DOWDING & MILLS Condition Monitoring Of High Voltage Condition Monitoring Of High Voltage Machines Machines By The Analysis of By The Analysis of Electrical Partial Discharges Electrical Partial Discharges 22 April 04 22 April 04 Dino Kouadria Dino Kouadria PhD MSc BEng CEng MIEE MIEEE PhD MSc BEng CEng MIEE MIEEE
32

DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

Mar 28, 2015

Download

Documents

Molly MacDonald
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Condition Monitoring Of High Voltage Condition Monitoring Of High Voltage

MachinesMachines

By The Analysis ofBy The Analysis of

Electrical Partial DischargesElectrical Partial Discharges

22 April 0422 April 04

Dino KouadriaDino KouadriaPhD MSc BEng CEng MIEE MIEEEPhD MSc BEng CEng MIEE MIEEE

Page 2: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

CONTENTCONTENT

What is Partial Discharge (PD) Analysis.What is Partial Discharge (PD) Analysis.

Stator winding Common FaultsStator winding Common Faults..

Basics Of Why & How To Measure PD.Basics Of Why & How To Measure PD.

Case Studies.Case Studies.

Open Discussions.Open Discussions.

Page 3: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

It is an It is an electricalelectrical condition monitoring condition monitoring

technique.technique.

Used to assess the condition of hv Used to assess the condition of hv

insulationinsulation

Wider applications Wider applications

static static itemsitems i.E. Switchgear, cables i.E. Switchgear, cables

transformers, etc. transformers, etc.

Dynamic items i.E. Dynamic items i.E. Electrical machinesElectrical machines

What is Partial Discharges AnalysisWhat is Partial Discharges Analysis

Page 4: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Apply to HV motors & generators (>5kv)Apply to HV motors & generators (>5kv)

Online & off line tests.Online & off line tests.

Predominantly Predominantly on-line testson-line tests - - no shut no shut

downdown & & testtestss under under

normal stress normal stress condition.condition.

PDs Analysis On HV WindingsPDs Analysis On HV Windings

Page 5: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Assess the current & development in Assess the current & development in

condition of the condition of the

windingswindings

Maintenance Maintenance planning planning based on machines’ based on machines’

health.health.

Elimination of unwanted/unexpected Elimination of unwanted/unexpected

shutdowns.shutdowns.

Assistance in Assistance in targeting maintenance effort targeting maintenance effort

effectivelyeffectively..

LeaveLeave MaintainMaintain

ReplaceReplace

PDs Analysis On HV WindingsPDs Analysis On HV Windings

Page 6: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Why Do HV Stators Fail?

Failures due to windings’ insulation failureFailures due to windings’ insulation failure caused caused

by the combinedby the combined

electrical, thermal, environmental and electrical, thermal, environmental and mechanicalmechanical

stress factors.stress factors.

Most common causes in modern insulation are Most common causes in modern insulation are

mechanically induced defects i.E. mechanically induced defects i.E. Loose wedgesLoose wedges, ,

erosion due to erosion due to bar vibrationbar vibration etc. - etc. - Short time Short time

degradation process.degradation process.

Discharge between phases due to cracks / low Discharge between phases due to cracks / low

spacingspacing

Contamination of end windings.Contamination of end windings.

Others: internal voids, insulation ageing, Others: internal voids, insulation ageing,

delamination.delamination.

Electrical partial dischargesElectrical partial discharges

Page 7: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Regardless of the type of defects, they Regardless of the type of defects, they

all result in the generation of all result in the generation of

Electrical partial discharges.Electrical partial discharges.

So what are partial discharges?So what are partial discharges?

Page 8: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

What is a partial dischargeLocal breakdown that short circuits part of theLocal breakdown that short circuits part of the Insulation.Insulation.

Formation of corrosive ions, acids, nitrogen oxides, ozone.Formation of corrosive ions, acids, nitrogen oxides, ozone.

Detected using Detected using of chemical sensors for detection.of chemical sensors for detection.

Emission of light, sound & electromagnetic waves. Emission of light, sound & electromagnetic waves.

Detected using Detected using ultrasonic devices, antennae, cameras..ultrasonic devices, antennae, cameras..

Injection of high frequency current pulses.Injection of high frequency current pulses.

Detected using Detected using electrical partial discharges measurement electrical partial discharges measurement

(pd).(pd).

Vs = Vs = AApplied voltagepplied voltage

CavityCavityVVss

Page 9: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

-

+ +

Patterns & location of pulses within AC cyclePatterns & location of pulses within AC cycleIs the key in defects identificationIs the key in defects identification

Partial Discharges Basic Partial Discharges Basic Theory Theory

Page 10: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Importance Of Monitoring PDs Importance Of Monitoring PDs

Different defects produce different PD patterns.Different defects produce different PD patterns.

Complex PD patterns are produced when multiple defects Complex PD patterns are produced when multiple defects

are present.are present.

Failures are due to localized defects.Failures are due to localized defects.

PD pattern development over time represents developing PD pattern development over time represents developing

degradation processes.degradation processes.

