ING. WILSON E. PARRA PINZON DISEÑO DE TANQUES SEPTICOS (V < 6000 L) NOTA: ESTA PLANTILLA DE DISEÑO SE HIZO EN BASE A LAS" NORMAS TECNICAS PARA EL DISEÑO, CONSTRUCCION E INSTALACION DE TANQUES SEPTICOS Y DISPOSICION DE EFLUENTES FINALES" DE LA C.D.M.B. DE BGA/COL NIVEL DEL TERRENO 0,10minimo Tapa removible Tapa Tapa removible 0,025 m MINIMO 0,30m ENTRADA 4" 0.075 NIVEL DE AGUA SALIDA 4" 0.15 0,4m TUBO 4" 0,4m H 0,20 m 0,60m 0,3m 0,60m B 0,60m L1 L2
15

DISEÑO DE TANQUES SEPTICOS

Nov 21, 2014

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

DISEÑO DE TANQUES SEPTICOS (V < 6000 L)

NOTA: ESTA PLANTILLA DE DISEÑO SE HIZO EN BASE A LAS" NORMAS TECNICAS PARA EL DISEÑO, CONSTRUCCION E

INSTALACION DE TANQUES SEPTICOS Y DISPOSICION DE EFLUENTES FINALES" DE LA C.D.M.B. DE BGA/COLOMBIA

NIVEL DEL TERRENO

0,10 minimo Tapa removible Tapa Tapa removible

0,025 m MINIMO

0,30m ENTRADA 4"

0.075 NIVEL DE AGUA SALIDA 4" →

0.15

0,4m TUBO 4" 0,4m

H

0,20 m

0,60m 0,3m 0,60m

B 0,60m

L1 L2

L

Page 2: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

CALCULO VOLUMEN Y DIMENSIONES

p NUMERO DE HABITANTES, COMIDAS, ALUMNOS, HUESPEDES, CARROS, ASIENTOS 100

TIPO DE ESTABLECIMIENTO TEMPLOS

q CONSUMO DE AGUA (Tablas 3 y 4 de las Normas Tecnicas para diseño de tanques septicos) 2 l/hab.dia

t TIEMPO DE RETENCION CALCULADO 0.81 dias

t TIEMPO DE RETENCION AUTORIZADO POR NORMA DE LA CDMB 1 dias

V VOLUMEN UTIL DEL TANQUE 200 litros

VL VOLUMEN DE ALMACENAMIENTO DE LODOS 60 litros

VT VOLUMEN TOTAL DEL TANQUE = V + VL CALCULADO 260 litros

VT VOLUMEN TORTAL DEL TANQUE AUTORIZADO POR LA CDMB (2000< VT< 12500 LITROS) 2000 litros

H PROFUNDIDAD (POR NORMA CDMB 1.20 m MINIMO) 1.20 m

A AREA UTIL TOTAL DEL TANQUE 1.67 m2

B ANCHO INTERNO (MINIMO NORMA CDMB= 0,80 m) 0.80 m Bmax = 2.40 m CUMPLE

L LONGITUD UTIL DEL TANQUE = 2.08 m Lmax = 3.20 m CUMPLE

L1 LONGITUD UTIL DEL PRIMER COMPARTIMIENTO 1.39 m

L2 LONGITU UTIL DEL SEGUNDO COMPARTIMIENTO 0.69 m

Page 3: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

P PENDIENTE DEL TERRENO 6.00 %

POR LA PENDIENTE, PARA DISPOSICION DEL EFLUENTE SE RECOMIENDA = CAMPO Y/O ZANJAS DE INFILTRACION

DISEÑO DEL FILTRO ANAEROBIO

0,10 m minimo

TAPA DE INSPECCION

VIENE DEL T.SEP.0,20 MIN

0,10 MIN NIVEL DE AGUA

VERTEDERO TIPO CAJA 0,10 m DE ANCHO SALIDA →0,30 MIN

HMEDIO FILTRANTE 0,80 MIN

FONDO FALSO CON ABERTURAS

ENTRADA 4" 0,30 MIN

L

V VOLUMEN UTIL DEL FILTRO ANAEROBIO CALCULADO 200 litros

V VOLUMEN UTIL DEL FILTRO ANAEROBIO APROBADO POR LA CDMB 1250 litros

H PROFUNDIDAD (POR NORMA CDMB: 1.40 m <H <1,80 m) 1.40 m

A AREA REQUERIDA POR EL FILTRO ANAEROBIO 0.89 m2

B ANCHO INTERNO (NORMA CDMB= 0,85 m MINIMO) 0.85 m Bmax = 4.20 m CUMPLE

L LONGITUD UTIL DEL FILTRO ANAEROBIO 1.05 m

NOTAS: 1. EL FONDO FALSO DEBERA TENER ABERTURAS DE 0,03 M ESPACIADAS 0,15 M ENTRE SI

2. EL MEDIO FILTRANTE PUEDEN SER PIEDRAS DE TAMAÑO DE 40 A 80 mm, DE PLASTICO, O ANILLOS DE PVC.

Page 4: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

3. PARA FILTROS ANAEROBIOS DE VOLUMEN MAYOR DE 12 m3, DEBERA PROVEERSE LA FORMA DE

REALIZAR EL MANTENIMIENTO, MEDIANTE UNA FORMA HIDRAULICA O MECANICA, INCLUYENDO EL

FALSO FONDO.

