-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
1/11
ASAE EP484.1 DEC97
Diaphragm Design of Metal-Clad, Post-Frame
RectangularBuildings
Developed by the ASAE Diaphragm Design of Metal-Clad,
Post-FrameRectangular Buildings Subcommittee of the Structures
Group; approvedby the Structures and Environment Division Standards
Committee;
adopted by ASAE September 1989; revised December 1990;
reaffirmedDecember 1994, December 1995, December 1996; reaffirmed
for oneyear December 1997.
1 Purpose and scope1.1 This Engineering Practice standardizes
the methods for testing andreporting the strength and stiffness of
metal-clad, timber-framediaphragms and outlines engineering
procedures for the diaphragmanalysis and design of metal-clad,
post-frame rectangular buildings.
1.2 The provisions of this Engineering Practice are suitable for
theanalysis and design of rectangular, metal-clad, post-frame
buildingsusing roof and ceiling diaphragms, alone or in
combination. Theprovisions are limited to the analysis of
single-story buildings symmetricin design and construction with
respect to the major axes of the building
and with endwalls sufficiently rigid to transfer roof shear
loads to theground with negligible lateral deflection at the eave.
The endwalls mayrequire supplemental reinforcement to replace lost
strength and stiffnessdue to placement of doors and large openings
in the endwalls.
2 Terminology (See Figs. 1, 2, 3, and 4)
2.1 Building diaphragm stiffness, ch: The stiffness of the
entire roofdiaphragm assembly. The stiffness is obtained from test
panel resultsand is adjusted for differences between the length of
the test panel andthe roof diaphragm and for the slope of the
roof.
2.2 Cantilever test: A load test arrangement for a diaphragm in
whichthe diaphragm is supported along one edge and the shear load
is appliedat a corner of the opposite edge and in the direction
parallel to thedirection of the line of action of the supports (see
Fig. 2).
2.3 Ceiling stiffness, cc: The stiffness of a horizontal
diaphragmconsisting of the ceiling of the building.
2.4 Diaphragm: A structural assemblyincluding the timber
framing(truss chords and purlins), metal cladding, fasteners and
fasteningpatternscapable of transferring in-plane shear forces
through thecladding and framing members.
2.5 Diaphragm design: The design of a post frame, including the
rooftruss, sidewall posts, endwalls, shear connectors, chord
splices andground anchorages, in which the diaphragm strength and
diaphragm
stiffness are utilized to transfer applied horizontal loads to
the ground.
Figure 1 Definition sketch for terminology
Figure 2 Cantilever test assembly
Figure 3 Simple beam test assembly
ASAE STANDARDS 1998 719
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
2/11
2.6 Diaphragm fastenings: The various fastenings and
fasteningpatterns used to connect the several components of the
diaphragm.These include the fastenings between the cladding and
purlins, between
the diaphragm framing members, and between individual sheets
ofcladding.
2.7 Diaphragm length, b: The test diaphragm dimension measured
inthe direction of the corrugations.
2.8 Diaphragm shear stiffness, c: The shear stiffness, force per
unitlateral in-plane displacement, of a diaphragm. It is defined as
the slopeof the diaphragm load-shear displacement curve between
zero load andthe load corresponding to the diaphragm design shear
strength.
2.9 Diaphragm shear strength: The design shear strength
(seeparagraph 3.3.6.2) of a diaphragm in the plane of the
cladding.
2.10 Diaphragm width, a or 2a: The test diaphragm
dimensionmeasured in the direction perpendicular to the
corrugations.
2.11 Endwall diaphragm: The endwall of the building where
theendwall cladding and framing are constructed so as to transfer
in-plane
shear forces from the roof and/or ceiling diaphragm to the
ground.
2.12 Frame stiffness, k:The horizontal stiffness to a load
applied at theeave of the individual unclad post frames, including
the truss, in each bayof the building.
2.13 Horizontal restraining force, R: The force applied at the
leewardeave of the post frame to prevent translation due to design
loads whendiaphragm action is not included.
2.14 Metal cladding: The metal exterior and interior coverings,
usuallycold-formed aluminum or steel sheet, fastened to the timber
framing.
2.15 Post frame: A structural frame consisting of a wood roof
trussconnected to vertical timber columns.
2.16 Shear fastenings: The fastenings and fastening patterns
used totransfer the shear forces between sheets of cladding,
between thecladding and frame, and between roof or ceiling cladding
to endwall orshearwall diaphragms.
2.17 Shear transfer: The transfer of the resultant shear forces
betweenindividual sheets of cladding, between the edges of roof
diaphragms andthe top of the endwalls, between the edges of ceiling
diaphragms and theendwalls, or between the bottom of the endwall
diaphragms and theground.
2.18 Shear wall: A vertical diaphragm in a structural framing
system.The wall may be an endwall or an intermediate wall. In
either case, thewall transfers shear forces from the roof or
ceiling diaphragm to thegroundline.
2.19 Simple beam test: A load test arrangement for a diaphragm
inwhich the diaphragm is loaded as a deep beam. Both ends of
thediaphragm are supported to resist in-plane shear and one end
issupported to resist perpendicular-to-plane movement. A
singleconcentrated load is applied in the direction of the truss
chords atmidspan (see Fig. 3).
2.20 Tension fastenings: The fastenings required to transfer
theresultant tensile forces in the flanges of deep beam diaphragms
at pointswhere the flange members are spliced. In a roof diaphragm,
the flangemembers are the edge purlins at the eave and ridge.
