1 DHC VARIZON ® Displacement unit with adjustable spread pattern Quick facts Adjustable spread pattern and affected area Suitable for all types of rooms Air volume measuring point Cleanable Concealed fastening Available in alternative colours Quick guide A I R F L O W S O U N D L E V E L DHC Cubic Feet per Minute 25 NC 30 NC 35 NC 125 130 155 180 160 200 240 275 200 290 340 400 250 400 475 550 315 650 760 900 400 960 1100 1300 500 1400 1600 1800 630 1800 2200 2500 800 3400 3900 4500 Data for the DHC with regulator REG are shown in a separate table.
8

DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20

Jan 24, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20

1

DHCVARIZON® Displacement unit with adjustable spread pattern

Quick facts ► Adjustable spread pattern and affected area

► Suitable for all types of rooms

► Air volume measuring point

► Cleanable

► Concealed fastening

► Available in alternative colours

Quick guideA I R F L O W – S O U N D L E V E L

DHCCubic Feet per Minute

25 NC 30 NC 35 NC

125 130 155 180

160 200 240 275

200 290 340 400

250 400 475 550

315 650 760 900

400 960 1100 1300

500 1400 1600 1800

630 1800 2200 2500

800 3400 3900 4500

Data for the DHC with regulator REG are shown in a separate table.

Page 2: DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20

2Swegon reserves the right to alter specifi cations. 20130425 www.swegon.com

DHC

Technical descriptionDesignThe DHC is a complete, semi-circular displacement unit for wall installation. The body consists of a rear section with top and bottom plates and an air diffusion plate equipped with a number of adjustable discs. The top plate has a circular inlet socket. The diffusion plate has an access hatch for accessing the duct system. The perforated front plate is fastened to the terminal with concealed screws, behind the removable aluminium side strips. The measuring point is placed behind one of the side strips.

Materials and surface treatmentsThe displacement unit is manufactured in galvanized sheet steel and aluminium profi les. It is powder coated with our pure white standard paint, RAL 9010. The unit is also available in other standard colours: Dusty grey 7037, white aluminium RAL 9006, jet black RAL 9005, grey aluminium RAL 9007 and signal white RAL 9003 (NCS 0500).

CustomizationIn addition to the standard sizes, these displacement units are available in special dimensions, with reinforced front plates etc. The duct covers, regulator units and basess can also be supplied in different dimensions. Please contact your nearest sales representative for further information.

AcessoriesRegulator:REG - Combination unit with damper and sound attenuator.

Duct cover:DHCT 1 - for the aesthetic installation of the regulator unit and the connecting circular duct.

Base:DHCT 2 - for the aesthetic installation of the displacement

unit on the fl oor.

Decorative top:DHCT 3. Removable top board either in varnished beech blockboard or white painted medium-density fi berboard (MDF). Can be used when duct cover is not utilized.

PlanningIt is possible to modify the affected area by adjusting the nozzles behind the front plate. This does not affect the air fl ow, pressure drop or sound level. This fl exibility simplifi es any future changes in the furnishings of the room etc.

Page 3: DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20

3Swegon reserves the right to alter specifications. 20130425 www.swegon.com

DHC

Figure 1. Installation

InstallationThe terminal is attached to the wall using angle brackets and screws. The base is screwed into place on the bottom of the unit. The telescopic duct cover is attached to the wall using the wall brackets, the screws being concealed by the side strips. The regulator, which has a circular connection spigot with a rubber seal, is pressed into the inlet socket of the terminal. See fig. 1.

0.79 in

0.67 in

0.67 in

0.67 in

Figure 2. Commissioning. Maintenance.

CommissioningThe measuring point is placed on the side of the displace-ment unit behind the aluminium profile. The k-factor of the unit is marked on one side of the measurement outlet. The k-factor can also be found on our Internet site in the relevant k-factor guide. It is recommended that the REG regulator is used to regulate the air flow. See figure 2.

MaintenanceThe displacement unit can be cleaned when necessary using luke warm water with added detergent. The duct system is accessed by removing the perforated front plate and the inspection hatch. See figure 2.

Page 4: DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20

4Swegon reserves the right to alter specifications. 20130425 www.swegon.com

DHC

Technical data• Sound level NC applies to a room attenuation of 4 dB.

• Maximum recommended temperature difference is -10 °F.

• To calculate the width of the spread pattern, air veloci-ties in the zone of occupation or sound levels in rooms with other dimensions, please refer to our calculation software, ProAir web, available for download at www.swegon.com.

Engineering graphsAir flow – Pressure drop – Sound level – Affected area• The graphs are not to be used for commissioning.

• For data concerning the affected area, see the graph for DHC + REG combination.

