Top Banner

of 32

Design of Fire Protection Systems for Tall Buildings

Jul 06, 2018

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    1/32

     

    Design of Fire Protection Systems for Tall Buildings

    And

    Problems in the light of Case study 

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    2/32

    Index

    1. 

    Background of fires in Tall Buildings

    2.  Characteristic of Tall Buildings

    3.  Comparison between Low Rise and High Rise Buildings

    4.  Design Of Fire Protection Systems in the light of Standards and

    Codes

    5.  Fire-Resistance-Rated Construction

    6.  Fire Protection System

    7.  Problems of Fire protection systems with WTC Case Study

    8.  Conclusion

    9. 

    References

    10.  Appendices

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    3/32

    Background of Fires in Tall Buildings

    Recent collapse of tall building had a havoc effects and have made an all designers and building

    engineers reconsider the potential dangers to the structures and the safety of the inhabitants. Now

    fires in Tall buildings have become a prominent possible reason for collateral damage of both

    life and finances. These structures pose an equal threat to the neighboring structures as well.

    The only reason that designer didn’t previously considered it as a potential threat was that

    occurrence of these events are very less. But detailed studies after the WTC event have shown

    immense levels of flaws in the fire protection systems of tall buildings. The recent examples of

    fires resulting into complete collapse are the WTC 1, 2 and 7. Then the complete collapse of

    Apartment Block in St. Petersburg, Russia in June 3.2002, then Jackson Street apartments in

    Hamilton, Ontario, Canada in Feb 8,2002. A list of collapses has been provided in the Appendix

    2 of all the collapse that was seen in the past. The concept of fire proof construction is that the

    despite the complete burnout of the structure, the structure must not collapse at any cost. For this

    there are two steps that are taken by the standards and other implementation bodies. Firstly the

     building should be resistant to fire for a certain level which about 3 hrs, this is done to safeguard

    from the collapse of structure and secondly an effective fire protection system should be in place,

    which is present for the purpose of detection, fire fighting and for effective evacuation of

    inhabitants. At present the only International Building Code IBC 2006 solely has prescriptive fire

    resistance construction regulations and bounds the designer to follow it for protection of

    structure against fire. IBC is also supported by National Fire Protection Association and other

    similar organization, which I have discussed in detail in later sections. The Approach of this

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    4/32

    report would be very similar to the process involved in designing a fire resistant Tall building

    with effective fire protection system.

    Characteristic of Tall Buildings

    As we are well aware of the processes through which the fire protection facility is brought into

    commission, where the first phase is the analysis and requirement determination of the fire

     protection, then the second is the design of these required systems, the third is the construction

    and finally the maintenance and operations of these systems.

    Before the commencement of the design phase of a fire protection system the first and foremost

    step is to evaluate and analyze the building features and when does it become of detrimental to

    design a prefect system. What are the different category of buildings and the types of

    construction. The first and basic categorization is on the basis of number of stories, under which

    the building which has more than 7 stories is declared as tall building. Then these tall building or

    high rise building are subdivided into four property classes, where first is Apartment Buildings,

    second being Hotels, Hospitals and other facilities that care for the sick and Office Buildings

     being the third and fourth type.

    On the other hand the discrimination is made on the basis of construction material. According to

     National Fire Protection Association, (NFPA 220, 2006) there are two basic types of

    construction: it either burns (combustible) or it does not (noncombustible). These types of

    construction can be further broken down into five categories. Type I is fire-resistive construction

    which majorly consists of materials such as precast concrete slabs, concrete columns and beams

    in this type the structural members are designed to resist fire for about 3 -4 hours and have

    sufficient fire resisting rating. Type II is Noncombustible, this type represents those building

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    5/32

    having steel beams and girders, they are susceptible to steel deformation and resulting collapse

    with less or no warning. Where as Type III is the ordinary construction, Type IV is the Heavy

    Timber, Type V is Wood Frames but these structures are not used to make tall buildings and IBC

     permits only Type I and Type II to be used.

     Now the first problem that arises is that, at present all over the world fire regulations and

     building codes through out the world using performance-based systems. These systems include

    aspects like (David Scott, 2006) Calculation of fire size, means of detection and suppression,

    smoke management fire initiation and development, means of escape, fire fighting facilities and

    response, materials and their response to fire – internal linings and finishes and etc. But the real

    issue is that all these provide us the post fire situation and does not consider the collapse analysis

    of the structure as a whole and elements as individuals. Where as the latest concept of induced

     progressive collapse solves the major issues and now through these analysis techniques and

     procedures we can simulate and calculate the failure pattern and forces due to fire loadings

    which were not possible before. The progressive collapse analysis is now becoming the basis of

    almost all codes that consider fire protections. The structural response is evaluated on the basis

    of two aspects, firstly it is the dimensions of the facility, secondly and more importantly it is the

     burning behavior of material. As mentioned before mainly there are two materials used in the

    structures esp the high rise. These are concrete and steel.

