output of the heater requires to be larger so as to satisfy the required hot water
demand instead of the existing smaller power output of 120kW. Moreover, finding a heater with
a recovery rate of exactly 2300 L/hr on the existing market is not very possible although
2300L/hr recovery rate is the theoretical value based on the plot. Perhaps, we can pick a
2500L/hr recovery rate heater that should be available on the market for our need.
Or if the power output of the heater is kept to 120kW, with 1872L/hr recovery rate, based on the
storage make-up ratio, the hot water tank should require around 12000L
8/18/2019 Drainage System Project
9/17
B) Sizing the primary and secondary pipework
Consider a primary circuit of a hot water system,
Design flow rate = 2.0 L/s
Cold water = 20 °C (density 998 kg/ m3)
Hot water = 65° C (density 980 kg/m3)
The height difference between boiler and calorifier = 8m
Pressure difference of two columns of water=∆ℎ= (998 – 980) x 9.81x 8 = 1413 PaAssume the overall hydraulic length of the pipe = 24m (measured pipe length + length of fittings)
Allowable pressure drop = 1413Pa/ 24m = 59 Pa/m
From the pipe sizing chart for copper pipe, at design flow =2.0L/s,
Based on average 989kg/m3,
Head loss per meter run = 59 = 0.006 /,(see Pipe Sizing Chart on the next page) 76mm pipe suits the requirement.
Consider secondary pipework of a hot water system
The secondary return pipe has to be sized based on the minimum
flow rate to determine the possible heat loss from hot water pipe.
Given from the diagram that supply temperature of water=65°C
Return temperature of water = 55°C
Consider insulated supply pipe size =54mm OD (~21W/m run heat
loss), with the assumption of head loss = 0.1 mH/m at 3.5L/s (see
Pipe Sizing Chart on the next page)
Supply pipe length = 20m
Heat loss= 21W/m x 20m = 320W
Assume water density as 1kg/L
Temperature drop ∆ = 5°C (from 65°C - 60°C at the end of supply) = ∆ 21 20 = 4200 5°C =0.02/ This is the minimum flow rate in the secondary circuit to ensure the end of the supply still has
60°C
As for the secondary return, = ∆ ℎ 20 = 0.02 4200 (6055)°C ℎ = 21
8/18/2019 Drainage System Project
10/17
Since the secondary return has very similar conditions, including same temperature drop, same
mass flow rate, same pipe length, the size of secondary return should be 54mm OD same as the
secondary supply pipe.
Pipe Sizing Chart
Source: Plumbing Engineering Services Design Guide (2002)
For primary
circuit (orange)
For secondary
supply circuit
(red)
8/18/2019 Drainage System Project
11/17
Question 3
A) Wobbe index is equal to higher heating value (calorific value) in MJ/m3 divided by square
root of gas specific gravity. The Wobbe index is used to compare the combustion energy output
of different fuel gases, such as natural gas, liquefied petroleum gas (LPG), and town gas, in an
appliance, like a water heater. If two fuels have identical Wobbe indices, then for a given
pressure and valve setting, the energy output will also be the same. For example, under the same
pressure and valve setting condition, if gas A with a Wobbe index of 24 and gas B also with the
same Wobbe index of 24, although they both have different calorific values and specific gravity
values, both gases will give the same energy output. Hence, we can make use of any fuels that
have the identical Wobbe index and give out same combustion energy output to substitute one
another.
Town
gas LPG
calorific value (MJ/m3) 17.27 104.9
specific gravity 0.52 2.05
wobbe index= √ 24 73Consider 1 water heater and 1 table top cooker
Water heater rating = 102.2 MJ/hr
Table top cooker rating = 51.3 MJ/hr
Total = 102.2 +51.3 =153.5 MJ/hr =././ =8.89/ℎ
The Pole formula is used for determining the flow of gas in pipes.
