DIAGNOSTIC TESTING USING ASHRAE 110

Gerhard Knutson, Ph.D., CIHKnutson Ventilation, Inc.

952-928-0195

Page 2: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

ASHARE 110A Method of TestingThree components

Face velocity measurementsSmoke visualizationTracer gas testing

“Owner” sets acceptance levelsThe problem

What do you do when the results are unacceptable?

Page 3: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

General Approach

Operational ProblemsTracer gas leakageReentry

Hood problemsAerodynamicsOperations

Room Conditions Other Considerations

Page 4: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Gas Delivery System Leakage

SymptomsSteady increaseNo reduction when gas is turned off

AnalysisUse meter as a leak meter

SolutionStop leakPlace cylinder inside hood

Page 5: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Cylinder Inside the Hood

Page 6: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Reentry

Tracer gas released inside the hoodCharacteristics

Delayed onsetTracer gas in the roomOften slow decay

Page 7: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Potential Reentry

Page 8: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Room Concentration

Page 9: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Repeat with Different Wind

Page 10: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Smoke Visualization

ASHRAE 110 Failure – Smoke spills outDiagnostic testing

Lazy airReverse air flowInterior roll

Page 11: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Reverse FlowReverse flow

Page 12: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Lazy FlowLazy Flow

Page 13: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Good Sweeping Action

Good sweeping flow

Page 14: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Smoke Showing the Hood Roll

Roll in top of hood

Page 15: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Summary

Poor flow characteristic can “pass” but can contribute to poor performanceRepeat somke tests with mannequin

Vortex formed by mannequin interacts with the weak airflow in the hoodCan show spillage where not seen without the mannequin

Page 16: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Equipment in the Hood

Page 17: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Other Issues

Equipment in hoodSash Position

Mandates other than left, right, centerDifference between use and design

Heat sources or disturbances in hoodWork positionOperator position

Page 18: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Room Air Supply

The supply ventilation design is as important (or more important than) the exhaust ventilation designRule of thumb:

Room air currents in the laboratory near the hood should be less than half, preferably less than one third, of the face velocity

Page 19: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Room Air Currents

Side ViewFront View

Top View

Left Center Right

High

Midpoint

Low

VerticalDraft

PerpendicularDraft

HorizontalDraft

Cross Draft Grid & Probe Orientation

Vertical

Horizontal

Perpendicular

Stand

Page 20: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Minor Room Air Currents

Hood 628, Position A, 52.5 inches

0

20

40

60

80

100

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29

Time, Seconds

Velo

city

, fpm Vertical

Perpendicular

Horizontal

Page 21: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Significant Room Air Currents

Hood 628, Position AB, 52.5 inches

0

20

40

60

80

100

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29

Time, seconds

Velo

city

, fpm Vertical

Perpendicular

Horizontal

Page 22: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Case History

New 12-foot bench top hoodsAcceptance level AI 0.05Preliminary tests not acceptableDiagnostic testing

Reverse flow at work surfaceHigh Turbulence in laboratoryHigh Cross drafts near hoodTemperature variable in laboratory

Page 23: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Original Design

Page 24: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Approach

Change diffusers to reduce room air turbulenceModify airfoil on laboratory hoodsModify room temperature controlRecalibrate CV supply and exhaust boxesRewire part of Building Management System – Readout matched boxes

Page 25: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Diffuser Replacement

Page 26: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Original Diffuser and Hood

Hood Rating 0.45

Page 27: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Change Diffuser

Hood Rating 0.03

Page 28: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Changed Diffuser – Modified Airfoil

Hood Rating <0.01

Page 29: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Conclusions

In many instances ASHRAE 110 can be used diagnostically to determine the probable cause of poor hood performance

Page 30: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Other Test

Dynamic testsHuman as a mannequinArtificial clutterWalk by testsLarge apparatus (walk in hoods)Floor mounted fans

Page 31: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Philosophy

Provides additional information relative to robustnessOften no correlation to safetyInterpretation is difficult

Page 32: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Caution

Hoods are designed for specific strengthSome hood manufacturers modifies the hood to provide strength in the top of the hood

Reduce rollAirfoil that tends to “lift” the air up

Some manufacturers provide a strong baseExceptional turning action by airfoilPiston flow in lower portion of the hood

Many manufactures design for general flow

Page 33: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Manufacture Recommended Tests

Higher release rate is better controlled by a hood strong at the topA lower diffuser is better controlled by a hood strong along the work surfaceBoxes and induced flow may work bit the geometry may be criticalSome tests can be self serving

Page 34: DIAGNOSTIC TESTING USING ASHRAE 110 · DIAGNOSTIC TESTING USING ASHRAE 110 Gerhard Knutson, Ph.D., CIH Knutson Ventilation, Inc. 952-928-0195

Conclusion

Special tests are useful and provide additional information concerning the robustness of the hoodOften suggested by user but have no comparative basisHood manufactures recommend tests that favor their hoods