    The interaction between fires and structural element and then the consequent response of the

    structure as whole is largely analyzed and affected by few aspects which includes burning

     behavior of materials including the mass loss and energy release, then stages of fire development

    and lastly interaction of fully developed fire. Covering these aspects briefly the burning behavior

    of materials can be shown in the following equation. (James, FEMA)

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    6/32

    ′′  =′′ 

    ∆ 

    Where

    Q’’= energy released per unit surface area of fuel

    q’’= incident heat released per unit surface area of fuel

    Lv= latent heat of vaporization ∆ = Heat of combustion 

    Where as other aspects included stages of the fire development, these include initiation of fire

    from single fuel object. The next stage is the transfer of smoke plume’s heat energy into smoke

    layer. Therefore the temperature and depth of these layers are increased. The layer produced till

    now then starts to ignite the unburned material or fuel giving further rise to temperature.

    Therefore it can be deduced that the fire is transfer through mainly two means the first is from

    radiation of heat and the other is through the smoke layer that is created. This cycle is repeated

    resulting into exponential increase in the temperature of fire. Then comes the stage of subsequent

     pattern of burning of fuel, which subdivided by compartment size. The small compartment’s

    unburned object normally catches fire simultaneously and this process is called Flashover.

    Where as large compartment’s objects can fire in an order and sequence.

    A fire is declared as fully developed when it acquires a steady state burning stage and the mass

    loss is a constant with respect to time. The main reason for this state is the lack of ventilation or

    the fuel type. According to the equation given above if the rate of burning with constant influx

    heat exceeds the quantity that can be supported by available air, then under these conditions the

     burning becomes ventilation controlled otherwise it is fuel controlled.

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    7/32

    The case study of WTC 1 and WTC 2 shows that 3 GW fire could be supported by a flow of

    1500000 cfm and which could have been supplied through openings in exterior wall and shaft

    walls. Given that heat released per unit of oxygen is a relatively constant value of 13.1 kj/g for

    common fuels, the air supply required to support fires. It is to be noted that every 1 MW of heat

    resale rate consumes 76 g/s and there is 21% of oxygen which requires 0.24m3/s (500 cfm) of

    ambient air.

    As we are well aware of the fact that the fire resistance of the structure is deduced on the basis of

    several aspects which include the loading on the structure, member types and dimensions and

    finally and most importantly construction materials used. Fires in buildings induce geometric

    (thermal expansion) and material effects (reduction in strength and stiffness) in structural

    elements. There are two types of materials that need to be assessed for fire resistance, firstly steel

    and secondly concrete. The mechanical and thermal properties of these materials are of

    importance to assess the structural response. To assess these attributes test such as ASTM E119,

    ASTM E1529, UL 1709 are performed and then later the results are translated into codes. The

    response of steel structures is based on the deflection and deformation. The reason for this is that

    when fire increases the temperature of the steel frame as a result the strength also decreases, this

    gives rise to dangerous deformations, consequently the very basic structural properties of the

    material such as modulus of elasticity changes which was considered constant in the design

     phase and eventually the failure of facility is inevitable. So to analyze the structural response of

    the structure we resort to structural mechanics analysis methods such as progressive collapse

    analysis.

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    8/32

    Comparison between Low Rise and High Rise Buildings

    The level of danger in small buildings and high rise building, although much research has not be

    done on this comparison, the reason for which is lack of data available and basic difference of

    conception & design may make it incomparable. Where as a comprehensive research has been

    made by Fire Analysis and Research Division at National Fire Protection Association. According

    to which they have gather all the data available both high rise and non high rise buildings and

    after the analysis of the data sample. They have come to a conclusion that during 1999-2002, an

    average of 7.7%-11.6% apartment fire broke out in non high rise building, in the analysis one

    assumption is considered which is that these apartments were occupied throughout the year and

    the building consisted of 3 or more housing units. Whereas on the other hand in the very same

    time period of In 1999-2002, the high-rise percentage of apartment fires was in the range of 8-

    10%.

    The two percentages 7.7-11.6%(non high rise ) and 8-10% (high rise) are almost the same.

    Therefore it cannot be declared that the fire risk in high rise building is lesser or higher when in

    comparison to non high rise or apartment buildings.

    Another estimate and analysis is made by U.S. Energy Information Administration which

    calculate the fire risk on the basis of floor space which is represented by the percentage exposure

    that is directly proportional to floor spaces in high rise buildings. Accroding to the the empirical

    relationship developed by EIA the high rise share of exposure (floor space) for lodging, hotels is

    7%-24.8% (considering 17.2%),for office buildings the figure ranges from 9.4-26.9% (middle

    estimate 19.4%) and for health care facilities it is 15.7-37.4% with an average value of 28.1%.

