Top Banner
Dorman Smith Electrical Distribution and Circuit Protection 2009 Energy Division
176

Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Aug 08, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Dorman Smith Electrical Distribution

and Circuit Protection 2009

Energy Division

Page 2: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

How to use this catalogue

This catalogue has been designed to enable users to access the information on thewhole product range in a straight-forward and logical manner. We are consciousthat the needs of our customers vary considerably and that, as our marketscontinue to grow, many will be dealing with our systems and products for the first time.

Where product codes are already well known, the Product and Parts Locator at theback of the catalogue will direct you to the pages relevant to each occurrence of aparticular item.

Each main product or system category has its own section. The sections arearranged such that those detailing the simpler and smaller systems are at thebeginning. Exploded views of typical system configurations are given as a guide,near to the front of each section.

In order to help you to ‘build’ a system, there are detailed Selection Charts at theend of each section. Again, these are formatted in a logical manner, from mainhousings to incomers, outgoing devices to their accessories. Once a reasonablelevel of familiarity with the Dorman Smith product range has been attained,complete circuit distribution systems can be readily configured directly from theSelection Charts alone.

Following the main products sections, the Technical Data and Applications sectionprovides a high level of detail on both specific products and the principles of circuitprotection in general.

We trust you will find this catalogue informative, helpful and a quick and easy-to-use tool whenever you need to configure MCB or MCCB distribution schemes.

Page 3: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

1

Electrical Distribution and CircuitProtection Product Catalogue

Contents

SP&N Distribution Systems (DA Type) 5-14

TP&N Distribution Systems (DB Type) 15-31TP&N Metering 33-36

Light Duty Panel Boards (250A & 400A) 37-44

Fuse Switch Panel Boards (800A) 45-56

Medium Duty Panel Boards (400A & 800A) 57-86

Fuse Combination Units 87-96

Dorman Smith Circuit Protection and Modular Devices and General Purpose Enclosures 97-116

Technical Data & Applications 117-164

Products & Parts Locator 165-173

How to use this catalogue

Contents 1

Tyco Electronics/Dorman Smith 3

123456

89

7

Page 4: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

2

Page 5: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Tyco Electronics

With a 50-plus year history of leadership, Tyco Electronics is a US$ 13billion global provider of engineered electronic components for thousandsof consumer and industrial products; network solutions and systems fortelecommunications and energy markets; undersea telecommunicationsystems; and wireless systems for critical communications

Energy Division – connecting the world of power

The Energy Division, a global operating unit within Tyco Electronics, is focused onproviding products and systems for the electrical power industry. Energy Divisionproducts are extensively used by power utilities, equipment manufacturers, railwaysand by a wide range of industries.

Each Business Unit within the Energy Division comes with a specialised product line and focused set of application skills for its specific market niche. Thus the Energy Division is able to bring innovative and technology driven products efficientlyto market by synchronising the product development and manufacturing facility capabilities.

The Energy Division has a significant position in multiple market segmentsproviding customers with a high level of engineering assistance and continuousafter-sales support.

The Energy Division is a leading global supplier of:

• Cable accessories

• Connectors and fittings

• Insulators and insulation

• Surge arresters

• Switching, protection and lighting

• Power measurement and control

Dorman Smith SwitchgearDorman Smith Switchgear has been a part of Tyco Electronics since 2000.With over 130 years of experience in switchgear design and production,Dorman Smith continues to strengthen its ability to bring high qualityelectrical distribution and circuit protection equipment to market.

Dorman Smith’s line-up of electrical equipment begins with simple SP&Ndistribution boards and extends to custom designed, factory built, low-voltageswitchboards for a broad range of commercial and industrial applications.

Dorman Smith, Crompton Instruments and Bowthorpe EMP products combinethrough shared technologies and close co-operation a complementary portfolio of low voltage power measurement and protection products for energyapplications worldwide.

The extensive array of electrical distribution systems suited to a broad scope of ,commercial and industrial applications, together with instruments for measurementof key electrical parameters and surge protectors for power and communicationlines ensures unrivalled capability to fulfil the most demanding specifications.

End user applications for the company’s products and systems are found in railtransportation, building management, utilities and infrastructure, together with the manufacturing sector and many parts of the process industry.

From its headquarters in Witham, Essex, the Dorman Smith product rangecontinues to build upon the foundations of well proven methods to further enhanceits reputation as a leading supplier in its field.

The Dorman Smith product range includes:

• MCB distribution board systems

• MCCB panel board systems

• Fuse combination switch units

• Modular control devices

• Digital metering panel instruments3

Page 6: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

The range of Modis LV distribution switchboard systems is designed and engineered by DormanSmith and this range of fully type tested assemblies comprehensively covers all low-voltageswitchboard requirements up to 3200 amps!

The Modis range of LV distribution switchboard systems is available as wall-mounted or floorstanding with front or rear access.

Assembled by our trained certified partners, the Modis range of LV distribution switchboards aremore than capable of satisfying individual customer needs, for the control and protection of thepower distribution system in commercial and industrial applications.

Dorman Smith Modis switchboards

4

To find out more, please contact our sales teamPhone 01772 325 380, Fax: 01772 325 385E-mail: [email protected], www.dormansmithswitchgear.com

TE logo, Tyco Electronics, Dorman Smith and Modis are trademarks.

Energy Division

Page 7: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

1Section

SP&N Distribution Systems

Loadlimiter 63 Range of SP&N DistributionSystems (DA Type)

Page 8: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

6

Key Features• Distribution board has 125A

rated busbars• Distribution boards can

be stacked• Choice of switch disconnector

or RCCB incomer• Boards have standard height

(250mm) and depth (116mm)

Available Options• Distribution boards provide from

6 to 22 outgoing ways• Incomer can be double-pole

switch disconnector up to 125Aor double-pole RCCB up to 100A

• Outgoing ways can beconfigured with 10kA-ratedMCBs or RCBOs

• Matching service centresequipped with 8 to 24 modular ways

Additional Features • Single module shunt trip, UVR

and auxiliary contacts easilyfitted to MCBs

• Neutral and earth terminal foreach single-pole way

• IP4X Ingress Protection

Compliance

Distribution Boards EN 60439-3

MCBs EN 60898

Contactors EN 61095

RCBOs EN 61009

RCCBs EN 61008

Overview

The Dorman Smith Loadlimiter 63 distribution systemincludes a versatile range of MCB distribution boardsand components for constructing comprehensive SP&Ncircuit management solutions. The system is designedfor applications demanding up to 125A incoming and63A outgoing capacity and the distribution boardexceeds the requirements of EN 60439-3.

The array of circuit devices includes an extensive rangeof MCBs, RCBOs, RCCBs and switch disconnectors. The system ensures simple configuration and quickinstallation as demanded by today’s new and retrofit,commercial and industrial applications. The standardfinish is epoxy powder coating in light grey RAL 7035.

Page 9: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

7

SP&N Distribution SystemConfiguration

Using DA distribution boards andDAS service centres in a stackedarrangement.

Page 10: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

8

1

3

2

4

SP&N Distribution Boards• Exceeds the requirements of EN 60439-1• 125A rated• Neutral and earth terminal for each single-pole way• 6-22 single-pole outgoing ways• IP4X Ingress Protection

6 270 3.8 DA06X

9 323 4.3 DA09X

12 377 4.8 DA12X

15 430 5.3 DA15X

18 484 6.0 DA18X

22 555 7.0 DA22X

Outgoing Width Weight Cat. no.1-pole ways (mm) (kg)

SP&N Service Centre• Accepts all DIN-rail mounting devices• 8-24 modular ways• IP4X Ingress Protection

8 270 3.8 DAS08X

11 323 4.3 DAS11X

14 377 4.8 DAS14X

17 430 5.3 DAS17X

20 484 6.0 DAS20X

24 555 7.0 DAS24X

Modular ways Width (mm) Weight (kg) Cat. no.

Accessories for SP&N Distribution Boards

Vertical stacking kitsDAS20X to B type board 1 DAXSKAStacking kit for 270mm width 1 DAXSK08Stacking kit for 323mm width 1 DAXSK11Stacking kit for 377mm width 1 DAXSK14Stacking kit for 430mm width 1 DAXSK17Stacking kit for 484mm width 1 DAXSK20Stacking kit for 555mm width 1 DAXSK24Earth bar kitsEarth bar 3 DAXEBEarth bar isolation kit 3 DBXLDoor lock kitsCylinder door lock 4 DBXCLPadlock bracket kit 4 DBXPLBlanking kits10 busbar terminal blanks 2 DAXTPMCB blanks 4xTP MCB + 12 busbar terminal blanks - DBXBP5x1P MCB + 5 busbar terminal blanks - DBXBM5x1⁄2 MCB blanks - DBXBH

Description Picture Cat. no.

Page 11: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

9

Direct connection 35 1 DAXD0

Direct connection 70 2 DAXD1

Incoming Options for SP&N Distribution Boards

Switch Disconnector• Exceeds the requirements of EN 60947-3• 50mm2 cable capacity• Duty category of AC22

Switch disconnector 63 2 50 AV263

Switch disconnector 100 2 50 AV2100

Switch disconnector 125 2 50 AV2125

Incoming Current Poles Max. cable Cat. no.device type rating (A) (mm2)

RCCB 63 30 AC LLM63/30/2

RCCB 63 100 AC LLM63/100/2

RCCB 63 300 AC LLM63/300/2

RCCB 80 30 AC LLM80/30/2

RCCB 100 30 AC LLM100/30/2

RCCB 100 100 AC LLM100/100/2

RCCB time delay 80 100 A LLMA-S80/100/2

RCCB time delay 100 100 A LLMA-S100/100/2

Incoming Current Sensitivity Device Cat. no.device type rating (A) (mA) type

Double-pole RCCB• Exceeds the requirements of EN 61008• Equipped with transient suppression filter• Voltage 230/400V 50/60 Hz• Double module for both type AC• Terminal capacity: top 25mm2

• Terminal capacity: bottom 35mm2

Direct Connection

Incoming device type Max. cable (mm2) Pic number Cat. no.

Single-phase transient voltage surge suppression A1SPM/40/230

Single-phase + NE transient voltage surge suppression A1SPM/40/230N

MOV replacement plug-in SPM SPM/40/230

MOV neutral/earth replacement plug-in SPM SPM/NE/40/230

Device type Cat. no.

Transient Voltage Surge Suppression• Plug-in surge protection modules• Integral protection status indicator• Thermal and current overload fusing• Operating range 200-300V rms max• ‘Hot working’ replaceable modules• Terminals 35mm2 max

See page 110 for more information

Note: It is recommended that SPM surge protectors are installed on the load side of a MCB - type C, MCCB or a fused disconnector 63A to provide isolationand protection.

1

2

Page 12: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

10

Single-pole MCBs• Exceeds the requirements of EN 60898• 10kA rated breaking capacity• Contact position indicator• 35mm2 cable capacity

6 K1PB06 K1PC06 K1PD06

10 K1PB10 K1PC10 K1PD10

13 K1PB13 K1PC13 X1PD13

16 K1PB16 K1PC16 K1PD16

20 K1PB20 K1PC20 K1PD20

25 K1PB25 K1PC25 K1PD25

32 K1PB32 K1PC32 K1PD32

40 K1PB40 K1PC40 K1PD40

50 K1PB50 K1PC50 K1PD50

63 K1PB63 K1PC63 K1PD63

Current rating (A) B type cat. no. C type cat. no. D type cat. no.

6 30 GR1PB0630 GR1PC0630

10 30 GR1PB1030 GR1PC1030

16 30 GR1PB1630 GR1PC1630

20 30 GR1PB2030 GR1PC2030

32 30 GR1PB3230 GR1PC3230

40 30 GR1PB4030 GR1PC4030

50 30 GR1PB5030 GR1PC5030

6 100 - GR1PC06100

10 100 - GR1PC10100

16 100 - GR1PC16100

20 100 - GR1PC20100

32 100 - GR1PC32100

40 100 - GR1PC40100

Current rating (A) Sensitivity (mA) B type cat. no. C type cat. no.

RCBOs• Exceeds the requirements of EN 61009• Single module: type AC• 10kA rated breaking capacity• Terminal capacity: top terminals 10mm2

• Terminal capacity: bottom terminals 25mm2

Page 13: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

11

Accessories for MCBs and RCBOs

MCB auxiliary contact (one changeover contact) XAC2

MCB signal/auxiliary contact (one changeover contact) XCS2

MCB shunt trip (110-400V ac, 110-125V dc) XST415

MCB shunt trip (12-48V ac/dc) XST48

MCB under-voltage release (230V ac) time delay adjustable 0-300mS XUVR240

Auxiliary equipment

Description Cat. no.

MCB dolly locking device XDL

Padlock for dolly locking device XPL

Padlocking

MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) DBXBP

MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) DBXBM

MCB blanks (5x1⁄2 MCB ways) DBXBH

Blanking pieces

Kilowatt Hour Meter• Class 2 accuracy• For nominal 230V systems• Opto-isolated pulse output• Counter resolution to 1 kWh• LED display of power supply, activity status and negative condition

Measuring Current Transformers• For use with above kilowatt hour meter• System voltage up to 720V• Secondary output of 5A• Operating temperature range of –20°C to +70°C

Device type Counter Pulse Width Cat. no.digits (ms) (mm)

Quad module kWh 7 mechanical <100 70 DRK-1PCT-240

Description Cable aperture Height Width Cat. no.(mm) (mm) (mm)

100A current transformer 25 80 55 M53J-100/5D

125A current transformer 25 80 50 M53J-125/5D

Page 14: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

12

Selection Chart - DA Type

Distribution BoardsBusbar rating Outgoing ways Width (mm) Weight (kg) Cat. no.

Single module TVSS A1SPM/40/230Single module TVSS +NE A1SPM/40/230NSPM plug-in unit SPM/40/230SPM NE plug-in unit SPM/NE/40/230

Service CentresFor DIN-rail modules Modular ways

DAS20X to B type board DAXSKAStacking kit for 270mm width DAXSK08Stacking kit for 323mm width DAXSK11Stacking kit for 377mm width DAXSK14Stacking kit for 430mm width DAXSK17Stacking kit for 484mm width DAXSK20Stacking kit for 555mm width DAXSK24Blanking kitsBusbar terminal blanks (set of 10) DAXTPEarth bar kitsEarth bar DAXEBEarth bar isolation kit DBXLDoor lock kitsCylinder door lock DBXCLPadlock bracket kit DBXPL

Accessories for DA Type Distribution BoardsVertical stacking kits

Switch disconnector 63 - 50 AV263Switch disconnector 100 - 50 AV2100Switch disconnector 125 - 50 AV2125RCCB, type AC 63 30 35 LLM63/30/2RCCB, type AC 63 100 35 LLM63/100/2RCCB, type AC 63 300 35 LLM63/300/2RCCB, type AC 80 30 35 LLM80/30/2RCCB, type AC 100 30 35 LLM100/30/2RCCB, type AC 100 100 35 LLM100/100/2RCCB type A time delay 80 100 35 LLMA-S80/100/2RCCB type A time delay 100 100 35 LLMA-S100/100/2Direct connection - - 35 DAXD0Direct connection - - 70 DAXD1

Incoming DevicesDevice type Current rating (A) Sensitivity (mA) Max. cable (mm2)

Incoming Auxiliaries

125A 6 270 3.8 DA06X125A 9 323 4.3 DA09X125A 12 377 4.8 DA12X125A 15 430 5.3 DA15X125A 18 484 6.0 DA18X125A 22 555 7.0 DA22X

Service centre 8 270 3.8 DAS08XService centre 11 323 4.3 DAS11XService centre 14 377 4.8 DAS14XService centre 17 430 5.3 DAS17XService centre 20 484 6.0 DAS20XService centre 24 555 7.0 DAS24X

Page 15: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

13

Selection Chart - DA Type Circuit Devices

Single module 6 K1PB06 K1PC06 K1PD06

Single module 10 K1PB10 K1PC10 K1PD10

Single module 13 K1PB13 K1PC13 X1PD13

Single module 16 K1PB16 K1PC16 K1PD16

Single module 20 K1PB20 K1PC20 K1PD20

Single module 25 K1PB25 K1PC25 K1PD25

Single module 32 K1PB32 K1PC32 K1PD32

Single module 40 K1PB40 K1PC40 K1PD40

Single module 50 K1PB50 K1PC50 K1PD50

Single module 63 K1PB63 K1PC63 K1PD63

SP&N MCBs – B, C & D types10kA breaking capacity Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Single module, type A 6 30 GR1PB0630 GR1PC1030

Single module, type A 10 30 GR1PB1030 GR1PC1630

Single module, type A 16 30 GR1PB1630 GR1PC2030

Single module, type A 20 30 GR1PB2030 GR1PC3230

Single module, type A 32 30 GR1PB3230 GR1PC4030

Single module, type A 40 30 GR1PB4030 GR1PC06100

Single module, type A 40 30 GR1PB4030 GR1PC06100

Single module, type A 50 30 GR1PB5030 GR1PC5030

Single module, type A 6 100 - GR1PC10100

Single module, type A 10 100 - GR1PC16100

Single module, type A 16 100 - GR1PC20100

Single module, type A 20 100 - GR1PC32100

Single module, type A 32 100 - GR1PC40100

Single module, type A 40 100 - GR1PC40100

SP&N RCBOs – B & C types10kA breaking capacity Sensitivity B type C typeDevice type (mA) cat. no. cat. no.

Accessories for MCBs and RCBOsDescription Cat. no.

Single Phase kWh meter DRK-1PCT-240

Current transformer, 100A M53J-100/5D

Current transformer, 125A M53J-125/5D

MeteringDescription Cat. no.

Auxiliary equipmentMCB auxiliary contact (one changeover contact) XAC2

MCB signal/auxiliary contact (one changeover contact) XCS2

MCB shunt trip (110-400V ac, 110-125V dc) XST415

MCB shunt trip (12-48V ac/dc) XST48

MCB under-voltage release (230V ac) time delay adjustable 0-300mS XUVR240

PadlockingMCB dolly locking device XDL

Padlock for dolly locking device XPL

Blanking piecesMCB blanks (4xTP MCB ways + 12 busbar terminal blanks) DBXBP

MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) DBXBM

MCB blanks (5x1⁄2 MCB ways) DBXBH

Page 16: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

14

Outline Drawing and Dimensions

6 270 3.8 DA06X

9 323 4.3 DA09X

12 377 4.8 DA12X

15 430 5.3 DA15X

18 484 6.0 DA18X

22 555 7.0 DA22X

1-pole ways Width (mm) Weight (kg) Cat. no.

DA Type Distribution Boards

8 270 3.8 DAS08X

11 323 4.3 DAS11X

14 377 4.8 DAS14X

17 430 5.3 DAS17X

20 484 6.0 DAS20X

24 555 7.0 DAS24X

Modular ways Width (mm) Weight (kg) Cat. no.

DA Type Service Centres

All dimensions in mm

Page 17: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

2Section

TP&N Distribution Systems

Loadlimiter 63 Range of TP&N DistributionSystems (DB Type)

Page 18: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

16

Key Features• Conforms to EN 60439-3• ASTA certified busbars rated at

10kA for 250ms• Neutral and earth terminal

25mm2 for each single-pole way• Clean earth facility• Enclosures are 484mm wide x

159 deep• 4 to 24 TP&N outgoing ways• IP4X Ingress Protection• Double earth kits available• Extended service centres with

fitted earth and neutral terminals

Available Options• Incomer can be switch

disconnector, contactor, fuseswitch, MCCB or RCCB

• Outgoing ways can beconfigured with 10kA-ratedMCBs or RCBOs

• Matching service centresequipped with one or two rowsof 18-pole ways

• Surge protection modules canbe accommodated withinstandard configuration

• Modular kWh meter fits withinstandard configuration

Benefits • Extra spreading room for single

module RCBOs• Multi incoming options• Earth/neutral close to phase

terminal• MCBs with symmetrical dual

terminals• Integral metering options• Exceptional flexibility

Applications• Commercial and industrial final

circuit protection• Part L2 Building Regulations• 17th Edition Wiring Regulations

Standards• EN60898 MCBs• EN61095 Contactors• EN61009 RCBOs• EN61008 RCCBs• EN60439-3 Distribution Boards

Overview

The Dorman Smith Loadlimiter 63 distribution boardsystem promotes build simplicity and versatility of finalcircuit management solutions up to 250A with itscomprehensive range of MCB distribution boardsand components for commercial and industrial TP&Napplications. The distribution board exceeds therequirements of EN 60439-3.

The array of circuit devices includes an extensive rangeof MCBs, RCBOs, MCCBs, RCCBs, contactors and fuse switch incomers. The system ensures simpleconfiguration and quick assembly for new and retrofitinstallations. The standard finish is epoxy powdercoating in light grey RAL 7035.

Page 19: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

17

TP&N System Configuration

The Loadlimiter 63 DB-type systemcan be arranged for either YA3 frameMCCB incomer or modular switchdisconnector incomer, as shown.

Page 20: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

18

TP&N Distribution Boards• Exceeds the requirements of EN 60439-3• ASTA certified busbars rated at 10kA for 250mS• Neutral and earth terminal 25mm2 for each single-pole way• Clean earth facility • Enclosure are 484mm wide x 159mm deep• 4-24 TP&N outgoing ways• IP4X Ingress Protection

4 544 10 DBX04R

6 598 11 DBX06R

8 651 12 DBX08R

12 758 15 DBX12R

16 865 18 DBX16R

20 1025 22 DBX20R

24 1132 27 DBX24R

Outgoing Height Weight Cat. no.3-pole ways (mm) (kg)

YA3 Frame MCCB Housing• Enclosure to mount any YA3 Frame MCCB up to 250A• Facility to mount two panel mounted meters (using available knockouts)

3-pole unit 321 8 DBXYA3

4-pole unit 321 8 DBXYA3

Incomer Height (mm) Weight (kg) Cat. no.

Service Centres for all TP&N Distribution Boards• Accepts all DIN-rail mounting devices• 18 or 36 modular ways• IP4X Ingress Protection• General purpose enclosure includes facility to mount two panel mounted meters

and DIN-rail for current transformers• Neutral and earth bars fitted as standard

Double earth bar kits are available Order as DBTE**X, where ** = 04 to 24.

Note: Devices to be ordered separately.Triple-pole device requires neutral link YA3NL to be ordered separately.

18 x 1-pole ways(single row) 213 5 DBS18X

36 x 1-pole ways(double row) 427 8 DBS36X

General purpose enclosure 213 3 DBMSB

Modular ways Height (mm) Weight (kg) Cat. no.

Supplied without top or bottom plate. Intended for use with removable plate fromdistribution board.

Page 21: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

19

Conversion kits plus spares

TP&N to SP&N conversion kit 1 DBXTS

Spare end plate 2 DBXEP

Fixing kit for 24 way distribution boards DBX24FK

Blank way label for 24 way distribution boards DBX24WL

Blanking piecesMCB blanks (4xTP MCB ways + 12 busbar terminal blanks) DBXBP

MCB blanks (5x1P MCB ways + 5 busbar terminal blanks) DBXBM

MCB blanks (5x1⁄2 MCB Ways) DBXBH

Joining kit

Kit for vertically joining two distribution boards 3 DBXJK

Terminal bars

Terminal bar for 6 ways 6 DBXT06

Terminal bar for 12 ways 6 DBXT12

Terminal bar for 18 ways 6 DBXT18

Terminal bar for 24 ways 6 DBXT24

Blanking kits

Busbar terminal blanks (set of 10) 4 DAXTP

Earth bar kits

Earth bar 7 DAXEB

Earth bar isolation kit 5 DBXL

Double earth bar facility

Earth bar kit with terminal for each outgoing way (where ** = 04, 06, 08, 12, 16, 20 or 24 ways) DBTE**X

Door lock kits

Cylinder door lock DBXCL

Padlock bracket kit DBXPL

Description Picture Cat. no.

Accessories for all TP&N Distribution Boards

Direct Connection Terminal Kits

1 2

3

4

5 6

7

Terminals 35 DBXD0Terminals 70 DBXD1Terminals 150 DBXD2

Description Max. cable (mm2) Cat. no.

Page 22: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Terminals 35 DBXD0Terminals 70 DBXD1Terminals 150 DBXD2

Direct connection

20

Incoming Devices and Connection Kits

Switch disconnectorDevice type Max. cable Sensitivity Incoming Connection

(mm2) (mA) device kitcat. no. cat. no.

100A, 3-pole 50 - AV3100 N/A100A, 4-pole 50 - AV4100 DBXCK125A, 3-pole 50 - AV3125 N/A125A, 4-pole 50 - AV4125 DBXCK250A, 3-pole 150* - YA3B3P250D DBXYA3250A, 4-pole 150* - YA3B4P250D DBXYA3

4-pole RCCB

63A, type AC 35 30 LLM63/30/4 DBXCK63A, type AC 35 100 LLM63/100/4 DBXCK63A, type AC 35 300 LLM63/300/4 DBXCK100A, type AC 35 30 LLM100/30/4 DBXCK100A, type AC 35 100 LLM100/100/4 DBXCK100A, type AC 35 300 LLM100/300/4 DBXCK

Contactor

40A, 4-pole - - LLM4P40CO DBXCK63A, 4-pole - - LLM4P63CO DBXCK

Fuse switch

100A, 3-pole 70 - HBF3P100N DBXLSA1200A, 3-pole 150 - HBF3P200N DBXLSA2

Device type Max. cable Sensitivity Incoming Connection(mm2) (mA) device kit

cat. no. cat. no.

63A, 3-pole 150* - YA3N3P63T DBXYA363A, 4-pole 150* - YA3N4P63T DBXYA3100A, 3-pole 150* - YA3N3P100T DBXYA3100A, 4-pole 150* - YA3N4P100T DBXYA3125A, 3-pole 150* - YA3N3P125T DBXYA3125A, 4-pole 150* - YA3N4P125T DBXYA3160A, 3-pole 150* - YA3N3P160T DBXYA3160A, 4-pole 150* - YA3N4P160T DBXYA3200A, 3-pole 150* - YA3N3P200T DBXYA3200A, 4-pole 150* - YA3N4P200T DBXYA3250A, 3-pole 150* - YA3N3P250T DBXYA3250A, 4-pole 150* - YA3N4P250T DBXYA3

YA3 frame MCCB - 25kA

*Max. cable termination = 150mm2 (using M8 reduced palm width lugs)

Description Cat. no

YA3 neutral link YA3NL

Page 23: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

21

Transient Voltage Surge Suppression (TVSS)

Outgoing Devices

3-phase TVSS module 54 A3SPM/40/230

3-phase with neutral/earth TVSS module 54 A3SPM/40/230N

MOV replacement plug-in SPM 17.5 SPM/40/230

MOV neutral/earth replacement plug-in SPM 17.5 SPM/NE/40/230

Device type Width (mm) Cat. no.

• Plug-in surge protection modules• Integral protection status indicator• Thermal and current overload fusing• Three-phase operating range, 380-515V rms max• ‘Hot working’ replaceable modules

Note: Connection kit DBXCK must be ordered to provide the additional DIN-railneeded to mount this device in the distribution enclosure below the incomingdisconnector.

6 K1PB06 K1PC06 K1PD06

10 K1PB10 K1PC10 K1PD10

13 K1PB13 K1PC13 N/A

16 K1PB16 K1PC16 K1PD16

20 K1PB20 K1PC20 K1PD20

25 K1PB25 K1PC25 K1PD25

32 K1PB32 K1PC32 K1PD32

40 K1PB40 K1PC40 K1PD40

50 K1PB50 K1PC50 K1PD50

63 K1PB63 K1PC63 K1PD63

Current B type C type D typerating (A) cat. no. cat. no. cat no.

Single-pole MCBs• Exceeds the requirements of EN 60898• 10kA rated breaking capacity• Contact position indicator• 35mm2 cable capacity

6 K3PB06 K3PC06 K3PD06

10 K3PB10 K3PC10 K3PD10

13 K3PB13 N/A N/A

16 K3PB16 K3PC16 K3PD16

20 K3PB20 K3PC20 K3PD20

25 K3PB25 K3PC25 K3PD25

32 K3PB32 K3PC32 K3PD32

40 K3PB40 K3PC40 K3PD40

50 K3PB50 K3PC50 K3PD50

63 K3PB63 K3PC63 K3PD63

Current B type C type D typerating (A) cat. no. cat. no. cat no.

Triple-pole MCBs

Page 24: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

22

6 30 GR1PB0630 GR1PC0630

10 30 GR1PB1030 GR1PC1030

16 30 GR1PB1630 GR1PC1630

20 30 GR1PB2030 GR1PC2030

32 30 GR1PB3230 GR1PC3230

40 30 GR1PB4030 GR1PC4030

50 30 GR1PB5030 GR1PC5030

6 100 - GR1PC06100

10 100 - GR1PC10100

16 100 - GR1PC16100

20 100 - GR1PC20100

32 100 - GR1PC32100

40 100 - GR1PC40100

Current Sensitivity B type C typerating (A) (mA) cat. no. cat no.

MCB auxiliary contact (one changeover contact) XAC2

MCB signal/auxiliary contact (one changeover contact) XCS2

MCB shunt trip (110-400V ac, 110-125V dc) XST415

MCB shunt trip (12-48V ac/dc) XST48

MCB under-voltage release XUVR240(230V ac, time delay adjustable 0-300mS)

RCBOs• Exceeds the requirements of EN 61009• Single module: Type AC• 10kA rated breaking capacity• Terminal capacity: outgoing terminals 10mm2

• Terminal capacity: busbar side terminals 25mm2

Accessories for MCBs and RCBOs

DescriptionAuxiliary equipment Cat. no.

MCB dolly locking device XDL

Padlock for dolly locking device XPL

Padlocking

MCB blanks (4xTP MCB ways + 12 busbar terminal blanks) DBXBP

MCB blanks (5x1⁄2 MCB ways) DBXBH

MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) DBXBM

Blanking pieces

Page 25: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

23

40 30 AC LLM40/30/2

40 100 AC LLM40/100/2

63 30 AC LLM63/30/2

63 100 AC LLM63/100/2

63 300 AC LLM63/300/2

80 30 AC LLM80/30/2

100 30 AC LLM100/30/2

100 100 AC LLM100/100/2

80, time delay 100 A LLMA-S80/100/2

100, time delay 100 A LLMA-S100/100/2

Current rating (A) Sensitivity (mA) Type Cat. no.

Double-pole RCCBs• Exceeds the requirements of EN 61008• Equipped with transient suppression filter• Voltage 230/400V 50/60Hz• Double width module, 35mm• Type AC • Terminal capacity: 40A-63A: 25mm2

• Terminal capacity: 100A: 35mm2

Switch16 1 N/O + neon LLM1P16NON

16 2 N/O + neon LLM2P16NON

32 1 N/O + neon LLM1P32NON

32 2 N/O + neon LLM2P32NON

16 1 C/O LLM1P16CO

16 2 C/O LLM2P16CO

32 1 C/O LLM1P32CO

32 2 C/O LLM2P32CO

Pushbutton16 1 N/O + neon LLMPBNON

16 1 N/O + 1 N/C LLMPBNONC

Indicator- Lens - red LLMLR*

- Lens - green LLMLG*

- Lens - amber LLMLA*

- Lens - clear LLMLC*

- 240V lamp LLMRL*

16 Lampholder LLMPL*

Current rating (A) Function Cat. no.

Auxiliary Devices – DIN-rail Mounted• 240V ac• 17.5mm module width• Terminal capacity 10mm2

*For complete indicator please order lens, lamp and lampholder separately.

Page 26: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

24

16A (AC7A) 1 or 2 channel 35 DRT-DW2R

Current rating (A) Function Width (mm) Cat. no.

20A 2N/O 17.5 LLM2P20CO

20A 2N/C 17.5 LLM2P20CC

24A 3N/O 35 LLM3P24CO

24A 2N/O+2N/C 35 LLM4P24COC

24A 4N/C 35 LLM4P24CC

24A 4N/O 35 LLM4P24CO

40A 2N/C 54 LLM2P40CC

40A 2N/O 54 LLM2P40CO

40A 3N/O 54 LLM3P40CO

40A 4N/O 54 LLM4P40CO

63A 2N/O 54 LLM2P63CO

63A 4N/O 54 LLM4P63CO

Venting kit * - 9 LLMV

Current rating (A) Contacts Width (mm) Cat. no.

Programmable Timers – DIN-rail Mounted• 250V ac 50/60Hz• Running reserve of 3 years • Switching capacity 150mA

When controlling highly inductive loads, a suitably rated contactor should beemployed with timers, programmers and relays.

* Ventilation module must be fitted between alternate pairs of contactors to prevent overheating.

Contactors – DIN-rail Mounted• Exceeds the requirements of EN 61095• May require de-rating when used with inductive loads – see Contactor De-rating

table in the Technical Applications section

Page 27: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Meters, Current Transformers andWiring Looms

Kilowatt Hour Meter - DIN-rail Mounted • Class 2 accuracy• For nominal 400V, 3 or 4 wire systems• Opto-isolated pulse output• Counter resolution to 1 kWh• LED display of power supply, activity status and negative condition

Quad module kWh 7 mechanical <100 70 DRK-3PCT-415

Quad module 7 digital >100 70 DRK-3PCT-415-LCDkWh

Device type Counter Pulse Width Cat. no.digits (mS) (mm)

Note: Connection kit DBXCK must be ordered to provide the additional DIN-rail neededto mount these devices integral to distribution board below the incoming disconnector.

Kilowatt Hour Meter - Panel Mounted - Analogue Display• Class 1.0 accuracy• Wide operating voltage 85-500V• True RMS measurement• Fully programmable CT ratios

3-phase meter with 1 pulse output 6 electro-mechanical KWH-400

Device type Counter digits Cat. no.

Integra 1630 Multi-function Meter - Panel Mounted• Low Profile• 0.2 accuracy• LED annuniciators for each measured• True RMS measurement• User programmable system configuration

3-phase meter with 1 pulse output INT-1630-M-5-M-100

3-Phase meter with 1 pulse output and 1 RS485 Modbus output INT-1630-M-5-M-110

Device type Cat. no.

Dintegra 1260 Multi-function Meter - DIN-rail mounted (6 Module)• 190V–260V ac 50/60Hz• Measures three-phase voltage, current, frequency, Watts, VAr, VA, energy kWh,

power factor, 5-line, 3-digit LED display• Opto-isolated pulse output

3-phase meter with 2 pulse output 106 DRI—1260-210& RS485 Modbus output

Device type Width (mm) Cat. no.

Tegra 710 Multi-function Meter - DIN-rail Mounted (4 module)• Monitors up to 57 parameters • True RMS, 3-phase voltage and current, Hz, CosØ, phase angle, active, reactive

and apparent power, KWh• Optional 2 programmable relay or RS485 Modbus outputs• Selectable VT and CT ratios

3-phase meter with 2 pulse output 70 TEGRA-710-200

Device type Width (mm) Cat. no.

25

Page 28: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

26

Measuring Current Transformers• For use with kilowatt hour meter• Up to Class 0.5 accuracy• System voltage up to 720V• Secondary output of 5A• Operating temperature range of –20°C to +70°C

100A current 25 80 50 M53J-100/5Dtransformer

125A currenttransformer 25 80 50 M53J-125/5D

200A current 25 80 50 M53J-200/5Dtransformer

250A currenttransformer 25 80 50 M53J-250/5D

General purpose enclosure - - - DBMSB

Description Cable Height Width Cat. no.aperture (mm) (mm) (mm)

Wiring Looms for TP&N Applications (refer to page 34 for application details)• 1A fuse (rated 400V) metering harness• Current transformer harness

Wiring loom DBX04R — DBX16R Any Crompton DBXW16for single meter Instruments meter

Wiring loom DBX20R – DBX24R Any Crompton DBXW24for single meter Instruments meter

Wiring loom for DBX04R — DBX16R Any Crompton DBXW16Tsingle meter for Instruments metertop distributionboard (vertical stacking)

Description For use with Suitable meter Cat. no.distribution boards

Power Loom for Sub-Metered Distribution Boards (refer to page 34 for application details)• 125A and 250A power loom for joining two distribution boards

Power loom for sub metered 125A max DBXWP125distribution board

Power loom for sub metered 250A max DBXWP250distribution board

Description Current rating Cat. no.

Note: Meters, current transformers and enclosure to be ordered separately.

Kilowatt Hour Meters for Outgoing Circuits• In-built current transformers, direct connection• Single-pole and triple-pole versions• DIN-rail mountable in Loadlimiter service centres• Phase cable hole diameter 12.5mm

63 Direct mounted 54 DRK-1P-230-D63

100 Direct connected 126 DRK-3P-400-D100

Max. current Description Width Cat. no.rating (A) (mm)

Page 29: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

27

TP&N Digital MeteringFor use with panel mounted meters Cable Height Weight Cat. no.

aperture (mm) (mm) (kg)

18 x 1-pole ways (single row) 213 5 DBS18X36 x 1-pole ways (double row) 427 8 DBS36XCable spreader box 213 3 DBMSB

TP&N Service CentresFor use with DIN-rail modules Height (mm) Weight (kg) Cat. no.