DHC 125 to 250

in WGTotal pressure

100 200 300 400 500

0.02

0.030.040.05

0.1

0.2

0.30.40.5

20

25

30

35

40 NC

125 160

200

CFM

DHC 250 to 400

in WGTotal pressure

200 300 400 500 1000 20000.01

0.02

0.030.040.05

0.1

0.2

0.30.40.5

2025

3035

40 NC

250 315

400

CFM

DHC 500 to 800

in WGTotal pressure

1000 2000 3000 4000 50000.005

0.01

0.02

0.030.040.05

0.1

0.2

2025

303540 NC

500 630

800

CFM

Page 5: DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20

5Swegon reserves the right to alter specifications. 20130425 www.swegon.com

DHC

D

in WGTotal pressure

30 40 50 100 200 3000.040.05

0.1

0.2

0.30.40.5

1

2

20

25

30

35

40 NC

100%

0%

0.5 1 2 3 4

2 3 4 5 10t -5 °F∆Affected area at

FPM40a

FPM40b

CFM

DHC 160 + REG

in WGTotal pressure

50 100 200 300 4000.05

0.1

0.2

0.30.40.5

1

2

20

25

30

35

40 NC

100%

0%

1 2 3 4 5

3 4 5 10 20

FPM40a

FPM40b

t -5 °F∆Affected area at

CFM

DHC 200 + REG DHC 250 + REG

in WGTotal pressure

100 200 300 400 500 10000.040.05

0.1

0.2

0.30.40.5

1

2

20

25

30

35

40 NC

100%0%

2 3 4 5 10

4 5 10 20 30t -5 °F∆Affected area at

FPM40a

FPM40b

CFM

in WGTotal pressure

100 200 300 400 500CFM

10000.040.05

0.1

0.2

0.30.40.5

1

2

2025

30

35

40 NC

100%

0%

2 3 4 5 10

4 5 10 20 30t -5 °F∆Affected area at

FPM40a

FPM40b

Air flow – Pressure drop – Sound level – Affected area• The affected area refers to the distance to the isovel limit

of 40 FPM at Dt -5 °F. In this case, Dt signifies the differ-ence between the room air temperature and the supply air temperature, measured at 4 ft above floor level. It does not refer to the difference between the extract air and the supply air temperatures.

• The graphs illustrate data for the displacement unit with the regulator installed.

• The graphs are not to be used for commissioning.

• = min. air flow to obtain sufficient commissioning pressure.

DHC 125 + REG

40

40

Figure 3. Affected area.

Page 6: DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20

6Swegon reserves the right to alter specifications. 20130425 www.swegon.com

DHC

DHC 315 + REG DHC 400 + REG

in WGTotal pressure

200 300 400 500 1000 20000.040.05

0.1

0.2

0.30.40.5

1

2

20

25

30

35

40 NC

100%

0%

4 5 10 20 30

10 20 30 40 50t -5 °F∆Affected area at

FPM40a

FPM40b

CFM

in WGTotal pressure

300 400 500 1000 2000 30000.040.05

0.1

0.2

0.30.40.5

1

2

2025

3035

40 NC

100%

0%

5 10 20 30 40

10 20 30 40 50t -5 °F∆Affected area at

FPM40a

FPM40b

CFM

DHC 500 + REG

in WGTotal pressure

400 500 1000 2000 3000 40000.030.040.05

0.1

0.2

0.30.40.5

1

20

2530

3540 NC

100%

0%

5 10 20 30 40

10 20 30 40 50t -5 °F∆Affected area at

FPM40a

FPM40b

CFM

DHC 630 + REG

in WGTotal pressure

1000 2000 3000 4000 50000.030.040.05

0.1

0.2

0.30.40.5

1

2025

3035

40 NC

100%

0%

10 20 30 40 50

20 30 40 50 100t -5 °F∆Affected area at

CFM

FPM40a

FPM40b

Page 7: DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20

7Swegon reserves the right to alter specifications. 20130425 www.swegon.com

DHC

Dimensions and weightsDHC

SizeDimensions (in) Weight

A B C ØD G kg lbs

125 9.65 24.53 9.84 4.92 4.84 7 15.4

160 11.02 24.53 11.22 6.30 5.51 10 22.0

200 12.60 36.34 12.79 7.87 6.30 15 33.0

250 14.57 36.34 14.76 9.84 7.28 18 39.7

315 17.13 59.96 17.13 12.40 8.58 23 50.7

400 20.47 78.86 20.67 15.75 10.24 29 63.9

500 24.41 78.86 24.41 19.68 12.20 36 79.4

630 29.53 78.86 29.53 24.80 14.76 45 99.2

800 36.22 78.86 36.22 31.50 18.11 56 123.5

REG

SizeDimensions (in)

ØC Ød G H

125 8.90 4.88 11.81 19.68

160 10.04 6.26 11.81 19.68

200 11.34 7.84 11.81 19.68

250 13.58 9.80 11.81 19.68

315 15.87 12.36 11.81 31.50

400 18.86 15.71 13.78 31.50

500 23.62 19.65 13.78 35.43

630 28.74 24.76 13.78 35.43

Figure 5. Regulator unit REG.

Figure 4. DHC

Figure 6. DHC with duct cover and base. 1: Size 125-315: 95 - 108 inches. Size 400: 112 - 126 inches. If other lengths are required always state the total room height.

Page 8: DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20

8Swegon reserves the right to alter specifications. 20130425 www.swegon.com

DHC

Specification example SD XX

Swegons VARIZON® semi-circular displacement unit of type DHC, having the following functions:

• Adjustable spread pattern and affected area

• Air volume measuring point

• Concealed fastening

• Cleanable

• Powder coated in white paint, RAL 9010

Size: DHCe aaa xx items

Accessories

Duct cover: DHCT 1 aaa xx items

Base: DHCT 2 aaa - 70 xx items

Ordering keyProduct

Semi-circular displacement unit DHC e -aaa

Version:

Size: 125, 160, 200, 250 315, 400, 500, 630, 800

Accessories

Duct cover DHCT 1 d -aaa

Version:

Size: 125, 160, 200, 250, 315, 400

Specify special dimensions. Always state the total room height.

Base DHCT 2 a -aaa 70

Version:

Size: 125, 160, 200, 250, 315, 400, 500, 630, 800

Height in mm. Specify special heights. Always state the total room height.

Regulator unit REG b -aaa

Version:

Size: 125, 160, 200, 250, 315, 400, 500, 630

Decorative top DHCT 3 a

Version:

Please contact your nearest sales representative for further help with the design of the product.