2. Declaration of Conformity The device was tested according to the applicable standards. Con- formity was proofed. The declaration of conformity is available at the manufacturer METZ CONNECT GmbH. Notes Regarding Device Description These instructions include indications for use and mounting of the device. In case of questions that cannot be answered with these instructions please consult supplier or manufacturer. The indicated installation directions or rules are applicable to the Federal Republic of Germany. If the device is used in other countries it applies to the equipment installer or the user to meet the national directions. Safety Instructions Keep the applicable directions for industrial safety and prevention of accidents as well as the VDE rules. Technicians and/or installers are informed that they have to electrically discharge themselves as prescribed before installation or maintenance of the devices. Only qualified personnel shall do mounting and installation work with the devices, see section “qualified personnel”. The information of these instructions have to be read and under- stood by every person using this device. Symbols Warning of dangerous electrical voltage Danger means that non-observance may cause risk of life, grievous bodily harm or heavy material damage. Qualified Personnel Qualified personnel in the sense of these instructions are persons who are well versed in the use and installation of such devices and whose professional qualification meets the requirements of their work. This includes for example: • Qualification to connect the device according to the VDE specifications and the local regulations and a qualification to put this device into operation, to power it down or to activate it by respecting the internal directions. • Knowledge of safety rules. • Knowledge about application and use of the device within the equipment system etc. 3. Technical Data BACnet Interface Protocoll BACnet MS/TP Transmission rate 9600 ... 115200 Bd (factory setting 9600 Bd) Cabling RS485 two wire bus with voltage equalizing cable in bus / line topology; terminate with 120 Ohms Supply Operating voltage range 20 ... 28 V AC/DC (SELV) Current consumption 200 mA (AC) / 75 mA (DC) Relative duty cycle 100 % Input Voltage input 30 V AC/DC High-signal recognition >7 V AC/DC Output Output contacts 2 changeover contacts Switching voltage max. 250 V AC Continuous current max. 16 A / relay (80 A / 20 ms) Total current for all contacts 25 A Housing Dimensions WxHxD 2.0 x 2.8 x 3.0 in. (50 x 70 x 75 mm) Weight 126 g Mounting position any Mounting standard rail TH35 per IEC 60715 Mounting in series the maximum quantity of modules without space connected in line is limited to 15 or to a maximum power consumption of 2 Amps (AC or DC) per connection to the power supply. For any similar block of additional modules a sepa- rate connection to the power supply is mandatory. Material Housing Polyamide 6.6 V0 Terminal blocks Polyamide 6.6 V0 Cover plate Polycarbonate Type of protection (IEC 60529) Housing IP40 Terminal blocks IP20 Terminal blocks Supply and bus 4 pole terminal block max. AWG 16 (1,5 mm²) solid wireg max. AWG 18 (1,0 mm²) stranded wire Wire diameter min. 0.3 mm up to max. 1.4 mm (terminal block and jumper plug are included to each packing unit) Module connection Input/Output max. AWG 12 (4.0 mm²) solid wire max. AWG 14 (2.5 mm²) stranded wire Wire diameter min. 0.3 mm up to max 2.7 mm Protective circuitry polarity reversal protection of operating voltage polarity reversal protection of supply and bus Temperature range Operation -5 °C ... +55 °C Storage -20 °C ... +70 °C Display Operating / bus activity green LED Error indication red LED Status of the inputs & outputs yellow LED 5. Connection Diagram 4 3 C1 C1 22 21 24 BUS A- BUS B+ A1 A2 A- B+ A1 A2 A- B+ GND 24 V AC/DC 1 2 C1 C1 12 11 14 4. Wiring Diagram BUS A- BUS B+ 12 N.C. 11 C A2 /GND A1/+24 V BACnet MS/TP on RS-485 RISC - CPU 24 V 14 N.O. 22 N.C. 21 C 24 N.O. 1 2 C1 3 C1 4 C1 C1 GND +24 V J 7624/899299-04 Digital I/O Module BMT-DIO4/2 1108831326 1. Description The BACnet MS/TP module with 4 digital inputs and 2 relay outputs with manual control was developed for decentralized switching tasks. It is suitable for accommodating, for example, light switches and window contacts in a room, switching two light strips or controlling louvers. It can also be used to control 2 mo- torized fire dampers. With strong inductive loads, we recommend protecting the relay contacts with an RC element. The inputs can be used as contact or voltage inputs. The inputs and outputs can be switched and scanned by means of standard objects via a BAC- net client. The module address and the baud rate are set by means of two address switches on the front. Suitable for decentralized mounting in serial sub-distributor. METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany Phone +49 7702 533-0 | Fax +49 7702 533-433 Mounting instruction see www.metz-connect.com
4
Embed
Digital I/O Module BMT-DIO4/2 - Contemporary Controls1 2 C1 C1 12 11 14 4. Wiring Diagram BUS A-BUS B+ 12 N.C. A2 /GND 11 C A1/+24 V BACnet MS/TP on RS-485 RISC - CPU 24 V 14 N.O.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
2. Declaration of Conformity The device was tested according to the applicable standards. Con-formity was proofed. The declaration of conformity is available at the manufacturer METZ CONNECT GmbH.
Notes Regarding Device DescriptionThese instructions include indications for use and mounting of the device. In case of questions that cannot be answered with these instructions please consult supplier or manufacturer. The indicated installation directions or rules are applicable to the Federal Republic of Germany. If the device is used in other countries it applies to the equipment installer or the user to meet the national directions.