3-pole housing 321 8 DBXYA34-pole housing 321 8 DBXYA3

TP&N Incoming YA3 MCCB Enclosure(Physical data only, unit specified with selected incomer) Height (mm) Weight (kg) Cat. no.

Selection Chart - DB Type

250A 4 544 10 DBX04R250A 6 598 11 DBX06R250A 8 651 12 DBX08R250A 12 758 15 DBX12R250A 16 865 18 DBX16R250A 20 1025 22 DBX20R250A 24 1132 27 DBX24R

TP&N Distribution Boards (without incoming device)Busbar rating TP outgoing ways Height (mm) Weight (kg) Cat. no.

Accessories for all TP&N Distribution Boards

Description Cat. no.

Conversion kits plus sparesTP&N to SP&N conversion kit DBXTSSpare end plate DBXEPFixing kit for 24 way distribution boards DBX24FKBlank way label for 24 way distribution boards DBX24WLBlanking piecesMCB blanks (4xTP MCB ways + 12 busbar terminal blanks) DBXBPMCB blanks (5xSP MCB ways + 5 busbar terminal blanks) DBXBMMCB blanks (5x1⁄2 MCB Ways) DBXBHJoining kitMechanical joining kit (For joining two distribution boards vertically) DBXJKTerminal barsTerminal bar for 6 ways DBXT06Terminal bar for 12 ways DBXT12Terminal bar for 18 ways DBXT18Terminal bar for 24 ways DBXT24Blanking kitsBusbar terminal blanks (set of 10) DAXTPEarth bar kitsEarth bar DAXEBEarth bar isolation kit DBXLDouble earth bar facility

Earth bar kit with terminal for each outgoing way (where ** = 04, 06, 08, 12, 16, 20 or 24 ways) DBTE**XDoor lock kitsCylinder door lock DBXCLPadlock bracket kit DBXPL

Enclosure (excluding meter) 213 5 DBMSBIntegra 1630 multi-function panel mounted meter with INT-1630-M-5-M-100pulse outputIntegra 1630 multi-function panel mounted meter with INT-1630-M-5-M-110one pulse & one Modbus outputPanel mounted kWh meter KWI-400

For use with 4 DIN-Module metersDIN-rail kWH mounting Kit (4 DIN-module meters only) DBXCK4 Module DIN-rail kWh meter (analogue display) DRK-3PCT-4154 Module DIN-rail kWh meter (LCD display) DRK-3PCT-415-LCD4 Module DIN-rail multi-function meter TEGRA-710-200

For use in DB service centres6 Module DIN-rail multi-function meter with two pulse DRI-1260-210Output & Modbus

For use with all meters100A Current transformer 25 M53J-100/5D125A Current transformer 25 M53J-125/5D200A Current transformer 25 M53J-200/5D250A Current transformer 25 M53J-250/5D

Page 30: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

28

Connection kit for surge suppression DBXCK3-phase TVSS module A3SPM/40/2303-phase with neutral/earth TVSS module A3SPM/40/230NMOV replacement plug-in SPM SPM/40/230MOV neutral/earth replacement plug-in SPM SPM/NE/40/230

Surge suppression Cat. no.

Selection Chart - DB Type Incomers

Terminals 35 DBXD0Terminals 70 DBXD1Terminals 150 DBXD2

Direct connection Max. cable (mm2) Cat. no.

Switch DisconnectorDevice type Max. cable Sensitivity Incoming device Connection kit

(mm2) (mA) cat. no. cat. no.

100A, 3-pole 50 - AV3100 N/A100A, 3-pole 50 - AV3100 N/A100A, 4-pole 50 - AV4100 DBXCK125A, 3-pole 50 - AV3125 N/A125A, 4-pole 50 - AV4125 DBXCK250A, 3-pole 150 - YA3B3P250D DBXYA3250A, 4-pole 150 - YA3B4P250D DBXYA3

4-pole RCCB63A, type AC 35 30 LLM63/30/4 DBXCK63A, type AC 35 100 LLM63/100/4 DBXCK63A, type AC 35 300 LLM63/300/4 DBXCK100A, type AC 35 30 LLM100/30/4 DBXCK100A, type AC 35 100 LLM100/100/4 DBXCK100A, type AC 35 300 LLM100/300/4 DBXCK

Contactor40A, 4-pole - - LLM4P40CO DBXCK63A, 4-pole - - LLM4P63CO DBXCK

Fuse switch100A, 3-pole 70 - HBF3P100N DBXLSA1200A, 3-pole 150 - HBF3P200N DBXLSA2

100A current transformer 25 80 <1 MS3J-100/5D125A current transformer 25 80 <1 MS3J-125/5D200A current transformer 25 80 <1 MS3J-200/5D250A current transformer 25 80 <1 MS3J-250/5D

Current TransformersDescription Cable Height Weight Cat. no.

aperture (mm) (mm) (kg)

Page 31: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

29

MCB auxiliary contact (one changeover contact) XAC2

MCB signal/auxiliary contact (one changeover contact) XCS2

MCB shunt trip (110-415V ac, 110-125V dc) XST415

MCB shunt trip (12-48V ac/dc) XST48

MCB under-voltage release (240V ac) time delay adjustable 0-300mS XUVR240

PadlockingMCB dolly locking device XDL

Padlock for dolly locking device XPL

Blanking piecesMCB blanks (4xTP MCB ways + 12 busbar terminal blanks) DBXBP

MCB blanks (5xSP MCB ways + 5 busbar terminal blanks) DBXBM

MCB blanks (5x1⁄2 MCB ways) DBXBH

Single module 6 30 GR1PB0630 GR1PC0630Single module 10 30 GR1PB1030 GR1PC1030Single module 16 30 GR1PB1630 GR1PC1630Single module 20 30 GR1PB2030 GR1PC2030Single module 32 30 GR1PB3230 GR1PC3230Single module 40 30 GR1PB4030 GR1PC4030Single module 50 30 GR1PB5030 GR1PC5030Single module 6 100 - GR1PC06100Single module 10 100 - GR1PC10100Single module 16 100 - GR1PC16100Single module 20 100 - GR1PC20100Single module 32 100 - GR1PC32100Single module 40 100 - GR1PC40100

RCBOs10kA breaking Current Sensitivity B type C typecapacity, AC type rating (A) (mA) cat. no. cat. no.

Selection Chart - DB Type Circuit Protective Devices

1-poleSingle module 6 K1PB06 K1PC06 K1PD06Single module 10 K1PB10 K1PC10 K1PD10Single module 13 K1PB13 K1PC13 N/ASingle module 16 K1PB16 K1PC16 K1PD16Single module 20 K1PB20 K1PC20 K1PD20Single module 25 K1PB25 K1PC25 K1PD25Single module 32 K1PB32 K1PC32 K1PD32Single module 40 K1PB40 K1PC40 K1PD40Single module 50 K1PB50 K1PC50 K1PD50Single module 63 K1PB63 K1PC63 K1PD63

3-poleTriple module 6 K3PB06 K3PC06 K3PD06Triple module 10 K3PB10 K3PC10 K3PD10Triple module 13 K3PB13 N/A N/ATriple module 16 K3PB16 K3PC16 K3PD16Triple module 20 K3PB20 K3PC20 K3PD20Triple module 25 K3PB25 K3PC25 K3PD25Triple module 32 K3PB32 K3PC32 K3PD32Triple module 40 K3PB40 K3PC40 K3PD40Triple module 50 K3PB50 K3PC50 K3PD50Triple module 63 K3PB63 K3PC63 K3PD63

TP&N – B, C & D types10kA breaking capacity Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Accessories for MCBs and RCBOsAuxiliary equipment Cat. no.

Page 32: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

30

Kilowatt hour meter 63 1 current transformer 54 DRK-1P-230-D63Kilowatt hour meter 100 3 current transformer 126 DRK-3P-400-D100

Kilowatt hour meter

Contactor 20A 2N/O 17.5 LLM2P20COContactor 20A 2N/C 17.5 LLM2P20CCContactor 24A 3N/O 35 LLM3P24COContactor 24A 2N/O+2N/C 35 LLM4P24COCContactor 24A 4N/C 35 LLM4P24CCContactor 24A 4N/O 35 LLM4P24COContactor 40A 2N/C 54 LLM2P40CCContactor 40A 2N/O 54 LLM2P40COContactor 40A 3N/O 54 LLM3P40COContactor 40A 4N/O 54 LLM4P40COContactor 63A 2N/C 54 LLM2P63CCContactor 63A 2N/O 54 LLM2P63COContactor 63A 4N/O 54 LLM4P63COVenting kit - - 9 LLMV

Contactor

Timer 16A (AC7A) 1 or 2 channel 35 DRT-DW2R

Programmable timer

Lampholder - - 17.5 LLMPLLamp - 240V - LLMRLLens - Amber - LLMLALens - Green - LLMLGLens - Red - LLMLRLens - Clear - LLMLC

Indicator

Pushbutton 16 1 N/O + neon 17.5 LLMPBNONPushbutton 16 1 N/O + 1 N/C 17.5 LLMPBNONC

Pushbutton

Switch 16 1 N/O + neon 17.5 LLM1P16NONSwitch 16 2 N/O + neon 17.5 LLM2P16NONSwitch 32 1 N/O + neon 17.5 LLM1P32NONSwitch 32 2 N/O + neon 17.5 LLM2P32NONSwitch 16 1 C/O 17.5 LLM1P16C0Switch 16 2 C/O 17.5 LLM2P16C0Switch 32 1 C/O 17.5 LLM1P32C0Switch 32 2 C/O 17.5 LLM2P32C0

Switch

Selection Chart - DB Type RCCBs and Modular Devices

Type AC 40 30mA 35 LLM40/30/2Type AC 40 100mA 35 LLM40/100/2Type AC 63 30mA 35 LLM63/30/2Type AC 63 100mA 35 LLM63/100/2Type AC 63 300mA 35 LLM63/300/2Type AC 80 30mA 35 LLM80/30/2Type AC 100 30mA 35 LLM100/30/2Type AC 100 100mA 35 LLM100/100/2Type A 80 100mA 35 LLMA-S80/100/2Type A 100 100mA 35 LLMA-S100/100/2

2-pole RCCBDescription Current rating (A) Function Width (mm) Cat. no.

Page 33: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

31

Outline Drawings and Dimensions

TP&N Distribution Boards (without incoming device)

4 1 544 10 DBX04R

6 1 598 11 DBX06R

8 1 651 12 DBX08R

12 1 758 15 DBX12R

16 1 865 18 DBX16R

20 1 1025 22 DBX20R

24 1 1132 27 DBX24R

3-pole ways Drawing Height Weight Cat. no.no. (mm) (kg)

YA3 Frame MCCB Enclosure for TP&N Distribution Boards

3-pole MCCB 2 321 8 DBXYA3

4-pole MCCB 2 321 8 DBXYA3

Income Drawing Height Weight Cat. no.no. (mm) (kg)

1

2

3

All dimensions in mm

18 x 1-pole ways(single row) 213 5 DBS18X

36 x 1-pole ways(double row) 427 8 DBS36X

General purpose enclosure 213 3 DBMSB

Modular ways Height (mm) Weight (kg) Cat. no.

Supplied without top or bottom plate. Intended for use with removable plate fromdistribution board.

Page 34: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

32

Page 35: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Configuration options• Single or sub metered power and

lighting boards• Horizontal or vertical sub metered

power & lighting boardarrangements

• The choice of number of outgoingways of both power and lightingboards

• Choice of meter type (multi-functionor kWh)

Benefits• Flexible — different metering

strategies can be employed• Overcomes dimensional constraints• System tailored to specification• Cost effective solutions

33

Loadlimiter 63 TP&N DistributionSystem Metering

OverviewThe NEW Loadlimiter 63 TP&N system focuses on the requirement to provide metering options at thedistribution board stage. Using standard components it is now possible to accomplish a large variety ofconfigurations of single or sub metered distributionboards up to 250A.

A metering distribution system can be tailored to meetindividual requirements, whether built by the contractoror fully assembled by an affiliated Dorman Smith partner(contact local sales engineer for more information).

New FunctionalityExtra functionality has been added to distributionboards and standard enclosures to accommodatecurrent transformers and panel mounted meters. Aselection of meter wiring looms are now available forquick and simple control wiring and power looms areavailable for sub-metered power and lighting boardapplications.

Page 36: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

34

Loadlimiter 63 Metering Selection Chart

Split Metered Power & Lighting Board Single Board

125A 250A

YA3B3P250DYA3B4P250DOr any YA3 MCCB

AV3125AV3100AV4125AV4100

125A Incomer 250A Incomer

AV3100AV3125AV4100AV4125

Integral

DBXW16OR

DBXW24

DBXW16T*

DBXW16ORDBXW24

Select Meter WiringLoom x1 for Bottom

Board

Select Meter WiringLoom x1 for Top Board

Select Meter Wiring Loom x2

Vertical Arrg’t Horizontal Arrg’t

DBMSBDBXJK

YA3B3P250DYA3B4P250DOr Any YA3 MCCB

Spreader Box

Select Dist Board x 2

DBX04RDBX06RDBX08RDBX12RDBX16RDBX20RDBX24R

Select Incomer

M53J-100/5D x6OR

M53J-125/5D x6

M53J-200/5D x6ORM53J-250/5D x6

DBXD0see table 1

DBXD0see table 1

DBXWP125 x1 DBXWP250 x1

DBMSB x1 DBXYA3 x1 DBXYA3

Select Meter x2

INT-1630-M-5-M-100 (Multi-function)

KWh - 400 (KWh)

Select Outgoing Devices

* Top board max size 16 way (vertical arrangement only)

Select Dist Board x 1

DBX04RDBX06RDBX08RDBX12RDBX16RDBX20RDBX24R

Select Incomer

Select Meter

** Meter DRK-3PCT-415 only

Select CT x3

M53J-100/5DM53J-125/5D

DBXW16ORDBXW24

Select Meter WiringLoom x1

Cable Connection Terminals

DBXD0see table 2

INT-1630-M-5-M-100 KWh - 400

DRK-3PCT-415

multiKWh

Select Outgoing Devices

Switch Disconnectors (125A max)

Meter Enclosure (125A)

Meter Enclosure(125A)

Din-rail Mounting Kit

Meter Enclosure (250A) Meter Enclosure (250A)

Power Loom (125A) Power Loom (250A)

Cable Connection Terminals Cable Connection Terminals

Current Transformers (125A) Current Transformers (250A)

Current Transformers

Vertical Joining Kit Meter Enclosure (DB 2)

Switch Disconnectors (250A max) Switch Disconnectors Switch Disconnectors

DBMSB DBXCK **

1 5 3 02 4 2 02 3 N/A 1

Quantity of AV DBXD0's DBXD0'S DBXCK (switch disconnectors) required (125A) required (250A) required

Main incomer 2 1 1mounted in DBMSB Main incomer mounted 0 0 -in standard position

DBXD0’s DBXD0 DBXWP125required 125A required 250A (125A rated only)

Table 1 Table 2

Page 37: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

35

100A — 3P switch disconnector 50 AV3100100A — 4p switch disconnector 50 AV4100125A — 3P switch disconnector 50 AV3125125A — 4p switch disconnector 50 AV4125250A—3P MCCB switch disconnector 150 YA3B3P250D250A—4P MCCB Switch Disconnector 150 YA3B4P250D160A — 3P MCCB 150 YA3N3P160T160A — 4P MCCB 150 YA3N4P160T200A—3P MCCB 150 YA3N3P200T200A—4P MCCB 150 YA3N4P200T250A—3P MCCB 150 YA3N3P250T250A— 4P MCCB 150 YA3N4P250T

Incoming DevicesDescription Device Type Max cable size Cat. no.

Spreader box with facility to mount 2 panel mounted meters 213 DBMSB250A incoming enclosure with facility to mount 2 panel mounted meters 321 DBXYA3Connection Kit for DIN rail meter - DBXCKMechanical joining kit for joining two distribution boards vertically - DBXJK

Metering Enclosures and Connection KitsDescription Height Cat. no.

Power loom for sub metered distribution board 125A Max DBXWP125Power loom for sub metered distribution board 250A Max DBXWP250

Power LoomsDescription Current rating Cat. no.

3 Phase Integra 1630 Multi-function meter with 1 pulse output INT-1630-M-5-M-1003 Phase Integra 1630 Multi-function meter with 1 pulse output & Modbus INT-1630-M-5-M-1103 Phase Kilowatt hour meter KWH-4003 Phase Kilowatt hour meter (DIN-rail mounted) DRK-3PCT-415

Metering OptionsDescription Cat. no.

Cable joining terminal kit DBXD0

Cable Joining Terminal KitDescription Cat. no.

100A Current Transformer with DIN clips M53J-100/5D125A Current Transformer with DIN clips M53J-125/5D200A Current Transformer with DIN clips M53J-200/5D250A Current Transformer with DIN clips M53J-250/5D

Current TransformersDescription Cat. no.

Wiring Loom for single meter DBX04R — DBX16R Any Crompton DBXW16Instrument Meter

Wiring Loom for single meter DBX20R — DBX24R Any Crompton instrument DBXW24meter

Wiring Loom for single meter for top DBX04R — DBX16R Any Crompton instrument DBXW16Tdistribution board when vertically meterstacking

Metering LoomsDescription For use with following Suitable Meter Cat. no.

distribution boards

TP&N Metering Selection Chart - TP&N DistributionBoards (Without Incoming Device)

250A 4 544 10 DBX04R250A 6 598 11 DBX06R250A 8 651 12 DBX08R250A 12 758 15 DBX12R250A 16 865 18 DBX16R250A 20 1025 22 DBX20R250A 24 1132 27 DBX24R

Busbar Rating Number of TP ways Height Weight Cat. no.

Page 38: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

36

Example 1 Requirement – Vertically stacked, 125A split metered powerand lighting distribution board• 8 way TP&N power board• 6 TP&N lighting board• Multi-function meters

DBX08R 1 8 way TP&N distribution board

DBX06R 1 6 way TP&N distribution board

AV3125 1 125A — 3P switch disconnector

DBMSB 1 Spreader box with facility to mount 2panel mounted meters

DBXJK 1 Mechanical joining kit for joining twovertically stacked distribution boards

DBXWP125 1 Power loom for split metered distributionboard (125A)

INT-1630-M-5-M-100 2 3-Phase Integra 1630 Multi-function meterwith 1 pulse output

DBXW16 1 Wiring loom for single meter

DBXW16T 1 Wiring loom for single meter for topdistribution board when vertically stacked

DBXD0 5 Cable joining terminal kit

M53J-125/5D 6 125A current transformer

Cat. no. Quantity Description

Flow Chart Examples

Example 1: Bill of Material List

Example 2: Bill of Material List

Example 2 Requirement – Single Metered Distribution Board (250A)• 24 way TP&N distribution board• kWh meter

DBX24R 1 24 way TP&N distribution board

YA3B3P250D 1 250A–3P MCCB switch disconnector

DBXYA3 1 250A incoming enclosure with facility tomount 2 panel mounted meters

KWH-400 1 3-Phase Kilowatt hour meter with 1 pulseoutput (panel mounted)

DBXW24 1 Wiring loom for single meter

DBXD0 1 Cable joining terminal kit

M53J-250/5D 3 250A current transformers

Cat. no. Quantity Description

Split metered 125A

Split metered 250A

Single metered 125A & 250A

Page 39: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

3Section

Light Duty Panel Boards

Loadbank 125 Range of Light Duty Panel Boards(250A and 400A Rating)

Page 40: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Key Features• ASTA certified busbars with a

short circuit rating of 25kA for 1 second

• Shunts, UVRs and auxiliaries are common for YA2, YA3 andYA5 MCCBs

• Single frame size outgoingMCCBs from 16A to 125A

• Generous cable-spreading space for incoming andoutgoing cables

• Common width (700mm) anddepth (190mm) for all enclosures

• A single part number identifiesthe complete main enclosure

Available Options• 250A panel boards with 6, 8 or

12 triple-pole outgoing ways canchoose incoming devices fromthe YA3 MCCB range or a direct connection

• 400A panel boards with 6, 8, 12or 16 triple-pole outgoing wayscan choose incoming devicesfrom the YA5 MCCB range or adirect connection

• Panel build options include:• Cable spreader box• Service centre with 24

single-pole ways• Integra metering housing• YA3 frame outgoing housing

Additional Features • Neutral and earth terminal for

each single-pole way• Clean earth facility• 250A panels use YA3 MCCBs for

incoming devices• 400A panels use YA5 MCCBs

for incoming devices• All versions use YA2 MCCBs for

outgoing devices• All triple-pole MCCBs have

adjustable overload andinstantaneous trips

CompliancePanel boards EN 60439-1MCCBs EN 60947-2

Overview

The Dorman Smith Loadbank 125 panel board systemprovides the user with a power distribution solutionsized between the Loadlimiter 63 MCB distribution boardsystems and the Loadbank 250 MCCB panel boards.

This range offers 250A and 400A rated panel boardswith outgoing YA2 MCCBs rated up to 125A. TheLoadbank 125 range of panel boards has been designedto provide the user with maximum flexibility while at thesame time offering a cost effective solution for MCCBcircuit distribution.

Loadbank 125 enclosure panel boards house both theincomer and outgoing units in a single enclosure and aresupplied with two doors, one over the incomer and oneover the outgoing MCCB units. The standard finish isepoxy powder coating in light grey RAL 7035. Anadditional enclosure is also available for mounting oneYA3 frame MCCB for circuits rated up to 250A.

38

Page 41: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

39

Loadbank 125 System Configuration

Illustrating the use of a YA5 frameMCCB incomer and YA2 frame singleand triple-pole MCCBs as outgoingways, together with system meteringand surge suppression.

Page 42: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

40

250A Panel Boards• ASTA certified busbars rated at 250A, 25kA for 1 second• Common internal accessories for MCCBs and switch disconnectors• Single part number for complete main enclosure• Enclosure are 700mm wide and 190mm deep• IP4X Ingress Protection• Suitable for direct connection (150mm2)

YA3 MCCB/switch disconnector 6 904 PB206YA

YA3 MCCB/switch disconnector 8 994 PB208YA

YA3 MCCB/switch disconnector 12 1174 PB212YA

Incoming device Outgoing Height Cat. no.ways (mm)

YA3 frame switch disconnector 250 3 YA3B3P250D

YA3 frame MCCB 125 3 YA3N3P125T

YA3 frame MCCB 160 3 YA3N3P160T

YA3 frame MCCB 200 3 YA3N3P200T

YA3 frame MCCB 250 3 YA3N3P250T

Device type Current Poles Cat. no.rating (A)

Multi-function Digital Metering Enclosure (250A and 400A)• Utilises Integra 1630 multi-function digital metering system• Fully programmable three-phase configuration• Measurement and display of up to 34 parameters including THD• Compact modular construction• Current transformer not included, see below• IP4X Ingress Protection

Enclosure (with digital panel meter) 270 11 PB1630

Description Height Weight Cat. no.(mm) (kg)

Measuring Current Transformers• For use with Integra 1630 digital metering• Up to Class 0.5 accuracy • 5A secondary output

Surge Suppression• See page 111 for suitable devices

125A currenttransformer 25 80 50 M53J-125/5D

250A currenttransformer 25 80 50 M53J-250/5D

Optional enclosure - 270 700 PBYA2CSB

Description Cable Height Width Cat. no.aperture (mm) (mm) (mm)

Incoming Devices for 250A Panel Boards• YA3 MCCB frame size switch disconnector• MCCB rating of 25kA Icu @ 415 Var• MCCBs have both adjustable overload and instantaneous trips• Rated insulation voltage 800V ac (Ui)• Four-pole incoming kit available in accessories• Standard cable termination = 95mm2

• Max. cable termination = 150mm2 (using M8 reduced palm width lugs)

Note: To shroud incoming terminals please order shroud separately (YA3TS3P).

Page 43: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

41

400A Panel Boards• ASTA certified busbars rated at 400A, 25kA for 1 second• Common internal accessories for MCCBs and switch disconnectors• Single part number for complete main enclosure• Enclosure are 700mm wide and 190mm deep• IP4X Ingress Protection• Suitable for direct connection (240mm2) - to be ordered separately

YA5 MCCB/switch disconnector 6 1084 PB406YAYA5 MCCB/switch disconnector 8 1174 PB408YAYA5 MCCB/switch disconnector 12 1354 PB412YAYA5 MCCB/switch disconnector 16 1534 PB416YA

Incoming device Outgoing Height Cat. no.ways (mm)

Incoming Devices for 400A Panel Boards• YA5 MCCB frame size switch disconnector• MCCB Icu rating of 25kA • MCCBs have both adjustable overload and instantaneous trips• Rated insulation voltage 800V ac (Ui)• Standard cable termination = 95mm2

• Max. cable termination = 185mm2 (using M8 reduced palm width lugs)

YA5 frame switch disconnector 400 3 YA5B3P400DYA5 frame MCCB 250 3 YA5N3P250TYA5 frame MCCB 400 3 YA5N3P400TDirect connection 400 3 PBYA2DC4

Device type Current Poles Cat. no.rating (A)

Surge Suppression• See page 111 for suitable devices

Multi-function Digital Metering Enclosure• See page 40 for details

Measuring Current Transformers• For use with Integra 1630 digital meter• Up to Class 0.5 accuracy • 5A secondary output

250A currenttransformer 25 80 50 M53J-2505D400A currenttransformer 32 94 60 M63N-400/5Optional enclosure - 270 700 PBYA2CSB

Description Cable Height Width Cat. no.aperture (mm) (mm) (mm)

Transient Voltage Surge Suppression (TVSS) Mounting Kits for 250Aand 400 Panelboards• Easily installed inside panelboard closely located to incoming device• DIN-rail mounting for triple-pole MCB• C/W 30Ka three-phase surge protector• Remote status indication• Site fault indication

TVSS Loadbank 125 mounting kit c/w surge protector & remote indicator 435 PBSM

Description Height (mm) Cat. no.

Auxiliary Units for 250A and 400A Panel Boards• Cable spreader box• 24 way service centre• Housing to accommodate outgoing YA3 MCCB

Cable spreader box 270 PBYA2CSBService centre with 24 1-pole ways 270 PBYA2SC24YA3 MCCB outgoing housing 450 PBYA2OG

Description Height (mm) Cat. no.

Note: To shroud incoming terminals please order shroud separately (YA5TS3P).

Page 44: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

42

Accessories

YA3 4-pole MCCB incoming kit PB4PNC250YA5 4-pole MCCB incoming kit (pic 2) PB4PNC400YA2 cable clamps (1.5-50mm2) YA2CC3PYA3 cable clamps (35-120mm2) YA3CC3PYA5 cable clamps (95-240mm2) YA5CC3PYA2 1-pole terminal shroud YA2TS1PYA2 3-pole terminal shroud YA2TS3PYA3 1-pole terminal shroud YA3TS1PYA3 3-pole terminal shroud (pic 1) YA3TS3PYA5 3-pole terminal shroud YA5TS3PYA3 4-pole terminal shroud YA3TS4PYA5 4-pole terminal shroud YA5TS4PDoor cylinder lock DBXCLDoor padlock device lock DBXPLYA2 SP dolly lock Y2DLYA2 TP dolly lock YADL1

Shunt tripsYA frame shunt trip 100-120V ac YAST115ACYA frame shunt trip 200-240V ac YAST240ACYA frame shunt trip 380-450V ac YAST450ACYA frame shunt trip 24V dc YAST24DC

Under-voltage releaseYA frame under-voltage release 100-120V ac YAUVR120ACYA frame under-voltage release 200-240V ac YAUVR240ACYA frame under-voltage release 380-450V ac YAUVR450ACYA frame under-voltage release 24V dc YAUVR24DC

Description Cat. no.

Outgoing Devices for 250A and 400A Panel Boards• Single frame size for MCCBs 16-125A• MCCB Icu rating of 25kA • Triple-pole MCCBs have adjustable Thermal and magnetic trips• Rated insulation voltage 800V ac (Ui)• Standard cable termination = 35mm2

• Max. cable termination = 70mm2 (using M8 reduced palm width lugs)

YA2 frame MCCB 16 YA2N1P16T N/AYA2 frame MCCB 20 YA2N1P20T YA2N3P20T YA2 frame MCCB 32 YA2N1P32T YA2N3P32T YA2 frame MCCB 50 YA2N1P50T YA2N3P50T YA2 frame MCCB 63 YA2N1P63T YA2N3P63T YA2 frame MCCB 80 YA2N1P80T N/AYA2 frame MCCB 100 YA2N1P100T YA2N3P100T YA2 frame MCCB 125 YA2N1P125T YA2N3P125T

Description Current Cat. no.rating (A) 1-pole 3-pole

1

2

Page 45: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

MCCB 16 YA2 25kA YA2N1P16T N/AMCCB 16 YA2 25kA YA2N1P16T N/AMCCB 20 YA2 25kA YA2N1P20T YA2N3P20T MCCB 32 YA2 25kA YA2N1P32T YA2N3P32T MCCB 50 YA2 25kA YA2N1P50T YA2N3P50T MCCB 63 YA2 25kA YA2N1P63T YA2N3P63T MCCB 80 YA2 25kA YA2N1P80T N/AMCCB 100 YA2 25kA YA2N1P100T YA2N3P100T MCCB 125 YA2 25kA YA2N1P125T YA2N3P125T

Outgoing Devices for 250A & 400A Panel BoardsDevice type Current Frame MCCB Icu Cat. no.

rating (A) size 1-pole 3-pole

Cable spreader box PBYA2CSBService centre with 24 1-pole ways PBYA2SC24Enclosure and Integra digital meter PB1630125A current transformer M53J-125/5D250A current transformer M53J-250/5D400A current transformer M63N-400/5Optional enclosure PBYA2CSBYA3 MCCB outgoing housing PBYA2OG400A direct connection kit PBYA2DC4

Auxiliary Units for both 250A & 400A Panel BoardsDescription Cat. no.

TVSS Loadbank 125 mounting kit c/w surge protector & remote indicator 435 PBSM

Transient Voltage Surge Suppression (TVSS) Mounting Kits for 250A and 400A PanelboardsDescription Height (mm) Cat. no.

Switch disconnector 400 YA5 N/A YA5B3P400DMCCB 250 YA5 25kA YA5N3P250TMCCB 400 YA5 25kA YA5N3P400T

Incoming Devices for 400A Panel BoardsDevice type Current Frame size MCCB Icu Cat. no.

rating (A)

400A 25kA for 1 second YA5 MCCB/switch disconnector 6 PB406YA400A 25kA for 1 second YA5 MCCB/switch disconnector 8 PB408YA400A 25kA for 1 second YA5 MCCB/switch disconnector 12 PB412YA400A 25kA for 1 second YA5 MCCB/switch disconnector 16 PB416YA

400A Panel BoardsBusbar rating ASTA busbar Incoming device Outgoing ways Cat. no.

short circuit rating

Switchdisconnector 250 YA3 N/A YA3B3P250DMCCB 125 YA3 25kA YA3N3P125TMCCB 160 YA3 25kA YA3N3P160TMCCB 200 YA3 25kA YA3N3P200TMCCB 250 YA3 25kA YA3N3P250T

Incoming Devices for 250A Panel BoardsDevice type Current rating (A) Frame size MCCB Icu Cat. no.

43

Selection Chart - Panel Boards

250A 25kA for 1 second YA3 MCCB/switch disconnector 6 PB206YA250A 25kA for 1 second YA3 MCCB/switch disconnector 8 PB208YA250A 25kA for 1 second YA3 MCCB/switch disconnector 12 PB212YA

250A Panel BoardsBusbar rating ASTA busbar Incoming device Outgoing ways Cat. no.

short circuit rating

Page 46: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

44

Selection Chart - Accessories

Accessories

YA3 4-pole MCCB kit PB4PNC250

YA5 4-pole MCCB kit PB4PNC400

YA2 cable clamps (1.5-50mm2) YA2CC3P

YA3 cable clamps (35-120mm2) YA3CC3P

YA5 cable clamps (95-240mm2) YA5CC3P

YA2 1-pole terminal shroud YA2TS1P

YA2 3-pole terminal shroud YA2TS3P

YA3 1-pole terminal shroud YA3TS1P

YA3 3-pole terminal shroud YA3TS3P

YA5 3-pole terminal shroud YA5TS3P

70mm2 outgoing cable clamps PBYA2NA

YA3 4-pole terminal shroud YA3TS4P

YA5 4-pole terminal shroud YA5TS4P

Door cylinder lock DBXCL

Door padlock device lock DBXPL

YA2 single pole dolly locking device Y2DL

YA2 triple pole dolly locking device YADL1

Shunt tripsYA frame shunt trip 100-120V ac YAST115AC

YA frame shunt trip 200-240V ac YAST240AC

YA frame shunt trip 380-450V ac YAST450AC

YA frame shunt trip 24V dc YAST24DC

Under-voltage releaseYA frame under-voltage release 100-120V ac YAUVR120AC

YA frame under-voltage release 200-240V ac YAUVR240AC

YA frame under-voltage release 380-450V ac YAUVR450AC

YA frame under-voltage release 24V dc YAUVR24DC

Description Cat. no.

Page 47: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

4Section

Fuse Switch Panel Boards

Loadbank 200 Range of Fuse Switch Panel Boards 800A

Page 48: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

46

Key Features• ASTA certified short circuit

withstand rating• Allows inclusion of TP&N

and four-pole fuse switch distribution

• Generous cable-spreading space for incoming andoutgoing cables

• Common width (750mm) and depth (200mm) for all enclosures

Available Options• 800A panel boards with 6 or 10

outgoing fuse switch ways • 400A, 630A or 800A fuse

switch incomers • Panel build options include:

• SP&N MCB distribution board for 17 ways

• TP&N distribution board with 6 and 12 ways

• TP&N distribution board withdouble banks of 12 ways

• General purpose enclosureswith uncut front plates

• Metering housings and service centres

• Current transformers

Additional Features • Add-on incomer units include

all copper connections andincoming cable shrouds

• Panel and distribution boardsexceed EN 60439-1requirements

• Fully shielded busbars andinterconnections on distribution boards

• Various locking options• IP4X Ingress Protection

Compliance

Switch fuse panelboards EN 60439-1

Skeleton switches EN 60947-3

Overview

The Dorman Smith Loadbank 200 panel board range isdesigned to fulfil the need for fuse switch panel boardsof up to 800A capacity.

This range provides standard panel boards with 400A,630A or 800A incomers and either 6 or 10 outgoingTP&N and four-pole ways to house fuse switches of upto 200A. In addition, a range of MCB distributionboards complements the core panel boards, togetherwith an array of cableways, to cover a wide assortmentof distribution arrangements.

Loadbank 200 panel boards are provided with Form 2separation, with Form 4 shielding as an option. Thestandard finish is epoxy powder coating in light greyRAL 7035.

Loadbank 200 is a modular distribution system whereeach single module equals 152mm.

Page 49: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

47

Loadbank 200 System Configuration

Showing an 800A incoming fuseswitch, outgoing fuse switches andTP&N add-on distribution system.

Page 50: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

48

800A Fuse Switch Panel Boards – Form 2 • ASTA certified busbars rated at 800A, 50kA for 1 second • Cableway units available for cable sizes above 70mm2

• Supplied with two end plates and two side plates• IP4X Ingress Protection

800A Panel Boards – Form 4

Fuse switch 6 5 modules 59 LF806AFuse switch 10 8 modules 98 LF810A

Outgoing device Outgoing ways Height Weight (kg) Cat. no.

Incoming Units – Form 4 • Supplied with all necessary copper connections• Incoming terminations fully shrouded• Supplied with two side plates only• IP4X Ingress Protection• For 200A incoming device an outgoing way can be used

Fuse switch 400 5 modules 49 LF1F4AFuse switch 630/800 6 modules 67 LF1F8A

Incomer housing Current rating (A) Height Weight (kg) Cat. no.

Fuse Switch Cableways – Form 2 • Recommended for cables sizes above 70mm2

• 250mm wide x 200mm deep• Supplied with two end plates only• IP4X Ingress Protection

Cableway 1 module 2 LECK1Cableway 2 modules 4 LECK2Cableway 3 modules 6 LECK3Cableway 4 modules 8 LECK4Cableway 5 modules 8 LECF5Cableway 6 modules 12 LECK6Cableway 8 modules 14 LECF8

Description Height Weight (kg) Cat. no.

Form 4 shields for outgoing cables up to 70mm2 LFS41AForm 4 shields for outgoing cables up to 150mm2 LFS42AVertical connection kit for 800A panelboard LCFVKBlank cover plate for fuse switch handle LFXHBA

Form 4 Conversion Cat. no.

Note: Fuse switch devices must be ordered separately.Weight given for incoming housings is inclusive of incoming device.