2.21 Test diaphragm: A diaphragm model of sufficient size to
simulatethe behavior of the diaphragm in the building. Except for
overall size, the
test diaphragm construction is functionally equivalent (see
paragraph 3.1)to the building diaphragm and is supported in a
manner similar to thatencountered in the building application.
3 Diaphragm strength and stiffness3.1 General provisions. This
section outlines methods for determiningdiaphragm strength and
stiffness for post-frame buildings. Unlessotherwise noted, this
Engineering Practice assumes that the testdiaphragm construction is
functionally equivalent to that used in thebuilding being designed.
This requires that post spacing, purlin spacingand orientation,
cladding type, cladding profile, cladding thickness,fastening type
and pattern, and support patterns for both the claddingand
diaphragm framing each be identical. Functional equivalence
also
requires that the specific gravity and Group Number of both the
purlinsand the chords used in the test diaphragm be equal to or
greater than thespecific gravity and Group Number of the species
used in the buildingconstruction. Group Number is defined by the
National Forest ProductsAssociation Standard, National Design
Specification for WoodConstruction, Table 8.1A (NDS, 1986).
3.2 Diaphragm tests.The shear strength and stiffness of wall,
roof andceiling diaphragms are to be determined by shearing tests
of diaphragmsor by other acceptable analysis methods. Testing may
be accomplishedby either the cantilever test (see Fig. 2) or the
simple beam test (see Fig.3).
3.2.1 Test apparatus
3.2.1.1 General. The test diaphragm shall meet all the
functionalequivalence provisions of paragraph 3.1.
3.2.1.2 Frame size.The length,b, of the test frame shall not
exceed thediaphragm length used in design. The width, a or 2 a, of
the test frameshall not be less than the overall width of three
sheets of cladding ineither the cantilever or simple beam test
procedures. The frame width,a, shall also not be less than the
width of one building bay (the distancebetween post frames) for the
cantilever test or two bays for the simplebeam test.
3.2.1.3 Frame material requirements. The moisture content of
allframing members shall be below 19% when the test section is
fabricatedand shall not vary by more than 3% from the initial
moisture contentwhen the section is tested. A specific gravity test
per ASTM StandardD143-83, Method of Testing Small Clear Specimens
of Timber, shall beconducted and recorded on all framing members
immediately after thetest is completed.
3.2.1.4 Purlin and chord size and spacing. All test frames shall
beconstructed with purlin size and spacing equal to those used in
thebuilding design. Test frame chords shall have the same thickness
andspacing as the chords in the building and shall have sufficient
depth toaccommodate full penetration of all purlin to chord
fasteners.
3.2.1.5 Support placement
3.2.1.5.1 Cantilever test (see Fig. 2). For the cantilever test,
the frame
shall be supported at corner C(see Fig. 2) with a pinned
connection toallow transfer of the horizontal forces into the
supports. Frame corner
G (see Fig. 2) shall be supported with a roller type connection.
Side
Figure 4 Diaphragm test results
720 ASAE STANDARDS 1998
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
3/11
DE shall be supported vertically by a series of rollers (for
horizontalframe testing). A restraining force may be necessary to
resist out-of-plane movement at corner E.
3.2.1.5.2 Simple beam test. For the simple beam test, the frame
shallbe supported at corner G (see Fig. 3) with a pinned connection
and atcorner Ewith a roller type connection. In addition, line HJ
shall besupported in a manner similar to the supports along line DE
in thecantilever test procedure. Restraining forces may be
necessary to resistout-of-plane movement at corners C and E.
3.2.1.6 Loading and instrumentation
3.2.1.6.1 Calibration and accuracy. Loading equipment and
measurement devices shall be calibrated and verified in
accordance withASTM Standard E4-83a, Practices for Load
Verification of TestingMachines. All deflection and load
measurement gages shall have anaccuracy within 2% of the respective
design values.
3.2.1.6.2 Load application. Loading shall be applied parallel to
and inthe plane of contact between the diaphragm and the frame. The
methodof loading and relevant equipment shall accommodate a loading
schemein which loads are continuously measured, and are applied in
equalincrements from zero to failure. Proper load locations are
illustrated inFigs. 2 and 3.
3.2.1.6.3 Deflection measurement.Deflections shall be recorded
to thenearest 0.02 mm (0.001 in.). Deflection measurements shall be
takensuch that the relative movement of the adjacent rafters is
measured.Proper gage locations (numbered) are illustrated in Figs.
2 and 3.
3.2.2 Test procedures3.2.2.1 Number of tests and failure
strength criteria. A minimum ofthree replications of each test
diaphragm configuration shall be tested.Each replication requires
construction of a new test frame. Evaluation oftest strength
results shall be made based on the minimum failure valueof the
three tests. Design stiffness shall be based on the average of
thethree tests. The design failure value shall be based on the
lower 33rdpercentile estimate according to the nonparametric point
estimate, NPE,method described in ASTM Standard D2915-84, Method
for EvaluatingAllowable Properties for Grades of Structural Lumber,
(see paragraph4.5.4).
3.2.2.2 Loading procedure.The test diaphragm shall be loaded as
perASTM Standard E564-76, Method for Static Load Test for
ShearResistance of Framed Walls for Buildings; ASTM Standard
E72-80,Method for Conducting Strength Tests of Panels for
Building
Construction; and ASTM Standard E455-76(1984), Method for
StaticLoad Testing of Framed Floor or Roof Diaphragm Constructions
forBuildings.
