Diesel Generator Maintenance Guide (V1.0)Secret
Diesel Generator Maintenance Guide
(V1.0)Prepared byZeng Jie (66228)Date2007-09-21
Reviewed byDate
Reviewed byGuo Jianxiang (00123485)Date
Approved byDate
2007.9
Revision HistoryDateVersionDescriptionAuthor
2007-9-211.0First draftZeng Jie
2008-3-101.0RevisedZheng Shenyuan
Contents41 Objective
52 Applicability Scope
63 Competency Requirements for Maintenance Engineers
74 Operation Guide
74.1 Preparations
74.2 Monthly (or Pre-Operation) Check
134.3 Replacement of Consumables
184.4 Site Clean-Up and Maintenance Record
19Appendix: Diesel Generator Maintenance Record
1 ObjectiveThis document describes the contents, operation
modes, and precautions for routine maintenance of diesel
generators. Field maintenance engineers should comply with this
guide to supply the maintenance service for diesel generators.
2 Applicability ScopeThis document applies to service delivery
of diesel generator maintenance engineers. If a customer does not
purchase the diesel generator maintenance service from Huawei, this
document can be used as a reference for Huawei engineers to give
suggestions on routine maintenance of diesel generators to the
customer.
3 Competency Requirements for Maintenance EngineersMaintenance
engineers should have a knowledge of components, working
principles, and basic maintenance of diesel generators. In
addition, maintenance engineers should have experience in
maintaining diesel generators, such as replacing filters (including
a lube oil filter, a fuel filter, and an air filter), using common
tools, and operating the related meters.
4 Operation Guide4.1 PreparationsNo.PrepareRemarks
1GogglesChecking the electrolyte level and the voltage of a
battery
2Protective glovesChecking engine oil, fuel, and antifreeze
3Maintenance toolsRoutine maintenanceAttachment:
4EarplugsProtecting your ears during trial running of a diesel
generator
5Duster clothCleaning diesel generators after maintenance
4.2 Monthly (or Pre-Operation) Check1. Fuel Tank (External Fuel
Tank)ObjectiveTo ensure that the fuel tank is clean, the fuel is
sufficient, and the fuel pipe is in good condition without block
and leak.
Check Items Ensure that no water, iron dust, or other sediment
exists in the fuel tank.
Ensure that the fuel level reach at least 1/2 of the capacity of
the fuel tank.
Ensure that the fuel pipes are not leaky or deformed.
Ensure that the valve in the fuel pipe is in good condition
without rust and block.
Exception Handling Remove the sediment from the fuel tank
through the drain valve at the bottom of the tank.
Fill the fuel tank (based on the fluid level gauge) and remove
the overflowed diesel.
Replace any leaky or deformed fuel pipe with a new one.
Replace any rusty or blocked valve.
Precautions No smoking when filling the fuel tank.
You can replenish an external fuel tank but not a built-in one
when the diesel generator is running.
0# or 10# diesel is recommended. 10# diesel should be used when
the ambient temperature is below 0C.
2. Engine OilObjectiveTo ensure that the engine oil is
sufficient in the total loss system, the lubrication system works
normally, and all mechanical parts work well A refers to the oil
filler.
It is best that the oil level reaches position D on the oil
scale.
Check Items Ensure that the fuel level in the oil pan is between
ADD and FULL on the oil scale.
Touch the engine oil to check its viscosity and observe its
color.
Exception Handling If the oil level is lower than the ADD
position, fill engine oil till the oil level is close to the FULL
position.
If the engine oil becomes thicker or extremely thin, replace it
with new oil.
Precautions Do not check the oil level when the diesel generator
is running.
Drain the degraded oil after the diesel oil has been running for
10 minutes. This speeds up the oil drainage.
You should replace the degraded engine oil with the engine oil
of the same brand and specification.
3. Cooling SystemObjectiveTo ensure that the cooling system
works normally
Check Items Ensure that the cooling water is sufficient.
Ensure that the water pipes are not leaky.
Exception Handling If the cooling water is not sufficient, fill
the water till the water level is 3 cm to 5 cm below the sealing
cover.
If any water pipe is leaky, fasten or replace the connector.
Precautions Do not open the filler on the water tank when the
motor is hot or the pressure in the water tank is high.
Do not check the water level till 15 minutes after the generator
stops.
When you are filling water, air in the pipe cannot be removed at
a time. Therefore, you should fill water by stages. That is to say,
wait for a moment after you fill some water, and then fill water
again. Repeat this process till you see the water level in the
inlet pipe.
4. BatteryObjectiveTo ensure that the battery works normally
Check Items Check the electrolyte level of the battery.
Test the density of the electrolyte of the battery by using a
densimeter. The best density is 1.28.
Ensure that the wiring terminals are free of rust and the wiring
is correct.