Surge Suppression• See page 110 for suitable devices

Transient Voltage Surge Suppression (TVSS) Cableway Mounting Kits • Easily installed within a standard cableway (2 modules onward)• DIN-rail mounting for triple-pole MCB• C/W 30Ka three-phase surge protector• Remote status indication• Site fault indication

Cableway mounting frame c/w surge protector & remote indicator (pic 1) 304 LECK2SM2 module enclosure c/w surge protector & remote indicator (pic 2) 304 LECK2SP

Description Height (mm) Cat. no.

1

2

Page 51: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

49

Service Centres • Fully shielded busbars and interconnections• Supplied with one end plate and two side plates• IP3X (IP4X with door fitted) Ingress Protection

24 DIN modules 1 module 10 LDS24 LD1DS

Description Height Weight Enclosure Door kit(kg) cat. no. cat. no.

SP&N MCB Distribution Boards • Exceeds EN 60439-1 requirements• Fully shielded busbars and connections• Supplied with one end plate and two side plates• IP3X (IP4X with door fitted) Ingress Protection• Facility for direct connection to busbar

17 1 module 15 LDS17 LD1DS

Outgoing ways Height Weight Enclosure Door kit(kg) cat. no. cat. no.

TP&N MCB Distribution Boards • Exceeds EN 60439-1 requirements • Space saving twin distribution board option• Fully shielded busbars and connections• Supplied with two end plates and two side plates• IP3X (IP4X with door fitted) Ingress Protection• Facility for direct connection to busbar

6 2 modules 23 LDT106X LD1D06X

12 3 modules 30 LDT112X LD1D12X

2x12 4 modules 35 LDT212X LD2D12X

Outgoing ways Height Weight Enclosure Door kit(kg) cat. no. cat. no.

Loadbank 200 General Purpose Enclosures • Wide range of modular sizes• Supplied with front plate, two end plates and two side plates• IP4X Ingress Protection

GP enclosure 1 module 4 LEE1

GP enclosure 2 modules 10 LEE2

GP enclosure 3 modules 16 LEE3

GP enclosure 4 modules 22 LEE4

GP enclosure 5 modules 28 LEE5

GP enclosure 6 modules 34 LEE6

Description Height Weight (kg) Cat. no.

Note: A one module general purpose enclosure LEE1 will assist in cabling twindistribution boards.

Single module RCBOs can be fitted into only the LDT1 series of TP&N distribution boards.

Page 52: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

50

Multi-function Digital Metering Enclosure • Utilises Integra 1630 multi-function digital metering system• Fully programmable three-phase configuration• Measurement and display of up to 34 parameters including THD• Compact modular construction• Supplied with one end plate and two side plates • Current transformer not included, see below• IP4X Ingress Protection

Enclosure (with digital panel meter) 152 11 LEM1630

Description Height Weight Cat. no.(mm) (kg)

Measuring Current Transformers • For use with the Integra 1630 digital meter• Up to Class 0.5 accuracy • System voltage up to 720V• Secondary output 5A• Operating temperatures from -20°C to +70°C

400A current transformer 32 94 60 M63N-400/5

600A current transformer 42 131 90 M93L-600/5

800A current transformer 63 156 134 MB5D-800/5

Description Cable Height Width Cat. no.aperture (mm) (mm)(mm)

Loadbank 200 Accessories

800A PanelboardVertical connection kit - LCFVK

Blank cover plate for fuse switch handle - LFXHBA

Loadbank200/EnclosuresCylinder lock/key kit for door kits - DBXCL

Padlocking kit for door kits - DBXPL

GP Enclosures/Metering EnclosuresHorizontal insulation kit - MXEPF

Steel end plate - LGES

Description Height Cat. no.

Page 53: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

51

400 SL3P400N SL4P400

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

630 SN3P630N SN4P630

800 SN3P800N SN4P800

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

Rated current (A) 400 630 800

Frame size L N N

Mechanical endurance 5,000 5,000 3,000

Fused s/c current kA rms 80 80 80

kW @ 415V ac 230 330 450

Max. cable (mm2) * 300 630 630

Terminals M12 4xM8** 4xM8**

Terminals - 1xM16** 1xM16**

Max cable lug 50 80 80

Weight (kg) 21 37 37

Max. current rating 400 630 800(A) =

Loadbank 200 Incoming Devices

400A Skeleton Switches• Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

630A and 800A Skeleton Switches• Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

Switch Data

* These figures are for guidance only and are dependent upon lug palm width** Only with cable extension terminals (SNCET)

Page 54: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

52

Loadbank 200 Outgoing Devices

63/125A Skeleton Switches• Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

63 SF3P63N SF4P63

100 SF3P100N SF4P100

125 SF3P125N SF4P125

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

160/200A Skeleton Switches• Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

160 SF3P160N SF4P160

200 SF3P200N SF4P200

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

Rated current (A) 63 100 125 160 200

Frame size F F F F F

Mechanical endurance 10,000 10,000 8,000 8,000 8,000

Fused s/c current kA rms 80 80 80 80 80

kW @ 415V ac 30 55 75 90 110

Max. cable (mm2) * 150 150 150 150 150

Terminals M8 M8 M8 M8 M8

Max cable lug palm width 22 22 22 22 22

Weight (kg) 6 6 6 12 12

Max. current rating 125 200(A) =

Switch Data

* These figures are for guidance only and are dependent upon lug palm width.

Page 55: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

53

Accessories for Outgoing Skeleton Switches

Solid links (set of 1) 63 1 HFL63

Solid links (set of 1) 100/200 1 HFL200A

2-bank auxiliary switch 63/200 2 SAUX2F

4-bank auxiliary switch 63/200 2 SAUX4F

Terminal shrouds and barriers 63/200 – SFTSS

Terminal barriers (set of 3) 63/200 – SFTB

Description Current Picture Cat. no.rating (A)

63 A3, A2 TIS, TIA GTIA TIS, TIA BAO, AAO SB4, SB3

100 A4 TCP - CEO SD5(DIA 33 Max)

125 As A4 TFP TFP DEO, CEO SD6, SD5

160 As A4 TFP TFP DEO, CEO SD6, SD5(DIA 38 max)

200 As A4 TFP TFP DEO, CEO SD6, SD5(DIA 38 max)

400 B4, B3, TMF, TFK, TMF, TFK, ED, DD, CD SF8, SF7, B2, B1 TF, TC TF, TC SF6, SF5

630 C2, C1 TTM, TM TTM, TM FF, EF SH9, SH8

800 C3, C2, C1 TLM, TTM, TLM, TTM, GF, FF, EF SH10, SH9,TM TM SH8

Current BS88 Lawson GEC Bussmann MEMrating (A) Reference Paramount

Fuse Data

Cable extension terminals (set of 8) 630/800 – SNCET

Solid links (set of 1) 400 1 HLL400

Solid links (set of 1) 630/800 1 HNL800

2-bank auxiliary switch 400/630/800 2 SAUX2N

4-bank auxiliary switch 400/630/800 2 SAUX4N

6-bank auxiliary switch 400/630/800 2 SAUX6N

Terminal shrouds and barriers 400 – SLTS

Terminal shrouds and barriers 630/800 – SNTS

Terminal barriers (set of 3) 400 – SLTB

Terminal barriers (set of 3) 630/800 – Supplied

Description Current Picture Cat. no.rating (A)

Accessories for Incoming Skeleton Switches

1 2

Page 56: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Enclosure (including digital - 1 module 11 LEM1630panel meter)400A current transformer 32 94 60 M63N-400/5600A current transformer 42 131 90 M93L-600/5800A current transformer 63 156 134 MB5D-800/5

Service centre (DIN units) 24 DIN 1 module 10 LDS24 LD1DS

Digital MeteringFor use with Integra meter Cable aperture Height Weight (kg) Cat. no.

(mm)

Service CentresType Outgoing ways Height Weight (kg) Cat. no. Door kit

1 module 4 LEE12 modules 10 LEE23 modules 16 LEE34 modules 22 LEE45 modules 28 LEE56 modules 34 LEE6

General Purpose EnclosuresHeight Weight (kg) Cat. no.

1 module 2 LECK12 modules 4 LECK23 modules 6 LECK34 modules 8 LECK45 modules 8 LECF56 modules 12 LECK68 modules 14 LECF8

CablewaysHeight Weight (kg) Cat. no.

Incoming UnitsDevice type Current Height Weight (kg) Cat. no.housing rating (A)

Form 4 shields for outgoing cables up to 70mm2 LFS41AForm 4 shields for outgoing cables up to 150mm2 LFS42AVertical connection kit for 800A panelboard LCFVKBlank cover plate for fuse switch handle LFXHBA

800A Panel Boards - Form 4 Conversion Cat. no.

54

Selection Chart - Loadbank 200 Enclosures

Fuse switch 6 5 modules 59 LF806AFuse switch 10 8 modules 98 LF810A

800A Panel Boards - Form 2Outgoing device Outgoing ways Height (mm) Weight (kg) Cat. no.

Cableway mounting frame c/w surge protector & remote indicator 304 LECK2SM

2 module enclosure c/w surge protector & remote indicator 304 LECK2SP

Transient Voltage Surge Suppression (TVSS) Cableway Mounting Kits Description Height (mm) Cat. no.

Fuse switch 400 5 modules 48.5 LF1F4AFuse switch 630/800 6 modules 66.5 LF1F8A

Page 57: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

55

Selection Chart - Loadbank 200 Incomers andDistribution Boards

Skeleton switch 200 SF3P200N SF4P200

Skeleton switch 400 SL3P400N SL4P400

Skeleton switch 630 SN3P630N SN4P630

Skeleton switch 800 SN3P800N SN4P800

Fuse SwitchesDevice type Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

Loadbank 200 Incoming Devices

17 1 module 15 LDS17 LD1DS

SP&NOutgoing ways Height Weight (kg) Enclosure cat. no. Door kit cat. no.

TP&NOutgoing ways Height Weight (kg) Enclosure cat. no. Door kit cat. no.

6 2 modules 23 LDT106X LD1D06X

12 3 modules 30 LDT112X LD1D12X

2x12 4 modules 35 LDT212X LD2D12X

MCB Distribution Boards

Cable extension terminals (set of 8) 630/800 – SNCET

Solid links (set of 1) 400 1 HLL400

Solid links (set of 1) 630/800 1 HNL800

2-bank auxiliary switch 400/630/800 2 SAUX2N

4-bank auxiliary switch 400/630/800 2 SAUX4N

6-bank auxiliary switch 400/630/800 2 SAUX6N

Terminal shrouds and barriers 400 – SLTS

Terminal shrouds and barriers 630/800 – SNTS

Terminal barriers (set of 3) 400 – SLTB

Terminal barriers (set of 3) 630/800 – Supplied

Description Current rating (A) Picture Cat. no.

Accessories for Incoming Skeleton Switches

Page 58: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

56

Selection Chart - Loadbank 200 Accessories

Vertical connection kit LCFVK

Blank cover plate for fuse switch handle LFXHBA

800A PanelboardDescription Cat. no.

Horizontal insulation kit MXEPF

Steel end plate LGES

Main Enclosures - Insulation & Plates

(Loadbank 200 Outgoing Fuse Switches)

Skeleton switch 63 SF3P63N SF4P63

Skeleton switch 100 SF3P100N SF4P100

Skeleton switch 125 SF3P125N SF4P125

Skeleton switch 160 SF3P160N SF4P160

Skeleton switch 200 SF3P200N SF4P200

Outgoing Fuse SwitchesDevice Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

Solid links (set of 1) 63 HFL63

Solid links (set of 1) 100/200 HFL200A

2-bank auxiliary switch 63/200 SAUX2F

4-bank auxiliary switch 63/200 SAUX4F

Terminal shrouds and barriers 63/200 SFTSS

Terminal barriers (set of 3) 63/200 SFTB

AccessoriesDescription Current rating (A) Cat. no.

Door lock/key kit DBXCL

Padlocking kit for door kits DBXPL

Door Locking

Page 59: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

5Section

Medium Duty Panel Boards

Loadbank 250 Range of Medium Duty PanelBoards Form 2 & Form 4 400-800A

Page 60: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

58

Key Features• ASTA certified busbars with a

short-circuit withstand rating of35kA for 1 second (400A)

• ASTA certified busbars with a short-circuit rating of 50kA for 1 second (800A)

• Allows mounting of YA3, Y6 or Y7 MCCBs and switchdisconnectors

• Single frame size for outgoing 16A to 250A MCCBs

• Generous cable-spreading space for incoming andoutgoing cables

• Common width (750mm) anddepth (200mm) for allenclosures

Available Options• 400A and 800A panel boards

with 6, 12 or 18 triple-poleoutgoing ways with Y6/Y7 orYA3 incoming devices, withForm 2 separation

• 800A panel boards with 6 or 10TP&N or four-pole outgoingways with fuse switch/MCCBincomer, with Form 4separation

• Panel build options include:

• Range of MCB distribution boards

• General purposeenclosures with uncut front plates

• Metering housings andservice centres

• Current transformers

Compliance

Panel boards EN 60439-1

MCCBs EN 60947-2

MCBs EN 60898

RCCBs EN 61008

RCBOs EN 61009

Skeleton Switches 60947-3

Overview

The Dorman Smith Loadbank 250 panel board systemprovides the user with unrivalled versatility and thebuild simplicity needed to produce a wide range ofpower distribution solutions. The panel boards aredesigned for wall-mounting with the options of Form 2or Form 4 separation.

This range offers 400A and 800A rated panel boardswith outgoing YA3 MCCBs that cover all the way from16-160A single-pole to 20-250A triple-pole ratingrequirements. Incomers can be sourced from YA3, Y6and Y7 MCCB ranges up to 800A or from anappropriate selection of switch fuses.

Loadbank 250 panel boards house the incomer andoutgoing units in separate, adjoining enclosures toallow the widest range of possible circuit permutations,including oversized outgoing circuits, to beaccommodated within a common format. The standardfinish is epoxy powder coating in light grey RAL 7035.

Loadbank 250 is a modular enclosure system whereeach single module equals 152mm high.

8 Module Height-1219mm

6 Module Height-914mm

5 Module Height-762mm

4 Module Height-609mm

3 Module Height-457mm

2 Module Height-304mm

1 Module Height-152mm

Cableway250mm

Main Enclosure750mm

Depth of all Enclosures – 200mm

Page 61: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

59

400A/800A Panel Board Configuration Form 2

The arrangement shown illustrates aY6 frame MCCB incomer with singleand triple-pole YA3 frame MCCBs asoutgoing devices.

Page 62: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

60

MCCB/YA3 6 4 modules 36 LB406YA LBDD06

MCCB/YA3 12 6 modules 52 LB412YA LBDD12

MCCB/YA3 18 8 modules 66 LB418YA LBDD18

Additional bottom plate supplied with incoming enclosure. If incoming enclosurenot required please order spare end plate.

Outgoing Outgoing Height Weight Panel Door kitdevice ways (kg) cat. no. cat. no.

• ASTA certified busbars rated at 35kA for 1 second• Accepts single-pole and triple-pole MCCBs up to 250A• Cableway units available for cable sizes above 70mm2

• Enclosures are 750mm wide x 200mm deep• Supplied with one end plate and two side plates• IP3X (IP4X with door fitted) Ingress Protection

Incoming Enclosures for 400A Form 2 Panel Boards• Supplied with all necessary copper connections• Enclosures are 750mm wide x 200mm deep• Supplied with one end plate and two side plates• IP3X (IP4X with door fitted) Ingress Protection

Accessories for 400A Loadbank 250 System

Panel Board Stacking KitsThe Loadbank 250 panel boards can be stacked to create larger capacityinstallations or used as a retrofit to increase the capacity of existing facilities.

Housed Fuse Switch Adaptor Kits• Kit enables housed fuse switch to be connected to MCCB panel board• Supplied with all necessary connections

MCCB/YA3* 250 3 modules 26 LB1YA3

MCCB/Y6 400 5 modules 45 LB1Y6

Direct connection 400 2 modules 18 LBDR4Fuse switch 200 3 modules 37.5 LB1F2A

Fuse switch 400 5 modules 49 LB1F4A

Incoming Current Height Width Cat. no.device rating (A) (kg)

* Note: Triple-pole YA3 MCCB requires YA3NL when used in LB1YA3

HBF3P200N 200 LBSK2B

HBF3P400N 400 LBSK4B

Switch type Current rating (A) Cat. no.

Loadbank 250/Distribution Boards/Service Centres

Blanking piece – 3-pole MCCB (1 front shield blank) LBBP3PYA3

Vertical stacking kit – 400A panel board to 400A panel board LBCK4

Busbar terminal extensions with shield – to connect both LBSKEends of busbar

Cylinder lock/key kit for door kits DBXCL

Padlocking kit for door kits DBXPL

Description Cat. no.

Surge Suppression• See page 111 for suitable devices

400A Panel Boards - Form 2

Page 63: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

61

Incoming Devices for 400A Panel Boards – Form 2

YA3 Frame MCCB – Icu 25kA and 36kA• Exceeds EN 60947-2 requirements • Rated insulation voltage 800V ac (Ui)• Adjustable thermal and magnetic trip settings• Standard M8 cable lug termination = 95mm2

• Maximum cable termination = 150mm2 (using M8 reduced palm width lugs)

250 YA3B3P250D YA3B4P250D

YA3 Frame Switch DisconnectorCurrent rating (A) 3-pole cat. no. 4-pole cat. no.

250 160 YA3N3P250T YA3N4P250T

YA3 Frame MCCB – 25kACurrent rating (A) 3-pole cat. no. 4-pole cat. no.Max. Min.

250 160 YA3S3P250T YA3S4P250T

YA3 Frame MCCB – 36kACurrent rating (A) 3-pole cat. no. 4-pole cat. no.Max. Min.

400 250 Y6H3P400T5 Y6H4P400T5

YA6 Frame MCCB - 50kACurrent rating (A) 3-pole cat. no. 4-pole cat. no.Max. Min.

400 Y6B3P400D Y6B4P400D

Y6 Frame Switch Disconnector 3-pole cat. no. 4-pole cat. no.Current rating (A)

Y6 Frame MCCB – Icu 50kA• Exceeds EN 60947-2 requirements • Rated insulation voltage 690V ac (Ui)• Adjustable thermal and magnetic trip settings• No extension terminal bars supplied, see ‘Accessories’ if required• Standard M12 cable lug termination = 240mm2

400A Skeleton Switches• Exceeds the requirements of EN 60947-3• 80kA rms fused short circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

200 SF3P200N SL4P200

400 SL3P400N SL4P400

Rated current (A) 400

Frame size L

Mechanical endurance 5,000

Fused short circuit current kA rms 80

kW @ 415V ac 230

Max. cable (mm2)* 300

Terminals M12

Max cable lug width 50

Weight (kg) 21

Skeleton SwitchesCurrent rating (A) 3-pole+N cat. no. 4-pole cat. no.

Note: Fuses must be ordered separately

Note: See page 102 for switch data

* These figures are for guidance only and are dependent upon lug palm width

Switch Data

Page 64: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Accessories for 800A Loadbank 250 Systems

Loadbank250/Distribution Boards/Service CentresBlanking piece – 3-pole MCCB (1 front shield blank) LBBP3PYA3

Vertical stacking kit – 800A panel board to 800A panel board LBCK8

Busbar terminal extensions with shield – to connect bothends of busbar LBSKE

Cylinder lock/key kit for door kits DBXCL

Padlocking kit for door kits DBXPL

Horizontal insulation kit MXEPF

Steel end plate LGES

Description Cat. no

62

• ASTA certified busbars, rated at 50kA for 1 second• Accepts single-pole and triple-pole MCCBs up to 250A• Cableway units are available for cable sizes above 70mm2

• Enclosures are 750mm wide x 200mm deep• Supplied with one end plate and two side plates• IP3X (IP4X with door fitted) Ingress Protection

Incoming Enclosures for 800A Form 2 Panel Boards• Supplied with all necessary copper connections• Enclosures are 750mm wide x 200mm deep• Supplied with one end plate and two side plates• IP3X (IP4X with door fitted) Ingress Protection

MCCB/YA3 6 4 modules 42 LB806YA LBDD06

MCCB/YA3 12 6 modules 62 LB812YA LBDD12

MCCB/YA3 18 8 modules 78 LB818YA LBDD18

Additional bottom plate supplied with incoming enclosure. If incoming enclosurenot required please order spare end plate.

Outgoing Outgoing Height Weight Panel Door kitdevice ways (kg) cat. no. cat. no.

MCCB/Y6 630 5 modules 45 LB1Y6*

MCCB/Y7 800 6 modules 69 LB1Y7*

Direct 800 3 modules 23 LBDR8connection

Incomer Current Height Weight Cat. no.device rating (A) (kg)

*Neutral link supplied

800A Panel Boards - Form 2

Twin YA5 Outgoing Housing • Can be mounted direct to incoming enclosure• Can be mounted direct to 800A panelboard (LBCK8 required)• 3 module cableway required (LECM3)

Twin YA5 (400A 3 modules 35 LB802YA5 LBDD02max each)

Description Height Weight (kg) Cat. no. Door kitcat. no.

Note: Available June

Page 65: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

63

Incoming Devices for 800A Panel Boards – Form 2• Exceeds EN 60947-2 requirements • Rated insulation voltage 690V ac (Ui)• MCCBs have both adjustable overload and instantaneous trips• Electronic MCCBs are Category B rated for discrimination• Electronic MCCBs have adjustable long, short and instantaneous trip functions• No extension terminal bars supplied, see ‘Accessories’ if required• Standard M18 cable lug termination = 240mm

630 Y6B3P630D Y6B4P630D

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Y6 Frame Switch Disconnector

Y6 Frame MCCB Thermal/Magnetic – Icu 50kA

630 400 Y6H3P630T5 Y6H4P630T5

Current rating (A) 3-pole cat. no. 4-pole cat. no.Max. Min.

Y6 Frame MCCB Electronic – Icu 50kA

630 315 Y6H3P630E Y6H4P630E

Current rating (A) 3-pole cat. no. 4-pole cat. no.Max. Min.

Surge Suppression• See page 110 for suitable devices

Terminal covers 3-poleInterphase barriers (set of 2) – Y5TB3P

Terminal covers 4-poleInterphase barriers (set of 3) – Y5TB4P

Terminations 3-poleExtension terminal bars Y6XT3P

Terminations 4-poleExtension terminal bars Y6XT4P

Locking devicesDolly padlock device 3 Y6DL

Shunt tripsShunt 100-120V ac 4 Y6ST115AC

Shunt 200-480V ac 4 Y6ST480AC

Shunt 24V dc 4 Y6ST24DC

Under-voltage releaseUVR 100-120V ac 5 Y6UVR120AC

UVR 200-240V ac 5 Y6UVR240AC

UVR 380-450V ac 5 Y6UVR450AC

UVR 24V dc 5 Y6UVR24DC

Auxiliary switches1AB auxiliary switch 6 Y6AUX1

2AB auxiliary switch 6 Y6AUX2

Alarm switch + 1 auxiliary 6 Y6AUXAL

Description Picture Cat. no.

Y6 Frame Accessories

2

3

1

4

65

Page 66: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

64

• Exceeds EN 60947-2 requirements • Rated insulation voltage 690V ac (Ui)• Electronic MCCBs are Category B rated for discrimination• Electronic MCCBs have adjustable long, short and instantaneous trip functions

800 Y7B3P800D Y7B4P800D

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Y7 Frame Switch Disconnector

Y7 Frame MCCB Electronic – Icu 65kA

1000 500 Y7J3P1000E Y7J4P1000E

Current rating (A) 3-pole cat. no. 4-pole cat. no.Max. Min.

Note: This MCCB must be set for 800A maximum.

Terminal covers 3-poleInterphase barriers (set of 2) – Y5TB3P

Terminal covers 4-poleInterphase barriers (set of 3) – Y5TB4P

Locking devicesDolly padlock device 2 Y7DL

Shunt tripsShunt 100-120V ac 3 Y7ST115AC

Shunt 200-480V ac 3 Y7ST480AC

Shunt 24V dc 3 Y7ST24DC

Under-voltage releaseUVR 100-120V ac 4 Y7UVR120AC

UVR 200-240V ac 4 Y7UVR240AC

UVR 380-450V ac 4 Y7UVR450AC

UVR 24V dc 4 Y7UVR24DC

Auxiliary switches 3-pole MCCB1AB auxiliary switch 5 Y7AUX3P1

2AB auxiliary switch 5 Y7AUX3P2

Alarm switch + 1 auxiliary 5 Y7AUX3PAL

Auxiliary switches 4-pole MCCB1AB auxiliary switch 5 Y7AUX4P1

2AB auxiliary switch 5 Y7AUX4P2

Alarm switch + 1 auxiliary 5 Y7AUX4PAL

Description Picture Cat. no.

Y7 Frame Accessories

1

2

3

54

Incoming Devices for 800A Panel Boards - Form 2

Page 67: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

800A Panel Board Form 4 Configuration

This example shows the 800A fuseswitch incomer with single andtriple-pole YA3 frame MCCBs asoutgoing devices. 65

Page 68: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Accessories for 800A Loadbank 250 Systems - Form 4

Vertical stacking kit – 800A panel board to 800A panel board LCFVK

Cylinder lock/key kit for door kits DBXCL

Padlocking kit for door kits DBXPL

Horizontal insulation kit MXEPF

Steel end plate LGES

Description Cat. no

66

• ASTA certified busbars rated at 50kA for 1 second• Incoming device 800A maximum• Accepts single-pole and triple-pole MCCBs up to 250A• Cableways for cable sizes up to 150mm2

• Enclosures are 750mm wide x 200mm deep• Supplied with two end plates and two side plates• IP3X (IP4X with door fitted) Ingress Protection

Incoming Enclosures for 800A Form 4 Panel Boards• Supplied with all necessary copper connections• Incoming terminations fully shrouded• IP4X Ingress Protection

MCCB/YA3 6 5 modules 59 LF806YA MXD06

MCCB/YA3 10 8 modules 98 LF810YA MXD10

Outgoing Outgoing Height Weight Panel Door kitdevice ways (kg) cat. no. cat. no.

Fuse switch 630/800 5 modules 67 LF1F8A

Y6 frame MCCB 800 6 modules 59 MMS15Y*

Y6 connection kit MCFMY6

Incomer Current Height Weight Cat. no.housing rating (A) (kg)

Form 4 Shielding

70mm2 cables - LFS41YA

150mm2 cables Cableway LFS42YA

Blanking kit - YA3F4BP

Description Additional housing Cat. no.

Note: TP&N applications require YA3NL neutral link.

Note: Fuse switch devices/MCCBs must be ordered separately.

*Neutral link supplied

800A Panel Boards - Form 4

Page 69: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

67

• Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

Incoming Devices for 800A Panel Boards – Form 4• Exceeds EN 60947-2 requirements • Rated insulation voltage 690V ac (Ui)• MCCBs have both adjustable overload and instantaneous trips• Electronic MCCBs are Category B rated for discrimination• Electronic MCCBs have adjustable long, short and instantaneous trip functions• No extension terminal bars supplied, see ‘Accessories’ if required• Standard M12 cable lug termination = 240mm2

630 SN3P630N SN4P630

800 SN3P800N SN4P800

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Switch data

800 Y6B4P800D

Current rating (A) 4-pole cat. no.

Y6 Frame MCCB Thermal/Magnetic – Icu 50kA

Y6 Frame Switch Disconnector

800 500 Y6H4P800T5

Current rating (A) 4-pole cat. no.Max. Min.

Y6 Frame MCCB Electronic – Icu 50kA

800 400 Y6H4P800E

Current rating (A) 4-pole cat. no.Max. Min.

Rated current (A) 630 800

Frame size N N

Mechanical endurance 5,000 3,000

Fused s/c current kA rms 80 80

kW @ 415V ac 330 450

Max. cable (mm2)* 630 630

Terminals 4xM8 1xM16**

Max. cable lug 80 80

Weight (kg) 37 37

Max. current rating (A) = 800

* These figures are for guidance only and are dependent upon lug palm width.** Only with cable extension terminals (SNCET)

Surge Suppression• See page 111 for suitable devices

Incoming Devices for 800A PanelBoards - Form 4 630A and 800ASkeleton Switches

Page 70: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

68

Cable extension terminals (set of 8) 630/800 – SNCET

Solid links (set of 1) 630/800 1 HNL800

Castell* lock mounting kit 630/800 – SCLK

Castell* lock with key (see note) 630/800 2 FS2

Terminal shrouds and barriers 630/800 – SNTS

Terminal barriers (set of 3) 630/800 – Supplied

Fuse shrouds 630/800 – SNFS

Description Current Picture Cat. no.rating (A)

Accessories for 630/800A Skeleton Switches

Fuse Data

630 C2, C1 TTM, TM TTM, TM FF, EF SH9, SH8

800 – TLM, TTM, TLM, TTM, GF, FF, SH10, SH9,TM TM EF SH8

Current BS88 Lawson GEC Bussmann MEMrating (A) reference Paramount

1

2

Note: Standard symbol DS1, special symbols are available direct from Castell. Quote reference: Castell FS2 - Spigot 9.5mm square x 22.5mm, 65°anti-clockwise totrap key.

Y6 Frame Accessories

Terminal covers 3-poleTerminal shroud (set of 1) Y6TS3PTerminal cover Y6TC3PInterphase barriers (set of 2) Y5TB3P

Terminal covers 4-poleTerminal shroud (set of 1) Y6TS4PTerminal cover Y6TC4PInterphase barriers (set of 3) Y5TB4P

Terminations 3-poleExtension terminal bars Y6XT3P

Terminations 4-poleExtension terminal bars Y6XT4P

Locking devicesDolly padlock device Y6DLCastell* lock (DS1 direct mounting) Y6CLDS1Castell* lock (door mounted) Y5DCLCastell* lock door mounted cam for shaft only Y5DCLCAM

Shunt tripsShunt 100-120V ac Y6ST115ACShunt 200-480V ac Y6ST480ACShunt 24V dc Y6ST24DC

Under-voltage releaseUVR 100-120V ac Y6UVR120ACUVR 200-240V ac Y6UVR240ACUVR 380-450V ac Y6UVR450ACUVR 24V dc Y6UVR24DC

Motor actuatorsMotor actuator 100-110V ac Y6MA110Motor actuator 200-240V ac Y6MA240

Auxiliary switches1AB auxiliary switch Y6AUX12AB auxiliary switch Y6AUX2Alarm switch + 1 auxiliary Y6AUXAL

Neutral linkY6 neutral link Y6NL

Description Cat. no.

*Castell is a trademark of Castell Safety International Ltd.

Page 71: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

69

General Purpose Accessories for Loadbank 400A and 800A Loadbank250 Systems

General Purpose Cableways• Recommended for cables above 70mm2

• Cableways are 250mm wide x 200mm deep• Supplied with two end plates only• IP4X Ingress Protection

General Purpose Enclosures• Wide range of modular sizes• Supplied with two end plates, two side plates and front plates• Enclosures are 750mm wide x 200mm deep• IP4X Ingress Protection

1 module Yes 2 LECK1

2 modules Yes 4 LECK2

3 modules Yes 6 LECK3

3 modules Yes 6 LECM3

4 modules Yes 8 LECK4

5 modules Yes 8 LECF5

6 modules Yes 12 LECK6

8 modules Yes 14 LECF8

Modular Standard Large Weight Cat. no.height apertures apertures (kg)

1 module 4 LEE1

2 modules 10 LEE2

3 modules 16 LEE3

4 modules 22 LEE4

5 modules 28 LEE5

6 modules 34 LEE6

Modular height Weight (kg) Cat. no.

Transient Voltage Surge Suppression (TVSS) Cableway Mounting Kits • Easily installed within a standard cableway (2 modules onward)• DIN-rail mounting for triple-pole MCB• C/W 30Ka three-phase surge protector• Remote status indication• Site fault indication

Cableway mounting frame c/w surge protector & remote indicator (1) 304 LECK2SM

2 module enclosure c/w surge protector & remote indicator (2) 304 LECK2SP

Description Height (mm) Cat. no.

Horizontal insulation kit MXEPFSteel end plate LGES

Description Cat. no.

1

2

Auxiliary Enclosures and Accessoriesfor 400A and 800A Form 2 andForm 4 Panel Boards

Page 72: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

70

Multi-function Digital Metering Enclosure• Utilises the Integra 1630 multi-function digital metering system• Fully programmable three-phase configuration• Measurement and display of up to 34 parameters including THD• Compact modular construction• Supplied with one end plate and two side plates • IP4X Ingress Protection• Current transformer not included, see following page

Enclosure (with digital panel meter) 152 11 LEM1630

Description Height Weight Cat. no.

600A current transformer 42 131 90 M93L-600/5

800A current transformer 63 156 137 MB5D-800/5

Description Capture Height Width Cat. noaperture (mm) (mm) (mm)

Measuring Current Transformers• For use with the Integra 1630 digital meter• Provides safe current measurement by the ammeter• Use to drive ammeter indicators, transducers, overload protection

and control devices• Up to Class 0.5 accuracy• System voltage up to 720V• Secondary output 5A• Operating temperatures from -20°C to +70°

Note: New metering facilities available July 2009.

Page 73: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

71

Description Cat. no

• Exceeds EN 60947-2 requirements • Rated insulation voltage 800V ac (Ui)• Adjustable overload and instantaneous trip settings (triple and four-pole only)• Standard M8 cable lug termination = 95mm2

Maximum cable termination = 150mm2 (using M8 reduced palm width lugs)

YA3 Frame MCCB Thermal/Magnetic – Icu 25kA

16 16 YA3N1P16T – –

20 13 YA3N1P20T YA3N3P20T –

32 20 YA3N1P32T YA3N3P32T –

40 25 YA3N1P40T – –

50 32 YA3N1P50T YA3N3P50T YA3S3P50T

63 40 YA3N1P63T YA3N3P63T YA3S3P63T

80 50 YA3N1P80T – –

100 63 YA3N1P100T YA3N3P100T YA3S3P100T

125 80 YA3N1P125T YA3N3P125T YA3S3P125T

160 100 YA3N1P160T YA3N3P160T YA3S3P160T

200 125 – YA3N3P200T YA3S3P200T

250 160 – YA3N3P250T YA3S3P250T

Current rating (A) 1-pole, 25kA 3-pole, 25kA 3-pole, 36kA Max. Min. cat. no. cat. no. cat. no.

Outgoing Devices for 800A Panel Boards Form 4

20 13 YA3N4P20T - -

32 20 YA3N4P32T - -

50 32 YA3N4P50T YA3S4P50T YA3J4P50T

63 40 YA3N4P63T YA3S4P63T YA3J4P63T

100 63 YA3N4P100T YA3S4P100T YA3J4P100T

125 80 YA3N4P125T YA3S4P125T YA3J4P125T

160 100 YA3N4P160T YA3S4P160T YA3J4P160T

200 125 YA3N4P200T YA3S4P200T YA3J4P200T

250 160 YA3N4P250T YA3S4P250T YA3J4P250T

Current rating (A) 4-pole, 25kA 4-pole, 36kA 4-pole, 65kAMax. Min. cat. no. cat. no. cat. no.

16 - YA3N1P16T – –

20 13 YA3N1P20T YA3N3P20T –

32 20 YA3N1P32T YA3N3P32T –

40 - YA3N1P40T – –

50 32 YA3N1P50T YA3N3P50T YA3S3P50T YA3J3P50T

63 40 YA3N1P63T YA3N3P63T YA3S3P63T YA3J3P63T

80 - YA3N1P80T – –

100 63 YA3N1P100T YA3N3P100T YA3S3P100T YA3J3P100T

125 80 YA3N1P125T YA3N3P125T YA3S3P125T YA3J3P125T

160 100 YA3N1P160T YA3N3P160T YA3S3P160T YA3J3P160T

200 125 - YA3N3P200T YA3S3P200T YA3J3P200T

250 160 - YA3N3P250T YA3S3P250T YA3J3P250T

Current rating (A) 1-pole, 25kA 3-pole, 25kA 3-pole, 36kA 3-pole, 65kAMax. Min. cat. no. cat. no. cat. no. cat. no.

Note: TP&N applications neutral links required.

Outgoing Devices for 400A and 800A Form 2 YA3 Frame MCCBs

YA3 neutral link YA3NL

Page 74: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

72

Terminal covers 3-poleYA3 frame interphase barrier (set of 1)2 required for 3-pole device – YA3TBYA3 frame long terminal shroud (set of 1) – YA3TS3PYA3 frame short terminal shroud (set of 1) – YA3TS3PS

Terminations 3-poleYA3 frame cable clamps 35-120mm2 (set of 3) 1 YA3CC3P

Terminal covers 4-poleYA3 frame interphase barrier (set of 1)3 required for 3-pole device – YA3TBYA3 frame long terminal shroud (set of 1) – YA3TS4PYA3 frame short terminal shroud (set of 1) 2 YA3TS4PS

Terminations 4-poleYA3 frame cable clamps 35-120mm2 (set of 4) 1 YA3CC4P

Shunt tripsYA frame shunt trip 100-120V ac 3 YAST115ACYA frame shunt trip 380-450V ac 3 YAST450ACYA frame shunt trip 200-240V ac 3 YAST240ACYA frame shunt trip 24V dc 3 YAST24DC

Auxiliary and alarm switchesYA frame 1AB auxiliary switch 4 YAAUX1YA frame alarm switch 4 YAAL

Under-voltage releaseYA frame under-voltage release 100-120V ac 5 YAUVR120ACYA frame under-voltage release 200-240V ac 5 YAUVR240ACYA frame under-voltage release 380-450V ac 5 YAUVR450ACYA frame under-voltage release 24V dc 5 YAUVR24DC

Locking devicesYA frame dolly padlock device 6 YADL1YA frame Castell mounting kit – YACL

Note: Standard symbol DS1, special symbols are available direct from Castell. Quote reference: Castell FS2 - Spigot 9.5mm square x 22.5mm, 65° anti-clockwise totrap key.