Provide an early warning of potential problemsProvide an early warning of potential problems

Page 11: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Discharge Discharge levelslevels

TimeTime

3 – 6 months3 – 6 months ?? Years?? Years

CuringCuring Process Process Fabrication Defects

Contamination

Mechanical failure

Partial discharge monitoring over a machine Partial discharge monitoring over a machine life cyclelife cycle

Repair/action required

Page 12: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

PD DetectionPD Detection

Two main type of permanently installed sensors.Two main type of permanently installed sensors.

Capacitive couplers first developed in north Capacitive couplers first developed in north

america. Main users power industry.america. Main users power industry.

Rogowski coils first developed for the north sea Rogowski coils first developed for the north sea

oil industry. oil industry.

North sea oil industry – mainly Rogowski coilsNorth sea oil industry – mainly Rogowski coils

Ease of Ease of installation: installation: no disconnection of supply no disconnection of supply

cables, cables, lessless installation installation timetime..

Atex certifiedAtex certified

Page 13: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Rogowski Coils: Typical InstallationRogowski Coils: Typical Installation

Page 14: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Partial DischargePartial Discharge Analysis/Display Analysis/Display: Typical : Typical Cycle Cycle

Page 15: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Partial Discharge Partial Discharge Analysis/DisplayAnalysis/Display: Total : Total Discharge ActivityDischarge Activity

Page 16: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Partial Discharge Partial Discharge Analysis/DisplayAnalysis/Display: : Pulse Pulse Height AnalysisHeight Analysis

Page 17: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

CASE STUDIESCASE STUDIES

Page 18: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Case studiesCase studies

1 Contamination on old pump motor 1 Contamination on old pump motor 11KV-11KV-3MW3MW

2 New motor manufacturing problem 2 New motor manufacturing problem 13.8KV-12MW13.8KV-12MW

3 Coil Movement old motor 3 Coil Movement old motor 6.6KV-9MW6.6KV-9MW

4 Plastics plant old motor high PD 4 Plastics plant old motor high PD 11KV-2.5MW11KV-2.5MW

Page 19: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Total Discharge ActivityTotal Discharge Activity

3MW Pump Motor

Page 20: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

White power deposits clear White power deposits clear signs of discharge activitysigns of discharge activity

Typical Detected Faults Damage due to movement and contaminationTypical Detected Faults Damage due to movement and contamination3MW Pump Motor

Page 21: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

13.8 kV 12.7 MW Gas Compressor13.8 kV 12.7 MW Gas Compressor

Page 22: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

13.8 kV 12.7 MW Gas Compressor13.8 kV 12.7 MW Gas Compressor

0ver 70% of wedges loose or missing

Page 23: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Typical Detected Faults Damage due to wedge movementTypical Detected Faults Damage due to wedge movement

13.8 kV 12.7 MW Gas Compressor13.8 kV 12.7 MW Gas Compressor

Page 24: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Banded Discharge is Banded Discharge is

modulated which is due to modulated which is due to

coil movement .....coil movement .....

9MW Gas Compression Motor

Page 25: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

9MW Gas Compression Motor

Page 26: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Good Coil Good Coil

Air Duct ImpressionsAir Duct Impressions

9MW Gas Compression Motor

Page 27: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Damaged Coil

Lamination groves due to movement

Air Ducts (no abrasion)

9MW Gas Compression Motor

Page 28: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Heavily Damaged Coil Due to impacting on slot bottom

9MW Gas Compression Motor

Page 29: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

2420KW 11kV ASEA synchronous compressor motor

Page 30: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Detect any potential insulation problems.

The contribution of the different problems.

Location of problems within the winding.

Development in windings condition (through regular

monitoring)

Early detection allows scheduling of remedial work/repairs.

“Provide the maintenance engineer with the information to

make

The most cost effective decisions on planned maintenance”

Outcome of A PD Analysis SurveyOutcome of A PD Analysis Survey

Page 31: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Partial Discharge AnalysisPartial Discharge Analysis

Not an exact Science.Not an exact Science.

Does not predict when plant is likely to Does not predict when plant is likely to

fail.fail.

BUTBUT will highlight which machines are will highlight which machines are

most likely to fail.most likely to fail.

Does not detectDoes not detect Inter-turn FaultsInter-turn Faults

More room for improvement in defect More room for improvement in defect

recognition.recognition.

Future development in insulation/motor Future development in insulation/motor

designs.designs.

Page 32: DOWDING & MILLS Condition Monitoring Of High Voltage Machines By The Analysis of Electrical Partial Discharges 22 April 04 Dino Kouadria PhD MSc BEng CEng.

DOWDING & MILLS

Condition Monitoring Of High Voltage Condition Monitoring Of High Voltage

MachinesMachines

By The Analysis ofBy The Analysis of

Electrical Partial DischargesElectrical Partial Discharges

22 April 0422 April 04

Dino KouadriaDino KouadriaPhD MSc BEng CEng MIEE MIEEEPhD MSc BEng CEng MIEE MIEEE