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    9/32

    After similar calculation, analysis and estimate it was suggested by John R. Hall, Jr. of National

    Fire Protection Association that “high-rise buildings are less risky than low-rise buildings

    for office buildings. For hotels and motels and for hospitals and other facilities that care for the

    sick, the risks appear comparable in high-rise and low-rise buildings”.

    Hence from all this discussion and research it can be concluded that evidence and ground cases

    and their studies shows that the risk of fires does not directly links to the height or its being high

    rise or non high rise. The risk of fire is mainly dependent on the purpose, usage and

    serviceability of the structure and does independent to the no of floors.

    Design Of Fire Protection Systems

    in the light of

    Standards and Codes

    There are many standards and codes that dictate the design and planning of fire protection

    systems. Through researching I have come to a conclusion that there are very few regulations

    and standards that legally bound the designer to design keeping fire protection as the primary

     basis of failure. In British standards unlike others the difference for fire protection is made on the

     basis of the material of construction which is steel, for which British Standard EuroCode 3. Part

    1-2: General rules — Structural fire design is employed, then for composite or concrete

    structures are based on BS EN 1994-1-2 Design of Composite Steel and Concrete Structures.

    General Rules Structural Fire Design. Then other standards include BS 5950-8: Part 8: Code of

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    10/32

     practice for fire resistant design. Where as on the other side the most prominent among these are

     National Fire Protection Association (NFPA) and then comes the International Code Council and

    its International Building Codes IBC. Where as the there are many organizations that also

     provide these guidelines and assistance to the design and regulation system. The organizations

    with good implementation and impact include Health, Safety, and the Environment (HSE), 

    Health and Safety Executives, Royal Institute of British Architects and  Society of Fire Protection

    Engineers (SFPE) a professional association for fire protection engineering, E-5 committee,

    ASTM International, National Institute of Standards and Technology (NIST)—The Building and

    Fire Research Laboratory at NIST,  Underwriters Laboratories (UL) which is a product-safety

    testing and certification organization. The list of bodies and local regulatory organization is quite

    extended. So for the time moment we have to restrict ourselves to only those which have the

    highest impact value in the world and have a status of a regulatory body, which the builder of

    facility is legally bound to follow.

    The most widely used code around the world is the International Building Code IBC 2006. This

    code is followed and used throughout the globe , in addition all the local or national codes that

    are developed in the other country are derivative of the IBC 2006. Where as on the other hand in

    the UK the BS 5950-8 Code of practice for fire resistant design is the most widely used. The

    another reason apart from the extensive usage of the IBC 06 and BS 5950-8 that these are the

    only codes available which has incorporated both aspects of fire protection system. It has

    extensive restriction and bounding of design of structural member that is covered in the chapter 7

    of the IBC 06 and Part 8 of the BS 5950 under the title of Fire-Resistance-Rated Construction.

    This makes it the only code that bounds the designer to design every aspect according to fire

     protection, without going to any other standard separately. Therefore the upcoming discussion

    http://www.google.com.pk/url?sa=t&source=web&cd=3&ved=0CD4QFjAC&url=http%3A%2F%2Fwww.slb.com%2Fhse.aspx&rct=j&q=HSE&ei=EMuzTbL7G4e8rAeG-sjIDQ&usg=AFQjCNEcpxzZIqj4_B-GUt5_V1ys83DQ_g&cad=rjahttp://www.sfpe.org/http://www.sfpe.org/http://www.fire.nist.gov/http://www.ul.com/http://www.ul.com/http://www.fire.nist.gov/http://www.sfpe.org/http://www.sfpe.org/http://www.google.com.pk/url?sa=t&source=web&cd=3&ved=0CD4QFjAC&url=http%3A%2F%2Fwww.slb.com%2Fhse.aspx&rct=j&q=HSE&ei=EMuzTbL7G4e8rAeG-sjIDQ&usg=AFQjCNEcpxzZIqj4_B-GUt5_V1ys83DQ_g&cad=rja

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    11/32

    would be on the basis of two aspects of fire protection, firstly it would be using the codes for

     protection of the building and structure which would employ the fire resisting construction of the

    facility. Secondly the discussion would be on the fire protection system themselves. Then the

    British standard has provided us with a design flow chart to follow as well which I have included

    in the appendix 1. Where as there are many British Standards and Euro codes on fire protection

    some of which are listed below which are acquired from the web portal of British Standards

    Institution. These are

    Fire detection and alarm systems: 

    BS 10999:2010Specification for distress signal units for the fire and rescue service

    BS 5839-1:2002+A2:2008

    Fire detection and fire alarm systems for buildings. Code of practice for system design,

    installation, commissioning and maintenance

    BS 5839-8:2008

    Fire detection and fire alarm systems for buildings. Code of practice for the design, installation,commissioning and maintenance of voice alarm systems