3.2.2.2.1 Method of load application. (See ASTM Standard
E72-80,Method for Conducting Strength Tests of Panels for
BuildingConstruction) Load and unload the test diaphragm in three
stages to 3.5,7.0, and 10.5 kN (800, 1600, and 2400 lbf) total load
at a uniform rate.To provide data to meet performance requirements,
other values of totalload may be included in the test procedure.
Use the same rate of loadingfor all tests and report all results.
At least 10 sets of uniformly-spaceddeflection readings shall be
taken prior to failure to establish the load-deformation curve.
3.2.2.2.2 Load rate. Load rate should be applied
continuouslythroughout the test at a uniform rate of motion of the
loading deviceused. The rate of loading shall be such that the
loading to 3.5 kN (800lbf) total load shall be completed in not
less than two minutes from thestart of the test. Loading to 7.0 and
to 10.5 kN (1600 and 2400 lbf) totalload and to failure shall occur
at the same loading rate. The rate of theloading shall be such that
that the anticipated full design load level will bereached in not
less than 10 minutes.
3.2.2.2.3 Subsequent load cycles. (See ASTM Standard
E72-80,Method for Conducting Strength Tests of Panels for
BuildingConstruction) After the load of 3.5 kN (800 lbf) is placed
on thespecimen, immediately remove all of the load at the same rate
as loadingcommenced, wait five minutes and note any residual
deflection (set) in
the diaphragm. Reload the specimen to 7.0 kN (1600 lbf) and
againremove the load, wait five minutes and note any additional
set. Reloadthe specimen to 10.5 kN (2400 lbf), remove the load,
wait five minutesand note the set. Apply load continuously for each
of the increment loadsspecified above and obtain load-deflection
data. Obtain these data for atleast each 900 N (200 lbf) of
loading. Obtain deflections during theloading and the unloading
portion of the cycle.
3.2.2.2.4 Final load cycle. (See ASTM Standard E72-80, Method
forConducting Strength Tests of Panels for Building Construction)
After thespecimen is loaded as specified to 3.5, 7.0 and 10.5 kN
(800, 1600 and2400 lbf), load it again to failure or until the
adjusted deflection of the
diaphragm at pointEfor cantilever tests or point Jfor simple
beam tests
equalsa/24 in cantilever test panels or 2 a/48 in deep beam test
panels.Obtain readings of deflection for the same intervals of load
as were usedfor the other loadings. In the event of test diaphragm
failure before thefourth load cycle, use the results of the
completed load cycles forevaluation of diaphragm strength and
stiffness.
3.2.2.3 Failure definition. The ultimate failure load will be
defined bythe serviceability limit. That is, any permanent failure
of the cladding,framing or fastenings which would be objectionable
based onappearance or performance.
3.3 Diaphragm test reports.The following information shall be
reportedfor each diaphragm test panel. The report shall be
sufficient to allow forthe incorporation of the test results into
building design. See Fig. 4 for asample data sheet. The items noted
with an asterisk are desirable but notrequired for design; they are
required for research and theoreticalapplications.
3.3.1 General information. Sufficient information shall be
provided touniquely identify each diaphragm tested, including:
3.3.1.1 Laboratory investigator. The laboratory and
principalinvestigator shall be identified.
3.3.1.2 Test ID. An identifying number which uniquely references
onetest replication.
3.3.1.3 Date of test. Date when the test was performed.
3.3.2 Test diaphragm configurations. The overall
diaphragmconfiguration must be identified with the following
information:
3.3.2.1 Length, b. Distance measured parallel to the sheets.
Fordiaphragms utilizing a single-length sheet, this would be the
sheet lengthunless the end fasteners are located more than 75 mm (3
in.) from theends of the sheets. The length is measured from the
centerline of the
end fasteners when fasteners are more than 75 mm (3 in.) from
the endsof the sheets.
3.3.2.2 Width, a or 2a. Distance measured perpendicular to the
lengthof the sheets. The width is measured from the centerline of
the outsideframing members.
3.3.2.3 Loading configuration.A sketch of the test configuration
shallbe provided. Support types and locations, deflection
measurementlocations, and load application locations shall be
identified.
3.3.3 Lumber properties. For each framing component used
toconstruct the test assembly (i.e., purlins, rafters, etc.),
provide thefollowing information:
3.3.3.1 Number. Total number of pieces used in the test
assembly.
3.3.3.2 Nominal size. Nominal order-entry size of the wood
member.
3.3.3.3 Grade and species. The grade and species of lumber
used.
3.3.3.4 Stiffness. The modulus of elasticity of each edge purlin
pieceshall be measured prior to test panel fabrication. If a test
machine isavailable, the method of ASTM Standard D198-84, Method
for StaticTests of Timbers in Structural Sizes, using a continuous
load-deflectiontrace is recommended. Alternately a flatwise
measurement using twocenter-point deadweights can be used
(Percival, 1981).
3.3.3.4.1 Span for flatwise E measurement.A recommended
distancebetween supports is the diaphragm width, a, for the
cantilever test butnot greater than 3.0 m (10 ft). For the simple
beam tests, more than two
ASAE STANDARDS 1998 721
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
4/11
boards may be used as edge purlins. If only one board is used
per edge,use a distance between supports of the test diaphragm
width, 2 a, butnot greater than 3.0 m (10 ft). If two boards are
used to form one edge(because of lapping or recessing purlins
between truss chords) therecommended span is the truss spacing, a,
but not greater than 3.0 m(10 ft).
