1 DHC VARIZON ® Displacement unit with adjustable spread pattern Quick facts ► Adjustable spread pattern and affected area ► Suitable for all types of rooms ► Air volume measuring point ► Cleanable ► Concealed fastening ► Available in alternative colours Quick guide A I R F L O W – S O U N D L E V E L DHC Cubic Feet per Minute 25 NC 30 NC 35 NC 125 130 155 180 160 200 240 275 200 290 340 400 250 400 475 550 315 650 760 900 400 960 1100 1300 500 1400 1600 1800 630 1800 2200 2500 800 3400 3900 4500 Data for the DHC with regulator REG are shown in a separate table.
8
Embed
DHC - Swegon · 2018. 5. 24. · 5 Swegon reserves the right to alter specifications. 20130425 DHC D in WG Total pressure 30 40 50 100 200 300 0.04 0.05 0.1 0.2 0.3 0.4 0.5 1 2 20
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
1
DHCVARIZON® Displacement unit with adjustable spread pattern
Quick facts ► Adjustable spread pattern and affected area
► Suitable for all types of rooms
► Air volume measuring point
► Cleanable
► Concealed fastening
► Available in alternative colours
Quick guideA I R F L O W – S O U N D L E V E L
DHCCubic Feet per Minute
25 NC 30 NC 35 NC
125 130 155 180
160 200 240 275
200 290 340 400
250 400 475 550
315 650 760 900
400 960 1100 1300
500 1400 1600 1800
630 1800 2200 2500
800 3400 3900 4500
Data for the DHC with regulator REG are shown in a separate table.
2Swegon reserves the right to alter specifi cations. 20130425 www.swegon.com
DHC
Technical descriptionDesignThe DHC is a complete, semi-circular displacement unit for wall installation. The body consists of a rear section with top and bottom plates and an air diffusion plate equipped with a number of adjustable discs. The top plate has a circular inlet socket. The diffusion plate has an access hatch for accessing the duct system. The perforated front plate is fastened to the terminal with concealed screws, behind the removable aluminium side strips. The measuring point is placed behind one of the side strips.
Materials and surface treatmentsThe displacement unit is manufactured in galvanized sheet steel and aluminium profi les. It is powder coated with our pure white standard paint, RAL 9010. The unit is also available in other standard colours: Dusty grey 7037, white aluminium RAL 9006, jet black RAL 9005, grey aluminium RAL 9007 and signal white RAL 9003 (NCS 0500).
CustomizationIn addition to the standard sizes, these displacement units are available in special dimensions, with reinforced front plates etc. The duct covers, regulator units and basess can also be supplied in different dimensions. Please contact your nearest sales representative for further information.
AcessoriesRegulator:REG - Combination unit with damper and sound attenuator.
Duct cover:DHCT 1 - for the aesthetic installation of the regulator unit and the connecting circular duct.
Base:DHCT 2 - for the aesthetic installation of the displacement
unit on the fl oor.
Decorative top:DHCT 3. Removable top board either in varnished beech blockboard or white painted medium-density fi berboard (MDF). Can be used when duct cover is not utilized.
PlanningIt is possible to modify the affected area by adjusting the nozzles behind the front plate. This does not affect the air fl ow, pressure drop or sound level. This fl exibility simplifi es any future changes in the furnishings of the room etc.
3Swegon reserves the right to alter specifications. 20130425 www.swegon.com
DHC
Figure 1. Installation
InstallationThe terminal is attached to the wall using angle brackets and screws. The base is screwed into place on the bottom of the unit. The telescopic duct cover is attached to the wall using the wall brackets, the screws being concealed by the side strips. The regulator, which has a circular connection spigot with a rubber seal, is pressed into the inlet socket of the terminal. See fig. 1.
0.79 in
0.67 in
0.67 in
0.67 in
Figure 2. Commissioning. Maintenance.
CommissioningThe measuring point is placed on the side of the displace-ment unit behind the aluminium profile. The k-factor of the unit is marked on one side of the measurement outlet. The k-factor can also be found on our Internet site in the relevant k-factor guide. It is recommended that the REG regulator is used to regulate the air flow. See figure 2.
MaintenanceThe displacement unit can be cleaned when necessary using luke warm water with added detergent. The duct system is accessed by removing the perforated front plate and the inspection hatch. See figure 2.
4Swegon reserves the right to alter specifications. 20130425 www.swegon.com
DHC
Technical data• Sound level NC applies to a room attenuation of 4 dB.
• Maximum recommended temperature difference is -10 °F.
• To calculate the width of the spread pattern, air veloci-ties in the zone of occupation or sound levels in rooms with other dimensions, please refer to our calculation software, ProAir web, available for download at www.swegon.com.
Engineering graphsAir flow – Pressure drop – Sound level – Affected area• The graphs are not to be used for commissioning.
• For data concerning the affected area, see the graph for DHC + REG combination.