    PAS 79:2007

    Fire risk assessment. Guidance and a recommended methodology

    The bestselling guide gives a nine-step approach to fire risk assessment in buildings

    Fire extinguishing/fighting equipment: 

    BS 336:2010

    Specification for fire hose couplings and ancillary equipment

    BS 5306:2009

    Fire extinguishing installations and equipment on premises. Commissioning and maintenance of portable fire extinguishers. Code of practice

    BS 750:2006Specification for underground fire hydrants and surface box frames and covers

    BS EN 14339:2005Underground fire hydrants

    http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030194710http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030171701http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030136499http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030168131http://shop.bsigroup.com/ProductDetail/?pid=000000000030176708http://shop.bsigroup.com/ProductDetail/?pid=000000000030152564http://shop.bsigroup.com/ProductDetail/?pid=000000000030167157http://shop.bsigroup.com/ProductDetail/?pid=000000000030064831http://shop.bsigroup.com/ProductDetail/?pid=000000000030064831http://shop.bsigroup.com/ProductDetail/?pid=000000000030167157http://shop.bsigroup.com/ProductDetail/?pid=000000000030152564http://shop.bsigroup.com/ProductDetail/?pid=000000000030176708http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030168131http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030136499http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030171701http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030194710

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    12/32

    Design & fire safety: 

    BS 9999:2008

    Code of practice for fire safety in the design, management and use of buildings

    Fire sprinkler systems: 

    BS EN 12845+Amendment 1:2009

    Fixed firefighting systems. Automatic sprinkler systems. Design, installation and maintenance

    Fire testing: 

    BS 476-10:2009

    Fire tests on building materials and structures. Guide to the principles, selection, role andapplication of fire testing and their outputs

    Fire-Resistance-Rated Construction

    The first thing that is determined is the fire resistance rating of the key building elements for

    which the test such as BS 476-10:2009 and   ASTM E 119 is employed as the basic and

     preliminary yard stick. On the other hand  BS 10999:2010 , ASTM E1529 and UL 1709 are also

    used for the reference and quality assurance. Whereas alternative methods to determine the fire

     protection rating includes NFPA 252 or BS476 Part 21. Then materials required to be

    noncombustible shall be tested in accordance with ASTM E 136, in addition with a surfacing not

    more than 0.125 inch (3.18 mm) thick that has a flame spread index not greater than 50 when

    tested in accordance with ASTM E 84 shall be acceptable as noncombustible materials. Then

    under the section 705 of the IBC 06 we have to make a firewall, this is a wall which is fire-

    resistance rated wall used to protect opening and contain fires to a certain area. These are

    extended from the foundation to or through roofs. The material should be noncombustible and

    they should be structurally stable so that under fire conditions the possible collapse of

    http://shop.bsigroup.com/ProductDetail/?pid=000000000030158436http://shop.bsigroup.com/ProductDetail/?pid=000000000030208000http://shop.bsigroup.com/ProductDetail/?pid=000000000030147205http://shop.bsigroup.com/en/Browse-by-Subject/Fire/http://shop.bsigroup.com/ProductDetail/?pid=000000000030147205http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030194710http://shop.bsigroup.com/en/ProductDetail/?pid=000000000030194710http://shop.bsigroup.com/ProductDetail/?pid=000000000030147205http://shop.bsigroup.com/en/Browse-by-Subject/Fire/http://shop.bsigroup.com/ProductDetail/?pid=000000000030147205http://shop.bsigroup.com/ProductDetail/?pid=000000000030208000http://shop.bsigroup.com/ProductDetail/?pid=000000000030158436

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    13/32

    construction but not the wall providing a safe exist duration to the inhabitants. The fire resistance

    rating of fire wall is in the table below which is taken from IBC 2006 section 705.4

    The codes bounds to have continuous from exterior wall to exterior wall and shall extend at least

    18 inches (457 mm) beyond the exterior surface of exterior walls for Horizontal continuity and

    for Vertical continuity. Fire walls shall extend from the foundation to a termination point at least

    30 inches (762 mm) above both adjacent roofs.

    Among the walls for fire protection then it’s the fire partitions, these are the wall which include

    separation in housing units in the same building, sleeping units in hotels, corridor walls and

    elevator lobby separation. The material must be used must be resistant for at least 1 hour. Next it

    is the smoke barrier that needs to be build, a smoke barrier is a continuous membrane, either

    vertical or horizontal, such as a wall, floor, or ceiling assembly, which is designed and

    constructed to restrict the movement of smoke. A1-hour fire-resistance rating is required for

    smoke barriers at minimum.

