CODE OPTIONS CSD-1 UTC Lockout/Reset Control Manual Reset LWCO Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment. 2. Dimensions are subject to change without notice. DOMINATOR 300 Category I or Category III Appliance (see Installation and Operation Manual for venting information) SDOM-300-7 The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009. 15 3/8 in [39.1 cm] 15 in [38.1 cm] 4 1/4 in [10.8 cm] 26 9/16 in [67.5 cm] 37 7/8 in [96.2 cm] 4 7/8 in [12.4 cm] 29 5/16 in [74.4 cm] 4 7/16 [11.3 5 3/16 [13.2 c 2 1/2" WATER (2 PLCS.) Ø3/4" NAT & LP 5 in [12.6 cm] 27 3/16 in [69.1 cm] 35 3/16 in [89.4 cm] 12 15/16 in [32.9 cm] 19 1/16 in [48.4 cm] 11 1/16 in [28.1 cm] 22 1/8 in [56.2 cm] 4 7/16 in [11.3 cm] 31 7/8 in [81.0 cm] 7 1/2 in [19.1 cm] Ø6" 5 3/16 in [13.2 cm] ATER CS.) 6 in [15.2 cm] 33 1/16 in [84.0 cm] REAR FLUE OUTLET (OPTIONAL) AIR INTAKE 2 3/4 in [7.0 cm] 10 7/8 in [27.6 cm] CENTER OF GRAVITY RSUB-27-D
20
Embed
DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 300Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-300-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
4 7/8 in [12.4 cm]
29 5/16 in [74.4 cm]
11 1/16 in [28.1 cm]
22 1/8 in [56.2 cm]
4 7/16 in [11.3 cm]
31 7/8 in [81.0 cm]
7 1/2 in [19.1 cm]
Ø6"
5 3/16 in [13.2 cm]
2 1/2" WATER(2 PLCS.)
Ø3/4"NAT & LP
5 in [12.6 cm] 6 in
[15.2 cm]
33 1/16 in [84.0 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE
27 3/16 in [69.1 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
12 15/16 in [32.9 cm]
19 1/16 in [48.4 cm]
10 7/8 in [27.6 cm]
CENTER OFGRAVITY
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
4 7/8 in [12.4 cm]
29 5/16 in [74.4 cm]
11 1/16 in [28.1 cm]
22 1/8 in [56.2 cm]
4 7/16 in [11.3 cm]
31 7/8 in [81.0 cm]
7 1/2 in [19.1 cm]
Ø6"
5 3/16 in [13.2 cm]
2 1/2" WATER(2 PLCS.)
Ø3/4"NAT & LP
5 in [12.6 cm] 6 in
[15.2 cm]
33 1/16 in [84.0 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE
27 3/16 in [69.1 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
12 15/16 in [32.9 cm]
19 1/16 in [48.4 cm]
10 7/8 in [27.6 cm]
CENTER OFGRAVITY
RSUB-27-D
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 300Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 3.8*
Input BTU/hr. 300,000 / 88 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 400Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-400-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
RSUB-28-D
15 3/8 in [39.1 cm]
15 in [38.1 cm]
3 13/16 in [9.7 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
4 7/8 in [12.4 cm]
5 in [12.6 cm]
29 5/16 in [74.4 cm]
14 5/16 in [36.4 cm]
28 5/8 in [72.7 cm]
4 7/16 in [11.3 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø6"
5 3/16 in [13.2 cm]
Ø3/4"NAT & LP
6 in [15.2 cm]
33 1/16 in [84.0 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE
33 11/16 in [85.6 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
19 1/16 in [48.4 cm]
14 1/16 in [35.7 cm]
CENTER OFGRAVITY
15 3/8 in [39.1 cm]
15 in [38.1 cm]
3 13/16 in [9.7 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
4 7/8 in [12.4 cm]
5 in [12.6 cm]
29 5/16 in [74.4 cm]
14 5/16 in [36.4 cm]
28 5/8 in [72.7 cm]
4 7/16 in [11.3 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø6"
5 3/16 in [13.2 cm]
Ø3/4"NAT & LP
6 in [15.2 cm]
33 1/16 in [84.0 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE
33 11/16 in [85.6 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
19 1/16 in [48.4 cm]
14 1/16 in [35.7 cm]
CENTER OFGRAVITY
Dominator 400 model water heater not available for sale in the U.S. market due to DOE regulations.
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 400Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 3.8*
Input BTU/hr. 399,000 / 117 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
Dominator 400 model water heater not available for sale in the U.S. market due to DOE regulations.
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 600Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-600-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
RSUB-29-D
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
4 7/8 in [12.4 cm]
5 in [12.6 cm]
29 5/16 in [74.4 cm]
17 9/16 in [44.6 cm]
35 1/8 in [89.2 cm]
4 7/16 in [11.3 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø8"
5 3/16 in [13.2 cm]
Ø2 1/2" WATER(2 PLCS.)
Ø1"NAT & LP
7 in [17.8 cm]
33 1/16 in [84.0 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE
40 3/16 in [102.1 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
12 15/16 in [32.9 cm]
19 1/16 in [48.4 cm]
17 1/4 in [43.9 cm]
CENTER OFGRAVITY
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
4 7/8 in [12.4 cm]
5 in [12.6 cm]
29 5/16 in [74.4 cm]
17 9/16 in [44.6 cm]
35 1/8 in [89.2 cm]
4 7/16 in [11.3 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø8"
5 3/16 in [13.2 cm]
Ø2 1/2" WATER(2 PLCS.)
Ø1"NAT & LP
7 in [17.8 cm]
33 1/16 in [84.0 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE
40 3/16 in [102.1 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
12 15/16 in [32.9 cm]
19 1/16 in [48.4 cm]
17 1/4 in [43.9 cm]
CENTER OFGRAVITY
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 600Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 3.8*
Input BTU/hr. 600,000 / 176 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 750Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-750-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
RSUB-30-D
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
Ø2 1/2" WATER(2 PLCS.)
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø8"[20.32 cm]
4 7/16 in [11.3 cm]
41 5/8 in [105.7 cm]
20 13/16 in [52.9 cm]
5 3/16 in [13.2 cm]
8 in [20.3 cm] REAR FLUE OUTLET
(OPTIONAL)
AIR INTAKE(REAR MOUNTOPTIONAL)
6 1/4 in [15.9 cm]
Ø1"NAT & LP
29 5/16 in [74.4 cm]
37 7/8 in [96.1 cm]
26 9/16 in [67.5 cm]
5 in [12.7 cm]
15 15/16 in [40.5 cm]
11 in [28.0 cm]
46 11/16 in [118.7 cm]
35 3/16 in [89.4 cm] 31 7/8 in
[80.9 cm]
2 3/4 in [7.0 cm]
19 in [48.3 cm]
12 15/16 in [32.9 cm]
20 5/16 in [51.5 cm]
CENTER OFGRAVITY
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
Ø2 1/2" WATER(2 PLCS.)
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø8"[20.32 cm]
4 7/16 in [11.3 cm]
41 5/8 in [105.7 cm]
20 13/16 in [52.9 cm]
5 3/16 in [13.2 cm]
8 in [20.3 cm] REAR FLUE OUTLET
(OPTIONAL)
AIR INTAKE(REAR MOUNTOPTIONAL)
6 1/4 in [15.9 cm]
Ø1"NAT & LP
29 5/16 in [74.4 cm]
37 7/8 in [96.1 cm]
26 9/16 in [67.5 cm]
5 in [12.7 cm]
15 15/16 in [40.5 cm]
11 in [28.0 cm]
46 11/16 in [118.7 cm]
35 3/16 in [89.4 cm] 31 7/8 in
[80.9 cm]
2 3/4 in [7.0 cm]
19 in [48.3 cm]
12 15/16 in [32.9 cm]
20 5/16 in [51.5 cm]
CENTER OFGRAVITY
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 750Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 5.9*
Input BTU/hr. 750,000 / 220 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 900Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-900-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
RSUB-31-D
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
6 5/16 in [16.1 cm]
29 5/16 in [74.4 cm]
24 1/16 in [61.1 cm]
48 1/8 in [122.2 cm]
6 7/16 in [16.4 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø10"
5 3/16 in [13.2 cm]
Ø2 1/2" WATER(2 PLCS.)
Ø1"NAT & LP
10 in [25.4 cm]
31 5/8 in [80.3 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE(REAR MOUNTOPTIONAL)
53 3/16 in [135.2 cm] 18 15/16 in
[48.1 cm]
11 in [28.0 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
19 1/16 in [48.4 cm]
23 5/8 in [60.1 cm]
12 15/16 in [32.9 cm]
CENTER OFGRAVITY
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
6 5/16 in [16.1 cm]
29 5/16 in [74.4 cm]
24 1/16 in [61.1 cm]
48 1/8 in [122.2 cm]
6 7/16 in [16.4 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø10"
5 3/16 in [13.2 cm]
Ø2 1/2" WATER(2 PLCS.)
Ø1"NAT & LP
10 in [25.4 cm]
31 5/8 in [80.3 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE(REAR MOUNTOPTIONAL)
53 3/16 in [135.2 cm] 18 15/16 in
[48.1 cm]
11 in [28.0 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
19 1/16 in [48.4 cm]
23 5/8 in [60.1 cm]
12 15/16 in [32.9 cm]
CENTER OFGRAVITY
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 900Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 5.9*
Input BTU/hr. 900,000 / 264 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 1050Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-1050-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
RSUB-32-D
15 3/8 in [39.1 cm]
15 in [38.1 cm]
3 13/16 in [9.7 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
6 5/16 in [16.1 cm]
29 5/16 in [74.4 cm]
29 3/16 in [74.1 cm]
58 3/8 in [148.3 cm]
4 3/16 in [10.7 cm]
8 7/8 in [22.5 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø10"
5 3/16 in [13.2 cm]
Ø2 1/2" WATER(2 PLCS.)
Ø1 1/4"NAT & LP
10 in [25.4 cm]
31 5/8 in [80.3 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE(REAR MOUNTOPTIONAL)
63 7/16 in [161.2 cm]
20 7/8 in [53.1 cm]
11 in [28.0 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
12 15/16 in [32.9 cm]
28 11/16 in [72.9 cm]
19 1/16 in [48.4 cm]
CENTER OFGRAVITY
15 3/8 in [39.1 cm]
15 in [38.1 cm]
3 13/16 in [9.7 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
6 5/16 in [16.1 cm]
29 5/16 in [74.4 cm]
29 3/16 in [74.1 cm]
58 3/8 in [148.3 cm]
4 3/16 in [10.7 cm]
8 7/8 in [22.5 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
Ø10"
5 3/16 in [13.2 cm]
Ø2 1/2" WATER(2 PLCS.)
Ø1 1/4"NAT & LP
10 in [25.4 cm]
31 5/8 in [80.3 cm]
REAR FLUE OUTLET(OPTIONAL)
AIR INTAKE(REAR MOUNTOPTIONAL)
63 7/16 in [161.2 cm]
20 7/8 in [53.1 cm]
11 in [28.0 cm]
35 3/16 in [89.4 cm]
2 3/4 in [7.0 cm]
12 15/16 in [32.9 cm]
28 11/16 in [72.9 cm]
19 1/16 in [48.4 cm]
CENTER OFGRAVITY
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 1050Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*
Input BTU/hr. 1,050,000 / 308 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 1350Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-1350-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
RSUB-33-E
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
7 13/16 in [19.8 cm]
29 5/16 in [74.4 cm]
35 11/16 in [90.6 cm]
71 3/8 in [181.3 cm]
4 3/16 in [10.7 cm]
13 3/8 in [34.0 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
2 3/4 in [7.0 cm]
5 3/16 in [13.2 cm]
Ø1 1/4"NAT & LP Ø12"
12 in [30.5 cm]
30 in [76.3 cm]
AIR INTAKE(REAR MOUNTOPTIONAL)
27 3/8 in [69.6 cm]
11 in [28.0 cm]
76 7/16 in [194.2 cm]
35 3/16 in [89.4 cm]
12 15/16 in [32.9 cm]
19 1/16 in [48.4 cm]
35 13/16 in [91.0 cm]
CENTER OFGRAVITY
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
7 13/16 in [19.8 cm]
29 5/16 in [74.4 cm]
35 11/16 in [90.6 cm]
71 3/8 in [181.3 cm]
4 3/16 in [10.7 cm]
13 3/8 in [34.0 cm]
29 5/8 in [75.2 cm]
7 1/2 in [19.1 cm]
2 3/4 in [7.0 cm]
5 3/16 in [13.2 cm]
Ø1 1/4"NAT & LP Ø12"
12 in [30.5 cm]
30 in [76.3 cm]
AIR INTAKE(REAR MOUNTOPTIONAL)
27 3/8 in [69.6 cm]
11 in [28.0 cm]
76 7/16 in [194.2 cm]
35 3/16 in [89.4 cm]
12 15/16 in [32.9 cm]
19 1/16 in [48.4 cm]
35 13/16 in [91.0 cm]
CENTER OFGRAVITY
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 1350Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*
Input BTU/hr. 1,350,000 / 396 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 1500Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-1500-8The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
RSUB-34-F
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 1500Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*
Input BTU/hr. 1,500,000 / 440 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 1950Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-1950-8The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
RSUB-35-F
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
7 13/16 in [19.8 cm]
29 5/16 in [74.4 cm]
48 11/16 in [123.7 cm]
97 3/8 in [247.3 cm]
4 3/16 in [10.7 cm]
26 3/8 in [67.0 cm]
5 3/16 in [13.2 cm]
Ø2"NAT & LP
Ø2 1/2" WATER(2 PLCS.)
Ø12"
7 1/2 in [19.1 cm]
29 5/8 in [75.2 cm]
30 in [76.3 cm]
REAR FLUEOUTLET(OPTIONAL)
AIR INTAKE(REAR MOUNTOPTIONAL)
102 7/16 in [260.3 cm]
40 3/8 in [102.6 cm]
11 in [28.0 cm]
35 3/16 in [89.4 cm]
14 in [35.6 cm]41 11/16 in
[105.9 cm]
2 3/4 in [7.0 cm]
47 7/8 in [47.9 cm]
19 1/16 in [19.1 cm]
12 15/16 in [12.9 cm]
50 9/32 in [50.3 cm]
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
7 13/16 in [19.8 cm]
29 5/16 in [74.4 cm]
48 11/16 in [123.7 cm]
97 3/8 in [247.3 cm]
4 3/16 in [10.7 cm]
26 3/8 in [67.0 cm]
5 3/16 in [13.2 cm]
Ø2"NAT & LP
Ø2 1/2" WATER(2 PLCS.)
Ø12"
7 1/2 in [19.1 cm]
29 5/8 in [75.2 cm]
30 in [76.3 cm]
REAR FLUEOUTLET(OPTIONAL)
AIR INTAKE(REAR MOUNTOPTIONAL)
102 7/16 in [260.3 cm]
40 3/8 in [102.6 cm]
11 in [28.0 cm]
35 3/16 in [89.4 cm]
14 in [35.6 cm]41 11/16 in
[105.9 cm]
2 3/4 in [7.0 cm]
47 7/8 in [47.9 cm]
19 1/16 in [19.1 cm]
12 15/16 in [12.9 cm]
50 9/32 in [50.3 cm]
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 1950Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*
Input BTU/hr. 1,950,000 / 572 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
† Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer. Cupronickel heat exchanger should be considered.
CODE OPTIONS
CSD-1UTC Lockout/Reset Control Manual Reset LWCO
Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.
DOMINATOR 2100Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
SDOM-2100-8The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
RSUB-36-F
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
7 13/16 in [19.8 cm]
29 5/16 in [74.4 cm]
51 15/16 in [131.9 cm]
103 7/8 in [263.8 cm]
4 3/16 in [10.7 cm]
29 7/8 in [75.9 cm]
5 3/16 in [13.2 cm]
Ø2"NAT & LP
Ø2 1/2" WATER(2 PLCS.)
Ø12"
7 1/2 in [19.1 cm]
29 5/8 in [75.2 cm]
REAR FLUEOUTLET(OPTIONAL)
30 in [76.3 cm]
AIR INTAKE(REAR MOUNTOPTIONAL)
43 5/8 in [110.9 cm]
11 in [28.0 cm]
108 15/16 in [276.8 cm]
35 3/16 in [89.4 cm]
14 in [35.6 cm]
44 15/16 in [114.1 cm]
2 3/4 in [7.0 cm]
12 15/16 in [32.9 cm]
19 1/16 in [48.4 cm]
51 1/16 in [129.7 cm]
15 3/8 in [39.1 cm]
15 in [38.1 cm]
4 1/4 in [10.8 cm]
26 9/16 in [67.5 cm]
37 7/8 in [96.2 cm]
5 in [12.6 cm]
7 13/16 in [19.8 cm]
29 5/16 in [74.4 cm]
51 15/16 in [131.9 cm]
103 7/8 in [263.8 cm]
4 3/16 in [10.7 cm]
29 7/8 in [75.9 cm]
5 3/16 in [13.2 cm]
Ø2"NAT & LP
Ø2 1/2" WATER(2 PLCS.)
Ø12"
7 1/2 in [19.1 cm]
29 5/8 in [75.2 cm]
REAR FLUEOUTLET(OPTIONAL)
30 in [76.3 cm]
AIR INTAKE(REAR MOUNTOPTIONAL)
43 5/8 in [110.9 cm]
11 in [28.0 cm]
108 15/16 in [276.8 cm]
35 3/16 in [89.4 cm]
14 in [35.6 cm]
44 15/16 in [114.1 cm]
2 3/4 in [7.0 cm]
12 15/16 in [32.9 cm]
19 1/16 in [48.4 cm]
51 1/16 in [129.7 cm]
REP FIRM
SUBMITTED BY
JOB NAME
ARCHITECT
ENGINEER
CONTRACTOR
DATE
DOMINATOR 2100Category I or Category III Appliance
(see Installation and Operation Manual for venting information)
A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515
BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*
Input BTU/hr. 2,100,000 / 616 kW Min. Gas Pressure Required 7" WC**
The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.
† Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer. Cupronickel heat exchanger should be considered.