3.3.3.5 Specific gravity. Specific gravity for each member shall
bedetermined in accordance with ASTM Standard D143-83, Method
ofTesting Small Clear Specimens of Timber. The average and range
ofspecific gravity shall be reported for each assembly.
3.3.4 Metal cladding.The following information shall be reported
for themetal cladding used in the test assembly:
3.3.4.1 Manufacturer.The name of the manufacturer of the
cladding.
3.3.4.2 Profile. The commercial name of the profile which will
uniquelyidentify the profile configuration.
3.3.4.3 Base metal. The type of metal used to form the panel
(i.e.,aluminum, steel).
3.3.4.4 Grade or alloy. The specific grade or alloy of metal
used (i.e.,Grade E Steel, 3004-H37 Aluminum).
3.3.4.5 Yield strength. The measured yield strength of the
materialbeing used, or the yield strength from manufacturers
data.
3.3.4.6 Thickness. The base metal thickness as reported by
themanufacturer.
3.3.4.7 Section modulus.The elastic section modulus per unit
width ofcladding based on the full section.
3.3.4.8 g/p ratio. The ratio of the total flat width of metal
used to formone complete repeating corrugation to the pitch of the
corrugation.
3.3.4.9 Profile dimensions. A sketch which includes all
profiledimensions.
3.3.5 Fastenings. For each type of fastening used to construct
theassembly, report the following (The items with an asterisk are
desired butoptional):
3.3.5.1 Manufacturer.The name and address of the manufacturer
ofthe fastenings.
3.3.5.2 Type. The brand name of each fastening and its general
type(i.e., screw, nail, etc.).
3.3.5.3 Diameter.The shank diameter of the fastening.
3.3.5.4 Length. The nominal length of the fastening.
3.3.5.5 Thread spacing*. The spacing of threads for all screw
typefastenings.
3.3.5.6 Washer type and size. The type washer (i.e., flat,
domed, etc.)and the outside diameter.
3.3.5.7 Base metal*.The type metal used to form the shank part
of thefastening.
3.3.5.8 Shear strength*. The tested ultimate shear strength of
thefastening using a single-lap shear test in accordance with
ASTMStandard D1761-77, Method of Testing Mechanical Fasteners in
Wood.
3.3.5.9 Shear stiffness*. The tested shear stiffness of the
fasteningusing a single-lap shear test in accordance with ASTM
Standard D1761-77, Method of Testing Mechanical Fasteners in
Wood.
3.3.6 Results. Report the following test results consistent with
the
procedure outlined in paragraph 3.2 of this Engineering
Practice:3.3.6.1 The load-deflection curves for each of the
assemblies tested,indicating the scale.
3.3.6.1.1 Cantilever test. The ultimate strength, Pul t, equals
themagnitude of the applied load at failure.
3.3.6.1.2 Simple beam test. The ultimate strength, Pul t ,
equals onehalf of the resultant of the applied load at failure.
3.3.6.2 Design shear strength. The long-term design shear
strengthequals 0.4Pul t/LDF if the failure was initiated by lumber
breakage or byfailure of the fastenings in the wood; otherwise
design shear strength
equals 0.4 Pul t . The load duration factor, LDF, may
conservatively betaken as 1.6 or be determined for actual test
duration from NDS (1986).Shear strength per unit length may be
reported as the design shear
strength divided by the diaphragm length, b.
3.3.6.3 Test diaphragm shear stiffness, c.
3.3.6.3.1 Cantilever test.The shear stiffness, c, for a test
diaphragm isbased on the relatively linear portion of the
load-deflection curve below0.4Pul t in accordance with the
formula
cP
Ds
a
b
(1)
where
P 0.4 Pul tDs shear deflection of test diaphragm at 0.4 Pul ta/b
aspect ratio of the frame shown in Fig. 2
3.3.6.3.1.1 The shear deflection,Ds, for the cantilever test
diaphragm is
obtained from the deflection measurementsD1 , D2 , D3 , andD4 in
Fig.2 and the following equations
DS DTDbDT D3D1a/bD2D4
Db Pa3/3EpIp (2)
EpIp EffectiveE Iof the panels contributed by the edge purlins.
(Themoment of inertia contribution of the purlins about their own
axes isneglected.) The following equation is recommended
EpIpby2A 1E1y
2A2E2 (3)
where
A1 ,A2 average area for each edge purlinE1 ,E2 average modulus
of elasticity for each edge purlinb center to center distance
between edge purlins
y bE1A 1/A 1E1A2E2
3.3.6.3.2 Simple beam test.The shear stiffness,c, for a test
diaphragmis based on the relatively linear portion of the total
load-midspandeflection curve below 0.4Pul t in accordance with the
formula
c1
2
P
Ds
a
b (4)
where
P 0.4 Pul tDs shear deflection of test diaphragm at 0.4 Pul
t
a/b aspect ratio of the frame shown in Fig. 33.3.6.3.2.1 The
shear deflection, Ds, for the simple beam testdiaphragm is obtained
from the deflection measurements D2 , D3 , andD4 in Fig. 3 and the
following equations
DsDTDb
DT D21/2D3D4Db Pa
3/6EpIp (5)
3.4 Building diaphragm stiffness, ch.
722 ASAE STANDARDS 1998
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
5/11
3.4.1 Definition. The building diaphragm shear stiffness is
defined bythe following equation
ChCcos2 b/a (6)
where
b/a aspect ratio of the roof diaphragm
roof slopeC test panel stiffness adjusted for diaphragm
length
per equation 7
3.4.2 Diaphragm length adjustment. Shear stiffness, c, for a
given
length test diaphragm may be corrected to shear stiffness, C
, for roofdiaphragms of different length by the following
equation
CEt
21vg/pK2/bt2
(7)
where
E modulus of elasticity of cladding cladding thickness
cladding Poissons ratiog/p see paragraph 3.3.4.8b diaphragm
length between end fastening along one
slope measured parallel to the corrugationsK2 constant for a
given panel design
3.4.2.1 The constantK2 is determined by substituting the shear
stiffnessof the test diaphragm calculated from equation 1 or 4 and
otherdiaphragm geometric and material design values into equation
7.