*Castell is a trademark of Castell Safety International Ltd.

Description Picture Cat. no.

YA3 Frame MCCB Accessories

1

26

4 3

5

Page 75: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

73

SP&N MCB Distribution Boards• Exceeds EN 60439-3 requirements • Fully shielded busbars and connections• IP3X (IP4X with door fitted) Ingress Protection• Facility for direct connection to busbar

17 1 module 15 LDS17 LD1DS

Outgoing Height Weight Enclosure Door kitways (kg) cat. no. cat. no.

Service Centres• Fully shielded busbars and interconnections• IP3X (IP4X with door fitted) Ingress Protection

24 DIN modules 1 module 10 LDS24 LD1DS

Description Height Weight Enclosure Door kit(kg) cat. no. cat. no.

TP&N MCB Distribution Boards• Exceeds EN 60439-3 requirements• Fully shielded busbars and connections• Space saving twin distribution board option• IP3X (IP4X with door fitted) Ingress Protection• Facility for direct connection to busbar

6 2 modules 23 LDT106X LD1D06X

12 3 modules 30 LDT112X LD1D12X

2x12 4 modules 35 LDT212X LD2D12X

Outgoing Height Weight Enclosure Door kitways (kg) cat. no. cat. no.

Note: A single module general purpose enclosure LEE1 will assist thecabling of twin distribution boards.

Single module RCBOs can be fitted into only the LDT1 series of TP&Ndistribution boards.

Page 76: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

74

Selection Chart - 400A Panel Boards and Incomer Housings

400A Panel Boards - Form 2

Rating250A outgoing MCCB/YA3 6 4 modules 36 LB406YA LBDD06250A outgoing MCCB/YA3 12 6 modules 52 LB412YA LBDD12250A outgoing MCCB/YA3 18 8 modules 66 LB418YA LBDD18

ASTA busbar short circuit Outgoing Outgoing Height Weight Panel Door kitrating of 35kA for 1 second device ways (kg) cat. no. cat. no.

Incomer Housings - Form 2

MCCB/YA3 250 3 modules 26 LB1YA3MCCB/Y6 400 5 modules 45 LB1Y6Direct connection 400 2 modules 18 LBDR4Fuse switch 200 3 modules 37.5 LB1F2AFuse switch 400 5 modules 48.5 LB1F4A

Incoming device type Current Height Weight (kg) Cat. no.rating (A)

Housed Fuse Switch

Adaptor kits Current Cat. no.rating (A)

Metering Units

Enclosure with digital panel meter - - 11 LEM1630Current transformer 250 28 <1 PE401-250/5Current transformer 400 45 <1 PE601-400/5

Description Current Cable aperture Weight Cat. no.rating (A) (mm) (kg)

Cableways - Form 2

Cableway Yes 1 module 2 LECK1Cableway Yes 2 modules 4 LECK2Cableway Yes 3 modules 6 LECK3Cableway Yes 4 modules 8 LECK4Cableway Yes 5 modules 8 LECF5Cableway Yes 6 modules 12 LECK6Cableway Yes 8 modules 14 LECF8

Housing type Standard Large Height Weight (kg) Cat. no.apertures apertures

Kit for HBF3P200N, incl. connections 200 LBSK2BKit for HBF3P400N, incl. connections 400 LBSK4B

General Purpose Enclosures

Housing type Height Weight (kg) Cat. no.

General purpose – uncut front plate 1 module 4 LEE1General purpose – uncut front plate 2 modules 10 LEE2General purpose – uncut front plate 3 modules 16 LEE3General purpose – uncut front plate 4 modules 22 LEE4General purpose – uncut front plate 5 modules 28 LEE5General purpose – uncut front plate 6 modules 34 LEE6

Transient Voltage Surge Suppression (TVSS) Cableway Mounting Kits

Cableway mounting frame c/w surge protector & remote indicator 304 LECK2SM

2 module enclosure c/w surge protector & remote indicator 304 LECK2SP

Description Height (mm) Cat. no.

Page 77: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

75

Selection Chart - 400A Panel Boards(Continued)

17 1 module 15 LDS17 LD1DS

Outgoing waysSP&N Height Weight Enclosure Door kit

(kg) cat. no. cat. no.

Service centre (24 DIN units) 1 module 10 LDS24 LD1DS

Service CentresType Height Weight Cat. no. Door kit

(kg) cat. no.

6 2 modules 23 LDT106X LD1D06X

12 3 modules 30 LDT112X LD1D12X

2x12 4 modules 35 LDT212X LD2D12X

TP&N

Loadbank 250/distribution boards/service centresBlanking piece – 3-pole MCCB (1 front shield blank) LBBP3PYA3

Vertical connection kit (400A) LBCK4

Busbar terminals - extensions with shield, to connect both ends of busbar LBSKE

Adaptor kit for 200A housed fuse switch LBSK2B

Adaptor kit for 400A housed fuse switch LBSK4B

Horizontal insulation kit MXEPF

Description Cat. no.

MCB Distribution Boards

Door lock/key kit DBXCL

Padlocking kit for door kits DBXPL

Door Locking Cat. no.

Accessories for 400A Panel Board Systems

Page 78: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Selection Chart - 400A Panel Board Circuit Devices

YA3 switch disconnector250 – YA3B3P250D YA3B4P250D

YA3 frame MCCB - 25kA250 160 YA3N3P250T YA3N4P250T

YA3 frame MCCB - 36kA250 160 YA3S3P250T YA3S4P250T

Y6 switch disconnector400 – Y6B3P400D Y6B4P400D

Y6 frame MCCB - 50kA400 250 Y6H3P400T5 Y6H4P400T5

200A skeleton switches200 – SF3P200N SF4P200

400A skeleton switches400 – SL3P400N SL4P400

400A direct connection400 – – LBDR4

Incoming DevicesCurrent rating (A) 3-pole cat. no. 4-pole cat. no.Max. Min.

YA3 MCCB – 25kA16 16 YA3N1P16T –

20 13 YA3N1P20T YA3N3P20T

32 20 YA3N1P32T YA3N3P32T

40 25 YA3N1P40T –

50 32 YA3N1P50T YA3N3P50T

63 40 YA3N1P63T YA3N3P63T

80 50 YA3N1P80T –

100 63 YA3N1P100T YA3N3P100T

125 80 YA3N1P125T YA3N3P125T

160 100 YA3N1P160T YA3N3P160T

200 125 – YA3N3P200T

250 160 – YA3N3P250T

YA3 MCCB - 36kA50 32 – YA3S3P50T

63 40 – YA3S3P63T

100 63 – YA3S3P100T

125 80 – YA3S3P125T

160 100 – YA3S3P160T

200 125 – YA3S3P200T

250 160 – YA3S3P250T

Outgoing Devices for Form 2 Panel BoardsCurrent rating (A) 1-pole cat. no. 3-pole cat. no.Max. Min.

76

Page 79: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

77

Selection Chart - Accessories for YA3 Frame Devices

Terminal covers 3-poleYA3 frame interphase barrier (set of 1) 2 required for 3-pole device YA3TBYA3 frame long terminal shroud (set of 1) YA3TS3PYA3 frame short terminal shroud (set of 1) YA3TS3PS

Terminations 3-poleYA3 frame cable clamps 35-120mm2 (set of 3) YA3CC3P

Terminal covers 4-poleYA3 frame interphase barrier (set of 1) 3 required for 3-pole device YA3TBYA3 frame long terminal shroud (set of 1) YA3TS4PYA3 frame short terminal shroud (set of 1) YA3TS4PS

Terminations 4-poleYA3 frame cable clamps 35-120mm2 (set of 4) YA3CC4P

Shunt tripsYA frame shunt trip 100-120V ac YAST115ACYA frame shunt trip 200-240V ac YAST240ACYA frame shunt trip 380-450V ac YAST450ACYA frame shunt trip 24V dc YAST24DC

Auxiliary and alarm switchesYA frame 1AB auxiliary switch YAAUX1YA frame alarm switch YAAL

Under-voltage releaseYA frame under-voltage release 100-120V ac YAUVR120ACYA frame under-voltage release 200-240V ac YAUVR240ACYA frame under-voltage release 380-450V ac YAUVR450ACYA frame under-voltage release 24V dc YAUVR24DC

Locking devicesYA frame dolly padlock device YADL1YA frame Castell* (DS1) lock direct mtg. trapped ‘on’ YACL

Description Cat. no.

*Castell is a trademark of Castell Safety International Ltd.

Page 80: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

78

Solid links (set of 1) HLL400

Terminal barriers (set of 3) SLTB

Fuse shrouds SLFS

Terminal shrouds and barriers SLTS

2-blank auxiliary switch SAUX2N

4-blank auxiliary switch SAUX4N

6-blank auxiliary switch SAUX6N

Description Cat. no.

Terminal covers 3-poleInterphase barriers (set of 2) Y5TB3P

Terminal covers 4-poleInterphase barriers (set of 3) Y5TB4P

Terminations 3-poleExtension terminal bars Y6XT3P

Terminations 4-poleExtension terminal bars Y6XT4P

Locking devicesDolly padlock device Y6DL

Shunt tripsShunt 100-115V ac Y6ST115AC

Shunt 200-450V ac Y6ST450AC

Shunt 24V dc Y6ST24DC

Under-voltage releaseUVR 100-120V ac Y6UVR120AC

UVR 200-240V ac Y6UVR240AC

UVR 380-450V ac Y6UVR450AC

UVR 24V dc Y6UVR24DC

Auxiliary switches1AB auxiliary switch Y6AUX1

2AB auxiliary switch Y6AUX2

Alarm switch + 1 auxiliary Y6AUXAL

Y6 Frame AccessoriesDescription Cat. no.

Selection Chart - 400A Panel Board and IncomingDevices Accessories

Accessories for 400A Skeleton Switches

Page 81: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

79

250A outgoing MCCB/YA3 6 4 modules 42 LB806YA LBDD06

250A outgoing MCCB/YA3 12 6 modules 62 LB812YA LBDD12

250A outgoing MCCB/YA3 18 8 modules 78 LB818YA LBDD18

800A Panel Boards – Form 2ASTA busbar short circuit rating Outgoing Outgoing Height Weight Panel Door kitof 50kA for 1 second device ways (kg) cat. no. cat no.

250A outgoing MCCB/YA3 6 5 modules 59 LF806YA MXD06

250A outgoing MCCB/YA3 10 8 modules 98 LF810YA MXD10

800A Panel Boards – Form 4ASTA busbar short circuit rating Outgoing Outgoing Height Weight Panel Door kitof 50kA for 1 second device ways (kg) cat. no. cat no.

MCCB/Y6 630 5 modules 45 LB1Y6

MCCB/Y7 800 6 modules 69 LB1Y7

Direct connection 800 3 modules 23 LBDR8

Incomer Housings – Form 2Incomer device type Current Height Weight Cat. no.

rating (A) (kg)

2x YA5 MCCB 400 3 modules 25 LB802YA5

Outgoing Housings – Form 2Incomer device type Current Height Weight Cat. no.

rating (A) (kg)

Fuse switch 630/800 6 modules 67 LF1F8A

Y6 frame MCCB 800 5 modules 59 MMS15Y

Y6 connection kit MCFMY6

Incomer Housings – Form 4Device type housing Current Height Weight Cat. no.

rating (A) (kg)

70mm2 cables LFS41YA

150mm2 cables Cableway LFS42YA

Shielding – Form 4Description Additional Cat. no.

housing

Selection Chart - 800A Panel Boardsand Incomer Housings

Page 82: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Accessories for 800A Panel Board Systems

Service centre (24 DIN units) 1 module 10 LDS24 LD1DS

Service CentresType Height Weight (kg) Cat. no. Door kit

6 2 modules 23 LDT106X LD1D06X12 3 modules 30 LDT112X LD1D12X2x12 4 modules 35 LDT212X LD2D12X

TP&N

Loadbank250/distribution boards/service centresBlanking piece – 3-pole MCCB (1 front shield blank) LBBP3PYA3Vertical stacking kit – 800A panel board to 800A panel board LBCK8Busbar terminals – extensions with shield, to connect both ends of busbar LBSKECylinder lock/key kit for door kits DBXCLPadlocking kit for door kits DBXPL

GP enclosures/metering enclosuresHorizontal insulation kit MXEPFSteel end plate LGES

Description Cat. no.

80

Selection Chart - 800A Panel Boards(Continued)

General purpose – uncut front plate 1 module 4 LEE1General purpose – uncut front plate 2 modules 10 LEE2General purpose – uncut front plate 3 modules 16 LEE3General purpose – uncut front plate 4 modules 22 LEE4General purpose – uncut front plate 5 modules 28 LEE5General purpose – uncut front plate 6 modules 34 LEE6

Housing type Height Weight (kg) Cat. no.

General Purpose Enclosures

Transient Voltage Surge Suppression (TVSS) Cableway Mounting Kits

Enclosure with digital panel meter - 11 LEM1630600A current transformer 45 <1 PE601-600/5800A current transformer 60 <1 PE801-800/5

Description Cable aperture Weight Cat. no.(mm) (kg)

Metering Units

MCB Distribution Boards

17 1 module 15 LDS17 LD1DS

SP&NOutgoing ways Height Weight (kg) Cat. no. Door kit

Cableway mounting frame c/w surge protector & remote indicator 304 LECK2SM

2 module enclosure c/w surge protector & remote indicator 304 LECK2SP

Description Height (mm) Cat. no.

Page 83: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

81

Selection Chart - 800A Panel Boards Incoming Devices

Y6 Frame Switch Disconnector630 - Y6B3P630D Y6B4P630D

Y6 Frame MCCB Thermal/Magnetic –Icu 50 kA630 400 Y6H3P630T5 Y6H4P630T5

Y6 Frame MCCB Electronic – Icu 50kA630 315 Y6H3P630E Y6H4P630E

Y7 Frame Switch Disconnector800 - Y7B3P800D Y7B4P800D

Y7 Frame MCCB Electronic – Icu 65kA1000 500 Y7J3P1000E Y7J4P1000E

Incoming Devices – Form 2Current rating (A) 3-pole cat. no. 4-pole cat. no.Max. Min.

630 SN3P630N SN4P630

800 SN3P800N SN4P800

Incoming Devices – Form 4Fuse Switch 3-pole+N cat. no. 4-pole+N cat. no.Current rating (A)

800 500 - Y6H4P800T5

Y6 Frame MCCB Thermal/MagneticCurrent rating (A)Max. Min.

800 400 - Y6H4P800E

Y6 Frame MCCB ElectronicCurrent rating (A)Max. Min.

800 - Y6B4P800D

Y6 Switch DisconnectorCurrent rating (A)

Note: This MCCB must be set at 800A maximum.

Page 84: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

82

Selection Chart - 800A Panel Boards Outgoing Devices

YA3 frame MCCB - 25kA16 16 YA3N1P16T -

20 13 YA3N1P20T YA3N3P20T

32 20 YA3N1P32T YA3N3P32T

40 25 YA3N1P40T -

50 32 YA3N1P50T YA3N3P50T

63 40 YA3N1P63T YA3N3P63T

80 50 YA3N1P80T -

100 63 YA3N1P100T YA3N3P100T

125 80 YA3N1P125T YA3N3P125T

160 100 YA3N1P160T YA3N3P160T

200 125 - YA3N3P200T

250 160 - YA3N3P250T

YA3 frame MCCB - 36kA50 32 - YA3S3P50T

63 40 - YA3S3P63T

100 63 - YA3S3P100T

125 80 - YA3S3P125T

160 100 - YA3S3P160T

200 125 - YA3S3P200T

250 160 - YA3S3P250T

Outgoing Devices for all 800A Panel BoardsCurrent rating (A) 1-pole cat. no. 3-pole cat. no.Max. Min.

YA3 frame MCCB20 13 YA3N4P20T - -

32 20 YA3N4P32T - -

50 32 YA3N4P50T YA3S4P50T YA3J4P50T

63 40 YA3N4P63T YA3S4P63T YA3J4P63T

100 63 YA3N4P100T YA3S4P100T YA3J4P100T

125 80 YA3N4P125T YA3S4P125T YA3J4P125T

160 100 YA3N4P160T YA3S4P160T YA3J4P160T

200 125 YA3N4P200T YA3S4P200T YA3J4P200T

250 160 YA3N4P250T YA3S4P250T YA3J4P250T

Outgoing Devices for Form 4 Panel BoardsCurrent rating (A) 4-pole 25kA 4-pole 36kA 4-pole 65kAMax. Min. cat. no. cat. no. cat. no.

Page 85: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

83

Cable extension terminals (set of 8) SNCET

Solid links (set of 1) HNL800

Terminal barriers (set of 3) Supplied

Fuse shrouds SNFS

630/800A Skeleton Switches AccessoriesDescription Cat. no.

Terminal covers 3-pole

Interphase barriers (set of 2) Y5TB3P

Terminal covers 4-pole

Interphase barriers (set of 3) Y5TB4P

Terminations 3-pole

Extension terminal bars Y6XT3P

Locking devices

Dolly padlock device Y6DL

Shunt trips

Shunt 100-120V ac Y6ST115AC

Shunt 200-450V ac Y6ST450AC

Shunt 24V dc Y6ST24DC

Under-voltage release

UVR 100-120V ac Y6UVR120AC

UVR 200-240V ac Y6UVR240AC

UVR 380-450V ac Y6UVR450AC

UVR 24V dc Y6UVR24DC

Auxiliary switches

1AB auxiliary switch Y6AUX1

2AB auxiliary switch Y6AUX2

Alarm switch + 1 auxiliary Y6AUXAL

Y6 Frame AccessoriesDescription Cat. no.

Selection Chart - 800A Panel Board Incoming Devices Accessories

Page 86: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

84

Terminal covers 3-pole

Interphase barriers (set of 2) Y5TB3P

Terminal covers 4-pole

Interphase barriers (set of 3) Y5TB4P

Locking devices

Dolly padlock device Y7DL

Shunt trips

Shunt 100-120V ac Y7ST115AC

Shunt 200-450V ac Y7ST450AC

Shunt 24V dc Y7ST24DC

Under-voltage release

UVR 100-120V ac Y7UVR120AC

UVR 200-240V ac Y7UVR240AC

UVR 380-450V ac Y7UVR450AC

UVR 24V dc Y7UVR24DC

Auxiliary switches 3-pole MCCB

1AB auxiliary switch Y7AUX3P1

2AB auxiliary switch Y7AUX3P2

Alarm switch + 1 auxiliary Y7AUX3PAL

Auxiliary switches 4-pole MCCB

1AB auxiliary switch Y7AUX4P1

2AB auxiliary switch Y7AUX4P2

Alarm switch + 1 auxiliary Y7AUX4PAL

Y7 Frame AccessoriesDescription Cat. no.

Page 87: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

85

Selection Chart - Accessories for YA3 Frame Devices

Terminal covers 3-poleYA3 frame interphase barrier (set of 1) 2 required for 3-pole device YA3TBYA3 frame long terminal shroud (set of 1) YA3TS3PYA3 frame short terminal shroud (set of 1) YA3TS3PS

Terminations 3-poleYA3 frame cable clamps 35-120mm2 (set of 3) YA3CC3P

Terminal covers 4-poleYA3 frame interphase barrier (set of 1) 3 required for 3-pole device YA3TBYA3 frame long terminal shroud (set of 1) YA3TS4PYA3 frame short terminal shroud (set of 1) YA3TS4PS

Terminations 4-poleYA3 frame cable clamps 35-120mm2 (set of 4) YA3CC4P

Shunt tripsYA frame shunt trip 100-120V ac YAST115ACYA frame shunt trip 200-240V ac YAST240ACYA frame shunt trip 380-450V ac YAST450ACYA frame shunt trip 24V dc YAST24DC

Auxiliary and alarm switchesYA frame 1AB auxiliary switch YAAUX1YA frame alarm switch YAAL

Under-voltage releaseYA frame under-voltage release 100-120V ac YAUVR120ACYA frame under-voltage release 200-240V ac YAUVR240ACYA frame under-voltage release 380-450V ac YAUVR450ACYA frame under-voltage release 24V dc YAUVR24DC

Locking devicesYA frame dolly padlock device YADL1YA frame Castell* (DS1) lock direct mtg. trapped ‘on’ YACL

Motor actuatorYA3 motor actuator ac 100-110V YA3MA110YA3 motor actuator ac 230-240V YA3MA240

Description Cat. no.

*Castell is a trademark of Castell Safety International Ltd.

Page 88: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

86

Page 89: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

6Section

Fuse Combination Units

Loadswitch Range of Fuse Combination Units

Housed – Skeleton – Disconnect & FuseCombination 16-800A

Page 90: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

88

Key Features• 80kA short-circuit capacity• Housed or skeleton versions• Integral cable spreading facility

with choice of position• AC23A utilisation category

Benefits• Ease of installation• Accepts large cables• Rated for continuous

full-rated load

ComplianceFuse switches EN 60947-3

Overview

The Dorman Smith Loadswitch fuse combination rangeincludes skeleton switches, housed switches and switchdisconnectors. All Loadswitch fuse combination unitsexceed EN 60947-3 requirements and amply meetspecifications for full uninterrupted duty to ensure thatswitches will maintain the maximum rated loadindefinitely. Given their utilisation category of AC23Aand a short-circuit capacity of 80kA, Loadswitch fusecombination devices provide complete confidencewhen installed in any resistive or inductive loadapplication. Housed switches are supplied in sheet steelboxes with integral cable spreading space that can be positioned above or below the switch to suit ease of installation.

The switch disconnector units are supplied in eitherIP65 insulated enclosures or sheet steel boxes.

The robust steel enclosures are finished in light greyRAL 7035 epoxy powder coating and have doors thatopen 180° for ease of access. Padlocking is arranged tobe ’off‘ as standard and up to three padlocks can beattached with ease.

Page 91: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

89

Housed Switches

Skeleton Switches

32A

63/125A

160/200A

315/400A

630/800A

160/200A

63/125A

315/400A

630/800A

Page 92: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

90

Housed Switches – 32A Complete with Fuses • Exceeds the requirements of EN 60947-3• All terminals supplied with cable clamps• Full withstand duty• 80kA rms fused short-circuit capacity• 415V ac rated voltage• Supplied with fuse links• AC23A utilisation category• IP4X Ingress Protection

Housed Switches – 63/125A Complete with Fuses • Exceeds the requirements of EN 60947-3• All terminals supplied with lug-fixing screws• Full withstand duty• 80kA rms fused short-circuit capacity• 415V ac rated voltage• Supplied with fuse links• AC23A utilisation category• IP4X Ingress Protection

Housed Switches – 160/200A • Exceeds the requirements of EN 60947-3• All terminals supplied with lug-fixing screws• Full withstand duty• 80kA rms fused short-circuit capacity• 415V ac rated voltage• AC23A utilisation category• IP4X Ingress Protection

32 – HBE3P32N –

Current rating (A) 3-pole cat. no. 3-pole+N cat. no. 4-pole cat. no.

63 HBF3P63N -100 HBF3P100N HBF4P100125 HBF3P125N -

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

160 HBF3P160N -200 HBF3P200N HBF4P200

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

315 HBK3P315N -400 HBL3P400N HBL4P400

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

630 HBN3P630N -800 HBN3P800N HBN4P800

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

Housed Switches – 315/400A • Exceeds the requirements of EN 60947-3• All terminals supplied with lug-fixing screws• Full withstand duty• 80kA rms fused short-circuit capacity• 415V ac rated voltage• AC23A utilisation category• IP4X Ingress Protection

Housed Switches – 630/800A • Exceeds the requirements of EN 60947-3• All terminals supplied with lug-fixing screws• Full withstand duty• 80kA rms fused short-circuit capacity• 415V ac rated voltage• AC23A utilisation category• IP4X Ingress Protection

Not supplied with fuse links.For fuse links see page 53

Not supplied with fuse links.For fuse links see page 53

Not supplied with fuse links.For fuse links see page 53

Page 93: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Accessories for Housed Switches

Cable spreader box 63/125 1 HB125CSB160/200 1 HB200CSB315/400 1 HB400CSB630/800 1 HB800CSB

Solid links (set of 1) 32 2 HEL3263/125 2 HFL63160/200 2 HFL200A315/400 2 HLL400630/800 2 HNL800

Castell* lock mounting kit All – SCLKCastell* lock with key (see note) All 3 FS22-bank auxiliary switch 63/200 4 SAUX2F

315/800 4 SAUX2N4-bank auxiliary switch 63/200 4 SAUX4F

315/800 4 SAUX4N6-bank auxiliary switch 315/800 4 SAUX6N

Description Current Picture Cat. no.rating (A)

Note: Standard symbol DS1, special symbols are available direct from Castell. Quotereference: Castell FS2 - Spigot 9.5mm square x 22.5mm, 65° anti-clockwise to trap key

*Castell is a trademark of Castell Safety International Ltd.

1

2

4

3

Housed Switches Technical Data

Max. current rating (A) = 32 125 200

Rated current (A) 315 400 630 800Frame size K L N NMechanical endurance 8,000 5,000 5,000 3,000Fused s/c current kA rms 80 80 80 80kW @ 415V ac 160 230 330 450Max. cable (mm2)* 185** 300 630 630Terminals M10 M10 4xM8 4xM8

M10 M10 1xM16 1xM16Max cable lug palm width 35 50 80 80Weight (kg) 21 21 37 37

Max. current rating (A) = 400 800

* These figures are for guidance only and are dependent upon lug palm width.** 240mm2 with terminal barriers

Housed Switches Dimensions

32 210 210 220 363 420 263 273 6100 420 263 273 6125 420 263 273 6160 525 315 325 12200 525 315 325 12315 735 420 325 21400 735 420 325 21630 840 630 378 37800 840 630 378 37

Current Height Width Depth over Weightrating (A) (mm) (mm) handle (mm) (kg)

Spreader Box Dimensions

63A-125A 105 263 183 HB125CSB200A 105 315 235 HB200CSB315-400A 210 420 235 HB400CSB630-800A 210 630 288 HB800CSB

Current Height Width Depth over Weightrating (A) (mm) (mm) handle (mm) (kg)

All dimensions in mm

91

Rated current (A) 32 63 100 125 160 200Frame size E F F F F FMechanical endurance 10,000 10,000 10,000 8,000 8,000 8,000Fused s/c current kA rms 80 80 80 80 80 80kW @ 415V ac 15 30 55 75 90 110Max. cable (mm2)* 10 70 70 70 150 150Terminals Clamp type M8 M8 M8 M8 M8Max cable lug palm width – 22 22 22 22 22Weight (kg) 3 6 6 6 12 12

32A Top and Bottom KnockOut Dimensions

63 - 125A Top and BottomKnock Out Dimensions

630-800A Loadswitch Terminal

Page 94: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

92

63 SF3P63N SF4P63

100 SF3P100N SF4P100

125 SF3P125N SF4P125

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

160 SF3P160N SF4P160

200 SF3P200N SF4P200

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

315 SK3P315N SK4P315

400 SL3P400N SL4P400

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

630 SN3P630N SN4P630

800 SN3P800N SN4P800

Current rating (A) 3-pole+N cat. no. 4-pole cat. no.

Skeleton Switches – 63/125A • Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

Skeleton Switches – 160/200A • Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

Skeleton Switches – 315/400A • Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

Skeleton Switches – 630/800A • Exceeds the requirements of EN 60947-3• 80kA rms fused short-circuit capacity• AC23A utilisation category• Full uninterrupted duty• 415V ac rated voltage

Page 95: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

93

2

13

4

5

6

Accessories for Skeleton Switches

Cable extension terminals (set of 8) 630/800 – SNCET

Solid links (set of 1) 63 1 HFL63

100/200 1 HFL200A

315/400 1 HLL400

630/800 1 HNL800

2-bank auxiliary switch 63/200 3 SAUX2F

315/800 3 SAUX2N

4-bank auxiliary switch 63/200 3 SAUX4F

315/800 3 SAUX4N

6-bank auxiliary switch 315/800 3 SAUX6N

Castell* lock mounting kit

(standard symbol DS1 – see note) All – SCLK

Castell* lock with key 32/800 2 FS2

Handle assembly for:

E frame – 5 SHA1

F frame – 5 SHA2

K + L frame – 5 SHA3

KL+N frame – 5 SHA4

Shaft extensions 63A - 200A 4 SXT127for panel depth 270mm 315A - 800A 4 SXT227

Shaft extensions 63A - 200A 4 SXT160for panel depth 600mm 315A - 800A 4 SXT260

Terminal shrouds 160/200 – SFTSL (recommended for cable sizes above 70mm)

63/200 – SFTSS

315 – SKTS

400 – SLTS

630/800 – SNTS

Terminal barriers (set of 3) 63/200 – SFTB

315 – SKTB

400 – SLTB

630/800 – Supplied

Fuse shrouds (set of 3) 63/125 – SFFS125

160/200 – SFFS200

315 – SKFS

400 – SLFS

630/800 – SNFS

Rating label (strip of 8) 63 6 SRLB63

100 6 SRLB100

125 6 SRLB125

160 6 SRLB160

200 6 SRLB200

315 6 SRLB315

400 6 SRLB400

630 6 SRLB630

800 6 SRLB800

Description Current Picture Cat. no.rating (A)

Note: Special symbols are available direct from Castell. Quote reference: Castell FS2 - Spigot 9.5mm square x 22.5mm, 65˚ anti clockwiseto trap key.

*Castell is a trademark of Castell Safety International Ltd.

Page 96: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

94

Skeleton Switches Technical Data

* These figures are for guidance only and are dependent upon lug palm width** 240mm2 with terminal barriers*** Only with cable extension terminals (SNCET)

F 63A 2.5 2.7

F 100-125A 2.5 2.7

F 160-200A 6.0 6.2

K 315A 7.0 7.2

L 400A 8.5 8.7

N 630-800A 16.5 16.7

Frame Size Weight (kg)3-pole+N 4-pole

Skeleton Switches Frame Weights

Rated current (A) 63 100 125 160 200

Frame size F F F F F

Mechanical endurance 10,000 10,000 8,000 8,000 8,000

Fused s/c current kA rms 80 80 80 80 80

kW @ 415V ac 30 55 75 90 110

Max. cable (mm2)* 70 70 70 150 150

Terminals M8 M8 M8 M8 M8

Max cable lug palm width 22 22 22 22 22

Weight (kg) 6 6 6 12 12

Max. current rating (A) = 125 200

Rated current (A) 315 400 630 800

Frame size K L N N

Mechanical endurance 8,000 5,000 5,000 3,000

Fused s/c current kA rms 80 80 80 80

kW @ 415V ac 160 230 330 450

Max. cable (mm2)* 185** 300 630 630

Terminals M12 M12 4xM8*** 4xM8***

M12 M12 1xM16*** 1xM16***

Max cable lug palm width 35 50 80 80

Weight (kg) 21 21 37 37

Max. current rating (A) = 400 800

Page 97: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

95

F 63A 80 135 170 186 270 35 140 150 165 50 73 N/A 30 80 160 161 3 M5 170* M8 20F100-125A 80 135 170 186 270 35 140 150 165 50 94 N/A 30 80 160 161 3 M5 170* M8 20

F 160-200A 80 135 170 186 300 35 140 150 165 50 94 N/A 30 80 196 197 3 M5 220 M8 20

K 315A 60 180 220 250 384 52.5 210 225 235 90 111 N/A 45 87 210 212 5 M5 220 M12 35

L 400A 60 180 220 250 414 70 280 295 305 125 111 N/A 45 87 210 212 5 M5 220 M12 50

N 630-800A 100 180 235 255 534 105 420 460 475 195 133 184 60 129 240 242 5 M6 270 M12 80

Dimensions

Frame A B C D E F G H I J K L M N O P Q W X Y Z

63 A3, A2 TIS, TIA GTIA TIS. TIA BAO, AAO SB4, SB3

100 A4 (DIA 33 Max) TCP - CEO SD5

125 As A4 TFP TFP DEO, CEO SD6. SD5

160 As A4 (DIA 38 max) TFP TFP DEO, CEO SD6. SD5

200 As A4 (DIA 38 max) TFP TFP DEO, CEO SD6. SD5

400 B4, B3, B2, B1 TMF, TFK, TF, TC TMF, TFK, TF, TC ED, DD, CD SF8, SF7, SF6, SF5

600 C2, C1 TTM, TM TTM, TM FF, EF SH9, SH8

800 C3, C2, C1 TLM, TTM, TM TLM, TTM, TM GF, FF, EF SH10, SH9, SH8

Current rating (A) BS88 Reference Lawson GEC Bussman MEM Paramount

Fuse Data

Skeleton Switches Dimensions 630/800A standard terminal

* Supplied suitable for an ‘X’ dimension of 220mm, the drive shaft can be cut to give a minimum ‘X’ dimension of 170mm.

630/800A extensionterminal (accessory)

Page 98: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

96

Switch Disconnectors in IP65 Insulated Enclosures • Exceeds the requirements of EN 60947-3• Padlockable handle• Rotary handle accepts three padlocks• Terminals accept large cables• Includes earth and neutral terminals• IP65 Ingress Protection

16 PS16NY25 PS25NY32 PS32NY40 PS40NY63 PS63NY80 PS80NY100 PS100NY125 PS125NY

Current rating (A) 3-pole cat. no.

Rated insulation voltage Ui (V) 800 800 800 800 800 800 800 800Dielectric strength (kV) 50 Hz 1 min 3 3 3 3 3 3 3 3Shock resistance Uimp (kV) 8 8 8 8 8 8 8 8 Operational current Ie (A)415V ac – AC21A/AC21B 16 25 32 40 63 80 100 125AC22A/AC22B 16 25 32 40 63 80 100 125AC23A/AC23B 16 25 32 40 63 80 80 80500V ac – AC21A/AC21B 16 25 32 40 63 80 100 125AC22A/AC22B 16 25 32 40 63 80 100 125AC23A/AC23B 16 25 32 40 40 63 63 63690V ac – AC20A/AC20B 16 25 32 40 63 80 100 125AC21A/AC21B 16 25 32 40 63 80 100 125AC22A/AC22B 16 25 32 40 63 80 100 100AC23A/AC23B 16 25 25 25 25 50 50 50Motor power (kW) AC23415V ac 7.5 9 11 11 15 22 37 40500V ac 7.5 9 11 15 18.5 30 37 37690V ac 11 11 11 18.5 18.5 30 30 30Overload capacity at 415V acFuse rating 16 25 32 40 63/40 80 100 125Short-circuit current with fuses (kA rms) 50 50 50 50 20/50 25 25 11Asymmetric short time ratingcurrent (kA peak) 6 6 6 6 6 9 9 9Admissible short time current 1s (kA rms) 1.26 1.26 1.26 1.26 1.26 1.5 1.5 1.5Making and breaking characteristicsBreaking capacity (A rms) 415V AC23A 128 200 256 320 504 640 640 640Making capacity (A rms) 415V AC23A 160 250 320 400 630 800 800 800WithstandMechanical (number of operations) x 1000 100 100 100 100 100 30 30 30Electrical (no. of operations at 415VAC23A) x 1000 3 3 3 3 3 1.5 1.5 1.5ConnectionMaximum Cu cable section (mm2) 16 16 16 16 16 50 50 50Using stranded cable (mm2) 25 25 25 25 25 – – –

Current rating (A) 16 25 32 40 63 80 100 125

Technical Data for Disconnectors in IP65 Insulated Enclosures

Dimensions

16 133 86 104 0.3625 133 86 104 0.3632 175 125 136 0.7540 175 125 136 0.7563 300 200 168 1.8280 400 300 168 2.74100 400 300 168 2.74125 400 300 168 2.74

Current Height Width Depth over Weightrating (A) (mm) (mm) handle (mm) (kg)

Page 99: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

7Section

Dorman Smith Circuit Protection and Modular Devicesand General Purpose Enclosures

Page 100: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

98

Circuit Protection Devices

10kA MCBs • Exceeds the requirements of EN 60898• 10kA rated breaking capacity• Contact position indicator• 35mm2 cable capacity• Multiples of 17.5mm width

6 K1PB06 K1PC06 K1PD06

10 K1PB10 K1PC10 K1PD10

13 K1PB13 K1PC13 N/A

16 K1PB16 K1PC16 K1PD16

20 K1PB20 K1PC20 K1PD20

25 K1PB25 K1PC25 K1PD25

32 K1PB32 K1PC32 K1PD32

40 K1PB40 K1PC40 K1PD40

50 K1PB50 K1PC50 K1PD50

63 K1PB63 K1PC63 K1PD63

Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Single-pole MCBs

6 K2PB06 K2PC06 K2PD06

10 K2PB10 K2PC10 K2PD10

13 N/A N/A N/A

16 K2PB16 K2PC16 K2PD16

20 K2PB20 K2PC20 K2PD20

25 K2PB25 X2PC25 K2PD25

32 K2PB32 K2PC32 K2PD32

40 K2PB40 K2PC40 K2PD40

50 K2PB50 K2PC50 K2PD50

63 K2PB63 K2PC63 K2PD63

Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Double-pole MCBs

6 K3PB06 K3PC06 K3PD06

10 K3PB10 K3PC10 K3PD10

13 N/A N/A N/A

16 K3PB16 K3PC16 K3PD16

20 K3PB20 K3PC20 K3PD20

25 K3PB25 K3PC25 K3PD25

32 K3PB32 K3PC32 K3PD32

40 K3PB40 K3PC40 K3PD40

50 K3PB50 K3PC50 K3PD50

63 K3PB63 K3PC63 K3PD63

Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Triple-pole MCBs

Page 101: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

99

6 X4PB06 X4PC06 X4PD06

10 X4PB10 X4PC10 X4PD10

13 X4PB13 X4PC13 X4PD13

16 X4PB16 X4PC16 X4PD16

20 X4PB20 X4PC20 X4PD20

25 X4PB25 X4PC25 X4PD25

32 X4PB32 X4PC32 X4PD32

40 X4PB40 X4PC40 X4PD40

50 X4PB50 X4PC50 X4PD50

63 X4PB63 X4PC63 X4PD63

Current rating (A) B type cat. no. C type cat. no. D type cat. no.