Safety InstructionsKeep the applicable directions for industrial safety and prevention of accidents as well as the VDE rules. Technicians and/or installers are informed that they have to electrically discharge themselves as prescribed before installation or maintenance of the devices.Only qualified personnel shall do mounting and installation work with the devices, see section “qualified personnel”. The information of these instructions have to be read and under-stood by every person using this device.
SymbolsWarning of dangerous electrical voltage Danger
means that non-observance may cause risk of life, grievous bodily harm or heavy material damage.
Qualified PersonnelQualified personnel in the sense of these instructions are persons who are well versed in the use and installation of such devices and whose professional qualification meets the requirements of their work. This includes for example: • Qualification to connect the device according to the VDE specifications and the local regulations and a qualification to put this device into operation, to power it down or to activate it by respecting the internal directions. • Knowledge of safety rules. • Knowledge about application and use of the device within the equipment system etc.
3. Technical DataBACnet InterfaceProtocoll BACnet MS/TPTransmission rate 9600 ... 115200 Bd (factory setting 9600 Bd)Cabling RS485 two wire bus with voltage equalizing cable in bus / line topology; terminate with 120 Ohms
SupplyOperating voltage range 20 ... 28 V AC/DC (SELV)Current consumption 200 mA (AC) / 75 mA (DC)Relative duty cycle 100 %
InputVoltage input 30 V AC/DCHigh-signal recognition >7 V AC/DC
OutputOutput contacts 2 changeover contactsSwitching voltage max. 250 V ACContinuous current max. 16 A / relay (80 A / 20 ms)Total current for all contacts 25 A
HousingDimensions WxHxD 2.0 x 2.8 x 3.0 in. (50 x 70 x 75 mm)Weight 126 gMounting position anyMounting standard rail TH35 per IEC 60715Mounting in series the maximum quantity of modules without space connected in line is limited to 15 or to a maximum power consumption of 2 Amps (AC or DC) per connection to the power supply. For any similar block of additional modules a sepa- rate connection to the power supply is mandatory.Material Housing Polyamide 6.6 V0 Terminal blocks Polyamide 6.6 V0Cover plate PolycarbonateType of protection (IEC 60529) Housing IP40 Terminal blocks IP20
Terminal blocksSupply and bus 4 pole terminal block max. AWG 16 (1,5 mm²) solid wireg max. AWG 18 (1,0 mm²) stranded wireWire diameter min. 0.3 mm up to max. 1.4 mm (terminal block and jumper plug are included to each packing unit)Module connection Input/Output max. AWG 12 (4.0 mm²) solid wire max. AWG 14 (2.5 mm²) stranded wireWire diameter min. 0.3 mm up to max 2.7 mm Protective circuitry polarity reversal protection of operating voltage polarity reversal protection of supply and bus
Temperature rangeOperation -5 °C ... +55 °CStorage -20 °C ... +70 °C
DisplayOperating / bus activity green LEDError indication red LEDStatus of the inputs & outputs yellow LED
5. Connection Diagram
4 3 C1 C1 22 21 24
BUS A-BUS B+
A1A2
A-B+
A1A2
A-B+
GND24 V AC/DC
1 2 C1 C1 12 11 14
4. Wiring Diagram
BUS A-
BUS B+
12 N.C.
11 CA2 /GND
A1/+24 V
BAC
net
MS/
TPon
RS-
485
RISC
- C
PU
24 V14 N.O.
22 N.C.
21 C24 N.O.
1
2C13C14C1
C1
GND+24 VJ
7624
/899
299-
04
Digital I/O Module BMT-DIO4/21108831326
1. DescriptionThe BACnet MS/TP module with 4 digital inputs and 2 relay outputs with manual control was developed for decentralized switching tasks. It is suitable for accommodating, for example, light switches and window contacts in a room, switching two light strips or controlling louvers. It can also be used to control 2 mo-torized fire dampers. With strong inductive loads, we recommend protecting the relay contacts with an RC element. The inputs can be used as contact or voltage inputs. The inputs and outputs can be switched and scanned by means of standard objects via a BAC-net client. The module address and the baud rate are set by means of two address switches on the front.Suitable for decentralized mounting in serial sub-distributor.
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | GermanyPhone +49 7702 533-0 | Fax +49 7702 533-433Mounting instruction see www.metz-connect.com
21
6. MountingPower down the equipmentMount the module on standard rail (TH35 per IEC 60715 in junction boxes and/or on distribution panels).InstallationElectric installation and device termination shall be done by qua-lified persons only, by respecting all applicable specifications and regulations.Plug in the terminal block for bus connection
43
5 mm
5 6The module can be aligned without interspace. Use the jumper plug to connect bus and supply voltage when the modules are mounted in series.The maximum quantity of modules connected in line is limited to 15 or to a maximum power consumption of 2 Amps (AC or DC) per connection to the power supply. For any similar block of additional modules a separate connection to the power supply is mandatory.
Connect the cable for bus supply
Mounting in series
7. Network adress and Bit rate settingConfiguration SwitchesHexadecimal Switches x10, x1 define the Network-Address (00 - F9; e.g. F9h = 15x16+9 = 249d) and Baudrate (FA – FF). • Turn Switch x10 to E (Device is temporaryly configured as Slave) • Turn Switch x1 to A – F to select Baudrate • Turn Switch x10 to F, wait 1 Second • Red and green LEDs are blinking when Baudrate ist stored in EEPROM • Turn Switch x10 to select Network-Address • Turn Switch x1 to select Network-Address
The Watchdog Timer resets Present_Value of all output objects to Relinquish_Default, if BACnet communication fails permanently. The timer is re-started, when a BACnet message with an APDU is received.When the timer times out, the priority arrays of all output objects are completely cleared to NULL.