3.4.2.2 Equation 7 is applicable for diaphragm lengths up to 1.5
timesthe length of the test diaphragm (see Section
5Commentary).
3.4.3 When full-size diaphragm stiffness test results are
available, Cc.
4 Design procedures4.1 Diaphragm analysis of the building shall
be performed in accordancewith the provisions of this section or by
other acceptable structuralanalysis methods.
4.2 Assumptions
4.2.1 The stiffness, ch and/or cc , of the diaphragm is
known.4.2.2 Uniform spacing and stiffness of frames.
4.2.3 Uniform roof stiffness.
4.2.4 Endwalls sufficiently rigid for negligible lateral shear
and momentdisplacement at the eave under design loads.
4.2.5 The diaphragm length equals the length of one roof
slope.
4.2.6 The building is rectangular and may have a flat or sloped
roof thatconforms to the geometry illustrated in Figs. 1 and 5.
4.3 Calculation procedures for buildings without ceilings
4.3.1 Horizontal stiffness of the frame, k. A horizontal force,
P, isapplied at the eave node of the post frame as shown in Fig. 6.
The framestiffness is defined as the ratio of the applied force to
the lateraldisplacement of the node,k P/.
4.3.2 Horizontal restraining force at the eave line, R. A
horizontalrestraint (vertical roller) is placed at the eave line as
shown in Fig. 7 andthe structural analog is analyzed with all
external loads in place. Therestraining force,R, is the force
required to prevent horizontal deflectionat the eave.
4.3.2.1 Design loads should be determined from approved
standards orengineering practices.
4.3.2.2 Diaphragms help transfer only in-plane loads to
endwalls.
4.3.3 Roof stiffness, ch. The roof stiffness is determined by
themethods presented in Section 3Diaphragm strength and
stiffness.
4.3.4 Stiffness ratio, k/ch. Calculate the ratio of the frame to
roofstiffness.
4.3.5 Sidesway force modifier, mD. The sidesway force modifier
is
calculated from the principles of compatibility of the lateral
displacementof the frame and roof cladding at the eave line.
Alternately, m D values
for a range of k/chvalues and number of frames between endwalls
aregiven in Table 1. The number of frames include the framed
endwalls.
4.3.5.1 As m Dapproaches 1.0, more load is carried by the
diaphragm
to the endwalls. As m Dapproaches zero, more load is resisted by
thepost frames. An mD value of zero is equivalent to a simple
sideswayproblem. Anm Dvalue of 1.0 corresponds to zero sidesway
movementat the eave.
4.3.6 Cladding shear force modifier, mS. The shear force
modifier,mS, is calculated from the mDvalues. Alternately, mS
values for arange ofk/chvalues and number of frames between
endwalls are givenin Table 2. The number of frames include the
framed endwalls.
4.3.7 Roof diaphragm sidesway resistance force, Q. This force
is
calculated by multiplying the horizontal restraining force, R,
at the eaveline by m D(see paragraph 4.3.2).
Figure 5 Definition sketch of rectangular, metal-clad,
post-frame building
Figure 6 Definition sketch for frame stiffness, k
ASAE STANDARDS 1998 723
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
6/11
4.3.8 Shear force in roof cladding. The horizontal component of
themaximum shear force, Vh, in the roof cladding is calculated
bymultiplying the horizontal restraining force, R, at the eave line
by mS(see paragraph 4.3.2).
4.3.8.1 The maximum shear force, V, in the cladding equals
Vh/cos
.4.3.8.2 The maximum shear force,V, in roof cladding must be
less thanor equal to the design shear strength of the diaphragm.
The design shearstrength, as defined in paragraph 3.3.6.2, may be
increased by 33% byprovisions of most model building codes.
4.3.8.3 The largest shear value of the roof cladding occurs in
the baynext to the framed endwalls.
4.3.9 Analysis of the post-frame building including roof
diaphragmaction. Roof diaphragm action is included by applying the
roofdiaphragm sidesway resistance force, Q, (see paragraph
4.3.7)distributed as a horizontal uniform load along the top chords
of the trussin the direction of Ras illustrated in Fig. 8. The
distributed force, q, inforce per unit length along the member,
equals Qdivided by the lengthof both slopes of the roof
diaphragm.
4.3.9.1 The critical frame on a building with symmetric shear
walls isalways the one at or closest to the building midlength.
4.3.9.2 Appropriate changes in the post-frame design, including
membersizes, stress grades, and frame geometry, are made until all
limitingfactors for design are satisfied. Post strength,
post-horizontal shear,shear force in roof cladding, truss-web
buckling about the weak axis,bottom-chord lateral stability,
strength and embedment of endwalls, etc.,can be limiting and
critical factors in design.