Current rating (A) B type cat. no. C type cat. no.

Four-pole MCBs

6 30 GR1PB0630 GR1PC0630

10 30 GR1PB1030 GR1PC1030

16 30 GR1PB1630 GR1PC1630

20 30 GR1PB2030 GR1PC2030

32 30 GR1PB3230 GR1PC3230

40 30 GR1PB4030 GR1PC4030

50 30 GR1PB5030 GR1PC5030

6 100 - GR1PC06100

10 100 - GR1PC10100

16 100 - GR1PC16100

20 100 - GR1PC20100

32 100 - GR1PC32100

40 100 - GR1PC40100

Current rating (A) Sensitivity B type cat. no. C type cat. no.

RCBOs

6kA – Single-pole MCBs• Exceeds the requirements of EN 60898• 6kA rated breaking capacity• Contact position indicator• 25mm2 cable capacity

6 S1PB06 S1PC06

10 S1PB10 S1PC10

16 S1PB16 S1PC16

20 S1PB20 S1PC20

32 S1PB32 S1PC32

40 S1PB40 S1PC40

50 S1PB50 S1PC50

63 S1PB63 S1PC63

Page 102: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

100

80 X1PB80 X1PC80100 K1PB100 K1PC100125 X1PB125 X1PC125

Current rating (A) B type cat. no. C type cat. no.

High Current MCBs • Exceeds the requirements of EN 60898• 10kA rated breaking capacity• Contact position indicator• 35mm2 cable capacity• Multiples of 27mm widths

Single-pole MCBs

80 X2PB80 X2PC80100 K2PB100 K2PC100125 X2PB125 X2PC125

Current rating (A) B type cat. no. C type cat. no.

Double-pole MCBs

80 X3PB80 X3PC80100 K3PB100 K3PC100125 X3PB125 X3PC125

Current rating (A) B type cat. no. C type cat. no.

Triple-pole MCBs

80 X4PB80 X4PC80100 X4PB100 X4PC100125 X4PB125 X4PC125

Current rating (A) B type cat. no. C type cat. no.

Four-pole MCBs

MCB auxiliary contact (one changeover contact) XAC2MCB signal/auxiliary contact (one changeover contact) XCS2MCB shunt trip (110-415V ac, 110-125V dc) XST415MCB shunt trip (12-48V ac/dc) XST48MCB under-voltage release (240V ac - time delay adjustable 0-300mS) XUVR240

PadlockingMCB dolly locking device XDLPadlock for dolly locking device XPL

Auxiliary equipment Cat. no.

Accessories for 10kA MCBs and RCBOs

Note: Not suitable for use within Loadlimiter 63 distribution board

Page 103: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

101

Double-pole RCCBs • Exceeds the requirements of EN 61008• Equipped with transient suppression filter• Voltage 230/400V 50/60Hz• Double width module, 35mm• Type AC• Terminal capacity: top 25mm2

• Terminal capacity: bottom 35mm2

Four-pole RCCBs • Exceeds the requirements of EN 61008• Equipped with transient suppression filter• Voltage 230/400V 50/60Hz• Quad width module, 70mm• Type AC• Terminal capacity: top 25mm2

• Terminal capacity: bottom 35mm2

25 30 AC LLM25/30/2

40 30 AC LLM40/30/2

40 100 AC LLM40/100/2

63 30 AC LLM63/30/2

63 100 AC LLM63/100/2

63 300 AC LLM63/300/2

80 30 AC LLM80/30/2

100 30 AC LLM100/30/2

100 100 AC LLM100/100/2

80, time delay 100 A LLMA-S80/100/2

100, time delay 100 A LLMA-S100/100/2

Current rating (A) Sensitivity (mA) Type Cat. no.

40 30 AC LLM40/30/4

40 100 AC LLM40/100/4

40 300 AC LLM40/300/4

63 30 AC LLM63/30/4

63 100 AC LLM63/100/4

63 300 AC LLM63/300/4

100 30 AC LLM100/30/4

100 100 AC LLM100/100/4

100 300 AC LLM100/300/4

100 300 A LLMA100/300/4

100, time delay 100 A LLMA-S100/100/4

Current rating (A) Sensitivity (mA) Type Cat. no.

Time delay RCCB fixed 200ms

Time delay RCCB fixed 200ms

Page 104: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

102

YA2 3-pole front shield blank LBYA2BP3PYA2 cable clamps 1.5 - 70mm2 (set of 3) YA2CC3PYA2 cable clamps 1.5 - 70mm2 (set of 4) YA2CC4PYA2 1-pole terminal shroud YA2TS1PYA2 3-pole terminal shroud (pic 1) YA2TS3PYA3 4-pole terminal shroud YA2TS4PMotor actuator 100-110V ac YA2MA110YA2 dolly lock YADL1YA2 neutral link YA2NLMotor actuator 200-240V ac YA2MA240Extension terminalsYA2 flat extension terminals (set of 3) YA2XT3PYA2 flat extension terminals (set of 4) YA2XT4PRotary handlesYA2 door mounted rotary handle IP54 270mm panel depth YA2RH1YA2 door mounted rotary handle IP54 STD panel depth YA2RH2Plug-in basesYA2 plug-in base IP20 for 3-pole YA2PB3PYA2 plug-in base IP20 for 4-pole YA2PB4PYA2 plug-in base front/rear extension terminals 3 off YA2PFT3PYA2 plug-in base front/rear extension terminals 4 off YA2PFT4PYA2 plug-in conversion for 3-pole YA2PT3PYA2 plug-in conversion for 4-pole YA2PT4PYA2 terminal cover for plug-in/rear, 3-pole YA2TC3PYA2 terminal cover for plug-in/rear, 4-pole YA2TC4P

Description Cat. no.

YA2 Frame MCCBs • Exceeds EN60947-2 • Rated insulation voltage is 800V ac (Ui)• Triple and four-pole MCCBs have both adjustable overload and instantaneous trips• Standard M8 cable lug termination = 35mm2

• Maximum cable termination = 95mm2 (using M8 reduced palm width lugs)

16 YA2N1P16T N/A N/A20 YA2N1P20T YA2N3P20T YA2N4P20T 32 YA2N1P32T YA2N3P32T YA2N4P32T 50 YA2N1P50T YA2N3P50T YA2N4P50T 63 YA2N1P63T YA2N3P63T YA2N4P63T80 YA2N1P80T - -100 YA2N1P100T YA2N3P100T YA2N4P100T 125 YA2N1P125T YA2N3P125T YA2N4P125T

Current rating (A) 1-pole cat. no. 3-pole cat. no. 4-pole cat. no.

YA2 Frame MCCB Thermal/Magnetic – Icu 25kA

50 YA2S3P50T YA2S4P50T 63 YA2S3P63T YA2S4P63T 100 YA2S3P100T YA2S4P100T 125 YA2S3P125T YA2S4P125T

Current rating (A) 3-pole cat. no. 4-pole cat. no.

YA2 Frame MCCB Thermal/Magnetic – Icu 36kA

20 YA2J3P20T YA2J4P20T 32 YA2J3P32T YA2J4P32T 50 YA2J3P50T YA2J4P50T 63 YA2J3P63T YA2J4P63T 100 YA2J3P100T YA2J4P100T 125 YA2J3P125T YA2J4P125T

Current rating (A) 3-pole cat. no. 4-pole cat. no.

YA2 Frame MCCB Thermal/Magnetic – Icu 65kA

YA2 Frame Accessories

Note: Shunt trips, UVT, auxiliariesswitches, alarm switches - seecommon accessories page 127.

1

Page 105: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

103

YA3 Frame MCCBs• Exceeds EN 60947-2 requirements • Triple and four-pole MCCBs have both adjustable overload and instantaneous trips• Rated insulation voltage 800V ac (Ui)• Standard M8 cable lug termination = 95mm2

• Maximum cable termination = 150mm2 (using M8 reduced palm width lugs)

250 YA3B3P250D YA3B4P250D

Current rating (A) 3-pole cat. no. 4-pole cat. no.

YA3 Switch Disconnector

16 16 YA3N1P16T - -

20 13 YA3N1P20T YA3N3P20T YA3N4P20T

32 20 YA3N1P32T YA3N3P32T YA3N4P32T

40 25 YA3N1P40T - -

50 32 YA3N1P50T YA3N3P50T YA3N4P50T

63 40 YA3N1P63T YA3N3P63T YA3N4P63T

80 50 YA3N1P80T - -

100 63 YA3N1P100T YA3N3P100T YA3N4P100T

125 80 YA3N1P125T YA3N3P125T YA3N4P125T

160 100 YA3N1P160T YA3N3P160T YA3N4P160T

200 125 - YA3N3P200T YA3N4P200T

250 160 - YA3N3P250T YA3N4P250T

Current rating (A) 1-pole cat. no. 3-pole cat. no. 4-pole cat. no.

Max. Min.

YA2 Frame MCCB Thermal/Magnetic – Icu 25kA

50 32 YA3S3P50T YA3S4P50T

63 40 YA3S3P63T YA3S4P63T

100 63 YA3S3P100T YA3S4P100T

125 80 YA3S3P125T YA3S4P125T

160 100 YA3S3P160T YA3S4P160T

200 125 YA3S3P200T YA3S4P200T

250 160 YA3S3P250T YA3S4P250T

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

YA3 Frame MCCB Thermal/Magnetic – Icu 36kA

50 32 YA3J3P50T YA3JP50T

63 40 YA3J3P63T YA34J63T

100 63 YA3J3P100T YA34J100T

125 80 YA3J3P125T YA34J125T

160 100 YA3J3P160T YA34J160T

200 125 YA3J3P200T YA34J200T

250 160 YA3J3P250T YA34J250T

YA3 Frame MCCB Thermal/Magnetic – Icu 65kA

Page 106: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

104

Neutral LinkFor use with YA3-frame MCCBs in GP boxes and Loadbank panel boardincoming enclosures.

Terminal covers 3-poleYA3 frame interphase barriers (set of 1) YA3TBYA3 frame long terminal shroud (set of 1) YA3TS3PYA3 frame short terminal shroud (set of 1) YA3TS3PSTerminations 3-poleYA3 frame cable clamps 35 - 120mm2 (set of 3) YA3CC3PTerminal covers 4-poleYA3 frame long terminal shroud (set of 1) YA3TS4PYA3 frame short terminal shroud (set of 1) YA3TS4PSTerminations 4-poleYA3 frame cable clamps 35 - 120mm2 (set of 4) YA3CC4PShunt trips**YA frame shunt trip 100-120V ac YAST115AC**YA frame shunt trip 200-240V ac YAST240AC**YA frame shunt trip 380-450V ac YAST450AC**YA frame shunt trip 24V dc YAST24DCAuxiliary and alarm switches**YA frame 1AB auxiliary switch YAAUX1**YA frame alarm switch YAALUnder-voltage release**YA frame under-voltage release 100-120V ac YAUVR120AC**YA frame under-voltage release 200-240V ac YAUVR240AC**YA frame under-voltage release 380-450V ac YAUVR450AC**YA frame under-voltage release 24V dc YAUVR24DCMotor actuatorsMotor actuator 100-110V ac YA3MA110Motor actuator 200-240V ac YA3MA240Locking devicesYA frame dolly padlock device YADL1YA frame Castell* mounting kit YACLExtension terminalsYA3 flat extension terminals (set of 3) YA3XT3PYA3 flat extension terminals (set of 4) YA3XT4PRotary handlesYA3 door mounted rotary handle IP54 270mm panel depth YA3RH1YA3 door mounted rotary handle IP54 STD panel depth YA3RH2Plug-in basesYA3 plug-in base IP20 for 3-pole YA3PB3PYA3 plug-in base IP20 for 4-pole YA3PB4PYA3 plug-in base front/rear extension terminals 3 off YA3PFT3PYA3 plug-in base front/rear extension terminals 4 off YA3PFT4PYA3 plug-in conversion for 3-pole YA3PT3PYA3 plug-in conversion for 4-pole YA3PT4PYA3 terminal cover for plug-in/rear, 3-pole YA3TC3PYA3 terminal cover for plug-in/rear, 4-pole YA3TC4P

Description Cat. no.

YA3 neutral link YA3NL

Description Cat. no.

Adapter Kit AA Frame to YA3 FrameFor use when replacing existing AA frame with YA3 MCCBs.

Loadbank panel board 1 YAA1PLB

Loadbank panel board 3 YAA3PLB

Type 2 Loadframe switchboard 3 YAA3PLFT2

Description – for AA frame kit Poles Cat. no.

YA3 Frame MCCB Accessories

** Common to all YA2, YA3, YA5 MCCBs.

*Castell is a trademark of Castell Safety International Ltd.

Page 107: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

105

YA5 Frame MCCBs

• Exceeds EN60947-2 requirements• Triple and four-pole MCCBs have both adjustable overload and instantaneous trips• Rated insulation voltage 800V ac (Ui)• Electronic MCCBs are Category B rated for discrimination• No extension terminal bars supplied, see ‘Accessories’ if required• Standard M10 cable lug termination = 95mm2

• Maximum cable termination = 185mm2 (using M10 reduced palm width lugs)

400 YA5B3P400D YA5B4P400D

Current rating (A) 3-pole cat. no. 4-pole cat. no.

YA5 Switch Disconnector

250 157 YA5N3P250T YA5N4P250T

400 252 YA5N3P400T YA5N4P400T

YA5 Frame MCCB Thermal/Magnetic – Icu 25kA

250 157 YA5H3P250T YA5H4P250T

400 252 YA5H3P400T YA5H4P400T

YA5 Frame MCCB Thermal/Magnetic – Icu 50kA

250 157 YA5J3P250T YA5J4P250T

400 252 YA5J3P400T YA5J4P400T

YA5 Frame MCCB Thermal/Magnetic – Icu 65kA

250 125 YA5K3P250E YA5K4P250E

400 200 YA5K3P400E YA5K4P400E

YA5 Frame MCCB Electronic – Icu 70kA

YA5 Frame MCCB Accessories

Motor actuator 100-110V ac YA5MA110

Motor actuator 200-240V ac YA5MA240

YA5 interphase barrier (set of 1) YA5TB

YA5 cable clamps (set of 3) YA5CC3P

YA5 cable clamps (set of 4) YA5CC4P

YA5 3-pole terminal shroud YA5TS3P

YA5 dolly lock YA5DL

Description Cat. no.

Note: Shunt trips, UVT and auxiliaries - see common accessories page 104.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Page 108: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

106

Y6 Frame MCCBs

Y6 Frame MCCBs Thermal/Magnetic• Exceeds the requirements of EN 60947-2• Rated insulation voltage 690V ac (Ui)• Electronic MCCBs have adjustable long, short and instantaneous trip functions• Electronic MCCBs are Category B rated for discrimination• Standard M12 cable termination = 240mm2

630 Y6B3P630D Y6B4P630D

800 Y6B3P800D Y6B4P800D

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Y6 Frame Switch Disconnector

400 250 Y6H3P400T5 Y6H4P400T5

630 400 Y6H3P630T5 Y6H4P630T5

800 500 Y6H3P800T5 Y6H4P800T5

Y6 Frame MCCB Thermal/Magnetic – Icu 50kA

400 250 Y6K3P400T5 Y6K4P400T5

630 400 Y6K3P630T5 Y6K4P630T5

800 500 Y6K3P800T5 Y6K4P800T5

Y6 Frame MCCB Thermal/Magnetic – Icu 85kA

630 315 Y6H3P630E Y6H4P630E

800 400 Y6H3P800E Y6H4P800E

Y6 Frame MCCB Electronic – Icu 50kA

630 315 Y6J3P630E Y6J4P630E

800 400 Y6J3P800E Y6J4P800E

Y6 Frame MCCB Electronic – Icu 65kA

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Page 109: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

107

Y6 Frame Accessories

Terminal covers 3-poleTerminal shroud (set of 1) Y6TS3P

Terminal cover Y6TC3P

Interphase barriers (set of 2) Y5TB3P

Terminal covers 4-poleTerminal shroud (set of 1) Y6TS4P

Terminal cover Y6TC4P

Interphase barriers (set of 3) Y5TB4P

Terminations 3-poleCable clamps 240mm2 or 2x120mm2 (set of 3) Y6CC3P

Extension terminal bars Y6XT3P

Terminations 4-poleCable clamps 240mm2 or 2x120mm2 (set of 4) Y6CC4P

Extension terminal bars Y6XT4P

Locking devicesDolly padlock device Y6DL

Castell* lock (DS1 direct mounting) Y6CLDS1

Castell* lock (door mounted) Y5DCL

Castell* lock door-mounted cam for shaft only Y5DCLCAM

Shunt tripsShunt 100-120V ac Y6ST115AC

Shunt 200-480V ac Y6ST480AC

Shunt 24V dc Y6ST24DC

Under-voltage releaseUVR 100-120V ac Y6UVR120AC

UVR 200-240V ac Y6UVR240AC

UVR 380-450V ac Y6UVR450AC

UVR 24V dc Y6UVR24DC

Motor actuatorsMotor actuator 100-110V ac Y6MA110

Motor actuator 200-240V ac Y6MA240

Auxiliary switches

1AB auxiliary switch Y6AUX1

2AB auxiliary switch Y6AUX2

Alarm switch + 1 auxiliary Y6AUXAL

Neutral linkY6 neutral link Y6NL

Description Cat. no.

*Castell is a trademark of Castell Safety International Ltd.

Page 110: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

108

Y7 Frame Accessories

Terminal covers 3-poleTerminal shroud (set of 1) Y7TS3P

Interphase barriers (set of 2) Y5TB3P

Terminal covers 4-poleTerminal shroud (set of 1) Y7TS4P

Interphase barriers (set of 3) Y5TB4P

Locking devicesDolly padlock device Y7DL

Castell* lock (DS1 direct mounting) Y7CL

Castell* lock (door mounted) Y5DCL

Castell* lock door-mounted cam for shaft only Y5DCLCAM

Shunt tripsShunt 100-120V ac Y7ST115AC

Shunt 200-480V ac Y7ST480AC

Shunt 24V dc Y7ST24DC

Under-voltage releaseUVR 100-120V ac Y7UVR120AC

UVR 200-240V ac Y7UVR240AC

UVR 380-450V ac Y7UVR450AC

UVR 24V dc Y7UVR24DC

Motor actuatorsMotor actuator 100-110V ac Y7MA110

Motor actuator 200-240V ac Y7MA240

Auxiliary switches 3-pole MCCB1AB auxiliary switch Y7AUX3P1

2AB auxiliary switch Y7AUX3P2

Alarm switch + 1 auxiliary Y7AUX3PAL

Auxiliary switches 4-pole MCCB

1AB auxiliary switch Y7AUX4P1

2AB auxiliary switch Y7AUX4P2

Alarm switch + 1 auxiliary Y7AUX4PAL

Neutral linkY7 neutral link Y7NL

Description Cat. no.

Y7 Frame MCCBs

• Exceeds EN 60947-2 requirements • Rated insulation voltage 690V ac (Ui)• Electronic MCCBs have adjustable long, short and instantaneous trip functions• Electronic MCCBs are Category B rated for discrimination

1000 Y7B3P1000D Y7B4P1000D

1250 Y7B3P1250D Y7B4P1250D

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Y7 Frame Switch Disconnector

1000 500 Y7J3P1000E Y7J4P1000E

1250 630 Y7J3P1250E Y7J4P1250E

Y7 Frame MCCB Electronic – Icu 65kA

*Castell is a trademark of Castell Safety International Ltd.

Current rating (A) 3-pole cat. no. 4-pole cat. no.

Max. Min.

Page 111: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

109

Y8 Frame MCCBs

• Exceeds EN 60947-2 requirements• Rated insulation voltage 690V ac (Ui)• Electronic MCCBs have adjustable long, short and instantaneous trip functions• Electronic MCCBs are Category B rated for discrimination

1600 Front terminals Y8B3P1600D Y8B4P1600D

1600 Rear terminals Y8B3P1600DR -

1600 Drawout Y8B3P1600DDO -

Current rating (A) Type 3-pole cat. no. 4-pole cat. no.

Y8 Frame Switch Disconnectors

1600 Front terminals Y8K3P1600E Y8K4P1600E

1600 Rear terminals Y8K3P1600ER N/A

1600 Ground fault Y8K3P1600EG N/A

Current rating (A) Type 3-pole cat. no. 4-pole cat. no.

Y8 Frame MCCB Electronic – Icu 85kA

Y8 Frame Accessories

Terminal covers 3-poleTerminal shroud (set of 1) Y7TS3P

Interphase barriers (set of 2) Y5TB3P

Terminal covers 4-poleTerminal shroud (set of 1) Y7TS4P

Interphase barriers (set of 3) Y5TB4P

Locking devicesDolly padlock device Y7DL

Castell* lock (DS1 direct mounting) Y7CL

Castell* lock (door mounted) Y5DCL

Castell* lock door-mounted cam for shaft only Y5DCLCAM

Shunt tripsShunt 100-120V ac Y7ST115AC

Shunt 200-480V ac Y7ST480AC

Shunt 24V dc Y7ST24DC

Under-voltage releaseUVR 100-120V ac Y7UVR120AC

UVR 200-240V ac Y7UVR240AC

UVR 380-450V ac Y7UVR450AC

UVR 24V dc Y7UVR24DC

Motor actuatorsMotor actuator 100-110V ac Y7MA110

Motor actuator 200-240V ac Y7MA240

Auxiliary switches 3-pole MCCB1AB auxiliary switch Y7AUX3P1

2AB auxiliary switch Y7AUX3P2

Alarm switch + 1 auxiliary Y7AUX3PAL

Auxiliary switches 4-pole MCCB1AB auxiliary switch Y7AUX4P1

2AB auxiliary switch Y7AUX4P2

Alarm switch + 1 auxiliary Y7AUX4PAL

Neutral linkY7 neutral link Y7NL

Description Cat. no.

*Castell is a trademark of Castell Safety International Ltd.

Page 112: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

110

10 LM10 - -

20 LM20 LM2P20 LM3P20

30 LM30 - LM3P30

40 LM40 - -

50 LM50 - -

60 LM60 - -

Current rating (A) 1-pole cat. no. 2-pole cat. no. 3-pole cat. no.

Loadmaster MCBs

100 - LW2 LW3

Current rating (A) 1-pole cat. no. 2-pole cat. no. 3-pole cat. no.

Loadmaster Isolators

Loadmaster Accessories

Mounting bracket for MCB/isolator 2-pole LMMB2

Mounting bracket for MCB/isolator 3-pole LMMB3

Description Cat. no.

Page 113: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

111

Modular Devices

Transient Voltage Surge Suppression (TVSS) • Module DIN-rail mounted device comprising of base and protection unit• Plug-in surge protection modules• Integral protection status indicator as standard• Thermal and current overload fusing• Operating range 200-300V rms max• ‘Hot working’ replaceable modules

Distribution Surge Protectors (Internal Mounting)• Two stage (redundant) protection• Full protection status indicators• Site fault indicator• Remote signalling

Modular Distribution Surge Protectors (External Mounting) • Two stage (redundant) protection• Replaceable DIN-rail modules• Dual overload fusing• Status indication• Site fault indicator• Remote signalling

40kA MOV 1-phase TVSS module A1SPM/40/230

40kA MOV 1-phase with neutral/earth TVSS module A1SPM/40/230N

40kA MOV 3-phase TVSS module A3SPM/40/230

40kA MOV 3-phase with neutral/earth TVSS module A3SPM/40/230N

Accessories40kA MOV replacement plug-in SPM SPM/40/230

40KA MOV neutral/earth replacement plug-in SPM SPM/NE/40/230

Device type Cat. no.

Basic 30kA 2-stage 3-phase surge protector DSP3/600/BOW

30kA 2-stage 3-phase surge protector with visual faultindication and terminals for remote status monitoring DSP3N/600/BOW

30kA 2-stage 3-phase surge protector with visual faultindication and terminals for remote status monitoringand 1m cable plug-in display unit DSP3L/600/BOW

Optional enclosure for above units 2IP-7-0244

Device type Cat. no.

90kA 3-phase assembly DSP3/600/BOW

150kA 3-phase assembly MDSP3/150

90kA line replacement module DSPM/90/230R

90kA neutral/earth replacement module DSPM/90/230NR

150kA line replacement module DSPM/150/230R

150kA neutral/earth replacement module DSPM/150/230NR

Device type Cat. no.

Note: It is recommended that SPM surge protectors are installed on the load side of a MCB - type C, MCCB or a fused disconnector 63A to provide isolationand protection.

Note: DSP600 surge protectors should be installed as close as possible andsupplied with 63A MCB - type C or a HRC fused switch to provide isolation and protection

Page 114: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

112

63 2 50 AV26363 3 50 AV36363 4 50 AV463100 2 50 AV2100100 3 50 AV3100100 4 50 AV4100125 2 50 AV2125125 3 50 AV3125125 4 50 AV4125

Current rating (A) Poles Max. cable (mm) Cat. no.

Modular Switch Disconnectors

Modular Auxiliary Devices

Switch16 17.5 1 N/O + neon LLM1P16NON16 17.5 2 N/O + neon LLM2P16NON32 17.5 1 N/O + neon LLM1P32NON32 17.5 2 N/O + neon LLM2P32NON16 17.5 1 C/O LLM1P16CO16 17.5 2 C/O LLM2P16CO32 17.5 1 C/O LLM1P32CO32 17.5 2 C/O LLM2P32CO

These devices are not contactors

Pushbutton16 17.5 1 N/O + neon LLMPBNON16 17.5 1 N/O + 1 N/C LLMPBNONC

Indicator- - Lens – red LLMLR*- - Lens – green LLMLG*- - Lens – amber LLMLA*- - Lens – clear LLMLC*- - 40V lamp LLMRL*

16 - Lampholder LLMPL*

Current rating (A) Width (mm) Function Cat. no.

* For complete indicator please order lens, lamp and lamp holder separately

Modular Contactors • Exceeds the requirements of EN 61095• May require de-rating when used with inductive loads

– see Contactor De-rating table in the Technical Applications section

Modular Programmable Timers

16A (AC7A) 1 or 2 channel 35 DRT-DW2R

Current rating (A) Width (mm) Function Cat. no.

20A 17.5 2N/O LLM2P20CO20A 7.5 2N/C LLM2P20CC24A 35 3N/O LLM3P24CO24A 35 2N/O+2N/C LLM4P24COC24A 35 4N/C LLM4P24CC24A 35 4N/O LLM4P24CO40A 54 2N/C LLM2P40CC40A 54 2N/O LLM2P40CO40A 54 3N/O LLM3P40CO40A 54 4N/O LLM4P40CO63A 54 2N/C LLM2P63CC63A 54 2N/O LLM2P63CO63A 54 4N/O LLM4P63COVenting kit * 9 - LLMV

Current rating (A) Width (mm) Contacts Cat. no.

* Ventilation module must be fitted between alternate pairs of contactorsto prevent overheating.

Page 115: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

113

Meters, Current Transformers andWiring Looms

Kilowatt Hour Meter — DIN-rail Mounted • Class 2 accuracy• For nominal 400V, 3 or 4 wire systems• Opto-isolated pulse output• Counter resolution to 1 kWh• LED display of power supply, activity status

Quad module kWh 7 mechanical <100 70 DRK-3PCT-415

Quad module 7 digital >100 70 DRK-3PCT-415-LCDkWh

Device type Counter Pulse Width Cat. no.digits (mS) (mm)

Kilowatt Hour Meter - Panel Mounted - Analogue Display• Class 1.0 accuracy• Wide operating voltage 85-500V• True RMS measurement

3-phase meter with 1 pulse output 6 electro-mechanical KWH-400

Device type Counter digits Cat. no.

Note: Connection kit DBXCK must be ordered to provide the additional DIN-rail neededto mount these devices integral to distribution board below the incoming disconnector.

Integra 1630 Multi-function Meter - Panel Mounted• Low Profile• 0.2 accuracy• LED annuniciators for each measured• True RMS measurement• User programmable system configuration

3-phase meter with 1 pulse output INT-1630-M-5-M-100

3-Phase meter with 1 pulse output and 1 RS485 Modbus output INT-1630-M-5-M-110

Device type Cat. no.

Dintegra 1260 Multi-Function Meter - DIN-rail mounted (6 Module)• 190V–260V ac 50/60Hz• Measures three-phase voltage, current, frequency, Watts, VAr, VA, energy kWh,

power factor, 5-line, 3-digit LED display• Opto-isolated pulse output

3-phase meter with 2 pulse output 106 DRI—1260-210& RS485 Modbus output

Device type Width (mm) Cat. no.

Tegra 710 Multi-function Meter - DIN-rail Mounted (4 module)• Monitors up to 57 parameters • True RMS, 3-phase voltage and current, Hz, CosØ, phase angle, active, reactive

and apparent power, KWh• Optional 2 programmable relay or RS485 Modbus outputs• Selectable VT and CT ratios

3-phase meter with 2 pulse output 70 TEGRA-710-200

Device type Width (mm) Cat. no.

Page 116: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

114

Measuring Current Transformers• For use with kilowatt hour metering• Up to Class 0.5 accuracy • System voltage up to 720V• Secondary output 5A• Operating temperatures from –20°C to +70°C

Kilowatt Hour Meters for Outgoing Circuits• In-built current transformers, direct connected• Single-pole and triple-pole versions• DIN-rail mountable in Loadlimiter service centres• Phase cable hole diameter 12.5mm

100 25 80 50 M53J-100/5D

125 25 80 50 M53J-125/5D

200 25 80 50 M53J-200/5D

250 25 80 50 M53J-250/5D

400 32 94 60 M63N-400/5

600 42 131 90 M93L-600/5

800 63 156 134 MB5D-800/5

Current Cable aperture Height Width Cat. no.rating (A) (mm) (mm) (mm)

63 1 current transformer 54mm DRK-1P-230-D63

100 3 current transformer 126mm DRK-3P-400-D100

Current Function Width Cat. no.

rating (A)

Note: Fitted with integral current transformer(s) as above

M30-DINCLIP DIN-rail mounting clip for DIN-rail mounting option for M63N /M93L current tranformers (2 required)

M50-DINCLIP DIN-rail mounting clip for DIN-rail mounting option for MB5Dcurrent transformers (2 required)

Earth Leakage Relay – DIN-rail Mounted• Precision digital protection relay• Adjustable sensitivity of 30mA to 10A• Adjustable time delay from 0 to 10 seconds• Double-pole relay contacts 8A, 250V• Supply voltage 100-250V ac/dc (50/100Hz)

Core Balanced Current Transformers• For use with ELR1 earth leakage protection relay• Leakage measurement range 0 to 10A• Integral wire-sealable terminal cover• Flame retardant, high impact moulded case

50 100-250 ac/dc ELR1

Frequency (Hz) Auxiliary supply (V) Cat. no.

250 35 100 79 33 CBT-94F-035

630 70 130 110 33 CBT-94F-070

1000 105 170 146 33 CBT-94F-105

1000 140 220 196 33 CBT-94F-140

Current Aperture Width Height Depth Cat. no.rating (A) (mm) (mm) (mm) (mm)

Page 117: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

115

Sheet steel 1 6 225x134x73 1.0 LLMGPS6S

Insulated, IP4X 2 2 130x50x60 0.1 LLMGPI2

Insulated, IP4X 4 130x86x60 0.2 LLMGPI4

Insulated, IP4X 3 8 162x214x92 0.6 LLMGPI8

Insulated, IP55 5 175x125x115 0.5 LLMGPW5

Insulated, IP55 4 8 175x214x115 0.8 LLMGPW8

Construction Picture Number HxWxD Weight Cat. no.of ways (mm) (kg)

General Purpose MCB/Modular Units Enclosures

Sheet steel - surface YA3 687x263x120 16 LLGPYA3

Construction Device HxWxD Weight Cat. no.type (mm) (kg)

General Purpose MCCB Enclosures 16-250A• Accepts all YA3 devices up-to 250A• IP4X rated• Spreading room for 150mm2

Note: LLGPYA3 requires neutral link YA3NL to be ordered separately.

Note: For terminating two cables with YA5 frame please order extension terminals(YA5XT3P) separately.

Sheet steel YA5/6 1060x420x175 16 LLGPYA56

Construction Device HxWxD Weight Cat. no.type (mm) (kg)

General Purpose MCCB Enclosures 400A-800A• Accepts all YA5 & Y6 devices up-to 800A• IP4X• Neutral link included• Spreading room for 240mm2

General Purpose Enclosures1

2

3 4

Page 118: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

116

Page 119: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

8Section

Technical Data & Applications

Page 120: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

118

Page 121: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

119

Technical Data & Applications

Index

Compliance with International Standards 120

Standard Terminology 121

Current Carrying and Switching Devices 123

Miniature Circuit Breakers (MCBs) 126

Residual Current Circuit Breakers (RCCBs) 130

Modular Contactors 132

Moulded Case Circuit Breakers (MCCBs) 136

Motor Starting Applications (MCCBs) 137

Discrimination and Cascading 138

System Sizing and Diversity 144

Prospective Short-circuit Current 145

Earth Fault Protection 148

Forms of Separation 151

Ingress Protection 153

Loadline MCCB Insulation Data 154

Loadline YA2 Frame MCCB Characteristics and Dimensions 155

Loadline YA3 Frame MCCB Characteristics and Dimensions 157

Loadline YA5 Frame MCCB Characteristics and Dimensions 159

Loadline Y6 Frame MCCB Characteristics and Dimensions 160

Loadline Y7 Frame MCCB Characteristics and Dimensions 161

SPM Series – Plug-In Surge Protection Modules and Bases 162

DSP3 - Distribution Surge Protector 600 Series 163

Earth Leakage 164

Page 122: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

120

Compliance with InternationalStandards

Dorman Smith branded products comply with internationally recognised technicaland quality standards to ensure that each product is fully capable of meeting therelevant standard requirements for its intended use.

The design, manufacture, procurement, supply and servicing of Dorman Smithbranded products is also governed by compliance to an international standardthrough the operation of a Quality Management System.

• Quality Management System BS EN ISO 9001:2000

The Institute of Electrical Engineers (IEE) British Standard BS 7671 addressesRequirements for Electrical Installations and dictates that all relevant products mustcomply with applicable British, International or Harmonised Standards according tothe intended installation and application of the equipment. The BS 7671 documentis commonly referred to as ‘The Wiring Regulations’.

Dorman Smith branded products are type tested, manufactured, routinely testedand assembled in accordance and compliance with a number of relevantHarmonised Standards recognised by the electrical industry.

A Harmonised Standard is a European Standard formally presented by theEuropean Committee for Electrotechnical Standardisation, CENELEC, to theEuropean Commission and published in its official journal. These documents aredenoted by the prefix EN (European Norm).

The products listed within this catalogue conform to appropriate electrical andmechanical standards as follows:

• Consumer Units Distribution Boards EN 60439-3• Panel Boards EN 60439-1• MCBs EN 60898• MCCBs EN 60947-2• Switches EN 60947-3• RCCBs EN 61008• RCBOs EN 61009• Contactors EN 61095

In addition to the above, and where appropriate, Dorman Smith branded productsalso comply with the relevant requirements of the standard for protection againstphysical, mechanical and liquid ingress as follows:

• Ingress Protection EN 60529

Page 123: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

121

Standard Terminology

The Harmonised Standard EN 60898 and the IEE Wiring Regulations BS 7671:2001contain references to a set of adopted standard terminology for the principaldevice parameters with regard to MCBs. This terminology is also embraced byother standards with regard to MCCBs and switches (EN60947-2 and EN 60947-3).