Exception Handling Fill distilled water or purified water till
the level exceeds the pole plate by 5 cm to 10 cm.
Recharge the battery or check the charger in the case of low
battery.
Polish the rusty wiring terminals by using a sand paper and then
apply oil to the wiring terminals. Fasten the connected wires if
necessary.
Precautions Keep the battery away from any sparkle or flame,
because the volatile gas of the electrolyte is flammable.
Mis-connected polarities of a battery will damage the electrical
system and the battery.
For an automatic start generator set, ensure that the start
switch is off; otherwise, the generator set might suddenly
starts.
When removing a battery, disconnect the cathode and then the
anode. When installing a battery, connect the anode and then the
cathode.
5. Fan Belt and Driving BeltObjectiveTo ensure that the belts
are not loosened, aged, or brokenA loosened, aged, or broken belt
is loosened degrades heat dissipation.
Check Items Check the tightness of the fan belt.
Check the tightness of the driving belt.
Ensure that no belt is aged and no crack exists on the surface
of any belt.
Exception Handling Tighten the loosened fan belt by using the
automatic tightener.
Remove the fastening screw before tightening the driving belt.
Tighten the driving belt till you can press down the belt by about
10mm.
Replace a belt on which cracks exist.
Precautions Replace all worn belts in pairs.
Replace any belt with a new belt of the same specification.
6. ATS and ACDBObjectiveTo ensure that both the ATS and the ACDB
work normally
Check Items Ensure that the power and signal cables connecting
the diesel generator, ATS, and ACDB are firmly connected.
Ensure that no electrical part is burned out.
Ensure that the diesel generator, ATS, and ACDB are well
grounded.
Exception Handling Fasten any loosened cables.
Replace any burned electrical parts.
Fasten all grounding cables.
PrecautionsEnsure that the diesel generator, ATS, and ACDB are
well grounded
7. Protective Cover, Screws, and NutsObjectiveTo ensure that the
protective cover and all screws and nuts are firmly fixed
Check ItemsEnsure that the protective cover and all screws and
nuts are firmly fixed.
Exception HandlingFasten the loosened protective cover and all
loosened screws and nuts.
PrecautionsDo not start the engine if no protective cover is
installed.
8. Running TestObjective To ensure that the diesel generator can
work normally after a basic check
To ensure that a diesel generator that has not worked for a long
time (within two weeks) can start in the case of emergency power
supply
To ensure that the diesel generator, ATS, and ACDB can work
normally
Check Items Check all parameters displayed on the control panel,
including the revolutions, voltage, current, frequency, oil
pressure, and water temperature.
Ensure that the diesel generator is free of leakage (fuel,
water, or air).
Ensure that all joints are firmly connected and the diesel
generator does not vibrate greatly.
Ensure that the ATS can automatically start and stop the diesel
generator and that the ATS can switch over power supply.
Exception Handling Shut down the diesel generator in the case of
any exception.
Search for the reason immediately or turn to the technical
support engineers in the case of any exceptional parameter.
Check all pipes and connectors and replace or fasten any
loosened connectors in the case of leakage (oil, water, or
air).
In the case of exceptional vibration of the diesel generator,
find out and fasten the loosened joints.
Locate the reason immediately or turn to the Technical Support
if the ATS is in an exceptional state.
4.3 Replacement of ConsumablesThe replacement frequency of
consumables described in this document refers to a practice in the
industry and is for reference only. Maintenance engineers can
adjust the replacement frequency based on the environment and the
operation of the diesel generator.
Do not replace any consumables when the diesel generator is
running.9. Engine OilFrequencyReplace the engine oil after the
first 50-hour operation, and then replace it once every 250-hour
operation (or quarterly).
Operating Procedure Run the diesel generator without any load
for 10 minutes before draining the original engine oil (to speed up
the drainage).
Remove the drain plug to drain the original engine oil, and then
insert the plug.
Fill new engine oil through the oil filler till the oil is close
to the upper limit specified by the oil scale.
The position that the arrowhead points to is the drain plug. The
drain plug varies slightly with oil pan models.
Service Standards Replace engine oil with new engine oil of the
same or a higher SAE/API grade.
After filling engine oil, measure the engine oil with an oil
scale and ensure that the oil level is close to the upper limit
position on the oil scale.
After replacement of the engine oil, the oil pressure should be
in the allowed range when the diesel generator is running.
Precautions Replace the oil filter when replacing engine
oil.
The oil level should not exceed the upper limit position on the
oil scale.
10. Oil FilterFrequencyReplace the oil filter after the first
50-hour operation, and then replace it once every 250-hour
operation (or quarterly).
Operating Procedure Remove the oil filter with a belt
wrench.
Ensure that the new filter is equipped with a new sealing ring.
Clean the contact surface and fill the new filter with engine oil
of the specified grade. Apply engine oil to the sealing ring. Screw
the new filter to the original position, and then further fasten it
by two-third circle.