4.4 General calculation procedure for buildings with
ceilings
4.4.1 The analysis of a post-frame with both ceiling and roof
diaphragmsis accomplished from the principles of compatibility of
the horizontaldisplacements of the frame, roof and ceiling
diaphragms at the eave line.
4.4.2 Horizontal stiffness of the frame and horizontal
restrainingforce. The horizontal stiffness of the frame, k, and the
horizontal
restraining force,R, at the eave line are calculated per
paragraphs 4.3.1and 4.3.2 for buildings without ceilings.
4.4.3 Ceiling stiffness, cc. Determined by the methods presented
inSection 3Diaphragm Strength and Stiffness.
4.4.4 Ceiling and roof stiffness ratio, k/cT. Calculate the
ratio of theframe stiffness to the sum of the stiffnesses of the
ceiling, cc , and roof,cr.
cTcrcc
4.4.5 Modifiers, mD and mS. Use Tables 1 and 2 to select
thesidesway force modifier,m D, and the shear force modifier, m S,
basedon the k/cT ratio (see paragraph 4.4.4), and the number of
framesbetween the endwalls of the building. The number of frames
includes theframed endwalls.
4.4.6 Combined ceiling and roof diaphragm sidesway
resistance
force, QT. This force is calculated by multiplying the
horizontalrestraining force,R, at the eave line (see paragraph
4.3.2) by m D (seeparagraph 4.4.5).
4.4.7 Combined shear force in ceiling and roof diaphragms,VT.
This
force is calculated by multiplying the horizontal restraining
force, R, at
the eave line (see paragraph 4.3.2) by m S(see paragraph
4.4.5).4.4.7.1 Roof and ceiling diaphragm sidesway resistance
forces, Qand Qc. These forces are calculated by multiplying the
combinedresistance force, QT , by the ratio of stiffness of each
diaphragm to thesum of stiffnesses of the roof, cr , and ceiling,
cc , diaphragms, as
QcrcT
QT..... .... ..... .... ..for roof diaphragmand
QccccT QT .......................for ceiling diaphragm4.4.7.2
Shear forces in the roof and ceiling diaphragms, V andVc. These
forces are similarly calculated as
VcrcT
VT...... .... ..... ..... ...for roof diaphragmand
VccccT VT .......................for ceiling diaphragm4.4.8
Analysis of post-frame building including roof and ceilingdiaphragm
actions.Roof and ceiling diaphragm actions are included byapplying
the roof diaphragm sidesway resistance force (see paragraph4.3.7),
Q, distributed as a horizontal uniform load, q, along the topchords
of the truss, and the ceiling diaphragm sidesway resistance
force(see paragraph 4.4.6), Qc, distributed as a horizontal uniform
load,
qc , along the bottom chord of the truss, respectively. These
forces areillustrated in Fig. 9 and are applied in the direction of
restraining force,R. The vertical roller introduced in paragraph
4.3.2 is removed at thisstep.
4.4.8.1 Check all limiting and critical factors in design as
described inparagraph 4.3.9.2.
4.5 Shear transfer. Shear forces must be transferred through
theindividual sheets of the diaphragm, through the connectors,
through theconnections between the roof and ceiling diaphragms to
the endwalls,and through the endwall diaphragm to the groundline in
order to developdiaphragm action. These forces are illustrated in
Fig. 11.
4.5.1 Roof diaphragm. The roof diaphragm allowable shear
strengthmust be equal to or greater than the shear force, V,
calculated inparagraph 4.3.8. (see Fig. 5).
4.5.2 Roof diaphragm-endwall connection. The fastenings
betweenthe roof diaphragm and the endwall must be designed to
transfer theshear force, V, calculated in paragraph 4.3.8 (see Fig.
5).
4.5.3 Ceiling diaphragm. The ceiling diaphragm allowable
shearstrength must be equal to or greater than the shear force,
Vc.
4.5.4 Ceiling diaphragm-endwall connections. The
fasteningsbetween the ceiling diaphragm and the endwall must be
designed totransfer the shear force, Vc, calculated in paragraph
4.4.7 (see Fig. 5).
4.5.5 Endwall diaphragm. The endwall diaphragm allowable
shearstrength, must be equal to or greater than the sum of the
horizontal
Figure 7 Definition sketch for horizontal restraining force at
the eave
724 ASAE STANDARDS 1998
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
7/11
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
8/11
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
9/11
components of the diaphragm shear forces. The strength of the
endwalldiaphragm is determined by the methods outlined in Section
3Diaphragm strength and stiffness.
4.5.5.1 The endwall diaphragm is only effective where the shear
forcescan be transmitted to the base of the endwall columns and
foundations.Therefore, a portion of the endwall shear may need to
be transferred to
the column bases by other means (such as bracing) if the sum of
thehorizontal components of the roof and ceiling shear forces, Vh
Vc,exceeds the allowable shear strength of the endwall
diaphragm.
4.5.5.2 The endwall post embedments must be able to resist
the
overturning moment produced by the shear forces, Vand Vc(see
Fig. 5).
4.6 Tensile force transfer. The flanges of the roof (edge
purlins in Fig.1) and ceiling diaphragms must be designed to
transfer the tensile force,T, developed from deep beam action (see
Figs. 10 and 11).