    Then it’s the design of Fire-Resistant Joint Systems that is of major concern to the fire protection

    of the structure. This includes joints between walls, floors, roofs and their assemblies. These

     joints must comply with the requirements of either ASTM E 1966 or UL 2079.The fire resistant

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    14/32

     joints in smoke barriers are of prime importance and it shall be tested in accordance with the

    requirements of UL 2079 for air leakage.

    The air leakage rate of the joint shall not exceed 5 cfm per lineal foot (0.00775 m3/slm ) of joint

    at 0.30 inch (7.47 Pa ) of water for both the ambient temperature and elevated temperature tests.

    One of the most important part of structural fire safety involves the description of fire resistance

    of structural members, these members include columns, griders, trusses, beams and other force

     bearing members and they all must comply to a the required fire resistance. For these members

    in high rise building the codes bounds that the all members must have individually protected on

    all sides for the full length with materials having the required fire-resistance rating. Then the

    connection points and edges of lugs, brackets, rivets and bolt heads attached to structural

    members shall be permitted to extend to within 1 inch (25 mm) of the surface of the fire

     protection. The reinforcement of the concrete must also be protected but the stirrups and spiral

    reinforcement ties are permitted to project not more than 0.5-inch (12.7 mm) into the protection.

    Then it is to be noted that the fire protection is not required in bottom flange of lintels, shelf

    angles and plates. Whereas the isolation systems used for the protection of earthquake must also

     be fire protected and should have a sufficient fire resistance rating which comply with ASTM E-

    119.

    The section 715 of the IBC 2006 has a detailed standards on opening protections which the types

    of assembly. The table below is the descriptive of all the contents in the standards regarding the

    opening protections.

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    15/32

     

    These were a few most important aspects of the fire protection of the structure itself, there are

    several more aspects that are to be considered in the design of the fire resistant construction in

    the code which include Ducts And Air Transfer Openings, Thermal- And Sound-Insulating

    Materials, Fire-Resistance Requirements For Plaster. Lastly the code describes the procedure for

    calculating the fire protection rating of certain material and in different combinations. Now we

    will move towards the fire protection systems and how are they designed according to the codes

    and standards.

    IBC is one of the very few codes which dictate the dimensions and restrictions on the dimensions

    of the key structural members with respect to the fire protection ratings. So we will discuss a few

    most important members and the restrictions that are imposed under the IBC. All the tables

     below are extracts from the International Building Codes. The minimum slab thickness is shown

    in the table below. Which is self explanatory.

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    16/32

     

    Then the next structural component is cover which is to be provided to the concrete.

    Then we have to look into the dimensional restriction of the columns, where the IBC say to have

    a restricted the dimensions to values indicated in the table below.

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    17/32

    Fire Protection System

    The IBC 2006 is in direct coherence with the International Fire Code, and all the sections and

    clause related to fire protection in IBC 2006 are derivatives of International fire Codes. The first

    aspect of the fire protection system would be the Automatic Sprinkler System. The positions of

    the system are extensively prescribed in the code and these locations are categorized in groups of

    occupancies and other aspects. The first group is Group-A and its sub-group is Group A-1 which

    is defined as that occupancy where fire area exceeds 12000 square feet and there are more than

    300 occupants and area contains a multiheater complex. There are many other groups which

    include various and diverse conditions and specified buildings. The conclusion from this section

    is that, we have to provide an automatic Sprinkler system in a high rise building. Now the issue

    is what standards to follow in regards to the specification of sprinkler system. The system shall

     be designed and installed in accordance to NFPA 13 sprinkler systems. Then the water supply

    system must comply with the international plumbing codes as well, where the protection from

     backflow must be provided. A very important aspect that can not be overseen in the high rise fir

     protection system is the Secondary Water supply. A back up or secondary water supply is to be

    designed hydraulically and the sprinkler demand and hose stream is calculated and is provided in

    high-rise buildings in Seismic Design Category C, D, E or F. The secondary system sustenance

    time should be greater than 30 min and the rest must be in coherence with NFPA 13.

    Alarms should be connected to the automatic sprinkler system and these alarms must be audile

    and should be activated on abnormal flow in the sprinkler system. They should be provided on

    the exterior size of the buildings and the activation of sprinkler system should activate the

    facility’s fire alarm system. It is detrimental that floor control values should be provided in Tall

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    18/32

    Buildings. These values should be located at the point of connection to the riser on every floor in

    tall building.

    The Standpipe Systems is an integral part of the fire protection system and it becomes of

    immense importance when it comes to high rise buildings as the fires are of massive and

    normally sprinkler systems alone cannot handle the fire. The stand pipe must be selected and

    installed in accordance to NFPA 14. According to which Class I system is used in high rise

     buildings. Class I system is a system providing 21/2-inch (64 mm) hose connections to supply

    water for use by fire departments and those trained in handling heavy fire streams. In the design

    of standpipe system and its connection’s location is of key importance, the stand pipe hose is to

     be provided in every floor’s stairway and should be provided at an intermediate floor level

    landing. It should be on each side of the exit opening, at every exit passageway at entrance from

    the exit passageway. It is also important to provide hose where the sprinklers are absent. Then

    the cabinets having fire fighting equipment that are standpipes, fire extinguishers, hoses must be

    visible at all times and should not be locked. In addition portable fire extinguisher should be

     placed throughout the building at various locations so that any localized fire can be suppressed as

    soon as possible.

