DISTRIBUTION SYSTEMThe primary mission of Power Delivery System
is to deliver power to electrical consumers at their place of
consumption and in ready to use form. That means, It must;Place of
consumption Be dispersed throughout the service territory in rough
proportion to customer location. Have sufficient capacity to meet
the customer peak demand and energy demand. provide highly reliable
delivery to its customerready to use form Deliver the power at the
utilization voltage required for electrical appliances and
equipment. provide stable voltage quality to its customer And of
course to meet the above missions at least possible
cost.Distribution system is the electrical system between the
transmission system and the consumers meter. The integral part of a
distribution system is Distributor:- A distributor is a conductor
from which tapings are taken for supply to the consumers. The
current through a distributor is not constant.As the power is moved
from generation (large bulk source) to customer (small demand
amounts) it is first moved in bulk quantity at high voltage and as
power is dispersed throughout the service territory, it is
gradually moved down to lower voltage levels. See fig. 1. It is
more economical to move power at high voltage. The high voltage
lines: while potentially economical, cost a great deal more than
low voltage lines, but have a much greater capacity. They are only
economical if one truly needs the giant size.
Utilization voltage: is useless for the transmission of power.
The application of these voltages for anything more than very local
distribution at the neighborhood level results in unacceptably high
electrical losses, severe voltage drops, and sky-high equipment
cost.
Fig 1: power system overviewWhat is Transmission And What is
Distribution?By voltage Class: Transmission: 66 kV -1100kV
Distribution:33kV and below (some country up to 132 kV is
categorized as distribution.)By Function: Transmission:
Transmission of bulk power Distribution:includes utilization
voltage and sources for these including transformer & their
source.By Configuration: Transmission: often designed and operates
in network Distribution:often designed and operates radially.By
Design point of view: Transmission: grid status mainly the power
and distance Distribution: Consumers demand and location
The Distribution System Equipments & Terminology: Service
Wire (Or Secondary Distribution or LT/LV lines): The conductor
which route power at utilization voltage within very close
proximity to customers. Service Transformer (Distribution
Transformer Also Called Distribution Substation):The transformer
which lowers the voltage at utilization voltage level. Load
Center:Area served by a particular service transformer. Primary
Distribution (Feeder,HT/HV Lines): The line (conductor) which feds
power at to the primary of service transformer.
SERVICE MAINSFEEDER
SUB-STATION
DISTRIBUTOR
Generally from feeders no tapping is taken to the consumers,
therefore loading of current of the feeders remains the same along
its length. Substation( Area Substation):Meeting point between
transmission & distribution line. The primary distribution
lines receives power at this juncture. Service Area: Service area
of a particular substation or feeder is the area served by that
particular substation or feeder Sub-transmission Line:The line
(conductor) which feds power to the primary of transformer at
substations. For distribution system, three-phase segments have a
tremendous advantage: The current only has to be sent out to the
load. There are no losses or voltage drop associated with bringing
the current back to the source in a completely balanced ckt. By
contrast, if serving a load from a single-phase Y-circuit
(one-phase and neutral) or two-phase delta ckt. Current flows goes
out of the load & then must return and there are losses
associated with each direction. Exactly how and where the
transition from 3-phase to 1-phase ckt. Takes place in a
distribution system depends on planner preferences and other
situations.
Primary & Secondary distribution system Primary Distribution
System:- It is the part of distribution system which operates at
voltages somewhat higher than general utilization Handles large
blocks of electrical energy than the average low voltage consumers
uses. Criterion for primary voltage level?? The most commonly used
primary distribution voltages are 33kv, 11 kv, 6.6 kv, and 3.3kv.
Due to economic consideration, normally primary distribution is
carried out by 3-phase 3-wire system ?? Secondary Distribution
System:- It is the part of distribution system at which the
ultimate consumers utilizes the electrical energy delivered to
them. It employs 400/230 V,3-phase 4-wire system in our case. The
supply for this secondary distribution is obtained from
distribution transformer.
Feeder Layout TypesThere are three fundamentally different ways
Radial, Loops Network
Radial SystemIn this system, separate feeders radiate from a
single substation and feed the distributors at one end only. The
biggest advantage of the radial system configuration, in addition
to its lower cost, is the simplicity of analysis. On debt side,
radial feeder systems are less reliable than loop or network
systems because there is only one path between the substation and
the customer. Thus if any elements along the path fails, a loss of
power delivery results. The end of the distributor nearest to the
feeding point will be heavily loaded. The consumers at the distant
end of a distributor would be subjected to serious voltage
fluctuations when the load on the distributor changes.Loop
SystemLoop system consists of a distribution design with two paths
between the sources (substations, service transformer) and
customer. The system is very reliable as each distributor is fed
via two feeders. This layout is often called European because this
configuration is preferred in Europe. Equipment is sized and each
loop is designed so that service can be maintained regardless of
where an open point is on the loop. In terms of complexity, a loop
feeder system is only slightly more complicated than a radial
system A loop must be able to meet all power and voltage drop
requirements when fed from only one end, not both. There are less
voltage fluctuations at consumers terminals. The major disadvantage
of loop systems is capacity and cost.Network system The
distribution network involves multiple paths between all points in
the network. Power flow between any two points is usually split
among several paths, and if a failure occurs it instantly and
automatically re-routes itself. Rarely does a distribution network
involve primary voltage level network design, in which all or most
of the switches between feeders are closed so that the feeder
system is connected between substations. They are much more
complicated, than other forms of distribution, and thus more
difficult to analyze. It increases the service reliability. Any
area fed from one generating station during peak load hours can be
fed from the other generating stations. This reduces reserve
capacity and increases efficiency of the system.
Urban Vs Rural ElectrificationThe major criterions for urban and
rural electrification are voltage regulation, current carrying
capacity of conductor and power loss in distribution system. The
special characteristics of the urban distribution system are;
Capacity limits design: Voltage drop & losses costs are seldom
a major concern requiring large no. of feeders. Loads are large
& often 3-phases Reliability requirements are above average
Route are restricted ie. land problemThe load density is very high
in urban. Thus the current flowing in the conductor is very high.
Before the criteria of voltage drop and power loss violation, the
current carrying capacity of the conductor may be less than the
current in the feeder. Thus, current carrying capacity of conductor
is the guiding factor for the load center size. If the load center
is chosen such that it doesnt exceed the current carrying capacity
of the conductor then it automatically doesnt violate voltage
regulation and power loss criterion. For these reasons there are
some common adaptations to work within these design constraints as
follows Use of Interlaced feeder ie two feeder in parallel. ( but
there can be limits in number of possible gate way due to space
limit in the junction due to higher insulation for more feeder.)
Maximum size cable is often installed: Very grid like planning: The
special characteristics of the Rural distribution system are;
Sparse load Loads vary from small single phase to medium sized
three phase. Distances are tremendous Losses are high Voltage drop
limits design Reliability requirements below average Often not
profitable
For these reasons following there are some common adaptations to
work within these design constraints. Application of higher voltage
than its typically used in urban or sub urban distribution to meet
higher load reach. Use of single phase feeders Extreme and
innovative measures are sometime need to apply eg. Use of very high
voltage with earth return. No provision for contingency back up of
feeders Radial feeders layouts are normally the rule.