After replacing the oil filter, run the diesel generator for 10
minutes and ensure that no oil leakage exists.
Service Standards Replace the original oil filter with a new one
and ensure that no oil leakage exists when the diesel generator is
running.
After replacement of the oil filter, the oil pressure should be
in the allowed range when the diesel generator is running.
Precautions Replace engine oil when replacing the oil
filter.
Use a new sealing ring when replacing an oil filter.
Do not fasten the oil filter too tightly. If the oil filter is
fastened too tightly, oil leakage might exist because the sealing
ring is deformed and damaged.
11. Fuel FilterFrequencyReplace the fuel filter once every
250-hour operation (or quarterly).
Operating Procedure Remove the fuel filter with a belt
wrench.
Ensure that the new filter is equipped with a new sealing ring.
Clean the contact surface and fill the new filter with diesel of
the specified grade. Install the new filter to the original
position.
Remove air from the fuel pipes (the low pressure pipe and then
the high pressure one) by using a hand pump. See the following
figure.
After replacing the oil filter, run the diesel generator for 10
minutes. If air exists in the fuel system, remove the air by using
the fuel pump before starting the diesel generator.
Service Standards Replace the original fuel filter with a new
one and ensure that no leakage exists when the diesel generator is
running.
After replacement of the fuel filter, the diesel generator works
normally at a satisfactory speed.
Precautions Replace the fuel filter when the engine is cooled.
Do not spray any diesel to the exhaust pipe.
Use a new sealing ring when replacing the fuel filter. Do not
fasten the filter too tightly.
12. Air FilterFrequencyReplace the air filter once every 500
hours or when the indicator of the air filter turns red.
Operating Procedure Check the indicator of the air filter. If
the alarm system turns red, it means that the air filter needs to
be replaced.
Open the air filter, and then replace the cartridge. Press the
button on the top to reset the indicator.
Indicator of an air filter
Service StandardsReplace the cartridge with a clean new one of
the same specification.
PrecautionsDo not start a turbocharged engine if no air filter
is installed.
13. Cooling Water FilterFrequencyReplace the cooling water
filter once every 500-hour operation (or quarterly).
Operating Procedure Close the water inlet, and then remove the
filter with a belt wrench.
Ensure that the new filter is equipped with a new sealing ring.
Clean the contact surface. Screw the new filter to the original
position, and then further fasten it by two-third circle.
Open the water inlet.
Service StandardsReplace the original water filter with a new
one and ensure that no leakage exists when the diesel generator is
running.
Precautions Replace the fuel filter when the engine is cooled to
avoid scald.
Use a new sealing ring when replacing the water filter. Do not
fasten the filter too tightly.
14. Cooling WaterFrequencyReplace the cooling water once every
1000-hour operation (or annually).
Operating Procedure Remove the upper cover from the water tank.
Open the drain valve at the bottom of the water tank and ensure the
water outlet is unblocked. Drain the cooling water, wash the
cooling system with clean water, and then close the drain
valve.
Fill the water tank with cooling water, and then cover the water
tank.
Service StandardsThe cooling water level should be 5cm lower
than the sealing surface of the sealing cover.
Precautions Do not remove the upper cover from the water tank
within 15 minutes upon shutdown of the diesel generator.
Do not fill the cooling system with any sea water, electrolyte,
or other corrosive matters.
15. Running TestAfter replacing consumables, run the diesel
generator to check its working status. Ensure that the diesel
generator is free of leakage (oil, water, or air) and all working
parameters are normal. The running test verifies that the diesel
generator can work normally after maintenance.