The standard terminology relates to the following parameters:

Rated Operational Voltage, Ue

Rated Insulation Voltage, Ui

Rated Current, InRated Short Circuit Capacity, Icn

Rated Service Short Circuit Breaking Capacity, Ics

Rated Ultimate Breaking capacity, Icu

Rated Voltage and Current

Rated Operational Voltage, UeThe nominal voltage of the system should not exceed the stated value of Ue. For example: single-pole Ue = 230/400V, three-pole Ue = 400V.

The standardised values of 230V and 230/400V will progressively replace 240V,220/380V and 240/415V by 2010.

Rated Insulation Voltage, UiThis is the voltage upon which the dielectric properties are based, using tests athigh voltage and mains frequency.

For example: Ui = 690V, tested at 3kVac 50Hz.

Unless otherwise stated, the rated insulation voltage is the value of the maximumrated voltage of the circuit breaker.

In no case shall the maximum rated voltage exceed the rated insulation voltage.

Rated Current, InThis is the current that the circuit breaker will carry continuously under specifiedconditions and upon which the time/current characteristics are based.

For example: In = 32A type C (marked C32).

Unless otherwise stated, this value is based upon a reference ambient temperatureof 30 degrees Celsius.

EN 60898 Standard refers to the following terms:

Short Circuit Capacity

Rated Short Circuit Capacity, IcnThe calculated prospective fault current at the incoming terminals of the circuit breaker should not exceed the stated value. For example: Icn = 10kA (marked 10000).

Service Short Circuit Breaking Capacity, IcsThis value is the maximum level of fault current operation, after which furtherservice of the device is assured without loss of performance. Note that there is norequirement for Ics to be marked on the device.

There is a proscribed relationship between Ics and Icn, as follows:For values of Icn up to 6000A Ics = Icn

For values of Icn 6000A to10000A Ics = 0.75Icn (but with a minimum valueof Ics = 6000A)

For values of Icn above 10000A Ics = 0.5Icn (but with a minimum valueof Ics = 7500A)

Page 124: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

122

The EN 60947-2 and EN 60947-3 Standards also refer to the following terms.

Isolation SuitabilityThese define the requirements for the suitability of circuit breakers to performisolation duty by defining tests to which such units must comply. Conformingdevices must carry a standard symbol mark to show that they are suitable forisolation duty. For example, all Dorman Smith circuit breakers are so marked.

Utilisation CategoriesThe utilisation category of a circuit breaker is stated with reference to whether or not it is specifically intended for discrimination by means of an intentional timedelay with respect to other circuit breakers in series on the load side under short-circuit conditions.

Category A This designates circuit breakers not specifically intended for selectivity with deviceson the load side. Circuit breakers will discriminate only up to certain fault levels,above which discrimination with devices on the load side cannot be guaranteed.

Category B This designates circuit breakers specifically intended for selectivity with devices onthe load side. Such circuit breakers will incorporate some form of time delay.

EN 60947-2 recognises both a rated service and a rated ultimate short circuitbreaking capacity for both Category A and Category B circuit breakers.

Rated Service Breaking Capacity, IcsIn order to define this value, the circuit breakers under test must be subjected to atest sequence of:

Ics = o – t – co - t – co, where:o = opening time under fault conditionst = time interval before re-closing (not more than 3 minutes)c = closing operation on to a fault

After this test sequence, dielectric, terminal temperature and over-current tests areto be applied. The circuit breaker must meet certain test parameters to ensure thatthe device has not deteriorated in performance and can be put back into service.

Rated Ultimate Breaking capacity, IcuIn order to define this value, the circuit breakers under test must be subjected to atest sequence of:

Icu = o – t– co.

After this test sequence, dielectric and over-current tests are to be applied.

The rated service breaking capacity (Ics) applies to short circuit faults that couldoccur in practice; whereas the ultimate short circuit capacity (Icu) is the maximumtheoretical fault value of the installation at the point of connection.

The standard defines the ratio between the two values. Ics will be shown as 25%,50%, 75% or 100% of its Icu value for Category A devices and 50%, 75% or 100% ofIcu for Category B devices.

A circuit breaker can remain in service after interrupting a short circuit up to itsrated value of Ics. However, where two or more faults occur between the Ics and Icu

values, the capability of the device for continued operation must be verified.

X

Page 125: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

123

Current Carrying and Switching Devices

SwitchA switch is a mechanical device capable of making, carrying and breaking currentunder circuit conditions.

Disconnector (Isolator)A disconnector is a mechanical switching device that provides the function ofcircuit isolation.

Switch DisconnectorThis device combines the functionality of the two foregoing devices; it providesmaking, carrying, breaking and isolation of current within a circuit.

FusesFuses can be combined with any of the above devices in any physical order. Theinclusion of a fuse will add the functionality of short circuit protection, breaking thecircuit when the current flow is higher than that for which the circuit is rated.

Combination DevicesIn order to enhance circuit protection, switches and fuses are often combinedwithin a single device. The physical composition of the device can be identified bythe literal position of the words in its description. For example, the word ‘fuse’ atthe beginning of the device description identifies the fuse as forming part of themoving contact system, whereas placing it at the end of the description identifiesthe fuse as a static link.

Functional Summary

Switch Current rating Isolation

Operational and insulationvoltage Protection

Making and breaking of load

Short time current rating

Disconnector Current rating Protection

Isolation Making/breaking capability

Operational and insulationvoltage

Short time current rating

Fuse Overload protection Switching

Short circuit protection

Term Features FeaturesProvided Not Provided

Suitability for purposeAll of these devices have the ability to carry rated current either continuously or for a period of eight hours under defined conditions. Selection and specification ofa specific device depends upon the circuit application.

Page 126: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

124

Function

Fuse Combination Unit

Switching ApplicationsFor switching applications, the principal functions and capabilities include:

• Making and breaking operationA switch must have the ability to make or break defined load and overloadcurrents at a rated operational voltage, for the useful life of the device.

• Short circuit actionThe device must have the capability of handling short circuit current and/orthrough fault and/or fault making.

• ProtectionThe device must interrupt the circuit under overload and/or short circuitconditions.

• IsolationTo meet this requirement, the device must ensure disconnection of the supply forsafe downstream working. Facilities must be included for safety padlocking in the‘off’ position, together with positive indication of the contact position.

• Neutral switchingWhere the neutral is reliably earthed, it is accepted that the neutral need not beswitched except in defined circumstances (e.g. the incoming switch disconnectorin a consumer unit) even though the Wiring Regulations (BS 7671:2001) class theneutral as a current carrying conductor.

In applications where the neutral cannot be confirmed as reliably earthed, theneutral should be switched simultaneously with the phase(s) or alternativelyarranged to make before and break after the phase(s).

Page 127: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

125

Utilisation CategoryThe utilisation category defines the basic circuit conditions and the switchingcapability of the device.

AC20/DC20 Connecting and disconnecting under ‘no load’.

Assumes all switching operations are carried out by other capable devices before this device is operated.

AC21/DC21 Switching of resistive loads including moderate overloads.

Suitable for purely resistive type loads.

Device can switch 150% of its rated current under fault conditions.

AC22/DC22 Switching of mixed resistive/inductive loads, includingmoderate overloads.

Suitable for mixed resistive/inductive loads.

Device can switch 300% of its rated current under fault conditions.

AC23/DC23 Switching of highly inductive loads.

These devices are provided principally as back-up to other means of switching, e.g. contactors. In the event of failure of the functional device, the AC23/DC23 device can safely interrupt a stalled motor current. Where devices are the only means of controlling individual motors they should comply with the requirements of Appendix A of the EN 60947-3 standard.

Category Circuit/application

Note: Switch disconnectors for AC21/DC21, AC22/DC22 and AC23/DC23 categoriesalso have to meet the requirements of AC20/DC20.

For specific and special applications such as switching of capacitors and tungstenlamps not covered by the EN 60947-3 standard, the manufacturer’s advice shouldbe sought.

Frequent and Infrequent UseThe designation ‘A’ or ‘B’ should be appended to utilisation categories to indicatethe suitability for frequent or infrequent use in service. The ‘Rule of Thumb’definition for full load current switching duty is:

Frequent (A): Up to five times a day for small devices, say up to 100 amps, andonce per week for larger devices.

Infrequent (B): One per week for the smaller devices and once per month for the larger devices.

Page 128: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

126

Miniature Circuit Breakers (MCBs)

In general terms, circuit breakers are thermal/magnetic electromechanical devicesthat provide current making, carrying and breaking functions and will ‘trip’ tointerrupt a circuit under abnormal conditions. MCBs are equipped with positivecontact indication flags: red indicates that the contact(s) are closed, greenindicates the open state. The contact(s) will open when tripped due to abnormalcircuit conditions or can be manually put into the open state by use of a handle.

These devices are used to provide protection and control of circuits againstoverload and short circuit conditions. Dorman Smith supplies MCBs with variousbreaking capacities, particularly for ratings of 6kA and 10kA. The lower rateddevices are used typically in domestic installations, e.g. in consumer units, whereasthe higher rated devices are suitable for a range of commercial and industrialcircuit protection applications.

The thermal and magnetic trip functions cater for different circuit abnormalitiesand operate as follows:

Thermal Trip FunctionThe purpose of this form of protection is to interrupt the circuit upon sensing anoverload current. Typically, a bi-metallic strip is used such that it will deflect due todifferential expansion of the dissimilar metals in response to the heating effectcaused by the passage of current through it. The higher the current, the greater willbe the heating effect and the more the deflection. At a preset point the physicaldeflection will be sufficient to actuate the tripping mechanism, opening thecontact(s) and interrupting the circuit.

Magnetic Trip FunctionThe purpose of this form of tripping is to protect against the effects of short circuitfault currents. A wire coil or solenoid is used to provide this function, operating thetrip mechanism when the over-current reaches a preset magnitude. As the faultcurrent rapidly increases, the magnetic field also increases, energising the coil andmoving a cam that is part of the contact assembly to fully open the contact(s)thereby interrupting the circuit.

CharacteristicsMCBs are designed according to one of three distinct tripping characteristicsdesignated B, C or D. These designations relate to the magnetic trip setting andindicate the multiple of nominal current that will be tolerated by the device beforetripping. The following table illustrates these characteristics with typical duties andapplications. The nominal rated current is denoted by the symbol In.

B 3-5In Light duty, resistive loads

C 5-10In Fluorescent lights, small motors, inductive loads

D 10-20In Sodium lights, large motors (>3kW), large inductive loads

Type Magnetic ApplicationTrip

Dorman Smith business unit uses the Roman numeral ‘X’ to denote a breakingcapacity of 10kA. A typical MCB description would be X1PC10, defining the devicein this example as a circuit breaker with a breaking capacity of 10kA, single-polearrangement and a fixed trip setting of 5 to 10 times the nominal rated current of10 amps. Similarly an X3PB63 device would be three-poles, 3 to 5 times In to trip,rated current of 63 amps, and a breaking capacity of 10kA.

Page 129: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

127

MCB Tripping Characteristics – B, C and D Types

MCB Add-on FunctionsVarious accessories can be added to MCBs to enable remote access and signalling.For example, the contact status could be relayed to an alarm annunciator panel or SCADA system; the circuit breaker could be controlled also from the SCADA system.

Auxiliary ContactsRelaying of contact status can be achieved by the addition of an auxiliary contactand the contact form selected to suit the remote system input requirements.

Shunt TripThe addition of a shunt trip allows remote access to the breaker operation,permitting the supervisory system to manually trip the breaker. The shunt tripactuator is a coil that is normally de-energised in the closed (on) state. Whenactivated, the shunt trip will force the breaker to its ‘off’ state and the togglehandle and indicator flag will move to this corresponding position. Since the‘fail-safe’ (i.e. non-powered) state of a shunt coil is with the breaker remainingclosed, this precludes its use for emergency stop purposes. The interconnectingwiring could be open-circuit, for example, and would therefore not allow the shuntto open the breaker when the remote emergency switch is closed.

Under-voltage ReleaseIf the supply voltage dropped to a low level and devices tripped, a dangeroussituation could exist if the devices were automatically reset. For example, motorscould suddenly restart or other operating machinery set in motion without warning.In the event that the mains voltage should drop significantly below its normaloperating range, typically to less than 50%, an under-voltage release will force thebreaker to its ‘off’ state and the toggle handle and indicator flag will move to thiscorresponding position. Only when the supply has returned to, typically, at least85% of normal operating voltage will the under-voltage release allow the breaker tobe closed.

If a break occurred in the interconnecting wiring in this case, the breaker would betripped, just as if the voltage had fallen below the threshold value. For this reason,it is advisable to include an alarm function when using a UVR function.

The tripping time for the thermal release is defined according to specific values ofapplied overload current, as follows:

1.13In >1h (In < 63A)>2h (In > 63A)

1.45In <1h (In < 63A)<2h (In > 63A)

2.55In 1s<t<60s (In < 32A)1s<t<120s (In > 32A)

Text current Tripping time

B

C

D

Page 130: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

128

Energy Let-throughAn important facet of circuit protection devices is the extent to which they limitthe amount of electrical energy they allow to pass through them. This applies tofuses as well as to circuit breakers.

When an electric current flows through a resistance for a certain time, energy is produced in the form of heat. This thermal effect can be measured using the formula:

I2 x R x t, to give a quantity in ‘Watt seconds’. The unit of measurement for energyis the Joule, which is equivalent to one Watt second.

For all practical purposes, the resistance is treated as constant and negligible;therefore the commonly accepted term for energy let-through of a device is I2tsince this will always be proportional to the true thermal effect. The I2t term isreferred to as the Joule Integral since the results are expressed in integral form.

Under short-circuit fault conditions there is the potential for considerable energy to be let through by a circuit protection device. Knowledge of the energy let-through characteristics of circuit protection devices is useful for comparisonbetween different devices and also with regard to the selection of devices that arerequired to act in co-ordination to produce the levels of discrimination required forfault clearance.

The I2t characteristics of circuit breakers are depicted as curves, graphed againstvalues of prospective short-circuit current. These characteristics are relevant toboth MCBs and MCCBs as depicted in the following graphs.

Energy Let-through Characteristics –

Prospective Short-circuit Current

Maxim

um

En

erg

y L

et-

thro

ug

h (

I2t)

Page 131: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

129

Within the EN 60898 standard, circuit breakers with ‘B’ and ‘C’ characteristics arecategorised into energy limiting classes 1, 2 and 3, with Class 3 denoting deviceshaving the lowest energy let-through. The appropriate energy class is markedwithin a square box on conforming devices. Dorman Smith’s MCBs are categorisedwithin Class 3.

The following table indicates the maximum energy let-through values permissible ineach class, stated in Watt-seconds. In practice, compliance with the standard ischecked on the circuit breakers with the highest applicable rated current within therange, normally 40A.

6kA 1-16 100,000 120,000 35,000 42,000

20-32 No 130,000 160,000 45,000 55,000

40 limits 156,000 192,000 54,000 66,000

10kA 1-16 specified 240,000 290,000 70,000 84,000

20-32 310,000 370,000 90,000 110,000

40 372,000 444,000 108,000 132,000

Rated Current Class 1 Class 2 Class 3short- rating (A) I2t max. I2t max. I2t max.circuit B type and B type C type B type C typecapacity C type

Power LossAnother parameter of particular interest in the design of protection circuits is the power loss suffered by the circuit device. The power loss is calculated at therated current of the device and is based upon the voltage drop across the main terminals.

Since the power loss represents an energy release in the form of heat, the higherthe loss the greater will be the localised thermal effects upon the device. Devicesthat exhibit a low power loss will run at lower temperatures during operation thanthose with a higher power loss. This, in turn, will permit a higher packing density forlow loss devices without additional venting and will also promote stability andrepeatability of operation.

Power loss is generally stated ‘per pole’, as indicated in the accompanying table.The power loss characteristics are given for the Dorman Smith X-series range of MCBs.

1 1.062 1.06 3

2 0.449 0.9 3

4 0.326 1.3 3

6 0.325 1.96 3

10 0.185 1.85 3

16 0.148 2.35 3.5

20 0.147 2.96 4.5

25 0.135 3.18 4.5

32 0.102 3.26 6

40 0.082 3.28 7.5

50 0.073 3.65 9

63 0.113 7.12 13

Current Voltage Power Maximum power

rating (A) drop (V) loss (W) loss permitted (W)

Page 132: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

130

Currents of low magnitude caused by unintentional ‘leakage’ paths to earth can causedeterioration within circuit wiring and components with the potential to create arapidly escalating situation that will permit the current to reach dangerous levels.

Special forms of circuit breakers are designed to use the detection of earth leakageor ‘residual’ current to limit the effects of this type of fault.

The generic term ‘residual current device’ is used to describe a range of circuitprotection devices that include the functions of sensing and measurement of aleakage current, with subsequent tripping when the magnitude of the residualcurrent reaches a preset level. The purpose of these devices is to protect humanlife, livestock, property and equipment against the escalation of earth fault currentsto destructive magnitudes.

Two forms of technology are commonly employed in the design of residual currentdevices; electromagnetic and electronic. In both cases, a current transformer isused and is arranged such that normal current flows in the phase and neutralconductors cancel each other to produce a zero balance. The presence of anyresidual current will create an out-of-balance that can be used to signal theactuation of a mechanism for circuit interruption.

In the electromagnetic type, a trip relay is used as the actuation device. The relay ispowered by the fault current and therefore requires no external power source.

With electronic devices internal signal amplification allows a much smaller currenttransformer to be used, reducing the physical size of the circuit breaker. In thiscase, however, the actuation power is derived from both the fault current and themains power. Also, a separate earth reference connection may be required toensure continuity of operation in the event that the mains neutral is lost.

Residual current devices are accorded a ‘sensitivity’ coding that indicates the levelof residual current that would cause a trip action. Commonly, the availablesensitivity ranges are 10mA, 30mA, 100mA and 300mA. In general, the 10mA and30mA devices are used to protect human life, the 100mA and 300mA devicesbeing applied to protect wiring, cabling and equipment.

The degree of electrocution that could take place when a fault arises depends uponthe combined effects of the magnitude and duration of current flow. For sensitivitylevels of 30mA and below, tripping must be instantaneous to protect human life.Longer periods of residual current flow can be tolerated by equipment and the tripaction may not necessarily be required to interrupt the circuit instantaneously.

Residual Current Circuit BreakerThe RCCB device combines the functions of a switch with those of a residualcurrent device. It is often used in place of an incoming switch disconnector withthe advantage that it functions also as a residual current protection device. Thedisadvantage, however, is that a residual fault will cause the device to operateinterrupting ALL downstream circuits even when these circuits remain in a healthy state.

Note that an RCCB should not be used as the sole means to provide completeprotection. It has no overload or short circuit protection and must therefore befurther protected by an upstream device having these capabilities. Frequently, theRCCB is used in consumer units and distribution boards to protect sub-circuits in asplit load configuration. In these applications, the upstream back-up is provided bythe Regional Electricity Company’s local fuse.

Residual Current Breaker with Overload ProtectionThe RCBO combines the functions of an MCB with those of a residual currentdevice. It will therefore provide protection against overload, short circuit and earth leakage.

Residual Current Circuit Breakers

Page 133: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

131

RCBOs and RCCBs – GeneralThese devices are furnished with a test pushbutton on the front face of themodule. Operation of this button will simulate the presence of a residual fault andthe test should be made frequently, say once per month, to assure continuedcorrect functionality of the device.

In addition to the range of sensitivities, RCBOs and RCCBs are available in two types, type AC and type A. These refer to the types of circuit for which thedevices are suitable.

Type AC: for use with residual sinusoidal ac, whether applied as a step or ramp.

Type A: for use with either residual sinusoidal ac or residual chopped (pulsating)dc, whether applied as a step or ramp.

A time delay facility may also be included, adjustable up to, typically, 50-70mS.This is denoted by ‘S’ included within the description and also marked on thedevice. This function is included in order to enable the device to be used as part of a circuit device discrimination (or selectivity) arrangement. Without thetime delay, residual current circuit breakers cannot be easily used within adiscrimination scenario due to their inherent rapid tripping in response to residualcurrent detection.

Whereas RCBOs are single module width devices used in place of or alongsideMCBs in outgoing circuits, RCCBs are available in 2-pole and 4-pole forms and arereadily used in single phase and three phase distribution systems where they canfunction as either incoming or outgoing ways.

Due to their low levels of sensitivity RCCBs are generally equipped withsuppression filtering to avoid nuisance tripping that could be induced fromdisturbances in external or incoming circuits.

Page 134: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

132

Contactors are simply electromechanically controlled switches. A contactor acts as an interposing relay which, when its coil is energised, operates one or more sets of contacts that are able to carry currents of sufficient magnitude to switchpower equipment such as large banks of lights, highly inductive lamps, motors andlarge solenoids. The current required to operate the coil is minimal, therefore a contactor can be controlled by light duty contacts in a timer, pushbutton or othercontrol device.

Generally, contactors have no latching facility, i.e. once the coil is de-energised thecontact state returns to its normal ‘at res’ condition. However, whilst there is nomechanical latching, electrical latching can be easily accomplished by using aseparate relay contact to hold on the supply to the contactor’s coil.

Selection CriteriaThe correct choice of contactor depends upon a number of parameters within theintended application. These include:

• The form of power supply

• The magnitude of the power to be switched

• The type of load to be controlled

• The control voltage required

• The frequency of switching

Since the device operates by its coil being energised for possibly lengthy periods,considerable internal heat can be generated. For this reason, a venting insert mustbe placed between alternate pairs of contactors or between a contactor and anyother adjacent circuit device.

Switching CapacityContactor ratings are stated for AC1 type loads only (resistive). Where the load to beswitched differs from this, it is likely that the contactor will have to be de-rated toensure its performance. If the load is dc, inductive or capacitive, the degree of de-rating may be considerable. The following contactor de-rating tables indicate themaximum power/current that can be switched according to the type of load to becontrolled. The figures quoted are per phase and are based upon a 230V ac supply.

Switching of Heaters & Motors

Modular Contactors

Contactor current rating (A): 24 40 63

AC-1/AC-7a: HeatersRated operational current (A) 24.0 40.0 63.0

Rated operational power (kW)

230V 1-phase 5.3 8.7 13.3

230V 3-phase 9.0 16.0 24.0

400V 3-phase 16.0 26.0 40.0

Contactor current rating (A): 24 40 63

AC-3/AC-7b: HeatersRated operational current (A) 9.0 22.0 30.0

Rated operational power (kW)

230V 1-phase 1.3 3.7 5.0

230V 3-phase 2.2 5.5 8.0

400V 3-phase 4.0 11.0 15.0

Page 135: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

133

Switching of DC Circuits

Connection type: 1 current path 2 current 3 current paths series paths series

Nominal currentrating (A): 24 40 63 24 40 63 24 40 63

DC-1 (L/R <= 1mS)

Rated operational voltage (V dc):

24 24.0 40.0 50.0 24.0 40.0 63.0 24.0 40.0 63.0

48 21.0 23.0 25.0 24.0 40.0 43.0 24.0 40.0 63.0

60 17.0 18.0 20.0 24.0 32.0 35.0 24.0 40.0 60.0

110 7.0 8.0 9.0 16.0 17.0 19.0 24.0 30.0 33.0

220 0.9 1.0 1.1 4.5 5.0 5.5 13.0 15.0 17.0

DC-3 (L/R <= 2mS)

Rated operational voltage (V dc):

24 16.0 19.0 21.0 24.0 40.0 44.0 24.0 40.0 63.0

48 8.0 10.0 11.0 18.0 20.0 22.0 24.0 40.0 47.0

60 4.0 5.0 5.5 14.0 16.0 18.0 24.0 34.0 38.0

110 1.6 1.8 2.0 6.5 7.0 8.0 16.0 18.0 21.0

220 0.2 0.3 0.3 1.0 1.1 1.2 4.0 4.5 5.0

Switching of Lamp Loads

Contactor nominal 24 40 63current rating (A)

Lamp type: Watts Amps No. lamps allowed per phase Capacitor (uF)

Incandescent 60 0.26 25 54 83

100 0.43 15 32 50

200 0.87 7 16 25

300 1.30 5 11 16

500 2.17 3 6 10

1000 4.35 1 3 5

Fluorescent 15 0.35 30 100 155

(uncompensated 20 0.37 26 85 140

and series 40 0.43 20 65 105

compensation) 42 0.54 16 52 85

65 0.67 12 40 60

115 1.50 5 18 28

140 1.50 5 18 28

(two lamp circuit) 2x20 2x0.13 2x26 2x85 2x140

2x40 2x0.22 2x20 2x65 2x105

2x42 2x0.24 2x16 2x52 2x85

2x65 2x0.34 2x12 2x40 2x60

2x115 2x0.65 2x5 2x18 2x28

2x140 2x0.75 2x5 2x18 2x28

(parallel 15 0.11 8 15 67 4.5

compensation) 20 0.13 7 14 60 5.0

40 0.22 8 15 67 4.5

42 0.24 6 12 50 6.0

65 0.65 5 10 43 7.0

115 0.65 2 4 17 18.0

140 0.75 2 4 17 18.0

Page 136: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

134

Switching of Lamp Loads

Contactor nominal 24 40 63current rating (A)

Lamp type: Watts Amps No. lamps allowed per phase Capacitor (uF)

High pressure 50 0.61 14 36 50

mercury vapour 80 0.80 10 27 38

(uncompensated) 125 1.15 7 19 26

250 2.15 4 10 14

400 3.25 2 7 10

700 5.40 1 4 6

1000 7.50 1 3 4

(parallel 50 0.28 5 10 43 7

compensation) 80 0.41 4 8 37 8

125 0.65 3 6 26 10

250 1.22 2 3 15 18

400 1.95 1 3 10 25

700 3.45 - 1 5 45

1000 4.80 - 1 4 60

Lamps with 1x18 – 24 55 76

electronic power 2x18 – 18 34 48

supply (No. of 1x36 – 16 34 47

units per phase) 2x36 – 11 20 29

1x58 – 14 32 46

2x58 – 8 17 24

Metal-halogen 35 0.53 10 28 38

(uncompensated) 70 1.00 5 14 20

150 1.80 3 8 11

250 3.00 2 5 7

400 3.50 1 4 6

1000 9.50 – 1 2

2000 16.50 – 1 1

(Parallel 35 0.25 5 11 30 6

compensated) 70 0.45 3 5 18 12

150 0.75 1 3 9 20

250 1.50 1 2 7 33

400 2.50 1 2 6 35

1000 5.80 – – 2 95

2000 11.50 – – 1 148

Transformers for 20 – 52 110 174

halogen low voltage 50 – 24 50 80

(No. of transformers 75 – 16 35 54

per phase) 100 – 12 27 43

150 – 9 19 29

200 – 6 14 23

300 – 4 9 14

Page 137: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

135

Switching of Lamp Loads

Contactor nominal 24 40 63current rating (A)

Lamp type: Watts Amps No. lamps allowed per phase Capacitor (uF)

Low pressure 35 1.50 8 22 30

sodium vapour 55 1.50 8 22 30

(uncompensated) 90 2.40 5 13 19

135 3.50 3 10 13

150 3.30 3 10 14

180 3.30 3 10 14

200 2.30 5 14 20

(parallel 35 0.31 1 4 15 20

compensation) 55 0.42 1 4 15 20

90 0.63 1 3 10 30

135 0.94 – 2 7 45

150 1.00 – 2 8 40

180 1.16 – 2 8 40

200 1.32 – 3 12 25

High pressure 150 1.80 4 15 20

sodium vapour 250 3.00 3 9 15

(uncompensated) 330 3.70 2 8 10

400 4.70 1 6 8

1000 10.30 – 3 4

(parallel 150 0.83 1 3 15 20

compensation) 250 1.50 1 2 9 33

330 2.00 – 2 7 40

400 2.40 – 1 6 48

1000 6.30 – – 2 106

Page 138: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

136

The operation and application of the MCCB is similar to that of the MCB, howeverthis device has the air-break mechanism contained within a moulded case housingmade from a very robust non-conducting material. Generally, MCCBs exhibit muchhigher breaking capacities and rated current than their smaller counterparts andcan be used to perform full isolation duty. Consequently, MCCBs are employed inboth incoming and outgoing circuits. MCCBs are constructed to a particular framesize and typically provide rated current in the range 16-1600A.

These devices can be equipped with adjustable thermal and magnetic trippingmechanisms to cater for overload and short circuit protection to meet therequirements for isolation and Category A discrimination duty. Dorman Smith’selectronic versions provide adjustable long, short and instantaneous trip functions,allowing more complex overall tripping characteristics to be configured, allowingthese devices to be used for isolation and Category B discrimination requirements.(Refer to page 140 for Category definitions).

Devices equipped with the full range of adjustable trips for long, short andinstantaneous durations are generally referred to as ‘LSI-MCCBs’ to distinguishthem from the L and I only versions employed for Category A devices.

The range of accessories that can be added to MCCBs is similar to that given in thesection dealing with MCBs, including shunt trips, under-voltage releases and variousforms of auxiliary contacts. The physical size of triple-pole and four-pole MCCBsallows these accessories to be internally mounted, although there are somerestrictions with regard to combinations of these that can be co-mounted. Forexample, either a shunt trip or under-voltage release can be incorporated, but notboth. Also, due to the much larger physical size of these devices compared withMCBs, additional safety features normally include interphase barriers and terminalshrouds to provide IP2X ingress protection at the terminals.

The tripping operation of some MCCBs is different from that of MCBs in that there arethree distinct positions of the toggle or handle. Whereas MCBs are either ‘on’ or ‘off’,MCCBs have a central position when they are tripped. As a further safety feature, thecoloured flags indicating the ‘on’ and ‘off’ states are masked in the tripped state. Thebreaker can be reset only after it has been set into the fully ‘off’ state.

MCCBs are equipped with a test pushbutton that allows periodic testing of themechanical tripping mechanism. As in the case of a fault trip, the device must bemoved into the ‘off’ position before it can be reset following a test.

These devices conform to EN 60947-2 therefore the definitions that apply to someparameters differ from those of EN 60898 that apply to miniature circuit breakers.These differences are explained in the section covering Standard Terminology.

Motor Control ApplicationsThe MCCB is a viable means of providing motor control switching. However,MCCBs used for this type of application are often required to provide only shortcircuit protection, with the overload protection catered for by a separate thermalor electronic overload relay. For this reason, specifically designed ‘motor control’MCCBs are available upon request, with only the single tripping mechanism.

The range of circuit breakers for each frame size includes a basic switchdisconnector version, generally in both triple-pole and four-pole variants. Devicesof this type are sometimes referred to as ‘non-auto MCCBs’.

Moulded Case Circuit Breakers

Page 139: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

137

Loadline YA Frame MCCBs for Motor Starting (415 V ac)

P(Kw) Ie(A) Id"(A) In(A) Ii (lower tolerance) (A)

0.37 1.2 14 YA2/YA3 20 192

0.55 1.6 19 YA2/YA3 20 192

0.75 2 24 YA2/YA3 20 192

1.10 2.8 34 YA2/YA3 20 192

1.50 3.7 44 YA2/YA3 20 192

2.20 5.3 64 YA2/YA3 20 192

3.00 7 84 YA2/YA3 20 192

4.00 9 108 YA2/YA3 20 192

5.50 12 144 YA2/YA3 20 192

7.50 16 192 YA2/YA3 32 307

9.00 20 240 YA2/YA3 32 307

11.00 23 276 YA2/YA3 50 480

15.00 30 360 YA2/YA3 50 480

18.50 37 444 YA2/YA3 50 480

22.00 43 516 YA2/YA3 63 605

30.00 59 708 YA2/YA3 100 960

37.00 72 864 YA2/YA3 125 1200

45.00 85 1020 YA2/YA3 125 1200

55.00 105 1260 YA3 160 1664

75.00 140 1680 YA3 250 2600

90.00 170 2040 YA3 250 2600

110.00 210 2520 YA5 400 3840

132.00 224 2688 YA5 400 3840

150.00 255 3060 YA5 400 3840

Motor Motor full Sub-transient Breaker Breaker Breakerrating load starting frame rated instantaneous

current current current trip threshold(set on max.)

Notes1 In>le2 li/lower > ld"

The above table is suitable for DOL and Star Delta starting.

Page 140: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

138

In the context of power distribution schemes, the term ‘discrimination’ (sometimesreferred to as ‘selectivity’) describes a hierarchy of circuit devices that are arrangedsuch that a single upstream circuit breaker can fan out to several downstreamdevices to act in a co-ordinated fashion should a fault occur. Under fault conditions,only the upstream protective device closest to the fault should operate to clear thefault, leaving all other healthy circuits operable. This is especially important ininstallations where circuit failures could be life-threatening, such as in hospitals.

The concept of discrimination is similar to that of cascading, the prime differencebeing in the objectives of the application. Whereas discrimination is used to ensurecontinuity of supply to sub-circuits by limiting the disconnection to the faulted sub-circuit alone, cascading is used to buffer downstream protective devicesagainst the effects of high prospective short circuit currents.

In both cases, the protective devices are specifically selected to meet the criteriafor the type of co-ordination required.

When the selected devices are properly matched to fulfil the ideal discriminationprinciple described above, the co-ordinating devices are said to achieve ‘total’discrimination. In many practical installations, however, a partial discrimination maybe satisfactory for safe continuity of supply, with an added advantage of costsavings due to selecting a lower rated upstream circuit breaker.

Discrimination between two circuit breakers arranged in series may be based oneither current or time. Where the magnitude of the fault current is to be used asthe critical factor for selection, the co-ordination in this case is termed ‘currentdiscrimination’. Where the basis for selection is the duration over which theupstream device can withstand the fault current, the selection is to achieve ‘timediscrimination’. In some cases, time discrimination can be achieved by using anupstream device that has a built-in time delay.

Current DiscriminationIn general, the basis for current discrimination is that the downstream protectivedevice will have a lower current rating than the upstream device. It should alsohave a lower instantaneous tripping point. The discrimination tables that followhighlight the consequential increase in discrimination level as the differential incurrent ratings between the devices increases.

Time DiscriminationDiscriminating by time between two devices in series relies on the operation of theupstream device being delayed at least until the downstream circuit breaker hastripped to clear the fault. The clearing time of the downstream device must be lessthan the time setting of the upstream device and the upstream device must also becapable of withstanding the fault current for the full duration of its time setting.There is generally no problem in achieving these conditions where the upstreamdevice is a Category B circuit breaker specifically designed for this type of co-ordination duty.

Time/Current CharacteristicsComparison of the time/current characteristic graphs of the two devices proposedcan give a quick check on their suitability for co-ordination in both current andtime discrimination cases. Ideally, there should be no overlap of the respectivecurves to achieve total discrimination. If, however, the instantaneous portion of thecurves do intersect, a partial discrimination will be achieved at the current levelprojected from the intersect point.

In the tables that follow, total discrimination is indicated by the letter ‘T’ inappropriate boxes. Total discrimination applies for all fault levels up to the lowerbreaking capacity of the two devices in co-ordination. Where a value is containedin any of the boxes, this indicates a partial discrimination of that value of currentlimit. If no discrimination is possible, this is shown by a dash symbol.

Discrimination

Page 141: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

139

Note that ‘partial discrimination’ infers that, above the current limit value indicated,it is possible that both devices could trip, resulting in disconnection of other sub-circuits and loss of supply continuity to those areas of the distribution system.

Discrimination Tables

Case 1: Upstream MCCB with downstream MCB –

The table below is based on the following rules:

• All values are shown at 400V ac

• The MCB characteristic is type B

• The breaking capacity of the MCBs can be 6kA or 10kA at 400V

• The upstream device is the MCCB, with MCB downstream

• The value of partial discrimination is in amps

Case 2: Upstream Category B MCCB with downstream Category A MCCB –

The table below is based on the following rules:

• All values are shown at 400V ac

• The upstream device is a Y6 frame MCCB, with lower rated MCCBs downstream

• All pick-up current and time delay settings on upstream devices are set atmaximum

• The value of partial discrimination is in kA

• Category A devices have LSI adjustable trips; Category B devices have only L and I settings

MCB YA2N/S MCCB YA3N/S MCCB YA5Current Current rating Current rating MCCB

rating (A) (A) (A)(A)

20 32 50 63 100 125 20 32 50 63 100 125 160 200 250 250 400

6 260 T T T T T 260 T T T T T T T T T T

10 260 420 T T T T 260 420 T T T T T T T T T

16 260 420 650 T T T 260 420 650 T T T T T T T T

20 260 420 650 1000 T T 260 420 650 1000 T T T T T T T

25 260 420 650 1000 T T 260 420 650 1000 T T T T T T T

32 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 T T T T T

40 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 T T T T T

50 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 3000 T T T T

63 260 420 650 1000 1500 2000 260 420 650 1000 1500 2000 3000 2600 T T T

Y6HE Y6JE Y6HE Y6JEDownstream Downstream Downstream 630A 630A 800A 800A

MCCB current breaking 50kA 65kA 50kA 65kAtype rating capacity Category B Category B Category B Category B

YA2N 125 25 T T T T

YA2S 125 36 T T T T

YA2J 125 65 T T T T

YA3N 250 25 T T T T

YA3S 250 36 T T T T

YA3J 250 65 T T T 50

YA5N 400 25 10 10 T T

YA5H 400 50 10 10 25 25

Page 142: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

140

Cascading is sometimes referred to as ‘back-up protection’. The technique ofcascading is used to allow circuit breakers with a breaking capacity lower than thevalue of PSC at the connection point to be used when these are positioneddownstream of a current-limiting circuit breaker of higher breaking capacity. Thenet result of this arrangement is that the downstream device acquires an enhanced’installed‘ breaking capacity, therefore a less expensive, lower breaking capacitybreaker can be used.