4.6.1 Both flanges of a ceiling or roof diaphragm must be
designed totransmit or transfer a tensile force, T, per the
equation
TWL B2/8d (8)
where
LB
the building lengthddiaphragm length
Wdefined in paragraphs 4.6.1.1 and 4.6.1.2
4.6.1.1 In roof diaphragms, W is defined as 2 times the endwall
shearforce, V, calculated in paragraph 4.3.8 divided by the
building length,
LB, between endwalls or between endwalls and intermediate
shearwalls.
4.6.1.2 In ceiling diaphragms,Wis defined as 2 times the endwall
shearforce, Vc , calculated in paragraph 4.4.7 divided by the
building length,
LB, between endwalls or between endwalls and intermediate
shearwalls.
5 Commentary5.1 Commentary for Section 1Purpose and scope
5.1.1 This Engineering Practice is limited to the diaphragm
analysis anddesign of rectangular, metal-clad, post-frame
buildings. The proceduresare applicable to buildings with or
without a ceiling diaphragm. Theendwalls are assumed to be nearly
rigid endwalls; that is, their sway isnegligible under design
loads. The endwalls must have adequate
Figure 8 Structural analog for a building with a roof
diaphragm
Figure 9 Structural analog for a building with both a roof and a
ceilingdiaphragm
Figure 10 Deep beam diaphragm schematic
Figure 11 Diaphragm metal roof/endwall wind bracing system for a
rect-angular post frame building
ASAE STANDARDS 1998 727
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
10/11
strength and stiffness to transmit all the endwall shear forces
from theroof and ceiling diaphragms to the ground with negligible
sway.
5.2 Commentary for Section 3Diaphragm strength and stiffness
5.2.1 The test methods for determining the strength and
stiffness ofdiaphragms are based primarily upon published ASTM
Standards.Cantilever or simple beam (deep beam) test procedures can
be used.The test diaphragm construction needs to be functionally
equivalent tothe construction used in the building design in order
to apply testdiaphragm results to the structural design of the
buildings. Supportspacing should be the same as the post-frame
spacing in the building.The diaphragm stiffness needs to be
adjusted for roof slope, , and fordiaphragm length, b, by using the
equations of Luttrell (1967). Equation7 in paragraph 3.4.2 has only
been verified successfully for a 1.8 m (6 ft)difference in
diaphragm length. However, it is believed that this equationcan
with sufficient accuracy predict diaphragm stiffness for a
100%increase in diaphragm length over the test diaphragm. In cases
where allfunctional equivalency requirements are met except the
diaphragmlength exceeds 2.0 times the test diaphragm length, the
followinganalysis procedure is suggested. For design of the
building frame (postsand trusses), use the stiffness obtained by
equation in paragraph 3.4.2for a diaphragm length of 2 times the
test diaphragm length. For designof the roof, use the stiffness
obtained from this equation for the actualslope length of the roof
diaphragm. The former stiffness results in aconservatively designed
frame; the latter stiffness results in aconservatively designed
roof panel. Not following this two-step proceduremay result in an
underdesigned frame or roof panel.
5.2.1.1 More research is required before this two-step
analysisprocedure can be simplified for roof diaphragms more than
2.0 times thetest panel length. It has been demonstrated by Lukens
and Bundy (1987)and can be shown by rational application of Davies
and Bryansanalytical methods (Davies and Bryan, 1982) that the
equation inparagraph 3.4.2 overestimates diaphragm stiffness when
extendedbeyond 1.5 times the test panel length. Thus, the actual
stiffness liessomewhere between the two stiffnesses defined in the
previousparagraph.
5.2.2 Typical diaphragm strengths and stiffnesses are not
included inthis Engineering Practice. Typical values may be found
in numerouspublished articles on the subject. (Anderson, 1987;
Conway and White,1979; Gebremedhin and Irish, 1984, 1986; Hausman
and Esmay, 1975;Hoagland, 1981; Hoagland and Bundy, 1983; Lukens
and Bundy, 1987;Turnbull, 1981; Turnbullet al., 1982; Whiteet al.,
1977; White and Tocci,1978). Since diaphragm construction details
will undoubtedly vary fromthose of the diaphragms in the
literature, panel tests will likely have to beperformed in most
instances. Other acceptable engineering analysismethods for
predicting diaphragm strength and stiffness may be used inlieu of
the provisions of Section 3Diaphragm strength and
stiffness.Acceptable methods are those which have been documented
by testingand peer review.
5.3 Commentary for Section 4Design procedures
5.3.1 The procedures outlined for structural analysis of a
metal-clad,timber-framed diaphragm are based on the methods
developed byGebremedhin et al. (1986). The post-frame structural
analyses requiredare all statically indeterminate and are best
performed with a computerprogram. The SOLVER and METCLAD programs
developed byGebremedhin (1987a, 1987b) and PPSA III developed by
the PurdueResearch Foundation (1986) are especially useful for
analysis of the
timber post frames. Other acceptable structural analysis methods
may beused in lieu of the provisions of Section 4Design
Procedures.Acceptable methods are those which have been adequately
validatedand peer-reviewed.
5.3.2 The need for adequate shear and tensile force transfer to
developdiaphragm behavior is addressed in a general manner only.
Thelocations and magnitudes of these forces are identified.
Constructiondetails for transferring the forces are not included.
The uniform loadshown in Fig. 10 is a good approximation for
calculating the diaphragmmoment and chord tensile force if the wall
cladding transfers the loaddirectly to the edge of the diaphragm or
if the building is long and load
is transferred via posts. For short buildings point loads should
replace thedistributed load for moment and chord tensile force
calculations.