DHC 125 to 250
in WGTotal pressure
100 200 300 400 500
0.02
0.030.040.05
0.1
0.2
0.30.40.5
20
25
30
35
40 NC
125 160
200
CFM
DHC 250 to 400
in WGTotal pressure
200 300 400 500 1000 20000.01
0.02
0.030.040.05
0.1
0.2
0.30.40.5
2025
3035
40 NC
250 315
400
CFM
DHC 500 to 800
in WGTotal pressure
1000 2000 3000 4000 50000.005
0.01
0.02
0.030.040.05
0.1
0.2
2025
303540 NC
500 630
800
CFM
5Swegon reserves the right to alter specifications. 20130425 www.swegon.com
DHC
D
in WGTotal pressure
30 40 50 100 200 3000.040.05
0.1
0.2
0.30.40.5
1
2
20
25
30
35
40 NC
100%
0%
0.5 1 2 3 4
2 3 4 5 10t -5 °F∆Affected area at
FPM40a
FPM40b
CFM
DHC 160 + REG
in WGTotal pressure
50 100 200 300 4000.05
0.1
0.2
0.30.40.5
1
2
20
25
30
35
40 NC
100%
0%
1 2 3 4 5
3 4 5 10 20
FPM40a
FPM40b
t -5 °F∆Affected area at
CFM
DHC 200 + REG DHC 250 + REG
in WGTotal pressure
100 200 300 400 500 10000.040.05
0.1
0.2
0.30.40.5
1
2
20
25
30
35
40 NC
100%0%
2 3 4 5 10
4 5 10 20 30t -5 °F∆Affected area at
FPM40a
FPM40b
CFM
in WGTotal pressure
100 200 300 400 500CFM
10000.040.05
0.1
0.2
0.30.40.5
1
2
2025
30
35
40 NC
100%
0%
2 3 4 5 10
4 5 10 20 30t -5 °F∆Affected area at
FPM40a
FPM40b
Air flow – Pressure drop – Sound level – Affected area• The affected area refers to the distance to the isovel limit
of 40 FPM at Dt -5 °F. In this case, Dt signifies the differ-ence between the room air temperature and the supply air temperature, measured at 4 ft above floor level. It does not refer to the difference between the extract air and the supply air temperatures.
• The graphs illustrate data for the displacement unit with the regulator installed.
• The graphs are not to be used for commissioning.
• = min. air flow to obtain sufficient commissioning pressure.
DHC 125 + REG
40
40
Figure 3. Affected area.
6Swegon reserves the right to alter specifications. 20130425 www.swegon.com
DHC
DHC 315 + REG DHC 400 + REG
in WGTotal pressure
200 300 400 500 1000 20000.040.05
0.1
0.2
0.30.40.5
1
2
20
25
30
35
40 NC
100%
0%
4 5 10 20 30
10 20 30 40 50t -5 °F∆Affected area at
FPM40a
FPM40b
CFM
in WGTotal pressure
300 400 500 1000 2000 30000.040.05
0.1
0.2
0.30.40.5
1
2
2025
3035
40 NC
100%
0%
5 10 20 30 40
10 20 30 40 50t -5 °F∆Affected area at
FPM40a
FPM40b
CFM
DHC 500 + REG
in WGTotal pressure
400 500 1000 2000 3000 40000.030.040.05
0.1
0.2
0.30.40.5
1
20
2530
3540 NC
100%
0%
5 10 20 30 40
10 20 30 40 50t -5 °F∆Affected area at
FPM40a
FPM40b
CFM
DHC 630 + REG
in WGTotal pressure
1000 2000 3000 4000 50000.030.040.05
0.1
0.2
0.30.40.5
1
2025
3035
40 NC
100%
0%
10 20 30 40 50
20 30 40 50 100t -5 °F∆Affected area at
CFM
FPM40a
FPM40b
7Swegon reserves the right to alter specifications. 20130425 www.swegon.com
DHC
Dimensions and weightsDHC
SizeDimensions (in) Weight
A B C ØD G kg lbs
125 9.65 24.53 9.84 4.92 4.84 7 15.4
160 11.02 24.53 11.22 6.30 5.51 10 22.0
200 12.60 36.34 12.79 7.87 6.30 15 33.0
250 14.57 36.34 14.76 9.84 7.28 18 39.7
315 17.13 59.96 17.13 12.40 8.58 23 50.7
400 20.47 78.86 20.67 15.75 10.24 29 63.9
500 24.41 78.86 24.41 19.68 12.20 36 79.4
630 29.53 78.86 29.53 24.80 14.76 45 99.2
800 36.22 78.86 36.22 31.50 18.11 56 123.5
REG
SizeDimensions (in)
ØC Ød G H
125 8.90 4.88 11.81 19.68
160 10.04 6.26 11.81 19.68
200 11.34 7.84 11.81 19.68
250 13.58 9.80 11.81 19.68
315 15.87 12.36 11.81 31.50
400 18.86 15.71 13.78 31.50
500 23.62 19.65 13.78 35.43
630 28.74 24.76 13.78 35.43
Figure 5. Regulator unit REG.
Figure 4. DHC
Figure 6. DHC with duct cover and base. 1: Size 125-315: 95 - 108 inches. Size 400: 112 - 126 inches. If other lengths are required always state the total room height.
8Swegon reserves the right to alter specifications. 20130425 www.swegon.com
DHC
Specification example SD XX
Swegons VARIZON® semi-circular displacement unit of type DHC, having the following functions:
• Adjustable spread pattern and affected area
• Air volume measuring point
• Concealed fastening
• Cleanable
• Powder coated in white paint, RAL 9010
Size: DHCe aaa xx items
Accessories
Duct cover: DHCT 1 aaa xx items
Base: DHCT 2 aaa - 70 xx items
Ordering keyProduct
Semi-circular displacement unit DHC e -aaa
Version:
Size: 125, 160, 200, 250 315, 400, 500, 630, 800
Accessories
Duct cover DHCT 1 d -aaa
Version:
Size: 125, 160, 200, 250, 315, 400
Specify special dimensions. Always state the total room height.
Base DHCT 2 a -aaa 70
Version:
Size: 125, 160, 200, 250, 315, 400, 500, 630, 800
Height in mm. Specify special heights. Always state the total room height.
Regulator unit REG b -aaa
Version:
Size: 125, 160, 200, 250, 315, 400, 500, 630
Decorative top DHCT 3 a
Version:
Please contact your nearest sales representative for further help with the design of the product.