Designed for uses requiring a flexible power cables. For portable or fixed installations. Leads for motors generators, batteries, jumper cables. Deep well Submersible Pump Cable. Other industrial applications DLO 2000V RHH/RHW-2 2000V RW90/RW90-TC 1000V UL 44, UL 1685, IEEE-1202, CSA c22.2 No. 38 CSA C22.2 No. 230 ASTM B-172, ASTM B-174, ASTM B-33, AAR RP-588, RP-586 —————— Portable Power Cables 90°C UL C(UL) MSHA Industrial Grade APPLICATIONS CONSTRUCTION Nominal voltage RHH/RHW-2 600 and 2000V, RW-90 CSA 1kV, DLO 2kV Conductors Annealed flexible stranded tinned copper, ASTM B-172, ASTM B-174, ASTM B-33 Separator All sizes except for 14AWG have tape separator between conductor and insulation Insulation Ethylene-propylene rubber (EPR),UL,CSA, ICEA, AAR RP-588, 90°C Jacket Black heavy duty CPE thermosetting compound, ICEA S-95- 658 NEMA WC-70, AAR-586 Bending radius For fixed minimum 4xD Minimum 6 x D, D- outer diameter of cable Features UL listed RHH/RHW-2 600V and 2000V for black jacket. Rated 2kV DLO, 1kV RW90. 90°C (dry), 90°C (wet). Ozone, sunlight, oil, grease, weather, chemical and abrasion resistant. Rated RW90-TC (Tray Cable) for sizes 1/0 and larger. MSHA, VW-1, SUN RES, FOR CT USE for sizes 1/0AWG and larger and for black jacket. Limited Smoke (LS) ST1 in accordance with (UL) 1685. CSA listed RW90, RW90-TC (for black jacket ) 1kV
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Designed for uses requiring a flexible power cables. For portable or fixed installations. Leads for motors generators, batteries, jumper cables. Deep well Submersible Pump Cable. Other industrial applications
Jacket Black heavy duty CPE thermosetting compound, ICEA S-95-658 NEMA WC-70, AAR-586
Bending radius For fixed minimum 4xD Minimum 6 x D, D- outer diameter of cable
FeaturesUL listed RHH/RHW-2 600V and 2000V for black jacket. Rated 2kV DLO, 1kV RW90. 90°C (dry), 90°C (wet). Ozone, sunlight, oil, grease, weather, chemical and abrasion resistant. Rated RW90-TC (Tray Cable) for sizes 1/0 and larger. MSHA, VW-1, SUN RES, FOR CT USE for sizes 1/0AWG and larger and for black jacket. Limited Smoke (LS) ST1 in accordance with (UL) 1685. CSA listed RW90, RW90-TC (for black jacket ) 1kV
ApprovalsUL: E193954(CPE jacket) RHW-2 90°C wet and dry, VW-1 Sun Res, for 1/0 and larger ST1, FT4 IEEE 1202, for CT use C(UL): E193954 Type RW90 EP,1kV FT1, CSA: 1101269, LL 103932:205591, RW90°C FT1, FT4, -40°C, for 1/0AWG and larger, Oil Res, Tray Cable, Sun Res, MSHA: P-7K-268080-01
Technical and Electrical CharacteristicPartNumber
Power Conductor Size
PowerConductor
ConductorDiameter
Nominalinsulation
Nominaljacket
Overall diameter Weight Ampacityat 30°C
Stranding thickness thickness minimum approx maximum in air
Ampacity Based on single conductor in free air, 30°C ambient temperature, 90°C conductor temperature Per NEC Table 310.17For ambient temperature other than 30°C, multiply the allowable ampacities shown above by the appropriate factor shown below.
Correction factors for ambient temperature
Temperature of air°C 21-25 26-30 31-35 36-40 41-45 46-50 51-55 56-60 61-70 71-80
TF CABLE (size) 90C DLO 2KV P-7K-268080-01-MSHA - E193954 (UL) RHW–2 2KV VW-1 ST1 SUN RES - CSA 205591 RW90 EPR 1000V -40C FT1 FT4 TC SR Oil Res
All the information in this document – including tables and diagrams – is given in good faith and believed to be correct at the time of publication. The information does not constitute a warranty nor representation for which TELE-FONIKA Kable assumes legal responsibility. TELE-FONIKA Kable reserves rights to introduce changes to the document at any time