=0.0071 ℎ Where Q = flow (m
3/hr),
d= diameter of pipe (mm),
h =pressure drop (mbar), assume 100 Pa = 1mbar,
l= length of pipe (m), in this case, measured length of pipe: 5+8+1 =14m, length of fitting around
4m
s =specific gravity of gas (town gas =0.52)
8.89=0.0071 1
0.5218 = 2 7 Gas supply pipes from the gas meter to the individual appliances = 32mm (available on the
market)
8/18/2019 Drainage System Project
12/17
B) Determine pressure drop of steam pipe work and then size the steam pipe
Given:
A boiler plant producing 180°C superheated steam at 600kPa (absolute) = 6 bar
Minimum pressure at the heater at 150 °C = 475kPa =4.75 bar (absolute) from steam table
Pressure drop of steam pipe work = 6bar -4.75 bar = 1.25bar (absolute)
Steam loading of the heater =300kg/hr
Overall equivalent length of the steam pipe = 40m
Consider the heat loss from pipework = 3.5% of heater load per 100m
Hence, revised steam load = 300kg/hr + 300 x(3.5% x 40/100)=304kg/hr
Steam pressure drop factor table
6bar =43.54 (blue circle)
4.75bar= (29.27+30.27)/2=29.77
= where F= pressure factor, P1 = factor based on theinlet pressure, P2 = factor based on the pressure at a
distance of L metres, L= equivalent length of pipe (m) = .−. = 0 . 3 4 From pipeline capacity table (see the next page),
F=0.3, capacity =487.3kg/hr> 304kg/hr
Size =32mm
Steam = 304kg/hr at 6 bar
Specific volume = 0.316m3/kg at 6 bar
Volume flow = 96.064 m3/hr = 96.064/3600= 0.027m
3/s
32mm pipe area = 0.0008m2
Thus pipe velocity = 0.027m3/s / 0.0008 = 33.75m/s
The pipe size is within the normal design velocity range ( 24-36m/s)
8/18/2019 Drainage System Project
13/17
8/18/2019 Drainage System Project
14/17
Question 4
A) Given:
60% water depth for the drain pipe at peak hours
A measured velocity, v0.6= 1.2 m/s
450mm drain pipe is laid to fall at 1:225
Proportional flow chart:
. = ℎ = 0.6 . =1.05
= 1.2 / 1.05 = 1.14/ , = 4 = 0.454 = 0.159 , =
= 1 . 1 4 0.159
=0.181/
=181/ . =0.65 .181 =0.65 ,. = 118 / Lets assume full potential as ¾ bore flow.
8/18/2019 Drainage System Project
15/17
. =0.9. = 0.181 0.9 . =0.1629/ . =162.9 /Amount of discharge to reach its full potential=162.9118=44.9L/s
Since design daily discharge per occupant =225 L per day, ½ of the discharge is recorded in a 6
hour period,
Originally, with the existing drain12 ( 225)6ℎ =118/12 ( 225)6ℎ 1ℎ3600 =118/ =22656
To reach its full potential (3/4 bore flow)12 ( 225)6ℎ =162.9/12 ( 225)6ℎ 1ℎ3600 =162.9/ =31277 Therefore, the drain can accommodate 31277 – 22656 = 8621 people on top of the original
population.
B)
= Where Q is rain water flow (L/s)C is the impermeability factor or run-off coefficient
A is drainage or catchment area (m2)
I is rainfall intensity (m/hr) = +0.5 Where Af is the catchment floor area (m
2),
Aw is the area of vertical wall (m2)
A is catchment area (m2)
= 1010
= 100 Determine: the time of concentration of the storm water for the roof = 0.14465 ( . .)
Where tc is time of concentration (min)
H is average fall (m per 100m) from the summit of catchment to the point of drainage
outlet
8/18/2019 Drainage System Project
16/17
L is the largest distance from catchment boundary to the point of drainage outlet (m)
A is the catchment area (m2)
= 0.14465 ( 1 0 + 5(1).(100).)
=1.37
Determine the extreme mean intensity of the rainfall, i , for a 10 year rainstorm return period
= 603( +4.4). Where td duration of rainfall in min. In this case td is equal to tc at a peak discharge of the
rainstorm system
= 603(1.37+4.4
). = 279 /ℎ Determine stormwater flow rate to be handled by the system, Q = 0.278/
Where Q is rain water flow (L/s)
C is the impermeability factor or run-off coefficient, in this case, assume 0.95 for roof
A is drainage or catchment area (m2)
I is rainfall intensity (m/hr)
= 0.951002791000 0.278
= 7 . 3 6
Determine the expected bore flow of the storm water pipe
Based on empirical formula of vertical stacks
= Where Q is rain water flow (L/s), k is a coefficient to determine which bore flow is expected, D
is the diameter of pipe (mm)
7.36=(100) = 3.4 10− So 1 / 4 bore full is expected of the storm water pipe.
8/18/2019 Drainage System Project
17/17