The upstream circuit breaker must have the normally required breaking capacityfor its point of installation however, when combined with another circuit breakerdownstream, the two devices in series will be able to clear a larger fault. Forexample: if a 10A, 6kA MCB is place downstream of a YA frame MCCB rated at125A and 25kA, the MCB will have an installed breaking capacity of 14kA. Similarly,a 10A, 10kA MCB downstream of a YA frame MCCB rated at 250A and 25kA willhave an installed breaking capacity of 25kA.

It should be noted that the cascading technique is not limited to only two devicesin series. The important point is that it is the upstream device that is limiting thecurrent to a value that can be interrupted by the following device, so that thepattern of paired devices can be repeated many times in an hierarchy of devices.

The following tables give ‘installed breaking capacity’ values of downstream circuitbreakers for both the MCCB/MCB and MCCB/MCCB pairings of cascaded devices.Note that all values shown are at 400V ac. The values for the installed breakingcapacities are given in kA.

Case 1: Upstream YA frame MCCB with downstream S-series MCB –

Cascading

MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCBMCB YA2N YA2S YA2J YA3S YA3J YA3N YA3S YA3J

(6kA) (25kA) (36kA) (65kA) (36kA) (65kA) (25kA) (36kA) (65kA)125A 125A 125A 160A 160A 250A 250A 250A

6 14 14 14 12 12 12 12 12

10 14 14 14 12 12 12 12 12

16 14 14 14 12 12 12 12 12

20 14 14 14 12 12 12 12 12

32 14 14 14 12 12 12 12 12

40 12 12 12 10 10 10 10 10

50 12 12 12 10 10 10 10 10

63 12 12 12 10 10 10 10 10

MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCBMCB YA2N YA2S YA2J YA3S YA3J YA3N YA3S YA3J

(10kA) (25kA) (36kA) (65kA) (36kA) (65kA) (25kA) (36kA) (65kA)125A 125A 125A 160A 160A 250A 250A 250A

6 25 30 30 25 25 25 25 25

10 25 30 30 25 25 25 25 25

16 25 30 30 25 25 25 25 25

20 25 30 30 25 25 25 25 25

25 25 30 30 25 25 25 25 25

32 25 30 30 25 25 25 25 25

40 25 30 30 23 23 23 23 23

50 25 30 30 23 23 23 23 23

63 25 30 30 23 23 23 23 23

Case 2: Upstream YA frame MCCB with downstream X-series MCB –

Page 143: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

141

Case 3: Upstream YA2 and YA3 frame MCCBs with downstream YA2 and YA3 frame MCCBs –

Downstream MCCB MCCB MCCB MCCBYA2 MCCB YA5H(50kA) Y6HE(50kA) Y6HE(50kA) Y6J(65kA)

125A 400A 630A 800A 800A

25kA 36 36 – 36

36kA 50 50 – 50

65kA – – – –

YA3 MCCB250A

25kA 36 36 36 50

36kA 50 50 50 65

65kA – – – –

YA5 MCCB400A

25kA 36 36 36 50

65kA – – – –

Case 4: Upstream YA5 and Y6 frame MCCBs with downstream YA2, YA3 and YA5 frame MCCBs –

Down MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCBstream YA2N YA2S YA2J YA3S YA3J YA3N YA3S YA3J

YA2 MCCB (25kA) (36kA) (65kA) (36kA) (65kA) (25kA) (36kA) (65kA)125A 125A 125A 125A 160A 160A 250A 250A 250A

25kA – 36 50 36 50 – 36 50

36kA – – 65 – 65 – – 65

65kA – – – – – – – –

YA3 MCCB250A

25kA – – – – – – 36 50

36kA – – – – – – – 65

65kA – – – – – – – –

Page 144: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

142

MCB, type B FuseCurrent sizes

rating (A) 20 25 35 50 63 80 100 125 160

6 0.5 0.8 1.7 3.1 7.0 10.0 10.0 10.0 10.0

10 0.4 0.7 1.4 2.3 3.4 4.8 7.5 10.0 10.0

13 0.7 1.4 2.3 3.4 4.8 7.5 10.0 10.0

16 1.3 2.0 2.9 4.2 6.0 9.5 10.0

20 1.9 2.7 3.8 5.6 8.5 10.0

25 1.8 2.6 3.6 5.4 8.0 10.0

32 2.4 3.2 4.2 6.8 10.0

40 3.2 4.2 6.8 9.5

50 3.8 5.7 8.5

63 3.8 5.7 8.5

Short-circuit Discrimination LevelsWhere a high prospective fault level exists at the MCB distribution point,discrimination at short-circuit levels should be considered. This will requirecomparison of the device I2t characteristics at the relevant prospective fault level.

Discrimination will be obtained at all fault levels for which the MCB total operatingI2t is lower than the pre-arcing I2t of the device closer to the supply.

The data for typical cartridge fuses can be extracted from graphs and is presentedin the following tables.

MCB, type CCurrent

rating (A)

6 0.5 0.8 1.7 3.1 7.0 10.0 10.0 10.0 10.0

10 1.4 2.3 3.4 4.8 7.5 10.0 10.0

13 2.3 3.4 4.8 7.5 10.0 10.0

16 2.0 2.9 4.2 6.0 9.5 10.0

20 2.7 3.8 5.6 8.5 10.0

25 3.6 5.4 8.0 10.0

32 4.2 6.8 10.0

40 4.2 6.8 9.5

50 5.7 8.5

63 5.7 8.5

MCB, type CCurrent

rating (A)

6 0.7 1.7 3.0 5.9 6.0 6.0 6.0 6.0 6.0

10 1.3 2.2 3.6 6.0 6.0 6.0 6.0

13 1.7 2.5 4.0 6.0 6.0 6.0

16 1.6 2.2 3.1 4.6 6.0 6.0

20 2.2 3.1 4.6 6.0 6.0

25 3.1 4.6 6.0 6.0

32 2.6 3.5 6.0 6.0

40 3.5 6.0 6.0

50 5.5 6.0

63

Page 145: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

143

Current B type C type D typerating (A) 0.4s 5s 0.4s 5s 0.4s 5s

6 7.6 7.6 3.8 5.9 2.7 3.6

10 4.6 4.6 2.3 3.5 1.6 2.9

13 3.7 3.7 1.8 2.8 1.3 2.3

16 2.9 2.9 1.4 2.2 1.0 1.8

20 2.3 2.3 1.1 1.7 0.8 1.4

25 1.8 1.8 0.9 1.4 0.6 1.1

32 1.4 1.4 0.7 1.1 0.5 0.9

40 1.1 1.1 0.6 0.9 0.4 0.7

50 0.9 0.9 0.5 0.7 0.3 0.6

63 0.7 0.7 0.4 0.6 0.3 0.5

Maximum Zs for Loadlimiter MCBs

The above table is based on 230V rated voltage to earth.

Current B type C type D typerating (A) Fuse link rating (A)

6 20 32 25

10 20 32 40

13 20 32 40

16 32 50 63

20 40 63 63

25 50 80 80

32 63 100 100

40 80 100 125

50 100 125 125

63 125 125 125

Minimum Fuse Rating for Discrimination

Current B type C type D typerating (A) Fuse link rating (A)

6 63 40 40

10 80 63 63

13 80 63 63

16 80 80 80

20 80 80 80

25 100 100 100

32 100 100 100

40 125 125 125

50 160 160 160

63 160 160 160

Maximum Back-up Fuse Rating for Protection

Page 146: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

144

Number MCCB panel boards MCB distribution boardsof circuits to EN 60439-1 to EN 60439-3

2-3 0.9 0.8

4-5 0.8 0.7

6-9 0.7 0.6

10+ 0.6 0.5

The adequacy of sizing and rating of power distribution systems is important toensure supply continuity and safety in operation. A number of design parametersmust be taken into account in order to ensure that the supply and safetyrequirements are met. These include busbar ratings, short-circuit fault levels andcircuit utilisation.

Once the overall loading requirements have been established, and the supplytransformer selected, consideration of the circuit distribution systems follows.Distribution enclosures and their busbar systems are pre-tested to accepted normsof through-fault levels, typically 16kA, 25kA, 35kA, 50kA and 80kA. These short-circuit ratings alone will limit the choice of switchboard, panel board or distributionboard. The selection of the type and size of enclosure to be used will then dependupon the busbar current rating needed, together with availability of sufficientcircuit ways of the correct type for the circuits and sub-circuits to be supplied.

The busbar current rating is generally chosen to be sufficient to supply full load,plus some safety factor. For example, if the full load is expected to be 750 amps,an enclosure with a busbar rating of 800 amps may be selected. Once the busbarcurrent rating has been nominated, the incoming device for that group of circuitswill be matched to the rating. In the example cited, the incoming device would be rated at 800 amps. More than one incoming device may be required to effectproper circuit protection and isolation, such as a switch disconnector in series with a thermal fuse. In this case, the fuse link will provide the protection and the disconnector will permit isolation. Alternatively, a moulded case circuit breaker (MCCB) employed as the incoming device will provide both protection and isolation.

The size and type of circuits to be supplied will further refine the eventual choice of distribution system. Automatic or manual circuit disconnection will point to an enclosure suitable for either circuit breakers or switch-fuse devices. If therequirement is for automatic disconnection, prospective fault levels at theconnection point may dictate that an MCCB must be used, rather than an MCB ofthe same current rating.

Finally, consideration is given to the degree of circuit utilisation capacity, oftenreferred to as ‘diversity’. Notwithstanding the limitations of the busbar system andthe matched protection provided by the incoming device, the outgoing circuitways may be configured with individual circuit protection devices having anaggregate rated current capacity in excess of the rating of the incomer.

The basis for this approach is that it is often reasonable to assume that not allcircuits will be supplying their rated current at the same time. In this case, a‘diversity factor’ is applied during the design stage to give an overall servicecapacity for the outgoing circuits. The maximum current rating divided by thediversity factor will give the maximum aggregate ‘fitted’ current allowed. Thefollowing table lists the factors that may be applied subject to the number ofoutgoing circuits to be supplied.

Taking the example of a 400A panel board with 400A MCCB incomer and 6outgoing circuits, a diversity factor of 0.7 would allow outgoing MCCBs with anaggregate of 570A capacity to be installed. The individual circuits would beprotected at the level of current rating of each MCCB, with the incomer providingultimate protection at 400A. To allow for the possibility of future expansion of adistribution system, an allowance for 25% spare capacity is often included whenapplying a diversity factor to the initial design.

System Sizing and Diversity

Page 147: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

145

The Prospective Short-circuit Current, or PSC, is the theoretical maximum faultcurrent that could exist at any point within a complete circuit distribution system.

The magnitude of the fault current at any particular point is calculated on the basis ofa ‘bolted’ (virtually permanent) fault path at that point and therefore assumes aconstant voltage, continuous current supply feeding the fault. Using this assumption,the PSC that could possibly exist at the bolted fault path would be limited only by thesum of the circuit impedances of the complete current path, from high voltage feedto the supply transformer through to the bolted connection point. Since thisassumption cannot be fulfiled in practice (for example, the voltage will not remainconstant) the value of calculated PSC can never be exceeded in a practical scheme.

The foregoing commentary is particularly relevant to larger commercial and industrialnetworks, where many sub-systems are present and often, many sub-circuits withinthese. For more compact arrangements, such as domestic installations, where thedistribution scheme is contained within one or more consumer units, the situation ismuch simpler. The Regional Electricity Companies generally agree on a fixed faultlevel of 16kA at the local zone supply distribution point to one or more dwellings.Those dwellings that lie some distance from the zone origin point of the distributedsupply will have reduced PSC due to the higher impedance of the longer run ofservice cable. Consumer units should therefore have a minimum short-circuit rating of16kA. When an MCB trips, the combination of forced contact separation and rapid arcextinction produces a limiting effect on the fault current such that it will beadequately handled within the normal 6kA breaking capacity of MCBs fitted todomestic installations.

PSC at the origin point –In practice and with consideration of the total distribution network; the breakingcapacity of an individual circuit device would normally be less than that calculated forthe origin point of the scheme.

PSC at the connection point –The breaking capacity of individual devices must be greater than (or at least equal to)the PSC at the specific point of their connection within a scheme. Conversely, wherethe circuit device breaking capacity is greater than the PSC at origin, there is no needfor further measurement or calculation in this regard.

The PSC at any particular connection point can be estimated, calculated, ordetermined by measurement of the circuit impedance at that point. Measurement ofthe circuit impedances at all relevant connection points can be a laborious exercise;the calculation method is generally used since this can be readily carried out usingone of a number of available computer software packages.

PSC by calculation –The magnitude of the short-circuit current (rms value of the ac component) at theconnection point will depend upon:

• the PSC at the origin point.

• the total resistance in the circuit between the origin point and the relevant circuit reference point.

• whether the short-circuit condition is considered as phase-phase, phase-neutral or phase-earth.

The maximum PSC at the origin can be calculated from the following formula:

Supply transformer rating (kVA) x 100

√3 x secondary voltage x % transformer reactance

PSC by estimation –To estimate the PSC, first calculate the total resistance in the LV circuit bydetermining the sizes and lengths of cables between the supply source and the pointunder consideration. Next, use the following table to find the cable resistances andsummate these to obtain the total resistance. Finally, use this value to read off theestimated PSC from the following graph.

Prospective Short Circuit Current

PSC (kA) =

Page 148: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

146

Nominal Cable length (m)crosssectionalarea (mm2) 5 10 15 20 30 40 50 60 70 80 90 100

1 90.50 181.00

1.5 60.50 121.00 182.00

2.5 37.10 74.10 111.00 148.00

4 23.10 46.10 69.20 92.20 138.00

6 15.40 30.80 46.20 61.60 92.40 123.00

10 9.15 18.30 27.50 36.60 54.90 73.20 91.50 110.00

16 5.75 11.50 17.30 23.00 34.50 46.00 57.20 69.00 80.50 92.00

25 3.64 7.27 10.90 14.50 21.80 29.10 36.40 43.60 50.90 58.20 65.40 72.70

35 2.62 5.24 7.86 10.48 15.70 21.00 26.20 31.40 36.70 41.90 47.20 52.40

50 1.94 3.87 5.81 7.74 11.60 15.50 19.40 23.20 27.10 31.00 34.80 38.70

70 1.34 2.68 4.02 5.36 8.04 10.70 13.40 16.10 18.80 21.40 24.10 26.80

95 0.96 1.93 2.88 3.86 5.79 7.72 9.65 11.60 13.50 15.40 17.40 19.30

120 0.77 1.53 2.30 3.06 4.59 6.12 7.65 9.18 10.70 12.20 13.80 15.30

150 0.62 1.24 1.86 2.48 3.72 4.96 6.20 7.44 8.68 9.92 11.20 12.40

185 0.49 1.00 1.49 1.98 2.97 3.96 4.96 5.96 6.94 7.93 8.92 9.91

240 0.38 0.75 1.13 1.51 2.26 3.02 3.77 4.52 5.28 6.03 6.79 7.54

300 0.30 0.60 0.90 1.20 1.80 2.40 3.00 3.60 4.20 4.80 5.40 6.00

400 0.23 0.47 0.70 0.94 1.41 1.88 2.35 2.85 3.29 3.76 4.23 4.70

500 0.18 0.37 0.55 0.73 1.10 1.46 1.83 2.20 2.56 2.93 3.29 3.66

630 0.14 0.28 0.42 0.57 0.85 1.13 1.42 1.78 2.15 2.51 2.88 3.25

Maximum Resistance of Copper Conductors at 20°C (megohms)

Total Circuit Resistance (mΩ)

Fau

lt C

urr

en

t (k

A)

Page 149: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

147

PSC in a typical installation

Note that the values on the graph assume a symmetrical fault across the threephases. In a single circuit, for line-neutral faults, the cable resistance value given inthe table should be doubled.

The following values of PSC would be obtained at the various circuit points markedin the above diagram:

Point ‘A’ PSC = approximately 27kA

Point ‘B’ Two cables per phase, therefore halve the value.

Resistance from ‘A’ to ‘B’ = 0.3 megohms

PSC = 25kA

Point ‘C’ Resistance from ‘A’ to ‘B’ = 0.3 megohms

Resistance from ‘B’ to ‘C’ = 10.7 megohms

Total circuit resistance = 11.0 megohms

PSC = 12kA

Point ‘D’ Resistance from ‘A’ to ‘B’ = 0.3 megohms

Resistance from ‘B’ to ‘C’ = 10.7 megohms

Resistance from ‘B’ to ‘C’ = 46.0 megohms

(Double the value for the 2-core cable)

Total circuit resistance = 57.0 megohms

PSC = 3kA

Page 150: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

148

One of the most common means of protecting persons against the effects of highvoltages and currents is by insulating the wiring and components. Most earth faults occurwhen some part of the insulation has broken down, creating the possibility of causingelectric shock through indirect contact with the faulty circuit. The breakdown of insulationcan often cause all or part of an enclosure or frame to become ‘live’ by raising conductiveparts to a hazardous voltage level. Touching any of the exposed parts of the enclosure orframe would then be highly dangerous and would most likely cause an electric shock.

Whilst protective devices may open quickly to minimise the possibility of high currentsflowing for any significant length of time, additional measures are necessary to limit thepotential earth fault current at source. In some cases fault current limiting resistors orinductors may be installed at the transformer star point however, in all cases, it isimportant to ensure that the impedance of circuit conductors is kept to a minimum sothat the voltage developed under fault conditions will be restricted. The earth fault loopimpedance is denoted Zs and is an important circuit design parameter.

Circuit designs must always ensure that the magnitude of the fault current will besufficient to trip the over-current protective devices within acceptable times as stated inthe IEE Wiring Regulations. Circuit breakers are designed to trip and therefore disconnectfaulted circuits very quickly. The design value of tripping time is generally expressed in theform of a graph that maps current against time and any practical scheme can be checkedagainst this value to ascertain conformance with the requirements.

The fault current can be established very simply using Ohm’s law, as follows:

Fault current = Phase-to-earth voltage

Zs

Once this value is known, the corresponding tripping time can be read from the relevantdevice’s time/current characteristic graph and the result compared with that given withinthe Wiring Regulations. In general, the higher the nominal voltage of an installation, theshorter will be the required disconnection time. For fixed equipment installations, themaximum disconnection time is stated as 5 seconds, whereas it is 0.4 seconds forportable equipment. The Regulations define ‘portable’ as including fixed outlet socketsthat may be used to supply apparatus that is movable or portable when in use.

The following table illustrates the maximum Zs allowable for MCBs to achieve thespecified disconnection times.

Since the complete loop impedance is the sum of the individual impedances of thesupply transformer winding, circuit phase conductor and protective circuitconductor, the total may be higher than that specified for in-time disconnection forthe protection device proposed. In these cases, several solutions may be possibleto overcome or at least assist in achieving compliance.

• The supply cable may be replaced by one with greater cross sectional area

• The short-circuit tripping threshold of the device may be set to a lower value (if it is adjustable)

• A Residual Current Device could be used to replace the circuit breaker in question

The following tables indicate the maximum Zs for Dorman Smith’s range ofMCCBs. Using these tables obviates the need to determine the suitability of adevice by reference to its time/current characteristic graph.

Earth Fault Protection

Current 6 10 16 20 25 32 40 50 63rating (A)

Type Bmax. Zs 8.00 4.80 3.00 2.40 1.92 1.50 1.20 0.96 0.76

(ohms)

Type Cmax. Zs 4.00 2.40 1.50 1.20 0.96 0.75 0.60 0.48 0.38

(ohms)

Type Dmax. Zs 2.00 1.20 0.75 0.60 0.48 0.38 0.30 0.24 0.19

(ohms)

Page 151: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

149

Loadline YA Frame MCCBs –

Maximum Zs to achieve in-time disconnection

Note: The fourth character of the MCCB part number signifies the Icu rating of thedevice. The above table is based on the ‘N’ rated MCCBs with Icu = 25kA.However, the same values of Zs apply to the ‘S’ and ‘J’ MCCBs where:

S: Icu = 36kA and J: Icu = 65kA

Loadline MCCBs Magnetic Breaking Max Zs valuesadjustment In capacity

(kA) 0.4 sec 5 sec

YA2 Frame

YA2N3P20T Set at maximum 20 25 0.80 1.64

YA2N3P32T Set at maximum 32 25 0.50 1.05

YA2N3P50T Set at maximum 50 25 0.32 0.37

YA2N3P63T Set at maximum 63 25 0.25 0.29

YA2N3P100T Set at maximum 100 25 0.16 0.19

YA2N3P125T Set at maximum 125 25 0.13 0.15

YA3 Frame

YA3N1P16T Fixed 16 25 1.20 1.28

YA3N1P20T Fixed 20 25 0.96 1.05

YA3N1P25T Fixed 25 25 0.77 0.82

YA3N1P32T Fixed 32 25 0.60 0.62

YA3N1P40T Fixed 40 25 0.48 0.50

YA3N1P50T Fixed 50 25 0.38 0.41

YA3N1P63T Fixed 63 25 0.30 0.33

YA3N1P80T Fixed 80 25 0.24 0.26

YA3N1P100T Fixed 100 25 0.19 0.21

YA3N1P125T Fixed 125 25 0.15 0.17

YA3N1P160T Fixed 160 25 0.12 0.13

YA3N3P20T Set at maximum 20 25 0.80 0.88

YA3N3P32T Set at maximum 32 25 0.50 0.58

YA3N3P50T Set at maximum 50 25 0.32 0.37

YA3N3P63T Set at maximum 63 25 0.25 0.29

YA3N3P100T Set at maximum 100 25 0.16 0.18

YA3N3P125T Set at maximum 125 25 0.13 0.14

YA3N3P160T Set at maximum 160 25 0.09 0.11

YA3N3P200T Set at maximum 200 25 0.07 0.09

YA3N3P250T Set at maximum 250 25 0.06 0.06

YA5 Frame

YA5N3P250T Set at maximum 250 25 0.06 0.06

YA5N3P250T Set at minimum 250 25 0.13 0.13

YA5N3P400T Set at maximum 400 25 0.04 0.04

YA5N3P400T Set at minimum 400 25 0.08 0.08

Page 152: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

150

Loadline YA Frame MCCBs –

Maximum Zs to achieve in-time disconnection

Note: The fourth character of the MCCB part number signifies the Icu rating of the device where:

H: Icu = 50kA

J: Icu = 65kA

K: Icu = 85kA

Loadline MCCBs Magnetic Breaking Max Zs valuesadjustment In capacity

(kA) 0.4 sec 5 sec

Y6 Frame

Y6H3P400T Set at maximum 400 50 0.05 0.05

Y6H3P400T Set at minimum 400 50 0.10 0.10

Y6H3P630T Set at maximum 630 50 0.03 0.03

Y6H3P630T Set at minimum 630 50 0.07 0.07

Y6H3P800T Set at maximum 800 50 0.03 0.03

Y6H3P800T Set at minimum 800 50 0.05 0.05

Y6H3P630E "INST/STD 630 50 0.03 0.03set at maximum

Y6H3P630E "INST/STD" 630 50 0.17 0.17set at minimum

Y6H3P800E "INST/STD" 800 50 0.03 0.03set at maximum

Y6H3P800E "INST/STD" 800 50 0.13 0.13set at minimum

Y6H3P630E "INST/STD" 630 50 0.03 0.03set at maximum

Y6H3P630E "INST/STD" 630 50 0.17 0.17set at minimum

Y6J3P800E "INST/STD" 800 65 0.03 0.03set at maximum

Y6J3P800E "INST/STD" 800 65 0.20 0.20set at minimum

Y7 Frame

Y7J3P1000E "INST/STD" 1000 65 0.02 0.02set at maximum

Y7J3P1000E "INST/STD" 1000 65 0.10 0.1 set at minimum

Y7J3P1250E "INST/STD" 1250 65 0.02 0.02set at maximum

Y7J3P1250E "INST/STD" 1250 65 0.08 0.08set at minimum

Y8 Frame

Y8K3P1600E "INST/STD" 1600 85 0.01 0.01set at maximum

Y8K3P1600E "INST/STD" 1600 85 0.07 0.07set at minimum

Page 153: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

151

The principle of separation applied to multi-cubicle switchboards and panel boardsis the achievement of a high degree of safety for equipment and people duringnormal operation and to promote safe working during commissioning and service.The resulting concept is one of functional separation and segregation of live partsof the system into sub-units by the use of barriers or partitions.

In general, separation should provide enhanced safety by:

• Protecting against contact with the live parts of adjacent functional units

• Preventing the passage of solid foreign bodies from one section of an assemblyto an adjacent one

Various elements of an assembly must be considered for separation fromneighbouring live sections, such as busbars, terminals and functional units. Thespecific form of their separation can be achieved in several ways according to theparticular application and the requirements for access for maintenance. Theminimum degree of protection to be achieved at each barrier or partition is to IP2Xas specified in the Ingress Protection standard EN 60529. Typically, this may include:

• PVC sleeving, wrapping or plastic coating of conductors

• Insulated terminal shrouds or PVC ‘boots’

• Rigid insulated barriers or partitions

• Compartments formed from earthed metal

• A device’s integral housing

There are several forms of separation, indicated by numbered category and sub-category; however the requirements for the degree of separation need to becarefully considered since the cost increases significantly with increased degree.

The principal categories are:

Form 1 – no separationTypical applications are where the assembly is to be placed in a secure locationand where failure will cause little or no additional disruption to other areas beingsupplied by that particular assembly.

Form 2 – separation of busbars from functional unitsApplications may be similar to those of Form 1 but where it is important that a faultneed not affect all functional units being supplied by the same busbar system.

Form 3 – separation of busbars from functional units and the functional unitsfrom one another, but not their terminationsThis form should be applied where it is important to provide protection frominternal live parts and where failure of functional units being supplied from thesame busbar would cause unacceptable disruption.

Form 4 – separation of busbars from functional units and the functional unitsfrom one another, including their terminalsThis form should be applied where it is important to provide protection frominternal live parts and where failure of functional units being supplied from thesame busbar would cause unacceptable disruption. Because all the terminations areseparated, it is possible to isolate and work on a single functional unit.

Dorman Smith ‘LF-type’ panel board systems are supplied in Form 2 as standard,with Form 4 versions achieved with simple conversion kits. However, otherseparation forms can be provided in special cases.

With the exception of Form 1, the other separation forms have sub-categories thatpermit permutations of the general form to be configured according to therequirements for specific applications and to allow the accommodation of differenttypes of protection method. The exact form of separation provided on an assemblyis a matter for agreement between the manufacturer and the end user.

Forms of Separation

Page 154: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

152

Sub-categories of Separation Forms

Main criteria Sub criteria Form Type Construction

No separation 1

Separation of Terminals for externalbusbars from conductors not 2athe functional separated from units busbars

Terminals for external 1 Busbar separation by conductors separated 2b insulated coveringsfrom busbars 2 Busbar separation by

rigid barriers

Terminals for externalconductors not 3aseparated from busbars

Terminals for external 1 Busbar separation byconductors separated 3b insulated coveringsfrom busbars 2 Busbar separation by

rigid barriers

Cable Access OptionsGenerally, for front access assemblies, cable chambers are provided alongside theassociated functional units. For rear access assemblies cabling facilities areprovided at the rear of the assembly where working space is required. In bothcases, functional units are normally accessed and operated from the front.

Where the assembly is to be installed in a position where there is adequate workingspace all round, cabling access may be from either front or rear. However, if theassembly is to be installed against a wall, the design must be such as to ensure thatall necessary access can be gained from the front.

Generally, for the same number of functional units, front access assemblies aremuch longer than the rear access alternative. Conversely, where cabling chambersare required at the rear, this necessitates a deeper design of assembly.

The size of cabling chambers and the general arrangement can be influenced bythe number and size of circuit cables and also the direction in which the cablesneed to approach the assembly.

Terminals for externalconductors in the same compartment as the associatedfunctional unit

Busbar separation by insulatedcoveringsCables may be glanded elsewhere

Busbar separation by rigid barriersCables may be glanded elsewhere

All separation by rigid barriersThe termination for eachfunctional unit has its own integralglanding facility

Busbar separation by insulatedcoveringsCables may be glanded elsewhere

Busbar separation by rigid barriersTerminals may be separated byinsulated coverings and glandedin common cabling chambers

All separation by rigid barriersCables are glanded in commoncabling chambers

All separation by rigid barriersThe termination for eachfunctional unit has its own integralglanding facility

1

2

3

4

5

6

7

4a

4bTerminals for externalconductors not in thesame compartment asthe associatedfunctional unit but inindividual, separate,enclosed protectedspaces orcompartments

Separation of busbars from thefunctional units and separation of all functional units from one another.Separation of the terminals for externalconductors fromfunctional units butnot from each other

Separation ofbusbars from thefunctional units andseparation of allfunctional unitsfrom one anotherincluding terminalsfor externalconductors whichare an integral part of thefunctional unit

Page 155: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

153

The EN 60529 standard describes a system for classifying degrees of protectionagainst the ingress of foreign bodies and harmful liquids. It is intended that thisstandard is applied to enclosures of low voltage (LV) electrical equipment. Theclassification scheme comprises a designation prefixed by the upper case letters’IP‘, followed by two numerals.

The first numeral designates the degree of protection with regard to solid objects;the second numeral indicates the degree of protection against the ingress of liquid.Compliance to the standard is intended to:

• protect persons against access to hazardous parts inside enclosures and protectthe equipment inside the enclosure against the ingress of solid foreign objects.

• protect the equipment inside the enclosure against harmful ingress of liquids.

For switchboard (and panel board) assemblies intended for indoor use, there is norequirement for protection against the ingress of liquid. The IP designationspreferred for assemblies intended for indoor use are:

Ingress Protection

IP Protection Equivalent

0 No protection

1 Full entry of 50mm Back ofsphere, but no handcontact with hazardous parts

2 Full entry of 12.5mm Fingersphere not allowed,but no contact withhazardous parts withjointed test finger

3 2.5mm diameter Toolaccess probe shall not enter

4 1mm diameter access Wireprobe shall not enter

5 Limited ingress of Wiredust (no harmful deposit)

6 Total protection Wireagainst dust ingress

X Not tested -

IP21

IP31 IP32

IP42 IP42

IP53 IP54 IP55

IP64 IP65

IP Protection Equivalent

0 No protection

1 Against vertically Vertical failing water drops drips

2 As in 1, but with Slantedenclosure tilted 15 dripping degrees from vertical to 15

degreesfrom vertical

3 Against spray to 60 Limited degrees from sprayvertical – limited ingress permitted

4 Against splashing Splashingfrom any direction – from anylimited ingress directionpermitted

5 Against low pressure Hosing jets from any jets from direction – limited anyingress permitted direction

6 Against strong jets Powerfrom any direction hosing

from any direction

7 Against immersion Temporaryup to one metre immersion

8 Against prolonged Continuousimmersion under immersionpressure

X Not tested -

Page 156: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

154

Insulation Distances for Loadline YA Frame MCCBsThe insulation distances between an MCCB and adjacent earthed metal parts andinsulators shown in the diagram below must be maintained to prevent arcing faultsoccurring due to conductive ionised gases. In cases where requirements differ fromthose illustrated here, the greater distance must be maintained. Where twodifferent YA frame devices are installed one above the other, the insulationdistance between the two should be as for the lower size of MCCB.

Exposed conductors must be insulated up to the barrier terminals. Interphasebarriers or terminal covers are recommended. However, if terminal covers are used,the exposed conductor must be insulated until it overlaps the terminal cover.

1. Insulation plate

2. Top plate (earthed metal)

3. Interphase barriers

4. Front connected MCCB

5. Front connected MCCB with terminal bar

6. Rear connected type or plug-in type

7. Side panel (earthed metal)

*Note: (1) Insulate the exposed conductor until it overlaps the moulded case at theterminal or terminal cover.

A. Distance from lower breaker to exposedlive part of upper breaker terminal (frontconnected type) or from lower breaker toend face of upper breaker (rear connectedor plug-in type)

B1. Distance from end face of breaker to top plate

B2. Distance from end face of breaker to insulation plate

C. Gap between breakers

D. Distance from side of breaker to side panel

E. Dimensions of insulation over exposed conductors

MCCB Distances

Frame Poles A B1 B2 C D ESize

YA2N 1 50 10 10 0 25 *(1)

YA2N 3/4 50 10 10 0 25 *(1)

YA2S 3/4 50 10 10 0 25 *(1)

YA2J 3/4 75 45 25 0 25 *(1)

YA3N 1 50 40 40 0 50 *(1)

YA3N 3/4 50 40 40 0 50 *(1)

YA3S 3/4 50 40 40 0 50 *(1)

YA3J 3/4 100 80 60 0 50 *(1)

YA5N 3/4 100 80 60 0 80 *(1)

YA5H 3/4 100 80 60 0 80 *(1)

Page 157: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

155

YA2 1-pole Time/Current Characteristic

YA2 1-Pole Dimensions and Drilling Plan

Loadline YA2 Frame MCCBCharacteristics and Dimensions

YA2 1-pole Energy Let-through

Page 158: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

156

YA2 3 and 4-pole Time/Current Characteristic YA2 3 and 4-pole Energy Let-through

YA2 3 and 4-pole Dimensions and Drilling Plan

Page 159: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

157

YA3 1-pole Time/Current Characteristic YA3 1-pole Energy Let-through

YA3 1-pole Dimensions and Drilling Plan

Loadline YA3 Frame MCCBCharacteristics and Dimensions

Page 160: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

158

YA3 3 and 4-pole Time/Current Characteristic YA3 3 and 4-pole Energy Let-through

YA3 3 and 4-pole Dimensions and Drilling Plan

Page 161: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

159

YA5 3 and 4-pole Time/Current Characteristic

YA5 3 and 4-pole Dimensions and Drilling Plan

YA5 3 and 4-pole Energy Let-through

Loadline YA5 Frame MCCBCharacteristics and Dimensions

Page 162: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

160

Y6 Time/Current Characteristic

Y6 Dimensions and Drilling Plan

Loadline Y6 Frame MCCBCharacteristics and Dimensions

Page 163: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

161

Y7 Time/Current Characteristic

Y7 Dimensions and Drilling Plan

Loadline Y7 Frame MCCBCharacteristics and Dimensions

Page 164: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

162

SPM Series – Plug-In SurgeProtection Modules and Bases

It is recommended that SPM series surge protectors are installed on the load sideof a MCCB, MCB - type C or a fuse disconnector 63A max, to provide isolation formaintenance if required and for protection in high load circuits.

Connecting bases are fitted with terminals suitable for insulated cables 16mm2 -35mm2. It should be noted that the two slots for the plug in module are differentwidths, the widest one being aligned with the top of the module in the direction oftext so that reading of the module label is facilitated. However, the module is notpolarised and therefore the base and the module can be mounted in anyorientation.

MountingThe SPM surge protection modules should be mounted as close to the panel orequipment to be protected as possible. The effectiveness of the protector will bereduced by the use of long connecting cables as the voltage across the unit will beincreased due to the inductance of these cables.

Connecting CablesConnect the base and suppressor as shown in the installation diagram.Connect the terminals within the base to the load side of 63A (max) protection.

Recommended Wire GaugeMinimum 16mm2

Terminals accept 35mm2 max.

StandardsBS6651:1999 Annex CEN 61643-11: 2002 - SPD Class II

Length of Connecting CablesThe longer the connecting cables between the SPM Series and power panel, thehigher the residual transient voltage developed.

Each 250mm cable length increases clamping voltage by approximately 25V per1000A surge current discharged. 250mm (10") recommended.

Always use the shortest length of connecting cable possible.

MaintenanceAt intervals not exceeding a year or following lightning activity check:1. Status indicators

2. Conditions of connecting cables and terminals

3. Tightness of module

Page 165: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

163

MountingThe 600 Series is connected in parallel with the supply and therefore carries onlythe currents associated with the transient being dissipated. Connecting cablesshould be of suitable cross-section area, (6mm2 min.) as short as possible, ideally250mm or less and tightly bound together to reduce inductive effects. The 600Series connectors accept cable requirements up to 16mm2.