5.3.3 There are two potential computational difficulties
associated withthe distributed loads, q and qc, in SOLVER and PPSA
III. Thedistributed load q, as computed in paragraph 4.3.9, is the
load per unitslope length. Many structural analysis programs are
formatted such thatdistributed loads are inputted in load per unit
horizontal and unit verticalprojected lengths. The distributed
load, q, is converted to load per
vertical projected length on each slope by q* (slope
length/verticalprojected length of the slope). The distributed
load, qc , as computed inparagraph 4.4.8, cannot be defined as a
distributed load in computerprograms formatted for distributed
loads on the horizontal and verticalprojected lengths of a member
(the vertical projected length of thehorizontal chord is zero). An
alternative is to divide qc into a series ofconcentrated shear
loads along the length of the lower chord of the truss.
References:
1. AISI. 1986. Cold formed steel design manual. American Iron
and Steel Insti-tute, Washington, DC.
2. Anderson, G. A. 1987. Evaluation of light-gauge metal
diaphragm behaviorand the diaphragms interaction with the post.
M.S. Thesis. Iowa State Univer-sity.
3. Davies, J. M. and E. R. Bryan. 1982. Manual of stressed skin
diaphragmdesign. John Wiley and Sons, New York, NY.
4. Gebremedhin, K. G. and W. W. Irish. 1984. An experimental
investigation ofdiaphragm behavior of farm buildings. ASAE Paper
No. 84-4511. ASAE, St.
Joseph, MI 49085.5. Gebremedhin, K. G., E. L. Bahler and S. R.
Humphreys. 1986. A modifiedapproach to post-frame design using
diaphragm theory. TRANSACTIONS ofthe ASAE 29(5):13641372.
6. Gebremedhin, K. G. and W. W. Irish. 1986. Ultimate
load-deflection charac-teristics and failure modes of ceiling
diaphragms for farm buildings. Wood andFiber Science
18(4):565578.
7. Gebremedhin, K. G. 1987a. SOLVER: An interactive structures
analyzer formicrocomputers. (Version 2). Northeast Regional
Agricultural EngineeringService. Cornell University.
8. Gebremedhin, K. G. 1987b. METCLAD: Diaphragm design of
metal-clad post-frame buildings using microcomputers. Northeast
Regional Agricultural Engi-neering Service. Cornell University.
9. Hausmann, C. T. and M. L. Esmay. 1975. Pole barn wind
resistance designusing diaphragm action. ASAE Paper No. 75-4035.
ASAE, St. Joseph, MI49085.
10. Hoagland, R. C. 1981. Strength and stiffness of
screw-fastened roof panels
for pole buildings. M.S. Thesis. Iowa State University.11.
Hoagland, R. C. and D. S. Bundy. 1983. Strength and stiffness of
screw-fastened roof panels for pole buildings. TRANSACTIONS of the
ASAE26(2):512-515.
12. Lukens, A. D. and D. S. Bundy 1987. Strengths and
stiffnesses of post-framebuilding roof panels. ASAE Paper No.
87-4056. ASAE, St. Joseph, MI 49085.
13. Luttrell, L. D. 1967. Strength and behavior of light-gage
steel sheardiaphragms. Cornell Engineering Research Bulletin 67-1,
41p.
14. NDS. 1986. National design specification for wood
construction. NationalForest Products Association, Washington, DC,
87p.
15. Percival, D. H. 1982. Portable E-tester for selecting
structural componentlumber. Forest Products Journal 31(2):3942.
16. Purdue Research Foundation. 1986. Purdue plane structures
analyzer.(Version 3.0). Department of Forestry and Natural
Resources. Purdue Univer-sity.
17. Turnbull, J. E. 1981. A summary of Canada plan service
diaphragm design forwind bracing in farm buildings. ASAE Paper No.
81-4505. ASAE, St. Joseph,
MI 49085.18. Turnbull, J. E., K. C. McMartin and A. T. Quaile.
1982. Structural performanceof plywood and steel ceiling
diaphragms. Canadian Agricultural Engineer24(2):135140.
19. White, R. N., C. Warshaw and J. Hart. 1977. Shear strength
and stiffness ofaluminum diaphragms in timber-framed buildings.
Research Report No. 370.Department of Structural Engineering.
Cornell University.
20. White, R. N. and A. Tocci. 1978. Diaphragm action in
aluminum-clad timberframing systems. Research Report No. 78-3.
Department of Structural Engi-neering. Cornell University.
728 ASAE STANDARDS 1998
-
5/24/2018 Diaphragm Design of Metal Clad Post Framed
Buildings
11/11
Cited Standards:
ASTM D143-83, Standard Method of Testing Small Clear Specimens
ofTimber
ASTM D198-84, Standard Methods of Static Tests of Timbers in
Struc-
tural Sizes
ASTM D1761-77, Standard Method of Testing Mechanical Fasteners
in
Wood
ASTM E2915-84, Standard Method for Evaluating Allowable
Properties
for Grades of Structural Lumber
ASTM E4-83a, Practices for Load Verification of Testing
Machines
ASTM E72-80, Standard Method for Conducting Strength Tests
of
Panels for Building Construction
ASTM E455-76(1984), Static Load Testing of Framed Floor or
Roof
Diaphragm Construction for Buildings
ASTM E564-76, Standard Method of Static Load Test for Shear
Resis-
tance of Framed Walls for Buildings
ASAE STANDARDS 1998 729