CAMPOS Y ZANJAS DE INFILTRACION

pf SEPARACION ENTRE EL FONDO DE LA ZANJA Y EL NIVEL FREATICO 1.25 m

P PENDIENTE DE LOS RAMALES DE DISTRIBUCION 0.20 %

tr TIEMPO REQUERIDO PARA QUE EL AGUA BAJE 2,5 CM EN LA PRUEBA DE INFILTRACION 15 min

R TASA DE INFILTRACION 54 l/m2.dia

Aa AREA DE ABSORCION 3.70 m2

d ANCHO MAXIMO DISPONIBLE PARA EL CAMPO DE INFILTRACION 2.00 m

TIPO DE SOLUCION RECOMENDADA POR ANCHO DISPONIBLE CAMPO DE INFILTRACION

n NUMERO DE RAMALES RECOMENDADO 3

Lr LONGITUD DEL AREA DE INFILTRACION 1.85 m

h PROFUNDIDAD MINIMA DEL RAMAL POR NORMA DE LA CDMB 0.60 m

e ESPESOR DE CUBIERTA MINIMO POR NORMA CDMB 0.30 m

X1 ESPACIAMIENTO MINIMO ENTRE RAMAL POR NORMA CDMB 1.00 m

LONGITUD MAXIMA DEL RAMAL DE DISTRIBUCION < 25 M CUMPLE

SEPARACION MINIMA ENTRE EL FONDO DE LA ZANJA Y EL NIVEL FRATICO = 1,20 M CUMPLE

Page 5: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

PENDIENTE MAXIMA DE LOS RAMALES DE DISTRIBUCION = 0,4% CUMPLE

DISEÑO DE POZOS DE ABSORCION

NIVEL DEL TERRENO

0,30m 0,60m

TAPA DE CONCRETO

VIENE DEL TANQUE SEPTICO 4"

H

LECHO DE GRAVA0,50m

0,05 m 1,20 m MINIMO 0,05 m

: "RELLENO DE GRAVA ALREDEDOR DE LA MAMPOSTERIA" 1,20 m MINIMO

NIVEL FREATICO

Page 6: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

H ALTURA DE LA PARED PERMEABLE 0.98 m

NOTA: EN CASO DE PRESENTARSE POZOS DEMASIADO PROFUNDOS, SE PUEDE OPTAR POR CONSTRUIR VARIOS POZOS

QUE TRABAJEN EN PARALELO. LA SEPARACION ENTRE POZOS DEBERA SER MAYOR DE 3 VECES EL DIAMETRO

DEL MAYOR DE LOS POZOS, Y NUNCA MENOR QUE 4m. EN POZOS DE MAS DE 6m DE PROFUNDIDAD, EL ESPACIO

MINIMO ENTRE POZOS DEBERA SER DE 6.0 m.

Page 7: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

Page 8: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

Page 9: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

INSTALACION DE TANQUES SEPTICOS Y DISPOSICION DE EFLUENTES FINALES" DE LA C.D.M.B. DE BGA/COLOMBIA

CONSUMO MINIMO 5

CUANDO HAY POZO O PILA EN LA CASA 25

ZONAS RURALES CON ALGUN ORDENAMIENTO COMUNAL 150

PARCELACIONES UBICADAS EN EL AREA METROPOLITANA 250

ESCUELA (SIN CAFETERIA, DUCHAS, GIMNASIO) 50

ESCUELA- INTERNADO 150

HOTELES 95

CAMPAMENTOS 30

RESTAURANTES 25

INSPECCION DE POLICIA 250

CENTRO DE SALUD 400

TEMPLOS 2

BALNEARIOS 80

EDIFICIOS PUBLICOS O COMERCIALES 50

FABRICAS EN GENERAL 70

Page 10: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

Page 11: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

Page 12: DISEÑO DE TANQUES SEPTICOS

ING. WILSON E. PARRA PINZON

tr(min) l/m2.dia

<1 160

2 130

3 110

4 101

5 89

10 66

15 54

30 35

45 26

50 23

60 23