4.4 Site Clean-Up and Maintenance RecordAfter maintenance of a
diesel generator, clean the site, diesel generator, and tools. In
addition, make a maintenance record signed by both the maintenance
party and the supervisor (or the customer).Appendix: Diesel
Generator Maintenance Record
2008-4-26Huawei ConfidentialPage 7 of 19
_1270371197.xlsSheet1
List of Maintenance Tools for Diesel Generators
No.Tool NameSpecification
1Tool box
2Vigorous plier7"
3cutting pliers
4flat nose pliers
5Belt wrench
6monkey wrench8"
7Solid wrench17mm
8Solid wrench15mm
9Solid wrench14mm
10Solid wrench13mm
11Solid wrench12mm
12Solid wrench11mm
13Solid wrench10mm
14Solid wrench8mm
15hammer
16Cinquefoil screwdriver4"
17Cinquefoil screwdriver6"
18screwdriver4"
19screwdriver6"
20Hex tools334-4"
21Sleeve wrench28 sets
22Multimeter
23Float level gauge
24Oil scale
25Densimeter
26Sand paper
27Goggles
28Protective gloves
29Earplug
&L&G&C&F&R&","
&L&D&C&R&P&N
Sheet2
&L&G&C&F&R
&L&D&C&R&P&N
Sheet3
&L&G&C&F&R
&L&D&C&R&P&N
_1270475913.xlsSheet1
OSP Maintenance Record
Site NameSite ID
AddressProduct TypeDiesel Generator
ID of Diesel Generator 1Model of Diesel Generator 1
ID of Diesel Generator 2Model of Diesel Generator 2
CheckerDate
Check ItemDescriptionCheck RecordHandling ResultRemarks
PatrolFuel tank1.Ensure that no water, iron dust, or other
sediment exists in the fuel tank.YES NO
2. Ensure that the fuel level reach at least 1/2 of the capacity
of the fuel tank.YES NO
3. Ensure that the fuel pipes are not leaky or deformed.YES
NO
4. Ensure that the valve in the fuel pipe is in good condition
without rust or block.YES NO
Engine oil1. Ensure that the fuel level in the oil pan is
between ADD and FULL on the oil scaleYES NO
2. Check viscosity and color of engine oil.YES NO
Cooling system1. Ensure that the cooling water is sufficient.YES
NO
2. Ensure that the water pipes are not leaky.YES NO
Battery1. Check the electrolyte level of the battery.YES NO
2. Test the density of the electrolyte of the battery by using a
densimeter.YES NO
3. Ensure that the wiring terminals are free of rust and the
wiring is correct.YES NO
Fan belt and driving belt1. Check the tightness of the fan
belt.YES NO
2. Check the tightness of the driving belt.YES NO
3. Ensure that no belt is aged and no crack exists on the
surface of any belt.YES NO
ATS and ACDB1. Ensure that the power and signal cables
connecting the diesel generator, ATS, and ACDB are firmly
connected.YES NO
2. Ensure that no electrical part is burned out.YES NO
3. Ensure that the diesel generator, ATS, and ACDB are well
grounded.YES NO
Component fasteningEnsure that the protective cover and all
screws and nuts are firmly fixed.YES NO
Running test1. Check all parameters displayed on the control
panel, including the revolutions, voltage, current, frequency, oil
pressure, and water temperature.YES NO
2. Ensure that the diesel generator is free of leakage (fuel,
water, or air).YES NO
3. Ensure that all joints are firmly connected and the diesel
generator does not vibrate greatly.YES NO
4. Ensure that the ATS can automatically start and stop the
diesel generator and can switch over power supply.YES NO
Replacement of consumablesEngine oil1. Run the diesel generator
without any load for 10 minutes before draining the original engine
oil (to speed up the drainage). Remove the drain plug to drain the
original engine oil, and then insert the plug.YES NO
2. Fill new engine oil through the oil filler till the oil is
close to the upper limit specified by the oil scale.YES NO
Oil filter1. Remove the oil filter with a belt wrench.YES NO
2. Ensure that the new filter is equipped with a new sealing
ring. Clean the contact surface and fill the new filter with engine
oil of the specified grade. Apply engine oil to the sealing ring.
Screw the new filter to the original position, and then further
fasten it by two-third circle.YES NO
3. After replacing the oil filter, run the diesel generator for
10 minutes. Ensure that no oil leakage exists and the oil pressure
is normal.YES NO
Fuel filter1. Remove the fuel filter with a belt wrench when the
diesel generator is cooled.YES NO
2. Ensure that the new filter is equipped with a new sealing
ring. Clean the contact surface and fill the new filter with diesel
of the specified grade. Install the new filter to the original
position.YES NO
3. After replacing the oil filter, run the diesel generator for
10 minutes. If air exists in the fuel system, remove the air by
using the fuel pump before starting the diesel generator.YES NO
Air filterWhen the diesel generator is not running, open the air
filter, and then replace the cartridge. Press the button on the top
to reset the indicator.YES NO
Cooling water filter1. Close the water inlet, and then remove
the filter with a belt wrench.YES NO
2. Ensure that the new filter is equipped with a new sealing
ring. Clean the contact surface. Screw the new filter to the
original position, and then further fasten it by two-third
circle.YES NO
3. Open the water inlet.YES NO
Cooling water1. Remove the upper cover from the water tank. Open
the drain valve at the bottom of the water tank and ensure the
water outlet is unblocked. Drain the cooling water, wash the
cooling system with clean water, and then close the drain valve.YES
NO
2. Fill the water tank with cooling water, and then cover the
water tank.YES NO
Running testAfter replacing consumables, run the diesel
generator to check its working status. Ensure that the diesel
generator is free of leakage (oil, water, or air) and all working
parameters are normal. The running test verifies that the diesel
generator can work normally after maintenance.YES NO
Maintenance Suggestions(Briefly describe the check, including
all disclosed problems, their causes, corrective measures, and
preventive suggestions.)
SignaturesMaintenance Party (signature and date) Huawei
(signature and date)