    Another aspect is fire alarm and detection system that needs to be catered as well. The alarm and

    detection system must be in accordance to NFPA 72 and for tall buildings it must be connected

    to the automatic sprinkler system along with automatic heat detection and automatic fire detector

    which is basically smoke detector. The location of smoke detector is important, it should be

    located in the main return air and in the main return air and exhaust air plenum of each air-

    conditioning system having a capacity

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    19/32

    Greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a

    serviceable area downstream of the last duct inlet and each connection to a vertical duct or riser

    serving two or more stories from a return air duct or plenum of an air-conditioning system. In

    Group R-1 and R-2 occupancies a listed smoke detector is allowed to be used in each return air

    riser carrying not more than 5,000 cfm (2.4m3/s) and serving not

    more than 10 air inlet openings.{IBC, 06}.

    Then the operation of automatic fire detection and sprinkler’s water flow device is connected to

    emergency voice and alarm communication system and the paging zones must be elevator

    groups, exit stairways, each floor and areas of refuge. In addition a two-way communication

    system must be established between the facility and fire department is of vital importance.

    After the detection of smoke the next step is the controlling of smoke for which an effective

    smoke control system is to be designed. This will assist the suppression of the fire. The smoke

    control systems must be designed on the basis of stack effect, projected temperature effect of

    fire, wind effect, HVAC systems efficiency, climate in the surrounding of the facility and lastly

    duration of operation. While on the other hand the smoke control system includes firstly the

    smoke barrier construction, where the openings and leakage areas must be monitored the

    maximum allowable leakage areas ratios are given by IBC 06 in coherence with International

    Fire Codes which is

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    20/32

      The opening and the leakage areas must be safeguarded and well-protected by automatic-

    closing devices and other electro-mechanical systems. Where as the fire doors can be used to

     protect the door openings.

     Next measure for the smoke control protection are the systems that work on pressure

    measurement, the codes say that the minimum pressure should be 0.00124 kPa in a fully

    sprinkled facility. Where as the maximum pressure difference across the smoke is to be

    calculated by the force applied by the smoke on the smoke barrier, the formula of which is as

    under provided by the international fire code,

    Lastly and most important is the fire command center and its working. This is the place where

    the decisions in crisis situations are to be made and is very detrimental in the level of damage

    that might be caused by the fires. For this we must comply to the National Fire Protection

    Association NPFA 72. According to which commands to have a emergency voice/alarm

    communication system unit, a communication link with the fire department, operational

    command over the elevators and auto locking doors. The command center must be in control of

    all air handling systems, sprinkler values and water flows. The center must be in full possession

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    21/32

    of the building plans, every aspect and details of the each floors, details and specifications of all

    fire protection systems, status and locations of fire fighting equipments on each floor. Controls of

     backup power supply and backup communication systems can be decisive nature for the

    command center.

    Problems of Fire protection systems

    With

    WTC Case Study

    There are many issues and problems that are not foreseen while designing the facilities and need

    to be focused on by the information from the case studies and analysis of the fire that have

    actually occurred. Although there are very few fires observed in the tall building there are several

    reasons which include the over protective designs and then secondly very few are taken up by

    forensic engineers. But there are some case studies that offer extensive research to fire systems,

    their failure and the performance of structures under fires. Extensive research has been done and

    case studies have been compiled on the incidents that have occurred. The most prominent and

    researched among these are NIST  National Institute of Standards and Technology and its

    committee on World Trade Center Investigation. The outcomes have been really helpful in

    understanding the problems and rectifying them for other tall buildings. There are several issues

    that are highlighted, the first and the foremost issue is that all standards and codes rely on the

    results of tests that are preformed in the labs. The problem here is that these tests can not

    simulate the same temperatures or conditions that are present in a real time fires. Neither do we

    have enough data or even knowledge about the response of different materials which acts as

    http://www.google.com.pk/url?sa=t&source=web&cd=1&ved=0CCQQFjAA&url=http%3A%2F%2Fwww.nist.gov%2F&rct=j&q=NISt%20&ei=eRuxTZuLK-vXiAL5r_SvBg&usg=AFQjCNHDr2hK4iSbBWNRBUpEAC29fOPNwA&cad=rjahttp://www.google.com.pk/url?sa=t&source=web&cd=1&ved=0CCQQFjAA&url=http%3A%2F%2Fwww.nist.gov%2F&rct=j&q=NISt%20&ei=eRuxTZuLK-vXiAL5r_SvBg&usg=AFQjCNHDr2hK4iSbBWNRBUpEAC29fOPNwA&cad=rja

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    22/32

    fuels under fire at different temperature. So the problem can be solved through establishment of

     better testing procedure and better lab equipments.

    On the other side the case studies made by the investigation team of Project 4 made under the

     NIST World Trade Center Investigation have also highlighted some major issues that were faced

    in case of fires in WTC 1, 2, 7. These issues related the minimum level of performance for active

    fire protection systems, then they emphasized on the quantity and reliability of information to

    first responder at fire and significance of command center in crisis situations. Then the study

    focused on the data and information given by Fire Alarm Systems for the declaration of crisis

    and response and other preventive measures which includes the evacuation and fire fighting.

    Lastly the study accentuated on the survival of fire alarm system and other recording systems

    So that later these data collecting systems can be recovered and the data analysis can help in a

    more accurate case study. Therefore probability of future fires can be reduced.

    Lets analyze what was the first major issue highlighted in the case study and its findings, It stated

    that all Fire Sprinkler Systems design method for WTC 1, 2, and 7 was based on the occupancy

    hazard fire control approach from NFPA 13. Light hazard was the occupancy classification for

    water spray density which had a density of 0.1 gpm/ft2. Where as the area is 1500 ft2. It was also

    found that almost all tall buildings have the same classification, which is danger and has proved

    to be insufficient in strong fires. Then there was another assumption that proved to be wrong was

    that the fire’s fuel was only ordinary office material so the system was designed accordingly.

    As a result the recommendation said that the NFPA 13 should now reconsider the minimum

    requirements and should also consider the threat profile, terrorism, prohibited activities and fuel

    loads in the building, compartmentation, population in the building while designing thee

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    23/32

    sprinkler systems and water spray density. The designer must consider these factors and should

    design accordingly if not considering all may be a part in to his design.

    Then another fault that was seen in the system was that the fire sprinkler system was automatic

    for water from tank but for continuous operation they solely relied on manually operated pumps

    as a result the whole system became manually operated and consequently making efficiency

    lesser. Then again the fire alarms systems in WTC 1 and 2 were automatic but the activation of

    notification devices was manual. Where as the smoke purge systems were manually activated.

    All this shows that the coherence in the automation of the systems is very vital for maximum

    efficiency. The case study also unveiled the danger of system’s complete failure due to damage

    at a single point. The report stated WTC 1, 2, and 7 fire sprinklers and standpipe systems were

    vulnerable to single point failures as shown in the APPENDIX 3. Almost the same problem was

    observed with the fire alarm system voice notification, fire warden telephones, and fire fighter

    telephones that they all halted due to one place disconnection, as shown in Appendix 4.

    The next issue that was observed was pertaining availability and reliability of information that

    was reaching the Fire command Center and how did it respond to the emergency. At the WTC 1

    there were numerous alarms that were registering fires in their zones but none of them was used

    to show the status of the water supply’s conditions. Then at WTC 1 the alarm systems showed

    only those area that were on fires and had no other information what so ever. Then there was

    system that could announce any information at a specific floor in the building. This show that

    how even the most well designed building small mistakes can lead to chaos in both management

    and life toll. Then another issue that was seen in the building as a whole and system as specific,

    this was that no information or data about events and happenings inside the building was

    available outside, eventually any one outside had any idea what was going on inside the build

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    24/32

    and no accurate actions were possible to safeguard the loss. These systems which can transport

    and communicate the information outside the building can be really helpful, so that the future

    events in the fire can be projected more accurately and fire fighting and damage control can be

    done effectively and strategically. Lastly the recommendation of the case study pointed out that

    there alarm system and other backup systems provide valuable information about all events and

    the response of the facility under fire. There were many hardware and systems installed for the

    data collection under a fire situation but almost every system was damaged in the fire and no

    information was available or recovered from the fire alarm system. Hence the Survivability of

    alarm systems and data collection devices and the communication/ transmission of information

    from within the building is very detrimental for fire fighting and forensic studies of the fires and

    hence a lot of work is to be done in this field.

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    25/32

    Conclusion

    The reiterative process of learning from the mistakes and then using them to understand more

    closely the principles that govern will carry on. The first priority for every designer must be the

    safety of the life and should be protected at any cost. There are very few regulatory bodies and

    standard that directs the designer to have a fire resistance construction. Many standards and

    codes throughout the world are yet to have clauses for fire protection and this aspect has been

     previously neglected but things have changed now, the trend is now heading towards

    improvement and they should because our structures are getting higher and higher every day, so

    shall the protection standards should. On the other hand there is immense work and research to

     be done to make our fire protection systems effective and fire testing procedures more accurate.

    Till we have the full confidence and grasp of the knowledge of fires and its interactions with the

    facilities we must have an over protective system, the cost might be more but not more than

    human life.

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    26/32

    References

    John R. Hall, Jr. (August 2005). HIGH-RISE BUILDING FIRES . Fire Analysis and ResearchDivision, US: National Fire Protection Association. 5-74.

    INTERNATIONAL CODE COUNCIL, INC. (2006). International Building Code 2006 . :

    INTERNATIONAL CODE COUNCIL, INC.. 104-657.

    British Standards Institution (2008). BS 5950-8 Part 8: Code of practice for fire resistant design.

    UK: British Standards Institution.

    British Standards Institution. (2011). Standards and Publications . Available:

    http://shop.bsigroup.com/en/Browse-by-Subject/Fire/. Last accessed 22-04-2011. 

    Project 4: Investigation Team (2003). Active Fire Protection Systems Issues. New York, US:

     NIST World Trade Center Investigation. 2-20.

    Beitel, J. J. (2005). Historical Survey of Multi-Story Building Collapses Due to Fire. Hughes

    Associates, Inc.

    British Standards Institution (2005). BS EuroCode EN 1993-1-2:2005 Part 1-2: General rules —

    Structural fire design. UK: British Standards Institution.

    Morgan Hurley, P.E., SFPE. (06-02-2009). Fire Protection Engineering. Available:

    http://www.wbdg.org/design/dd_fireprotecteng.php. Last accessed 19-04-2011. 

    British Standards Institution (2005). BS EN 1992-1-1 2004 - Eurocode 2 - Design of concrete

    and composite structures. UK: British Standards Institution

    http://www.wbdg.org/design/dd_fireprotecteng.php.%20Last%20accessed%2019-04-2011http://www.wbdg.org/design/dd_fireprotecteng.php.%20Last%20accessed%2019-04-2011

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    27/32

     

     NFPA 5000. (2009). Building Construction and Safety Code. U.S: National Fire Protection

    Association.

    Ramon Gilsanz, P.E., S.E.. (feb 2008). Reconsidering Fire Resistance Requirements for Tall

    Buildings. In: . Structural Practices - Practical knowledge beyond the textbook . .: American

    Institute of Steel Construction. 41-44.

    James Milke. (2002). Overview of Fire Protection in Buildings. In: Federal Emergency

    Management Agency WTC Performance Study . Appendix A.

     National Fire Protection Association (2009). NFPA 72: National Fire Alarm and Signaling Code.

    US: National Fire Protection Association 

     National Institute of Standards and Technology. (2001-2011). NIST and the World Trade Center. 

    Available: http://wtc.nist.gov/. Last accessed 21-04-2011.

    Sumit Khanna, Underwriters Laboratories. (2006). Fundamental of High Rise Building Fire Safety. 

    Available: http://www.ul.com/asiaonthemark/as-en/2009-Issue29/page1.htm. Last accessed 20-04-2011. 

    911Research. (2007, 12 07). WTC 1, 2 collapses. Retrieved 02 25, 2010, from 911Research:http://911research.wtc7.net/wtc/analysis/fires/index.html

    INTERNATIONAL CODE COUNCIL, INC. (2006). International Fire Code 2006 . :

    INTERNATIONAL FIRE CODE COUNCIL, INC..

    http://www.ul.com/asiaonthemark/as-en/2009-Issue29/page1.htm.%20Last%20accessed%2020-04-2011http://www.ul.com/asiaonthemark/as-en/2009-Issue29/page1.htm.%20Last%20accessed%2020-04-2011

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    28/32

     National Fire Protection Association (2009). NFPA 13: Standard for the Installation of Sprinkler

    Systems. US: National Fire Protection Association

    David Scott, Barbara Lane, Craig Gibbons,. (2001). Fire Induced Progressive Collapse. ArupPapers. . (1-17), NewYork,US.

     National Fire Protection Association (2009). NFPA 220: Standard on Types of Building

    Construction. US: National Fire Protection Association.

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    29/32

    Appendix 1

    British Standards Institution (2008). BS 5950-8 Part 8: Code of practice for fire resistant design. UK:

    British Standards Institution. ..

     

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    30/32

    Appendix 2

    Beitel, J. J. (2005). Historical Survey of Multi-Story Building Collapses Due to Fire. Hughes Associates, Inc 

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    31/32

    Appendix 3

    Project 4: Investigation Team (2003). Active Fire Protection Systems Issues. New York, US: NIST World

    Trade Center Investigation. 2-20. 

  • 8/17/2019 Design of Fire Protection Systems for Tall Buildings

    32/32

    Appendix 4

    Project 4: Investigation Team (2003). Active Fire Protection Systems Issues. New York, US: NIST World

    Trade Center Investigation. Pg 8.