Connecting CablesThe longer the connecting leads between the 600 Series and power source, thehigher the residual transient voltage.

Recommended Maximum: 500mm (20")Ideally: 250mm (10")

Each 250mm increase in cable length increases clamping voltage by 25V per1000A surge current discharged. Always use the shortest length of connectingcable possible.

Bind the phase, neutral and earth conductors tightly, over the entire run.

Remote Monitoring Unit (DSP3L only)A remote monitoring unit is supplied with a 1 metre cable and appropriate plug andsocket connectors which allows the 600 Series to be installed in areas that areinaccessible for regular inspection.

Site Fault Condition Indicator (DSP3N, DSP3L only). Should the light on thisindicator flash or be permanently illuminated at any time, it is to warn of a highvoltage between neutral and earth lines, and therefore potentially hazardous siteconditions.

ImportantIn order to achieve the most effective protection all earth connections must bereferenced to a common point.

The 600 Series should be considered as part of a co-ordinated approach totransient protection and while protecting the primary mains input it should beremembered that any equipment connected following the unit is susceptible totransients that can occur at other points within the system and therefore requirelocal protection.

BS 6651: 1999 Annex C.

DSP3 - Distribution Surge Protector 600 Series

3-phase 600 series 176 110 72

1/3-phase optional enclosure 245 195 100

Dimensions (mm) Length Width Depth

Page 166: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

164

ELR1 Earth Leakage Relay

Measuring input From core balanced current transformer

Overload 20 x nominal for 1 second

Frequency 50Hz or 60Hz ±10%

Auxiliary voltage 12-48V dc, 24-48V ac and dc or 100-250V ac and dc

Auxiliary burden Less than 1.5 Watts

Trip current settings Selectable 30mA, 100mA, 200mA, 300mA, 500mA, 1A, 2A, 3A, 5A, 10A

Trip accuracy 50% <trip point current <100% in accordance with IEC 1543

Trip response time <40ms (at 5 x rated trip current, ignoring the selected time delay)

Time delay set points Selectable 0ms, 50ms, 100ms, 150ms, 200ms, 300ms,400ms, 500ms, 600ms, 700ms, 800ms, 900ms, 1 second, 2seconds, 5 seconds, 10 seconds. When 30mA leakage isselected, the time delay is disabled

Indication 5 yellow LED bargraph for leakage levelsRed LED indicated trip functionGreen LED indicated auxiliary power presenceRed LED pre-alarm indication (SPCO version only)

Relay contacts Standard: 2-pole change over Option: 2 1-pole change over (pre-alarm and main alarm)

Relay contact rating 8 amps at 250V ac8 amps at 30V dc resistive

Relay mechanical life >100,000 operations

Analogue output 0 to 1mA = 0 to 100% of selected tripping level. Compliance 1V, accuracy 10%

Enclosure style DIN 43880, rail width 70mm

Compliant with EMC and LVD, UL 3111-1 File No: E203000, CSA 22.2/1010.1-92 BSEN 50081-1, BSEN 50082-2, IEC 60255-22-1 (BS5992), IEC 60255-11, BSEN 61543 (IEC 1543), BSEN 61010 (IEC 1010),EN 60068 (IEC 68)

Material Flame retardant UL94V0

Terminals 1 to 4mm2 solid or stranded conductors.IP20 protection

Operating temperature –10°C to +60°C

Storage temperature –20°C to +70°C

Relative humidity <95% non condensing

Weight <250g

Dimensions 71mm wide x 90.5mm high x 73mm deep2.79" wide x 3.56" high x 2.87" deep

Dimensions

Connections

Page 167: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

9Section

Products & Parts Locator

Page 168: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

166

2IP-7-0244 111

A1SPM/40/230 9

A1SPM/40/230 111

A1SPM/40/230N 9

A1SPM/40/230N 111

A3SPM/40/230 21

A3SPM/40/230 111

A3SPM/40/230N 21

A3SPM/40/230N 111

AV263 9

AV263 112

AV2100 9

AV2100 112

AV2125 9

AV2125 112

AV363 112

AV3100 20

AV3100 112

AV3125 20

AV3125 112

AV463 112

AV4100 20

AV4100 112

AV4125 20

AV4125 112

CBT-94F-035 114

CBT-94F-070 114

CBT-94F-105 114

CBT-94F-140 114

DA06X 8

DA09X 8

DA12X 8

DA15X 8

DA18X 8

DA22X 8

DAS08X 8

DAS11X 8

DAS14X 8

DAS17X 8

DAS20X 8

DAS24X 8

DAXD0 9

DAXD1 9

DAXEB 8

DAXEB 19

DAXSK08 8

DAXSK11 8

DAXSK14 8

DAXSK17 8

DAXSK20 8

DAXSK24 8

DAXSKB 8

DAXTP 4

DAXTP 19

DBMSB 18

DBMSB 26

DBS18X 18

DBS36X 18

DBTE04X 19

DBTE06X 19

DBTE08X 19

DBTE12X 19

DBTE16X 19

DBTE20X 19

DBTE24X 19

DBX04R 18

DBX06R 18

DBX08R 18

DBX12R 18

DBX16R 18

DBX20R 18

DBX24R 18

DBX24FK 19

DBX24WL 19

DBXBH 8

DBXBH 11

DBXBH 19

DBXBH 22

DBXBH 42

DBXBM 8

DBXBM 11

DBXBM 19

DBXBM 22

DBXBM 42

DBXBP 8

DBXBP 11

DBXBP 19

DBXBP 22

DBXBP 42

DBXCL 8

DBXCL 11

DBXCL 19

DBXCL 42

DBXCL 50

DBXCL 60

DBXCL 62

DBXCL 66

DBXCL 70

DBXCK 20

DBXD0 19

DBXD0 20

DBXD1 19

DBXD1 20

DBXD2 19

DBXD2 20

DBXEP 19

DBXJK 19

DBXL 8

DBXL 19

DBXLSA1 20

DBXLSA2 20

DBXPL 8

DBXPL 50

DBXPL 60

DBXPL 62

DBXPL 66

DBXPL 70

DBXT06 19

DBXT12 19

DBXT18 19

DBXT24 19

DBXTS 19

DBXYA3 18

DBXYA3 20

DBXW16 26

DBXW16T 26

DBXW24 26

DBXWP125 26

DBXWP250 26

DRI-1260-210 25

DRI-1260-210 113

DRK-1P-230-D63 26

DRK-1P-230-D63 114

DRK-3P-400-D100 26

DRK-3P-400-D100 114

DRK-1PCT-240 11

DRK-1PCT-240 25

DRK-1PCT-240 113

DRK-3PCT-415 25

DRK-3PCT-415 113

DRK-3PCT-415-LCD 25

DRK-3PCT-415-LCD 113

DRT-DW2R 24

DRT-DW2R 112

DSP3/600/BOW 111

DSP3L/600/BOW 111

DSP3N/600/BOW 111

DSPM/90/230NR 111

DSPM/90/230R 111

DSPM/150/230NR 111

DSPM/150/230R 111

ELR1 114

FS2 68

FS2 91

FS2 93

GR1PB0630 10

GR1PB0630 22

GR1PB0630 99

GR1PB1030 10

GR1PB1030 22

GR1PB1030 99

GR1PB1630 10

GR1PB1630 22

GR1PB1630 99

GR1PB2030 10

GR1PB2030 22

GR1PB2030 99

GR1PB3230 10

GR1PB3230 22

GR1PB3230 99

GR1PB4030 10

GR1PB4030 22

GR1PB4030 99

GR1PB5030 10

Page 169: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

GR1PB5030 22

GR1PB5030 99

GR1PC0630 10

GR1PC0630 22

GR1PC0630 99

GR1PC1030 10

GR1PC1030 22

GR1PC1030 99

GR1PC1630 10

GR1PC1630 22

GR1PC1630 99

GR1PC2030 10

GR1PC2030 22

GR1PC2030 99

GR1PC3230 10

GR1PC3230 22

GR1PC3230 99

GR1PC4030 10

GR1PC4030 22

GR1PC4030 99

GR1PC5030 10

GR1PC5030 22

GR1PC5030 99

GR1PC06100 10

GR1PC06100 22

GR1PC06100 99

GR1PC10100 10

GR1PC10100 22

GR1PC10100 99

GR1PC16100 10

GR1PC16100 22

GR1PC16100 99

GR1PC20100 10

GR1PC20100 22

GR1PC20100 99

GR1PC32100 10

GR1PC32100 22

GR1PC32100 99

GR1PC40100 10

GR1PC40100 22

GR1PC40100 99

HB125CSB 91

HB200CSB 91

HB400CSB 91

HB800CSB 91

HEL32 91

HBE3P32N 90

HBF3P63N 90

HBF3P100N 20

HBF3P100N 90

HBF3P125N 20

HBF3P125N 90

HBF3P160N 90

HBF3P200N 60

HBF3P200N 90

HBF4P100 90

HBF4P200 90

HBK3P315N 90

HBL3P400N 60

HBL4P400 90

HBL3P400N 90

HBN3P630N 90

HBN3P800N 90

HBN4P800 90

HFL63 53

HFL63 91

HFL63 93

HFL200A 53

HFL200A 91

HFL200A 93

HLL400 53

HLL400 91

HLL400 93

HNL800 53

HNL800 67

HNL800 91

HNL800 93

INT-1630-M-5-M-100 25

INT-1630-M-5-M-100 113

INT-1630-M-5-M-110 25

INT-1630-M-5-M-110 113

KWH-400 25

KWH-400 113

K1PB06 10

K1PB06 21

K1PB06 98

K1PB10 10

K1PB10 21

K1PB10 98

K1PB13 10

K1PB13 21

K1PB13 98

K1PB16 10

K1PB16 21

K1PB16 98

K1PB20 10

K1PB20 21

K1PB20 98

K1PB25 10

K1PB25 21

K1PB25 98

K1PB32 10

K1PB32 21

K1PB32 98

K1PB40 10

K1PB40 21

K1PB40 98

K1PB50 10

K1PB50 21

K1PB50 98

K1PB63 10

K1PB63 21

K1PB63 98

K1PB100 100

K1PC06 10

K1PC06 21

K1PC06 98

K1PC10 10

K1PC10 21

K1PC10 98

K1PC13 10

K1PC13 21

K1PC13 98

K1PC16 10

K1PC16 21

K1PC16 98

K1PC20 10

K1PC20 21

K1PC20 98

K1PC25 10

K1PC25 21

K1PC25 98

K1PC32 10

K1PC32 21

K1PC32 98

K1PC40 10

K1PC40 21

K1PC40 98

K1PC50 10

K1PC50 21

K1PC50 98

K1PC63 10

K1PC63 21

K1PC63 98

K1PC100 100

X1PC125 100

K1PD06 10

K1PD06 21

K1PD06 98

K1PD10 10

K1PD10 21

K1PD10 98

K1PD16 10

K1PD16 21

K1PD16 98

K1PD20 10

K1PD20 21

K1PD20 98

K1PD25 10

K1PD25 21

K1PD25 98

K1PD32 10

K1PD32 21

K1PD32 98

K1PD40 10

K1PD40 21

K1PD40 98

K1PD50 10

K1PD50 21

K1PD50 98

K1PD63 10

K1PD63 21

K1PD63 98

K2PB06 98

K2PB10 98

K2PB16 98

K2PB20 98

167

Page 170: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

168

K2PB32 98

K2PB40 98

K2PB50 98

K2PB63 98

K2PC06 98

K2PC10 98

K2PC16 98

K2PC20 98

K2PC32 98

K2PC40 98

K2PC50 98

K2PC63 98

K2PC100 100

K2PD06 98

K2PD10 98

K2PD16 98

K2PD20 98

K2PD32 98

K2PD40 98

K2PD63 98

K3PB06 21

K3PB06 98

K3PB10 21

K3PB10 98

K3PB16 21

K3PB16 98

K3PB20 21

K3PB20 98

K3PB25 21

K3PB25 98

K3PB32 21

K3PB32 98

K3PB40 21

K3PB40 98

K3PB50 21

K3PB50 98

K3PB63 21

K3PB63 98

K3PC06 21

K3PC06 98

K3PC10 21

K3PC10 98

K3PC16 21

K3PC16 98

K3PC20 21

K3PC20 98

K3PC25 21

K3PC25 98

K3PC32 21

K3PC32 98

K3PC40 21

K3PC40 98

K3PC50 21

K3PC50 98

K3PC63 21

K3PC63 98

K3PC100 100

K3PD06 21

K3PD06 98

K3PD10 21

K3PD10 98

K3PD16 21

K3PD16 98

K3PD20 21

K3PD20 98

K3PD25 21

K3PD25 98

K3PD32 21

K3PD32 98

K3PD40 21

K3PD40 98

K3PD50 21

K3PD50 98

K3PD63 21

K3PD63 98

LB1F2A 60

LB1YA3 60

LB1F4A 60

LB1Y6 60

LB1Y7 62

LB406YA 60

LB412YA 60

LB418YA 60

LB802YA5 62

LB806YA 62

LB812YA 62

LB818YA 62

LBBP3PYA3 60

LBBP3PYA3 62

LBBP3PYA3 70

LBBP3PYA3 75

LBDD06 60

LBDD06 62

LBDD12 60

LBDD12 62

LBDD18 60

LBDD18 62

LBDR4 60

LBDR8 62

LBCK4 60

LBCK8 70

LBCK8 62

LBSK2B 60

LBSK4B 60

LBSKE 60

LBSKE 62

LBSKE 70

LBYA2BP3P 42

LBYA2BP3P 102

LCFVK 48

LCFVK 50

LCFVK 66

LD1D06X 49

LD1D06X 73

LD1D12X 49

LD1D12X 73

LD1DS 49

LD1DS 73

LD2D12X 49

LD2D12X 73

LDS17 49

LDS17 73

LDS17 49

LDS17 73

LDT106X 49

LDT106X 73

LDT112X 49

LDT112X 73

LDT212X 49

LDT212X 73

LECK1 48

LECK1 69

LECK2 48

LECK2 69

LECK3 48

LECK3 69

LECK4 48

LECK4 69

LECF5 48

LECF5 69

LECK6 48

LECK6 69

LECF8 48

LECF8 69

LECK2SM 48

LECK2SM 69

LECK2SP 48

LECK2SP 69

LECM3 62

LEE1 49

LEE1 69

LEE2 49

LEE2 69

LEE3 49

LEE3 69

LEE4 49

LEE4 69

LEE5 49

LEE5 69

LEE6 49

LEE6 69

LEM1630 50

LEM1630 70

LF1F4A 48

LF1F8A 48

LF1F8A 66

LF806A 48

LF806YA 66

LF810A 48

LF810YA 66

LFS41A 48

LFS41YA 66

LFS42A 48

LFS42YA 66

LFXHBA 48

LFXHBA 50

LGES 50

LGES 60

LGES 62

Page 171: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

169

LGES 69

LGES 70

LLGPYA3 115

LLGPYA56 115

LLM100/30/2 9

LLM100/30/2 23

LLM100/30/2 101

LLM100/30/4 20

LLM100/30/4 101

LLM100/100/2 9

LLM100/100/2 23

LLM100/100/2 101

LLM100/100/4 9

LLM100/100/4 101

LLM100/300/4 20

LLM100/300/4 101

LLM1P16CO 23

LLM1P16CO 112

LLM1P16NON 23

LLM1P16NON 112

LLM1P32CO 23

LLM1P32CO 112

LLM1P32NON 23

LLM1P32NON 112

LLM25/30/2 9

LLM25/30/2 23

LLM25/30/2 101

LLM2P16CO 23

LLM2P16CO 112

LLM2P16NON 23

LLM2P16NON 112

LLM2P20CC 24

LLM2P20CC 112

LLM2P20CO 24

LLM2P20CO 112

LLM2P32CO 23

LLM2P32CO 112

LLM2P32NON 23

LLM2P32NON 112

LLM2P40CC 24

LLM2P40CC 112

LLM2P40CO 24

LLM2P40CO 112

LLM2P63CO 24

LLM2P63CO 112

LLM3P24CO 24

LLM3P24CO 112

LLM3P40CO 24

LLM3P40CO 112

LLM40/30/2 9

LLM40/30/2 23

LLM40/30/2 101

LLM40/30/4 20

LLM40/30/4 101

LLM40/100/2 9

LLM40/100/2 23

LLM40/100/2 101

LLM40/100/4 20

LLM40/100/4 101

LLM40/300/4 20

LLM40/300/4 101

LLM4P24CC 24

LLM4P24CC 112

LLM4P24CO 24

LLM4P24CO 112

LLM4P24COC 24

LLM4P24COC 112

LLM4P40CO 24

LLM4P40CO 112

LLM4P63CO 24

LLM4P63CO 112

LLM63/30/2 9

LLM63/30/2 23

LLM63/30/2 101

LLM63/30/4 20

LLM63/30/4 101

LLM63/100/2 9

LLM63/100/2 23

LLM63/100/2 101

LLM63/100/4 20

LLM63/100/4 101

LLM63/300/2 9

LLM63/300/2 23

LLM63/300/3 101

LLM63/300/4 20

LLM63/300/4 101

LLM80/30/2 9

LLM80/30/2 23

LLMA-S63/300/4 101

LLMA-S80/100/2 9

LLMA-S80/100/2 23

LLMA-S80/100/2 101

LLMA-S100/100/2 9

LLMA-S100/100/2 23

LLMA-S100/100/2 101

LLMA-S100/100/4 101

LLMGPI2 115

LLMGPI4 115

LLMGPI8 115

LLMGPS6S 115

LLMGPW5 115

LLMGPW8 115

LLMLA 23

LLMLA 112

LLMLC 23

LLMLC 112

LLMLG 23

LLMLG 112

LLMLR 23

LLMLR 112

LLMPBNON 23

LLMPBNON 112

LLMPBNONC 23

LLMPBNONC 112

LLMPL 23

LLMPL 112

LLMRL 23

LLMRL 112

LLMV 112

LM10 110

LM20 110

LM30 110

LM40 110

LM50 110

LM60 110

LM2P20 110

LM3P10 110

LM3P20 110

LM3P30 110

LM3P40 110

LMMB2 110

LMMB3 110

LW2 110

LW3 110

M53J-100/5D 11

M53J-100/5D 26

M53J-100/5D 114

M53J-125/5D 11

M53J-125/5D 26

M53J-125/5D 114

M53J-200/5D 26

M53J-200/5D 40

M53J-200/5D 114

M53J-250/5D 26

M53J-250/5D 40

M53J-250/5D 114

M63N-400/5 50

M63N-400/5 114

M93L-600/5 50

M93L-600/5 70

M93L-600/5 114

MB5D-800/5 50

MB5D-800/5 70

MB5D-800/5 114

MCFMY6 66

MDSP3/90 111

MDSP3/150 111

MMS15Y 66

MXD06 66

MXD10 66

MXEPF 50

MXEPF 62

MXEPF 66

MXEPF 69

MXEPF 70

PB1630 40

PB206YA 40

PB208YA 40

PB212YA 40

PB406YA 41

PB408YA 41

PB412YA 41

PB416YA 41

PB4PNC250 42

PB4PNC400 42

PBSM 41

PBYA2CSB 40

PBYA2CSB 41

Page 172: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

PBYA2DC4 41

PBYA2NA 42

PBYA2OG 41

PBYA2SC24 41

PS16NY 96

PS25NY 96

PS32NY 96

PS40NY 96

PS63NY 96

PS80NY 96

PS100NY 96

PS125NY 96

S1PB06 98

S1PB10 98

S1PB16 98

S1PB20 98

S1PB32 98

S1PB40 98

S1PB50 98

S1PB63 98

S1PC06 98

S1PC10 98

S1PC16 98

S1PC20 98

S1PC32 98

S1PC40 98

S1PC63 98

SAUX2F 53

SAUX2F 91

SAUX2F 93

SAUX2N 53

SAUX2N 91

SAUX2N 93

SAUX4F 53

SAUX4F 91

SAUX4F 93

SAUX4N 53

SAUX4N 91

SAUX4N 93

SAUX6N 53

SAUX6N 91

SAUX6N 93

SCLK 68

SCLK 91

SCLK 93

SFFS125 93

SFFS200 93

SFTB 53

SFTB 93

SFTSL 93

SFTSL 93

SFTSS 53

SFTSS 93

SF3P63N 52

SF3P63N 91

SF3P100N 52

SF3P100N 91

SF3P125N 52

SF3P125N 91

SF3P160N 52

SF3P160N 91

SF3P200N 52

SF3P200N 61

SF3P200N 91

SF4P63 52

SF4P63 91

SF4P100 52

SF4P100 91

SF4P125 52

SF4P125 91

SF4P160 52

SF4P160 91

SF4P200 52

SF4P200 61

SF4P200 91

SHA1 93

SHA2 93

SHA3 93

SHA4 93

SKFS 93

SKTB 93

SKTS 93

SK3P315N 91

SK4P315 91

SLFS 53

SLFS 93

SLTB 53

SLTB 93

SLTS 53

SLTS 93

SL3P400N 51

SL3P400N 61

SL3P400N 91

SL4P400 51

SL4P400 61

SL4P400 91

SNCET 53

SNCET 68

SNCET 93

SNFS 68

SNTS 68

SN3P630N 51

SN3P630N 67

SN3P630N 91

SN4P630 51

SN4P630 67

SN4P630 91

SN3P800N 51

SN3P800N 67

SN3P800N 91

SN4P800 51

SN4P800 67

SN4P800 91

SPM/40/230 9

SPM/40/230 20

SPM/40/230 111

SPM/NE/40/230 9

SPM/NE/40/230 20

SPM/NE/40/230 111

SRLB32 93

SRLB63 93

SRLB100 93

SRLB125 93

SRLB160 93

SRLB200 93

SRLB315 93

SRLB400 93

SRLB630 93

SRLB800 93

SXT127 93

SXT160 93

SXT227 93

SXT260 93

TEGRA-710-200 25

TEGRA-710-200 113

X1PB80 100

X1PB125 100

X1PC80 100

X2PB80 100

X2PB100 100

X2PB125 100

X2PC80 100

X2PC125 100

X3PB80 100

X3PB100 100

X3PB125 100

X3PC13 21

X3PC13 98

X3PC80 100

X3PC125 100

X4PB06 99

X4PB10 99

X4PB13 99

X4PB16 99

X4PB20 99

X4PB25 99

X4PB32 99

X4PB40 99

X4PB50 99

X4PB63 99

X4PB80 100

X4PB100 100

X4PB125 100

X4PC06 98

X4PC10 98

X4PC13 98

X4PC16 98

X4PC20 98

X4PC25 98

X4PC32 98

X4PC40 98

X4PC50 98

X4PC63 98

X4PC80 100

X4PC100 100

X4PC125 100

X4PD06 98

170

Page 173: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

171

X4PD10 98

X4PD13 98

X4PD16 98

X4PD20 98

X4PD25 98

X4PD32 98

X4PD40 98

X4PD50 98

X4PD63 98

XAC2 11

XAC2 22

XAC2 100

XCS2 11

XCS2 22

XCS2 100

XDL 11

XDL 22

XDL 100

XPL 11

XPL 22

XPL 100

XST415 22

XST415 100

XST48 22

XST48 100

XUVR240 22

XUVR240 100

Y5DCL 68

Y5DCL 107

Y5DCL 108

Y5DCL 109

Y5DCLCAM 68

Y5DCLCAM 107

Y5DCLCAM 108

Y5DCLCAM 109

Y5TB3P 63

Y5TB3P 64

Y5TB3P 68

Y5TB3P 107

Y5TB3P 108

Y5TB3P 109

Y5TB4P 63

Y5TB4P 64

Y5TB4P 68

Y5TB4P 107

Y5TB4P 108

Y5TB4P 109

Y6AUX1 63

Y6AUX1 68

Y6AUX1 107

Y6AUX2 63

Y6AUX2 68

Y6AUX2 107

Y6AUXAL 63

Y6AUXAL 68

Y6AUXAL 107

Y6B3P400D 61

Y6B3P400D 106

Y6B3P630D 63

Y6B3P630D 106

Y6B3P800D 106

Y6B4P400D 61

Y6B4P400D 106

Y6B4P630D 63

Y6B4P630D 106

Y6B4P800D 67

Y6B4P800D 106

Y6CC3P 107

Y6CC4P 107

Y6TC3P 68

Y6TC3P 107

Y6TC4P 68

Y6TC4P 107

Y6CLDS1 68

Y6CLDS1 107

Y6DL 63

Y6DL 68

Y6DL 107

Y6H3P400T5 61

Y6H3P400T5 106

Y6H3P630E 63

Y6H3P630E 106

Y6H3P630T5 63

Y6H3P630T5 106

Y6H3P800E 106

Y6H3P800T5 106

Y6H4P400T5 61

Y6H4P400T5 106

Y6H4P630E 63

Y6H4P630E 106

Y6H4P630T5 63

Y6H4P630T5 106

Y6H4P800E 67

Y6H4P800E 106

Y6H4P800T5 67

Y6H4P800T5 106

Y6J3P630E 106

Y6J3P800E 106

Y6J4P630E 106

Y6J4P800E 106

Y6K3P400T5 106

Y6K3P630T5 106

Y6K3P800T5 106

Y6K4P400T5 106

Y6K4P630T5 106

Y6K4P800T5 106

Y6MA110 68

Y6MA110 107

Y6MA240 68

Y6MA240 107

Y6NL 68

Y6NL 107

Y6ST115AC 63

Y6ST115AC 68

Y6ST115AC 107

Y6ST24DC 63

Y6ST24DC 68

Y6ST24DC 107

Y6ST480AC 63

Y6ST480AC 68

Y6ST480AC 107

Y6TS3P 68

Y6TS3P 107

Y6TS4P 68

Y6TS4P 107

Y6UVR120AC 63

Y6UVR120AC 68

Y6UVR240AC 63

Y6UVR240AC 68

Y6UVR24DC 63

Y6UVR24DC 68

Y6UVR450AC 63

Y6UVR450AC 108

Y7AUX3P1 64

Y7AUX3P1 108

Y7AUX3P2 64

Y7AUX3P2 108

Y7AUX3PAL 64

Y7AUX3PAL 108

Y7AUX4P1 64

Y7AUX4P1 108

Y7AUX4P2 64

Y7AUX4P2 108

Y7AUX4PAL 108

Y7B3P800D 64

Y7B3P800D 108

Y7B3P1250D 108

Y7B4P800D 64

Y7B4P800D 108

Y7B4P1250D 108

Y7CL 108

Y7DL 64

Y7DL 108

Y7J3P1000E 64

Y7J3P1000E 108

Y7J3P1250E 108

Y7J4P1000E 64

Y7J4P1000E 108

Y7J4P1250E 108

Y7MA110 108

Y7MA240 108

Y7NL 108

Y7NL 109

Y7ST115AC 64

Y7ST115AC 108

Y7ST115AC 109

Y7ST24DC 64

Y7ST24DC 108

Y7ST24DC 109

Y7ST480AC 64

Y7ST480AC 108

Y7ST480AC 109

Y7TS3P 108

Y7TS3P 109

Y7TS4P 108

Y7TS4P 109

Y7UVR120AC 64

Y7UVR120AC 108

Y7UVR120AC 109

Page 174: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Y7UVR240AC 64

Y7UVR240AC 108

Y7UVR240AC 109

Y7UVR24DC 64

Y7UVR24DC 108

Y7UVR24DC 109

Y7UVR450AC 64

Y7UVR450AC 108

Y7UVR450AC 109

Y8B3P1600D 109

Y8B3P1600DDO 109

Y8B3P1600DR 109

Y8B4P1600D 109

Y8K3P1600E 109

Y8K3P1600EG 109

Y8K3P1600ER 109

Y8K4P1600E 109

YA2CC3P 42

YA2CC3P 102

YA2CC4P 102

YA2DL 102

YA2J3P50T 102

YA2J3P63T 102

YA2J3P100T 102

YA2J3P125T 102

YA2J4P50T 102

YA2J4P63T 102

YA2J4P100T 102

YA2J4P125T 102

YA2MA110 102

YA2MA240 102

YA2NL 102

YA2N1P16T 42

YA2N1P16T 102

YA2N1P20T 42

YA2N1P20T 102

YA2N1P32T 42

YA2N1P32T 102

YA2N1P40T 42

YA2N1P40T 102

YA2N1P50T 42

YA2N1P50T 102

YA2N1P63T 42

YA2N1P63T 102

YA2N1P80T 42

YA2N1P80T 102

YA2N1P100T 42

YA2N1P100T 102

YA2N1P125T 42

YA2N1P125T 102

YA2N3P20T 42

YA2N3P20T 102

YA2N3P32T 42

YA2N3P32T 102

YA2N3P50T 42

YA2N3P50T 102

YA2N3P63T 42

YA2N3P63T 102

YA2N3P100T 42

YA2N3P100T 102

YA2N3P125T 42

YA2N3P125T 102

YA2N4P20T 102

YA2N4P32T 102

YA2N4P50T 102

YA2N4P63T 102

YA2N4P100T 102

YA2N4P125T 102

YA2PB3P 102

YA2PB4P 102

YA2PFT3P 102

YA2PFT4P 102

YA2PT3P 102

YA2PT4P 102

YA2RH1 102

YA2RH2 102

YA2TS1P 41

YA2TS1P 102

YA2TS3P 102

YA2TS3P 102

YA2TS4P 102

YA2S3P50T 102

YA2S3P63T 102

YA2S3P100T 102

YA2S3P125T 102

YA2S4P50T 102

YA2S4P63T 102

YA2S4P100T 102

YA2S4P125T 102

YA2TC3P 102

YA2TC4P 102

YA2XT3P 102

YA2XT4P 102

YA3B3P250D 20

YA3B3P250D 40

YA3B3P250D 61

YA3B3P250D 103

YA3B4P250D 20

YA3B4P250D 40

YA3B4P250D 61

YA3B4P250D 103

YA3CC3P 42

YA3CC3P 72

YA3CC4P 42

YA3CC4P 72

YA3F4BP 65

YA3J3P50T 71

YA3J3P50T 103

YA3J3P63T 71

YA3J3P63T 103

YA3J3P100T 71

YA3J3P100T 103

YA3J3P125T 71

YA3J3P125T 103

YA3J3P160T 71

YA3J3P160T 103

YA3J3P200T 71

YA3J3P200T 103

YA3J3P250T 71

YA3J3P250T 103

YA3J4P50T 71

YA3J4P50T 103

YA3J4P63T 71

YA3J4P63T 103

YA3J4P100T 71

YA3J4P100T 103

YA3J4P125T 71

YA3J4P125T 103

YA3J4P160T 71

YA3J4P160T 103

YA3J4P200T 71

YA3J4P200T 103

YA3J4P250T 71

YA3J4P250T 103

YA3MA110 72

YA3MA110 103

YA3MA240 72

YA3MA240 103

YA3N1P16T 71

YA3N1P16T 103

YA3N1P20T 71

YA3N1P20T 103

YA3N1P32T 71

YA3N1P32T 103

YA3N1P40T 71

YA3N1P40T 103

YA3N1P50T 71

YA3N1P50T 103

YA3N1P63T 71

YA3N1P63T 103

YA3N1P80T 71

YA3N1P80T 103

YA3N1P100T 71

YA3N1P100T 103

YA3N1P125T 71

YA3N1P125T 103

YA3N1P160T 71

YA3N1P160T 103

YA3N3P20T 71

YA3N3P20T 103

YA3N3P32T 71

YA3N3P32T 103

YA3N3P50T 71

YA3N3P50T 103

YA3N3P63T 71

YA3N3P63T 103

YA3N3P100T 71

YA3N3P100T 103

YA3N3P125T 40

YA3N3P125T 71

YA3N3P125T 103

YA3N3P160T 40

YA3N3P160T 71

YA3N3P160T 103

YA3N3P200T 40

YA3N3P200T 61

YA3N3P200T 71

YA3N3P200T 103

YA3N3P250T 40

172

Page 175: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

173

YA3N3P250T 61

YA3N3P250T 71

YA3N3P250T 103

YA3N4P20T 71

YA3N4P20T 103

YA3N4P32T 71

YA3N4P32T 103

YA3N4P50T 71

YA3N4P50T 103

YA3N4P63T 71

YA3N4P63T 103

YA3N4P100T 71

YA3N4P100T 103

YA3N4P125T 71

YA3N4P125T 103

YA3N4P160T 20

YA3N4P160T 71

YA3N4P160T 103

YA3N4P200T 20

YA3N4P200T 71

YA3N4P200T 103

YA3N4P250T 20

YA3N4P250T 71

YA3N4P250T 103

YA3NL 20

YA3NL 71

YA3NL 103

YA3PB3P 103

YA3PB4P 103

YA3PFT3P 103

YA3PFT4P 103

YA3PT3P 103

YA3PT4P 103

YA3RH1 103

YA3RH2 103

YA3S3P50T 71

YA3S3P50T 103

YA3S3P63T 71

YA3S3P63T 103

YA3S3P100T 71

YA3S3P100T 103

YA3S3P125T 71

YA3S3P125T 103

YA3S3P160T 71

YA3S3P160T 103

YA3S3P200T 61

YA3S3P200T 71

YA3S3P200T 103

YA3S3P250T 61

YA3S3P250T 71

YA3S3P250T 103

YA3S4P32T 71

YA3S4P32T 103

YA3S4P50T 71

YA3S4P50T 103

YA3S4P63T 71

YA3S4P63T 103

YA3S4P100T 71

YA3S4P100T 103

YA3S4P125T 71

YA3S4P125T 103

YA3S4P160T 71

YA3S4P160T 103

YA3S4P200T 71

YA3S4P200T 103

YA3S4P250T 71

YA3S4P250T 103

YA3TB 72

YA3TB 104

YA3TC3P 72

YA3TC3P 104

YA3TC4P 72

YA3TC4P 104

YA3TS1P 72

YA3TS1P 104

YA3TS3P 72

YA3TS3P 104

YA3TS3PS 104

YA3TS4P 104

YA3TS4PS 104

YA5B3P400D 41

YA5B3P400D 105

YA5B4P400D 105

YA5CC3P 42

YA5CC3P 105

YA5CC4P 105

YA5H3P250T 105

YA5H3P400T 105

YA5H4P250T 105

YA5H4P400T 105

YA5J3P250T 105

YA5J3P400T 105

YA5J4P250T 105

YA5J4P400T 105

YA5K3P250E 105

YA5K3P400E 105

YA5K4P250E 105

YA5K4P400E 105

YA5MA110 105

YA5MA240 105

YA5N3P250T 41

YA5N3P250T 105

YA5N3P400T 41

YA5N3P400T 105

YA5N4P250T 105

YA5N4P400T 105

YA5NL 105

YA5TB 105

YA5TS3P 42

YA5TS3P 105

YA5TS4P 42

YA5TS4P 105

YAA1PLB 103

YAA3PLB 103

YAA3PLFT2 103

YAAL 72

YAAUX1 72

YACL 72

YACL 103

YADL1 72

YADL1 103

YAST115AC 42

YAST115AC 72

YAST115AC 103

YAST240AC 42

YAST240AC 72

YAST240AC 103

YAST24DC 42

YAST24DC 72

YAST24DC 103

YAST450AC 42

YAST450AC 72

YAST450AC 103

YAUVR120AC 42

YAUVR120AC 72

YAUVR120AC 103

YAUVR240AC 42

YAUVR240AC 72

YAUVR240AC 103

YAUVR24DC 42

YAUVR24DC 72

YAUVR24DC 103

YAUVR450AC 42

YAUVR450AC 72

YAUVR450AC 103

Page 176: Dorman Smith Electrical Distribution and Circuit Protection 2009 - … · 2010-11-02 · 1 Electrical Distribution and Circuit Protection Product Catalogue Contents SP&N Distribution

Tyco Electronics UK LtdEnergy DivisionFreebournes RoadWitham, Essex CM8 3AH

Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289Email: [email protected]

www.dormansmithswitchgear.comhttp://energy.tycoelectronics.com/ds

© T

yco

Ele

ctr

on

ics

DS

-EP

P-C

AT

08

-02

/09

Energy Division

With 4000 employees and more than 10,000 customers world-

wide, the Energy Division represents a very significant part of

Tyco Electronics. Based in headquarters in Ottobrunn, near

Munich, Germany, the Energy Division is a global supplier to

power utilities and power industry customers, to equipment

manufacturers and transport systems. These customers are

served by dedicated R&D teams, sales representatives in more

than 80 countries, a professional marketing organization and

25 manufacturing sites in five continents.

While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalog, TycoElectronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that suchinformation is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expresslydisclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for aparticular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics’ Standard Terms and Conditions of Sale. Tyco Electronics will in no case beliable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products.Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE logo, TycoElectronics and Dorman Smith are trademarks. Other trademarks or company names used herein are the property of respective owners.

Energy Division – economical solutions for the electrical power industry: cable accessories, connectors & fittings, electricalequipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters.