Top Banner

of 40

Dolgu Duvar Deney Resimleri

Apr 03, 2018

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 7/28/2019 Dolgu Duvar Deney Resimleri

    1/40

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    2/40

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    3/40

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    4/40

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    5/40

    41

    3.3.3 Masonry PrismsTwo types of masonry prisms were constructed and tested in this study. One type was

    three-course high with a height to thickness ratio of 3.3 as shown in Figure 3.20.

    Figure 3.20 3-High Prisms testing arrangement

    A total of 12 prisms of this type including 3 hollow, and 9 fully grouted were constructed.

    The prisms were tested for the compressive strength, the modulus of elasticity, and thestress-strain relationship of the masonry in accordance with ASTM C1314-07 Standard

    test methods for compressive strength of masonry prisms.

    The second type of masonry prisms, referred to as square prisms, was 4-course high, 2-

    course wide with a height to thickness ratio of 4.4. A total of 27 prisms of this type

    including 9 hollow, 9 partially grouted, and 9 fully grouted were prepared. The partially

    grouted prisms were grouted on the two outer cells of the prisms. They were tested for

    compressive strength under three loading conditions. Vertical compression refers to a

    loading direction which was perpendicular to the bed joint; horizontal compression

    indicates that the loading was applied in parallel to the bed joint; and the diagonal

    compression was to load the specimen in diagonal direction. The diagonal, vertical and

    horizontal loading conditions are shown in Figure 3.21. These prisms were tested to have

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    6/40

    42

    a better understanding of the effect of loading direction on the compressive strength of

    masonry assemblage. All prisms were cured together with the walls and tested at

    approximately the same time as the walls. LVDTs were mounted at the front and the back

    of all the square prisms to obtain deformation readings. The gauge lengths of the LVDTs

    were kept at approximately 200 mm. Horizontal and vertical specimens had a similar

    testing procedure to the three-high prisms. For testing in the diagonal direction, two

    custom-made supports were used for the loaded corners where each support was a V-

    shaped joint inside a rectangular box designed to encase the corners and provide a

    straight surface for testing as shown in Figure 3.22.

    Diagonal Vertical Horizontal

    Figure 3.21 Loading Conditions of Compression Test for Square Prisms.

    Figure 3.22 Diagonal prism test loading shoe.

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    7/40

    48

    4.2.2.2MortarType S mortar was used in the construction of wall infills. Three batches of mortar were

    used in the building of specimens and mortar cubes were made from each batch. A total

    of twenty-six 50mm mortar cubes were tested for their 28-day strength according to CSA

    A179-04 (2004) Mortar and grout for unit masonry. For batch 1 mortar, nine cubes were

    tested for 7-day strength as well for quality control purposes. Figure 4.3 shows an

    example of the failure of mortar cubes under compressive testing where most of the

    mortar cubes showed a conical shear or pyramidal shape failure. The compressive

    strength for mortar cubes are summarized in Table 4.3 where the mean 28-day

    compressive strength of all the mortar cubes tested was 13.6MPa. The average 28-day

    compressive strengths were 15.1MPa from batch 1 (BM1) and 9.6MPa for Batch 2

    (BM2) mortar cubes. Mortar cubes from batch 3 (BM3) attained compressive strength of

    19.6MPa. The COVs of all 3 batches mortar strength were well within the specified limit

    of 15%. It should be pointed out that BM2 mortar strength was lower than the minimum

    28-day strength (12.5MPa) specified in CSA A179 - 04 (2004) for type S mortar under

    laboratory conditions.

    Figure 4.3 Failure of mortar cubes under compressive testing

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    8/40

    51

    Figure 4.4 Failure of grout cubes under compressive testing

    Figure 4.5 Load-displacement diagram of a grout cube in compressive

    0

    5

    10

    15

    20

    25

    0 1 2 3 4 5

    Load(kN)

    Displacement (mm)

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    9/40

    53

    while the grouted column remained practically intact. These are common failure modes

    in prisms as reported by Drysdale and Hamid (2005).

    Vertical crack (face-shell) Vertical crack (web) Face-shell spalling

    Figure 4.6 Failure of 3-high prisms under compressive loading.

    Net areas were used for the calculation of compressive strength of prisms. The net area

    for the 3-high ungrouted prisms is the outside shell-area of the prism as shown in Figure

    4.7. The net area of the 3-high fully grouted prisms was the gross area less the web area

    of the unit block as shown in Figure 4.8.

    Figure 4.7 Net area for 3-high ungrouted prisms

    Figure 4.8 Net area for 3-high grouted prisms

    The compressive stress of the BP1 ungrouted and grouted prisms were 12.7MPa and

    8.0MPa, a difference of 37% with the difference in net areas of 49%. The higher

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    10/40

    55

    For the horizontally loaded prisms, net area was calculated to be the same as the

    vertically loaded prisms with respect to the different grouting situations. For diagonally

    loaded prisms, the net area used for the fully grouted diagonally loaded prisms was the

    rectangular area where the prisms were in contact with the loading shoes as shown in

    Figure 4.11. The net area of the hollow prisms was taken as the faceshell area contained

    within the loading shoe. For partially grouted diagonal loaded prisms, the average areas

    between the fully grouted and hollow diagonally loaded prisms were used to calculate the

    net areas.

    Figure 4.11 Diagonally loaded prisms net area

    To study the behavior of the prisms in different loading directions, a stress-strain curve of

    each prism specimen was obtained and the Modulus of Elasticity, Em, was also

    determined. It is a common practice to express Em in terms of compressive strength, f'm,

    obtained with loading applied perpendicular to the prism bed joint. In this study, this

    practice was followed and thus Em in the following tables is expressed in terms of f'mV,

    compressive strength of the vertically loaded prisms. Figure 4.12 shows the stress-strain

    curves of partially grouted prisms loaded in three directions. The full-set of stress-strain

    curves can be found in Appendix A. It can be seen that partially grouted prisms loaded in

    the horizontal direction displayed the lowest modulus of elasticity. However, diagonally

    loaded partially grouted prisms had the highest modulus of elasticity. As expected,

    Loading

    Shoe

    Net Area

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    11/40

    41

    4 Preliminary System Identification

    This chapter deals with the results of the component and system tests performed before the start

    of the actual shake-table experiments involving the application of earthquake records. The

    component tests include standard concrete compression tests and concrete split tension tests on

    concrete cylinders fabricated during the construction of the test structure. These component tests

    also include masonry compression, shear and bending tests performed on masonry prisms and

    masonry panels constructed at the same time as the URM infill wall in the test structure. The

    system tests are a series of pull-back (snap-back) tests on the test structure at different stages of

    completion of the test structure configuration, namely before and after building the URM infill

    wall and after the placement of additional mass on the test structure. The results of these

    preliminary tests are used to gather the required data for calibrating and validating analytical

    models of the test structure as discussed in Chapter 7 and to document the state of the test

    structure at the beginning of the shake-table experiments as a point of reference when discussing

    the results of these experiments in Chapter 6.

    4.1 COMPONENT TESTS

    4.1.1 Concrete Cylinder Compression Tests

    A total of 30 test cylinders are prepared after each concrete placement for foundation, columns,

    and beams and slab in accordance with ASTM C 837-99. The cylinders are kept in the same

    environmental conditions as the test structure. Three uniaxial compression tests are performed

    for each patch of concrete at different times to monitor the strength gain with time, the last of

    which was performed on the day before the start of the shake-table experiments. Mean values

    and the coefficient of variation (COV) of each test group are reported in Tables 4.1 and 4.2,

    respectively. It can be observed that the compressive strength of the concrete on the day of the

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    12/40

    42

    test is on average 22% higher than its 28-day compressive strength. No clear conclusion can be

    made on the COV for the test results due to the small sample size, namely three for each reported

    value. However, based on the results in Table 4.2 and for the purpose of practical reliability

    analyses as in Chapter 8, one may consider a mean value of the COV of the concrete

    compressive strength of 4.5%. The test setup and the resulting relationship of the mean strength-

    gain with time for the used concrete are shown in Figure 4.1. The mean strength values obtained

    at the time of the shake-table test are used in the computational modeling of the test structure

    (Chapter 7) and for system identification purposes (Chapter 6).

    Table 4.1 Mean uniaxial concrete compression test results.

    Structural

    element

    First group

    [ksi (MPa)]

    Second group

    [ksi (MPa)]

    Third group (start of

    shake-table experiments)[ksi (MPa)]

    Foundation 3.27 (22.5)@11 day 4.15 (28.6)@28 day 4.98 (34.3)@567 day

    Columns 3.04 (20.9)@5 day 4.36 (30.1)@33 day 5.40 (37.2)@552 day

    Beams and slab 3.28 (22.6)@10 day 4.53 (31.2)@32 day 5.56 (38.3)@538 day

    Table 4.2 COV of uniaxial concrete compression test results.

    Structural

    element

    First group

    (%)

    Second group

    (%)

    Third group (start of

    shake-table experiments)

    (%)Foundation 7.6@11 day 5.6@28 day 1.1@567 day

    Columns 4.0@5 day 4.6@33 day 9.1@552 day

    Beams and slab 5.4@10 day 1.6@32 day 1.4@538 day

    0 100 200 300 400 500 6000

    1

    2

    3

    4

    5

    6

    Concrete

    strength[ksi]

    Time [days]

    Beams and slab

    Coulmns

    Foundation0

    10

    20

    30

    40

    [

    MPa]

    (a) Test setup (b) Concrete compressive strength-gain with time

    Fig. 4.1 Concrete compressive strength test.

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    13/40

    43

    4.1.2 Concrete Cylinder Split Tension Tests

    Concrete cylinder split tension tests are performed on three concrete cylinders constructed using

    the columns concrete batch. The tests are carried out at the start of the shake-table experiments.

    The split tension tests conform to ASTM C496 and are used to identify the tensile strength of

    concrete cylinders as defined in Equation 4.1.

    dl

    Pfct

    2= (4.1)

    where P is the maximum load at failure, l and d are the length and diameter of the cylindrical

    specimen, respectively. The failure is sudden, with a vertical splitting crack across the section of

    the specimen. The individual results as well as their mean value and COV are summarized in

    Table 4.3. The mean value of the tensile splitting strength of concrete (about 8% of the

    compressive strength) is used for the computational modeling of the test structure as described in

    Chapter 7.

    Table 4.3 Concrete split tension tests.

    SpecimenMaximum load

    [kips (kN)]ctf

    [psi (MPa)]

    1 48.8 (217) 431 (2.97)

    2 50.4 (224) 446 (3.08)

    3 46.5 (207) 411 (2.83)

    Mean 48.6 (216) 429 (2.96)

    COV 3.3% Fig. 4.2 Concrete split tension test setup.

    4.1.3 Masonry Compression Tests

    Three masonry prisms are constructed at the time of the construction of the URM infill wallaccording to the requirements of the ASTM C 1314. The prisms are capped and secured to two

    steel plates on top and bottom using Hydrocal gypsum cement, and tested under uniaxial

    compression 28 days after the wall construction. Both the axial load and the axial displacement

    (measured between the two steel plates) of the masonry prisms are recorded during these axial

    compression tests. Figure 4.3 shows the configuration of the masonry prism tests as well as the

    typical failure mode consisting of vertical splitting and crushing. The stress-strain curves for the

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    14/40

    44

    three prisms are shown in Figure 4.4 with the individual results, as well as their mean values and

    COV, summarized in Table 4.4. In this table mof , mE , mo , and mu indicate the compressive

    strength of the masonry, the modulus of elasticity measured as the secant modulus at 75% of the

    compressive strength, and strain corresponding to maximum compressive stress and ultimate

    strain of masonry corresponding to the residual stress value of momu ff 15.0= , respectively, as

    shown in the insert of Table 4.4.

    (a) Test setup (b) Typical failure mode

    Fig. 4.3 Masonry prism tests.

    0 0.005 0.01 0.0150

    0.5

    1

    1.5

    2

    2.5

    3

    Strain

    Stress[ksi]

    0

    5

    10

    15

    20

    [MPa]

    Specimen 3

    Specimen 2

    Specimen 1

    Fig. 4.4 28-day compression stress-strain curves for masonry prisms.

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    15/40

    45

    Table 4.4 28-day uniaxial compression test results for masonry prisms.

    Specimen mof

    [ksi (MPa)]

    mE

    [ksi (GPa)]mo mu

    1 2.31 (16.0) 948 (6.54) 0.0038 0.0120

    2 2.31 (16.0) 812 (5.60) 0.0035 0.00863 2.76 (19.0) 935 (6.45) 0.0040 0.0120

    Mean 2.46 (17.0) 898 (6.19) 0.0038 0.0109

    COV 10% 8.3% 6.1% 18% Tension Compressionmo

    mu

    mof

    muf

    mE

    mo0.75 f

    Tension Compressionmo

    mu

    mof

    muf

    mE

    mo0.75 f

    Tension Compressionmo

    mu

    mof

    muf

    mE

    Tension Compressionmo

    mu

    mof

    muf

    mE

    mo mu

    mof

    muf

    mo

    mo mumu

    mofmof

    mufmuf

    mEmE

    mo0.75 fmo0.75 f

    4.1.4 Masonry Diagonal Tension (Shear) Tests

    In order to determine the shear strength of masonry, diagonal tension (shear) tests in accordance

    with ASTM E519 are performed on three specimens. The used specimens are 2 -5"2-5" (75

    cm75 cm) instead of the usual 44 (122 cm122 cm) as specified in ASTM E519 in order to

    facilitate the construction and handling of the specimens. This reduction in size is suggested and

    allowed by ASTM E519. The specimens are loaded in compression along the diagonal, and the

    applied load and its corresponding vertical and horizontal deformations (along the diagonals) are

    recorded. The loading causes almost diagonal cracking (vertical splitting in the testing position)

    along an axis parallel to the direction of loading corresponding to a rapid drop in the load-

    carrying capacity of the specimen. The force-deformation plots corresponding to the vertical and

    horizontal diagonal deformations of the three tested specimens are shown in Figures 4.5 (a) and

    (b), respectively. From these plots, note that the horizontal deformation (corresponding to the

    crack opening of the vertical splitting cracks) is one order of magnitude higher than the vertical

    deformation.

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    16/40

    46

    0 0.01 0.02 0.03 0.04 0.05 0.06 0.070

    5

    10

    15

    20

    25

    30

    35

    40

    45

    Vertical deformation [in]

    Verticalforce[kip

    s]

    Specimen 1

    Specimen 2

    Specimen 3

    0 0.5 1 1.5

    0

    50

    100

    150

    200

    [kN]

    [mm]

    0 0.1 0.2 0.3 0.4 0.5 0.6 0.70

    5

    10

    15

    20

    25

    30

    35

    40

    45

    Horizontal deformation [in]

    Verticalforce[kip

    s]

    Specimen 1

    Specimen 2

    Specimen 3

    0 5 10 15

    0

    50

    100

    150

    200

    [mm]

    [kN]

    (a) Deformation along vertical diagonal

    axis of specimen

    (b) Deformation along horizontal diagonal

    axis of specimen

    Fig. 4.5 Diagonal force-deformation plots for masonry shear tests.

    The shear strength of the masonry vf is obtained using Equation 4.2.

    eff

    vA

    Pf = (4.2)

    where P is the applied peak compressive diagonal force on the specimen and effA is the gross

    sectional area of the specimen along its diagonal direction calculated as th2 where h and t

    are the side length and thickness of the square specimen, respectively. The applied peak

    compressive force and its corresponding shear strength for the three specimens as well as the

    mean value (about 11% of the masonry compressive strength) and COV are presented in Table

    4.5. The test setup and a typical failure mode are shown in Figure 4.6.

    Table 4.5 Masonry shear test results.

    SpecimenPeak compressive

    load [kips (kN)]

    Shear strength

    [psi (MPa)]

    1 44.2 (197) 283 (1.95)2 41.1 (183) 263 (1.81)

    3 38.0 (169) 243 (1.68)

    Mean 41.1 (183) 263 (1.81)

    COV 7.6%

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    17/40

    47

    (a) Test setup (b) Typical failure mode

    Fig. 4.6 Masonry diagonal tension (shear) test.

    4.1.5 Masonry Bending Test

    To determine the tensile strength of the masonry assembly, a bending test on 2 -5"2-5" (75

    cm75 cm) specimen is performed. The test setup is such that the middle third of the span of the

    specimen is subjected to pure bending moment (i.e., no shear) as shown in Figure 4.7(a).

    Assuming an elastic-brittle behavior for masonry in tension, the tensile strength of the masonry

    assembly can be calculated from Equation 4.3:

    6/

    6/2tb

    LP

    S

    Mft == (4.3)

    where is the applied bending moment, S is the section modulus, P is the total applied peak

    vertical load, L is the span, and b and t are the width and thickness of the specimen,

    respectively. The total applied peak vertical load recorded during the test is 978=P lbs (4.35

    kN) which corresponds to 5.69=tf psi (479 kPa) representing only 3% of the masonry

    compressive strength and 26% of its shear strength. This relatively low value, compared to those

    in more homogeneous materials, such as concrete, is attributed to the mode of failure of themasonry composite (two-phase) material (Loureno 1996), in Figure 4.7(b), which is dominated

    by a single vertical crack along the weak plane of the mortar-brick interface.

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    18/40

    48

    (a) Test setup (b) Typical failure mode

    Fig. 4.7 Masonry bending test.

    4.2 SNAP-BACK TESTS

    Pull-back (snap-back) tests are performed on the test structure before and after the URM infill

    wall construction to determine the stiffness, natural frequency, and damping ratio of the

    structural system before starting the shake-table experiments. These tests are separately

    conducted for both the longitudinal (north-south) and transverse (east-west) directions of the test

    structure. It is to be noted that the torsional response of this symmetric test structure is not of

    interest; therefore, asymmetric snap-back tests of the longitudinal and transverse directions are

    not considered in this study. For each test, the structure is pulled in one direction by applying 3

    8 kips (1336 kN) lateral force, depending on the stiffness of the test structure, using lever hoist

    (come-along), and then released suddenly to allow free vibration. The floor acceleration and

    displacements are measured during both the loading (pulling) phase and the free vibration phase

    of the test. The force-displacement results of the pull test are used to obtain an estimate of the

    stiffness of the test structure. The floor acceleration responses during the free vibration after

    releasing the pulling force, both in the time and frequency domains, are analyzed and used to

    estimate the natural period of vibration of the test structure and the corresponding damping ratio.A typical configuration and sample test results of the snap-back test is shown in Figure 4.8. The

    results in this figure refer to the second snap-back test in the north-south and east-west directions

    after building the URM infill wall, post-tensioning of the columns, and installation of additional

    mass on the RC slab. The complete results of the snap-back tests are presented in Appendix B.

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    19/40

    70 4. Experimental tests on FRP strengthened masonry wall panels

    also includes a comparison of the reinforcement schemes, and comparisons of the

    results with other tests from the literature.

    4.2 Experimental programThe Diagonal Tension/Shear Test involves subjecting a square section of ma-

    sonry, with height and length both equal to 1.2 m, to a compressive load applied

    along the diagonal. A schematic of the test is shown in Figure 4.1a. A photograph

    of the test is shown in Figure 4.1b.

    (a) Test schematic (b) Setup URM-1

    Figure 4.1: The Diagonal Tension/Shear Test

    The panels were constructed from solid clay masonry units with nominal di-

    mensions 230 mm long, 110 mm wide and 76 mm high. Five batches of mortar

    were used in the construction of the panels, all having a mix ratio of 1:1:6 (ce-

    ment:lime:sand by volume). The mortar joints were 10 mm thick. These are the

    same material specifications as used for the pull tests presented in Chapter 3.

    The mortar batches used to construct each panel are presented in Table 4.1.

    The flexural tensile bond strength of each mortar batch was determined using the

    bond wrench test, AS3700-2001, Standards Australia (2001c). The bond wrench

    test is described in further detail in Section 5.3.1. The average flexural tensile bondstrength (coefficient of variation in brackets) of each mortar batch is also presen-

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    20/40

    122 5. Finite element modelling

    Table 5.1: Summary of all bond wrench results

    Test Mortar batch Bond Strength (MPa) COV (%)Compression test 1:1:6 mortar 1.22 31

    (Section 5.3.2) Han (2008) specimens

    (1:1:6 + air entrainer) 0.176 -

    Torsion test Series 1 (1:1:6 + air entrainer) 0.14 26

    (Section 5.3.3) Series 2 (1:1:6) 1.74 11

    Pull tests 1 1.84 23

    (Section 3.2.1) 2 1.73 22

    3 1.22 31

    Wall Panel tests 1 1.25 51

    (Section 4.2) 1+W 0.65 34

    2 0.49 37

    2+W 0.29 46

    3 0.47 47

    3+W 0.31 57

    4 0.57 48

    5 1.26 32

    5+W 0.41 59

    5.3.2 Compression tests on masonry prismsCompression tests on 7-brick high masonry prisms were used to determine the

    elastic properties of the brick unit and mortar joint, as well as the compressive

    strength of the masonry. Five prisms were constructed using the same clay brick

    and mortar specification used to construct the pull test specimens and the wall

    panels tested in diagonal tension/shear. The flexural bond strength of these speci-

    mens was 1.22 MPa (COV 31%), determined using AS 3700 bond wrench test (Stan-

    dards Australia, 2001c). This value was approximately equal to the bond strengths

    of the strongest panels tested (URM-1, URM-2 and H4A - see Table 4.1 in Chap-

    ter 4).

    The compression specimens were constructed and tested in accordance with

    AS3700 Appendix C (Standards Australia, 2001b). Specimens were constructed 7

    bricks high to achieve a height-to-thickness ratio greater than 5 to minimise theinfluence of platen restraint. A photograph of the test is shown in Fig. 5.7.

    Potentiometers were placed on both sides of the specimen to measure the dis-

    placement across a mortar joint and across 3 bricks to calculate the strain in the

    mortar joint and masonry respectively (as recommended by Drysdale et al. (1994)).

    Potentiometers were not used to measure the displacement within a single brick

    unit because they were not sensitive enough to measure the small brick displa-

    cement. Potentiometers were mounted onto brackets that were screwed onto the

    specimen at fine target points to allow the gauge lengths for displacement measu-

    rement to be determined accurately.

    To improve the determination of the elastic modulus from the compressiontest each specimen was loaded and then unloaded three times before being loa-

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    21/40

    5.3 Compression tests on masonry prisms 123

    Figure 5.7: Compression test setup

    ded to failure. Specimens were loaded to approximately 40 % of their predicted

    peak load, before unloading, to capture the elastic loading range and minimise

    non-recoverable damage. Specimen 1 was loaded to 200 kN before unloading (ba-

    sed on an estimate ofPc = 500 kN); specimens 2-4 were loaded to 260 kN before

    unloading (40% ofPc specimen 1); and specimen 5 was loaded to 300 kN before

    unloading (approximately 40% of average ofPc for first four specimens). The dis-

    placements recorded from the second, third and final load cycles were averaged

    and used in the calculations to determine the elastic modulus values of the ma-

    sonry and the mortar (displacements recorded from the first load cycle were igno-

    red). All of the compression tests were stopped once the ultimate load was reachedto avoid damaging the potentiometers.

    All of the specimens failed by crushing in the mortar joint and vertical cracking

    through the front and back faces of the brick units. The ultimate load (Pc) and cor-

    responding maximum compressive stress (fc), masonry strain at fc, and the elastic

    modulus of the mortar (Emor) and masonry (Emas) are shown in Table 5.2. The

    elastic modulii of the mortar (Emor) and masonry (Emas) were determined as the

    gradients of the compressive stress-strain curves (for mortar and masonry respec-

    tively) between 5 and 33% of the maximum compressive strength (Drysdale et al.,

    1994).

    The average elastic modulus of a single brick unit Eunit was determined indi-rectly using the average values ofEmor and Emas and by considering compatibility

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    22/40

    124 5. Finite element modelling

    of displacements between masonry, brick unit and mortar joint. This calculation

    was required because brick unit displacement (used to calculate strain) was not re-corded. The total masonry displacement is equal to the sum of the displacement

    of the units and mortar. The masonry displacement across 3 bricks and 3 mortar

    joint is equal to:

    mas= 3unit+3mor (5.6)

    The displacements are calculated using:

    mas=PLmas

    EmasA(5.7)

    unit=PLunitEunitA

    (5.8)

    mas=PLmor

    EmorA(5.9)

    Where P=compression load, A=bedded area of prism, Lmas=258 mm, Lunit=76

    mm, Lmor=10 mm. By substituting Equations 5.7, 5.8, and 5.9 into Equation 5.6,

    Eunit was determined as 27592 MPa.

    Table 5.2: Compression test results (bond strength = 1.22 MPa)

    Specimen Pc (kN) fc (MPa) Masonry strain at fc Emor (MPa) Emas (MPa)1 664.88 26.28 0.0013 4801 17698

    2 651.73 25.76 0.0030 8047 18895

    3 970.51 38.36 0.0027 5067 17909

    4 894.86 35.37 0.0025 2650 18157

    5 873.10 34.51 0.0023 4854 18415

    Average 811.12 32.06 0.0025 5084 18215

    The average shear modulus values of the brick unit (Gunit) and mortar (Gmor)

    were calculated as 11497 MPa and 2118 MPa respectively, using Equation 5.10 and

    Equation 5.11. A Poissons ratio (

    ) equal to 0.2 was adopted for both the brick unitand the mortar (Loureno, 1996a).

    Gunit=Eunit

    2(1+)(5.10)

    Gmor=Emor

    2(1+)(5.11)

    The experimentally determined elastic properties of the brick unit and mortar

    joint were valid for the actual dimensions of the unit and the joint. As expanded

    units and zero-thickness mortar joints were used in the FE model, adjustments

    to the elastic properties were required to achieve an equivalent overall elastic res-ponse. A method that alters the elastic properties of the interface elements and

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    23/40

    5.3 Compression tests on masonry prisms 125

    leaves the enlarged unit properties untouched is described in Rots (1997) and Lou-

    reno (1996a). The normal elastic stiffness (kn) and the shear elastic stiffness (ks)of the mortar joint interface element were altered using Equation 5.12 and Equa-

    tion 5.13, respectively, where hmor = thickness of mortar joint = 10 mm. The nor-

    mal elastic stiffness (kn) was calculated as 623 N/mm3 and the shear elastic stiff-

    ness (ks) was calculated as 260 N/mm3.

    kn=EunitEmor

    hmor(EunitEmor)(5.12)

    ks=GunitGmor

    hmor(GunitGmor)(5.13)

    In addition to the maximum compressive stress (fc), the equivalent plastic re-

    lative displacement (p) and the compressive fracture energy (Gc) were also re-

    quired to model compression failure. The equivalent plastic relative displacement

    (p) was calculated using Equation 5.14 as 0.024 mm in order to obtain a total ma-

    sonry strain of 0.25% at fc (Table 5.2) (Loureno, 1996a). In Equation 5.14 hunit is

    the height of the brick unit = 76 mm.

    p=

    0.0025fc

    1

    Eunit+

    1

    kn(hunit+hmor)

    fc (5.14)

    As each compression test was stopped just after the ultimate load was reached the

    compressive fracture energy was not recorded. The compressive fracture energy

    was estimated as 25 N/mm using Equation 5.15 (Loureno, 1996a).

    Gc= 15+0.43fc0.0036f2c (5.15)

    To estimate the elastic and compression properties for masonry panels with a

    weaker bond strength (the average bond strength for some of the panels tested was

    as low as 0.29 MPa) the results of Han (2008) were used. Han tested five masonry

    prisms constructed using a similar clay brick (as the current investigation), but a

    weaker mortar was used. This mortar consisted of cement:lime:sand in propor-

    tions of 1:1:6 by volume with eight times the recommended dose of air entrainingagent added to deliberately create low bond strength. The bond strength of these

    specimens was 0.176 MPa. The average values of the ultimate load (Pc), maximum

    compressive stress (fc), and the elastic modulus of the mortar (Emor), masonry

    (Emas) and brick unit(Eunit) are shown in Table 5.3. The masonry strain at fc was

    not reported.

    Table 5.3: Compression test average results from Han (2008) (bond strength = 0.176

    MPa)

    Pc (kN) fc (MPa) Emor (MPa) Emas (MPa) Eunit (MPa)

    516 20.0 2772 18135 35360

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    24/40

    126 5. Finite element modelling

    From these tests the values of fc = 20 MPa and Emor = 2772 MPa were adop-

    ted to represent masonry with a bond strength of 0.176 MPa. For consistency, theelastic modulus of the brick unit (Eunit) from the previously described test series

    (equal to 27592 MPa) was kept. The input properties required for the mortar joint

    interface elements were calculated the same way as described previously, and are

    shown in Table 5.4. For the calculation ofp, the masonry strain at fc was assu-

    med as 0.2% (Loureno, 1996a). The input properties required for the mortar joint

    interface elements determined for masonry with a bond strength of 1.22 MPa, are

    also shown in Table 5.4.

    Table 5.4: FE model input properties determined from compression tests

    Property Bond strength = 0.176 MPa Bond strength = 1.22 MPakn (N/mm

    3) 308 623

    ks (N/mm3) 128 260

    fc (MPa) 20 32

    Gc (N/mm) 22 25

    p (mm) 0.010 0.024

    5.3.3 Torsion testTo characterise the shear behaviour of the mortar joint the torsion test (shown

    in Figure 5.8), developed by Masia et al. (2006, 2007), was used. In this test anannular masonry specimen, which contains a single bed joint (Figure 5.8a), is sub-

    jected to combined compressive stress (normal to the bed joint) and torsion. The

    torsion test produces close to uniform distributions of normal and shear stress,

    thus allowing the shear behaviour at a point to be characterised.

    As part of the current investigation a set of torsion tests were performed on

    specimens constructed using the same brick and mortar as the wall panel tests.

    The specimens were prepared by coring a complete annular specimen through the

    height of a pre-cast masonry couplet. These specimens were prepared differently

    from previous torsion tests, reported in Masia et al. (2007). In Masia et al.s tests the

    specimens were prepared by coring annular sections from two separate solid units

    first, and then bonding them together with mortar. After testing, and then analy-

    sing the results of the current investigation (joints cast before coring) it was found

    that the joint shear strengths were lower than expected when compared to joints

    that were cast after coring (as in Masia et al. (2007)). The reduced joint strength

    was thought to be caused by damage to the joint during the coring procedure. The

    results from the current investigation were unreliable and therefore were not used

    for the characterisation of the shear behaviour. The results of tests conducted by

    Masia et al. (2007) were used instead.

    Torsion tests by Masia et al. (2007)

    This section outlines the specimens tested by Masia et al., the testing proce-dure they used, and their results. Torsion tests were performed on specimens

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    25/40

    37

    Figure 3.4 Triplet Test setup

    Figure 3.5 Shear stress vs. Lateral compressive stress graph (Average shear

    stresses)

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    26/40159

    CHAPTER 6

    PANEL TESTS

    6.1 GENERALBefore the frame tests, two series of panel tests were conducted to obtain

    information about the behavior of the strengthened masonry walls. The information

    gathered in panel tests were used to model the frame tests in analytical evaluation.

    In these tests, square masonry walls having dimensions of 700 700 mm and width

    of 69 mm were loaded in diagonal direction.

    Test set-up was prepared between two heavy concrete support blocks. Test

    specimen was placed on thin metal plates parallel to floor. Steel plate was oiled and

    sat on ball roller supports to ensure friction free movement of panel specimens.

    Steel heads were placed to corners of the wall specimen in the diagonal direction

    and were attached with gypsum. Dial gages were placed in six directions to measure

    displacements on the wall. Test set-up is illustrated in Figures 6.1 and 6.2.

    Figure 6.1 Test Set-up of Panel Tests

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    27/40160

    Figure 6.2 General View of Panel Tests

    6.2 PANEL TESTS6.2.1 First Series Panel Tests

    In the scope of the first series, 12 tests were conducted. First, 6 reference wall

    specimens, composed of 3 non-plastered and 3 plastered, were tested. Then, 6

    plastered wall specimens strengthened in different ways were tested. Plastered wall

    specimens were produced of 10 mm plaster thickness on both sides. 10 mm

    thickness of mortar with 2% volumetric ratio of steel fibers was applied on one side

    of 3 specimens. To the remaining 3 specimens, 20 mm thickness of mortar with 2%

    volumetric ratio of steel fibers was applied again on one side. Specimen properties

    are given in Table 6.1.

    Mix proportions of the mortar used for the first series brick laying are presented in

    Table 6.2 and mix proportions of the mortar used for plastering are given in Table

    6.3.Mix proportions for 1 m3 of the mortar with steel fibers applied on the plaster of

    the first series panel specimens are shown in Table 6.4.

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    28/40176

    Figure 6.31 Views of SF2P-1

    Figure 6.32 Views of SF2P-2

    Figure 6.33 Views of SF2P-3

    Figure 6.34 View of 2SNPP-1 Figure 6.35 View of 2SNPP-2

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    29/40178

    Figure 6.44 View of 2SSF1P-3 Figure 6.45 View of 2SSF2P-1

    Figure 6.46 Views of 2SSF2P-2

    Figure 6.47 View of 2SSF1PD-1 Figure 6.48 View of 2SSF1PD-2

    Figure 6.49 View of 2SSF1PD-3 Figure 6.50 View of 2SSF2PD-1

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    30/40

    Figure5:Bondwrenchtestapparatusandjointfailure

    2.5.Masonrytensilebondstrength(Splittingtest)Becausethefailureofthewallettesalsoinvolvedsomeverticalsplitting,forlatermodellingpurposes,

    itwas

    also

    useful

    to

    determine

    the

    transverse

    strength

    of

    the

    masonry

    composite.

    This

    was

    achieved

    using thesplitting testreportedbyAli (7),seeFigure6,performedonspecimenswhichwerebuilt

    accordingtoreference(7)andwerecuredinairinthelaboratory.Usingthisprocedure,thetransverse

    strengthisgivenby:

    T

    CF

    Dt

    where/ 4

    hlD

    andhandlarethespecimenheightandwidth,respectively.Inaddition,tdenotes

    the

    specimen

    thickness;F

    is

    the

    applied

    load

    andC

    a

    constant

    of

    0.648.

    This

    constant

    depends

    on

    brick/jointstiffnessandthechosenvaluewasbasedonmoduliofelasticityratioofbrickandmortar,

    Eb/Em,ofapproximately2,seealso(7).

    Using this approach, the mean transverse tensile strength of the five specimens was found tobe

    0.62MPawithacoefficientofvariationof22.4%.DetailedresultsaregiveninTableA4.

    Figure6:Tensilebondtestapparatusandsplittingfailure

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    31/40

    TableA7 inAppendixA shows the specimendimensions, failure loadsaswellas the compressive

    strengthandmodulusofelasticity(asasecantmodulusattheloadof30%oftheultimate)forallfour

    specimens.ThemeanvalueforthemodulusofelasticityEmobtainedfromtestsonspecimens1and4

    was6.81GPa.Themeanvalueforthemasonrycompressivestrengthobtainedfromthetestswasonly

    ahalfof thatobtained from theprism tests inaccordancewith theAustraliancode (seeTableA6).

    Apartfromanysizeeffects,itisalsopossiblethatthespecimensmayhavebeendamagedduringthe

    cuttingoutprocess.The failuremodesof these specimens (Figure9)alsodiffered from thatof the

    masonrytripletsindicatingthatthetypeofspecimenmayhavealsoplayedarole.

    Figure9:Compressiontestoncutoutspecimenanditsfailure

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    32/40

    The objectives of these small-scale tests were (1) to understand the impact of a thin layer

    of ECC on unreinforced masonry, (2) to examine the performance of different ECC

    retrofit schemes, and (3) to help develop a retrofit scheme for unreinforced masonry

    infills in non-ductile reinforced concrete frames.

    The small-scale tests were compression tests, flexural tests and triplet (shear) tests

    (Figure 3.2). Compression tests of masonry prisms were conducted representing the

    compression strut of a masonry infill under in-plane lateral loading. Flexural tests of

    brick beams using a quarter point bending configuration with the constant moment region

    intended to approximately represent direct tension (in particular in the ECC), were

    performed to investigate the approximate response of tension struts in the masonry infill.

    Triplet specimens with ECC in the joints between the bricks were tested in shear to

    evaluate the ECC-brick bond in shear. With the small-scale tests different reinforcement

    ratios, as well as ECC-masonry bonding techniques were examined.

    (a) (b) (c)

    Figure 3.2. Schematic of the small-scale test set-ups (a) compression test, (b) flexural

    test, and (c) triplet test.

    3.2. Compression Experiments

    Masonry prisms with and without retrofit were fabricated and tested in compression. The

    procedure followed for the fabrication of the specimens, the design of the different

    ______________________________________________________________________________________Chapter 3 Small-Scale Tests

    40

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    33/40

    research had triple-wythe masonry infills and the intention was to use a 39 mm (1.5 in.)

    ECC layer for its retrofit. A thickness of 39 mm (1.5 in.) is the maximum thickness that

    the sprayable ECC was reported to reach when sprayed on a vertical surface (Kim et al.,

    2003) at the time these experiments were designed.

    (a) (b) (c) (d) (e) (f) (g)Figure 3.3. Schematic of the different variables tested, a) Tall plain specimen, b) Short

    plain specimen, c) ECC retrofit, d) ECC retrofit with stitch dowels, e) lightly reinforced

    ECC, f) lightly reinforced ECC with stitch dowels, and g) heavily reinforced ECC with

    stitch dowels. All dimensions are in mm.

    3.2.2. Fabrication of Masonry Prisms

    All specimens tested in compression had four mortar joints no thicker than 13 mm (0.5

    in.) each. As indicated in Figure 3.3, the specimens of group (a) were taller than those of

    groups (b) through (g). The tall plain prisms had a height of approximately 343 mm (13.5

    in.). The specimens of groups (b) through (g) had a height of approximately 267 mm

    (10.5 in.) with the top and bottom bricks being cut down to 20 mm (0.8 in.) in thickness.

    The height of the short specimens was controlled by the maximum specimen height that

    the Forney compression tester at Stanford could accommodate when modified to give the

    full compressive stress-strain response of the specimen. However, due to limitations in

    the free rotation of the loading plates of the compression tester when modified, all

    specimens were tested in the Powell laboratory, at The University of California, San

    ______________________________________________________________________________________Chapter 3 Small-Scale Tests

    42

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    34/40

    Diego.

    A professional mason from a local masonry company (Walton & Sons Masonry Inc.),

    was hired to build the brick specimens in order to ensure real practice conditions (Figure

    3.4). All fabrication was performed in one day in the laboratory of the John A. Blume

    Earthquake Engineering Center at Stanford University.

    200 mm200 mm

    Figure 3.4. Fabrication of masonry specimens for compression tests.

    The materials used were:

    Yellow clay bricks 94 mm x 58 mm x 196 mm (3.7 in. x 2.3 in. x 7.7 in.), grade

    MW, type FBS, and manufactured to meet ASTM C216-10.

    Mortar consisting of 1 part cement (Type I/II), 1 part lime (Type S) and 5 parts

    sand (Oly 1) by volume. The above types of cement, lime and sand were

    recommended by the masonry company. This type of mortar is similar to Type

    N which uses a 1:1:6 mix and results in a mortar with low compressive strength

    (ASTM C270-10).

    The type of bricks and mortar used were recommended by the Professional Advisory

    Panel (PAP) of the project to represent the mechanical properties of the materials used for

    the construction of masonry infills of a building that served as the project's prototype

    ______________________________________________________________________________________Chapter 3 Small-Scale Tests

    43

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    35/40

    Table 3.13. ECC-brick interface shear strength of TEB specimens.

    Joints are named based on Figure 3.79.

    TEB specimen Joint 1 Joint 2 f's ECC-brick

    1 1' 2 2' MPa (psi )1 R R* S S* 2.08 (302)

    2 R R* S S* 2.38 (346)

    3 S* S R* R 1.72 (250)

    4 R R* S S* 2.00 (289)

    5 R R* S S* 2.08 (302)

    Average f 's ECC-brick = 2.05 (298)

    S.D. f's ECC-brick = 0.21 (31)

    * toweled surface

    94 mm

    58 mm

    94 mm

    58 mm

    Figure 3.80. TE triplet specimen: Brick-ECC interface failure

    94 mm

    58 mm

    94 mm

    58 mm

    3.81. TEB triplet specimen: Brick shear failure

    ______________________________________________________________________________________Chapter 3 Small-Scale Tests

    128

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    36/40

    42

    Figure 2.32: equipment set up for vertical compression tests: the steel

    profiles fitted onto the Metrocom 3000 kN press (left), a wall ready to be

    crashed inside the press (right)

    Figure 2.33: diagonal compression tests set up, steel supports for

    diagonal compression tests (left), wall ready to be crashed inside the

    press (right)

    Figure 2.34: suspension system of the upper steel profile

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    37/40

    47

    Figure 2.45: equipment for compression test parallel to holes on hollowbrick walls (front and back view of the panel)

    Figure 2.46: equipment for compression test orthogonal to holes on

    hollow brick walls (front and back view of the panel)

    Figure 2.47: equipment for diagonal on hollow brick walls (front and

    back view of the panel)

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    38/40

    48

    Figure 2.48: equipment for compression test parallel to holes on half-full

    brick walls (front and back view of the panel)

    Figure 2.49: equipment for compression test orthogonal to holes on half-

    full brick walls (front and back view of the panel)

    Figure 2.50: equipment for diagonal compression test half-full brick

    walls (front and back view of the panel)

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    39/40

    Plugging this raw data into the formula, along with the measurements and parameters as defined

    by the equation, the tensile strengths are found, shown in Table 2.

    Table 2: Bond Wrench Flexural Strength Results

    Gross Area flexural Tensile Strength (psi)

    PRISM

    6(H + H)

    I$

    ( + )

    I

    Tensile Strength

    1 142.4 7.2 135.2 psi

    12 109.2 5.8 103.4 psi

    15 72.2 4.1 84.8 psi

    17 162.6 8.1 154.5 psi

    26 93.06 5.1 88.0 psi

    28 113.5 6.0 107.5 psi

    average 112.2 psi

    Taking the average of these values, neglecting the values of Prisms 8 and 15, yield an average of

    112.2 psi for the tensile strength of the mortar joints. However, there is a wide range of values,

    anywhere from 84 psi to 154 psi, which indicates that the accuracy of these values is not certain.

    3. SHEAR TEST

    a. MethodsThe second major material testing conducted is the shear test in which a triplet of bricks aremade with the center brick protruding on the top, as shown in Fig. 5.

    Prior to being tested, the triplets are capped using hydrostone and following ASTM 1552-07standards (Standard Practice for Capping Concrete Masonry Units). This is done so that the two

    bottom prisms are flat against the floor

    and the top of the prism is perfectly flat.

    To ensure the top is flat, a level is used inall directions to find the best possible fit of

    the capping with the triplets.

    However, it was found that the friction

    forces between the hydrostone capping

    and the bottom plate impacted the resultsof the testing. As a result, a steel plate was

    placed under the hydrostone, along with a

    small roller. The roller was used to eliminate the friction forces at the bottom of the triplets, andthe steel plate, which is hot glued directly onto the hydrostone, prevented the roller from digging

    in and crushing the hydrostone capping. This set up is shown in a close up view on Fig. 7.

    Figure 5: Shear Test Setup

  • 7/28/2019 Dolgu Duvar Deney Resimleri

    40/40

    The triplets are then tested in the MTS 500k machine where the

    central brick is subjected to a downward force while the entire

    prism has a horizontal load at various stresses. An in-housedesign for the test arrangement was used, as there are no

    ASTM Standards regarding this shear test. Following some

    tweaking to the apparatus and the construction, the shear test asused in the experimented is shown in Fig. 6.

    Stresses exerted on the mortar joints are 50 psi, 100 psi, 150psi, and 200 psi. Using the formula:

    = (2)

    the forces to be exerted in compression on the prisms are

    determined as shown in Table 3. This axial compressive stressis generated by tightening screws on plates surrounding the

    triplets, using an external load cell (shown in blue in Fig. 6)to measure the amount of force placed axially. Levels areused to ensure that the plates and the prisms are both as close

    to perpendicular with the base plate as possible. Wooden

    blocks, shown in Fig. 6, are placed on the sides as safetyprecautions, preventing the metal plates or the prisms from

    hitting the MTS machine upon the sudden failure of the

    mortar joint. In almost all the triplet tests, only one side of themortar joint failed while the other remained intact.

    Table 3: Shear Test Axial Forces

    Stress (psi) Force (kips)50 1.172

    100 2.344

    150 3.416

    200 4.688

    The results from this test are recorded through a data acquisition system which records both axialand shear forces. The shear displacements are recorded using a pair of pots located on the center

    brick, as shown in Fig. 7 in addition to the recording of the distance being pushed downward

    onto the prism. This is then post-processed and plotted to form coherent and readable graphs.

    b. ResultsThe results of the shear data is in forces and displacements; this is then converted to shear vs.

    displacement, as shown in Fig. 8.

    Figure 6: Shear Testing

    Figure 7: Shear Test, a close up

    view of the plates and the rollers